Panasonic M1X User Manual

Page 1
For speed control of 3-phase induction motor
Inverter M1X Series
Operating Instructions
Be sure to provide the customer with a copy of this manual.
Thank you for purchasing a Panasonic Inverter.
Be sure to read the instructions thoroughly before attempting to operate the
inverter. After reading, be sure to keep in a safe place for future reference.
Industrial and Appliance Motor Division, Motor Company
Page 2
CONTENTS
Before use
Preparation and adjustment
Safety Precaution Introduction
When unpacking・・・・・・・・・・・・・8
Inverter model check ・・・・・・・・・8
System Configuration
Wiring general view・・・・・・・・・11
●Wiring ・・・・・・・・・・・・・・・・・・・・・12
●Terminal function ・・・・・・・・・・・13
●Precautions when wiring ・・・・15
・・・・・・・・・・・・8
・・・・・・・4
・11
If necessary
Application
Specifications
Protective Function
●Protective functions・・・・・・・・・18
●Method of resetting trip・・・・・・20
Detailed Explanation of Parameters
●Parameter functions ・・・・・・・・23
Specifications
Outer Dimensions
・・・・・・・・37
・・・ 18
・・23
・・・・39
‑2‑
Page 3
CONTENTS
・・・・・・・・・・・
Precautions
・・・・・・・・・・・ 9
・・・・・・・・・・・・・・・・・・・・・・
Installation
・・・・・・・・・・
・・・・・・・・・・10
・・・・・・・・・・・・・・・・・・・・
Note the following precautions in order to use the inverter properly
・・・・・・・・・・・・9
Parameter Setting
How to set
Maintenance/
・・・・・・・・・・・・・・・・16
・・・・・・・・
・・・・・・・・ 21
・・・・・・・・・・・・・・・・
・・・・
・・・・16
・・・・・・・・
21
2121
・・・・・・・・・・・・・・・・・
Inverter
・・・・・・・・・・・・・・・・・ 10
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
Troubleshooting
・・・・・
・・・・・22
・・・・・・・・・・
22
2222
Before use
調
Adjustment
Preparation and
Inspection
Parameter Setting
Parameter overview
Parameter configuration and list of parameters
・・・
・・・ 41
・・・・・・
・・・・・・・・41
41
4141
・・・・41
Inspection to determine cause of problem
・・・・22
If necessary
Application
tions
Specifica-
‑3‑
Page 4
Safety Precautions
!!!!
Precautions that must be heeded in order to protect the user and others from harm and prevent property loss or damage are as follows:
■■■■
The extent of injury or damage that could be suffered by improper use contrary to directions is ranked and explained as follows:
DANGER
CAUTION
Items labeled as CAUTION could be connected with core serious consequences, depending upon the circumstances. In any case, these instr uctions are ex tremely import ant and should be observed in all cases.
■■■■
Installation
Situation involving danger which could result in death or serious injury if equipment is handled incorrectly.
Situation involving danger which could result in medium to light injury, or property damage if equipment is handled incorrectly.
CAUTION
Install on non-combustible material such as metal. Failure to do so could resu lt in fire.
Do not locate near combustibles. Doing so could result in fire.
Do not carry by the front case when moving the inverter. Doing so is dangerous and could result in injury if dropped.
Do not allow foreign material such as metal chips to get inside the inverter. Doing so could result in fire.
Be sure to install on a base capable of supporting the inverter’s weight in accordance with the directions giving in the instruction manual. Doing so is dangerous and could result in injury if dropped.
‑4‑
Page 5
Safety Precautions
■■■■
Wiring
DANGER
Make sure the power is cut off before handling wiring. Failure to do so could result in electrical shock or fire.
Be sure to install a no-fuse breaker (NFB). Failure to do so could resu lt in fire.
Be sure to ground the GND terminal. Failure to do so could result in electrical shock or fire.
Have wiring work done by an electrician. Failure to do so could result in electrical shock or fire.
Be sure to install the inverter before wiring. Failure to do so could result in electrical shock or fire.
CAUTION
Do not connect the AC power source with the output terminals (U/L1, V/L2, W/L3). Doing so could result in injury or fire.
Make sure the voltage of the AC power source agrees with the rated voltage of the inverter. If not, it could result in injury or fire.
‑5‑
Page 6
Safety Precautions
■■■■
Operation
DANGER
Be sure to mount the case and cover before turning the power on. Never remove the case or cover while the inverter is receiving power. Failure to mount or removing the case/cover could result in electric shock.
The operator should secure the area before turning the power on or off. Failure to do so could result in injury.
Never operate the switches with wet hands. Doing so could result in electric shock.
Never touch the terminals of the inverter when it is charged with power, even when it is not running. Doing so could result in electric shock.
If the retry function is selected, the inverter could unexpectedly start operating again if tripped. Do not approach the inverter in the condition. Doing so could result in injury.
If trip reset is carried out with the operate signal ON, the inverter could unexpectedly start operating again. Do not approach the inverter in the condition. Doing so could result in injury.
CAUTION
The radiator and regenerative resistor become ve ry hot. Touching these parts could result in skin burning injury.
It is very easy to set speed from "low" to "high" by an inverter. Set the operating speed so that it the motor and machine tolerance is not exceeded. Failure to do so could result in injury.
‑6‑
Page 7
Safety Precautions
■■■■
Maintenance/inspection
DANGER
Wait for at least 5 minutes after turning off the power to perform inspections. Failure to do so could result in electric shock.
Maintenance and inspection should not be performed by anyone except a specialist. The repairman should remove all metallic objects (watch, rings, etc.) before performing maintenance or inspection. Use only insulated tools when performing maintenance or inspection. Failure to do so could resu lt in electric shock or injury.
■■■■
Other
DANGER
Absolutely DO NOT modify the inverter in any way. Doing so could result in electric shock, injury or fire.
GENERAL PRECAUTIONS
The diagrams given in this instruction manual may show the cases, covers or safety breakers removed in order to show details. When operating, be sure to return the cases, covers or safety breakers and operate as specified in the manual.
‑7‑
Page 8
Introduction
When unpacking
Is the model correct?Was the equipment damaged in transport?
If there is anything wrong with the equipment, contact your Panasonic dealer.
Inverter model check
Nameplate
M1SO83CSA
M1SO83CSA
M1SO83CSAM1SO83CSA
ModelNo 
Power 15kW Input 3PHAC380〜460V50/60Hz
37A
Output 3PHAC380〜460V0〜400Hz
32A
MIXA54ASA
Product No.
Series name
Code Motor capacity
08 15 22 37 55 75 A1 A5
0.75 kW
1.5 kW
2.2 kW
3.7 kW
5.5 kW
7.5 kW 11 kW 15 kW
Ser.No. 9903012
MatsushitaElectricIndustrialCo.,Ltd.MadeinJapan
Code Interface specs.
A
C
Code Operation panel specs.
S V N
Code Regenerative brake specs.
Without set volume (standard)
Without communicatio n functi on/ standard type (NPN logic) With communication fun ction/ standard type (NPN logic)
With speed-set volume
Blank cover
A
Code Volt age class
4 3-phase 400 V
Consult your Panasonic de aler regarding products with communicat i on f unctions.
Without regenerative brake circuit
B
With regenerative brake circuit (bui lt -in)
‑8‑
Page 9
Precautions
Note the following precautions in order to use the inverter properly.
1. Arrange for the power source capacity to be between 1.5 to 500kVA the inverter's capacity. An excessively high peak current may flow to the power input circuit, and damage the converter section if the wiring length is short with a power source exceeding 500kVA, or the phase-advancing capacitor is switched on the power source side. In this case, pr ovi de indiv idual pow er factor -enha ncing AC reactors that match the inverter's capacity on the inverter input side.
2. Do not connect the phase- adv ancing cap acitor to th e outp ut sid e of th e inver ter. Doing so could result in damage to the phase-advancing capacitor.
3. Do not provide a magnetic contactor between the inverter and motor. To run or turn the motor on/off, use the RUN switch on the control panel or the control input terminal. Avoid frequently turning the magnetic contactor, provided on the power source, on and off.
