PolyScience LS Operating Manual

Operator’s Manual
LS-Series Compact Chiller
110-445 09.01.11
Table of Contents
Table of Contents
Introduction
Introduction ................................
IntroductionIntroduction General Information
General Information ................................
General InformationGeneral Information
General Safety Information............................................................................................................................................................... 2
Safety Recommendations................................................................................................................................................................. 3
Unpacking Your Chiller...................................................................................................................................................................... 3
Regulatory and Compliance Testing................................................................................................................................................ 3
Contents.............................................................................................................................................................................................. 3
Contr
Controls and Components
ols and Components ................................
ContrContr
ols and Componentsols and Components
Installation and Startup
Installation and Startup ................................
Installation and StartupInstallation and Startup
Site Requirements.............................................................................................................................................................................. 5
Ambient Temperature and Relative Humidity............................................................................................................................ 5
Location........................................................................................................................................................................................... 5
Clearance ........................................................................................................................................................................................ 5
Electrical Power.................................................................................................................................................................................. 5
Optional RS232 Serial Output .......................................................................................................................................................... 5
Plumbing.............................................................................................................................................................................................. 5
Process Piping................................................................................................................................................................................ 5
Fluid Filter....................................................................................................................................................................................... 6
Reservoir Drain............................................................................................................................................................................... 6
Closed System or Cooling Coil Setup............................................................................................................................................... 6
Startup................................................................................................................................................................................................. 7
Process Coolant ............................................................................................................................................................................. 7
Electrical Power ............................................................................................................................................................................. 8
Starting Process Fluid Flow..........................................................................................................................................................8
Normal Operation
Normal Operation ................................
Normal OperationNormal Operation
Selecting the Temperature Unit (°C or °F) ..................................................................................................................................... 8
Displaying and Adjusting the Set Point........................................................................................................................................... 9
Setting Operational Parameters ...................................................................................................................................................... 9
High Temperature Limit (H-##) ................................................................................................................................................... 9
Low Temperature Limit (L-##)....................................................................................................................................................10
Auto-Refrigeration Temperature (A ##)....................................................................................................................................10
Specific Heat (P.##) .....................................................................................................................................................................10
Communications Baud Rate (PC##)...........................................................................................................................................10
Temperature Calibration (C #.#).................................................................................................................................................. 11
Password (Pd00)............................................................................................................................................................................ 11
Enabling/Disabling the Local Lockout (LLO) .................................................................................................................................. 11
Display, Error and Fault Messages
Display, Error and Fault Messages ................................
Display, Error and Fault MessagesDisplay, Error and Fault Messages Routine Maintenance and Troubleshooting
Routine Maintenance and Troubleshooting ................................
Routine Maintenance and TroubleshootingRoutine Maintenance and Troubleshooting
Magnetic Drive Centrifugal Pump ................................................................................................................................................... 13
Condenser, Air Vents, and Reusable Filter....................................................................................................................................13
Fluid Level..........................................................................................................................................................................................13
Temperature Calibration.................................................................................................................................................................. 13
Cleaning Exterior Surfaces
Cleaning Exterior Surfaces............................................................................................................................................................14
Cleaning Exterior SurfacesCleaning Exterior Surfaces
Troubleshooting.................................................................................................................................................................................14
Technical Information
Technical Information ................................
Technical InformationTechnical Information
Model LS51/LS53 60Hz Compact Chiller Specifications..............................................................................................................15
Model LS52 50Hz Compact Chiller Specifications .......................................................................................................................16
General Information & Specifications............................................................................................................................................. 17
RS232 Serial Communications (Optional)......................................................................................................................................18
Equipment Disposal (WEEE Directive)
Equipment Disposal (WEEE Directive) ................................
Equipment Disposal (WEEE Directive)Equipment Disposal (WEEE Directive) Service and Technical Support
Service and Technical Support ................................
Service and Technical SupportService and Technical Support Replacement Parts and Accessories
Replacement Parts and Accessories ................................
Replacement Parts and AccessoriesReplacement Parts and Accessories PolyScience Chiller Fluids
PolyScience Chiller Fluids ................................
PolyScience Chiller FluidsPolyScience Chiller Fluids Warranty
Warranty ................................
WarrantyWarranty
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
................................................................
.........................................................
................................................................
............................................
................................................................
................................................................
................................................................
................................................
................................................................
...................................................
................................................................
..............................................
................................................................
.........................................................
................................................................
...............................................
................................................................
................................................................
................................................................
.............................................................
................................................................
..................................
................................................................
......................................
................................................................
.....................................
................................................................
........................................
................................................................
.................................... 21
................................................................
......................... 2222
..................................................
............ 2222
........................
...... 5555
............
................ 8888
................................
................... 12
......................................
..... 13
..........
........ 15
................
.............. 19
............................
......................... 19
..................................................
............... 20
..............................
............................. 21
..........................................................
.. 4444
....
12
1212 13
1313
15
1515
19
1919 19
1919
20
2020
21
2121 21
2121
110-445 1
2
Introduction
Introduction
IntroductionIntroduction
The LS-Series Compact Chiller provides cooling power for demanding applications and serves as an economical alternative to tap water cooling systems. It features a microprocessor-based controller, digital temperature display (°C or °F), and simple operation and maintenance.
To optimize cooling efficiency and performance, this sophisticated Chiller also features a modulated refrigeration system. As a result, temperature stability is greatly enhanced and compressor life extended.
The Chiller is equipped with either a magnetic drive centrifugal pump or a turbine pump. Wetted parts within the recirculation system are brass, copper, stainless steel, EPDM rubber, Alcryn, nylon, PVC, and polyethylene.
General Information
General Information
General InformationGeneral Information
General S
General Safety Information
General SGeneral S
When installed, operated, and maintained according to the directions in this manual and common safety procedures, your Chiller should provide safe and reliable heat removal. Please ensure that all individuals involved in the installation, operation, or maintenance of this unit read this manual thoroughly prior to working with the unit.
afety Information
afety Informationafety Information
This symbol alerts you to wide range of potential dangers.
This symbol advises you of danger from electricity or electric shock.
This symbol marks information that is particularly important.
This symbol indicates alternating current.
These symbols on the Power Switch / Circuit Breaker indicate that they place the main power supply ON /
/
OFF.
This symbol on the Power Switch indicates that it places the unit in a standby mode. It DOES NOT fully disconnect the unit from the power supply.
This symbol indicates a protective conductor terminal.
Read all instructions pertaining to safety, set
Read all instructions pertaining to safety, set----up, and operation.
Read all instructions pertaining to safety, setRead all instructions pertaining to safety, set
Proper operation and maintenance is the
Proper operation and maintenance is the user’s responsibility.
Proper operation and maintenance is the Proper operation and maintenance is the
up, and operation.
up, and operation. up, and operation.
user’s responsibility.
user’s responsibility.user’s responsibility.
