Panasonic S-LINK V User Manual

Flexible Wire-Saving System
S-LINK V
USER’S MANUAL
WUME-SLINKV-9
2020.9
panasonic.net/id/pidsx/global
9th Edition
2
Contents
Introduction ·············································· 6
Warnings ··············································· 6 Instructions for Safe Use ··························· 7
Ambient conditions ······························ 7
Instructions for Use ································ 8
Instructions for Designing ······················ 8 Fail-safe function ································· 8 Conformity to EC Directives ··················· 8 Use with S-LINK system ······················· 8
Instructions for Installation ························· 9
Hook-up cable connectors ····················· 9 Wiring ··············································· 9 Others ··············································· 9
Instructions for Disposal ···························· 9
Designing / Installation Procedures ············· 10
MEMO ··················································12
Chapter 1 ··············································· 13
Designing System ·································· 13
System Conguration ······························· 14 Outline of Design ···································· 16
Selection of Controller or Control board ·······16 I/O Control Points ···································16 Transmission Distance ·····························16 Outputting Error Signals ···························17 Connection of End Unit ····························18 Selection of Control Cable and Connector Link Cable ·············································18
Control cable selection method: (For use of Connector link cable selection method: (For
use of Making of Branch Lines Using Cable Connectors ············································19
SL-VCU1
SL-VCU1
only) ··················18
only) ··························18
Power Supply Capacity of System ·············· 20
Calculation of Total Current Consumption
Value ··············································20
Example: Calculation of current consump-
tion ··················································22 Calculation of Voltage Drop Value ··············23
Rated voltage (V) ·······························23 Necessity of Local Power Supply Unit ·········24
Designing of system using local power sup-
ply method ········································24
Connection of DC 2-Wire Output Device to Input Unit ······················································ 26
Example: Connection of DC 2-wire sensor 27
Transmission Delay Time ·························· 28
Response delay time ···························28
Operation at power-on ·························30
Error signal outputting delay time ···········30
System setting time ·····························31
Selection of Output Holding Function for Output Unit ······················································ 32
Output holding function setting method ···32
Address Setting ······································ 33
Setting of PLC I/O connector numbers ····33
Setting of I/O unit addresses ·················33
Example: Address setting ····················· 34
Chapter 2 ··············································· 35
Wiring ··················································· 35
Flowchart ·············································· 36 Basic Procedures ···································· 37
Connector hook-up work ······················37 Cutting of exclusive 4-core at cable·······37 How to use exclusive hook-up pliers (SL­JPS, SL-JPC, SL-JPE) ························38
Hook-up of Connector ······························39
Hook-up method of SL-JK connector for cable end and SL-JK1 connector for ‘T’­branch ·············································39 Hook-up method of ‘T’ - branch and SL-J3A connector for cable extension Hook-up method of CP3 snap male connectors and
SL-CJ2
Connection to Terminal Block ····················46 Extension of Main / Branch Line Cable ········47
Extension of exclusive 4-core at cables ·47 Extension of cable excluding exclusive 4-core at cables ································47 Extension of cable to I/O device·············47
Installation ·············································48
Installation of each unit ························48
···········································41
snap female connectors ··················44
SL-J1A
SL-CP1, SL-CP2
connector for
SL-CJ1
, and SL-
and
Construction ··········································· 50
Power Supply ····································50 Power supply to system ·······················50
Connection of Each Unit ···························51
Connection of controller ·······················51 Connection of bus direct-connection type controller and control board ··················52 Connection of PLC I/O Connector ··········53 Connection of I/O unit ··························55 Connection of I/O device ······················56 Connection of main line cable to end unit 57 Connection of local power supply unit ····58 Local power supply to system ···············58 Installation method of batteries ··············59
MEMO ··················································60
Chapter 3 ··············································· 61
Starting System ······································ 61
Flowchart ·············································· 62 Wiring Check ·········································· 64
Check before Starting ··························64 Check of wiring conditions of controller and control board ·······························64 Check of PLC I/O connectors ················65 Check of cable for short-circuit ··············65
Starting ················································· 66
Power-on (Main Power and Local Power) 66 CONFIG mode ···································66
Check of Recognized Addresses ················70
CHECK mode ····································70
3
Chapter 4 ··············································· 71
Specications ········································ 71
Specications ········································· 72
Common Specications ···························72
Address setting switches ······················72
Specications of Each Unit ·······················75
Controller ··········································75 Bus direct-connection type controller for FP2 / FP2SH Series ··································79 Bus direct-connection type controller for FP7 Series ··············································83 Mitsubishi MELSEC-Q Series PLC bus di­rect-connection type controller ···············87 Control board ·····································91 Control module ··································95 PLC I/O connector ······························97 I/O unit ··········································· 100 Input terminal ··································· 103 Output terminal ································ 107 Connector input unit ·························· 111 Connector output unit ························ 11 5 MIL connector input unit ····················· 119 MIL connector output unit ··················· 122 Analogue input unit ··························· 125 Analogue output unit ························· 131 Relay output terminal ························ 136 Input module ··································· 139 Output module ································· 141 Picking switch ·································· 143 Picking switch for shutter ···················· 146 Address setting remote controller ········· 149 End unit ·········································· 151 Handy monitor ································· 153 Cable ············································· 157 Hook-up connector ··························· 157 List of programmable logic controllers (PLC) (upper models) ································· 159
List of Models ········································160
Controller ········································ 161 Control board ··································· 161 Control module ································ 161 List of I/O units ································· 162 List of connectors ····························· 163 Handy monitor ································· 163 Address setting remote controller ········· 163 Others ············································ 164
Selection of connector link cable ·········· 176 Setting of connector numbers, ············· 180 addresses, and number of I/O control points 180 Glossary ········································· 181
FAX Sheet for Asking Question ·················183
MEMO ················································ 184
Chapter 5 ··············································165
Troubleshooting ····································165
Troubleshooting ·····································166
Flowchart for taking corrective action for de­tected error ····································· 166 Flowchart for power supply condition check 169 How to identify error unit after error detection 171 How to extinguish error indicator ·········· 172 Utilization of output holding function ····· 172
Appendix ··············································173
Appendix ··············································174
List of error numbers ························· 174 Flowchart for error detection ··············· 175
4

