Flexible Wire-Saving System
S-LINK V
USER’S MANUAL
|
|
|
WUME-SLINKV-9 |
9th Edition |
|
|
|
|
2020.9 panasonic.net/id/pidsx/global
2
Contents
Before Using This System··························5
Introduction·············································· 6
Warnings················································ 6 Instructions for Safe Use···························· 7 Ambient conditions······························· 7
Instructions for Use································ 8
Instructions for Designing······················· 8 Fail-safe function·································· 8 Conformity to EC Directives···················· 8 Use with S-LINK system························ 8 Instructions for Installation·························· 9 Hook-up cable connectors······················ 9 Wiring················································ 9 Others··············································· 9 Instructions for Disposal····························· 9
Designing / Installation Procedures·············· 10
MEMO··················································12
Chapter 1··············································· 13
Designing System··································· 13
System Configuration······························· 14 Outline of Design····································· 16
Selection of Controller or Control board········16 I/O Control Points····································16 Transmission Distance·····························16 Outputting Error Signals····························17 Connection of End Unit·····························18 Selection of Control Cable and Connector
Link Cable··············································18 Control cable selection method:
(For use of SL-VCU1 only)···················18 Connector link cable selection method: (For use of SL-VCU1 only)··························18
Making of Branch Lines Using Cable Connectors············································19
Power Supply Capacity of System··············· 20
Calculation of Total Current Consumption Value ···············································20
Example: Calculation of current consumption···················································22 Calculation of Voltage Drop Value···············23 Rated voltage (V)································23 Necessity of Local Power Supply Unit··········24 Designing of system using local power supply method·········································24
Connection of DC 2-Wire Output Device to Input Unit······················································· 26
Example: Connection of DC 2-wire sensor27
Transmission Delay Time··························· 28
Response delay time···························28 Operation at power-on··························30 Error signal outputting delay time············30 System setting time·····························31
Selection of Output Holding Function for Output Unit······················································· 32
Output holding function setting method····32
Address Setting······································· 33
Setting of PLC I/O connector numbers·····33 Setting of I/O unit addresses··················33 Example: Address setting······················34
Chapter 2··············································· 35
Wiring···················································· 35
Flowchart··············································· 36 Basic Procedures····································· 37
Connector hook-up work·······················37
Cutting of exclusive 4-core flat cable·······37
How to use exclusive hook-up pliers (SLJPS, SL-JPC, SL-JPE) ························38
Hook-up of Connector······························39 Hook-up method of SL-JK connector for cable end and SL-JK1 connector for ‘T’- branch ·············································39
Hook-up method of SL-J1A connector for ‘T’ - branch and SL-J3A connector for cable
extension············································41 Hook-up method of SL-CP1, SL-CP2, and SLCP3 snap male connectors and SL-CJ1 and SL-CJ2 snap female connectors···················44
Connection to Terminal Block·····················46 Extension of Main / Branch Line Cable·········47
Extension of exclusive 4-core flat cables··47 Extension of cable excluding exclusive 4-core flat cables·································47
Extension of cable to I/O device·············47 Installation·············································48 Installation of each unit·························48
Construction··········································· 50
Power Supply·····································50 Power supply to system························50 Connection of Each Unit···························51 Connection of controller························51 Connection of bus direct-connection type controller and control board···················52 Connection of PLC I/O Connector···········53 Connection of I/O unit··························55 Connection of I/O device·······················56 Connection of main line cable to end unit·57 Connection of local power supply unit ·····58
Local power supply to system················58 Installation method of batteries···············59 MEMO··················································60
Chapter 3··············································· 61
Starting System······································ 61
Flowchart··············································· 62 Wiring Check·········································· 64
Check before Starting··························64 Check of wiring conditions of controller
and control board································64 Check of PLC I/O connectors·················65 Check of cable for short-circuit···············65
Starting·················································· 66
Power-on (Main Power and Local Power)·66 CONFIG mode···································66 Check of Recognized Addresses················70 CHECK mode·····································70
3
Chapter 4··············································· 71
Specifications········································· 71
Specifications·········································· 72
Common Specifications····························72
Address setting switches······················72 Specifications of Each Unit························75
Controller··········································75 Bus direct-connection type controller for FP2 / FP2SH Series···································79 Bus direct-connection type controller for FP7 Series···············································83 Mitsubishi MELSEC-Q Series PLC bus di- rect-connection type controller···············87 Control board·····································91 Control module···································95 PLC I/O connector·······························97 I/O unit············································ 100 Input terminal··································· 103 Output terminal································· 107 Connector input unit··························· 111 Connector output unit························· 115 MIL connector input unit······················ 119 MIL connector output unit···················· 122 Analogue input unit···························· 125 Analogue output unit·························· 131 Relay output terminal························· 136 Input module···································· 139 Output module·································· 141 Picking switch··································· 143 Picking switch for shutter···················· 146 Address setting remote controller········· 149 End unit·········································· 151 Handy monitor·································· 153 Cable·············································· 157 Hook-up connector···························· 157 List of programmable logic controllers (PLC) (upper models)································· 159
List of Models·········································160
Controller········································ 161 Control board··································· 161 Control module································· 161 List of I/O units································· 162 List of connectors······························ 163 Handy monitor·································· 163 Address setting remote controller········· 163 Others············································ 164
Chapter 5··············································165
Troubleshooting·····································165
Troubleshooting······································166
Flowchart for taking corrective action for detected error······································ 166 Flowchart for power supply condition check· 169
How to identify error unit after error detection 171
How to extinguish error indicator·········· 172 Utilization of output holding function······ 172
Appendix···············································173
Appendix···············································174
List of error numbers·························· 174 Flowchart for error detection················ 175
Selection of connector link cable·········· 176 Setting of connector numbers,············· 180 addresses, and number of I/O control points· 180 Glossary·········································· 181
FAX Sheet for Asking Question··················183
MEMO················································ 184
4
5
<![endif]>Before Using This System
The S-LINK V is a flexible wire-saving that uses our original transmission system to enable high-speed and highly reliable signal transmissions.
Fully understand the functions and performance of this system before constructing this system.
This manual provides information necessary for construction of the S-LINK V flexible wire-saving system. Before constructing the S-LINK V system, carefully read this manual and fully understand the system.
In addition, be sure to observe the cautions, and correctly use the system. The controllers listed below have their own user’s manuals.
For a detailed description, refer to that documentation.
SL-VGU1-C, SL-VGU1-D : SL-VGU1-C / SL-VGU1-D User’s Manual
SL-VGU1-EC |
: SL-VGU1-EC User’s Manual |
SL-VGU1-485 |
: SL-VGU1-485 User’s Manual |
SL-VMEL-Q |
:SL-VMEL-Q User’s Manual |
SL-VFP7 |
:SL-VFP7 User’s Manual |
For other controllers, refer to the instruction manuals enclosed with the controllers.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
This manual uses three types of warnings depending on the hazard level. They are ‘DANGER,’ ‘WARNING,’ and ‘CAUTION.’ To safely use the S-LINK V system, be sure to observe these warnings.