110-445
3
Safety Recommendations
Safety Recommendations
Safety RecommendationsSafety Recommendations
To prevent injury to personnel and/or damage to property, always follow your workplace’s safety procedures when operating this equipment. You should also comply with the following safety recommendations:
Always connect the power cord on this unit to a grounded (3-prong) power outlet. Make certain that the
outlet is the same voltage and frequency as your unit.
Never operate the unit with a damaged power cord.
Always turn the unit OFF and disconnect Mains power before performing any maintenance or service.
Unpacking Your Chiller
Unpacking Your Chiller
Unpacking Your ChillerUnpacking Your Chiller
Your Chiller is shipped in a special carton. Retain the carton and all packing materials until the unit is completely assembled and working properly. Set up and run the unit immediately to confirm proper operation. Beyond one week, your unit may be warranty repaired, but not replaced. If the unit is damaged or does not operate properly, contact the transportation company, file a damage claim and contact the company where your unit was purchased immediately.
CAUTION:
CAUTION: Keep unit upright when moving. Be sure to follow your company’s procedures and practices
CAUTION:CAUTION: regarding the safe lifting and relocation of heavy objects.
Regulatory
Regulatory and Compliance Testing
RegulatoryRegulatory
and Compliance Testing
and Compliance Testing and Compliance Testing
CSA UL (60Hz units)
CSA UL (60Hz units)
CSA UL (60Hz units)CSA UL (60Hz units)
CAN/CSA C22.2 No. 61010-1-04 — Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use, Part I: General Requirements.
CAN/CSA C22.2 No. 61010-010-04 — Safety Requirements for Electrical Equipment for Measurement, Control and Laboratory Use - Part 2-010: Particular Requirements for Laboratory Equipment for the Heating of Materials.
UL Std No. 61010-1 — Electrical Equipment for Laboratory Use, Part I: General Requirements.
UL Std No. 61010A-2-010 — Electrical Equipment for Laboratory Use, Part 2: Particular Requirements for Laboratory Equipment for the Heating of Materials.
CE (50Hz units)
CE (50Hz units)
CE (50Hz units)CE (50Hz units)
EC Low Voltage Directive 2006/95/EC
EC Electromagnetic Compatibility Directive 2004/108/EC IEC 61010-1-2001 IEC 61326:2005 / EN 61326 : 2006
Contents
Contents
Contents Contents
The following items have been included with your Chiller:
Operator’s Manual
IEC Power Cord
Two sets of Inlet/Outlet Adapters: 1/2 inch NPT to 1/2 inch hose barb;
1/2 inch NPT to 5/8 inch hose barb
110-445
4
Controls and Components
Fluid Inlet
Fluid Outlet
IEC Power
RS-232
Reservoir Cap
Circuit Breaker /
Up & Down Arrow Buttons
Drain
Temperature
Temperature
Heating &
Set Button
On/Off Button
Fluid Level
Air Filter
Identification
Controls and Components
Controls and ComponentsControls and Components
Power Switch
Units LEDs
Cooling LEDs
Display
Compartment
Connection
Indicator
Connection (optional; not shown)
Label
NOTE:
NOTE: When controlling at the set point temperature, it is not uncommon for both the heating and cooling
NOTE:NOTE: LEDs to be lit simultaneously.
110-445
5
Installation and Startup
Installation and Startup
Installation and StartupInstallation and Startup
WARNING:
WARNING: Be sure all power is off before proceeding.
WARNING: WARNING:
Site Requirements
Site Requirements
Site RequirementsSite Requirements
Ambient Temperature and Relative Humidity
Ambient Temperature and Relative Humidity
Ambient Temperature and Relative HumidityAmbient Temperature and Relative Humidity
The Chiller is designed for indoor installation in ambient temperatures between 5° and 35°C (41° and 95°F); relative humidity should not exceed 80% (non-condensing).
Location
Location
LocationLocation
The Chiller should be installed on a strong, level surface. It should be located as close to possible to the process requiring cooling. It should not be installed closer than 1.4 meters (4 feet) to a heat-generating source, such as heating pipes, boilers, etc. If possible, the Chiller should be located near a suitable drain to prevent flooding in the event of leaks. Do not place it where corrosive fumes, excessive moisture, excessive dust, or high room temperatures are present.
NOTE:
NOTE: The Chiller may be located at a level below that of the equipment being cooled. As long as
NOTE:NOTE:
the process remains closed, overflow will not occur when adding cooling fluid to the Chiller reservoir.
Clearance
Clearance
ClearanceClearance
Adequate clearance should be allowed on the front, sides, top, and rear of the Chiller for access to connections and components. The front and side vents of the Chiller must be a minimum of 21 cm (8 inches) away from walls or vertical surfaces so air flow is not restricted.
Electrica
Electrical Power
ElectricaElectrica
An IEC power cord is provided with the Chiller. It should be attached to the receptacle on the rear of the enclosure. Make sure that the power outlet used for the Chiller is properly grounded and matches the voltage and frequency indicated on the identification label on the back of the Chiller.
To help prevent voltage drops, position the Chiller as close as possible to the power distribution panel. Avoid voltage drops by using a properly grounded power outlet wired with 14 gauge or larger diameter wire.
The use of an extension cord is not recommended. However, if one is necessary, it must be properly grounded and capable of handling the total wattage of the unit. The extension cord must not cause more than a 10% drop in voltage to the Chiller.
l Power
l Power l Power
WA
WARNING:
RNING: DO NOT plug the Chiller into the electrical outlet until the unit is ready for Startup....
WAWA
RNING: RNING:
Optional RS232 Serial Output
Optional RS232 Serial Output
Optional RS232 Serial OutputOptional RS232 Serial Output
This option allows you to remotely control the Chiller and/or output temperature readings to an external recorder or other auxiliary device. The maximum communications distance for Chillers equipped with the RS232 option is 15 meters (50 feet). A 9-pin D-connector is provided on the rear of the instrument enclosure for this connection. See the
Plumbing
Plumbing
Plumbing Plumbing
Process Piping
Process Piping
Process PipingProcess Piping
Technical Information
section for the RS232 serial communication protocol.
The Chiller has two internally threaded (0.5 inch ID NPT) fittings on the rear of the instrument housing for the process fluid connections. Two sets of 90° barbed hose adapters (0.5 inch and 5/8 inch) are supplied with the unit for connecting these fittings to the process piping.
To maintain a safe workplace and avoid leaks, special care should be taken when choosing hoses and connectors for the Chiller. It is the user’s responsibility to ensure that the tubing and fittings connected to the
110-445
6
Chiller are compatible with the fluid, temperature, and pressure being used.
Pressure Ratings — Hoses should be able to withstand the largest pressure that they will encounter.