Before Using This System

5

Introduction

S-LINK V
The highly reliable signal transmissions. Fully understand the functions and performance of this system before constructing this system.
is a flexible wire-saving that uses our original transmission system to enable high-speed and
This manual provides information necessary for construction of the Before constructing the In addition, be sure to observe the cautions, and correctly use the system. The controllers listed below have their own user’s manuals. For a detailed description, refer to that documentation.
SL-VGU1-C, SL-VGU1-D : SL-VGU1-C SL-VGU1-EC SL-VGU1-485 SL-VMEL-Q SL-VFP7
For other controllers, refer to the instruction manuals enclosed with the controllers.
EtherCAT® is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
:
:
S-LINK V
SL-VGU1-EC
:
SL-VGU1-485
:
SL-VMEL-Q SL-VFP7
system, carefully read this manual and fully understand the system.
SL-VGU1-D
/
User’s Manual
User’s Manual
User’s Manual
User’s Manual
User’s Manual
S-LINK V

Warnings

Before Using This System
This manual uses three types of warnings depending on the hazard level. They are ‘
CAUTION
.’ To safely use the
S-LINK V
system, be sure to observe these warnings.
DANGER
exible wire-saving system.
DANGER
WARNING
,’ ‘
,’ and
Remarks
DANGER
‘ word is limitedly used in the extremely hazardous situations.
’ indicates that mishandling of this system may result in death or serious injury, and this
WARNING
WARNING
’ indicates that mishandling of this system may result in death or serious injury.
CAUTION
CAUTION
NOTE
’ indicates that mishandling of this system may result in injury or damage of the system.
‘NOTE’ provides caution or information to you in order to prevent operation errors.
1) Panasonic Industrial Devices SUNX Co., Ltd. holds the copyright of this document. For this reason, do not copy this document without our permission.
2) The contents of this document may be subject to change without prior notice for the reasons of improve­ment.
3) The product specications shown in this document were determined in September 2020.
6

Instructions for Safe Use

WARNING
S-LINK V
The safety function. For this reason, do not use the fect human lives or assets. Even if this system is not used as an accident preventive system or safety system, if this system is used for a nuclear power control system, railroad facility, aviation facility, vehicle, combustion system, medical equipment, or the like, be sure to design a system having enough capacity, and adopt safety measures for the system, such as a fail-safe function. In addition, please contact our sales division.
Ambient conditions
Do not use this system at the following places:
system does not have any control functions, such as accident preventive function and
Place where the ambient tem-
perature is out of the specied
range of 0 to +55°C (Note 1)
Notes:
1) The optimum ambient temper­ature depends on the product type. For this reason, check the specications of this prod­uct shown in Chapter 4.
2) If this product is incorporated in the control box together with the other unit, the unit may generate heat to change the ambient temperature. In this case, install a cooling fan so that the ambient temperature cannot exceed the rated upper limit temperature.
S-LINK V
Introduction
system if malfunction of the system may af-
Before Using This System
Place where the ambient tem­perature extremely varies and dew condensation may be caused.
Place where the ambient hu­midity is out of the specified range of 35 to 85% RH (Note)
Note The optimum ambient humidity depends on the product type. For this reason, check the specifica­tions of this product shown in Chapter 4.
Steamy or dusty place or place near water, oil, or chemical source
Place where direct sunlight may enter
COR-
ROSIVE
GAS
FLAM-
MABLE
GAS
Place where there is a corro-
sive or ammable gas
Place where vibration or shock of more than the speci­ed level may be directly ap­plied to the system main body
Closed place
However, if a ventilation hole or a fan is installed, such a place can be used.
7
Instructions for Use
Note:
supply unit and the surge absorber. Check whether a resistor is needed.
+24V DC
Recommended part: ERZV05D390 manufactured by Panasonic Corporation (Note)
Not good
Good
Instructions for Designing

Fail-safe function

CAUTION
Disconnection of a signal line, instantaneous power failure, or abnormal signal may cause a problem. For this reason, please adopt a fail-safe function for the entire system by yourself. To ensure safety, be sure to incorporate the interlock circuit, limit circuit, or the like, in the external cir­cuit excluding the
S-LINK V
system circuit.
To incorporate the Regarding the fail-safe function, if you have an unclear or doubtful point, please contact our sales division.
S-LINK V
system in your equipment, be sure to adopt a fail-safe function.

Conformity to EC Directives

WARNING
● Each unit of the
Before Using This System
To conform to the EC Directives, the as EN 61000-6-4 of the EMI standard and EN 61000-6-2 of the EMS standard. When you incorporate the tem in your machine or equipment, check that the wiring condition conforms to the requirements of the EC Directives. To use the tric Corporation and to conform to the requirements of the EMC Directive, install the system in accordance with the PLC User’s Manual prepared by Mitsubishi, and be sure to observe the following items:
● Be sure to put the PLC and the
Be sure to ground the shielded cable that connects the PLC to the
● If the shielding e󰀨ect is not enough, install a ferrite core.
the system, check that entire system can conform to various standards.
● The lightning surge preventive function is not adopted for the I/O module (
conform to the requirements of EN 61000-6-2, incorporate the following circuit in your board.
Power supply
● If it is not necessary for the relay output terminal (
use of 250V AC, 3A is possible.
SL-VGU1-C
S-LINK V
If a different part is used, a resistor may be needed between the power
together with the PLC (programmable logic controller) manufactured by Mitsubishi Elec-
series conforms to various standards. However, to incorporate a unit in
+
Surge absorber
S-LINK V
SL-VGU1-C
SL-VM
0V
SL-VTPR4/8
system is tested in accordance with the EMC Directive standards, such
in a conductive box.
SL-VGU1-C
) to conform to the EC Directives,
in the 300mm area of the
□ /
VMP
□). To
S-LINK V
SL-VGU1-C
sys-
.

