Powerware, Powerware Hot Sync, and LanSafe are registered trademarks and X-Slot is a trademark of Eaton Power Quality Corporation. Greenlee
is a registered trademark of Greenlee Textron.
ECopyright 2006 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the
express written approval of Eaton Corporation.
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in
which case the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
IEC 62040-2
Some configurations are classified under IEC 62040-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these configurations, the following
applies:
WARNING This is a Class A -UPS Product. In a domestic environment, this product may cause radio interference, in which case, the user may be
required to take additional measures.
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition
S EU Directives:73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Eaton Power Quality Oy
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should
be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional information, such
as important operating and maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product
contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your
local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the
trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
ON - Indicates that the switch is in the ON position.
OFF - Indicates that the switch is in the OFF position.
Powerware Hot Sync CAN Bridge Card19.....................................................
5Service and Support27.................................................
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
i
TABLE OF CONTENTS
ii
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
Chapter 1Introduction
A Tie Cabinet can be installed as a wall-mounted bypass or to provide support for a
parallel system for redundancy or extra capacity.
A wall-mounted bypass switch is used to bypass the UPS during maintenance or
servicing, providing wrap-around bypass for UPS service without shutting down the
load.
A parallel (load sharing) system provides more capacity than a single UPS and can
provide backup, depending on the load and configuration. In addition, when one UPS
is taken out of service for maintenance or is not operating properly, a redundant UPS
continues to supply uninterrupted power to the critical load. A parallel Powerware
Hot Sync®Controller Area Network (CAN) Bridge Card provides connectivity for
system metering and operational mode control. The parallel system consists of two to
four UPSs, each with a parallel CAN Bridge Card and a parallel cabinet.
Figure 1 shows the Powerware 9355 UPS.
®
Figure 1. The Powerware 9355 UPS
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
1
INTRODUCTION
2
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
Chapter 2Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance of
the UPS and batteries. Please read all instructions before operating the equipment and save this manual for
future reference.
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZEDSERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
S This UPS contains its own energy source (batteries). The UPS output may carry live voltage even when
the UPS is not connected to an AC supply.
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity controlled,
indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C
(104°F). Do not operate near water or excessive humidity (95% maximum).
S To reduce the risk of fire, connect only to a circuit provided with 125 amperes maximum branch circuit
overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70.
S Output overcurrent protection and disconnect switch must be provided by others.
DANGER
WARNING
CAUTION
S Batteries can present a risk of electrical shock or burn from high short circuit current. Observe proper
precautions. Servicing should be performed by qualified service personnel knowledgeable of batteries
and required precautions. Keep unauthorized personnel away from batteries.
S Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
3
SAFETY WARNINGS
Consignes de Sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute procédure
d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulter entièrement ces
instructions avant de faire fonctionner l’équipement et conserver ce manuel afin de pouvoir vous y reporter
ultérieurement.
DANGER!
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation doit être
EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE RÉPARABLE PAR
L’UTILISATEUR ne se trouve dans l’onduleur.
AVERTISSEMENT!
S Cette onduleur possède sa propre source d’alimentation (batteries). Il est possible que la sortie de
l’onduleur soit sous tension même lorsque l’onduleur n’est pas connectée à une alimentation CA.
S Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur uniquement à
l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité ambiantes
sont contrôlées. La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser à proximité d’eau
ou dans une atmosphère excessivement humide (95 % maximum).
S Afin de réduire les risques d’incendie, n’effectuez le raccordement qu’avec un circuit muni d’une
protection de surintensité du circuit de dérivation maximum de 125 ampères conformément au Code
Électrique National (National Electrical Code) des États-Unis ANSI/NFPA 70.
S La protection de surintensité de sortie ainsi que le sectionneur doivent être fournis par des tiers.
ATTENTION!
S Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant d’un courant de
court-circuit haute intensité. Observez les précautions appropriées. L’entretien doit être réalisé par du
personnel qualifié connaissant bien les batteries et les précautions nécessaires. N’autorisez aucun
personnel non qualifié à manipuler les batteries.
S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans
votre localité.
S Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser.
4
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
Advertencias de Seguridad
SAFETY WARNINGS
INSTRUCCIONES DE SEGURIDAD IMPORTANTES
GUARDE ESTAS INSTRUCCIONES
Este manual contiene instrucciones importantes que debe seguir durante la instalación y el mantenimiento
del SIE y de las baterías. Por favor, lea todas las instrucciones antes de poner en funcionamiento el equipo y
guarde este manual para referencia en el futuro.
PELIGRO
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben ser efectuados
SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay NINGUNA PARTE QUE EL
USUARIO PUEDA REPARAR dentro del SIE.
ADVERTENCIA
S Este SIE contiene su propia fuente de energía (baterías). La salida del SIE puede transportar voltaje
activo aun cuando el SIE no esté conectado con una fuente de CA.
S Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar cubierto, con
temperatura y humedad controladas, libre de contaminantes conductores. La temperatura ambiente no
debe exceder los 40°C. No trabaje cerca del agua o con humedad excesiva (95% máximo).
S Para reducir el riesgo de incendio, realice la conexión únicamente hacia un circuito que cuente con un
máximo de 125 amperios de protección contra sobrecorriente de circuito derivado, de acuerdo con el
Código Eléctrico Nacional, ANSI/NFPA 70.
S La protección contra sobrecorriente de salida y el conmutador de desconexión debe suministrarse por
parte de terceros.
PRECAUCIÓN
S Las baterías pueden constituir un riesgo de descarga eléctrica o quemaduras por corriente alta de corto
circuito. Adopte las precauciones debidas. Personal calificado de servicio que conozca de baterías y esté
al tanto de las precauciones requeridas debe darle servicio al equipo. Mantenga al personal no
autorizado alejado de las baterías.
S Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los
requisitos pertinentes.
S Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
5
SAFETY WARNINGS
6
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
Chapter 3Tie Cabinet Installation
The Powerware 9355 has the following power connections:
S 3-phase (L1, L2, and L3), neutral, and ground connection for rectifier/bypass input
S 3-phase (L1, L2, and L3), neutral, and ground connection for load output
The nominal input/output voltages are:
S 120/208 or 127/220 Vac
Output overcurrent protection and disconnect switch must be provided by others.
Figure 9 and Figure 11 beginning on page 15 show the oneline diagrams.
Only qualified service personnel (such as a licensed electrician) should perform the UPS installation and
initial startup. Risk of electrical shock.
To hardwire the Tie Cabinet:
1.Verify that the electrical connections to the installation site have been properly
installed.
2.A wall-mounted, user-supplied, readily-accessible disconnection device must be
incorporated in the input wiring.
WARNING
Compare the circuit breaker ratings to the ones in Table 1 on page 11.
NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation
of the Powerware 9355 UPS contain wiring to support the maximum capacity of the UPS cabinet.
3.Switch off utility power to the distribution point where the Tie Cabinet and UPSs
will be connected. Be absolutely sure there is no power.
4.Determine your equipment’s grounding requirements according to your local
electrical code.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
7
TIE CABINET INSTALLATION
5.Remove the Tie Cabinet front cover (see Figure 2).
Figure 2. Tie Cabinet Front Cover
6.Remove the internal covers to gain access to the breakers (see Figure 3).
Figure 3. Internal Covers
8
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
TIE CABINET INSTALLATION
7.Punch holes for the conduit (AC input, UPS output, load connection, and
®
maintenance bypass contact wires) using a Greenlee
punch or similar device.
8.Verify that the Tie Cabinet bypass breaker is in the OFF position (see Figure 4).