Flexible Tubing — Avoid tubing that will expand and take up fluid volume when operating at the desired
pressure.
Hose Diameter — Process piping/hosing with a diameter smaller than 0.5 inch ID can be used if desired.
However, keep in mind that using smaller diameter hosing increases pressure and reduces flow in the circulating system and may result in a flow alarm. The minimum recommended tubing size is 3/8 inch ID.
Couplings and Clamps — The use of screw-tightened hose clamps is necessary on all joints to insure
good, tight connections. Quick connectors are not recommended as they have the potential for restricting flow rate.
Fluid Filter
Fluid Filter
Fluid FilterFluid Filter
If particulate matter may be present in the fluid, the installation of a 50 micron filter on the chiller inlet is recommended.
50 micron fluid filter: Part number 510-519
Reservoir Drain
Reservoir Drain
Reservoir DrainReservoir Drain
A 0.5 inch NPT connection is provided for the reservoir’s gravity drain. It should be piped to a drain or receptacle positioned below the bottom of the drain. If a receptacle is used, be sure it is of sufficient volume to hold all the water in the reservoir, process, and process lines.
Closed System or Cooling Coil Setup
Closed System or Cooling Coil Setup
Closed System or Cooling Coil SetupClosed System or Cooling Coil Setup
Connect the Chiller’s inlet and outlet to the external apparatus with hoses or pipes. The direction of the flow through the system can be controlled by the way the connections are made. Fluid is drawn into the Chiller through the “Inlet” connection; fluid is pumped out of the Chiller through the “Outlet” connection.
NOTE:
NOTE: If the Chiller is connected to an external apparatus with a built-in shutoff, an external bypass loop
NOTE:NOTE: assembly may be needed. This bypass assembly continues flow circulation to and from the pump even though the main flow to the external apparatus has been blocked.
External bypass loop assembly: Part number 510-147
110-445
7
Startup
Startup
StartupStartup
Process Coolant
Process Coolant
Process CoolantProcess Coolant
Suitable Fluids
WARNING:
WARNING: Only use fluids that will satisfy safety, health, and equipment compatibility requirements.
WARNING: WARNING: Caustic, corrosive, or flammable fluids must never be used.
The Chiller is designed to accommodate a variety of coolant fluids (water, glycol mixtures, etc). For most applications above 20°C (68°F), distilled water is satisfactory. For operation at or below 20°C (68°F), the Chiller must be protected with an antifreeze solution. Ethylene glycol (laboratory grade) and distilled water in a 50/50 mixture is satisfactory from +20° to -15°C (68° to 5°F). Select a fluid that is compatible with the Chiller’s wetted parts (brass, stainless steel, polyethylene, EPDM rubber, and nylon).
WARNING:
WARNING: Do not use caustic, corrosive, or flammable fluids.
WARNING: WARNING:
WARNING:
WARNING: Operation below 20°C (68°F) requires antifreeze in the circulation fluid.
WARNING: WARNING:
To prevent algae growth in the system, shield tubing from light. Insulation around the tubing will suffice. Use an algaecide in the cooling water to minimize algae growth.
WARNING:
WARNING: Do NOT use chlorine bleach as an algaecide.
WARNING:WARNING:
WAR
WARNING:
NING: Do not use the following fluids
WARWAR
NING: NING:
Do not use the following fluids
Do not use the following fluidsDo not use the following fluids
Automotive antifreeze with additives**
Hard tap water**
Deionized water with a specific resistance > 1 meg ohm
Any flammable fluids
Concentrations of acids or bases
Solutions with halides: chlorides, fluorides, bromides, iodides or sulfur
Bleach (Sodium Hypochlorite)
Solutions with chromates or chromium salts
Glycerin
Syltherm fluids
** At temperatures above 40°C, additives or mineral deposits can adhere to the heater. If deposits are allowed to
build up, the heater may overheat and fail. Higher temperatures and higher concentrations of additives can hasten deposit build up.
Filling the Reservoir
Unscrew the reservoir cap and carefully fill the reservoir with fluid. Leave the cap off and add additional fluid as instructed under Starting Process Fluid Flow, below.
110-445
8
Electrical Power
Electrical Power
Electrical PowerElectrical Power
Plug the Chiller’s power cord into an appropriate electrical outlet.
Place the Circuit Breaker/Power Switch on the rear of the instrument enclosure in the “On” position. Three decimal points will appear on the Temperature display.
Starting Process Fluid Flow
Starting Process Fluid Flow
Starting Process Fluid FlowStarting Process Fluid Flow
Press the Power Button on the front panel. The system startup sequence will begin and proceed as follows:
1. The pump will turn on and fluid will begin circulating through the system. The set point temperature will appear briefly on the Temperature display; after a few seconds, it will be replaced by the actual fluid temperature. Fifteen to 20 seconds after power up, the compressor will begin operating.
2. Check for leaks.
3. With the pump running, the reservoir’s fluid level will drop as the process and/or process cooling lines fill with fluid.
4. Slowly add fluid to the reservoir until the liquid level as shown on the front panel fluid level gauge remains stable at the “Full” mark.
5. Replace the reservoir cap.
IMPORTAN
IMPORTANT SPECIAL FEATURE:
IMPORTANIMPORTAN System, which increases/decreases fan speed based on heat load. You will notice that the fan speed changes during operation. This is particularly beneficial in an environment where low noise level is desirable.
T SPECIAL FEATURE: This Chiller equipped with the WhisperCool™ Environmental Control
T SPECIAL FEATURE: T SPECIAL FEATURE:
Normal Operation
Normal Operation
Normal OperationNormal Operation
Selecting the Temperature Unit (°C or °F)
Selecting the Temperature Unit (°C or °F)
Selecting the Temperature Unit (°C or °F)Selecting the Temperature Unit (°C or °F)
The LEDs adjacent to the Temperature Display indicate the unit (°C or °F) in which temperature is displayed. To change from °C to °F or vice versa, proceed as follows:
To change to °F — Place the Circuit Breaker/Power Switch on the rear of the instrument in the “Off” position. Press and hold the Down arrow button while returning the Circuit Breaker/Power Switch to the “On” position.
To change to °C — Place the Circuit Breaker/Power Switch on the rear of the instrument in the “Off” position. Press and hold the Up arrow button while returning the Circuit Breaker/Power Switch to the “On” position.
CAUTION:
CAUTION: User settings (except local lockout, baud rate, and calibration offset) return to the original
CAUTION: CAUTION: factory defaults when the unit in which temperature is displayed is changed. The Chiller’s temperature set point and various alarm settings should be reset to the desired values.
110-445
9
Displaying and Adjusting the Set Point
Displaying and Adjusting the Set Point
Displaying and Adjusting the Set Point Displaying and Adjusting the Set Point
Press the Set button on the front panel. The current set point temperature will be displayed and the decimal point at the bottom right of the display will flash, indicating the temperature can be changed.