Use with S-LINK system

S-LINK V
The mal operation or damage. Separately construct the However, if gateway controllers are used as the child station of the open network (CC-Link, DeviceNet, RS-485 / RS-232C, EtherCAT), 2 systems can be used together on the same network.
8
system cannot be used together with the
S-LINK V
gateway controller
S-LINK V
unit
S-LINK
unit
S-LINK
S-LINK V
system. Use with a system may cause abnor-
system and the
S-LINK V
gateway controller
S-LINK V
unit
S-LINK
S-LINK V
unit
system.
S-LINK
gateway controller
S-LINK
unit
S-LINK
unit

Instructions for Installation

CAUTION
● Select a power supply unit equipped with the short-circuit protective function (fuse, etc.).
● The power of the
the main cable or I/O device side. However, the short-circuit protective function is not adopted for this power supply circuit. For this reason, adopt a short-circuit protective function, such as a fuse, for the power supply circuit.
● Take care that wrong wiring will damage the product.
● Before starting the following works, be sure to turn o󰀨 the power of the PLC (programmable logic
controller), personal computer main body, of the I/O device.
• Machine assembly (installation)
• Removal or reinstallation of a
• Cable connection
• Address setting / change
● Before handling this product, remove any electrostatic charge that may be present on your body.
There is a danger of this product getting damaged due to the electrostatic charge.
S-LINK V
system passes through the inside of each unit and is then supplied to
S-LINK V
S-LINK V
unit or connection of I/O device
units, and also turn o󰀨 the power supply unit
Instruction for Use
Before Using This System
Hook-up cable connectors
To hook-up an exclusive cable connector, use the exclusive tool, and correctly hook-up the connector by follow-
ing the procedure specied in this manual.
If a connector is not correctly hooked-up, the In addition, observe the following items:
● After checking the cable type and the purpose, select the right type of connector.
● Before hook-up a connector, be sure to check the colors of cables to be connected.
● Use the exclusive hook-up pliers (
For the hook-up procedure of each connector, refer to pages 37 to 45.
● If a connector is once hooked-up, do not reuse the connector.
The performance of such a connector may be deteriorated.
SL-JPS, SL-JPC
S-LINK V
system will not operate.
SL-JPE
or
) to hook-up the connectors.
Wiring
Observe the following items to distribute cables:
● Keep cables away from the power line and the high-voltage line.
● Do not completely fold down any cables.
● Do not pull any cables with a strong force.
● Do not apply any weight to any cable.
● Do not touch a cable to any other system cables.
This is because signals of di󰀨erent systems may interfere with each other.
● Do not bend cables many times.
● Wind insulation tape on the end of each cable, if necessary.
Others
● Apply the specied torque to tighten terminal screws of each unit.
● Check the connectors for looseness.
● Do not disassemble or modify this product.

Instructions for Disposal

● Request a waste disposal company to dispose of this product.
9

Designing / Installation Procedures

Local power supply unit
Chapter 1 Designing System
● Determine the system design.
● Determine the necessary number of I/O points for
the I/O device.
● Determine the cable length necessary for transmis-
sion.
● Select the transmission speed.
● Set the address.
● Calculate the power supply capacity of the system.
● Determine the connection method for the input de-
vice of DC 2-wire output type.
● Determine the transmission delay time.
● Set the output holding function.
How long?
Chapter 2 Wiring
Before Using This System
● This chapter describes the wiring methods to be used for actual installation.
● Caution regarding cutting of exclusive 4-core flat
cable
● Connector hook-up method
● Cable extension method
● Connection to I/O device
● Connection of local power supply unit
● Connection to terminal block
ON
256 128
16
ADDRESS
8
4
2
1
+ -
AC
F.G.
Insulated
Chapter 3 Starting System
● Check the system before starting.
● Check the cable for short-circuit.
● Check the system before starting.
● Caution regarding power-on
● Description of CONFIG mode
● Description of CHECK mode
10
D (White)
+24V (Brown)
0V (Blue)
G (Black)
Transmission cable
Analogue tester
Designing / Installation Procedures
Chapter 4 Specications
● Select
S-LINK V
S-LINK V
S-LINK V
S-LINK V
control units
input units
output units
units optimum for the purpose of your system.
● Hook-up connector
● Exclusive 4-core at cable
Chapter 5 Troubleshooting
● This chapter describes how to solve the problem if the
not operate properly.
● Troubleshooting after error indication
● Power supply check procedure
● How to extinguish the error indicators
7
6
5
4
3
2
1
0
S-LINK V
1
Before Using This System
system does
Appendix
● List of error numbers
● Flowchart for error detection
● Selection of connector link cable for PLC
● Fax sheet for asking questions
This manual is prepared for the designer and the installer of the mon to both the designer and the installer:
Before Using This System
Chapter 4 Specications
● ‘
Chapter 5 Troubleshooting
● ‘
Appendix
In addition, the designer should refer to ‘
Chapter 2 Wiring
’ and ‘
Chapter 1 Designing System
Chapter 3 Starting System
.’
S-LINK V
system. The following items are com-
,’ and the installer should refer to
11