DANGER
‘DANGER’ indicates that mishandling of this system may result in death or serious injury, and this word is limitedly used in the extremely hazardous situations.
WARNING
‘WARNING’ indicates that mishandling of this system may result in death or serious injury.
CAUTION
‘CAUTION’ indicates that mishandling of this system may result in injury or damage of the system.
NOTE |
‘NOTE’ provides caution or information to you in order to prevent operation errors. |
Remarks
1)Panasonic Industrial Devices SUNX Co., Ltd. holds the copyright of this document. For this reason, do not copy this document without our permission.
2)The contents of this document may be subject to change without prior notice for the reasons of improvement.
3)The product specifications shown in this document were determined in September 2020.
6
Introduction
WARNING
The S-LINK V system does not have any control functions, such as accident preventive function and safety function. For this reason, do not use the S-LINK V system if malfunction of the system may affect human lives or assets.
Even if this system is not used as an accident preventive system or safety system, if this system is used for a nuclear power control system, railroad facility, aviation facility, vehicle, combustion system, medical equipment, or the like, be sure to design a system having enough capacity, and adopt safety measures for the system, such as a fail-safe function. In addition, please contact our sales division.
Do not use this system at the following places:
Place where the ambient temperature is out of the specified range of 0 to +55°C (Note 1)
Notes:
1) The optimum ambient temperature depends on the product type. For this reason, check
the specifications of this prod-
uct shown in Chapter 4.
2) If this product is incorporated in the control box together with the other unit, the unit may generate heat to change the ambient temperature. In this case, install a cooling fan so that the ambient temperature cannot exceed the rated upper limit temperature.
Place where the ambient humidity is out of the specified range of 35 to 85% RH (Note)
Note
The optimum ambient humidity depends on the product type. For this reason, check the specifications of this product shown in Chapter 4.
Steamy or dusty place or place near water, oil, or chemical source
Place where direct sunlight may enter
COR- FLAMROSIVE MABLE GAS GAS
Place where the ambient temperature extremely varies and dew condensation may be caused.
Place where there is a corrosive or flammable gas
Place where vibration or shock of more than the specified level may be directly applied to the system main body
Closed place
However, if a ventilation hole or a fan is installed, such a place can be used.
<![endif]>System This Using Before
7
Instructions for Use
<![endif]>Before Using This System
Instructions for Designing
CAUTION
Disconnection of a signal line, instantaneous power failure, or abnormal signal may cause a problem. For this reason, please adopt a fail-safe function for the entire system by yourself.
To ensure safety, be sure to incorporate the interlock circuit, limit circuit, or the like, in the external circuit excluding the S-LINK V system circuit.
To incorporate the S-LINK V system in your equipment, be sure to adopt a fail-safe function.
Regarding the fail-safe function, if you have an unclear or doubtful point, please contact our sales division.
WARNING
●●Each unit of the S-LINK V series conforms to various standards. However, to incorporate a unit in the system, check that entire system can conform to various standards.
●●The lightning surge preventive function is not adopted for the I/O module (SL-VM□ / VMP□). To conform to the requirements of EN 61000-6-2, incorporate the following circuit in your board.
+ |
+24V DC |
|
|
Power supply |
|
– |
0V |
|
Surge absorber
Recommended part: ERZV05D390 manufactured by Panasonic Corporation (Note)
Note: If a different part is used, a resistor may be needed between the power supply unit and the surge absorber. Check whether a resistor is needed.
●●If it is not necessary for the relay output terminal (SL-VTPR4/8) to conform to the EC Directives, use of 250V AC, 3A is possible.
To conform to the EC Directives, the S-LINK V system is tested in accordance with the EMC Directive standards, such as EN 61000-6-4 of the EMI standard and EN 61000-6-2 of the EMS standard. When you incorporate the S-LINK V system in your machine or equipment, check that the wiring condition conforms to the requirements of the EC Directives.
To use the SL-VGU1-C together with the PLC (programmable logic controller) manufactured by Mitsubishi Electric Corporation and to conform to the requirements of the EMC Directive, install the system in accordance with the PLC User’s Manual prepared by Mitsubishi, and be sure to observe the following items:
●●Be sure to put the PLC and the SL-VGU1-C in a conductive box.
●●Be sure to ground the shielded cable that connects the PLC to the SL-VGU1-C in the 300mm area of the SL-VGU1-C.
●●If the shielding effect is not enough, install a ferrite core.
The S-LINK V system cannot be used together with the S-LINK system. Use with a system may cause abnormal operation or damage. Separately construct the S-LINK V system and the S-LINK system.
However, if gateway controllers are used as the child station of the open network (CC-Link, DeviceNet, RS-485 / RS-232C, EtherCAT), 2 systems can be used together on the same network.
Not good |
|
|
|
|
|
|
|
|
|
|
|
Good |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
gateway |
|
|
|
|
gateway |
|
|
|
|
|
|
gateway |
|
|
|
|
|||||||||||||||
|
S-LINK V |
|
|
|
|
|
|
|
|
|
|
|
S-LINK V |
|
|
|
|
|
|
S-LINK |
|
|
|
|
|||||||
|
controller |
|
|
|
|
|
|
|
|
|
|
|
controller |
|
|
|
|
|
|
controller |
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S-LINK V |
|
S-LINK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
S-LINK V |
|
S-LINK V |
|
|
S-LINK |
|
S-LINK |
||||||||||||||||||
|
|
|
unit |
|
unit |
|
|
|
|
|
|
|
|||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
unit |
|
unit |
|
|
unit |
|
unit |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
8
Instruction for Use
CAUTION
●●Select a power supply unit equipped with the short-circuit protective function (fuse, etc.).
●●The power of the S-LINK V system passes through the inside of each unit and is then supplied to the main cable or I/O device side. However, the short-circuit protective function is not adopted for this power supply circuit. For this reason, adopt a short-circuit protective function, such as a fuse, for the power supply circuit.
●●Take care that wrong wiring will damage the product.
●●Before starting the following works, be sure to turn off the power of the PLC (programmable logic controller), personal computer main body, S-LINK V units, and also turn off the power supply unit of the I/O device.
•Machine assembly (installation)
•Removal or reinstallation of a S-LINK V unit or connection of I/O device
•Cable connection
•Address setting / change
●●Before handling this product, remove any electrostatic charge that may be present on your body. There is a danger of this product getting damaged due to the electrostatic charge.