4. Operating the motor by the inverter could increase leakage current and trip the earth leakage breaker. In this case, use earth leakage bre akers d esig ned for high freque ncy for this system and other systems.
5. Take the following precautions if using a built-in electronic thermal relay contained in the inverter:
Check the rated current of your 3-phase induction m otor, and set the appropriate
electronic thermal value.
Use one motor for each inverter.
6. in using the inverter to dri ve multi ple m otors co nnecte d in parall el, s elect an i nv erter of a capacity that does not exceed the total rated current of the inverter. When calculating by total output of the motor, the inverter’s rated current may be exceeded, depending on the type of motor.
7. The total wiring l ength betw een inv erter a nd mo tor sh ould not exceed 30 m eter s. I f th e wiring is to be longer than this, you should provide a reactor, etc., between inverter and motor.
8. Install the inverter securely to avoid injuries in the case of an earthquake.
9. Before running the inverter following an earthquake, check installation of the inverter and motor and make sure they are safe to operate.
‑9‑
Page 10
Installation
Install the inverter properly to prevent equipment failure or accidents.
Inverter
Installation location
Install the inverter indoors in a place not exposed to rain or direct sunlight. The inverter
is not waterproof.
Install in a place not exposed to c orrosi ve/flamm abl e g ases, gri nding fl ui d, oil mist, metal
powder or chips.
Place with adequate ventilation, w hic h is not exposed to excessive humidity, dirt or dust.Place not subject to vibration.
Environmental conditions
Item Conditions
10 50 (Must not freeze)
Ambient temperature
Ambient humidity
When ambie nt temperature is higher than +40, the air
apron and the linear rubber apron should be disassembled
Max. 90%RHMust be no condensation
Storage temperature
Storage humidity
20 65 (Must not freeze)
Max. 90 %RHMust be no condensation
Vibration Max. 5.9 m/s2(10 〜 60Hz)
Elevation Max. 1000 m
* Short-term temperature during transport
Mounting direction and clearance
Provide sufficient clearance for effective cooling.
30 mm
×
Min. 100 mm
Upper Upper Upper
M1X
Min.
Lower Lower Lower
50 mm
M1X M1X
Min. 50 mm
Min. 200 mm
30 mm
×
Min. 100 mm
Min.
× 30 mm
100 mm
Make sure ambient tem per atur e d oesn’t exceed al low able te mperat ure at p ositi on in dicat ed by X in the figure above.
‑10‑
Page 11
System Configuration and Wiring
A
Wiring general view
Main circuit
No-fuse breaker (NFB) or Earth leakage breaker
Used to protect the power line. Interrupts the circuit in the case of excessive current.
Noise filter (NF)
Blocks noise from the power line.
lso reduces effect of noise from the servomotor .
Magnetic contactor (MC)
Turn main power to servomotor on/off. Used with surge absorber mounted.
Inverter
Motor
Reactor (L)
Reduces harmonic current of the power source.
DC reactor
GND
‑11‑
Page 12
System Configuration and Wiring
I2I3I4
Wiring
Standard wiring diagram
External feedback resistor (5.5 kW-11kW only)
Those lower than 3.7 kW and 15Kw have no terminals for feedback resistor
Power source 3-phase
AC380〜460V
50/60Hz
External frequency setting volume
1/4W, 5k, B characteristic
Frequency meter
1mA (full scale)
Forward/stop switch Reverse/stop switch Frequency setting selection (1) Frequency setting selection (2) Free-run Trip reset
Ground for control
*
Be sure to provide proper treatment for the shielded wire terminals.
NFB
R/L1 S/L2 T/L3
Note1)
5V FIN1
FOUT
12V PLC
I1
I5 16
PB
(Frame ground)
U/T1 V/T2 W/T3
(Collector)
O1
trip output (Collector)
O2
Reach-signal (Emitter)
COM1
V
CE
max.=50mA
I
C
NC
Trip signal
COM2
Contact capacity
NO
AC30V 2A DC30V 2A
Motor
GND terminal
*
*
max.=DC24V
Be sure to ground
Asterisk (*) indicates factory-set function.
Note 1) PLC terminals and 12V ter minal s connect ed, it is called sy nchroniz ed inp ut circui t.
PLC terminals and G terminals connected, it is called power input circuit.
‑12‑
Page 13
System Configuration and Wiring
3
3
Terminal function
Not used
(1) Main circuit terminal
750W〜3700W 5.5kW
R/L1S/L2 T/L3U/T1V/L2
/L
R/L1S/L2 T/L3
Not used
15
Terminal No.
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
R/L1 S/L2 T/L3
Terminal
name
Power source input terminal
Output terminal
Connect to commercial power sourc e (3-phase 380-460V 50/60 Hz)
Connect to 3-phase induction motor
N U/T1 V/T2 W/T3
kW
Function description
PB
〜11kW
U/T1V/T2
/T
E P P terminal (+) terminals for the recitification part
N N terminal (-) terminals for the recitification part
PB PB terminal
GND terminal
Terminal for grounding inverter base
Terminals for external feedback resistor. Connect the resistor between P and PB.
‑13‑
Page 14
System Configuration and Wiring
t
(2) Control terminal
01 02 F1N1 F1N2 FOUT I2 I4 I6 12V
COM2 NC NO COM1 12V PLC G I1 I3 I5 G 5V
Terminal No. Terminal name Function description
Power source
5V
12V
FIN1 FIN2
FOUT
terminal for fre­quency setting
External power terminal
Input terminal for frequency setting
Ground for control
Frequency meter terminal
+ 5VDC applied.
+ 12VDC applied. The common terminal used for contact input of external power is used. When power is on (PLC and G connected), a closed terminal in ON, and an open one, OFF
Frequency can be set when 0 ~ +5VDC (or 0 - +10VDC) is input between “FIN1” and “G”, or 4-20mA between "FI N2"-G. If both are input , the bigger will be pick up.
If using these terminals, change “
Common ground terminal for contact input. The common terminal used for contact input of synchronized input is used. When power is on (PLC and 12V connected), a closed t erminal in ON, and an open one, OFF.
Outputs voltage proportional to output frequency between “FOUT” and “G.” Connect full-scale 1 mA DC ammeter. You can output pulses synchronized with output fr equency by altering “
or
.
frequency command” to
FOUT switch”.
Input terminal
I1
I2
I3 I4 I5 I6
O1 O2
COM1
Forward/stop command terminal
Reverse /stop command terminal
Frequency setting selection terminal
Ground for control
Output signal terminal
Forward by shorting between “I1” and “G”; stop by release Reverse by shorting between “I2” and “G”; st op by release You can change “I1” to run/stop command and “I2” t o forward/reverse command by altering“
You can select the following functions in operation mode.
Operation mode I3 I4 I5
2-speed operation mode
4-speed operation mode 8-speed operation mode 16-speed operation mode
Contact input common ground terminal. Open-collector output termina l. (Not maintained when power is OFF.)
You can select contents by “ Factory setting: “01” is trip signa l (transist or ON when tripped) “O1” (collector) IC max. = 50mA “C1” (emitter) VCE max. = 24VDC
I1.12” function selection.
Forward jogging
Frequency setting selection
Reverse jogging
output signal (1) selection.”
Select from among free-run, external forced trip, No. 2 acceleration/
deceleration, trip rese
Output terminal
NC NO
COM
Output signal terminal
Relay output termina l. 30VDC 1A (max.) (Not maintained when power is O FF. ) You can select output contents by “ Not built-in to products without regenerative brake circuit.
relay output polarity selection.”
‑14‑
Page 15
System Configuration and Wiring
Precautions when wiring
Main circuit
(1) The inverter will be damaged if you invert the connections of the power input terminal
and motor output terminal (U/L1, V/L2 ... W/L3). Absolutely do not invert connections. (2) Do not ground the main circuit terminal. (3) Do not short motor output terminals (U/L1, V/L2 ... W/L3) together. (4) The GND terminal (E) is the frame ground (FG) for the inverter. (5) Be sure to use insulated crimp terminals for connecting to the main circuit terminals.
