Perfect Fry PFS Installation Manual

Page 1
Part # L20-361 R2
EX257375
10/1/2013
PFS
OWNER’S MANUAL
INSTALLATION, INSPECTION,
MAINTENANCE & RECHARGE
PHONE: 603-225-6684 ADDRESS: P.O. Box 501 Concord, NH 03302-0501 FAX: 603-225-8472 GENERAL INFORMATION: [email protected] CUSTOMER SUPPORT: [email protected] WEB: www.perfectfry.com
©2013 PERFECT FRY COMPANY
Page 2
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
TABLE OF CONTENTS
PFS AUTOMATIC EXTINGUISHER ....................................................................................................................... 1
GENERAL DESCRIPTION ................................................................................................................................................. 2
OPERATION ....................................................................................................................................................................... 2
PFS INSTALLATION .............................................................................................................................................. 3
INSPECTION & MAINTENANCE ........................................................................................................................... 8
PFS REMOVAL & RECHARGE ........................................................................................................................... 10
NOZZLE CLEANING ............................................................................................................................................ 14
PARTS LIST.......................................................................................................................................................... 16
Figure 1: PFS shown in PFC Series Fryer
II 10/1/2013 EX257375
Page 3
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
y
k
k
t
g
PFS Automatic Extinguisher
This manual is intended for use with the PFS automatic extinguisher. Those who install, operate, inspect or maintain the PFS should read this entire manual. Specific sections will be of particular interest depending on one’s responsibilities.
The installation limitations for the PFS are outlined in this manual. The installation, inspection, testing, maintenance and recharge of the PFS is to be performed by Perfect Fry Company authorized service personnel only.
Upper nozzle Upper nozzle adapter
¼” elbow compression fitting
¼” tee compression fitting
S-hoo
Fusible lin
Fusible link cable
Corner pulle
Corner pulley bracke
Hitch pin clip
Manual pull
Pressure switch
Lower nozzle adapter
¼” copper tubin
lower nozzle
¼” straight compression fitting Safety pin
Actuating lever Pressure gauge Head
Cylinder
Label
Manual pull cable
Extension spring
- 1 - 10/1/2013 EX257375
Mounting bracket
Page 4
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
GENERAL DESCRIPTION
The PFS consists of a cylinder assembly (with pressure switch and gauge), actuating lever, fusible link assembly, manual pull station, and two nozzles. It is designed and acceptable for use in areas that have ambient conditions between 0°C (32°F) and 50°C (120°F).
The PFS must be stored above 0°C (32°F)
OPERATION
Automatic Operation Upon the detection of a fire, the PFS will automatically operate. The fusible link rated at
138ºC (280ºF) will operate when exposed to the fire and operate the PFS automatic extinguisher unit. When operated, the PFS unit will discharge wet chemical agent through the provided discharge piping and distribution nozzles.
Manual Operation The PFS unit can also be operated manually by pulling the remote lever (to be mounted
on the front of the cooking appliance) that is clearly marked “In Case Of Fire - PULL”.
Power shut-off is also achieved by system operation. If the pressure in the cylinder(s) drops below 92 psi, the pressure switch opens, deactivating the power relay causing the appliance to de-energize.
- 2 - 10/1/2013 EX257375
Page 5
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
7
t
7
r
PFS Installation
1. Install nozzle adapters, nozzles, and tubing and compression fittings as shown below. Appliance wall should be located between adapters and lock washer. Tighten all adapters, compression fittings and pipe threads securely. 1-5/16”, ¾” & ½” open end wrenches are required.
Upper nozzle
Upper nozzle
¼” elbow compression fitting
¼” tee compression fitting
¼” copper tubing
Lower nozzle
/8 lock washe
/8-9 jam nu
Lower nozzle
¼” elbow compression fitting
Upper nozzle slit is horizontal. Fan pattern sprays above air filter cartridge and below fan. Blow-off cap removed for illustration only.
Be sure to install the nozzles properly. Failure to do so will prevent them from working properly in the event of system actuation.
Lower nozzle sprays full cone pattern and is directed at oil vat. Blow-off cap removed for illustration only.