Hook-up cable connectors
To hook-up an exclusive cable connector, use the exclusive tool, and correctly hook-up the connector by following the procedure specified in this manual.
If a connector is not correctly hooked-up, the S-LINK V system will not operate. In addition, observe the following items:
●●After checking the cable type and the purpose, select the right type of connector. ●●Before hook-up a connector, be sure to check the colors of cables to be connected.
●●Use the exclusive hook-up pliers (SL-JPS, SL-JPC or SL-JPE) to hook-up the connectors. For the hook-up procedure of each connector, refer to pages 37 to 45.
●●If a connector is once hooked-up, do not reuse the connector. The performance of such a connector may be deteriorated.
Wiring
Observe the following items to distribute cables:
●●Keep cables away from the power line and the high-voltage line. ●●Do not completely fold down any cables.
●●Do not pull any cables with a strong force. ●●Do not apply any weight to any cable.
●●Do not touch a cable to any other system cables.
This is because signals of different systems may interfere with each other. ●●Do not bend cables many times.
●●Wind insulation tape on the end of each cable, if necessary.
Others
●●Apply the specified torque to tighten terminal screws of each unit. ●●Check the connectors for looseness.
●●Do not disassemble or modify this product.
<![endif]>System This Using Before
●●Request a waste disposal company to dispose of this product.
9
<![endif]>Before Using This System
Chapter 1 Designing System
●●Determine the system design.
●●Determine the necessary number of I/O points for the I/O device.
●●Determine the cable length necessary for transmission.
●●Select the transmission speed. |
|
●●Set the address. |
How long? |
●●Calculate the power supply capacity of the system. |
|
●●Determine the connection method for the input de- |
|
vice of DC 2-wire output type. |
|
●●Determine the transmission delay time. ●●Set the output holding function.
Chapter 2 Wiring
●●This chapter describes the wiring methods to be used for actual installation.
●●Caution regarding cutting of exclusive 4-core flat cable
●●Connector hook-up method ●●Cable extension method ●●Connection to I/O device
●●Connection of local power supply unit
●●Connection to terminal block
Local power supply unit
AC
F.G.
Insulated
Chapter 3 Starting System
●●Check the system before starting.
●●Check the cable for short-circuit. ●●Check the system before starting. ●●Caution regarding power-on
●●Description of CONFIG mode ●●Description of CHECK mode
D |
|
|
(White) |
G |
Analogue tester |
|
(Black) |
+24V (Brown) 0V (Blue) |
Transmission cable |
|
10
Designing / Installation Procedures
Chapter 4 Specifications
●●Select S-LINK V units optimum for the purpose of your system.
●●S-LINK V control units ●●S-LINK V input units ●●S-LINK V output units ●●Hook-up connector
●●Exclusive 4-core flat cable
Chapter 5 Troubleshooting
●●This chapter describes how to solve the problem if the S-LINK V system does not operate properly.
●●Troubleshooting after error indication ●●Power supply check procedure
●●How to extinguish the error indicators
Appendix
●●List of error numbers
●●Flowchart for error detection
●●Selection of connector link cable for PLC ●●Fax sheet for asking questions
This manual is prepared for the designer and the installer of the S-LINK V system. The following items are common to both the designer and the installer:
●●Before Using This System
●●‘Chapter 4 Specifications’
●●‘Chapter 5 Troubleshooting’ ●●Appendix
In addition, the designer should refer to ‘Chapter 1 Designing System,’ and the installer should refer to ‘Chapter 2 Wiring’ and ‘Chapter 3 Starting System.’
<![endif]>System This Using Before
11
<![endif]>Before Using This System
12
Chapter 1
Designing System
13
Example of system configuration
An example of the S-LINK V system is shown below. For the specifications of each unit, refer to Chapter 4.
Controller
SL-VCU1
Control board
S-LINK V control board |
S-LINK V control board |
for PCI bus |
for VME bus |
SL-VPCI |
SL-VVMES2 |
<![endif]>Chapter 1
Power supply unit
24V DC –+105 %
Bus direct-connection type S-LINK V controller for FP2 / FP2SH series
SL-VFP2
Bus direct-connection type S-LINK V
controller for FP7 series
SL-VFP7
Bus direct-connection type S-LINK V controller for MELSEC-Q series PLC manufactured by Mitsubishi Electric Corp.
SL-VMEL-Q
Gateway controller (Note)
S-LINK V gateway
controller for CC-Link
SL-VGU1-C
S-LINK V gateway
controller for DeviceNet
SL-VGU1-D
S-LINK V gateway controller for RS-485
/ RS-232C
SL-VGU1-485
S-LINK V gateway
controller for EtherCAT
SL-VGU1-EC
S-LINK V control module
SL-VMC1
4-channel connector |
e-CON type 4-channel |
16-channel MIL |
connector |
||
output unit |
connector output unit |
output unit |
SL-VTP4J |
SL-VTP4E |
SL-VTP16C1(-S) |
8-channel connector |
e-CON type 8-channel |
Analog output unit |
output unit |
connector output unit |
|
SL-VTP8J |
SL-VTP8E |
SL-VTDA1 |
4-channel output terminal |
16-channel output terminal |
|
SL-VTBP4 |
8-channel output terminal |
SL-VTBP16 |
|
SL-VTBP8 |
32-channel output terminal |
|
|
SL-VTBP32 |
Local power supply unit
Note: For a detailed description of the following controllers, refer to their respective user’s manuals.
SL-VGU1-C, SL-VGU1-D : SL-VGU1-C / SL-VGU1-D User’s Manual
SL-VGU1-EC |
: SL-VGU1-EC User’s Manual |
SL-VGU1-485 |
: SL-VGU1-485 User’s Manual |
SL-VMEL-Q |
: SL-VMEL-Q User’s Manual |
SL-VFP7 |
: SL-VFP7 User’s Manual |
14
|
|
System Configuration |
||
|
|
|
|
|
|
|
|
|
|
I/O module |
|
|
|
|
|
|
|
|
|
Input module |
Output module |
|
|
|
|
|
|
||
SL-VM8 / VM16 |
SL-VMP8 / VMP16 |
For flexible wire-saving system |
Cables and hook-up connectors
Hook-up connectors
4 |
3 |
2 |
|
|
|
1 |
SL-CP3
Flat cables are available so that 'T' - branch can be easily formed
by using hook-up connectors.
There are various types of hook-up connectors that enable easy connection of cables.