Control circuit
(1) Do not apply more than 24VDC, 50mA to the output terminals (O1, O2, COM1), or
apply voltage to terminal in reverse. (2) Input terminal configuration is shown in the following figure.
You can control by contact or by open collector output. Do not apply external voltage.
Internal circuits are as follows:
Photo coupler
Inverter internal power source +12V
I1〜I6
GND
(3) Do not short the frequency setting power source terminal (5V) and ground for control
terminal (G). (4) To directly drive the relay by the output terminals (O1, O2, COM), mount a flywheel
diode (FD).
1
O/O2
FD(100V 1A)
<Examples> Fuji Electric ERA15-01
ERB12-01
Pay attention to polarity of diode.
(5) Use shielded wires for the cable to be connected to the control circuit.
‑15‑
Page 16
Parameter Setting
How to set
Operation Panel
r/min Hz
^
^
A V
STOP
DATA
SET
RUN
MODE
2-digit LED
Frequency Hz is displayed when in the normal mo nit or mode. You can display synchronized rotations for the parameter "
5-digit LED
display power."
5-digit LED 2-digit LED
MODE
button
DATA SET
button
Displays output freque ncy, set frequency or display power, cause of error, or parameter.
Displays parameter No. Direction of rotation is displayed in the monitor mode. Switch for changing monitor mo de. Pressing the switch change s t he mode in the
cycle of: Output frequency     Rectificated     Motor current
Switch for selecting parameter No. mode and parameter value mode, setting parameter value.
Mode description
Monitor mode
Parameter No. mode
Displays output freque ncy, rectificated voltage or motor current.
Mode when the power is turned on.
When in the parameter No. mode or parameter value mode, pressing the MODE
Displays parameter No. When in the monitor mode, pressing the DATA SET changes to the parameter No. mode.
switch changes to the monitor mode.
by flashing.
switch
button
RUN button
STOP
button
Parameter value mode
Enable you to select parameters, and set/change contents.
Commands the inverter to run.
Commands the inverter to stop.
Displays parameter content s (set t ing value) by flashing. You can change the setting value with the △ ▽ switches. After changing the setting, press the DATA SET
enter the setting in the memory.
‑16‑
switch to
Page 17
Parameter Setting
Power ON
Push DATA SET
Monitor mode
Push
Output frequency
MODE
Rectificated voltage
MODE
Motor current
Display LED used to show
Use △ ▽ to set or change set speed of speed 0.
Parameter
MODE
Push
MODE
Use △ ▽ to select parameter
number mode
parameter number in
parameter number display
Push
Push DATA SET
Parameter
value mode
Push DATA SET
MODE
LED used to show
parameter value in
parameter number display
Use △ ▽ to select value
‑17‑
Page 18
Protective Function
Protective functions
The protective functions classified as shown below are built-in the inverters of this series.
Functions that do not display a warning, but act to avoid a tripping of the system.Functions that display a warning and shut off inverter output.Functions that trip the inverter. (Trip signal cannot be retained when the power is
turned off.)
Classifi­cation
5-digit LED display Description of prote ct ion Countermeasures, etc.
Electronic thermal relay operation
Monitor display flashes when output current reaches the electronic thermal relay level and the timer operat es.
Electronic thermal relay trip. Be careful of the size of the
load when using. (Monitor) (Flashes)
Acceleration/ deceleration stall prevention
Prevents tripping when acceleration/ deceleration time becomes too long in the following situ ations:
Increase acceleration/
deceleration time or
decrease inertia load. (no display)
DC voltage of the rectificated part
exceeds approx. 775V.
Motor current exceeds inverter’s
current limit operation po int.
Insufficient voltage warning
If DC voltage of the rectificated part drops below approx. 360V, it is
Investigate the wiring and
power source informatio n.
regarded as “instantaneous power Instantaneous power failure protection
failure,” and inverter output is shut o f f.
If it drops below approx. 300V, the
control circuit is reset. If voltage is
*1
restored by the time the control circuit
is reset, operation can be restarted
automatically.
*2
Reverse prevention
*3
Selecting the reverse prevention
function prevents reverse operation if
Check if the reverse command has been given.
the inverter receives a reverse sign al.
Restart prevention when power is restored
*2
Prevents the inverter from restarting
automatically if already given the run
command when power is turned,
After commanding the inverter to stop, command it
to run again. restored following power failure or reset.
*1
The inverter will operate correctly if power failure does not exceed approx. 15ms.
*2
Prevents the inverter from restarting automatically if “ restart prevention when power is restored” is selected for
.
*3
Effective only when “ reverse prevention” is selected for .
‑18‑
Page 19
Protective Function
Classifi­cation
5-digit LED display Description of protection Count ermeasures, etc.
Over-current trip
Regenerative over­voltage trip
Trips if inverter output current exceeds the rated current approx. by 200%.
Trips if DC voltage of the converter rises above approx. 800V.
Possible causes in cl ude drop in power source voltage, excessive
2
load, acceleratio n/
GD deceleration time is set too short , load short, or grounding. Take the proper measures to determine the cause.
If it trips while the inverter is running, deceleration time could be too short. Try setting deceleration time longer. If it trips when the power is turned on, the inductance of the power-boosting AC reactor provided on the input side of the inverter may be too high. Select an AC reactor that matches the inverter capacit y.
Over-voltage trip retry when power is turned on
Over-load trip (Electronic thermal relay)
CPU
error
If over-voltage trip occurs when the power is turned on because the inductance of the power­boosting AC reactor provided on the input side of the invert er is t oo
high, etc., and output is shut off.
The trip is automatically reset when DC voltage of the converter drops below approx. 800V, enabling normal operat ion.
If motor current continues to exceed the electronic thermal relay setting value, load is regarded as being to high causing the function to t r ip.
Trips if a control microcomputer error is detected.
is displayed
*1
The capacity of the power­boosting AC reactor provided on the input side of the inverter may be too large. Select a reactor that matches the inverter capacit y.
Try reducing load, modifying operating pattern, or raising capacity of inverter.
A malfunction caused by outside noise could have occurred. Check the area for noise and remove the source of noise.
*1
Effective only when “ over-voltage trip retry when power is turned on” is selected for .
‑19‑
Page 20
Protective Function
Classifi­cation
5-digit LED display Description of protection Count ermeasures, etc.
Self-diagno sis t rip
External forced trip
Trips if parameter such as “ operation mode selection” is changed.
Trips when “ I5 function selection” is set by external forced trip and I5 – G becomes open. Cancel by trip after shorting.
There is nothing wrong with the equipment. The results of the change become effective when the trip is reset.
Investigate the cause of overlo ad. Try reducing the load, changing the operation pattern, or raising the capacity of the inverter and motor.
Method of resetting trip
In the event of a trip, remove the cause and cancel by one of the following methods.
[1] Turn off the inverter’s power. When the trip display disappears, turn the power
on.
[2] Short between both I1 – G and I2 – G for at least 0.1 seconds while the cause of
the current trip is being displayed.
*1
[3] Press both △ ▽ switches on the operation panel simultaneously for at
least 1 second while the cause of the current trip is being displayed.
[4] Input the trip reset command while the cause of the current trip is being
displayed.
*2
A CPU error cannot be reset by methods 2, 3 or 4. Reset by method 1
given above.
*1
Cannot be reset if “ I1.I2 function selection” is set to I1: Run/stop or I2: Forward/reverse.
*2
Effective only when “ I5 function selection” is selected for .
‑20‑
Page 21
Maintenance/Inspection
You should perform maintenance/inspection on a regular basis in order to ensure safety and keep the inverter in good running order.
Precautions when performing maintenance/inspections
(1) The power should be turned on/off only by the person performing the task. (2) The internal circuits of the inverter remain charged with high voltage for a short while
after power is turned off. To perform inspection, first turn off the power and then wait for the LED display on the front panel to go off (min. 5 minutes).
