Two-hand Relays
EN 574, Type IIIA
P1HZ 2
Two-hand relay in accordance with
VDE 0113-1, 11/98, EN 60204-1,
12/97 and IEC 204-1, 11/98.
Features
● Conforms to EN 574, Type IIIA
with partial fail to safety and in
accordance with EN 954,
Category 1.
Approvals
P1HZ 2
●
●
●
Technical Details P1HZ 2
Electrical Data
Supply Voltage AC: 24, 42, 110, 115, 120, 230, 240 V
DC: 24 V
Tolerance 85 ... 110 %
Residual Ripple DC Max. 20 %
Power Consumption Approx. 4 VA/2 W
Voltage and Current at the 24 VDC, 40 mA
Input Circuits 1/2
Switching Capability in accordance with
EN 60947-4-1, 01/00 AC1: 240 V/6 A/1500 VA
DC1: 24 V/1.5 A/12 W
EN 60947-5-1, 08/00 AC15: 230 V/2.5 A; DC13: 24 V/1.5 A
(DC13: 6 cycles/min.)
Output Contacts 2 safety contacts (N/O)
Contact Fuse Protection 6 A quick or 4 A slow
(EN 60947-5-1, 08/00)
Times
Delay-on Energisation EN 574 10 ms
Delay-on De-energisation Approx. 30 ms
Simuiltaneity channel 1/2 Max. 500 ms
Mechanical Data
Torque Setting on Connection Terminals 1.2 Nm (screws)
Maximum Cross Section of 2 x 2.5 mm
External Conductors Single-core or multi-core with
crimp connectors
Dimensions (H x W x D) 87 x 45 x 110 mm
Weight AC: 380 g, DC: 280 g
Description
● 45 mm, P-75-housing, DIN-Rail
mounting
● Positive-guided relay outputs:
2 safety contacts (N/O)
● Increase in the number of
safety contacts available by
connecting expander modules.
Function Description
The two-hand relay is not suitable for
use as the primary safety device on
mechanical and hydraulic presses or
in safety circuits for type IIIC
applications. For such applications
we recommend using the P2HZ 5 or
P2HZ X1.
A cycle can only be initiated by
pressing the two pushbuttons
simultaneously. A cycle is interrupted
by releasing one or both buttons to
stop the output.
The output signal can only be
reinitiated after both inputs have
been released and the pushbuttons
are operated again.
2
3
NSG-D-2-081-07/01
Two-hand Relays
EN 574, Type IIIA
P1HZ 2
3
Internal Wiring Diagram
U
A1
(L+)
T1
~
G1
+
Feedback
B
control loop
A2
(L-)
=
X1X2
Function Diagram
Operating Voltage
Input circuit 1
Input circuit 2
Simultaneity
Feedback Control Loop
Output
No significance
Feedback control loop open: 0
Feedback control loop closed: 1
(1): Normal working cycle
(2): Fault: feedback control loop not
closed at least 0.5 s before input
circuit 1/2
1
U
B
0
1
0
1
0
1
t
g
0
1
0
1
0
Input circuit 1
T14
(6)
t
g
(1)
Safety
contacts
T24T13 T23
13 23
K1
K2
14 24
t
(5)
Switch-on delay/
cycle test
Channel 1
K2K1
(2)
Input circuit 2
Channel 2
(3) (4)
(3): Fault: difference
input circuit 1/2 > t
(4): Fault: input circuit
g
1/2 closed before UB applied
(5): Fault: feedback control loop not
opened before the cycle t
(6): Undefined time period
● Increase in safety contacts
The number of output contacts can
be increased by using expander
modules or relays/contactors with
positive-guided contacts.
1L1
(1L+)
K4
K3
X1 X2
1L2
(1L-)
g
g
F2
13
14
K3 K4
Connection Example
1L1
(1L+)
F1
S1
A1
13
23
(+)
24
14
T23
S2
1L2
(1L-)
T13
X1
T24
X2
T14
– Key
S1/S2: Two-hand pushbuttons
A2
(-)
NSG-D-2-081-07/01