Figure 4. Tie Cabinet Bypass Breaker
9.Mount the Tie Cabinet to the wall and install the conduit.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
9
TIE CABINET INSTALLATION
10. From each UPS, remove the UPS front door.
11. Verify that the UPS input circuit breaker is in the OFF position.
12. Verify that each UPS battery circuit breaker is in the OFF position (see Figure 5).
13. If you ordered the UPS with the optional output circuit breaker, verify that the
output circuit breaker is in the OFF position.
14. Remove the UPS wiring access cover and retain.
Input Circuit
Breaker
Output Circuit
Breaker (optional)
Wiring Access
Battery Circuit
Breaker
Cover
10
Figure 5. UPS Front View
15. Remove the UPS conduit landing box from the rear panel and retain.
16. Punch two holes in the conduit landing box for the input and output conduit using
a Greenlee punch o r similar device.
17. Route the wiring from the back of the UPS, through the wiring tray, to the front
of the UPS.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
TIE CABINET INSTALLATION
p
120lbin
p
(13.5
Nm)2.00Conduit(1)
p
120lbin
p
(13.5
Nm)
2.00Conduit(1
)
18. Hardwire the UPS input terminations.
See Table 1 for specifications and Figure 6 for a detailed view of the UPS
terminal block.
NOTE Input neutral must be wired for proper operation or the UPS will not start.
NOTE The Powerware 9355 UPS is shipped as a single-feed UPS and can be converted to a dual-feed UPS
in the field.
NOTE DO NOT o vertighten the screws; be sure to use the specified tightening torque values shown in
Table 1.
Table 1. Terminal Block Wiring
20 kVA
Input Voltage
208
220
480
(with transformer)45A
600 (with transformer)35A
208
220
480
(with transformer)
30 kVA
Input Voltage
208
220
480 (with transformer)60A
600 (with transformer)50A
208
220
480
(with transformer)
1
Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table 310-16. Code may require a larger
Wire
Function
Input
Output
Wire
Function
Input
Output
Input Circuit
Breaker Size
100A
100A
Input Circuit
Breaker Size
125A
125A
L1, L2, L3, N
Wire Size
1
Ground
Wire Size
1
Tightening
Torque
Conduit Size
(Number of Conduits)
1AWG6AWG
1AWG6AWG
8AWG10 AWG
8AWG10 AWG
(13.5 Nm)
2.00” Conduit (1)
1.00” Conduit (1)
1AWG6AWG
1AWG6AWG
120 lb in
2.00” Conduit (1)
1AWG6AWG
L1, L2, L3, N
Wire Size
1
Ground
Wire Size
1
Tightening
Torque
Conduit Size
(Number of Conduits)
1/0 AWG6AWG2.00” Conduit (1)
1/0 AWG6AWG
6AWG10 AWG
(13.5 Nm)
2.00” Conduit (1)
1.00” Conduit (1)
8AWG10 AWG1.00” Conduit (1)
1/0 AWG6AWG
1/0 AWG6AWG
120 lb in
2.00” Conduit (1)
1/0 AWG6AWG
2, 3
2, 3
AWG size than shown in this table because of temperature, number of conductors in the conduit, or long service runs. Follow local requirements.
2
Per NEC article 300-20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the
phase conductors.
3
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground conductor. If two neutral conductors or
an oversized neutral conductor are to be installed, check the size of the conduit needed to accommodate the extra wire or size and use that conduit size
in place of the conduit size listed. Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
11
TIE CABINET INSTALLATION
Maintenance
Bypass Auxiliary
Contacts (TB4)
Jumpers
(remove three
wires for
dual-feed)
TB4
Input Terminal
Block
L1,L2,L3,N,N
Ground
Remote DC
(battery)
DC +, DC –
Output Terminal
Block
L1,L2,L3,N,N
Figure 6. UPS Terminal Block
NOTE The two input neutral terminals are jumpered together; use either one of these terminals to make
the input neutral connection.
NOTE The two output neutral terminals are jumpered together; use either one of these terminals to make
the output neutral connection.