Press the Up and Down arrow button to adjust the set point temperature. It may be set anywhere from -20° to +60°C. The default set point is +10°C. The setting is accepted after either pressing the Set button a second time or will be accepted automatically after a few seconds of inactivity.
IMPORTANT:
IMPORTANT: While it is possible to set a temperature set point outside the temperature ranges outlined
IMPORTANT: IMPORTANT: above, the Chiller will not be able to control at that temperature reliably.
Setting Operational Para
Setting Operational Parameters
Setting Operational ParaSetting Operational Para
meters
meters meters
The Chiller’s temperature limits and other operational parameters are user-adjustable.
Accessing Operational Parameters Menu Items: You can access and scroll through the operational parameter menu items by pressing and releasing the Up and Down arrow buttons simultaneously. The first menu item that will appear on the display is the High Temperature Limit value (shown as an H followed by the present setting; e.g., H-71). To scroll to the next menu item, press and release the Up and Down arrow buttons again.
Changing an Operational Parameter: When the operational parameter you wish to change appears, wait until the decimal point on the right of the display flashes and then press the appropriate arrow button to change the displayed value.
Accepting an Operational Parameter Value: To accept the displayed value and return to the main operational display, either press the Set button or allow the display to timeout (approximately 15-20 seconds). To accept the displayed value and advance to the next menu item, press the Up and Down arrow buttons simultaneously.
Menu Item
Menu Item**** Description
Menu ItemMenu Item
HHHH----71
71 High Temperature Limit Set Point 1° to 71°C (33° to 159°F) 71°C (159°F)
7171
LLLL----46
46 Low Temperature Limit Set Point -46° to -1°C (-50° to 31°F) -46°C (-50°F)
4646
A 30
A 30 Auto-Refrigeration Temperature
A 30A 30
P.80
P.80 Specific Heat of Fluid 0.10 to 2.00 0.8
P.80P.80
PC96
PC96 Communication Baud Rate x 100 24, 48, 96, 192 96
PC96PC96
C0.0
C0.0 Temperature Calibration 2.0º to -2.0ºC (2.0º to -2.0ºF) 0.0°C (0.0°F)
C0.0C0.0
Pd00
Pd00 Password For factory use only 00
Pd00Pd00
**** The values shown after the Menu Item in the above table indicate how these menu items will appear as set by the factory. The actual
numeric value(s) displayed will differ for any menu item(s) you change.
High Temperature Limit
High Temperature Limit (H
High Temperature LimitHigh Temperature Limit
Description Choices / Ranges / Comments
DescriptionDescription
(H----##))))
(H (H
Choices / Ranges / Comments Default Setting
Choices / Ranges / CommentsChoices / Ranges / Comments
20°C – 90°C (always displayed/set in °C)
Default Setting
Default SettingDefault Setting
30°C
This menu item serves as a user adjustable high temperature limit. It limits how high the temperature set point may be set as well as the highest process fluid temperature at which the Chiller will operate. When this value is exceeded, the appropriate alarm or fault message will appear on the display (see
Error Messages
).
Display, Fault and
To change the high temperature limit value, press the Up or Down arrow button until the desired high limit value is displayed on the temperature display.
To accept the displayed value and return to the main operational display, either press the Set button or allow the display to timeout (approximately 15-20 seconds). To accept the displayed value and advance to the next menu item, press the Up and Down arrow buttons simultaneously.
110-445
10
Low Temperature Limit (L
Low Temperature Limit (L----##
Low Temperature Limit (LLow Temperature Limit (L
##))))
####
This menu item serves as a user adjustable low temperature limit. It limits how low the temperature set point may be set as well as lowest process fluid temperature at which the Chiller will operate. When this value is exceeded, the appropriate alarm or fault message will appear on the display (see
Messages
).
Display, Fault and Error
To change the low temperature limit value, press the Up or Down arrow button until the desired low limit value is displayed on the temperature display.
To accept the displayed value and return to the main operational display, either press the Set button or allow the display to timeout (approximately 15-20 seconds). To accept the displayed value and advance to the next menu item, press the Up and Down arrow buttons simultaneously.
Auto
Auto----Refrigeration Temperature (A ##)
Refrigeration Temperature (A ##)
AutoAuto
Refrigeration Temperature (A ##)Refrigeration Temperature (A ##)
This menu item allows you to select the temperature at which refrigeration is activated. When the set point exceeds the auto-refrigeration temperature by more than 1.0°C, the cooling and the fan are turned off.
To change the auto-refrigeration temperature, press the Up or Down arrow button until the desired auto­refrigeration temperature is displayed on the temperature display.
To accept the displayed value and return to the main operational display, either press the Set button or allow the display to timeout (approximately 15-20 seconds). To accept the displayed value and advance to the next menu item, press the Up and Down arrow buttons simultaneously.
CAUTION:
CAUTION: This value is always displayed/set in °C.
CAUTION:CAUTION:
Specific Heat (P
Specific Heat (P....##
Specific Heat (PSpecific Heat (P
This menu item allows you to adjust chiller performance to the specific heat of the cooling fluid, thus optimizing temperature control. It should be set to 0.80 for a 50% glycol / 50% water solution (the specific heat value for water is 1.00).
To change the specific heat setting, press the Up or Down arrow button until the desired low limit value is displayed on the temperature display.
To accept the displayed value and return to the main operational display, either press the Set button or allow the display to timeout (approximately 15-20 seconds). To accept the displayed value and advance to the next menu item, press the Up and Down arrow buttons simultaneously.
Communications Baud Rate
Communications Baud Rate (PC
Communications Baud RateCommunications Baud Rate
This menu item allows you to set the baud rate of the chiller to match the device to which it is connected. It is functional only on Chillers equipped with the optional RS232 output.
To change the baud rate setting, press the Up or Down arrow button until the desired low limit value is displayed on the temperature display.
To accept the displayed value and return to the main operational display, either press the Set button or allow the display to timeout (approximately 15-20 seconds). To accept the displayed value and advance to the next menu item, press the Up and Down arrow buttons simultaneously.
##))))
####
(PC##
##))))
(PC (PC
####
110-445
11
Temperature
Temperature Calibration (C
Temperature Temperature
Calibration (C ####....####))))
Calibration (CCalibration (C
The Chiller’s temperature probe is accurate to ±0.25°C. Therefore, if the displayed temperature 15°C, the actual temperature will be between 14.75°C and 15.25°C.
This menu item allows you to adjust the Chiller’s temperature reading to match that of a traceable standard or another piece of equipment. It allows you to offset the displayed temperature value by as much as ±2.0°C (±2.0°F).
To change the calibration offset value, press the Up or Down arrow button until the desired low limit value is displayed on the temperature display.