Picking switch |
Handy monitor |
SL-VPK01 SL-VPK02 SL-VHM1
1-channel input unit |
1-channel output unit |
|
|
SL-VCH10 |
SL-VCH11 |
8-channel connector |
e-CON type 4-channel |
2-channel input unit |
2-channel output unit |
input unit SL-VT8J |
connector input unit |
SL-VCH20 |
SL-VCH22 |
|
SL-VT4E |
2-channel I/O mixed unit
SL-VCH21
Analog input unit
SL-VTAD1
8-channel relay output
4-channel relay output terminal SL-VTPR8 terminal SL-VTPR4
16-channel MIL connector input unit
SL-VT16C1
16-channel input terminal
SL-VTB16
32-channel input terminal
SL-VTB32
End unit
SL-VEU
<![endif]>1 Chapter
15
<![endif]>Chapter 1
Select a S-LINK V controller or a S-LINK V control board optimum for the upper machines (PLC, PC, PCI bus computer, VME bus computer, open network).
The system needs the following I/O control points. Design the system considering these points.
●●Each controller or control board can control up to 256 nodes (number of I/O units connected to the system) and 512 points (512 points × 2 for the SL-VVMES2). To control more than 512 points (512 points × 2 for the SL-VVMES2) of I/O device, connect two or more controllers as the other systems.
●●To cope with various PLC connection types of various manufacturers, we can provide 8 types of PLC input connectors and 7 types of PLC output connectors. For a detailed description, refer to pages 159 and 160. Each PLC I/O connector has 32 points for any model.
Each system needs one controller or one control board.
NOTE Two or more controllers or control boards cannot be connected to one system.
The above described number of I/O control points (512 points or 512 points × 2 for the SL-VVMES2) and the number of nodes (256 nodes) are the maximum values.
This means that these values depend on the total cable length and the conditions of the connected machine (total current consumption, voltage drop, etc.).
For a detailed description, refer to pages 16 to 25.
The following two types of cables can be used for the S-LINK V system.
●●Exclusive 4-core flat cable (recommended cable)
●●4-core VCTF cable (0.3 to 2.0mm2, non-shielded) commercially available
Note: The VCTF cable is the vinyl cabtyre cable that conforms to the requirements of JIS C 3306 ‘Polyvinyl chloride insulated flexible cords.’
To wire the S-LINK V system, use 4-core cables so that the wire system can consist of 2 power supply lines (+24V, 0V) and 2 signal transmission lines (D, G).
The cable length depends on the total cable length and the transmission distance.
: S-LINK V I/O unit
B (Branch line) |
C (Branch line) |
D (Branch line) |
Control area |
A (Main line) |
Total cable length = A + B + C + D
Transmission distance = A
16
Outline of Design
|
|
|
|
|
|
|
|
|
|
|
●●The main line is the longest route distributed from the controller or control board. |
|
|
NOTE |
|
|
|
●●The branch lines are the routes branched from the main line. |
|
|
|
|
|
|
|
|
|
The total cable length should satisfy the conditions shown in the following table:
Transmission mode |
Total cable length (m) |
A |
100 |
B |
400 |
C |
1,600 |
The maximum transmission distance (between D and G) is as follows:
●●Mode A: 50m
The maximum length is 50m regardless of the cable conductor cross section (0.3 to 2.0mm2) and the number of nodes (1 to 256 nodes).
●●Mode B
Conductor cross
section
(mm2)
0.3
0.5
0.75
1.25
2.0
Number of nodes and maximum transmission length (m)
Up to 224 nodes |
Up to 256 nodes |
|
180 |
200 (full specification for mode B)
●●Mode C
Conductor |
|
|
Number of nodes and maximum transmission length (m) |
|
|
|||||
cross |
Up to 32 |
Up to 64 |
Up to 96 |
|
Up to 128 |
Up to 160 |
|
Up to 192 |
Up to 224 |
Up to 256 |
section |
|
|
||||||||
nodes |
nodes |
nodes |
|
nodes |
nodes |
|
nodes |
nodes |
nodes |
|
(mm2) |
|
|
||||||||
0.3 |
570 |
440 |
350 |
|
300 |
260 |
|
220 |
200 |
180 |
0.5 |
|
710 |
580 |
|
490 |
420 |
|
370 |
330 |
300 |
0.75 |
|
|
|
|
780 |
670 |
|
590 |
530 |
480 |
1.25 |
|
|
|
800 (full specification for mode C) |
|
|
|
|||
2.0 |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
<![endif]>1 Chapter
●●Voltage drop between +24V and 0V is not considered. For this reason, calculate this volt- NOTE age drop value, and use a local power supply unit, etc. to prevent voltage drop.
For a detailed description, refer to page 23.
●●The conductor cross section of the exclusive 4-core flat cable SL-RCM□ is 0.5mm2.
●●Wire the S-LINK V system while observing the communication distance specifications described above. In addition, use the cables that satisfy the specifications described above.
●●To select applicable cables, refer to the section describing cables. For a detailed description, refer to page 157.
●●The picking switch SL-VPK0□ cannot be used in mode A (transmission mode).
If the controller is equipped with the error signal output function, the controller can output an error signal after detection of an error.
To output an error signal, the S-LINK V system will be turned on properly. If an error occurs, the NPN output transistor will be turned off.
For each type of error, you can select whether the error signal should be output. For the Troubleshooting, refer to page 165.
For the error, refer to page 166.
17
Outline of Design
<![endif]>Chapter 1
CAUTION
Each system needs at least 1 SL-VEU end unit. If the SL-VEU unit is not connected, the system may not operate properly.
If the cable lengths are the same, connect the end unit to the line having fewer nodes (units).
Be sure to connect 1 SL-VEU end unit to the end of the main line.
If the branch line length exceeds 80% of the maximum transmission distance, connect 1 SL-VEU unit to the end of the branch line, too.
Up to 2 SL-VEU end units can be connected for 1 system.
<If the branch line length is equal to the main line length>
Same length (Note 1)
SL-VEU
Connect the end unit to the line having fewer nodes.
<If the branch line length is 80% of the main line length or more>
Main line
SL-VEU
Maximum transmission distance
Connect the end unit to the main line and branch line, respectively.
80% of the main line length or more
Notes: 1) The maximum transmission distance depends on the cable conductor cross section and the number of nodes. For the maximum transmission distance, refer to page 17.
2)Even if the cable lengths are the same, if both the main and branch line lengths exceed 80% of the maximum transmission distance, connect two SL-VEU end units.
Check the distance from the SL-VCU1 to the PLC I/O connector, and then select the applicable control cable: SL-VC1000 (1m long) or SL-VC2000 (2m long).
One control cable is needed for every 8 PLC I/O connectors.
The PLC I/O connector installation direction (vertical) and layout depend on the PLC manufacturers.
Check the connection distance of the PLC I/O connector, and then select the applicable connector link cable: SL-VF70 (70mm), SL-VF150 (150mm), or SL-VF250 (250mm).
For a detailed description, refer to page 176.
18
Outline of Design
Branch lines can be made by using connectors and terminal blocks.
