Panasonic WHADC1216G6E5UK Operating Instructions

Air-to-Water Hydromodule + Tank
Model No.
Indoor Unit
WH-ADC1216G6E5UK
Outdoor Unit
WH-UX09FE5 WH-UX12FE5 WH-UD12FE5 WH-UD16FE5
Operating Instructions Air-to-Water Hydromodule + Tank
Installation Instructions attached. Serial number and production year please refer to name plate.
English
Manufactured by: Panasonic Appliances Air-Conditioning Malaysia Sdn. Bhd. Lot 2, Persiaran Tengku Ampuan, Section 21, Shah Alam Industrial Site, 40300 Shah Alam, Selangor Darul Ehsan, Malaysia.
F569845
Thank you for purchasing Panasonic product.
Before operating the system, read these operating instructions thoroughly and keep them for future reference.
Table of contents
Safety precautions ………………………………………… 3-5 To adjust initial settings …………………………………… 6-7 How to use ……………………………………………… 8-11 Cleaning instructions ……………………………………… 12 Troubleshooting …………………………………………13-14 Information ………………………………………………… 15
The illustrations in this manual are for explanation purposes only and may differ from the actual unit. They are subject to change without notice for future improvement.
System overview
Open and Close Top Front Plate
Do not open or close the Top Front Plate by excessive force.
To Open: To Close:
Top Front Plate
open
“click”
Before use, make sure the system has been installed correctly by an authorised dealer according to the given instructions.
Panasonic Air-to-Water is a split system, consisting of two units: indoor and outdoor units. The indoor unit consist of the hydromodule and 200L sanitary water tank.
• These operating instructions describe how to operate the system using the indoor and outdoor units.
• As for the operation of other products such as radiator, external thermo controller, and underfloor units, refer to the operating instructions of each product.
• System could be locked to operate in HEAT mode and disable COOL mode.
• Some functions described in this manual may not be applicable to your system.
• Consult your nearest authorised dealer for further information.
1
*
The system is locked to operate without COOL mode.
It can be unlocked only by authorised installers or our authorised service partners. *2 Only displayed when COOL mode is unlocked (Means when COOL mode is available).
Bottom Front Plate
“click”
Control panel
“click”
Hold in position
Note:
Not recommended to open the Bottom Front Plate. (For authorised dealer/ specialist use only)
Operating conditions
HEATING
(TANK)
Water outlet temperature (°C)
(Min. / Max.)
Outdoor ambient temperature (°C)
(Min. / Max.)
* Above 55 °C, only possible with backup heater operation.
- / 65* 25 / 55 5 / 20
2
close
Power Supply Radiator
HEATING
(CIRCUIT)
-20 / 35 16 / 43
COOLING (CIRCUIT)
Floor HeatingOutdoor Unit
Fan Coil Unit
Indoor Unit
When the outdoor temperature is out of the range in the table, the heating capacity will drop significantly and the outdoor unit may stop operating for its protection. The unit will restart automatically after the outdoor temperature returns to the specified range.
Shower
Safety precautions
To prevent personal injury, injury to others or property damage, please comply with the following: Incorrect operation due to failure to follow instructions below may cause harm or damage, the seriousness of which is classified as below:
This sign warns of
WARNING
death or serious injury.
This sign warns of
CAUTION
injury or damage to property.
The instructions to be followed are classified by the following symbols:
This symbol denotes an action that is PROHIBITED.
These symbols denote actions COMPULSORY.
WARNING
Indoor unit and outdoor unit
This appliance may be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Please consult an authorised dealer or specialist to clean the internal parts, repair, install, remove and reinstall the unit. Improper installation and handling will cause leakage, electric shock or fire.
Safety precautions
Confirm with an authorised dealer or specialist on usage of any specified refrigerant type. Using refrigerant type other than the specified may cause product damage, burst and injury etc.
When open the Top Front Plate, make sure it is securely hold in position. Else it may fall and cause injury.
English
3
Safety precautions
Do not install the unit in a potentially explosive or flammable atmosphere. Failure to do so could result in fire.
Do not insert your fingers or other objects into the indoor or outdoor unit; the rotating parts may cause injury.