- 3 - 10/1/2013 EX257375
Page 6
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
2. Install PFS to appliance with mounting brackets and hardware. Tighten nuts with 3/8” nut driver or open end wrench.
3. With ½” open end wrench, attach tubing to ¼” compression fitting.
- 4 - 10/1/2013 EX257375
Page 7
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
4. Install manual pull.
5. Install corner pulley. Tighten nuts with 3/8” nut driver or open end wrench.
- 5 - 10/1/2013 EX257375
Page 8
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
k
t
6. Install 138C / 280F fusible link (6GT587) between two s-hooks and attach far ends to fusible link bracket and fusible link cable (6GT599-2). Route fusible link cable through appliance wall. Use small flat screwdriver or small pliers to help pull cable through if necessary.
Appliance wall
Fusible link cable
S-hoo
Fusible link
Fusible link bracke
7. INSTALL SAFETY PIN.
8. Run fusible link cable through adjuster and attach hitch pin clip from manual pull cable to underside of actuating lever. Move adjuster as needed to ensure proper tension on cable and keep actuating lever horizontal.
- 6 - 10/1/2013 EX257375
Page 9
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
9. Attach extension spring to actuating lever and appliance cutout.
Before arming the PFS, ensure that the safety pin is in place under the actuating lever.
10. Connect pressure switch wires. Switch is designed for normally closed operation within appliance to control relay/controller (and therefore shut down appliance). It must be installed according to ratings listed in table below.
Switch Ratings
Switch
Operation
Switch
Configuration
Application
Voltage
Electrical
Current AC Voltage Auto Reset SPST (NC) 5-28 VDC 5-400 mA DC Voltage Auto Reset SPST (NC) 120/240 5.8/2.9 A
The appliance will not operate and will display a system error message if wires are not connected.
Normally Closed SPST Switch
11. Remove safety pin. The PFS is now armed.
The safety pin is for maintenance purposes only. If the safety pin is not removed, the PFS will not operate. THE PIN MUST BE REMOVED.
- 7 - 10/1/2013 EX257375
Page 10
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
Inspection & Maintenance
The PFS Automatic Extinguisher must be serviced on a regular basis. Three types of servicing are required:
Monthly - an inspection or “quick check” must be conducted by the owner/operator and
include verification of the following:
1) The PFS is in its proper location.
2) The PFS shows no physical damage or condition that might prevent operation.
3) The pressure gauge is in the green operating range.
4) The maintenance tag is in place and is up to date.
5) The manual pull is unobstructed.
6) The nozzle blow-off caps are intact and undamaged.
Semi-Annually / Yearly – maintenance must be conducted by authorized service
personnel (as per NFPA 17A) and include the following:
1) A check to see that the hazard has not changed.
2) Examination of the fusible link, cylinder, tubing, nozzles and all auxiliary equipment.
3) Fusible links must be replaced at least annually from the date of installation. They must be destroyed when removed. They need to be replaced with the proper rated link (6GT587). A fusible link loaded with grease or other material can result in an excessive delay in actuation.
4) Verification that the agent distribution piping is not obstructed. Remove the blow­off caps (6GT014) from the nozzles to ensure that they are free of grease build-up and inspect them for deterioration. Replace them as necessary.
5) Where semi-annual maintenance of any wet chemical containers or PFS components reveals conditions such as, but not limited to, corrosion or pitting in excess of manufactured limits, structural damage or fire damage, repairs by soldering, welding, or brazing, the affected part(s) shall be replaced or hydrostatically tested. The hydrostatic testing of wet chemical containers shall follow the applicable procedures outlined in NFPA 17A.
6) All wet chemical systems must be tested for proper operation. A discharge of the wet chemical is normally not part of the test. Simply remove one lead from the pressure switch to initiate appliance shut-down.
- 8 - 10/1/2013 EX257375
Page 11
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
7) Where the maintenance of the PFS reveals defective parts that could cause an impairment or failure of proper operation of the PFS, the affected parts must be replaced or repaired.
8) The maintenance report, with recommendations if any, shall be filed with the owner or with the designated party responsible for the PFS.
9) The PFS must have a tag or label indicating the month and year the maintenance is performed and identifying the person performing the service. Only the current tag or label must remain in place.
