PARTS LIST.......................................................................................................................................................... 16
This manual is intended for use with the PFS automatic extinguisher. Those who install,
operate, inspect or maintain the PFS should read this entire manual. Specific sections will be
of particular interest depending on one’s responsibilities.
The installation limitations for the PFS are outlined in this manual. The installation,
inspection, testing, maintenance and recharge of the PFS is to be performed by Perfect Fry
Company authorized service personnel only.
The PFS consists of a cylinder assembly (with pressure switch and gauge), actuating
lever, fusible link assembly, manual pull station, and two nozzles. It is designed and
acceptable for use in areas that have ambient conditions between 0°C (32°F) and 50°C
(120°F).
The PFS must be stored above 0°C (32°F)
OPERATION
Automatic Operation
Upon the detection of a fire, the PFS will automatically operate. The fusible link rated at
138ºC (280ºF) will operate when exposed to the fire and operate the PFS automatic
extinguisher unit. When operated, the PFS unit will discharge wet chemical agent through
the provided discharge piping and distribution nozzles.
Manual Operation
The PFS unit can also be operated manually by pulling the remote lever (to be mounted
on the front of the cooking appliance) that is clearly marked “In Case Of Fire - PULL”.
Power shut-off is also achieved by system operation. If the
pressure in the cylinder(s) drops below 92 psi, the pressure
switch opens, deactivating the power relay causing the appliance
to de-energize.
1. Install nozzle adapters, nozzles, and tubing and compression fittings as shown below.
Appliance wall should be located between adapters and lock washer. Tighten all
adapters, compression fittings and pipe threads securely. 1-5/16”, ¾” & ½” open end
wrenches are required.
Upper nozzle
Upper nozzle
¼” elbow compression fitting
¼” tee compression fitting
¼” copper tubing
Lower nozzle
/8 lock washe
/8-9 jam nu
Lower nozzle
¼” elbow compression fitting
Upper nozzle slit is horizontal. Fan
pattern sprays above air filter
cartridge and below fan. Blow-off
cap removed for illustration only.
Be sure to install the nozzles properly.
Failure to do so will prevent them from
working properly in the event of system
actuation.
Lower nozzle sprays full cone
pattern and is directed at oil vat.
Blow-off cap removed for
illustration only.
6. Install 138C / 280F fusible link (6GT587) between two s-hooks and attach far ends to
fusible link bracket and fusible link cable (6GT599-2). Route fusible link cable through
appliance wall. Use small flat screwdriver or small pliers to help pull cable through if
necessary.
Appliance wall
Fusible link cable
S-hoo
Fusible link
Fusible link bracke
7. INSTALL SAFETY PIN.
8. Run fusible link cable through adjuster and attach hitch pin clip from manual pull cable
to underside of actuating lever. Move adjuster as needed to ensure proper tension on
cable and keep actuating lever horizontal.
9. Attach extension spring to actuating lever and appliance cutout.
Before arming the PFS, ensure that the safety pin is in
place under the actuating lever.
10. Connect pressure switch wires. Switch is designed for normally closed operation
within appliance to control relay/controller (and therefore shut down appliance). It
must be installed according to ratings listed in table below.
Switch Ratings
Switch
Operation
Switch
Configuration
Application
Voltage
Electrical
Current
AC Voltage Auto Reset SPST (NC) 5-28 VDC 5-400 mA
DC Voltage Auto Reset SPST (NC) 120/240 5.8/2.9 A
The appliance will not operate and will display a system
error message if wires are not connected.
Normally Closed SPST Switch
11. Remove safety pin. The PFS is now armed.
The safety pin is for maintenance purposes only. If the
safety pin is not removed, the PFS will not operate. THE
PIN MUST BE REMOVED.
The PFS Automatic Extinguisher must be serviced on a regular basis. Three types of
servicing are required:
Monthly - an inspection or “quick check” must be conducted by the owner/operator and
include verification of the following:
1) The PFS is in its proper location.
2) The PFS shows no physical damage or condition that might prevent operation.
3) The pressure gauge is in the green operating range.
4) The maintenance tag is in place and is up to date.
5) The manual pull is unobstructed.
6) The nozzle blow-off caps are intact and undamaged.
Semi-Annually / Yearly – maintenance must be conducted by authorized service
personnel (as per NFPA 17A) and include the following:
1) A check to see that the hazard has not changed.
2) Examination of the fusible link, cylinder, tubing, nozzles and all auxiliary equipment.