MEMO

Before Using This System
12

Chapter 1 Designing System

13
4
3
2
1
0
7
6
5
Example of system configuration
An example of the S-LINK V system is shown below. For the specifications of each unit, refer to Chapter 4.
Controller
SL-VCU1
Power supply unit
24V DC
+10 – 5
%
Bus direct-connection type S-LINK V controller for MELSEC-Q series PLC manufactured by Mitsubishi Electric Corp.
SL-VMEL-Q
Bus direct-connection type S-LINK V controller for FP2 /
FP2SH series
SL-VFP2
Gateway controller (Note)
Control board
S-LINK V control board
for VME bus
SL-VVMES2
S-LINK V control board
for PCI bus
SL-VPCI
S-LINK V control module
SL-VMC1
4-channel connector output unit
SL-VTP4J
e-CON type 4-channel connector output unit
SL-VTP4E
e-CON type 8-channel connector output unit
SL-VTP8E
8-channel connector output unit
SL-VTP8J
16-channel MIL connector output unit SL-VTP16C1(-S)
Analog output unit
SL-VTDA1
4-channel output terminal
SL-VTBP4
8-channel output terminal
SL-VTBP8
16-channel output terminal
SL-VTBP16
32-channel output terminal
SL-VTBP32
Local power supply unit
4-channel relay output terminal SL-VTPR4
S-LINK V gateway controller for CC-Link
SL-VGU1-C
S-LINK V gateway
controller for
RS-485
/ RS-232C
SL-VGU1-485
S-LINK V gateway
controller for EtherCAT
SL-VGU1-EC
S-LINK V gateway
controller for DeviceNet
SL-VGU1-D
Bus direct-connection type S-LINK V controller for FP7 series
SL-VFP7
System Conguration
Chapter 1
14
Note: For a detailed description of the following controllers, refer to their respective user’s manuals.
SL-VGU1-C, SL-VGU1-D SL-VGU1-EC SL-VGU1-485 SL-VMEL-Q SL-VFP7
:
:
:
:
SL-VGU1-C
:
SL-VGU1-EC SL-VGU1-485 SL-VMEL-Q SL-VFP7
SL-VGU1-D
/
User’s Manual
User’s Manual
User’s Manual
User’s Manual
User’s Manual
1
2
3
4
4
3
2
1
0
7
6
5
Analog input unit
SL-VTAD1
I/O module
Input module
SL-VM8 / VM16
Output module
SL-VMP8 / VMP16
Hook-up connectors
SL-CP3
Cables and hook-up connectors
Flat cables are available so that 'T' - branch can be easily formed by using hook-up connectors.
There are various types of hook-up connectors that enable easy connection of cables.
Handy monitor
SL-VHM1
Picking switch
SL-VPK01 SL-VPK02
For flexible wire-saving system
e-CON type 4-channel connector input unit
SL-VT4E
e-CON type 8-channel connector input unit
SL-VT8E
4-channel connector input unit SL-VT4J
16-channel MIL connector input unit
SL-VT16C1
8-channel connector input unit SL-VT8J
1-channel output unit
SL-VCH11
2-channel output unit
SL-VCH22
1-channel input unit
SL-VCH10
2-channel input unit
SL-VCH20
2-channel I/O mixed unit
SL-VCH21
4-channel relay output terminal SL-VTPR4
8-channel relay output terminal SL-VTPR8
8-channel input terminal
SL-VTB8
4-channel input terminal
SL-VTB4
16-channel input terminal
SL-VTB16
32-channel input terminal
SL-VTB32
End unit
SL-VEU
System Conguration
Chapter 1
15

Outline of Design

A
Transmission distance =

Selection of Controller or Control board

Select a computer, VME bus computer, open network).
S-LINK V
controller or a
S-LINK V
control board optimum for the upper machines (PLC, PC, PCI bus

I/O Control Points

The system needs the following I/O control points. Design the system considering these points.
● Each controller or control board can control up to 256 nodes (number of I/O units connected to the system)
and 512 points (512 points × 2 for the
SL-VVMES2
● To cope with various PLC connection types of various manufacturers, we can provide 8 types of PLC input
connectors and 7 types of PLC output connectors. For a detailed description, refer to pages 159 and 160. Each PLC I/O connector has 32 points for any model.
Chapter 1
NOTE
) of I/O device, connect two or more controllers as the other systems.
Each system needs one controller or one control board. Two or more controllers or control boards cannot be connected to one system. The above described number of I/O control points (512 points or 512 points × 2 for the
SL-VVMES2
This means that these values depend on the total cable length and the conditions of the con­nected machine (total current consumption, voltage drop, etc.). For a detailed description, refer to pages 16 to 25.
) and the number of nodes (256 nodes) are the maximum values.
SL-VVMES2
). To control more than 512 points (512 points × 2 for the

Transmission Distance

The following two types of cables can be used for the
● Exclusive 4-core at cable (recommended cable)
● 4-core VCTF cable (0.3 to 2.0mm2, non-shielded) commercially available
Note: The VCTF cable is the vinyl cabtyre cable that conforms to the requirements of JIS C 3306 ‘Polyvinyl chloride insulated exible cords.’
To wire the (+24V, 0V) and 2 signal transmission lines (D, G).
The cable length depends on the total cable length and the transmission distance.
S-LINK V
Control area
system, use 4-core cables so that the wire system can consist of 2 power supply lines
: S-LINK V I/O unit
(Branch line) (Branch line)
B C D
S-LINK V
(Main line)
A
system.
(Branch line)
16
Total cable length =
+
A
+B+
D
C
Outline of Design
NOTE
● The main line is the longest route distributed from the controller or control board.
● The branch lines are the routes branched from the main line.
The total cable length should satisfy the conditions shown in the following table:
Transmission mode Total cable length (m)
A 100 B 400 C 1,600
The maximum transmission distance (between D and G) is as follows:
Mode A: 50m
The maximum length is 50m regardless of the cable conductor cross section (0.3 to 2.0mm2) and the number of nodes (1 to 256 nodes).
Mode B
Conductor cross section
(mm2)
0.3 180
0.5
0.75
1.25
2.0
Number of nodes and maximum transmission length (m)
Up to 224 nodes Up to 256 nodes
200 (full specication for mode B)
Chapter 1
Mode C
Conductor cross section
(mm2)
0.3 570 440 350 300 260 220 200 180
0.5 710 580 490 420 370 330 300
0.75 780 670 590 530 480
1.25
2.0
NOTE
Up to 32 nodes
Up to 64 nodes
● Voltage drop between +24V and 0V is not considered. For this reason, calculate this volt-
age drop value, and use a local power supply unit, etc. to prevent voltage drop.
Number of nodes and maximum transmission length (m)
Up to 96 nodes
For a detailed description, refer to page 23.
● The conductor cross section of the exclusive 4-core at cable
● Wire the
S-LINK V
system while observing the communication distance specications de-
scribed above. In addition, use the cables that satisfy the specications described above.
● To select applicable cables, refer to the section describing cables.
For a detailed description, refer to page 157.
● The picking switch
SL-VPK0