To accept the displayed value and return to the main operational display, either press the Set button or allow the display to timeout (approximately 15-20 seconds). To accept the displayed value and advance to the next menu item, press the Up and Down arrow buttons simultaneously.
CAUTION:
CAUTION: Positive offsets are denoted with a blank space between C and the offset value (e.g., C 0.3);
CAUTION:CAUTION: negative offsets are denoted with a minus sign between C and the offset value (C-0.3).
Password
Password (Pd00)
PasswordPassword
This menu item is reserved for factory use only.
Enabling/Disabling the Local Lockout
Enabling/Disabling the Local Lockout (LLO)
Enabling/Disabling the Local LockoutEnabling/Disabling the Local Lockout
This feature is used to prevent unauthorized or accidental changes to set point and other operational values. When enabled, the temperature set point and operational parameters can be displayed, but not changed.
(Pd00)
(Pd00) (Pd00)
(LLO)
(LLO) (LLO)
To enable the local lockout, press and hold the Set button until LLO is displayed (approximately 5 seconds). Once enabled, LLO will appear momentarily when the Set button is pressed to display the set point.
To disable the local lockout, press and hold the Set button until CAn appears, indicating that the local lockout feature has been disabled.
CAUTION:
CAUTION: The Local Lockout feature does not prevent set point changes entered via the optional RS232
CAUTION:CAUTION: interface.
110-445
12
Display,
Display, Error
Display, Display,
Error and Fault
Error Error
and Fault Messages
and Fault and Fault
Messages
MessagesMessages
When certain conditions are detected, message codes flash on the display. Depending on the nature of the condition, power to various systems components is removed. When the condition is rectified, press the front panel Power button or turn power switch/circuit breaker Off then On to clear the fault or error.
Message Code
Message Code Description
Message CodeMessage Code
EHL
EHL
EHLEHL EEEE----HI
HI
HIHI
FHL
FHL
FHLFHL
ELL
ELL
ELLELL
EEEE----LO
LO
LOLO
ELL
ELL
ELLELL
EFL
EFL
EFLEFL
FFL
FFL
FFLFFL
Ft3
Ft3
Ft3Ft3
FOt
FOt
FOtFOt
Ft5
Ft5
Ft5Ft5
Ft7
Ft7
Ft7Ft7
Description Ac
DescriptionDescription
Error — The set point temperature has been set higher than the high limit temperature.
Error High Limit
Fault High Limit
Error Low Limit
Fault Low Limit
Fluid Low Error
Fluid Flow Fault
Fault 3
Fault OTP
Fault 5
Temperature Probe Fault
Chiller Operation — Chiller continues normal operation; display alternates between EHL, E-HI and the fluid temperature.
Action — Decrease set point temperature or increase high limit temperature.
Fault — The fluid temperature has exceeded the high limit temperature for more than 25 seconds.
Chiller Operation — Normal operation stops, with heating and cooling turned off and the pump remaining on. FHL displayed continuously.
Action — Correct high fluid temperature problem or increase high limit temperature.
Error — The set point temperature has been set lower than the low limit temperature.
Chiller Operation — Chiller continues normal operation; display alternates between ELL, E-LO and the fluid temperature.
Action — Increase set point temperature or decrease low limit temperature.
Fault — The fluid temperature has been below the low limit temperature for more than 25 seconds.
Chiller Operation — Normal operation stops, with heating and cooling turned off and the pump remaining on. ELL displayed continuously.
Action — Correct low fluid temperature problem or decrease low limit temperature.
Error — Fluid flow is low.
Chiller Operation — Chiller continues normal operation; display alternates between EFL and the fluid temperature.
Action — Add fluid to reservoir; check lines for restrictions.
Fault — The fluid flow has been low for more than 20 seconds.
Chiller Operation — Normal operation stops, with heating, cooling, and pump turned off. FFL displayed continuously.
Action — Add fluid to reservoir; check lines for restrictions.
Fault — One or all instrument settings are out of range.
Chiller Operation — Normal operation stops, with heating, cooling, and pump turned off. Ft3 displayed continuously.
Action — Contact manufacturer
Fault — Heater over-temperature fault.
Chiller Operation — Normal operation stops, with heating, cooling, and pump turned off. FOt displayed continuously.
Action — Contact manufacturer.
Fault — Heater Triac failure.
Chiller Operation — Normal operation stops, with heating, cooling, and pump turned off. Ft5 displayed continuously.
Action — Contact manufacturer.
Fault — The main temperature probe has failed.
Chiller Operation — Normal operation stops, with heating, cooling, and pump turned off. Ft7 displayed continuously.
Action — Contact manufacturer.
Action Required
tion Required
AcAc
tion Requiredtion Required
110-445
13
Routine Maintenance and Troubleshooting
Filter compartment
Washable
Routine Maintenance and Troubleshooting
Routine Maintenance and TroubleshootingRoutine Maintenance and Troubleshooting
The Chiller is designed to require a minimum of periodic maintenance.
Magnetic Drive Centrifugal Pump
Magnetic Drive Centrifugal Pump
Magnetic Drive Centrifugal PumpMagnetic Drive Centrifugal Pump
When used under continuous operating conditions, this pump should be oiled every six (6) months with SAE 20 oil. The pump incorporates two oil ports for this purpose.
To access the pump:
1. Turn both power switches off and unplug the power cord.
2. Remove the two screws securing the left side panel (as viewed from the front) of the housing to the
frame.
NOTE:
NOTE: If your Chiller is equipped with a turbine pump, no pump maintenance is required.
NOTE:NOTE:
Condenser, Air Vents, and Reusable F
Condenser, Air Vents, and Reusable Filter
Condenser, Air Vents, and Reusable FCondenser, Air Vents, and Reusable F
To keep the system operating at optimum cooling capacity, the condenser, the air vents, and reusable filter should be kept free of dust and dirt. They should be checked on a scheduled basis and cleaned as required.
To access the air filter, open the filter compartment door by placing your index finders in the cutouts on the sides of the compartment door (upper corners) and pulling towards you.
Remove the filter and remove accumulated dust and dirt. It may be cleaned by either vacuuming, blowing out with a clean air source, and/or washing with a mild detergent and water solution. If using a detergent/water solution, be sure to rinse and dry thoroughly before reinstalling.
ilter
ilterilter
door access cutouts
(both sides of
compartment door)
Reusable air filter: Part number 750-758
Fluid Level
Fluid Level
Fluid LevelFluid Level
The fluid level gauge on the front panel of the Chiller should be periodically checked to determine if the fluid level needs to be topped off. Generally, fluid should be added whenever the level in the reservoir is below the “Full” mark.
