This manual contains important instructions for your Uninterruptible Power
Supply (UPS) system. You should follow these instructions during the
installation and maintenance of the UPS, options, accessories, and batteries.
Cette notice contient des instructions importantes
concernant la sécurité.
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at
their own expense.
WARNING:
This is a product for restricted sales distribution to informed partners. Installation
restrictions or additional measures may be needed to prevent disturbances.
Powerware 9315 Parallel Redundant System I & O
164202013 Rev. D 041599
v
This Page Intentionally Left Blank.
vi
Powerware 9315 Parallel Redundant System I & O
164202013, Rev. D 041599
Introduction
The parallel redundant system allows two UPS modules to operate in parallel and
as backup for each other. When one UPS module is taken out of service for
maintenance or is not operating properly, the redundant UPS module continues to
supply uninterrupted power to the critical load. The parallel redundant system
refers to the parallel cabinet in conjunction with the UPS modules. The parallel
redundant system consists of one parallel cabinet, two identical UPS cabinets, and
up to four battery cabinets per UPS. Each UPS module may have its own battery
cabinet(s), or may share the same battery cabinet(s) with the other UPS module.
NOTE: The installation procedures of this manual only refer to the parallel cabinet
and its connection to the UPS cabinets for parallel redundant operation. The
operation section of this manual refers to the operation for the parallel
cabinet and the UPS system when in parallel. For full installation and
operation of the UPS system and battery installation, refer to the
PowerwareÒ 9315 Installation, PowerwareÒ 9315 Operation,andthe
PowerwareÒ Series 685 and 1085 Auxiliary Battery Cabinets
Installation manuals provided with the UPS system and battery cabinet
accessory.
The parallel cabinet is a free-standing cabinet. Figure 1 shows a typical parallel
cabinet.
Figure 1. Typical Parallel Cabinet
Powerware 9315 Parallel Redundant System I & O
164202013 Rev. D 041599
1
Using This Manual
This manual contains installation and operation procedures for the PowerwareÒ
9315 Parallel Redundant system. In this manual, parallel redundant system refers
to the parallel cabinet, its internal components, and those components of the UPS
modules that assist in parallel redundant operation. The text uses these
conventions:
·Bold type highlights important concepts in discussions, key terms in
procedures, and menu options.
·Italic type highlights notes, references to other system manuals, references to
other sections of this manual, and new terms where they are defined.
·Rectangular boxes containing bold type are warnings or cautions that pertain to
the parallel redundant system or its electrical connections. This important
information indicates possible dangers pertaining to personnel safety,
equipment damage, critical load protection, or operational concerns.
Before installation of the parallel redundant system, read through each installation
procedure provided in Section 1 Installation of this manual. Below is a description
of each chapter in each section as they appear:
Section 1
·Chapter 1 tells you how to prepare the site for the installation of the parallel
cabinet. It discusses equipment environmental requirements, inspecting and
unpacking the parallel cabinet, and pallet removal.
·Chapter 2 describes how to install the parallel cabinet.
·Chapter 3 describes parallel redundant configurations of UPS modules utilizing
separate battery cabinets or sharing a common battery cabinet.
Section 2
·Chapter 4 describes the parallel redundant system and its operation.
·Chapter 5 provides information on understanding parallel operation.
·Chapter 6 contains operation instructions for the parallel redundant system.
·Appendix A contains important information on wiring requirements and
recommendations, and important diagrams of the cabinet’s mechanical details
and electrical access.
Read through each procedure before you begin. Perform only those procedures
that apply to the UPS system you are installing.
2
Powerware 9315 Parallel Redundant System I & O
164202013, Rev. D 041599
For More Information
This manual describes the installation and operation of the parallel redundant
system. For more information on the installation and operation of the UPS system
and its accessories, refer to the following:
164200252Powerware
9315 30---160 kVA UPS Operation
164201036Powerware
164201119Powerware
Each manual describes the UPS cabinet Control Panel and
Monitor Panel, and explains the functions of the UPS; discusses
the standard features o f the UPS and optional accessories;
provides procedures for starting and stopping the UPS, and
information about maintenance and responding to system events.