Outputting Error Signals

Up to 128 nodes
800 (full specication for mode C)
Up to 160 nodes
Up to 192 nodes
SL-RCM
Up to 224 nodes
□ is 0.5mm2.
□ cannot be used in mode A (transmission mode).
Up to 256 nodes
If the controller is equipped with the error signal output function, the controller can output an error signal after detection of an error. To output an error signal, the
S-LINK V
system will be turned on properly. If an error occurs, the NPN output
transistor will be turned o󰀨.
For each type of error, you can select whether the error signal should be output. For the Troubleshooting, refer to page 165. For the error, refer to page 166.
17
Outline of Design
Same length (Note 1)
Connect the end unit to the line
Main line

Connection of End Unit

CAUTION
Each system needs at least 1 not operate properly. If the cable lengths are the same, connect the end unit to the line having fewer nodes (units).
Be sure to connect 1 If the branch line length exceeds 80% of the maximum transmission distance, connect 1 of the branch line, too. Up to 2
<If the branch line length is equal to the main line length>
SL-VEU
SL-VEU
end units can be connected for 1 system.
end unit to the end of the main line.
SL-VEU
end unit. If the
SL-VEU
SL-VEU
unit is not connected, the system may
Chapter 1
having fewer nodes.
<If the branch line length is 80% of the main line length or more>
Maximum transmission distance
SL-VEU
SL-VEU
unit to the end
Connect the end unit to the main line and branch line, respectively.
80% of the main line length or more
Notes: 1) The maximum transmission distance depends on the cable conductor cross section and the number of nodes. For the maximum transmission distance, refer to page 17.
2) Even if the cable lengths are the same, if both the main and branch line lengths exceed 80% of the maximum transmission dis­tance, connect two
SL-VEU
end units.

Selection of Control Cable and Connector Link Cable

Control cable selection method: (For use of SL-VCU1 only)
Check the distance from the
SL-VC1000
One control cable is needed for every 8 PLC I/O connectors.
(1m long) or
Connector link cable selection method: (For use of SL-VCU1 only)
The PLC I/O connector installation direction (vertical) and layout depend on the PLC manufacturers. Check the connection distance of the PLC I/O connector, and then select the applicable connector link cable:
SL-VF70
For a detailed description, refer to page 176.
(70mm),
SL-VF150
SL-VCU1
SL-VC2000
(150mm), or
to the PLC I/O connector, and then select the applicable control cable:
(2m long).
SL-VF250
(250mm).
18

Making of Branch Lines Using Cable Connectors

SL-VCU1
Intermediate connector
SL-JK
Branch lines can be made by using connectors and terminal blocks. In addition, for this product, cables or connectors that are commercially available can be used.
CAUTION
The exclusive hook-up connectors can connect the exclusive 4-core at cables only.
Outline of Design
Exclusive 4-core at cable
Making of ‘T’ - branch line using exclusive hook-up connector
SL-J1A
…1
Extension using exclusive hook-up connector
Exclusive 4-core at cable
4-core VCTF cable commercially available (non-shielded) (Note)
Note: The VCTF cord is the vinyl cabtyre cord that conforms to the requirements of JIS C 3306 ‘Polyvinyl chloride insulated exible cords.’
SL-J3A
…2
Connection of branch line using exclusive hook-up connector
SL-JK1 SL-JK
Intermediate connector commercially available…5 Intermediate terminal block commercially available…6
and
and
SL-CP3
SL-CP3
…3
…4
SL-J1A
4-core VCTF cable commercially available (non-shielded) (Note)
Intermediate connector commercially available or intermediate terminal block commercially available
Intermediate connector commercially available or intermediate terminal block commercially available Note: Use the same diameter cable.
1
6
SL-J1A
1
Intermediate connector
Intermediate terminal block
SL-CP3
3
SL-J3A
2
5
Chapter 1
SL-CP3
4
SL-JK1
SL-VEU
19