(3) Do not perform insulation resistance measurement on the inverter. Doing so will
damage the inverter.
Inspection items and environment
Ordinary/normal usage c ondi tions
Ambient conditions: Annual mean temperature 30°C, min. 20 hrs/day at max. load rate 80%
Perform daily and periodic inspections in accordance with the following items:
Classification Inspection cycle Inspection items
Ambient temperatur e, humidit y , dirt, dust, foreign o bjects, etc.
Is there abnormal vibration/noise?
Is main circuit volt age normal?
Daily
inspection
Periodic
inspections
Daily
1 year
Is there strange odor?
Is there lint in the air holes?
Cleanliness of control unit
Is wiring damaged?
Are equipment connections loose or off center?
Are foreign objects lodged in at the load side?
Are fastened sections loose?
Is there evidence of overhe ating?
Are terminal blocks da ma ged?
Caution Inspection cycle for periodic inspections may vary if usage conditions differ from those given above.
Approximate period for part replacement
Period for part replacement varies according to how the inverter is used. Parts must be replaced or repaired when something is wrong with them. Under the ordinary/normal usage conditions.
Product
name
Inverter
Smoothing capacitor Approx. 5 years Cooling fan Aluminum electrolytic
capacitor of PC board
Part name Standard replacement
period (hrs)
23 years (130,000 hrs)
Approx. 5 years
Remarks
Standard replacement period gives a number of years for reference only. If a part becomes faulty it must be replaced even if the standard replacement period has not yet been reached.
‑21‑
Page 22
Troubleshooting
Inspection to determine cause of problem
When a prob lem occurs , perform th e inspe ctions and t ake the m easures pre scribed in the following table. If you cannot determine the cause of the problem, if you suspect that the inverter is not working properly, if a part is damaged, or there are any other problems you cannot solve, contact your Panasonic dealer.
Problem Description of inspection Corrective measures, etc.
Motor doesn’t work.
Motor turns in reverse.
Is there anything wrong with the wiring?
Is power being supplied to the power input terminals?
Is the LED on the operation panel lit? Recheck the above. Is the voltage of the power in put
terminals normal? Is an error being displayed? See “protective function”. Has free-run been commanded? Cancel free-run. Are both the forward AND reverse
switches on? Is there anything wrong with the
frequency setting? Is the motor locked? (Is the load too
heavy?) Is phase interruption operation being
carried out? Is there a mistake in the phase order
of the output terminals (U/T1, V/T2, W/T3)?
Wire correctly.
Turn on the power. Turn off the power once, and then turn back on.
Check power source voltag e.
Turn either the forward OR reverse switch on, and the other off.
Check the frequency sett ing.
Cancel the motor lock. (Reduce the load.)
Recheck the wiring between the inverter and motor.
Match the phase order of the output terminals (U/T1, V/T2, W /T3) with the motor.
The motor runs but speed doesn’t change.
Motor speed is not correct.
Motor speed is unsteady.
Is the load too heavy? Reduce the load.
Are the number of poles and volt age of the motor correct?
Is voltage of the power input terminals (R/L1, S/L2, T/L3) c orrect ?
Is the frequency setting range normal?
Has motor terminal voltage dropped excessively?
Is the load too heavy? Reduce the load. Is load variation too large? Reduce load variation. Raise the
Check the specificat ion manual and name plate.
Check power source voltag e.
lower limit frequency” upper limit frequency”
base frequency” max. output voltage adjustment”
V/F reduction characteristics”
capacity of the inverter and motor.
‑22‑
Page 23
Detailed Explanation of Parameters
Parameter functions
No. Parameter name
Setting frequency (0 speed)
1st speed frequency
nd
speed frequency
2
rd
speed frequency
3
th
speed frequency
4
th
speed frequency
5
th
speed frequency
6
th
speed frequency
7
th
speed frequency
8
th
speed frequency
9
th
speed frequency
10
th
speed frequency
11
th
speed frequency
12
th
speed frequency
13
th
speed frequency
14
th
15
speed frequency
Run command selection
Explanation
Sets the frequency with which you want to run the machine. Valid when “
This sets the frequency when running in multi-speed mode. Valid when “
Allows you to set 4th speed frequency to 15th speed frequency when you select 16 speed running mode for “
Operation Mode
frequency command se lect” is
Running mode select” is higher than 4th speed operation.
Running Mode Select.”
Input Terminal
I 3 I 4 I 5 I 6
8 Speed Operation Mode
16 Speed Operation Mode Frequency Setting Selections
This selects the run command from the following.
(PANEL) :
Frequency Setting
Selections
RUN
switch on the operation panel.
No. 2 Acceleration/
Deceleration
.
Frequency command selection
V alues set at ex-factory.
●  
When
command.
This selects whether to set the 0 speed frequency using “ (0 speed), ” the input terminal for Frequency Setting Selections “F1” or the switch on the main unit.
■  
●  
●  
(TERMINAL) : Input terminals “I1” and “I2” (BOTH): Both operation panel and input terminals are
valid.
is selected, you cannot use the input terminal as the run
setting frequency
" setting frequency (0 speed)"
Analog Command “FIN1”
(Voltage Command) DC 0 to 5 V
Analog Command “FIN1”
(Voltage Command) DC 0 to 10 V
Volume on Main Unit
‑23‑
Page 24
Detailed Explanation of Parameters
No. Parameter name
Operation mode selection
Torque control
Explanation
These are the parameters that select the operation mode.
●    
■    
●    
●   
●    
This adjusts the voltage output of the inverter at a low frequency region.
Be aware that as the settings are
increased, excessive current will flow which will cause a trip.
2nd Speed mode 4th Speed mode 8th Speed mode 16th Speed mode
: Auto-boost Controls for the optimum auto-torque for the
inverter and motor with the same capacity.
: Auto-boost Controls for the optimum a little weaker auto-
torque for the inverter and motor with the same capacity.
Manual torque boost
Maximum output voltage
Large
Output voltage
Small
Base frequency
Output frequency
<Precautions regarding the selection of Auto-boost and slip frequency compensation>
Select parameters when the motor is stopped.
Do not use when running in serial.
There are cases in which the system will be unstable dep end ing on th e c ond itions of
the load. If that should occur, set the manual torque boost. When running at a high power supply voltage, adjust to lower the output voltage of
the inverter using “ adjustment.”
Jogging frequency This sets the frequency for operating in the jogging mode. Acceleration time
This determines the rate of change of the output frequency during acceleration.
Sets the time that changes in 50 Hz.
When set to 0 seconds, ac celerati on is at its op timum sp eed and deceler ation w ill b e
0.01 second. When less than 3 seconds set to 0.01 sec intervals; When 3 to 9 seconds set to 0.1
sec intervals; When 10 seconds or more set t o 1 sec interv als.
: Controls slip frequency compensation.
Controls compensation of the slip frequency for the motor selected by “
motor selection.”
Base frequency” or “ Maximum output voltage
No. 2 Acceleration time
Values set at ex-factory.
This sets the acceleration time of the No. 2 Acceleration. This is valid when you select “ No. 2 accel/decel.time.
I5 Function Selection” in the
‑24‑
Page 25
Detailed Explanation of Parameters
No. Parameter name
No. 3 Acceleration time
No. 4 Acceleration time
DC brake volume DC brake time
DC braking time This selects the type of DC brake.
Starting brake time This runs the inverter after applying the DC brake to the motor for the amount of time
This sets the acceleration time of the No. 3 and No.4 Acceleration. This is valid when you select “ Selection” in the
This adjusts the DC brake time and the DC brake volume when shifting from inverter drive to a stopped state.
- The machine will enter a free-run when either or both the time and volume are set to 0 (zero).
The DC brake time when you select a sudden brake (all regions) will be twice the
time of the positioning brake.
■  
set when you are starting up. This does not function when you set to 0 (zero). The strength (torque) of the DC brake (torque) is the “
but be careful because it does not operate when set to 0.
: Position
Explanation
I5 Function Selection” “
No. 2 accel/decel.time .