Do not touch the outdoor unit during lightning, it may cause an electric shock.
Do not sit or step on the unit, you may fall down accidentally.
Do not install the indoor unit outdoors. This is designed for indoor installation only.
Power supply
Do not use a modified cord, joint cord, extension cord or unspecified cord to prevent overheating and fire.
To prevent overheating, fire or electric shock:
• Do not share the same power outlet with other equipment.
• Do not operate with wet hands.
• Do not bend or twist power supply cord.
If the supply cord is damaged, it must be replaced by the manufacturer, service agent or similarly qualified persons in order to avoid a hazard.
This unit is equipped with Residual Current Circuit Breaker/Earth Leakage Circuit Breaker (RCCB/ELCB). Ask an authorised dealer to check RCCB/ELCB operation regularly, especially after installation, inspection, and maintenance. RCCB/ELCB malfunction may result in electric shock and/or fire.
It is strongly recommended that Install Residual Current Device (RCD) on-site to prevent electric shock and/or fire.
Before obtaining access to terminals, all supply circuits must be disconnected.
Stop using the product if any abnormality/failure occurs and disconnect the power supply. (Risk of smoke/fire/electric shock) Examples of abnormality/failure
• RCCB/ELCB trips frequently.
• Burning smell is observed.
• Abnormal noise or vibration of the unit is observed.
• Hot water leaks from the indoor unit.
Contact your local dealer immediately for maintenance/ repair.
Wear gloves during inspection and maintenance.
4
This equipment must be earthed to prevent electrical shock or fire.
Prevent electric shock by disconnecting the power supply
- Before cleaning or servicing.
- When extended non-use. This appliance is for multiple
uses. To avoid electric shock, burn and/or fatal injury, make sure to disconnect all power supplies before accessing any terminal in the indoor unit.
Prevent water leakage by ensuring that the drainage pipe is connected properly.
After a long period of use, make sure the installation rack is not deteriorated. The deteriorated rack may cause the unit to fall down.
Ask an authorised dealer to determine the level of sterilisation function field settings according to the local laws and regulations.
CAUTION
Indoor unit and outdoor unit
Do not wash the indoor unit with water, benzine, thinner or scouring powder to avoid damage or corrosion on the unit.
Do not install the unit close to any combustibles or at bathroom. Otherwise, it may cause electric shock and/or fire.
Do not touch the water discharge pipe of the indoor unit during operation.
Do not place any material on the unit or under it.
Do not touch the sharp aluminium fin; sharp parts may cause injury.
Do not use the system during sterilisation in order to prevent scalding with hot water, or overheating of shower.
Control panel
Do not wet the control panel. Failure to do so may result in electric shock and/or fire.
Do not press the buttons on the control panel using hard and sharp objects. Failure to do so may cause damage to the unit.
Do not wash the control panel using water, benzine, thinner or scouring powder.
Do not inspect or maintain the control panel by yourself. Consult an authorised dealer in order to prevent personal injury caused by incorrect operation.
Safety precautions
English
5
To adjust initial settings
Dealer
Select menus and determine settings according to the system available in the household. It is recommended that all alterations of settings are done by an authorised dealer or specialist.
• After initial installation, you may manually adjust the settings. The initial setting remains active until the user changes it.
• Ensure the operation LED is OFF before setting.
• The system may not work properly if set wrongly. Please consult an authorised dealer.
1
Press and simultaneously and hold for
5 seconds until the display shows SETTING STATUS.
2
Press
3
Press to enter the menu.
4
Press or to select Yes/No, or other options.
YES: to enable the menu No: to disable the menu
5
Press to confirm.
or to select the menu.
DisplayOperation LED
Control Panel
Before Indoor Unit operate, its Capacity Rank has to match with connected Outdoor Unit. See below table for detail.
Indoor Unit Outdoor Unit
Model
WH-ADC1216G6E5UK
WH-UX09FE5 9 WH-UX12FE5 12 WH-UD12FE5 12 WH-UD16FE5 16
Capacity Rank
Menu (1 ~ 15)
Room Thermostat Connection
1
To select whether or not to connect to the optional room thermostat.