In addition, for this product, cables or connectors that are commercially available can be used.
CAUTION
The exclusive hook-up connectors can connect the exclusive 4-core flat cables only.
|
Exclusive 4-core flat cable |
4-core VCTF cable commercially available (non-shielded) (Note) |
|
|
Making of ‘T’ - branch line using exclusive hook-up |
|
|
|
connector |
|
|
|
SL-J1A…1 |
|
|
|
Extension using exclusive hook-up connector |
Intermediate connector commercially available or |
|
Exclusive 4-core flat cable |
SL-J3A…2 |
||
intermediate terminal block commercially available |
|||
|
Connection of branch line using exclusive hook-up |
||
|
|
||
|
connector |
|
|
|
SL-JK1 and SL-CP3…3 |
|
|
|
SL-JK and SL-CP3…4 |
|
|
4-core VCTF cable |
Intermediate connector commercially available…5 |
Intermediate connector commercially available or |
|
commercially available |
intermediate terminal block commercially available |
||
Intermediate terminal block commercially available…6 |
|||
(non-shielded) (Note) |
Note: Use the same diameter cable. |
||
|
Note: The VCTF cord is the vinyl cabtyre cord that conforms to the requirements of JIS C 3306 ‘Polyvinyl chloride insulated flexible cords.’
SL-VCU1
|
SL-J1A |
|
|
1 |
|
6 |
|
|
Intermediate connector |
|
|
|
Intermediate terminal block |
|
Intermediate connector |
SL-CP3 |
3 |
5 |
|
|
SL-CP3 |
4 |
SL-JK1 |
|
|
|
|
|
SL-JK |
SL-J1A
1 |
SL-J3A
2 |
SL-VEU
<![endif]>1 Chapter
19
This section describes how to calculate the total current consumption value and voltage drop value in order to determine the power supply capacity (capacity of 24V DC power supply unit).
<![endif]>Chapter 1
Calculation of Total Current Consumption Value
To determine the total current consumption, check the current consumption of each I/O unit.
Calculate the power supply capacity while referring to the list of current consumption values shown below.
Designation |
Model No. |
Current consumption (mA) |
Controller |
SL-VCU1 |
135 |
Bus direct-connection S-LINK V controller for FP2 / FP2SH series |
SL-VFP2 |
60 |
Bus direct-connection S-LINK V controller for FP7 series |
SL-VFP7 |
80 |
Mitsubishi MELSEC-Q PLC bus direct-connection S-LINK V controller |
SL-VMEL-Q |
70 |
Control board for PCI bus |
SL-VPCI |
85 |
Control board for VME bus |
SL-VVMES2 |
88 (Note 1) |
Control module |
SL-VMC1 |
60 |
Gateway controller for CC-Link |
SL-VGU1-C |
300 |
Gateway controller for DeviceNet |
SL-VGU1-D |
300 |
Gateway controller for RS-485 / RS-232C |
SL-VGU1-485 |
300 |
Gateway controller for EtherCAT |
SL-VGU1-EC |
300 |
Input connector for PLC |
SL-VS□ |
30 |
Output connector for PLC |
SL-VP□ |
73 |
End unit |
SL-VEU |
10 |
1-channel input unit |
SL-VCH10 |
20 |
2-channel input unit |
SL-VCH20 |
28 |
2-channel I/O mixed unit |
SL-VCH21 |
24 |
1-channel output unit |
SL-VCH11 |
16 |
2-channel output unit |
SL-VCH22 |
20 |
4-channel connector input unit |
SL-VT4J, SL-VT4E |
70 (Note 2) |
8-channel connector input unit |
SL-VT8J, SL-VT8E |
105 (Note 2) |
16-channel MIL connector input unit |
SL-VT16C1 |
80 (Note 2) |
Analogue input unit |
SL-VTAD1 |
80 |
8-channel input module |
SL-VM8 |
18 |
16-channel input module |
SL-VM16 |
20 (Note 2) |
4-channel connector output unit |
SL-VTP4J, SL-VTP4E |
60 (Note 2) |
8-channel connector output unit |
SL-VTP8J, SL-VTP8E |
90 (Note 2) |
16-channel MIL connector output unit |
SL-VTP16C1(-S) |
50 (Note 2) |
Analogue output unit |
SL-VTDA1 |
90 |
8-channel output module |
SL-VMP8 |
60 |
16-channel output module |
SL-VMP16 |
95 (Note 2) |
4-channel relay output terminal |
SL-VTPR4 |
90 (Note 2, 3) |
8-channel relay output terminal |
SL-VTPR8 |
150 (Note 2, 3) |
Picking switch |
SL-VPK01 |
25 |
Picking switch for shutter |
SL-VPK02 |
25 (when shutter operation: 450) |
Handy monitor |
SL-VHM1 |
500 |
20
Power Supply Capacity of System
|
|
|
|
|
|
|
|
|
|
Designation |
Model No. |
Current consumption (mA) |
||
Unit side |
I/O side (Note 4) |
|||
|
|
|||
4-channel input terminal |
SL-VTB4 |
25 |
45 |
|
8-channel input terminal |
SL-VTB8 |
30 |
75 |
|
16-channel input terminal |
SL-VTB16 |
35 |
150 |
|
32-channel input terminal |
SL-VTB32 |
45 |
300 |
|
4-channel output terminal |
SL-VTBP4 |
25 |
40 |
|
8-channel output terminal |
SL-VTBP8 |
30 |
60 |
|
16-channel output terminal |
SL-VTBP16 |
40 |
100 |
|
32-channel output terminal |
SL-VTBP32 |
45 |
180 |
Notes: 1) SL-VVMES2, the value for 1 port is shown in the above table.
2)Regarding the SL-VTPR□, SL-VT□J, SL-VT□E, SL-VT□16C1(-S), and SL-VM□16, if the ambient temperature is not in the specified range, turning on of all the points may not be possible.
For a detailed description, refer to the specifications of each product shown in Specifications.
3)The SL-VTPR□ limits the output current depending on the ambient operation temperature and the number of ON points.
For the characteristics of the product when using PhotoMOS relay, refer to the ‘Panasonic Industrial Devices SUNX website: https://panasonic.net/id/pidsx/global .’
4)The value shown in the ‘Unit side’ area indicates the current consumption in the main circuit. The value shown in the ‘I/O side’ area indicates the current consumption in the I/O circuit.
The values shown in the above table does not include the current supplied to the PLC mod- NOTE ule and current consumption of sensors and loads.
In addition to the above units, when additional units (products) are connected, such as the 3-line sensor and output load, to the same 24V DC power supply unit, add the current consumption values of the additional units to the power supply capacity value.