 ●
: Sudden stop (all regions)
DC brake volume”
I6Function
Brake start frequency This adjusts the frequency for starting to apply the positioning DC brake.
Carrier frequency variable
Values set at ex-factory.
The DC brake will be applied when the output frequency is lower than “Brake start
frequency” when you cause a soft-stop using the stop command and stop from normal operation.
The DC brake will be applied when lower than 1 Hz regardless of the settings of
“Brake start frequency” when it stops because the frequency settings are low while in normal operation.
This is the parameter that selects the carrier frequency. This selects the following 8. Change the carrier frequency when the motor is stopped.Do not change while it is operating.
Setting value Carrier frequency Setting value Carrier frequency
0 1.2kHz 4 8.0kHz
12.6kHz■5 10.1kHz 2 3.9kHz 6 12.0kHz 3 6.0kHz 7 14.9kHz
‑25‑
Page 26
Detailed Explanation of Parameters
A
e
(
)
No. Parameter name
Explanation
Deceleration time This determines the rate of change of the output frequency when decelerating.
Sets the time that changes in 50 Hz.When set to 0 seconds, acceleration is at its optimum speed and deceleration will
be 0.01 second.
When less than 3 seco nds set to 0.01 sec intervals; When 3 to 9 seconds set to 0.1
sec intervals; When 10 or more seconds set t o 1 sec interv als. No. 2 Deceleration time
This sets the deceleration time of the No. 2 Deceleration. This is valid when you selec t “
I5 Function Selectio n” in the
accel/decel.time. No. 3 Deceleration time
This sets the deceleration time of the No. 2 Deceleration.
This is valid when you select “
Selection” in the
No. 2 accel/decel.time.
I5 Function Selection” “
No. 4Deceleration time Base frequency This sets the base frequency (maximum
Maximum output voltage
frequency of the torque region) to any
frequency within the range of 30 to 400 Hz
that matches the motor rating.
Output voltage 0
Output frequency
I6Function
Adjustment range
(30 ~ 400Hz)
Base frequency
No. 2
Max. Output voltage adjustment
V/F reduction characteristics
Values set at ex-factory.
This adjusts the maximum output voltage
(base frequency voltage). The range of
adjustment is 0 to 100%.
Maximum output voltage
100 : Power supply
voltage
Output voltage
Output frequency
djustment rang
0 ~ 100%
Base frequency
This adjusts the V/F characteristics to match
the load characteristics.
●   
Rated torque load
  
Reduction torque load
1.0
Output voltage
Large
Base frequency Output frequency
You can make fine adjustments between 1.0
and 2.0.
Note: This is valid only when you have selected “torque control” in the manual boost.
‑26‑
Page 27
Detailed Explanation of Parameters
0
No. Parameter name
No. 2 V/F selection No. 2 V/F base frequency No. 2 V/F boost
Explanation
This sets the special V/F pattern using “No. 2 V/F selection.”
This selects the No. 2 V/F upper pattern
set using the normal V/F and “No. 2 V/F base frequency” and “No. 2 V/F boost.”
■   
●   
●   
Normal pattern
Upper pattern
Lower pattern
Note: This is valid only when you have selected “torque control” in the manual boost
or the lower pattern
No. 2 V/F
Output voltage
Normal V/F
0
Output frequency
Upper selection
Output voltage
0
Output frequency
Lower selection
Output voltage
0
Output frequency
.
Jump frequency width Jump frequency 1 Jump frequency 2 Jump frequency 3 Jump frequency 4
This creates areas that cannot set the
frequency in a range set by “
Jump frequency width” above and below as the center of the frequency set by “ frequency 1” to “
Jump frequency 4”
Jump
Set frequency
Frequency Frequency Frequency
1 2 3
Frequency command (Between FIN and G)
in order to avoid mechanical resonance.
Acceleration time outputs the frequency even in the jump region.
If jump frequency ranges are overlapped, it jumps all overlapping ranges.
I1/I2 function selection This switches the input terminals “I1” and “I2” in the following manner.
Input terminal
(
Fwd-Stop/Rev-Stop
Between “I1” and “G” Between “I2” and “G”
Short Open Short Open
Forward
Operation
Stop
Operation Stop
Reverse
Operation
Reverse Forward
Run-Stop/Fwd-Rev)
Jump frequency width
Stop
Values set at ex-factory.
‑27‑
Page 28
Detailed Explanation of Parameters
No. Parameter name
I5 function selection I6 function selection
Multi-speed input selection
Explanation
This selects the input terminals “I5” functions in the following manner.
●    :
“Terminal” – “G” Short
●      :
“Terminal” – “G”
●      :
selection
“Terminal” – “G” short
■  
This selects the type of frequency setting for multi-speed operation.
“Terminal” – “G” short
Set the status of the short “Terminal” – “G” before selecting “ When open, a trip occurs.
(FREE)
(THeRmal)
(UpDown)
(ReSeT)
(1bit):1 bit input
Free-run Stop
External forced trip command
No. 2 acceleration and deceleration time
Trip reset command
.”
Not used
Values set at ex-factory.
This selects 1 type of multi-speed frequency for 1 terminal of the “Frequency setting selection terminals.” This runs the inverter in 3 speeds in 4 speed operation mode and 4 speeds in 8 speed operation mode.
Ex.) With 8 speed mode operation
Input terminals
I3 I4 I5
Open Open Open
Short
Open Short
Open Open Short
■  
This selects the frequency by setting “Frequency setting selection terminals” in binary.
××
×
(Binary):Binary input
Frequency setting
No. 0 speed
frequency
No. 1 speed
frequency
No. 2 speed
frequency
No. 3 speed
frequency
Open and short
are related to “G” and terminals.
・× means there
is no relationship between short and open.
‑28‑
Page 29
Detailed Explanation of Parameters
No. Parameter name
Output signal 1 selection Output signal 2 selection
Explanation
This selects the output signal between output terminals “O1” to “O2” in the following manner.
■   :
●   :
Trip output signal (When trip: ON*)
Arrival signal (When arrival: ON*)
●     :
●   :
Run/Stop signal (When run: ON*)
Free-run singnal (While Free-run: ON*)
●       :
Forward operation signal (While forward operation: ON*)
●       :
●   :  →
Reverse operation signal (While reverse operation: ON*)
Output frequency detection signal
Refer to:
(TRIP)
(STaBLe)
(RUN)
(FREE)
(Fwd)
(Rev)
(CheckF)
Compare frequency A” and “
Compare frequency B”
●   :  →
●   :
●   :
Motor current detection signal
Refer to “
DC brake signal (While DC brake: ON*)
Trip cause detection signal
(CheckC)
Motor current detection level”*
(DC-Brake)
(CAUS)
The following signals are output when a trip occurs.*
Trip contents
Normal over-current
Acceleration over-current
Deceleration over-current Over-voltage External forced trip
Electronic thermal CPU error
ON time
Continuous
3 seconds
1 second 1 second
0.25 second 0.25 second
0.9 second
0.1 second
OFF time
1 second
3 seconds
1 second
0.1 second
0.4 second
Values set at ex-factory.
* “
selection.”
Self-diagnosis
output signal 1 selection” can invert “
‑29‑
0.5 second
output signal 1 polarity
0.5 second
Page 30
Detailed Explanation of Parameters
No. Parameter name Explanation
Relay output selection
This selects the output signal w hen the rel ay output b etween “NC,” “CO M 2” and “NO” is used. Trip output signal
●  
●    
●    
(TRIP):Trip output signal (When trip: Between “NC” and “COM 2”: O pen, Betw een “NO” and “COM2”:Closed)
(STaBLe):Arrival signal (When arrival: Between “NC” and “COM2”: Open, Between “NO” and “COM2”: Closed)
(RUN):Run/stop signal (When run: Between “NC” and “COM2”: Open Between “NO” and “COM2”: Closed)
(FREE):Free-run signal (When free-run: Between “NC” and “COM2”: Open, Between “NO” and “COM2”: Closed)
(Fwd):Forward operation signal (When forward operation: Between “NC” and “COM2”: Open, Between “NO” and “COM2”: Closed)
(Rev):Reverse operation signal (When reverse operation: Between “NC” and “COM2”: Open, Between “NO” and “COM2”: Closed)
Motor current detection level
Output signal 1 polarity selection
Current limit operating point
Values set at ex-factory.
