The ARC 4100—highly dependable analog recording for up to two process variables.
Utterly
Dependable
and easy
to operate.
he ARC 4100 is a circular chart recorder capable of
T
measuring, recording, and controlling up to two process variables. Its analog design provides protection from
electronic noise interference, making it a highly dependable device. Applications for this instrument are many
and include temperature, relative humidity, pH, level,
electrical measurement, and flow. The ARC 4100 operates with either 115V AC or 230V AC line voltage at 50 or
60Hz; voltage and frequency are selected when ordering.
It accepts a variety of inputs and can be ordered with
RTD, thermocouple, and analog inputs. The process
input for each pen is configured at the factory according
to the range ordered and directly connects to either
thermocouple, RTD, mVDC, VDC, or mADC inputs.
Changes to input type are easily accomplished in the
field simply by changing the range module. Outputs
include On/Off, time proportioning, and 4 to 20mA
with full PID. All recording, controlling, and alarm capabilities/options are selected from the order matrix for
factory implementation.
This recorder incorporates a 10” circular chart. These
charts are available in a wide selection of zero-based,
non-zero based, reverse, and dual-scale ranges. The pens,
disposable fiber-tip types, are quickly and easily replaced.
The ARC 4100 is backed by a one-year warranty as well
as free technical support throughout the life of
the product.
5-02
ARC 4100
1
ARC 4100 SPECIFICATIONS
PROCESS INPUT
Thermocouples: Type J, K, T, R, S
Cold junction compensated with thermocouple break
protection. 8.5mV min. span, 100mV max. span
RTD: 100Ω, 2 or 3 wire
20Ω min. span
200Ω max. span
0.00385Ω/Ω/°C
DC Voltage:
0V DC min., 10V DC max.
1V DC min. span
DC Millivolts:
0mV min., 100mV max.
l0mV min. span
Milliamps:
4 to 20mA
Accommodated with an internal 249Ω jumper-selectable
shunt resistor
Call your distributor for available ranges and charts.
REMOTE SETPOINT INPUT
DC Voltage
0 to 5V DC
1 to 5V DC
Milliamp
0 to 20mA
4 to 20mA
Accommodated with an internal 249Ω jumper selectable
shunt resistor
Potentiometric
Accommodated by three-wire connection
The unit provides +5V DC and ground to the potentiometer
OUTPUTS
Control Output 1 and 2 (each pen)
Relay: SPDT
115V AC: 5.0A Resistive, 1/8HP, 250VA
230V AC: 2.5A Resistive, 1/8HP, 250VA
SSR Driver: Open collector output
Short circuit protected @ 40mA max.
Provides 5V DC at 23mA or 3V DC at 30mA.
Current: 4 to 20mA - 0 to 450Ω grounded load
max. Output span may exceed the stated span,
but shall cover the minimum span of 4 to 20mA
Alarm Output
Relay: SPDT
115V AC: 5.0A Resistive, 1/8HP, 250VA
230V AC: 2.5A Resistive, 1/8HP, 250VA
SSR Driver: Open collector output
Short circuit protected @ 40mA max.
Provides 5V DC @ 23mA or 3V DC @ 30mA.
Control/Alarm Outputs
Output 1: User configurable:
On/Off, Time Proportioning, 4 to 20mA - User selectable
Direct or Reverse Acting, or high limit
Output 2: User configurable:
On/Off Direct or Reverse Acting Control Output
High or Low Process Alarm
High or Low Deviation Alarm
Deviation Band Alarm - Open or Closed within the band
NOTE : Up to two outputs provided for each pen (Pen 1 or 2)
RECORD AND DISPLAY
Chart: 10” circular chart; 100 charts furnished with each
instrument.
Chart Drive: AC synchronous motor
Chart Rotation: Counter-clockwise
Pen Type: Disposable fiber-tip
Pen Color: Pen 1–Red, Pen 2–Green
PERFORMANCE
Measurement Error Limit: All input types: 1.0% of span
Ambient Temperature Error:
Noise Rejection: Normal mode: 65dB min. at 60Hz or greater
Common mode: 85dB min., 24V AC max., 33V DC max.
Line Voltage: Standard 115V AC +/- 10%, 50 or 60Hz
Optional: 230V AC +/-l0%, 50 or 60Hz—Soldered jumper
configurable to 115V AC
Power Consumption: 25VA max.
Operating Temperature: 32° F to 131°F , 0°C to 55°C
Storage Temperature: -40°F to 149°F, -40°C to 65°C
Humidity: 0 to 90% RH non-condensing
Dimensions: 13.19” H x 15.13” W x 3.63” D
Weight: 20 pounds max.
Vibration: 0.5 to 100Hz @ 0.2g
Sensor Fault Detection: Jumper selectable for upscale or downscale
sensor break. Only downscale break is available for milliamp
inputs due to the use of a low ohm shunt resistor.
Agency Approvals: UL Spec. - 1092 File #E67237 Listed
CSA Spec. - C22.2 File #LR39885
0.04% of span per °C deviation from 25°C
2
ARC 4100 Benefits:
A variety of input capabilities—RTD,
thermocouple, mADC, VDC, and mVDC
provide flexibility
Many output choices—On/Off, time proportioning, and 4 to 20mA with full PID for many output
options
Front access thumbwheel—easily changes the
setpoint
Analog design—provides protection from electronic noise
interference
Structural foam enclosure—suitable for panel mounting or
surface mounting
Remote setpoint input capability—change the setpoint without
needing to be in the vicinity of the device
Variety of charts for your particular recording needs—
zero based, non-zero based, reverse, and dual-scale range
Alarm outputs available for each pen—safety shut-off and
over- or under-temperature alarms
5-02