Partlow 1160+, 1800+, 1400+
Temperature & Process Controllers
Jumperless Configuration
Auto Detected Hardware
Process & Loop Alarms
Modbus & ASCII Comms
Auto or Manual Tuning
Heat/Cool Operation
Ramping Setpoint
Remote/Dual Setpoint Options
Available in 1/16, 1/8 & 1/4 DIN Formats
With their improved interface, technical functionality and field flexibility, the Partlow 1160+, 1800+ and 1400+ give
you the best in comprehensive control for most temperature and process control loops.
Specification
Features
Control Types Full PID with Pre-tune, Self-tune, manual tuning, or On-Off control. Heat only or heat & cool
Auto/Manual
Output Configuration Up to 3 possible, for control, alarm, 24VDC transmitter power supply or retransmit of process value or
Alarm 1 & 2 Types Process high, process low, SP deviation, band, logical OR / AND. Also 1 loop alarm for process control
Human Interface 4 button operation, dual 4 digit 10mm & 8mm high (6100+, 8100+) and 13mm & 10mm high (4100+)
PC Configuration Off-line configuration from PC serial port to dedicated config socket (comms option not required).
Input
Thermocouple J, K, C, R, S, T, B, L, N & PtRh20%vsPtRh40%.
RTD 3 Wire PT100, 50Ω per lead maximum (balanced)
DC Linear 0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V.
Impedance >10MΩ for Thermocouple and mV ranges, 47KΩ for V ranges and 5Ω for mA ranges
Accuracy ±0.1% of input range ±1 LSD (T/C CJC better than 1°C)
Sampling 4 per second, 14 bit resolution approximately
Sensor Break Detection <2 seconds (except zero based DC ranges), control O/P’s turn off, high alarms activate for T/C and mV
Outputs & Operations
Control & Alarm Relays Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations
Control SSR Driver Outputs
Triac Outputs 0.01 to 1 Amp AC, 20 to 280Vrms, 47 to 63Hz
DC Linear Outputs 0 to 20mA, 4 to 20mA into 500Ω max, 0 to 10V, 2 to 10V, 0 to 5V into 500Ω min.
Transmitter Power Supply Output 24VDC (nominal) into 910Ω minimum to power external devices
Communications 2 Wire RS485, 1200 to 19200 Baud, Modbus and ASCII protocol (selectable)
Selectable from front panel or via digital input, with bumpless transfer
setpoint
security. Process alarms have adjustable hysteresis.
LED displays, optional choice of colours (Red/Red, Red/Green, Green/Red or Green/Green), plus 5 LED
indicators
Configuration Software for Windows 98 or higher. West Part Number: PS1-CON
Scaleable -1999 to 9999, with adjustable decimal point
ranges, low alarms activate for RTD, mA or V ranges
Drive capability >10V DC in 500 minimum
Control outputs have 2% over/under drive applied. Accuracy ±0.25% at 250Ω (degrades linearly to 0.5%
for increasing burden to specified limits)
Ref DS-Px100-1209-1-EN
© West Control Solutions 2009

Digital Input Selects between 2 setpoints or Auto/Manual control. Volt free or TTL input
Remote Setpoint Input 0 to 20mA, 4 to 20mA, 0 to 5V, 1 to 5V, 0 to 10V or 2 to 10V. Scaleable -1999 to 9999. Local/Remote
Operating & Environmental
Temperature & RH
Power Supply
Front Panel Protection
Standards
Dimensions
1160+
setpoint selected from front panel
0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing
100 to 240V 50/60Hz 7.5VA (optional 20 to 48V AC 7.5VA/22 to 65V DC 5 watts)
IEC IP66 (Behind panel protection is IP20)
CE, UL & ULC recognised
10mm (approx.)
110mm 48mm
x 45mm
+0.5 –0.0
48mm
1800+
48mm
100mm
10mm
rox)
96mm
1400+
96mm
100mm
Cut out
92mm +0.5
96mm
10mm
Approx
92mm +0.5
Ref DS-Px100-1209-1-EN
© West Control Solutions 2009