Set the current level you want to detect using a percentage for the rated current of the inverter when you selected “ selection” in exceeds the detection level you set and it will turn “OFF” when it is below.
This function inverts the polarity of the output signal between output terminals “O1” and “COM1.”
■  
●  
This limits the operating point for the motor current that was set. Numbers are percentages for the inverter rated current.
(NORmal): When operation: transistor “ON” (REVerse): When operation: transistor “OFF
(Check-F):Output frequency detection signal
 →"   Refer to “
(Check C):Motor current detection signal  →Refer to “
. The output terminal will operate when the motor current
Compare frequency A,” and
Compare frequency B."
Motor current detection level.”
Output signal 1 selection” and “
Relay output
‑30‑
Page 31
Detailed Explanation of Parameters
No. Parameter name Explanation
Stall deceleration magnification
Acceleration mode switch
Deceleration mode switch
This adjusts the decelerat ion tim e when the stall prevention function of the decelerati on is operating.
 ・Set in percentages for the deceleration time of the normal setting. This selects the straight line acceleration/deceleration or curved line (S) acceleration/
deceleration independently.
Output frequency
This is a general acceleration mode to accelerate and decelerate on a straight line up to the set frequency.
Straight line ●   S Shape 1 ●   S Shape 2
Time
utput frequency
Base frequency
0
Time
With large output of the motor torque, the incline is steep and when the output torque is small, the incline is gentle.
Output frequency
f2
f1
0
Time
This shows an S characteristic between running frequencies f1 t o f2.
This is a smooth accelera­tion and deceleration characteristic.
* This changes using the acceleration and deceleration time set when under the base
frequency if you select  
S shape 1, but when over the base frequency,
the incline is gentler than the set time.
Monitor mode switch This selects the content that displays in the 4 digit LED.
Display magnification This sets the magnification of the value that displays in the 4 digit LED. This displays
Values set at ex-factory.
The value to which the “
display magnification” was applied is displayed with the
frequency display.
■  
●  
Output frequency ● Set frequency Converter unit DC voltage
Output current
the motor synchronized rotation or the line speed. * The parameters related to frequency (below) display the value to which the display
magnification was applied when you change the display magnification.
〜〜〜〜 0 to 8th speed frequency” " 〜〜〜 Compare frequency"
"
Jogging frequency"    "Matching detection width"
"
Brake start frequency"    " Instantaneous drop frequency"
" " 〜〜〜 Jump frequenc y"  "Lower limit frequency"
Frequency meter full scale indication"  " Upper limit frequency"
"
‑31‑
Page 32
Detailed Explanation of Parameters
No. Parameter name Explanation
Frequency meter adjustment
Frequency meter full scale indication
This calibrates the frequency meter. Adjust using the △ ▽ switches so that the needle on the frequency meter points at the full scale.
This indicates the frequency when using the frequency meter full scale. This is set to 60 Hz full scale at ex-factory so adjust to be used higher than 60 Hz.
“FOUT” switch This selects the frequency signal to output to the frequency output terminal “FOUT.”
■  
●  
Frequency analog output Frequency digital output
Current analog outp ut Compare frequency A Compare frequency B
This sets the frequency to detect when you selected “ output signal 1 selection” and “
relay output selection” in the output frequency detection signal
.
- The output signal is ON when the outp ut fre que ncy exceeds*1 “compare frequency A”
and is OFF when it is less
Output frequency
0
ON
Between “01” and “COM”
*1
than “compare frequency B.”
Output frequency
A
B
0
ON
ON ON
Between “01” and “COM”
A
B
Match detection width This adjusts the timing to output the arrival signal during acceleration and deceleration
Values set at ex-factory.
When A ≧ B
when you selected “ the
arrival signal.
output signal 1 selection” and “ relay output selection” in
When A < B
- The arrival signal is output when the difference of the output frequency and the set
frequency is smaller than “match detection width.”
- The arrival signal is not output when 0 is set.
- The arrival signal is not output when forward/reverse are switched when stopped
or during DC brake.
- The arrival signal is output until immediately before stopping when “ brake
start frequency” < “match detection width.”
‑32‑
Page 33
Detailed Explanation of Parameters
No. Parameter name Explanation
Instantaneous drop frequency
Instantaneous free­run time
Restart prevention when power is restored
Retry selection Retry start time
This adjusts the output frequency after instantaneous stop or after the power is restored.
- This starts the output from the value that subtracted “Instantaneous drop
frequency” from the output frequency of the instantaneous detection when power was restored.
- It starts running from 0.5 Hz in the same way as when turning on the power under
normal conditions even though power is restored and the control circuit was reset when the power cut was long.
This adjusts the free-run time after instantaneous stop or restoring power.
This prevents restarting after an instantaneous stop or after power was restored by setting
You can try to continue running by automatically canceling the trip after “Retry start time” even when a trip occurs. This will retry (re-execute) the set number of times but if a trip does not occur in over approximately 120 minutes, the retry count will be initialized.
  
.
(NO): Does not retry
●     〜     :Retries the set number of times
Outputs a trip signal and stops when the set number of retries is reached but does
not output the trip signal (when trip is “ output signal 1 selection” and “ relay output selection”) during a retry.
* The retry function is invalid when Restart prevention when power is restored is set
to
Frequency setting bias
Lower limit frequency This sets the lower limit of the inverter output frequency. Upper limit frequency This sets the upper limit of the inverter output frequency. Constant for input
filter
This sets the “0 V input frequency” of the frequency setting input terminal “FIN1.”
This sets the constant for input filter of the voltage or the current’s frequency setting signal from an external source.
* Increase the constant of the filter if you cannot attain stable operation because of
the effects of noise. As you increase the setting value, response will worsen.
.
Set frequency
0V
0 V input frequency Frequency setting voltage
5 V input fr e que nc y
5V
(Between “FIN1” and “G”)
Values set at ex-factory.
‑33‑
Page 34
Detailed Explanation of Parameters
No. Parameter name Explanation
Over-voltage trip retry when power is turned on
Reverse prevention Electronic thermal
relay
This displays the   on the power when you set to  
Also, the trip is automatically canceled at the point the DC voltage falls below approximately 400 V on the converter.
※ The display will change from   to    and it will consider the
normal over-voltage trip when you continue the over-voltage beyond a prescribed amount of time after turning on the power supply.
This prevents the trouble caused by reversing when you set to   This adjusts the amount that the electronic
thermal relay functions. Set the percentage for the inverter’s rated
current.
The operation panel display unit will flash
when the motor current exceeds the set value.
It is necessary to check the ambient
temperature when the setting is higher than the ex-factory setting.
and trips when an over-voltage trip occurs when turning
.
.
1 min.
50 100 150
Operating time
0
100% 150%
Parameter value
200%
Motor current
Trip cause clear This clears the cause of the trip.
<How to clear>
Trip cause 1 Trip cause 2 Trip cause 3 Trip cause 4 Trip cause 5
Parameter initialization
Use the
is.
After the display extinguishes, it will be cleared when the power is turned back on.
Switch the power supply again if the inverter does not operate in this state and use
after turning on the power again. This remembers the latest 5 trips. Refer to “Monitor” for details regarding the content of the display.
This initializes and returns all parameters to our standard ex-factory settings. <How to initialize>
Use the
is.
After the display extinguishes, it will be init ializ ed w hen the power i s turned bac k on.
switch to switch the power supply with the setting   as it
will be displayed in the 4 digit LED.
switch to switch the power supply with the setting   as it
will be displayed in the 4 digit LED.
Switch the power supply again if the inverter does not operate in this state and use
after turning on the power again.