Indoor Backup Heater Selection
2
To reduce the heater power if unnecessary. *Options of kW vary depending on the model.
Water System Freeze Prevention
3
To activate or deactivate the water freeze prevention when the system is OFF.
1, *2
*
Cooling/Heating Operation Interval
4
To set the interval for COOL or HEAT mode during COOL + TANK or HEAT + TANK mode.
1
*
Tank Heat-up Interval
5
To set the interval for the water tank during COOL + TANK or HEAT + TANK mode.
6
System Capacity Rank Setting
The Capacity Rank can be set by Control Panel
1
Press and buttons simultaneously for 5
seconds.
2
Press
3
Press button then press or button
4
Press button and Exit to home display.
or button to select menu CAP RAN.
to change capacity rank and press button to confirm the outdoor capacity rank.
Default
Setting Display
Setting
NO YES NO
9 kW
YES YES NO
30 minutes
1 hour
35 minutes
*3 kW / 6 kW /
9 kW
0.5 hours ~ 10 hours
5 minutes ~
1 hour 35 minutes
Dealer
Operation/settings to be done only by the authorised dealer/specialist.
User
Operation/settings to be done by the authorised dealer/specialist or user.
Backup Heater For Tank
6
To activate backup heater during tank operation.
YES YES NO
• Do not use the system during sterilisation in order to prevent scalding with hot water, or overheating of shower.
• Ask an authorised dealer to determine the level of sterilisation function field settings according to the local laws and regulations.
Sterilisation
7
To sterilise the water tank, if required.
YES YES NO
Note: If NO is selected, menus 8 to 10 are skipped.
Sterilisation Day & Time
8
To set timer for sterilisation. (Only once a week. Operates even under a standby condition)
Sterilisation Temperature
9
To set the temperature of sterilisation.
Continuation of Sterilisation
10
To maintain heating temperature in order to complete the sterilisation.
Base Pan Heater
11
To select whether or not to connect to the optional base pan heater.
Monday
12:00
65 °C 40 °C ~ 65 °C
10 minutes
NO YES NO
Monday ~
Sunday
0:00 ~ 23:50
5 minutes ~
1 hour
Note: If NO is selected, menu 12 is skipped.
Base Pan Heater type
12
Type A - The base pan heater activates only during deice
operation.
AAB
Type B - The base pan heater activates when outdoor ambient
temperature is 5 °C or lower.
1, *2
*
Cool Outdoor Temperature setting
13
To set the outdoor ambient temperature for the AUTO mode to
15 °C 5 °C ~ 25 °C
change from HEAT to COOL.
1, *2
*
Heat Outdoor Temperature setting
14
To set the outdoor ambient temperature for the AUTO mode to
10 °C 5 °C ~ 25 °C
change from COOL to HEAT.
Dry Concrete
15
During construction to dry the concrete under a preset temperature. Do not use this menu for any other purposes and in period other
- 1 day ~ 99 days
than during construction (Refer to Information page).
To adjust initial settings
User
Control panel preparation
1
Press .
2
Press
3
Press
4
Repeat steps
or to set the current day.
to confirm.
2
3
to set the current time.
and
■ Note:
• The current day and time need to be set in cases below:
- When the power is turned on for the first time.
- A long time has elapsed since the power was turned on the last time.
• The current time that has been set will be the standard time for all the timer operations.
Caution Indicator (Tank Temperature above 60 °C)
*1 The system is locked to operate without COOL mode. It can be unlocked only by authorised installers or our authorised service partners.
2
*
Only displayed when COOL mode is unlocked (Means when COOL mode is available).
English
7
How to use
User
Turn on or off the system
Press .
When the system is ON, the operation LED is lit and the actual water outlet temperature and outdoor ambient temperature are shown on the display.
User
Select operation mode
Press to select operation mode.
AUTO • Depending on the preset outdoor
AUTO + TANK
HEAT • The outdoor unit provides heat to the
HEAT + TANK
TANK • The outdoor unit provides heat to the
1, *2
COOL
*
+ TANK
1, *2
*
User
temperature, the system selects HEAT or *1 COOL operation mode.