12
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
TIE CABINET INSTALLATION
19. Hardwire the output terminations from the UPS to the Tie Cabinet (see Figure 7).
20. Repeat Steps 11 through 19 for each UPS.
Neutral
Line 1
Line 2
Line 3
Ground
Figure 7. UPS Output to Tie Cabinet Wiring
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
13
TIE CABINET INSTALLATION
21. Hardwire the load to the Tie Cabinet (see Figure 8).
Maintenance Bypass
Wiring to UPS TB4
Neutral
Line 1
Ground
Line 3
Line 2
Figure 8. Load Connections
14
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
TIE CABINET INSTALLATION
22. Wire the maintenance bypass auxiliary contacts and terminate to the
maintenance bypass wires in the Tie Cabinet (see Figure 6 on page 12).
Connect the black and the red wire to TB4 on the UPS (see Figure 9). Cap the
blue wire.
NOTE The maintenance bypass contacts are normally-open. To ensure proper bypass operation, DO NOT
use the blue wire (it is normally-closed).
NOTE There are two sets of maintenance bypass wires; you can terminate to either set. If you are
installing four UPSs, it is recommended to terminate two UPSs to one set of wires and two UPSs to the other
setofwires.
Red Wires
(open when breaker is open)
350A Breaker
Auxiliary Contacts
350A
Black Wires
(common)
Blue Wires
(closed when breaker is open)
Bypass Input
110A (4X)
From UPS 1 Output
From UPS 2 Output
From UPS 3 Output
From UPS 4 Output
Figure 9. Parallel Wiring Diagram
23. Reinstall the UPS wiring access cover.
24. Reinstall the UPS conduit landing box in the reversed position.
LOAD
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
15
TIE CABINET INSTALLATION
25. Wire the AC input to the bypass breaker (see Figure 10).
Line 1 Line 2 Line 3
16
Figure 10. Bypass AC Input Wiring
26. Verify the phase rotation for each UPS and the bypass input.
27. Reinstall the internal cover removed in Step 6.
28. Reinstall the Tie Cabinet front covers removed in Step 5.
29. Continue to “Installing Options” on page 19.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
TIE CABINET INSTALLATION
Figure 11. Parallel UPS System with Tie Cabinet Diagram (Single-Feed, 208V or 220V Input : 208V or 220V Output)
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
17
TIE CABINET INSTALLATION
18
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
Chapter 4Installing Options
This section describes the Powerware Hot Sync CAN Bridge Card.
REPO (normally open)
Signal Input 2
Signal Input 1
For other options, such as additional X-Slot
t cards, Powerware LanSafe
®
Power
Management Software, remote emergency power-off (REPO), relay output contacts,
or programmable signal inputs, refer to the Powerware 9355 UPS (20/30 kVA)Installation and Operation Manual.
Figure 12 shows t he location of the communication options and control terminals on
the UPS.
REPO (normally closed)
X-Slot
Communication
Bay #1
Control
Terminals
Pull-Chain Output
Contacts (parallel only)
X-Slot
Communication
Bay #2
DB-9 Communication Port
Figure 12. Communication Options and Control Terminals
Powerware Hot Sync CAN Bridge Card
The Powerware Hot Sync CAN Bridge Card, shown in Figure 13, can be installed to
provide connectivity for operational mode control and metering of a parallel system at
any UPS in the system.
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
Relay Output Contacts
Plug-in Terminal Block
Figure 13. Powerware Hot Sync CAN Bridge Card
19
INSTALLING OPTIONS
To install the Powerware Hot Sync CAN Bridge Card:
1.Remove the UPS front door.
2.Remove the communication wiring access plate from the UPS rear panel and
punch a hole in it using a Greenlee punch or similar device (see Figure 14).
3.Install conduit for the communication wiring.
Communication
Wiring Access Plate
20
Figure 14. Communication Wiring Access
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
INSTALLING OPTIONS
4.Set the jumper pins on the Powerware Hot Sync CAN Bridge Card according to
the parallel configuration (see Figure 15):
S If only two UPSs are paralleled, then set both cards to Pins 1 and 2.