‑34‑
Page 35
Detailed Explanation of Parameters
No. Parameter name Explanation
Motor selection
Start-up starting frequency
Automatic voltage regulation reference voltage
Automatic voltage regulation selection
Parameter lock This locks the parameters that you set.
Set the motor volume and polarity to use when you selected compensation control) using “
* Select the motor when it is stopped. This sets the inverter output starting frequency.
This increases the starting torque but it is close to a direct startup and is not
appropriate for a shock-less start. Also, there are cases of a trip occurring depending on the load.
This selects the motor’s rated voltage when using automatic voltage regulation.
This corrects the output voltage and suppresses the variations in the output voltage for the variations of the input power supply voltage.
However, you cannot output the value higher than the maximum output voltage or the input power voltage.
Does not lock parameters
torque control.”
(slip frequency
Locks all parameters. Locks parameters for which setting is unnecessary.
Setting to switches become invalid. None of the parameters can then be set.
RUN and STOP switches are valid
Setting to
parameter extraction.”
Parameter copy This copies parameters.
Reads parameters to panel. Writes parameters to main unit. Parameters initialization on operation panel
Motor rated current This sets the motor rated current when using the slip frequency compensation control.
*
1
Motor current without load
This sets the motor current without load when using the slip frequency compensation control.
Does not copy parameters.
*
1
locks all parameters and the MODE △
allows setting of only the parameters selected by the “
‑35‑
Page 36
Detailed Explanation of Parameters
No. Parameter name Explanation
Motor 1 primary resistance
Slip correction gain Adjusts the slip correction gain when using slip frequency compensation control.
Sets the motor 1 primary resistance w hen usi ng slip fre quen cy compe nsatio n control.
*1
Slip correction response time
Parameter extraction This extracts the parameter. Refer to “How to Extract Parameters” for details.
*1
Because slip frequency compensation control requires a motor constant, set to our standard motor constant that was set at ex-factory. Set the motor constant to use when driving another motor.
Sets the slip correction res pons e t ime w hen us ing sl ip frequency compensation control.
‑36‑
Page 37
Specifications
Part Number M1X 84BSA M1X154BSA M1S224BSA M1X374BSA
Applicable motor (kW) Output capacity (kVA) Rated output current (A)
Rated output
Rated output voltage
Voltage 3-phase AC 380 to 460 V
Frequency 50/60Hz
Allowable voltage flu ctua tion
Power source
Allowable frequency fluctuation
Control method Low noise sine wave PWM style
Output frequency range 0.5 to 400 Hz (Start and stop from 0.5 Hz)
Frequency accuracy ± 0.5%(25°C ± 10°C
Frequency s etti ng r es ol uti on
Frequency setting signal
Voltage/Frequency
characteristics
Rated overload current 150%/minute
Regenerative brake
torque (Short time)
Control method
Acceleration/deceleration
Jogging frequency range 0 to 30Hz
Protective functions
Ambient conditions
Protective structure Built-in the panel (IP40) (With ventilation cover)
DC brake Brake start frequency/break operating time/brea k volume adjustable.
time
Operation mode
Others
Ambient temperature
Ambient humidity Relative humidity: 90% max. (No dew condensation is allowed)
Atmosphere Indoor (place free from corrosive gas and dirt or dust)
Altitude 1000m max.
Vibration 5.9m/s2 (0.6G) max. (10 to 60Hz)
Cooling method Self-cooling method
Weight (kg) 2.9
*1
*2
*3
・ ・
0.75 1.5 2.2 3.7
2.0 3.0 4.4 7.2
2.5 3.7 5.5 9.0 3-phase AC 380 to 460 V
-15%, +10% ± 5%
Digital: 0.01 Hz Analog: Setting frequency range/1000 Hz (minimum 0.05 Hz)
DC0 to +5V, 0 to +10V , 4 to 20mA
Base frequency: 30 to 400 Hz (1 Hz step), with reduced torque
pattern
150% min.
(Short time)
(0 to 3s: 0.01s step, 3 to 10s: 0.1s step, 10s or more: 1s step)
Time that changes in 50 Hz. Adjustable to a maximum of 4
kinds of acceleration/deceleration speeds.
2-speed operation mode, 4-speed operation mode,
8-speed operation mode, 16-Speed operation mode
Automatic boost, slip frequency compensation control selectable
AVR function/retry function selectable, parameter lock available
Insufficient vol t ag e pr ot ecti on, ov er-c urrent protecti on, over vol ta ge pr ot ec ti on,
instantaneo us po wer fail ur e pr otection, stall prev ent i on, over -l oa d li mit ati on (c urr e nt
limiter), overl oad tr i p (el ectri c thermal relay), rest ar t pr eve nt i on wh e n po wer is
restored, self- di ag nos i s tr i p (the l ast 5 c aus es of tri ps ar e st ored)
-10°C to +50°C (No dew condensation is allowed.)
When the ambient temperature exceeds +40°C, mount a ventilation
cover and rubber bush.
100% min.
(Short time)
0 to 3600 s(seconds)
(Short time)
70% min.
*1
Applicable motor: For Panasonic 3-phase in duction motor (4 poles)
When using another motor, select the motor within inverter ratings.
*2
Output capacity: If the rated output voltage is 460V.
*3
Output voltage does not become higher than the pow er source voltage.
‑37‑
Page 38
Specifications
Part Number M1X554BSA M1X754BSA M1XA14BSA M1XA54ASA
Applicable motor (kW) Output capacity (kVA) Rated output current (A)
Rated output
Rated output voltage
Voltage 3-phase AC 380 to 460 V
Frequency 50/60Hz
Allowable voltage flu ctua tion
Power source
Allowable frequency fluctuation
Control method Low noise sine wave PWM style
Output frequency range 0.5 to 400 Hz (Start and stop from 0.2 Hz)
Frequency accuracy ± 0.5%(25°C ± 10°C
Frequency s etti ng r es ol uti on
Frequency setting signal
Voltage/Frequency
characteristics
Rated overload current 150%/minute
Regenerative brake
torque (Short time)
Control method
Acceleration/deceleration
Jogging frequency range 0 to 30Hz
Protective functions
Ambient conditions
Protective structure Closed model (IP20)
DC brake Brake start frequency/break operating time/brea k volume adjustable.
time
Operation mode
Others
Ambient temperature
Ambient humidity Relative humidity: 90% max. (No dew condensation is allowed)
Atmosphere Indoor (place free from corrosive gas and dirt or dust)
Altitude 1000m max.
Vibration 5.9m/s2 (0.6G) max. (10 to 60Hz)
Cooling method Self-cooling method
Weight (kg) 7.8 8.5
*1
*2
*3
・ ・
When the ambient temperature exceeds +40°C, mount a ventilation
5.5 7.5 11 15
10.4 12.8 19.2 25.5
13.0 16.0 24.0 32.0 3-phase AC 380 to 460 V
-15%, +10% ± 5%
Digital: 0.01 Hz Analog: Setting frequency range/1000 Hz (minimum 0.05 Hz)
DC0 to +5V, 0 to +10V, 4 to 20 mA
Base frequency: 30 t o 400 Hz (1 Hz step), with reduced torque
pattern
70% min.
(Short time)
(0 to 3s: 0.01s step, 3 to 10s : 0.1s st e p, 10s or m or e: 1s st ep)
*Time that chan ges in 50 H z. A d j ust a bl e to a ma xi mu m of 4 kin ds of
2-speed operation mode, 4-speed operation mode,
8-speed operation mode, 16-Speed operation mode
Automatic bo ost , AV R fu nct i on/r et r y func ti on s electable
Slip frequency compensation control selectable, parameter lock available
Insufficient vol t ag e pr ot ecti on, ov er-c urrent protecti on, over v olta g e pr ot ect i on,
instantaneo us po wer fail ur e pr ot ection, stall prevent i on, over -l oa d li mit ati on (c urr e nt
limiter), overl oad tr i p (el ectri c thermal relay), rest ar t pr eve nt i on wh e n po wer is
restored, self- di ag nos i s tr i p (the l ast 5 c aus es of tri ps ar e st ored)
-10°C to +50°C (No dew condensation is allowed.)