Power Supply Capacity of System

This section describes how to calculate the total current consumption value and voltage drop value in order to determine the power supply capacity (capacity of 24V DC power supply unit).
Calculation of Total Current Consumption Value
To determine the total current consumption, check the current consumption of each I/O unit. Calculate the power supply capacity while referring to the list of current consumption values shown below.
Designation Model No. Current consumption (mA) Controller Bus direct-connection Bus direct-connection Mitsubishi MELSEC-Q PLC bus direct-connection Control board for PCI bus Control board for VME bus Control module Gateway controller for CC-Link Gateway controller for DeviceNet Gateway controller for RS-485 / RS-232C Gateway controller for EtherCAT Input connector for PLC
Chapter 1
Output connector for PLC End unit 1-channel input unit 2-channel input unit 2-channel I/O mixed unit 1-channel output unit 2-channel output unit 4-channel connector input unit 8-channel connector input unit 16-channel MIL connector input unit Analogue input unit 8-channel input module 16-channel input module 4-channel connector output unit 8-channel connector output unit 16-channel MIL connector output unit Analogue output unit 8-channel output module 16-channel output module 4-channel relay output terminal 8-channel relay output terminal Picking switch Picking switch for shutter Handy monitor
S-LINK V S-LINK V
controller for controller for
FP2 FP7
FP2SH
/ series
S-LINK V
series
controller
SL-VCU1 SL-VFP2 SL-VFP7 SL-VMEL-Q SL-VPCI SL-VVMES2 SL-VMC1 SL-VGU1-C SL-VGU1-D SL-VGU1-485 SL-VGU1-EC SL-VS
30
SL-VP
73
SL-VEU SL-VCH10 SL-VCH20 SL-VCH21 SL-VCH11 SL-VCH22 SL-VT4J, SL-VT4E SL-VT8J, SL-VT8E SL-VT16C1 SL-VTAD1 SL-VM8 SL-VM16 SL-VTP4J, SL-VTP4E SL-VTP8J, SL-VTP8E SL-VTP16C1(-S SL-VTDA1 SL-VMP8 SL-VMP16 SL-VTPR4 SL-VTPR8 SL-VPK01 SL-VPK02 SL-VHM1
) 50 (Note 2)
25 (when shutter operation: 450)
135
60 80 70 85
88 (Note 1)
60 300 300 300 300
10
20
28
24
16
20
70 (Note 2)
105 (Note 2)
80 (Note 2)
80
18
20 (Note 2) 60 (Note 2) 90 (Note 2)
90
60
95 (Note 2)
90 (Note 2, 3)
150 (Note 2, 3)
25
500
20
Power Supply Capacity of System
Designation Model No.
4-channel input terminal 8-channel input terminal 16-channel input terminal 32-channel input terminal 4-channel output terminal 8-channel output terminal 16-channel output terminal 32-channel output terminal
Notes: 1)
2) Regarding the
For a detailed description, refer to the specications of each product shown in
3) The For the characteristics of the product when using PhotoMOS relay, refer to the ‘
4) The value shown in the ‘Unit side’ area indicates the current consumption in the main circuit. The value shown in the ‘I/O side’ area indicates the current consumption in the I/O circuit.
SL-VVMES2
range, turning on of all the points may not be possible.
https://panasonic.net/id/pidsx/global
NOTE
, the value for 1 port is shown in the above table.
SL-VTPR
SL-VTPR
□ limits the output current depending on the ambient operation temperature and the number of ON points.
SL-VT□J, SL-VT□E, SL-VT□16C1(-S
□,
.’
The values shown in the above table does not include the current supplied to the PLC mod­ule and current consumption of sensors and loads.
SL-VTB4 SL-VTB8 SL-VTB16 SL-VTB32 SL-VTBP4 SL-VTBP8 SL-VTBP16 SL-VTBP32
SL-VM□16,
), and
if the ambient temperature is not in the specied
Specications
Panasonic Industrial Devices SUNX website:
In addition to the above units, when additional units (products) are connected, such as the 3-line sensor and output load, to the same 24V DC power supply unit, add the current con­sumption values of the additional units to the power supply capacity value.
Current consumption (mA)
Unit side I/O side (Note 4)
25 45 30 75 35 150 45 300 25 40 30 60 40 100 45 180
.
Chapter 1
21
Power Supply Capacity of System
Input connector for PLC
8-channel connector input unit
SL-VTP4J

Example: Calculation of current consumption

<System conguration for control of 8 sensors and 4 output loads>
SL-VS1
Chapter 1
Controller End unit Input connector for PLC Output connector for PLC 8-channel connector input unit 4-channel connector output unit 8-channel input terminal Sensors
(Average current consumption: approx. 30mA ) Output loads
(Average current consumption: approx. 20mA )
Power supply unit
SL-VT8J
Designation Model No. Qty Current consumption (mA)
Output connector for PLC
SL-VP1
Controller
SL-VCU1
Sensors
4-channel connector output unit
SL-VCU1 SL-VEU SL-VS1 SL-VP1 SL-VT8J SL-VTP4J SL-VTB8
1 135 1 10 1 30 1 73 1 105 1 60 1 30 + 75 = 105
8 30 × 8 = 240
4 20 × 4 = 80
Total 838
8-channel input terminal
SL-VTB8
Sensors
End unit
SL-VEU
Output loads
22

Calculation of Voltage Drop Value

8
60
Allowable passing
Ambient temperature (˚C)
Power Supply Capacity of System
The transmission cables of the cables themselves. For this reason, calculate the voltage drop value between +24V and 0V, and supply the rat­ed voltage to all the and G, and that of the control cables and connector link cables.
S-LINK V
S-LINK V
I/O units. However, it is not necessary to consider the voltage drop between the D
system may cause voltage drop due to the conductor resistance of the
CAUTION
Use of a longer cable will cause more voltage drop. If the voltage drops below the rated voltage, the I/O units will not work. In this case, use the local power supply unit.
Elongation of the transmission distance will cause more voltage drop at the line end (between +24V and 0V).
Voltage drop (V) = Cable length (m) × 2 × conductor resistance (Ω/m) × current (A)
Relation between the ambient temperature and allowable passing current when exclusive S-LINK V
cable SL-RCM100□ / RCM200 or SL-CBM100 / CBM200 (conductor cross section = 0.5mm
cable) is used.
2
for each
Chapter 1
Rated voltage (V)
CAUTION
The rated voltage depends on the unit. Check the rated voltage, and then select the right power sup­ply unit and cables.
Supply the rated voltage to each unit.
Since the rated voltage to be supplied to the controller is +24V (-5%), the voltage supplied to the con-
troller should not be dropped below the following value:
24 - (24 × 0.05) =
Since the rated voltage to be supplied to the I/O units and end unit is +24V (-10%), the voltage sup-
plied to these units should not be dropped below the following value:
24 - (24 × 0.1) =
22.8V
21.6V
7
6
5
4
current (A)
0
5 10 15 20 25 30 35 40 45 50 55
23
Power Supply Capacity of System

