Partlow 1160+, 1800+, 1400+
Temperature & Process Controllers
Jumperless Configuration
Auto Detected Hardware
Process & Loop Alarms
Modbus & ASCII Comms
Auto or Manual Tuning
Heat/Cool Operation
Ramping Setpoint
Remote/Dual Setpoint Options
Available in 1/16, 1/8 & 1/4 DIN Formats
With their improved interface, technical functionality and field flexibility, the Partlow 1160+, 1800+ and 1400+ give
you the best in comprehensive control for most temperature and process control loops.
Specification
Features
Control Types Full PID with Pre-tune, Self-tune, manual tuning, or On-Off control. Heat only or heat & cool
Auto/Manual
Output Configuration Up to 3 possible, for control, alarm, 24VDC transmitter power supply or retransmit of process value or
Alarm 1 & 2 Types Process high, process low, SP deviation, band, logical OR / AND. Also 1 loop alarm for process control
Human Interface 4 button operation, dual 4 digit 10mm & 8mm high (6100+, 8100+) and 13mm & 10mm high (4100+)
PC Configuration Off-line configuration from PC serial port to dedicated config socket (comms option not required).
Input
Thermocouple J, K, C, R, S, T, B, L, N & PtRh20%vsPtRh40%.
RTD 3 Wire PT100, 50Ω per lead maximum (balanced)
DC Linear 0 to 20mA, 4 to 20mA, 0 to 50mV, 10 to 50mV, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V.
Impedance >10MΩ for Thermocouple and mV ranges, 47KΩ for V ranges and 5Ω for mA ranges
Accuracy ±0.1% of input range ±1 LSD (T/C CJC better than 1°C)
Sampling 4 per second, 14 bit resolution approximately
Sensor Break Detection <2 seconds (except zero based DC ranges), control O/P’s turn off, high alarms activate for T/C and mV
Outputs & Operations
Control & Alarm Relays Contacts SPDT 2 Amp resistive at 240V AC, >500,000 operations
Control SSR Driver Outputs
Triac Outputs 0.01 to 1 Amp AC, 20 to 280Vrms, 47 to 63Hz
DC Linear Outputs 0 to 20mA, 4 to 20mA into 500Ω max, 0 to 10V, 2 to 10V, 0 to 5V into 500Ω min.
Transmitter Power Supply Output 24VDC (nominal) into 910Ω minimum to power external devices
Communications 2 Wire RS485, 1200 to 19200 Baud, Modbus and ASCII protocol (selectable)
Selectable from front panel or via digital input, with bumpless transfer
setpoint
security. Process alarms have adjustable hysteresis.
LED displays, optional choice of colours (Red/Red, Red/Green, Green/Red or Green/Green), plus 5 LED
indicators
Configuration Software for Windows 98 or higher. West Part Number: PS1-CON
Scaleable -1999 to 9999, with adjustable decimal point
ranges, low alarms activate for RTD, mA or V ranges
Drive capability >10V DC in 500 minimum
Control outputs have 2% over/under drive applied. Accuracy ±0.25% at 250Ω (degrades linearly to 0.5%
for increasing burden to specified limits)
Ref DS-Px100-1209-1-EN
© West Control Solutions 2009
Digital Input Selects between 2 setpoints or Auto/Manual control. Volt free or TTL input
Remote Setpoint Input 0 to 20mA, 4 to 20mA, 0 to 5V, 1 to 5V, 0 to 10V or 2 to 10V. Scaleable -1999 to 9999. Local/Remote
Operating & Environmental
Temperature & RH
Power Supply
Front Panel Protection
Standards
Dimensions
1160+
setpoint selected from front panel
0 to 55°C (-20 to 80°C storage), 20% to 95% RH non-condensing
100 to 240V 50/60Hz 7.5VA (optional 20 to 48V AC 7.5VA/22 to 65V DC 5 watts)
IEC IP66 (Behind panel protection is IP20)
CE, UL & ULC recognised
10mm (approx.)
110mm 48mm
x 45mm
+0.5 –0.0
48mm
1800+
48mm
100mm
10mm
rox)
96mm
1400+
96mm
100mm
Cut out
92mm +0.5
96mm
10mm
Approx
92mm +0.5
Ref DS-Px100-1209-1-EN