<![endif]>1 Chapter
21
Power Supply Capacity of System
<System configuration for control of 8 sensors and 4 output loads>
Input connector for PLC
SL-VS1
Output connector for PLC |
8-channel input terminal |
SL-VP1 |
SL-VTB8 |
Controller |
Sensors |
SL-VCU1 |
Power supply unit
<![endif]>Chapter 1
|
Sensors |
|
End unit |
|
|
|
SL-VEU |
||
|
|
|
Output loads |
|
8-channel connector input unit |
|
|
|
|
SL-VT8J |
4-channel connector output unit |
|||
|
||||
|
|
SL-VTP4J |
|
|
Designation |
Model No. |
Qty |
Current consumption (mA) |
|
Controller |
SL-VCU1 |
1 |
135 |
|
End unit |
SL-VEU |
1 |
10 |
|
Input connector for PLC |
SL-VS1 |
1 |
30 |
|
Output connector for PLC |
SL-VP1 |
1 |
73 |
|
8-channel connector input unit |
SL-VT8J |
1 |
105 |
|
4-channel connector output unit |
SL-VTP4J |
1 |
60 |
|
8-channel input terminal |
SL-VTB8 |
1 |
30 + 75 = 105 |
|
Sensors |
— |
8 |
30 × 8 = 240 |
|
(Average current consumption: approx. 30mA ) |
||||
|
|
|
||
Output loads |
— |
4 |
20 × 4 = 80 |
|
(Average current consumption: approx. 20mA ) |
||||
|
Total |
838 |
||
|
|
22
Power Supply Capacity of System
The transmission cables of the S-LINK V system may cause voltage drop due to the conductor resistance of the cables themselves. For this reason, calculate the voltage drop value between +24V and 0V, and supply the rated voltage to all the S-LINK V I/O units. However, it is not necessary to consider the voltage drop between the D and G, and that of the control cables and connector link cables.
CAUTION
Use of a longer cable will cause more voltage drop. If the voltage drops below the rated voltage, the I/O units will not work. In this case, use the local power supply unit.
Elongation of the transmission distance will cause more voltage drop at the line end (between +24V and 0V).
Voltage drop (V) = Cable length (m) × 2 × conductor resistance (Ω/m) × current (A)
Relation between the ambient temperature and allowable passing current when exclusive S-LINK V cable SL-RCM100□ / RCM200 or SL-CBM100 / CBM200 (conductor cross section = 0.5mm2 for each cable) is used.
<![if ! IE]> <![endif]>Allowable passing |
|
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>current (A) |
6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
5 |
|
|
|
|
|
|
|
|
|
|
|
|
||
4 |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
0 |
5 |
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
55 |
60 |
|
|
|
|
|
Ambient temperature (˚C) |
|
|
|
|
<![endif]>1 Chapter
CAUTION
The rated voltage depends on the unit. Check the rated voltage, and then select the right power supply unit and cables.
Supply the rated voltage to each unit.
●●Since the rated voltage to be supplied to the controller is +24V (-5%), the voltage supplied to the controller should not be dropped below the following value:
24 - (24 × 0.05) = 22.8V
●●Since the rated voltage to be supplied to the I/O units and end unit is +24V (-10%), the voltage supplied to these units should not be dropped below the following value:
24 - (24 × 0.1) = 21.6V
23
Power Supply Capacity of System
<![endif]>Chapter 1
The 24V DC power supply unit that drives the system uses either the centralized power supply method (use of only one power supply unit) or the decentralized power supply method (use of additional local power supply unit) to supply power to each unit.
At first, calculate the total current consumption value (sum total of current consumption values of all units ‘+’ sum total of load current values of I/O devices).
After that, from the obtained calculation result, cable length, and conductor resistance, calculate the voltage drop value, and determine the voltage to be supplied to each unit.
If the voltage supplied to each unit is above the rated voltage (22.8V or more for the controller, 21.6V or more for the I/O unit), you can design the system using the centralized power supply method.
If the voltage supplied to a unit is out of the rated voltage range, connect a local power supply unit, and use the local power supply method.
CAUTION
To use a local power supply unit, turn on the local power supply unit first, and then turn on the main power supply unit, or turn on these power supply units at the same time.
If the main power supply unit is turned on first, the system may not operate properly.
In the following cases, connect a local power supply unit:
●●The communication distance is too long, and voltage drop is too large.
For this reason, it is not possible to supply the rated voltage to the I/O units. ●●A 2-core cable is used for connection of the I/O unit (for the D-G line only).
●●The main power supply unit and the local power supply unit should be the small capacity type. ●●An I/O device that generates a large noise should be used.
<Reference value>
Conductor cross section (mm2) |
Conductor resistance (Ω/m) |
0.3 |
Approx. 0.065 |
0.5 |
Approx. 0.040 |
0.75 |
Approx. 0.025 |
1.25 |
Approx. 0.015 |
2.0 |
Approx. 0.010 |
Notes: 1) The conductor resistance values shown in the above table are reference values.
To determine the conductor resistance values for the actual cables, contact the cable manufacturer.
2) The conductor cross section of the exclusive 4-core flat cable should be 0.5mm2.
To determine whether a local power supply unit is necessary, refer to the flowchart shown on the next page.
24
Power Supply Capacity of System
Proposed system construction plan |
|
Reexamination |
Reexamination |
Calculation of total current consumption value (refer to page 22)
A unit should be changed |
Yes |
||
or removed |
No |
|
|
|
|
||
Out of rated range |
Yes |
||
of cable connector |
|||
|
|||
(refer to page 157) |
|
No
Calculation of voltage drop value (refer to page 23)
Yes |
A unit should be changed |
|
|
|
or removed |
|
|
|
|
No |
|
|
A local power supply unit |
Necessary |
|
|
is needed in view |
of the calculated |
|
|
|
||
|
voltage drop value |
|
Unnecessary
Decision 1
The I/O device should be Yes connected using 2-core cable
(for the D-G line only)
No
Decision 2
The main power supply unit and local Yes power supply machine should be the
small capacity type
No |
|
|
Decision 3 |
Yes |
|
An I/O device generates |
||
|
||
large noise |
|
|
No |
|
|
Centrailzed power supply method |
Local power supply method |
<![endif]>1 Chapter
25
<![endif]>Chapter 1
CAUTION
If you have to connect a DC 2-wire output device to an input unit, recommend our product.
If a product manufactured by another company is used, the conditions should be checked by following the procedure shown in the following flowchart.
This is because the output device of another company does not fit our input unit.