Necessity of Local Power Supply Unit

The 24V DC power supply unit that drives the system uses either the centralized power supply method (use of only one power supply unit) or the decentralized power supply method (use of additional local power supply unit) to supply power to each unit.
At rst, calculate the total current consumption value (sum total of current consumption values of all units ‘+’ sum
total of load current values of I/O devices). After that, from the obtained calculation result, cable length, and conductor resistance, calculate the voltage drop value, and determine the voltage to be supplied to each unit.
If the voltage supplied to each unit is above the rated voltage (22.8V or more for the controller, 21.6V or more for the I/O unit), you can design the system using the centralized power supply method. If the voltage supplied to a unit is out of the rated voltage range, connect a local power supply unit, and use the local power supply method.
Designing of system using local power supply method
Chapter 1
CAUTION
To use a local power supply unit, turn on the local power supply unit rst, and then turn on the main
power supply unit, or turn on these power supply units at the same time.
If the main power supply unit is turned on rst, the system may not operate properly.
In the following cases, connect a local power supply unit:
● The communication distance is too long, and voltage drop is too large.
For this reason, it is not possible to supply the rated voltage to the I/O units.
● A 2-core cable is used for connection of the I/O unit (for the D-G line only).
● The main power supply unit and the local power supply unit should be the small capacity type.
● An I/O device that generates a large noise should be used.
<Reference value>
Conductor cross section (mm2) Conductor resistance (Ω/m)
0.3 Approx. 0.065
0.5 Approx. 0.040
0.75 Approx. 0.025
1.25 Approx. 0.015
2.0 Approx. 0.010
Notes: 1) The conductor resistance values shown in the above table are reference values. To determine the conductor resistance values for the actual cables, contact the cable manufacturer.
2) The conductor cross section of the exclusive 4-core at cable should be 0.5mm2.
To determine whether a local power supply unit is necessary, refer to the owchart shown on the next page.
24
Proposed system construction plan
Calculation of total current consump­tion value (refer to page 22)
Power Supply Capacity of System
ReexaminationReexamination
A unit should be changed or removed
Out of rated range of cable connector (refer to page 157)
Calculation of voltage drop value
(refer to page 23)
Yes
A unit should be changed or removed
A local power supply unit
is needed in view of the calculated
voltage drop value
Yes
No
Yes
Chapter 1
No
No
Necessary
Unnecessary
Decision 1
The I/O device should be
connected using 2-core cable
(for the D-G line only)
No
Decision 2
The main power supply unit and local
power supply machine should be the
small capacity type
No
Decision 3
An I/O device generates
large noise
No
Centrailzed power supply method Local power supply method
Yes
Yes
Yes
25

Connection of DC 2-Wire Output Device to Input Unit

CAUTION
If you have to connect a DC 2-wire output device to an input unit, recommend our product. If a product manufactured by another company is used, the conditions should be checked by follow-
ing the procedure shown in the following owchart. This is because the output device of another company does not t our input unit.
DC 2-wire output device should be used
Chapter 1
Our product is used
Check 1
21.6V-V
=In specied op-
THON
21.6V-V
THOFF
eration voltage range
Check 2
A
21.6V-V
Minimum load current
i
R
Condition A
NO
≥ VA and
YES
YES
YES
NO
Connection to the is not possible
NO
RB1 ≤
Normal connection
S-LINK V
system
The bleeder resistance is necessary
Calulation of bleeder resistance
A
21.6V-V
Minimum load current-
21.6V-V
i
R
Condition B
VA : Residual voltage in ON mode A1 : Leakage current VTH : Input voltage of input unit
THON
V
: Input unit ON voltage
THOFF
V
: Input unit OFF voltage Ri : Input impedance RB : Bleeder resistance
A
Check 3
THOFF
V
≥ A1 (Leakage current
i
R
in OFF mode)
YES
Decision of condition
Condition A
Connection is possible without any bleeder resistor
26
NO
Condition B
Calulation of bleeder resistance
RB2 ≤
A1-
V
THOFF
i
R
THOFF
V
Decision of condition
Condition A
Connection is possible if the RB2 bleeder resistor is attached
Connection is possible if the RB1 bleeder resistor is attached
Condition B
Connection is possible if the RB1 or RB2 (small value) bleeder resistor is attached
Connection of DC 2-Wire Output Device to Input Unit
21.6V - VA of DC 2-wire input device
R1
21.6V-3V
3.3kΩ 3.3kΩ
18.6V
3.3kΩ
4V
V
≥ 0.8mA
+24V
Input device
S-LINK V input unit

Example: Connection of DC 2-wire sensor

To connect DC 2-wire proximity sensor GX-12MU to 8-channel connector input unit SL-VT8J
THON
V
THOFF
V R1 : Input impedance of VA (residual voltage in ON mode) of
Specied operation voltage range of
Minimum load current of A1 (leakage current) of
Check 1
21.6V - 17V = 4.6V ≥ 3V
21.6V - 4V = 17.6V (in range of 10.2 to 26.4V)
Since the requirements of both formulas are satised, carry out checks 2 and 3.
Check 2
Check 3
THOFF
R1
:
=
SL-VT8J SL-VT8J
:
ON voltage = 17V or more (between +24V and data input) OFF voltage = 4V or less (between +24V and data input)
1.21mA
GX-12MU
GX-12MU
SL-VT8J
= 0.8mA
= 3.3kΩ
GX-12MU
GX-12MU
= 3mA
= 3V or less
= 12 to 24V DC
=
+10
% = 10.2 to 26.4V DC
– 5
5.64mA ≥ 3mA
Chapter 1
Since the requirements of Checks 2 and 3 are satised, the bleeder resistor is not necessary.
RB : Bleeder resistance
Main circuit
VTH
Input
Output
R1 : Input impedance
DC 2-wire input device
0V
0V
27

Transmission Delay Time

CAUTION
Due to di󰀨erence in communication protocols, the transmission delay time of the di󰀨ers from that of the conventional
S-LINK
system.
S-LINK V
For transmission, there are fastest transmission time and the slowest transmission time. Since this product uses the serial transmission method, transmission will be carried out as shown in the follow-
ing gure.
For a detailed description of the following controllers, refer to their respective user’s manuals.
SL-VGU1-C, SL-VGU1-D : SL-VGU1-C SL-VGU1-EC SL-VGU1-485 SL-VMEL-Q SL-VFP7
SL-VGU1-EC
:
SL-VGU1-485
:
SL-VMEL-Q
:
SL-VFP7
:
SL-VGU1-D
/
User’s Manual
User’s Manual
User’s Manual
User’s Manual
User’s Manual