• Depending on the preset outdoor temperature, the system selects HEAT + TANK or *1 COOL + TANK operation mode.
indoor unit.
• The outdoor unit provides heat to the sanitary water tank and indoor unit.
sanitary water tank.
• The outdoor unit provides cooling to the indoor unit and heating to the sanitary water tank.
COOL
• The panel is either turned ON or OFF.
• The outdoor unit provides cooling to the indoor unit.
Initiate the backup heater
Press .
• The backup heater provides extra heat at low outdoor temperature. The backup heater is possible only in the heat mode.
• Once the backup heater is set, it is automatically operated when conditions are fulfilled.
• To disable the backup heater, press
again.
The system is turned off by an external switch.
User
Enjoy quiet operation
Press .
• This operation reduces the noise of outdoor unit. The operation may cause heating/ decrease.
User
*1 cooling ability to
System status check mode
Press
1
(The display shows STATUS.)
Press or to check the selected mode.
2
• Dry concrete (does not show during normal
• The Water Inlet Temperature
• Tank Temperature
• Compressor Running Frequency
• Error History
• Heat mode total power consumption (Up to 999 days)
• *1 Cool mode total power consumption (Up to 999 days)
• Tank mode total power consumption (Up to 999 days)
• Press to exit the STATUS mode.
.
operation)
■ Note:
• Once the STATUS mode is entered, the display shows STATUS.
• The STATUS mode cannot be activated when the display shows SETTING.
• The total power consumption is an estimated value based on AC 230 V and may differ from value measured by precise equipment.
■ Note: In normal operation, the , and buttons are not in use.
8
Dealer
Operation/settings to be done only by the authorised dealer/specialist.
User
Operation/settings to be done by the authorised dealer/specialist or user.
Dealer
System temperature setting
The system controls the temperature for each menu based on the outdoor ambient temperature.
• To set or change the temperatures, make sure to contact your nearest authorised dealer.
1
Press and hold for 5 seconds to enter the
temperature range setting mode.
(The display shows SETTING.)
2
Press
3
Press to enter the menu.
4
Press or to set the desired temperature.
5
Press
or to select a menu.
to confirm the setting.
• Repeat steps 2 to 5 to set other menus.
User
Checking the temperature range
1
Press and hold
2
Press
• Press
to exit.
Menu
Setting of low outdoor ambient temperature. -5 °C -15 °C ~ 15 °C
for 5 seconds to enter the temperature range setting mode.
or to select a menu.
Default setting
Temperature setting
Temperature setting Display
Display
How to use
Setting of high outdoor ambient temperature. 15 °C -15 °C ~ 15 °C Setting of water outlet temperature at low outdoor
ambient temperature. Setting of water outlet temperature at high outdoor
ambient temperature. During HEAT mode, the water
outlet temperature is adjusted as is shown the diagram on the right. It is performed within the preset
<Water outlet temperature>
55 °C 25 °C ~ 55 °C 35 °C 25 °C ~ 55 °C
max. water temp.
HEAT
min. water temp.
temperature range.
<Outdoor ambient temperature>
Setting of outdoor ambient temperature to turn OFF heating operation during HEAT mode.
Setting of outdoor ambient temperature to turn ON the backup heater.
Setting of water outlet temperature during
*1 COOL
mode. Setting of sanitary water tank temperature. 52 °C 40 °C ~ 65 °C
*1 The system is locked to operate without COOL mode. It can be unlocked only by authorised installers or our authorised service partners.
2
*
Only displayed when COOL mode is unlocked (Means when COOL mode is available).
24 °C 5 °C ~ 35 °C
0 °C -15 °C ~ 20 °C
10 °C 5 °C ~ 20 °C
HEAT
HEATER
1, *2
*
COOL
TANK
English
9
How to use
User
Shifting the water temperature
This easily shifts the water outlet temperature if the setting is undesirable.
1
Press
2
Press
3
Press
<Water outlet temperature>
4
Press to confirm the setting.
■ Note:
• Press or wait for 30 seconds to exit the SETTING mode.
• The set temperature will be saved in the system once confirmed.