DC 2-wire output device should be used
|
Our product is used |
YES |
|
|
Normal connection |
|
|
|
||||
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
||||||
|
|
|
|
NO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Check 1 |
|
|
|
|
|
|
|
|
|
|
21.6V-VTHON ≥ VA and |
NO |
|
Connection to the S-LINK V system |
|
|||||||
|
21.6V-VTHOFF =In specified op- |
|
|
|||||||||
|
|
|
is not possible |
|
|
|
||||||
|
eration voltage range |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
YES |
|
|
|
|
|
|
|
|
|
21.6V-VA |
Check 2 |
NO |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
||||
|
Ri |
|
≥ Minimum load current |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The bleeder resistance is necessary |
|
|||||
|
|
|
|
|
|
|
|
|||||
|
|
|
|
YES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Calulation of bleeder resistance |
|
||||
|
|
|
|
|
|
|
RB1 ≤ |
21.6V-VA |
|
|
|
|
|
|
|
|
|
|
|
Minimum load current- |
21.6V-VA |
|
|||
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
Ri |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Condition A |
|
|
|
Condition B |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
VA : Residual voltage in ON mode A1 : Leakage current
VTH : Input voltage of input unit VTHON : Input unit ON voltage VTHOFF : Input unit OFF voltage Ri : Input impedance
RB : Bleeder resistance
|
Check 3 |
|
|
|
|
|
|
|
VTHOFF ≥ A1 |
(Leakage current |
NO |
|
|
||||
|
|
|
|
|
|
|||
Ri |
in OFF mode) |
|
|
|
|
|
|
|
|
|
Calulation of bleeder resistance |
||||||
|
|
|
||||||
|
|
|
|
|
RB2 ≤ |
VTHOFF |
||
|
|
YES |
|
|
A1- VTHOFF |
|
||
|
|
|
|
|
|
|
Ri |
|
|
|
|
|
|
|
|
|
|
Decision of |
condition |
Condition B |
|
|
|
||
|
Condition A |
|
|
Connection is possible if the RB2 |
|
|
|
Connection is possible if the RB1 or RB2 |
|||
bleeder resistor is attached |
(small value) bleeder resistor is attached |
Decision of condition |
Condition B |
||
|
|
|
|
Condition A |
|
|
|
Connection is possible without any |
Connection is |
|
possible if the RB1 |
|
|||
bleeder resistor |
bleeder resistor is attached |
26
Connection of DC 2-Wire Output Device to Input Unit
●●To connect DC 2-wire proximity sensor GX-12MU to 8-channel connector input unit SL-VT8J
VTHON : SL-VT8J ON voltage = 17V or more (between +24V and data input) VTHOFF : SL-VT8J OFF voltage = 4V or less (between +24V and data input) R1 : Input impedance of SL-VT8J = 3.3kΩ
VA (residual voltage in ON mode) of GX-12MU = 3V or less
Specified operation voltage range of GX-12MU = 12 to 24V DC +10– 5 % = 10.2 to 26.4V DC Minimum load current of GX-12MU = 3mA
A1 (leakage current) of GX-12MU = 0.8mA
Check 1
21.6V - 17V = 4.6V ≥ 3V
21.6V - 4V = 17.6V (in range of 10.2 to 26.4V)
Since the requirements of both formulas are satisfied, carry out checks 2 and 3.
Check 2
21.6V - VA of DC 2-wire input device ≈ |
21.6V-3V |
= |
18.6V |
≈ 5.64mA ≥ 3mA |
||||||
|
3.3kΩ |
|
3.3kΩ |
|||||||
|
|
R1 |
|
|
|
|
||||
Check 3 |
|
|
|
|
|
|
|
|
|
|
VTHOFF |
= |
4V |
|
≈ 1.21mA ≥ 0.8mA |
|
|
|
|||
3.3kΩ |
|
|
|
|||||||
R1 |
|
|
|
|
|
|
|
|
Since the requirements of Checks 2 and 3 are satisfied, the bleeder resistor is not necessary.
<![if ! IE]> <![endif]>circuit |
VTH |
|
<![if ! IE]> <![endif]>Main |
||
|
R1 : Input impedance
+24V
RB : Bleeder resistance
Input
Output
DC 2-wire input device
0V 0V
S-LINK V input unit Input device
<![endif]>1 Chapter
27
<![endif]>Chapter 1
CAUTION
Due to difference in communication protocols, the transmission delay time of the S-LINK V system differs from that of the conventional S-LINK system.
For transmission, there are fastest transmission time and the slowest transmission time.
Since this product uses the serial transmission method, transmission will be carried out as shown in the following figure.
For a detailed description of the following controllers, refer to their respective user’s manuals.
SL-VGU1-C, SL-VGU1-D : SL-VGU1-C / SL-VGU1-D User’s Manual
SL-VGU1-EC |
: SL-VGU1-EC User’s Manual |
SL-VGU1-485 |
: SL-VGU1-485 User’s Manual |
SL-VMEL-Q |
: SL-VMEL-Q User’s Manual |
SL-VFP7 |
: SL-VFP7 User’s Manual |
<In case of SL-VCU1>
|
Input |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output |
|||||
I/O device |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Switch |
|
|
1. Response time of input device (sensor, etc.) |
|
|
|
|
|
|
|
|
|
11. Response time of |
||||||||
• Relay, etc. |
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
output device |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(actuator, etc.) |
|
|
|
|
|
2. Input |
|
|
|
|
|
|
|
|
|
|
|
|
|
10. Output |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
0.2ms |
|
|
|
|
|
|
|
|
|
|
|
|
|
0.35ms |
|||
S-LINK V system |
|
|
|
|
3. Filtration |
|
|
|
|
|
|
|
|
|
|
|
9. Refresh time |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
4. Refresh time |
|
|
|
|
8. Filtration |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5. Output to PLC |
|
|
7. PLC to Input |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
0.015ms |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
0.001ms |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
PLC |
|
|
|
|
|
|
|
|
|
|
|
|
6. PLC operation time (scanning time + PLC filtration time) |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||||
●●Response delay of S-LINK V system |
|
|
|
|
|
|
|
|
|
|
|
||||||||||