A l s o d e s c r i b ed a r e t h e R S --- 48 5 a n d R S --- 2 3 2 s e r ia l
communications capabilities of the UPS system; discusses the
two communications ports on the Customer Interface Panel
inside the UPS and how to connect optional remote accessories
to your UPS system; provides information about enabling,
disabling, and customizing building alarms.
164200253Powerware
164200292Powerware
164201037Powerware
164201118Powerware
Each manual contains the following information: how to prepare
the site and plan for installation, detailed step-by-step
procedures for installing each component of your system, how to
join cabinets in a line-up-and-match system, detailed illustrations
of cabinets and optional accessories, including dimensions and
connection points.
9315 200---300 kVA UPS Operation
9315 400/500 (300--- 500 kVA) UPS Operation
9315 30---80 kVA UPS Installation
9315 100---160 kVA UPS Installation
9315 200---300 kVA UPS Installation
9315 400/500 (300---500 kVA) UPS Installation
Contact the local Powerware Field Service office for information on how to obtain
copies of these manuals.
Getting Help
If you have a question about any of the information in this manual, or if you have a
question this manual does not answer, please call Powerware Corporation Field
Service:
United States1-800-843-9433
Canada1-800-461-9166
Outside the U.S.Call your local representative
Powerware 9315 Parallel Redundant System I & O
164202013 Rev. D 041599
3
This Page Intentionally Left Blank.
4
Powerware 9315 Parallel Redundant System I & O
164202013, Rev. D 041599
Section I
Installation
Powerware 9315 Parallel Redundant System I & O
164202013 Rev. D 041599
5
This Page Intentionally Left Blank.
6
Powerware 9315 Parallel Redundant System I & O
164202013, Rev. D 041599
Getting Started
This section describes how to install the parallel cabinet. It contains only
instructions for installing the parallel cabinet as a remote cabinet,
configuration needed for parallel redundant operation, and basic site preparation
procedures. Figure 2 shows the front and side view of the parallel cabinet.
Figure 2. Front and Side View of Parallel Cabinet
Powerware 9315 Parallel Redundant System I & O
164202013 Rev. D 041599
7
The parallel cabinet is shipped on a separate pallet. Use a forklift or pallet jack to
move the packaged cabinet to the installation site, or as close as possible to the
site, before unloading from the pallet.
The basic sequence of the installation steps is:
1. Prepare the site for the cabinet installation.
2. Inspect, unpack, and unload the cabinet.
3. Create an installation plan for wiring the parallel cabinet to the corresponding
UPS modules.
4. Prepare for wiring.
5. Complete the installation checklist from the PowerwareR 9315 Installation manual.
6. Have authorized service personnel perform preliminary checks and startup.
NOTE: Startup and operational checks should be performed only by authorized
service personnel. This service is usually offered as part of the sales
contract for your UPS system.
Preparing the Site
For the parallel redundant system to operate at peak efficiency, the installation site
should meet the environmental parameters outlined in the PowerwareÒ 9315Operation manual provided with the UPS system. The operating environment must
meet the size and weight requirements supplied in the PowerwareÒ 9315Installation manual provided with the UPS system. If the parallel redundant system
is to be operated at an altitude higher than 1500 meters (5000 feet), contact the
local sales or service office for important information about high altitude operation.
The basic environmental requirements for operation of the parallel redundant
system are:
The parallel cabinet uses convection cooling to regulate internal component
temperature. Air inlets are in the front of the cabinet, and outlets are in the top.
Clearance in front of and above each cabinet for proper air circulation is essential.
8
Powerware 9315 Parallel Redundant System I & O
164202013, Rev. D 041599
Environment Considerations
Thelifeoftheparallelredundantsystemwillbeadverselyaffectediftheinstallation
does not meet the following guidelines:
1. The parallel cabinet must be installed on a sealed concrete pad on a sealed
concrete floor.