• The SETTING mode cannot be activated when the SERVICE and STATUS indicators are ON.
• The system will shift the temperature within water outlet temperature range.
to enter the water temperature shifting mode.
to change setting.
or to set the desired temperature.
(temperature range: -5 °C ~ 5 °C)
Temperature setting
+5
Shift value
-5
<Outdoor ambient temperature>
Desired temperature setting
User
Holiday mode
• By setting the day (s) in holiday mode, it promotes energy saving while you are on holiday, and enables the system to resume at the preset temperature after your holiday.
• Ensure that the system is OFF before setting.
• The system will resume operation automatically at 00:00 am after the holiday.
• The day the HOLIDAY mode was set is counted as day 1.
Example: Setting the holiday mode on June 21, 08:00 am. By setting 3 days, the system resumes operation on June 24, 00:00 am.
1
Press
2
Press
(Setting range: 1 day ~ 999 days)
3
Press to confirm the setting.
to enter the HOLIDAY mode.
or to set the desired days.
■ Note:
• Press or wait 30 seconds to exit the HOLIDAY mode.
10
Desired days
Dealer
Operation/settings to be done only by the authorised dealer/specialist.
User
Operation/settings to be done by the authorised dealer/specialist or user.
User
Weekly timer setting
Promotes energy saving by allowing you to set up to 6 programmes in any given day.
Lights up if Timer operation is selected
ON Timer
OFF Timer
1
Press
2
Press
3
Press to confirm your selection.
4
“1” will be blinking, press
programme 1.
5
Press
6
Press or to select your desired time.
You can set , , and the Water Temperature Thermo Shift setting.
7
Press
day will be highlighted with .
• After 2 seconds, the display will move to the next programme. Repeat steps 4 to 7 to set programmes 2 to 6.
• During timer setup, if no button is pressed within 30 seconds, or if the
that moment is confirmed and timer setup is ended.
Indicates the next timer operation programme
Programme number in a day
Indicates the next timer operation day
Day to be selected
to enter the timer setting mode.
or to select your desired day.
to set
to select ON or OFF timer.
to confirm programme 1. The selected
is pressed, the setting at
To check current timer programme
1
Press to enter timer mode and press
to enter day setting.
2
3
Press
Press
or until your desired day is shown,
press
to confirm your selection.
or to check the set programmes.
To modify current timer programme or add new timer programme
1
Perform steps 1 to 7 of “Weekly timer setting” to modify existing timer programme, or add any timer programme.
To cancel current timer programme
1
Press to enter day.
2
Press
3
Press
or until your desired day is shown,
press to enter programme setting.
or until your desired programme is
shown.
Press disappear.
to cancel the programme and will
To disable/enable Weekly Timer
To disable weekly timer setting, press , then
press .
To enable previous weekly timer setting, press ,
then press .
How to use
English
■ Note:
• You may set the timer for each day of the week (Monday to Sunday) with 6 programmes per day.
• When the system is switched on by the timer, it will use the previously set temperature to control the water outlet temperature.
• The same timer programme cannot be set on the same day.
• You may also select 2 or more days with the same timer setting.
11
Cleaning instructions
To ensure optimal performance of the system, cleaning has to be carried out at regular intervals. Consult an authorised dealer.
Disconnect the power supply before cleaning.
• Do not use benzine, thinner or scouring powder.
• Use only soap (
• Do not use water hotter than 40 °C.
pH7) or neutral household detergent.
Indoor unit
• Do not splash water directly.
Wipe the unit gently with a soft dry cloth.
Anode Bar
Sanitary Water Tank
Water Filter Set
Water pressure gauge
• Do not press or hit the glass cover using hard and sharp objects. Failure to do so may cause damage to the unit.
• Ensure that the water pressure is between 0.05 and 0.3 MPa (0.1 MPa = 1 bar).
• In case the water pressure is out of the above range, consult an authorised dealer.
Outdoor unit
• Do not obstruct the air inlet and outlet vents. Failure to do so may result in low performance or system breakdown. Remove any obstruction to assure the ventilation.
• When it snows, clean and remove snow around the outdoor unit to prevent the air inlet and outlet vents from being covered with snow.