• Input response time (2 + 3 + 4 + 5) |
|
|
|
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
2 |
|
3 |
|
|
4 |
|
|
5 |
|
|
|
||||
|
|
MIN. |
= |
0.2 |
+ |
From Table 1 |
+ |
From Table 2 |
+ |
0.001 (ms) |
|||||||||||
|
|
MAX. |
= |
0.2 |
+ |
From Table 1 |
+ |
From Table 2 |
+ |
0.001 (ms) |
• Output response time (7 + 8 + 9 + 10)
|
|
7 |
|
8 |
|
9 |
|
10 |
MIN. |
= |
0.015 |
+ |
From Table 1 |
+ |
From Table 2 |
+ |
0.35 (ms) |
MAX. |
= |
0.015 |
+ |
From Table 1 |
+ |
From Table 2 |
+ |
0.35 (ms) |
28
Transmission Delay Time
<In case of SL-VFP2, SL-VMEL-Q, SL-VPCI, SL-VVMES2>
|
Input |
|
|
|
|
|
|
|
|
|
|
Output |
|||||
I/O device |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Switch |
|
|
1. Response time of input device (sensor, etc.) |
|
|
|
|
|
|
10. Response time of |
|||||||
• Relay, etc. |
|
|
|
|
|
|
|
|
output device |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(actuator, etc.) |
|
|
|
|
|
2. Input |
|
|
|
|
|
|
|
|
|
9. Output |
|||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
0.2ms |
|
|
|
|
|
|
|
|
|
0.35ms |
|||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
3. Filtration |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
S-LINK V system |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4. Refresh time |
|
|
|
|
8. Refresh time |
|||||
|
|
|
|
|
|
|
|
|
5. Internal memory |
|
|
7. Internal memory |
|||||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
Max. 1 refresh time |
|
|
Max. 1 refresh time |
|||||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
PLC etc. |
|
|
|
|
|
|
|
|
|
|
|
6. PLC / PC operation time (scanning time) |
|||||
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
||||||||
●●Response delay of S-LINK V system |
|
|
|
|
|
|
|
|
|||||||||
• Input response time (2 + 3 + 4 + 5) |
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
2 |
|
3 |
|
4 |
5 |
|
|
|
|
||
|
|
MIN. |
= |
0.2 |
+ |
From Table 1 |
+ |
From Table 2 |
+ From Table 2 (ms) |
||||||||
|
|
MAX. |
= |
0.2 |
+ |
From Table 1 |
+ |
From Table 2 |
+ From Table 2 (ms) |
• Output response time (7 + 8 + 9)
|
|
7 |
|
8 |
|
9 |
MIN. |
= |
From Table 2 |
+ |
From Table 2 |
+ |
0.35 (ms) |
MAX. |
= |
From Table 2 |
+ |
From Table 2 |
+ |
0.35 (ms) |
<Table 1 Filtration time> |
|
|
<Table 2 Refresh time, Internal memory max.1 refresh time> |
|
|
Filtration time (ms) |
|
|
|
A mode |
B mode |
C mode |
|||
MIN. |
MAX. |
MIN. |
MAX. |
MIN. |
MAX. |
0.05 |
0.06 |
0.19 |
0.26 |
0.77 |
1.02 |
Number of |
Refresh time, Internal memory max.1 refresh time (ms) |
||||||
I/O control |
A mode |
B mode |
C mode |
||||
points |
MIN. |
MAX. |
MIN. |
MAX. |
MIN. |
MAX. |
|
32 |
|
1.50 |
|
6.01 |
|
24.03 |
|
64 |
|
2.09 |
|
8.36 |
|
33.44 |
|
96 |
|
2.68 |
|
10.71 |
|
42.85 |
|
128 |
|
3.27 |
|
13.06 |
|
52.26 |
|
160 |
|
3.85 |
|
15.42 |
|
61.66 |
|
192 |
|
4.44 |
|
17.77 |
|
71.07 |
|
224 |
|
5.03 |
|
20.12 |
|
80.48 |
|
256 |
0.29 |
5.62 |
1.18 |
22.47 |
4.70 |
89.89 |
|
288 |
6.21 |
24.82 |
99.30 |
||||
|
|
|
|||||
320 |
|
6.79 |
|
27.18 |
|
108.70 |
|
352 |
|
7.38 |
|
29.53 |
|
118.11 |
|
384 |
|
7.97 |
|
31.88 |
|
127.52 |
|
416 |
|
8.56 |
|
34.23 |
|
136.93 |
|
448 |
|
9.15 |
|
36.58 |
|
146.34 |
|
480 |
|
9.73 |
|
38.94 |
|
155.74 |
|
512 |
|
10.32 |
|
41.29 |
|
165.15 |
<![endif]>1 Chapter
29
Transmission Delay Time
<![endif]>Chapter 1
Power-on
1.Time required for power-on (Depends on the supplied power)
S-LINK V |
|
|
|
|
|
|
|
|
controller |
|
|
|
2. Transmission |
|
|||
|
|
|
|
|
check |
|
||
|
|
|
|
|
|
|
3. Output |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
0.5ms |
|
|
|
Completion of |
|
|
|
|
READY |
|
|
|
|
|
|||||
|
|
transmission check |
|
|
|
|
output |
|
|
|
|
|
|
|
|
|
|
● READY output at normal starting |
|
|
|
|
|
|
||
OFF |
|
|
|
|
|
|
|
|
ON |
|
|
|
|
|
|
||
|
|
|
|
|
|
● READY output at starting after shorting line between +24V and 0V or between D and G line
OFF
ON
● Error output 1 and 2
OFF
ON
<Table 3 Time required for transmission check at starting controller>
Number of Time required for transmission check at starting cotroller (ms) I/O control
points 32 64
96
128
160
192
224
256
288
320
352
384
416
448
480
512
●●READY output delay time (1 + 2 + 3)
1 (Depending on supplied power) + 2 (From Table 3) + 3 (0.5 ms)
Occurrence of error
1. Error check
S-LINK V controller
2. Output
0.5ms
Error output
● Error output 1 and 2
OFF
ON
●●Error output delay time (1 + 2)
1 (From Table 4 or 5) + 2 (0.5ms)
<Table 4 Time required for error check (errors 3, 4, and 5)>
Number of |
Time required for error check (errors 3, 4, and 5) (ms) |
|||
I/O control |
A mode |
B mode |
C mode |
|
points |
||||
|
|
|
||
32 |
43.5 |
174.0 |
695.8 |
|
64 |
93.4 |
373.6 |
1494.3 |
|
96 |
162.1 |
648.4 |
2593.8 |
|
128 |
249.6 |
998.6 |
3994.4 |
|
160 |
356.0 |
1424.0 |
5696.0 |
|
192 |
481.2 |
1924.7 |
7698.7 |
|
224 |
625.2 |
2500.6 |
10002.4 |
|
256 |
788.0 |
3151.8 |
12607.2 |
|
288 |
969.6 |
3878.3 |
15513.1 |
|
320 |
1170.0 |
4680.0 |
18720.0 |
|
352 |
1389.2 |
5557.0 |
22228.0 |
|
384 |
1627.3 |
6509.2 |
26037.0 |
|
416 |
1884.2 |
7536.8 |
30147.1 |
|
448 |
2159.9 |
8639.6 |
34558.2 |
|
480 |
2454.4 |
9817.6 |
39270.4 |
|
512 |
2767.7 |
11070.9 |
44283.6 |
<Table 5 Time required for error check (errors 1 and 2)>
Time required for error check (errors 1 and 2) (ms)
A mode |
B mode |
C mode |
1.33 |
5.32 |
21.28 |
30