2. The parallel cabinet must be installed in a dust-free environment.
3. The parallel cabinet must be installed in a humidity-controlled environment.
Preparing for Wiring the Parallel Redundant System
See Tables A---1 through A---4 in Appendix A of this manual for wiring requirements.
The power wiring for this equipment is rated at 75_C. Ifwireisruninanambient
temperature greater than 30_C, higher temperature and/or larger size wire may be
necessary. Wiring for the paralle cabinet should be installed through the 28.6 mm
(1.1 in.) knockout in the bottom of the UPS cabinet. The top entry connection
requires installation of 1/2-in. flexible conduit within the UPS. Bottom entry
connection requires no additional routing of conduit within the UPS. For UPS
external wiring requirements, including minimum AWG size of external wiring, see
the PowerwareÒ 9315 Installation manual provided with the UPS system.
NOTE: Material and labor for external wiring are to be provided by designated
personnel.
Powerware 9315 Parallel Redundant System I & O
164202013 Rev. D 041599
9
Inspecting and Unpacking the Parallel Cabinet
The first task in preparing for installation of the parallel cabinet is inspecting and
unpacking the cabinet. The cabinet arrives covered with protective packaging
material as shown in Figure 3.
OUTER
PACKA GING
10
FOAM CUSHION
Figure 3. Cabinet as Shipped, with Outer Packaging and Pallet
1. Carefully inspect the outer packaging for evidence of damage during transit.
CAUTION:
Do not install a damaged cabinet. Report any damage to the carrier and
contact the local sales or service office immediately.
2. Use a forklift or other material handling equipment to move the cabinet to a
convenient unpacking area. Insert the forklift jacks between the foam cushions
on the bottom of the unit.
CAUTION:
Do not tilt cabinet more than 10 degrees from vertical.
Powerware 9315 Parallel Redundant System I & O
164202013, Rev. D 041599
3. Set the pallet on a firm, level surface, allowing a minimum clearance of
4.6m (15 ft) on each side for removing the cabinet from the pallet.
4. Cut the steel bands around the cabinet.
5. Remove the protective cardboard covering from the cabinet, cutting where
indicated, using a knife blade no longer than 25 mm (1 in.).
NOTE: Do not discard the packaging material yet. Instructions for unloading the
cabinet from the pallet are printed on the cardboard, and you will need to
refer to them.
6. Remove the plastic bag and foam packing material, and discard or recycle
them in a responsible manner.
Unloading the Parallel Cabinet From the Pallet
The parallel cabinet consists of four supports secured to foam cushions. The foam
cushions act as shock absorbers for the cabinet during shipment.
WARNING:
Cabinet is extremely heavy. If unloading instructions are not closely
followed, the cabinet may tip and cause serious injury.
Turning the jacking bolts unevenly may cause the cabinet to become
unbalanced. To prevent tipping, raise and lower the jacking bolts
evenly. The cabinet should only be raised approximately 3 mm (
above the floor (just enough to remove foam cushions).
1/8 in.)
1. Remove the doors. Remove the retaining screw located inside each door at
the bottom hinge pivot point, then lift the door off. Save the retaining screws
for reinstallation of the doors.
2. Locate the field kit (packed inside of the cabinet or communication panel).
Locate the four ½-in. jacking bolts and install them in the threaded holes in the
front and rear supports. Place a floor protector underneath each jacking bolt,
and screw the bolts down against them. The floor protectors will save the floor
from being marred by the jacking bolts.
3. Loosen, but do not remove the hardware holding the foam cushions to the
front and rear supports (labeled “1” in Figure 4).
4. Turn each jacking bolt consecutively, two full turns, until the foam cushions
clear the floor by approximately 3 mm (
1/8 in.).
5. After the foam cushions clear the floor, remove the hardware loosened in
step 3. Pull the foam cushions out from under the cabinet, and discard or
recycle them in a responsible manner.
Powerware 9315 Parallel Redundant System I & O
164202013 Rev. D 041599
11
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.