Response delay time

<In case of SL-VCU1>
Chapter 1
I/O device
• Sensor
• Switch
• Relay, etc.
S-LINK V system
Input
1. Response time of input device (sensor, etc.)
2. Input
 0.2ms
3. Filtration
4. Refresh time
8. Filtration
Output
10. Output
0.35ms
9. Refresh time
11. Response time of output device (actuator, etc.)
system
PLC
Response delay of S-LINK V system
• Input response time (2 + 3 + 4 + 5)
2 3 4 5 MIN. = 0.2 + From Table 1 + From Table 2 + 0.001 (ms) MAX. = 0.2 + From Table 1 + From Table 2 + 0.001 (ms)
• Output response time (7 + 8 + 9 + 10)
7 8 9 10 MIN. = 0.015 + From Table 1 + From Table 2 + 0.35 (ms) MAX. = 0.015 + From Table 1 + From Table 2 + 0.35 (ms)
5. Output to PLC
0.001ms
7. PLC to Input
0.015ms
6. PLC operation time (scanning time + PLC filtration time)
28
<In case of SL-VFP2, SL-VMEL-Q, SL-VPCI, SL-VVMES2>
Input Output
I/O device
• Sensor
• Switch
• Relay, etc.
S-LINK V system
1. Response time of input device (sensor, etc.)
2. Input
 0.2ms
3. Filtration
4. Refresh time
Transmission Delay Time
10. Response time of output device (actuator, etc.)
9. Output
0.35ms
8. Refresh time
PLC etc.
Response delay of S-LINK V system
• Input response time (2 + 3 + 4 + 5)
2 3 4 5
MIN. = 0.2 + From Table 1 + From Table 2 + From Table 2 (ms) MAX. = 0.2 + From Table 1 + From Table 2 + From Table 2 (ms)
• Output response time (7 + 8 + 9)
MIN. = From Table 2 + From Table 2 + 0.35 (ms) MAX. = From Table 2 + From Table 2 + 0.35 (ms)
<Table 1 Filtration time>
Filtration time (ms)
A mode B mode C mode
MIN. MAX. MIN. MAX. MIN. MAX.
0.05 0.06 0.19 0.26 0.77 1.02
5. Internal memory
Max. 1 refresh time
6. PLC / PC operation time (scanning time)
7 8 9
<Table 2 Refresh time, Internal memory max.1 refresh time>
Number of I/O control points
32 64 2.09 8.36 33.44
96 2.68 10.71 42.85 128 3.27 13.06 52.26 160 3.85 15.42 61.66 192 4.44 17.77 71.07 224 5.03 20.12 80.48 256 5.62 22.47 89.89 288 6.21 24.82 99.30 320 6.79 27.18 108.70 352 7.38 29.53 118.11 384 7.97 31.88 127.52 416 8.56 34.23 136.93 448 9.15 36.58 146.34 480 9.73 38.94 155.74 512 10.32 41.29 165.15
Refresh time, Internal memory max.1 refresh time (ms)
A mode B mode C mode
MIN. MAX. MIN. MAX. MIN. MAX.
1.50
0.29
7. Internal memory
Max. 1 refresh time
6.01
1.18
Chapter 1
24.03
4.70
29
Transmission Delay Time
Power-on
S-LINK V
controller
Occurrence of error
2. Output
0.5ms
S-LINK V
controller
Operation at power-on
1. Time required for power-on (Depends on the supplied power)
Completion of transmission check
● READY output at normal starting
OFF
ON
● READY output at starting after shorting line
Chapter 1
between +24V and 0V or between D and G line
OFF
ON
● Error output 1 and 2
OFF
ON
2. Transmission check
3. Output
0.5ms
READY output
<Table 3 Time required for transmission check at starting controller>
Number of I/O control points
32 69.5 134.3 422.1 64 82.6 186.8 632.2
96 100.4 258.1 917.5 128 123.0 348.3 1278.1 160 150.2 457.2 1713.9 192 182.2 585.0 2225.0 224 218.8 731.6 2811.4 256 260.2 897.0 3473.0 288 306.2 1081.2 4209.9 320 357.0 1284.3 5022.1 352 412.4 1506.1 5909.5 384 472.6 1746.8 6872.2 416 537.5 2006.3 7910.1 448 607.1 2284.6 9023.4 480 681.3 2581.7 10211.8 512 760.3 2897.6 11475.6
Time required for transmission check at starting cotroller (ms)
A mode B mode C mode
READY output delay time (1 + 2 + 3)
1 (Depending on supplied power) + 2 (From Table 3) + 3 (0.5 ms)
Error signal outputting delay time
1. Error check
● Error output 1 and 2
OFF
ON
Error output delay time (1 + 2)
1 (From Table 4 or 5) + 2 (0.5ms)
Error output
<Table 4 Time required for error check (errors 3, 4, and 5)>
Number of I/O control points
32 43.5 174.0 695.8
64 93.4 373.6 1494.3
96 162.1 648.4 2593.8 128 249.6 998.6 3994.4 160 356.0 1424.0 5696.0 192 481.2 1924.7 7698.7 224 625.2 2500.6 10002.4 256 788.0 3151.8 12607.2 288 969.6 3878.3 15513.1 320 1170.0 4680.0 18720.0 352 1389.2 5557.0 22228.0 384 1627.3 6509.2 26037.0 416 1884.2 7536.8 30147.1 448 2159.9 8639.6 34558.2 480 2454.4 9817.6 39270.4 512 2767.7 11070.9 44283.6
Time required for error check (errors 3, 4, and 5) (ms)
A mode B mode C mode
30
<Table 5 Time required for error check (errors 1 and 2)>
Time required for error check (errors 1 and 2) (ms) A mode B mode C mode
1.33 5.32 21.28
Loading...
+ 156 hidden pages