Temperature Calibration
Temperature Calibration
Temperature Calibration Temperature Calibration
At times, there may be a minor temperature difference between the Chiller’s displayed temperature and the actual temperature as determined by a certified temperature measurement device. There may also be situations where you want the displayed temperature to match a particular value to have standardization between different instruments. These adjustments can be performed using the Chiller’s temperature calibration offset functions. See
Normal Operation, Temperature Calibration (C #.#)
air filter
.
110-445
14
Cleaning Exterior Surfaces
Cleaning Exterior Surfaces
Cleaning Exterior Surfaces Cleaning Exterior Surfaces
Only mild detergents and water or an approved cleaner should be used on the painted surfaces of the Chiller. Do not allow cleaning liquids or sprays to come in direct contact with the digital display.
Troubleshooting
Troubleshooting
TroubleshootingTroubleshooting
NO
NOTE:
TE: Many problems can be resolved by restoring the factory defaults. If this solves the problem, be
NONO
TE: TE:
careful when restoring your operational settings in order not to repeat the problem. To restore the factory default settings:
1. Place the Power Switch/Circuit Breaker on the rear of the unit in the OFF position.
2. Press and hold either the Up (for °C) or Down (for °F) arrow button while returning the Circuit Breaker/Power Switch to the On position.
WARNING:
WARNING: Refer servicing to qualified service personnel.
WARNING:WARNING:
WARNING:
WARNING: When electrical power is On, dangerous voltages exist within chassis components. Use
WARNING:WARNING: extreme care when measuring voltages on live circuits.
Problem
Problem Possible Causes
ProblemProblem
Unit does not run (digital displays blank)
Unit does not run (three decimal points appear on temperature display, two decimal points on pressure/flow rate display)
No fluid circulation Insufficient fluid in reservoir
Insufficient circulation Fluid viscosity too high
Unit does not cool or cooling is insufficient
Display not responding
Numbers do not change; display does not respond when Set or Arrow buttons are pressed; incorrect numerals or characters are displayed; no large numbers or characters displayed on readout)
Possible Causes Corrective Action
Possible CausesPossible Causes
No power to unit
Unit in Standby mode Press Power Button on front panel.
Blockage in circulating system
Pump is not operating
External tubing diameter too small
Restrictions in fluid lines
Low line voltage
Dust build up on air filter or condenser
Blocked air ventilation screens
Excessive heat load
Ambient air temperature too high
Low or high line voltage
Electronics malfunction Reset factory defaults. If problem persists, contact
Corrective Action
Corrective ActionCorrective Action
Check that the electrical cord is secure and connected to an operating electrical outlet.
Check that Circuit Breaker / Power Switch on rear of unit is On.
Add fluid to reservoir.
Remove blockage.
Replace pump.
Replace with lower viscosity fluid.
Replace with larger diameter tubing.
Check and correct as required.
Check and correct as required.
Clean air filter and/or condenser as required.
Remove blockages as required.
Check that heat load does not exceed capacity of chiller; correct as required.
Decrease ambient air temperature.
Check and correct as required.
factory.
110-445
15
Technical Information
Centrifugal Pump
Turbine Pump
Model LS51/LS53 60Hz Compact Chiller Specifications
Model LS51/LS53 60Hz Compact Chiller Specifications
Model LS51/LS53 60Hz Compact Chiller SpecificationsModel LS51/LS53 60Hz Compact Chiller Specifications
Performance 120/230V, 60Hz
Performance 120/230V, 60Hz
Performance 120/230V, 60HzPerformance 120/230V, 60Hz
Working temperature range
Operating temperature range 2 -20° to +60°C / -4° to +140°F
Temperature Stability ±0.1°C (±0.18°F)
Cooling capacity Ethylene Glycol & Water (50/50 mix)
Pump MX Centrifugal M1 Centrifugal TX Turbine
@ Watts BTU/Hr Watts BTU/Hr @
-20°C
-10°C 0°C
+10°C +20°C +30°C
+40°C
1. The temperature that the chiller can reach without an external heating or cooling source.
2. The temperature range in which the chiller can control temperature, limited by electronics.
Pump option
Pump option MX
Pump optionPump option
260 475 750
1130 1290 1460
1610
1800
1600
1400
1200
1000
800
600
400
Cooling Capacity - Watts
200
0
-20 -10 0 10 20 30 40
Maximum Flow 13.2 lpm / 3.5 gpm 14.8 lpm / 3.9 gpm 9.8 lpm / 2.6 gpm
Maximum Pressure 14.5 psi / 0.99 bar 9 psi / 0.62 bar 43.4 psi / 2.99 bar
Maximum Head 10.2 m / 33.5 ft H2O 5.6 m / 18.5 ft H2O 26.75 m / 87.8 ft H2O
1
888 1622 2561
3859 4406 4986 5498
Fluid Temperature - °C
MX ---- Centrifugal
Centrifugal M1
MX MX
Centrifugal Centrifugal
-20° to +40°C / -4° to +104°F
230 435 680
1030
1160 1380 1550
M1 ---- Centrifugal
Centrifugal TX
M1 M1
Centrifugal Centrifugal
785
1486
2322
3518
3962
4713
5294
-20°C
-10°C 0°C
+10°C +20°C +30°C +40°C
Watts BTU/Hr
150 345 540 790 900
1020
1140
TX ---- Turbine
Turbine
TX TX
Turbine Turbine
512
1178
1844 2698 3074 3483 3893
Specifications are subject to change. Performance data based on 120V or 230V, 60hz input power, 20°C ambient temperature and a 50/50 mix of Ethylene Glycol and distilled water as coolant.
110-445
40
TX
35
30
25
MX
20
Pressure - psi
15
10
M1
5
0 5 10 15
Flow - lpm
280
240
200
160
120
80
40
0
Pressure - kPa
16
Model LS52 50Hz Compact
Model LS52 50Hz Compact Chiller Specifications
Model LS52 50Hz CompactModel LS52 50Hz Compact
Performance 240V, 50Hz
Performance 240V, 50Hz
Performance 240V, 50HzPerformance 240V, 50Hz
Working temperature range
Chiller Specifications
Chiller Specifications Chiller Specifications
1
-20° to +40°C / -4° to +104°F
Operating temperature range 2 -20° to +60°C / -4° to +140°F
Temperature Stability ±0.1°C (±0.18°F)
Cooling capacity: Ethylene Glycol & Water (50/50 mix)
Pump M2 Centrifugal MY Centrifugal TY Turbine
@ Watts BTU/Hr Watts BTU/Hr @ Watts BTU/Hr
-20°C
-10°C 0°C
+10°C +20°C +30°C +40°C
1. The temperature that the chiller can reach without an external heating or cooling source.
2. The temperature range in which the chiller can control temperature, limited by electronics.
230 435 680
1030
1160 1380 1545
1800
1600
1400
1200
1000
Cooling Capacity - Watts
785
1485
2322
3518
3962
4713
5276
800
600
400
200
0
-20 -10 0 10 20 30 40
240 460 700
1070
1190 1420 1580
Fluid Temperature - °C
820 1571
2391
3996 4064 4850 5396
Centrifugal Pump
Turbine Pump
-20°C
-10°C 0°C
+10°C +20°C +30°C +40°C
140 330 500 750 830 990 1105
478
1127 1708 2561
2835
3381
3774
Pump option M2 - Centrifugal MY - Centrifugal TY - Turbine
Maximum Flow 12.9 lpm / 3.4 gpm 11.7 lpm / 3.1 gpm 8.3 lpm / 2.2 gpm
Maximum Pressure 5.5 psi / 0.38 bar 10.5 psi / 0.72 mbar 32 psi / 2.2 bar
Maximum Head 4 m / 12.8 ft H2O 7 m / 23 ft H2O 17 m / 56.5 ft H2O
Specifications are subject to change. Performance data based on 240V, 50hz input power, 20°C ambient temperature and a 50/50 mix of Ethylene Glycol and distilled water as coolant.