Twelve Year – maintenance must be conducted by authorized service personnel (as per
NFPA 17A) and include the following:
1) The wet chemical extinguishing agent must be removed and discarded.
2) The cylinder needs to be hydrostatically tested to 300 psi.
3) If the cylinder shows no signs of rupture or distortion, recharge the PFS as directed in the recharging instructions.
- 9 - 10/1/2013 EX257375
Page 12
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
PFS Removal & Recharge
1. INSTALL SAFETY PIN.
2. Detach extension spring.
3. Remove hitch pin clip.
4. Disconnect pressure switch wires.
- 10 - 10/1/2013 EX257375
Page 13
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
5. With ½” open end wrench, remove tubing from ¼” compression fitting.
6. Remove mounting brackets and hardware.
7. Remove PFS from appliance.
8. Obtain replacement PFS from Perfect Fry or follow steps 9-20.
- 11 - 10/1/2013 EX257375
Page 14
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
r
Ensure the system has fully discharged. If the system is still pressurized, bleed slowly by unscrewing the head from the cylinder until dry nitrogen begins to escape. Failure to do so could cause personal injury or property damage.
9. Unscrew aluminum head from cylinder. Unscrew siphon tube and remove spring from head.
10. Remove main o-ring (6GV064) from head assembly and inspect for damage. Replace if necessary.
Valve stem
Main o-ring
Valve spring
Siphon tube
Cylinde
11. Remove valve stem (6GT591) by pressing down on actuating lever. Be careful not to damage seating area or o-ring. Thoroughly rinse all parts with warm water and let dry. Apply a high quality o-ring lube (Parker O-Lube) to all o-rings (two on valve stem and one main one).
Upper o-ring
O-ring seating area
12. Remove straight compression fitting from head assembly using a ½” open end wrench. Use a ¼” NPT male fitting with a standard air valve as a recharge adapter.
- 12 - 10/1/2013 EX257375
Page 15
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
13. Fill cylinder to rated capacity (1000 mL ±5mL or 33.8 oz. ± ¼ oz.) using only Amerex KP Wet Chemical Agent (6GT015). With a soft cloth, clean any spilled agent from main o-ring seating area, threads of cylinder and cylinder exterior.
14. Reassemble head assembly and thread it back onto cylinder. Tighten head so that it is firmly hand tight.
Charging Adapter
15. Thread charging adapter (6GTXXX) into head. Set regulator to required pressure based on chart shown below. The normal operating pressure of PFS is 100 psi at 21C / 70F. Press actuating lever and pressurize it with dry nitrogen from regulated source until required pressure is reached on in-line calibrated pressure gauge on fill line.
Temperature (C)
Temperature (F)
0 5 10 15 20 25 30 35 40
32 41 50 59 67 77 86 95 104
Pressure (psi) 93 95 97 98 100 102 103 105 107
The pressure gauge attached to the extinguishing unit should not be used to determine when the intended charging pressure has been reached. Use the calibrating gauge on the recharge system to determine if the correct pressure is being applied.
16. INSTALL SAFETY PIN before removal of regulated nitrogen source. Release actuating lever.
17. Remove charging adapter. Attach straight compression fitting to head assembly using a ½” open end wrench.
18. Check for leaks. Repeat steps 9-17 if PFS is leaking.
19. Re-install PFS (refer to page 3)
- 13 - 10/1/2013 EX257375
Page 16
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
r
Nozzle Cleaning
20. Remove nozzles from wall adapters and disconnect tubing from compression fittings.
¼” elbow compression fitting
¼” tee compression fitting
Upper nozzle
¼” elbow compression fitting
21. Clean tubing and compression fittings with warm soapy water then rinse. Blow filtered compressed air through all pieces to dry.
22. Disassemble both upper and lower nozzle, wash with warm soapy water then rinse. Use filtered compressed air to dry.
Blow-off cap
Upper nozzle
¼” copper tubing
Lower nozzle
Lower nozzle
Blow-off cap
Outer nozzle o-ring
Outer nozzle o-ring
Upper nozzle
Nozzle straine
Inner nozzle o-ring
- 14 - 10/1/2013 EX257375
Be sure to reassemble the nozzles properly. Failure to do so will prevent them from working properly in the event of system actuation.
