Pentax T87F Installation Manual

Page 1
TRADELINE
T87F
Universal Thermostat
Installation Instructions for the Trained Service Technician.
Application
The T87F Universal Thermostat provides tempera­ture control for 24 to 30 Vac residential heating, cooling or heating-cooling systems. For heating systems, the T87F mounts on the wallplate provided. For cooling only, or heating-cooling, order the 137421A (198170A if textured designer model) Heating-Cooling Wallplate with remote switching, or the Q539 Subbase, which provides switching at the thermostat location.
The spdt switch makes one set of contacts on a tem­perature fall to operate the heating system. The other set of contacts make on a temperature rise to operate the cooling system when the T87F is used to control cool­ing.
Heat anticipation is adjustable, 0.1 to 1.2A.
M3375
Mercury Notice
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube.
If you have questions, call Honeywell Inc. at 1­800-468-1502.
Installation and Setting
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to fol-
low them could cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
1. Disconnect power supply to prevent electri­cal shock or equipment damage.
2. To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase.
3. Do not overtighten thermostat captive mount­ing screws because damage to subbase threads can result.
4. Do not short across coil terminals on relay. This can burn out the thermostat heat antici­pator.
IMPORTANT: An incorrectly leveled thermostat will
cause the temperature control to deviate from set point.
LOCATION
Install the thermostat about 5 ft [1.5m] above the floor in an area with good air circulation at average temperature.
Do not install the thermostat where it may be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
This thermostat is a precision instrument and was carefully adjusted at the factory. Handle it carefully.
MOUNTING WALLPLATE OR SUBBASE (Fig. 2)
IMPORTANT:
1. Use a spirit level to accurately level the wallplate or subbase as in Fig. 1. Inaccurate leveling may cause thermostat control deviation.
2. When using the T87F with a Q539 Subbase, follow the mounting and wiring instructions included with the subbase.
1. Place the wallplate on the wall at the desired loca-
tion. Pull the thermostat cable through the entrance hole.
2. Fasten wallplate. Do not tighten the screws.
3. Level according to Fig. 1 then tighten screws.
4. After wiring wallplate, plug hole to prevent drafts
from affecting thermostat.
NOTE: To mount T87 Thermostat on an outlet box,
order 129044A Adapter Ring Assembly.
®U.S. Registered Trademark Copyright © 2002 Honeywell • • All Rights Reserved
60-0830-4
Page 2
Fig. 1—Leveling wallplate or subbase with spirit level or plumb line.
SPIRIT LEVEL
OPENING FOR THERMOSTAT WIRING
LEVELING POSTS (2)
MOUNTING SLOTS
M3319A
Fig. 2—Mounting wallplate or subbase to wall.
COVER RING
MOLDED LEVELING POST
WALLPLATE SHOWN
THERMOSTAT CABLE ENTRANCE HOLES
NO. 4 X 1 INCH SHEET METAL SCREWS (2)
WIRING
All wiring must comply with local electrical codes and ordinances. Disconnect power supply before con­necting wiring to prevent electrical shock or equipment damage.
The T87F is adaptable to most 2-wire, 24 to 30 volt heating systems, and to most 3-wire, 24 to 30 volt heating systems controlled by a Series 10 Thermostat. The following hookups are typical applications. See Figs. 3 through 7. When using the T87F for cooling control, refer to the hookups in the Q539 Subbase in­structions.
For variations of these systems, refer to the installa­tion instructions for the controlled equipment.
After wiring the wallplate, plug the hole to prevent drafts that may affect the thermostat.
ADD T87F AS SHOWN ON OUTLET BOX MOUNTING
M5324
Fig. 3—T87F used for 2-wire, spst control of heating only in a typical oil system. Low voltage power for the control circuit is supplied by a transformer in the oil primary control.
COMBINATION
L1 (HOT)
FAN AND LIMIT
L2
137421A WALLPLATE
TR
TRTH
CONTROL
BURNER MOTOR
T
T
F
F
IGNITION
R8184G
WHITE
2
ORANGE
BLACK
TRANSFORMER
B
W
R
OIL VALVE
COMBINATION FAN AND LIMIT CONTROL
FAN
LIMIT
JUMPER
B
W
R
FAN MOTOR
3
M6105
1
FAN MOTOR
M5318
TO THERMOSTAT CONNECTIONS ON SERIES 10 VALVE AT BURNER
M6102
1
THERMOSTAT
Y
R
W
CAD CELL
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
R8184 PROTECTORELAY OIL PRIMARY CONTAINS
2
INTERNAL TRANSFORMER.