25
23
21
19
17
15
13
Pressu re - p si
11
9
7
5
0 5 10 15
TY
MY
M2
Flow - lpm
180
160
140
120
100
80
60
40
20
Pressure - kPa
110-445
17
General Information & Specifications
General Information & Specifications
General Information & SpecificationsGeneral Information & Specifications
Safety
Safety
SafetySafety Auto-restart on power failure Yes
Low flow alarm and power cutoff Yes
High temperature safety Yes
High temperature limit Yes (user adjustable)
Low temperature limit Yes (user adjustable)
Compliance
Compliance
ComplianceCompliance CSA-US Yes
CE Yes
WEEE Compliant
RoHS Compliant
Construction
Construction
ConstructionConstruction
Outer case Epoxy powder coated steel
Wetted parts
Unit dimensions (L x W x H) 60.7 x 25.4 x 48.3 cm / 23.9 x 10 x 19 in.
Unit weight 46.3 kg / 102 lbs
Reservoir volume 2.65 L / 0.7 gal
Heat exchanger Stainless steel copper-brazed plate
Noise Rating (measured at .9 m from the unit)
Compressor Hermetic
Refrigerant type R-404a
Controller
Controller
ControllerController
Display type Digital, LED
Temperature stability ±0.1°C
Display resolution 0.1°
Temperature Units °C or °F
User calibration Temperature
Setup
Setup
SetupSetup
Recommended fluid(s) 50/50 mix of distilled water and ethylene glycol
Incompatible fluids
Ambient temperature operating range 5° to 35°C / 41° to 95°F
Maximum relative humidity 80% non-condensing
Operating power requirements
Fluid inlet/outlet 0.5 inch female brass NPT
Recommended tubing I.D. 0.375 inch / 9.5 mm (minimum)
Specifications subject to change without notice.
Environmental Conditions Indoor use only Maximum Altitude: 2000 meter Operating Ambient: 5° to 35°C (41° to 95°F) Relative Humidity: 80%, non-condensing Installation Category: II Pollution Degree: 2
Brass, Copper, Stainless Steel, EPDM Rubber, Alcryn, Nylon, PVC, and Polyethylene
53 dBA
Corrosive or flammable fluids; Deionized water package available
103 - 127V, 12A, 60Hz (LS51) 208 – 253V, 6A 60Hz (LS53) 216 – 264V, 6A, 50Hz (LS52)
110-445
18
RS232
RS232 Serial Communications
RS232RS232
Serial Communications (Optional)
Serial Communications Serial Communications
(Optional)
(Optional) (Optional)
This option allows you to remotely control the Chiller and/or output temperature readings to an external recorder or other auxiliary device. The maximum communications distance for Chillers equipped with the RS232 option is 15 meters (50 feet).
Serial Connector — A 9-pin D-connector is provided on the back panel of the Chiller for RS232 data communication. A serial cable that uses only the following pins should be used to connect the Chiller to the computer: Pin #2 — data read (data from computer) Pin #3 — data transmit (data to computer) Pin #5 — Signal ground
RS232 Protocol — The Controller uses the following RS232 protocol: Data bits — 8 Parity — None Stop bits — 1 Flow control — None Baud rate — Selectable (Chiller and PC baud rates must match).
Communications Commands — Commands must be entered in the exact format shown. Do not send a [LF] (line feed) after the [CR] (carriage return). Be sure to follow character case exactly. A response followed by an exclamation point (!) indicates that a command was executed correctly. A question mark (?) indicates that the Chiller could not execute the command (either because it was in an improper format or the values were outside the allowable range). A response must be received from the Chiller before another command can be sent. All responses are terminated with a single [CR].
Command Description
Command Description Command Format
Command DescriptionCommand Description
Set Command Echo SEi[CR]
Set On / Off SOi[CR]
Set Set Point SSxxx[CR] x = ASCII digit ![CR]
Read Set Point Temperature RS[CR]
Read Temperature RT[CR]
Read Temperature Units RU[CR] C or F
Read Status RW[CR]
Read Compressor Discharge Temperature (°C) RUT[CR]
Read fault status
Read Evaporator Inlet Temperature (°C) REI[CR] xxx.x[CR]
Read Evaporator outlet temperature (°C) REO[CR] xxx.x[CR]
Output continuous data stream, one set per second Set on/off
Command Format Values
Command FormatCommand Format
RF[CR]
RDi[CR]
Values Return Message
ValuesValues
Echo: i = 1 No Echo: i = 0
i = 1 to turn on i = 0 to turn off
1 = Run 0 = Standby
00 = System OK Faults
i = 1 to turn on i = 0 to turn off
Return Message
Return MessageReturn Message
![CR]
![CR]
+xx.x[CR] or
-xx.x[CR]
+xx.x[CR] or
-xx.x[CR]] C[CR] or F[CR]
1[CR] or 0[CR]
xxx.x[CR]
![CR]
![CR]
RD command results in a continuous data stream. Headers are:
Min.sec, software version, temperature units, temperature setpoint, fluid temperature, remote probe temperature, not used, compressor discharge temperature, evaporator inlet temperature, evaporator outlet temperature, heat %, cool %, fan %. Temperatures are always in degrees Celsius.
110-445
19
Equipment Disposal (WEEE Directive)
Equipment Disposal (WEEE Directive)
Equipment Disposal (WEEE Directive)Equipment Disposal (WEEE Directive)
or
This equipment is marked with the crossed out wheeled bin symbol to indicate it is covered by the Waste Electrical and Electronic Equipment (WEEE) Directive and is not to be disposed of as unsorted municipal waste. Any products marked with this symbol must be collected separately, according to the regulatory guidelines in your area.
guidelines in your area.
guidelines in your area.guidelines in your area.