S For three or four paralleled UPSs, set the cards of the first and last UPSs to
Pins 1 and 2; set the cards for the middle UPSs to Pins 2 and 3.
Jumper J7 - Pins 1 and 2
Jumper J7 - Pins 2 and 3
Figure 15. Setting the CAN Bridge Card Jumper J7 (Side View)
5.Install the CAN Bridge Card into X-Slot 2 (see Figure 12 and Figure 17).
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
21
INSTALLING OPTIONS
8.Route the wiring through the conduit from the communication wiring access
plate to the opening between the two X-Slot communication bays on each UPS
(see Figure 16).
Figure 16. Routing the Cables
9.Install the CAN Bridge Card wiring between each UPS (see Figure 18 on
page 25).
Use three wires of the four-wire twisted-pair wire. (Reserve two wires for
pull-chain wiring in S tep 11.) Be sure to check correct polarity for Pins 8 and 9:
S Connect SHIELD Pin 10 on all cards together.
S Connect CAN H Pin 9 and CAN L Pin 8 (twisted pair) on all cards together.
22
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
INSTALLING OPTIONS
10. Route the pull-chain wiring through the middle of the fan section and secure in
the cable clips f or each UPS (see Figure 17).
Figure 17. Installing Communication Cables
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
23
INSTALLING OPTIONS
11. Wire the pull-chain wiring to Signal Input 2 on each UPS and daisy chain the
wiring to each UPS as shown in Figure 18. Be sure to check correct polarity:
S Connect Pull-Chain Output Contact Pin 1 to Signal Input 2 Pin 1 on each UPS.
S Connect Pull-Chain Output Contact Pin 2 to Signal Input 2 Pin 2 on each UPS.
CAUTION
If polarity or wiring is not correct, the parallel system does not operate normally. For example, when shutting
down one UPS, the remaining UPS transfers the load to bypass instead of supporting the load. Verify all CAN
Bridge Card wiring is correct for proper operation.
NOTE Signal Input 2 can still be used for building alarms; it is automatically rerouted to the CAN Bridge
Card.
12. Reinstall the communication wiring access plate on each UPS.
13. Replace the UPS front door on each UPS.
24
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
INSTALLING OPTIONS
To Pull-Chain Contacts
ALM RTN
ALARM
COM
NO
NC
1
2
J3
J5
SHIELD
CAN H
CAN L
TX
TX
10
8
9
76543
ALARM1
ALARM2
X45X44
RS232 RELAYOUTPUT
X43
X57
PULLCHAIN OUTP
PARALLELONLY
X27
BPO
X--NP
X52--NC
ALARM1
ALARM2
BPO
X--NP
X45X44
X52--NC
UPS #3
RS232 RELAYOUTPUT
X43
X57
UPS #2
PULLCHAIN OUTP
PARALLELONLY
X27
ALARM1
ALARM2BPO
X45X44
X--NP
X52--NC
RELAYOUTPUT
RS232
X43
UPS #1
X57
PULLCHAIN OUTP
PARALLELONLY
X27
From UPS #1
To UPS #3
Signal Input 2Pull-Chain Output Contacts
Figure 18. CAN Bridge Card and Pull-Chain Wiring
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
25
INSTALLING OPTIONS
26
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
Chapter 5Service and Support
If you have any questions or problems with the UPS, call your Local Distributor or the
Help Desk at one of the following telephone numbers and ask for a UPS technical
representative.
United States:
Canada:1-800-461-9166 ext 260
All other countries:Call your local service representative
Please have the following information ready when you call for service:
1-800-843-9433 or 1-919-870-3028
S Model number
S Serial number
S Firmware version number
S Date of failure or problem
S Symptoms of failure or problem
S Customer return address and contact information
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
27
SERVICE AND SUPPORT
28
EATON Powerware®9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com
*164201630A*
164201630 A