Wiring Connections
1160+
1800+/1400+
Field Reconfiguration
Input
Jumper-free configuration for any type
(no extra parts required)
Option Slot 1
Relay Output ........................... PO1-C10
Linear mA/V DC Output .......... PO1-C21
SSR Driver Output .................. PO1-C50
Triac Output ............................ PO1-C80
Option Slot 2 Part Number
Relay Output ........................... PO2-C10
Linear mA/V DC Output .......... PO2-C21
SSR Driver Output .................. PO2-C50
Triac Output ............................ PO2-C80
Option Slot 3 Part Number
Relay Output ........................... PO2-C10
Linear mA/V DC Output .......... PO2-C21
SSR Driver Output .................. PO2-C50
24VDC Transmitter PSU ........ PO2-W08
Option Slot A Part Number
Digital Input ............................ PA1-W03
Remote Setpoint Input ........... PA1-W04
RS485 Comms ...................... PA1-W06
Field Reconfiguration
Input
Jumper-free configuration for any type
(no extra parts required)
Option Slot 1
Relay Output ........................... PO1-C10
Linear mA/V DC Output .......... PO1-C21
SSR Driver Output .................. PO1-C50
Triac Output ............................ PO1-C80
Option Slot 2 Part Number
Relay Output ........................... PO2-C10
Linear mA/V DC Output .......... PO2-C21
SSR Driver Output .................. PO2-C50
Triac Output ............................ PO2-C80
Option Slot 3 Part Number
Relay Output ........................... PO2-C10
Linear mA/V DC Output .......... PO2-C21
SSR Driver Output .................. PO2-C50
24VDC Transmitter PSU ....... PO2-W08
Option Slot A Part Number
Digital Input ............................. PA1-W03
Remote Setpoint Input ............ PA1-W04
RS485 Comms ....................... PA1-W06
Option Slot bB Part Number
Full Remote Setpoint input .... PB1-W0R
Ref DS-Px100-1209-1-EN
© West Control Solutions 2009

Order Code
MODEL
1/16 DIN Controller
1/8 Din Controller
¼ DIN Controller
OPTION SLOT 1
No Output 0
Relay 1
SSR Driver 2
Linear DC 3
Triac 8
OPTION SLOT 2
No Output 0
Relay 1
SSR Driver 2
Linear DC 3
Triac 8
OPTION SLOT 3
No Output 0
Relay 1
SSR Driver 2
Linear DC 3
Transmitter power Supply 4
OPTION SLOT A / DISPLAY COLOR
No Option A Red Upper/Red Lower 0
RS485 Serial Comms Red Upper/Red Lower 1
No option A Green Upper/Red Lower 2
RS485 Comms Green Upper/Red Lower 3
No Option A Red Upper/Green Lower 4
RS485 Comms Red Upper/Green Lower 5
No Option A Green Upper/Green Lower 6
RS485 Comms Green Upper/Green Lower 7
Digital input Red Upper/Red Lower 8
Digital input Green Upper/Red Lower 9
Digital input Red Upper/Green Lower A
Digital input Green Upper/Green Lower B
Basic Remote Setpoint Red Upper/Red Lower C
Basic Remote Setpoint Green Upper/Red Lower D
Basic Remote Setpoint Red Upper/Green Lower E
Basic Remote Setpoint Green Upper/Green Lower F
VOLTAGE
100-240 VAC 0 0
24-48V AC/DC 0 2
Options below are for 1/8 and ¼ DIN controllers only
Remote Setpoint (full with digital input) R R
24-48V AC/DC & Remote Setpoint (full with digital input) R 2
P
1 1 6 0
1 8 0 0
1 4 0 0
Austria T:+43 (0)2236 691 121 AT@West-CS.com
China T:+86 22 8398 8098 CN@West-CS.com
France T:+33 (1) 77 80 90 42 FR@West-CS.com
Germany T:+49 (0)561 505 1307 DE@West-CD.com
United Kingdom T:+44 (0)1273 606271 UK@West-CS.com
USA T:+1 800 866-6659 NA@West-CS.com
Email Enquiries@West-CD.com
Website www.West-CS.com
For more details on the complete product range from West
Control Solutions please contact your local distributor or
visit www.West-CS.com
Ref DS-Px100-1209-1-EN
© West Control Solutions 2009