Non serviceable criteria
Disconnect the power supply
then please consult an authorised dealer under the following conditions:
• Abnormal noise during operation.
• Water/foreign particles have entered the control panel.
• Water leaks from the indoor unit.
• Circuit breaker switches off frequently.
• Power cord becomes unnaturally warm.
For extended non-use
• The water inside the Sanitary Water Tank should be drained.
• Disconnect the power supply.
MAINTENANCE
User
• In order to ensure optimal performance of the units, user may inspect and clear any obstruction on the air inlet and outlet vents of the outdoor unit.
Dealer
• In order to ensure safety and optimal performance of the units, seasonal inspections on the units, functional check of RCCB/ELCB, field wiring and piping have to be carried out at regular intervals by authorised dealer.
• Specific to the Sanitary Water Tank, it is important to service the Water Filter Set periodically and inspect the Anode Bar annually. The Anode Bar which protects the tank body will corrode, depending on water quality. When diameter is approximate 8mm, the Anode must be replaced.
• Users should not try to service or replace parts of the unit.
• Contact authorised dealer for scheduled inspection.
12
Troubleshooting
The following symptoms do not indicate malfunction.
Symptom Cause
Water flowing sound during operation. • Refrigerant flow inside the unit. Operation is delayed a few minutes
after restarting. Outdoor unit emits water/steam. • Condensation or evaporation occurring in the pipes. Steam comes out of the outdoor unit in
the heating mode. Outdoor unit does not operate. • It is caused by the protection control of the system when outdoor temperature is
System operation switches off. • It is caused by the protection control of the system. When the water inlet
System is hard to heat up. • When the panel and the floor are heated simultaneously, warm water temperature
System does not heat up instantly. • System will take some time to heat up the water if it starts to operate at cold water Backup heater is automatically turned
ON when it is disabled. Operation starts automatically when the
timer is not set. Display power consumption remains
as previous value. HEAT indicator blinks on the display. • System is performing deice operation.
Loud refrigerant noise continue for a few minutes.
*1 Cool mode is unavailable. • System has locked to operate in HEAT mode only.
• The delay is a protection for the compressor.
• It is caused by defrost operation in the heat exchanger.
out of the operating range. temperature is lower than 10 °C, the compressor stops and the backup heater
power turns on. may decrease, which may reduce the heating ability of the system.
• When the outdoor air temperature is low, the system may need longer time to heat up.
• Discharge outlet or intake inlet in the outdoor unit is blocked by some obstacle, such as a pile of snow.
• When the preset water outlet temperature is low, the system may need longer time to heat up.
temperature.
• It is caused by the protection control of the indoor unit heat exchanger.
• Sterilisation timer has been set.
• Memory is saved on hourly basis. If a power failure occurs, the data kept from last hour will be displayed.
• Total power consumption has reached 999 days. Press
• It is caused by protection control during deice operation at outdoor ambient temperature lower than -10°C.
to reset the counter.
Cleaning instructions / Troubleshooting
Check the following before calling for servicing.
Symptom Check
Operation in HEAT/ not working efficiently.
Noisy during operation. • Outdoor unit or indoor unit has been installed at an incline.
System does not work. • Circuit breaker has tripped/activated. Operation LED is not lit or nothing is
displayed on the control panel.
Force Heater Mode Button
*1 The system is locked to operate without COOL mode. It can be unlocked only by authorised installers or our authorised service partners.
2
*
Only displayed when COOL mode is unlocked (Means when COOL mode is available).
*1 COOL mode is
• If a malfunction occurs in the system, the backup heater may be used to heat up the water. Press to switch on the backup heater.
• Press
• In the Force Heater mode, no other operation can be used.
• This feature is only available to certain error codes.
• Refer to dealer for more details.
to switch off the backup heater.
• Set the temperature correctly.
• Close the panel heater/cooler valve.
• Clear any obstruction in the air inlet and air outlet vents of the outdoor unit.
• Close the front plate properly.
• Check that the power supply is working correctly, or that a power failure has not occurred.
English
13
Troubleshooting
The operation LED blinks and error code appears on the display.