3) Fusible links must be replaced at least annually from the date of installation. They
must be destroyed when removed. They need to be replaced with the proper rated
link (6GT587). A fusible link loaded with grease or other material can result in an
excessive delay in actuation.
4) Verification that the agent distribution piping is not obstructed. Remove the blowoff caps (6GT014) from the nozzles to ensure that they are free of grease build-up
and inspect them for deterioration. Replace them as necessary.
5) Where semi-annual maintenance of any wet chemical containers or PFS
components reveals conditions such as, but not limited to, corrosion or pitting in
excess of manufactured limits, structural damage or fire damage, repairs by
soldering, welding, or brazing, the affected part(s) shall be replaced or
hydrostatically tested. The hydrostatic testing of wet chemical containers shall
follow the applicable procedures outlined in NFPA 17A.
6) All wet chemical systems must be tested for proper operation. A discharge of the
wet chemical is normally not part of the test. Simply remove one lead from the
pressure switch to initiate appliance shut-down.
7) Where the maintenance of the PFS reveals defective parts that could cause an
impairment or failure of proper operation of the PFS, the affected parts must be
replaced or repaired.
8) The maintenance report, with recommendations if any, shall be filed with the owner
or with the designated party responsible for the PFS.
9) The PFS must have a tag or label indicating the month and year the maintenance
is performed and identifying the person performing the service. Only the current
tag or label must remain in place.
Twelve Year – maintenance must be conducted by authorized service personnel (as per
NFPA 17A) and include the following:
1) The wet chemical extinguishing agent must be removed and discarded.
2) The cylinder needs to be hydrostatically tested to 300 psi.
3) If the cylinder shows no signs of rupture or distortion, recharge the PFS as directed
in the recharging instructions.
Ensure the system has fully discharged. If the system is
still pressurized, bleed slowly by unscrewing the head from
the cylinder until dry nitrogen begins to escape. Failure to
do so could cause personal injury or property damage.
9. Unscrew aluminum head from cylinder. Unscrew siphon tube and
remove spring from head.
10. Remove main o-ring (6GV064) from head assembly and inspect
for damage. Replace if necessary.
Valve stem
Main o-ring
Valve spring
Siphon tube
Cylinde
11. Remove valve stem (6GT591) by pressing down on actuating lever. Be careful not to
damage seating area or o-ring. Thoroughly rinse all parts with warm water and let dry.
Apply a high quality o-ring lube (Parker O-Lube) to all o-rings (two on valve stem and
one main one).
Upper o-ring
O-ring seating area
12. Remove straight compression fitting from head assembly using a ½” open end wrench.
Use a ¼” NPT male fitting with a standard air valve as a recharge adapter.
13. Fill cylinder to rated capacity (1000 mL ±5mL or 33.8 oz. ± ¼ oz.) using only Amerex
KP Wet Chemical Agent (6GT015). With a soft cloth, clean any spilled agent from
main o-ring seating area, threads of cylinder and cylinder exterior.
14. Reassemble head assembly and thread it back onto cylinder. Tighten head so that it
is firmly hand tight.
Charging Adapter
15. Thread charging adapter (6GTXXX) into head. Set regulator to required pressure
based on chart shown below. The normal operating pressure of PFS is 100 psi at
21C / 70F. Press actuating lever and pressurize it with dry nitrogen from regulated
source until required pressure is reached on in-line calibrated pressure gauge on fill
line.
Temperature (C)
Temperature (F)
0 5 10 15 20 25 30 35 40
32 41 50 59 67 77 86 95 104
Pressure (psi) 93 95 97 98 100 102 103 105 107
The pressure gauge attached to the extinguishing unit should not be
used to determine when the intended charging pressure has been
reached. Use the calibrating gauge on the recharge system to
determine if the correct pressure is being applied.
16. INSTALL SAFETY PIN before removal of regulated nitrogen source. Release
actuating lever.
17. Remove charging adapter. Attach straight compression fitting to head assembly using
a ½” open end wrench.
18. Check for leaks. Repeat steps 9-17 if PFS is leaking.
23. Reinstall tubing, compression fittings and nozzles in original positions. Use pipe
thread sealant tape on pipe threads if necessary. Make sure upper nozzle flat is
horizontal.
Upper nozzle slit is horizontal. Fan
pattern sprays above air filter
cartridge and below fan. Blow-off
cap removed for illustration only.
Be sure to install the nozzles properly.
Failure to do so will prevent them from
working properly in the event of system
actuation.
Lower nozzle sprays full cone
pattern and is directed at oil vat.
Blow-off cap removed for
illustration only.