It is your responsibility to correctly dispose of this equipment at lifecycle-end by handing it over to an authorized facility for separate collection and recycling. It is also your responsibility to decontaminate the equipment in case of biological, chemical and/or radiological contamination, so as to protect the persons involved in the disposal and recycling of the equipment from health hazards. By doing so, you will help to conserve natural and environmental resources and you will ensure that your equipment is recycled in a manner that protects human health.
Requirements for waste collection, reuse, recycling, and recovery programs vary by regulatory authority at your location. Contact your local responsible body (e.g., your laboratory manager) or authorized representative for information regarding applicable disposal regulations.
Any products marked with this symbol must be collected separately, according to the regulatory
Any products marked with this symbol must be collected separately, according to the regulatory Any products marked with this symbol must be collected separately, according to the regulatory
Service and Technical Support
Service and Technical Support
Service and Technical SupportService and Technical Support
If you have followed the troubleshooting steps and your Recirculating Chiller fails to operate properly, contact the supplier from whom the unit was purchased. Have the following information available for the customer service person:
Model, Serial Number, and Voltage (from back panel)
Date of purchase and your purchase order number
Suppliers' order number or invoice number
A summary of your problem
110-445
20
Replacement Parts and Accessories
Replacement Parts and Accessories
Replacement Parts and AccessoriesReplacement Parts and Accessories
Description
Description Part Number
DescriptionDescription
Reservoir Cap 300-460
Reservoir Spill Cup 300-575
Centrifugal Pump, M1 (120 V, 60 Hz) 525-782
Centrifugal Pump, M2 (230/240 V, 50/60 Hz) 525-783
Centrifugal Pump, MX (120 V, 60 Hz) 525-784
Centrifugal Pump, MY (230/240 V, 50/60 Hz) 525-785
Turbine Pump, TX (120 V, 60 Hz) 525-780
Turbine Pump, TY (230/240 V, 50/60 Hz) 525-781
Condenser 750-763
Compressor (120 V, 60 Hz) 750-369
Compressor (230 V, 60 Hz) 750-769
Compressor (240 V, 50 Hz) 750-370
Fan Motor (60 Hz) 215-642
Fan Motor (50 Hz) 215-643
Part Number
Part NumberPart Number
Circuit Breaker (50/60 Hz) 215-330
Buna N Tubing, ½” (13 mm); 1 m (39”) length 060308
Viton Tubing, ½” (13 mm); 1 m (39”) length 060316
Viton Tubing, 3/8” (10 mm); 1 m (39”) length 060319
Insulation for all ½” (13 mm) tubing; 1 m (39”) length 060311
Tube Clamp for ½” (13 mm), 5/8” (16 mm), and ¾” (18 mm) O.D. tubing, 1 each 400-898
Fitting, ½” male NPT to 3/8” (9.5 mm), hose barb, brass, straight 776-196
Fitting, ½” male NPT to 3/8” (9.5 mm), hose barb, brass, elbow 775-047
Fitting, ½” male NPT to 5/8” (16 mm), hose barb, nylon, straight 300-131
Fitting, ½” male NPT to ½” (13 mm), hose barb, nylon, straight 300-096
Fitting, ½” male NPT to ¾” (19 mm), hose barb, nylon, straight 776-197
Fitting, ½” male NPT to M16x1 13 mm (½”), brass, straight 775-048
Manifold Kit, 2 ports with shutoffs 510-665
Manifold Kit, 4 ports with shutoffs 510-664
Air Filter 750-758
Operator’s Manual 110-445
110-445
21
PolyScience Chiller Fluids
Manufactured by:
PolyScience Chiller Fluids
PolyScience Chiller FluidsPolyScience Chiller Fluids
Circulating Bath Fluids
Circulating Bath Fluids Quantity
Circulating Bath FluidsCirculating Bath Fluids
polyclean Algaecide 8 oz / 236 ml 004-300040
polyclean Algaecide Twelve 8 oz / 236 ml bottles 004-300041
polycool EG -25 (ethylene glycol) 1 gal / 4.5 liter 060340
Quantity Part Number
QuantityQuantity
Part Number
Part NumberPart Number
polycool PG -20 (propylene glycol)
polycool HC -50 (water-based heat transfer fluid)
polycool MIX -25 (50/50 blend polycool EG -25 / H2O plus polyclean algaecide)
Warranty
Warranty
WarrantyWarranty
The manufacturer agrees to correct for the original user of the product, either by repair (using new or refurbished parts), or at the manufacturer’s election, by replacement (with a new or refurbished product), any defects in material or workmanship which develop during the warranty period. The standard warranty is twenty-four (24) months after delivery of the product. In the event of replacement, the replacement unit will be warranted for the remainder of the original warranty period or ninety (90) days, whichever is longer. For purposes of this limited warranty, “refurbished” means a product or part that has been returned to its original specifications. In the event of a defect, these are your exclusive remedies.
If the product should require service, contact the manufacturer’s/supplier’s office for instructions. When return of the product is necessary, a return authorization number is assigned and the product should be shipped, transportation charges pre-paid, in either its original packaging or packaging affording an equal degree of protection to the indicated service center. To insure prompt handling, the return authorization number must be placed on the outside of the package. A detailed explanation of the defect should be enclosed with the item.
The warranty shall not apply if the defect or malfunction was caused by accident, neglect, unreasonable use, improper service, acts of God, modification by any party other than the manufacturer, or other causes not arising out of defects in material or workmanship.
1 gal / 4.5 liter
1 gal / 4.5 liter
Five 0.5 gal / 2.27 liter bottles 004-300060
060320
060330
EXCLUSION OF IMPLIED WARRANTIES.
EXCLUSION OF IMPLIED WARRANTIES. THERE ARE NO WARRANTIES, EXPRESSED OR IMPLIED,
EXCLUSION OF IMPLIED WARRANTIES.EXCLUSION OF IMPLIED WARRANTIES. INCLUDING, BUT NOT LIMITED TO, THOSE OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WHICH EXTEND BEYOND THE DESCRIPTION AND PERIOD AS STATED IN THE OPERATOR’S MANUAL INCLUDED WITH EACH PRODUCT.
LIMITATION ON DAMAGES.
LIMITATION ON DAMAGES. THE MANUFACTURER’S SOLE OBLIGATION UNDER THE WARRANTY IS LIMITED
LIMITATION ON DAMAGES.LIMITATION ON DAMAGES. TO THE REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT AND THE MANUFACTURER SHALL NOT, IN ANY EVENT, BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND RESULTING FROM USE OR POSSESSION OF THIS PRODUCT.
Some states do not allow: (A) limitations on how long an implied warranty lasts; or (B) the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may have other rights that vary from state to state.
PolyScience
6600 W. Touhy Avenue Niles, IL 60714 U.S.A.
1-800-229-7569  1-847-647-0611
www.polyscience.com
110-445
Loading...