DO NOT USE O-RING LUBE ON INNER O-RINGS AS THEY ARE DESIGNED TO HOLD STRAINERS IN PLACE.
Lower nozzle
Lower nozzle insert
Nozzle strainer Inner nozzle o-ring
Page 17
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
23. Reinstall tubing, compression fittings and nozzles in original positions. Use pipe thread sealant tape on pipe threads if necessary. Make sure upper nozzle flat is horizontal.
Upper nozzle slit is horizontal. Fan pattern sprays above air filter cartridge and below fan. Blow-off cap removed for illustration only.
Be sure to install the nozzles properly. Failure to do so will prevent them from working properly in the event of system actuation.
Lower nozzle sprays full cone pattern and is directed at oil vat. Blow-off cap removed for illustration only.
24. If nozzle blow-off caps are damaged, replace.
- 15 - 10/1/2013 EX257375
Page 18
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
23
Parts List
30
31
33
28
27
26
29
34
35
32
34
5
4
6
7
9
8
10
25
26
25
23
16
11
18
13
1
2
3
12
14
22
24
22
36
21
19
20
17
15
17
# Part# Description # Part# Description 1 6GT669 manual pull 32 N/A lower nozzle assembly 2 6GT674 extension spring NS 6GT006 lower nozzle 3 6GT008 cylinder NS 6GT007 lower nozzle insert 4 6GT671 hitch pin clip NS 6GT017 nozzle inner o-ring 5 6ST665 corner pulley bracket NS 6GT016 nozzle outer o-ring 6 6GT800 adjuster NS 6GT018 nozzle strainer 7 6GT801 adjuster nut NS 6GT014 blow-off cap 8 6ST002 actuating lever 33 N/A upper nozzle assembly
9 6GV128 pressure switch NS 6GT005 upper nozzle 10 6GV068 brass elbow NS 6GT017 nozzle inner o-ring 11 6GT001 head – w et chemical NS 6GT016 nozzle outer o-ring 12 6GT002 siphon tube – wet chemical NS 6GT018 nozzle strainer 13 6GV064 main o-ring NS 6GT014 blow-off cap 14 6GT591 valve stem 34 6GT597 s-hook 15 6GT592 valve spring 35 6GT587 fusible link 16 6GT664 lever rivet 36 6GT019 charging adapter 17 6ST001 mounting bracket NS 6GT599-1 manual pull cable 18 6GT009 pressure gauge NS 6GT599-2 fusible link cable 19 6GT594 safety pin NS 6GV013 inspection tag 20 6GT010 ¼” straight compression fitting NS 6GV071 epoxy thread sealant 21 6GT011-03 or -04 lower tube (-03 PFC/SFC, -04 PFA) NS 6GT015 wet chemical agent 22 6GT011-01 or -02 upper tube (-01 PFA/PFC, -02 SFC) 23 6GT012 ¼” elbow compression fitting 24 6GT013 ¼” tee compression fitting 25 6NT005 7/8-9 jam nut 26 6NT006 7/8 lock washer 27 6GT004 upper nozzle adapter 28 6GT673-1 fusible link gasket Mildly irritating to the eyes, skin, and respiratory system. 29 6GT003 lower nozzle adapter 30 6GT596 corner pulley 31 6GT666 corner pulley bushing
Amerex Corporation P.O. Box 81 Trussville, AL 35173-0081 1-205-655-3271
Symptoms may include coughing, shortness of breath, and eye and skin irritation. Ingestion, although unlikely, may cause gastrointestinal disturbance.
Contains: Water, potassium acetate, potassium citrate, organic phosphate esters, pink pigment
- 16 - 10/1/2013 EX257375
Page 19
PFS INSTALLATION, INSPECTION, MAINTENANCE & RECHARGE MANUAL
Perfect Fry Company LLC.
Mailing Address: P.O. Box 501, Concord, NH 03302-0501
Shipping Address: 10 Ferry St., Concord, NH 03301
Tel: 603-225-6684
Fax: 603-225-8472
General Information: [email protected]
Customer Support: [email protected]
Web: www.perfectfry.com
© 2013 PERFECT FRY COMPANY
PRINTED IN USA
L20-361 R2
- 17 - 10/1/2013 EX257375
Loading...