• Disconnect the power supply, and report the error code to an authorised dealer.
• The timer operation will be cancelled when an error code is displayed.
Diagnostic display
H12 H15
H20 H23 H27 H42 H62 H63 H64 H65
H70 H72
H76 H90 H91
H95 H98 H99
Abnormality or Protection control works
Capacity mismatch, Capacity rank not set
Abnormal compressor temperature sensor
Abnormal water pump Abnormal refrigerant 1 sensor Abnormal service valve Compressor low pressure protection Abnormal water flow Abnormal low pressure sensor Abnormal high pressure sensor Abnormal deice water circulation Abnormal back-up heater overload
protector Abnormal tank temperature sensor Control panel communication error Abnormal indoor / outdoor
communication Abnormal tank heater overload protector Abnormal voltage connection Outdoor high pressure protection Indoor heat exchanger freeze prevention
Diagnostic display
F12 F14 F15 F16
F20 F22
F23 F24 F25 F27 F30
F36 F37
F40 F41
F42 F43
F45 F46
F48 F49
F95
Abnormality or Protection control works
Pressure switch activated Poor compressor rotation Abnormal outdoor fan motor lock Comprehensive current protection Compressor temperature overload
protection Transistor module temperature overload
protection DC peak abnormal of operation Abnormal Refrigerant cycle Abnormal in a Abnormal pressure switch Abnormal water outlet sensor 2 Abnormal outdoor air temperature
sensor Abnormal water inlet sensor Abnormal outdoor discharge sensor Abnormal power factor correction Abnormal outdoor heat exchanger
sensor Abnormal outdoor defrost sensor Abnormal water outlet sensor Abnormalities in outdoor current
transformer disconnection Abnormal evaporator outlet temperature
sensor Abnormal bypass outlet temperature
sensor Abnormal
*1 cooling / heating charge
*1 cooling high pressure
*1 The system is locked to operate without COOL mode. It can be unlocked only by authorised installers or our authorised service partners.
2
*
Only displayed when COOL mode is unlocked (Means when COOL mode is available).
14
Information
Information for Users on Collection and Disposal of Old Equipment
These symbols on the products, packaging, and/or accompanying documents mean that used electrical and electronic products should not be mixed with general household waste. For proper treatment, recovery and recycling of old products, please take them to applicable collection points, in accordance with your national legislation and the Directives 2002/96/EC and 2006/66/EC. By disposing of these products correctly, you will help to save valuable resources and prevent any potential negative effects on human health and the environment which could otherwise arise from inappropriate waste handling. For more information about collection and recycling of old products, please contact your local municipality, your waste disposal service or the point of sale where you purchased the items. Penalties may be applicable for incorrect disposal of this waste, in accordance with national legislation.
For business users in the European Union
If you wish to discard electrical and electronic equipment, please contact your dealer or supplier for further information.
[Information on Disposal in other Countries outside the European Union]
These symbols are only valid in the European Union. If you wish to discard these items, please contact your local authorities or dealer and ask for the correct method of disposal.
Operation/settings to be done only by the authorised dealer/specialist.
Dry Concrete Function
• During construction to dry the concrete under a preset temperature. 1
Press
2
Press
3
Press
Press
4
Press to confirm the selection.
5
Repeat step 3 and 4 to set other days and temperature.
and simultaneously and hold for 5 seconds until the display shows “ ”.
.
(The display shows “ ”).
to select day.
or to set the desired temperature.
Troubleshooting / Information
• Press to exit.
To Reset the Control Panel to Default Setting
1
Press , , continuously for 5 seconds. The
operation is off during this period.
2
The display shows “
seconds for confirmation. After 2 seconds, it goes to normal display.
, , ” for 2
English
15
Country Telephone Number
UK/England +44 (0) 134 485 3393 UK/Ireland +353 (0) 872 696 043
Panasonic Corporation
Website: http://www.panasonic.com
© Panasonic Corporation 2015
Printed in Malaysia
Authorised representative in EU Panasonic T esting Centre Panasonic Marketing Europe GmbH Winsbergring 15, 22525 Hamburg, Germany
F569845
SS0415-0
Loading...