3
CONNECT OIL VALVE, IF APPLICABLE.
Fig. 4—T87F used for 2-wire, spst control of heating only in a typical gas system.
Y
R
W
GAS VALVE
TH
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 5—T87F replacing a Series 10 Thermostat connected to a 3-wire, open-contact, high-limit control.
LOW LIMIT OPERATING CONTROL
T87F
Y
R
W
SERIES 10 OPEN CIRCUIT HIGH LIMIT
L1 (HOT)
L2
60-0830—4 2
Page 3
Fig. 6—T87F used for Series 20, 3-wire, spdt
control of low-voltage motors and electric
radiator valves. Used in applications where
thermostat makes contact on both a rise and
fall in room temperature.
RED
R
Y
WHITE
R
W
BLUE
137421A WALLPLATE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
TR
W
B
THREE-WIRE SPDT VALVE OR MOTOR
L1 (HOT)
L2
M5319
1
2. Let the system operate for one minute before read-
ing the ammeter.
3. Move the anticipator indicator to match the amme-
ter reading.
A slightly higher setting to obtain longer burner-on times (fewer cycles per hour) may be desirable for some systems.
RECALIBRATION
The T87F is calibrated at the factory and no recali­bration should be necessary. If the thermostat is accu­rately leveled and still appears to be out of calibration, order 104994A Calibration Wrench. Instructions for recalibrat-ing are furnished with the wrench.
Fig. 7—T87F used in cooling-only system.
THERMOSTAT WALLPLATE OR SUBBASE
Y
R
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
1
OVERLOAD PROTECTION AS REQUIRED.
ONLY R AND Y TERMINALS ARE USED FOR COOLING ONLY.
2
2
COOLING CONTACTOR COIL
1
L1 (HOT) L2
M3516
MOUNTING THERMOSTAT TO WALLPLATE OR SUBBASE
To remove standard cover, pull ring outward with
fingertips, pressing lightly on dial with thumbs.
To remove locking cover, loosen the three screws along the cover edge with the Allen wrench supplied. Remove the cover as indicated above.
Remove and discard the plastic insert protecting the mercury switch.
Align the thermostat over the wallplate and tighten the three captive mounting screws. These captive screws complete the electrical connections to the thermostat. Adjust heat anticipator to match current rating of pri­mary control. See Fig. 8.
HEAT ANTICIPATOR SETTING
If the T87F is used for 3-wire, spdt, heating-only (Series 20) control (Fig. 6), set the heat anticipator for
1.2 (far left end of scale). A fixed resistor-type heater is provided in the 137421A or 198170A Wallplate for this application. For other control applications, proceed as follows.
Adjust anticipator to match current rating of primary control. Rating is usually stamped on the control name­plate. Move the indicator to the marking that matches this rating. Indicator may be moved with fingers or pencil point through the hole shown in Fig. 8. If the current rating is not given, proceed as follows before mounting the thermostat:
1. Connect an ac ammeter of appropriate range (0 to
2.0A, for example) between the R and W terminals on the wallplate or subbase.
Fig. 8—Setting heat anticipator current rating.
1.0 .8
.6
.5
.4
.3
SCALE
HOLE SUITABLE FOR PENCIL POINT TO MOVE INDICATOR
.2
.12
.15
LONGER
HEAT ANTICIPATOR INDICATOR
M1368
Checkout
HEATING
Turn down temperature setting to the lowest point. If subbase or remote switching is used, move system switch to HEAT position. Raise temperature setting until heat­ing equipment starts. This point should be at room tem­perature as indicated on the thermometer. Slowly turn back dial. Heating equipment should stop when dial has been turned below room temperature.
COOLING
CAUTION
1. Do not operate cooling if outdoor tempera­ture is below 50° F [10° C]. Refer to manu­facturer recommendations.
2. Allow five-minute off-time after compres­sor has been run to avoid compressor dam­age.
If T87F controls cooling, move system switch (if used) to call for COOL and lower setting until cooling equipment starts. Raise setting above room temperature and cooling system should shut down. Make certain all equipment properly responds to the thermostat.
3 60-0830—4
Page 4
Automation and Control Solutions
HoneywellInternational Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9
60-0830—4 G.H. Rev. 8-02
www.honeywell.com/yourhome
Loading...