50% min.
(Short time)
0 to 3600 s(secon ds )
acceleration/deceleration speeds.
cover and rubber bush.
30% min.
(Short time)
20% min.
(Short time)
*1
Applicable motor:For Panasonic 3-phase ind uct ion motor (4 poles)
When using another motor, select the motor within inverter ratings.
*2
Output capacity If the rated out put voltage is 460V.
*3
Output voltage does not bec ome higher than the power source v olt age.
‑38‑
Page 39
Outer Dimensions
●●●● MIX 0.75 〜〜 3.7kW
(Mounting dimension)
(Mounting dimension)
●●●● MIX 5.5 〜〜〜 11 kW
(Mounting dimension)
(Mounting dimension)
‑39‑
Page 40
Outer Dimensions
●●●● MIX 15 kW
(Mounting dimension)
(Mounting dimension)
‑40‑
Page 41
Parameter Setting
Parameter overview
Inverters of this series hav e vari ous parameters th at adjust /set charact eristics and functions, etc. The objectives and functions of various parameters are described herein. Get a good understanding of the parameters and use to adjust inverter to the best condition for the customer’s operating conditions.
Parameter configuration and list of parameters
Parameter settingNo. Parameter name
*1
Setting frequency (0 speed)
1st speed frequency 2nd speed frequency 3rd speed frequency 4th speed frequency 5th speed frequency 6th speed frequency 7th speed frequency 8th speed frequency 9th speed frequency 10th speed frequency 11th speed frequency 12th speed frequency 13th speed frequency 14th speed frequency 15th speed frequency
Run command selection
Frequency command selection
Operation mode selection
Adjustment range Min. unit Factory setting Check
0 0.50upper limit frequency 0 0.50upper limit frequency
0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency 0 0.50upper limit frequency
- 0〜10V (4-20 mA)
Operation panel Terminal block,
Both Operation panel Volume
- 0〜5V (4-20 mA)
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
0.01Hz
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
2, 4, 8, 16, speed operation mode 4 speed
operation mode
0Hz
50Hz 30Hz 15Hz
0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz 0Hz
*1
Parameters marked by in the Check column are tripped for safety if modified or memorized. Release the trip
to use.
*2
The minimum unit is 0.05 Hz when the setting frequency is min. 160 Hz.
‑41‑
Page 42
Parameter Setting
Adjustment range Min. unit
0 100
Torque control
Jogging frequency Acceleration time 5 sec
No. 2 acceleration time No. 3 acceleration
0〜3600 sec 3
time No. 4 acceleration time
DC brake volume
Case of
DC brake time
0〜3 sec Case of ­ 0〜6 sec
DC brake selection
-
Starting brake time Brake start frequency
Carrier frequency variable
Deceleration time 5 sec
, Automatic boost(standard) Automatic boost(little)
Slip correction control
0 0.530 Hz
sec10 sec : 0.1 sec interval
10
sec :1 sec interval
0 〜 100%
Positioning Sudden stop
0 〜 3 sec
0.50 〜 400 Hz 0,1,2,3,4,5,6,7
Parameter settingNo. Parameter name
3
sec : 0.01 sec interval
:
:
∗2
Factory setting
2
20
0.01 Hz 7 Hz
5 sec 5 sec 5 sec
270
0.05 sec
0.1 sec
0.05 sec
0.01 Hz
*2
0.5 sec
1.0 sec
0 (non­operational)
3 Hz
5
Check
*1
Not used 5 sec Not used
0〜3600 sec 3
No. 4 deceleration
sec10 sec : 0.1 sec interval
10
sec :1 sec interval
time Base cycle Max. output voltage
adjustment V/F reduction characteristics
No. 2 V/F selection
No. 2 V/F base frequency
No. 2 V/F boost
30 〜 400 Hz
0 〜 100%
1.0 〜 2.0 squared No selected
(usually V/F pattern)
Upper selection
Lower selection
30 〜 400 Hz
0 〜 100%
*1
Parameters marked by to use.
*2
Rated current is 90% if carrier frequency of 3 or 4 is selected. Rated current is 80% if carrier frequency of 5,6 or 7 is selected.
     in the Check column are trippe d for saf ety if modifie d or me morized. Rele ase the trip
3
sec : 0.01 sec interval
5 sec 5 sec
1 Hz 50 Hz
1 100
0.1 1.0
1 Hz 50 Hz
200
‑42‑
Page 43
Parameter Setting
Adjustment range Min. unit
Jump frequency width
Jump frequency 0、 0.50400 Hz Jump frequency 0、 0.50400 Hz Jump frequency 0、 0.50400 Hz Jump frequency 0、 0.50400 Hz
I1: Forward/Stop
I1/I2 function selection
0 0.50400 Hz
I2: Reverse/Stop
I1: Run/Stop
I2: Forward/Reverse
Parameter settingNo. Parameter name
*1
0.01 Hz
0.01 Hz
0.01 Hz
0.01 Hz
0.01 Hz
Factory setting
*2
*2
*2
*2
*2
Check
0 Hz 0 Hz
0 Hz 0 Hz 0 Hz
I5 function selectio n
Not used
Multi-speed input selection
Not used Output signal
selection
Not used
Relay output signal selection *Effective only when relay output terminals NC, C2 or NO are used.
Free-run
External forced
- No. 2 acceleration/deceleration Trip reset
1 bit Binary
Trip Arrival Running Free-run
Forward Reverse
- Output frequency detection
- Motor current detection Trip cause
- DC brake
Trip Arrival Running Free-run
Forward Reverse
- Output frequency detection
- Motor current detection
Motor current detection level
Output signal polarity selection
50150%
Forward polarity, Reverse polarity
5% 100%
*1
Parameters marked by      in the Chec k colu mn ar e trippe d for saf ety if modifie d or me morized. Rele ase the trip to use.
*2
The minimum unit is 0.05 Hz when the setting frequency is min. 160 Hz.
‑43‑
Page 44
Parameter Setting
Adjustment range Min. unit
Current limit operation point Stall time deceleration power Acceleration mode switching Deceleration mode switching
Monitor mode switching
Display power Frequency meter
adjustment Frequency meter full scale indication
FOUT switching
Comparison frequ ency A Comparison frequ ency B Agreement detection width
Reduced frequency at instantaneous stop Instantaneous stop free­run time
Restart prevention when power is restored
Retry selection Retry start time
Frequency setting bias Lower limit frequency
Upper limit frequency Constant for input filter
Over-current trip retry when power i s tu rned on
Reverse prevention
Electronic thermal relay
frequency
Restart prevention
(Maximum frequency-0.01) Hz
(Minimum frequency-0.01)
50〜200%
124816
Straight line - S-curve
- Set frequency
- Output frequency
- DC voltage
Output current
0.1 60.0
---
0 400 Hz
Digit Digital output for frequency Needle Analogous output for
Analogous output current
00.50400 Hz 00.50400 Hz 00.50400 Hz
00.50400 Hz
12345
Restart
No retry
0120 sec
0-50 Hz
00.5
400 Hz
12345
No retry Retry Reverse Reverse prevention
30150%
Parameter settingNo. Parameter name
10% 180%
- S-curve
0.1 1.0
1 Hz 60 Hz
0.01 Hz
0.01 Hz
0.01 Hz
0.01 Hz
Retry No. of set times
2 sec 4 sec
0.01 Hz 0 Hz
0.1 Hz
0.1 Hz
*2
*2
*2
*2
11
*2
*2
5% 115%
Factory setting
8
0 Hz 0 Hz 3 Hz
3 Hz
0 Hz
60 Hz
-
1
Check
*1
*1
Parameters marked by to use.
*2
The minimum unit is 0.05 Hz when the setting frequency is min. 160 Hz.
     in the Check column are trippe d for saf ety if modifie d or me morized. Rele ase the trip
‑44‑
Page 45
Parameter Setting
Adjustment range Min. unit
Trip cause clear Trip cause Trip cause Trip cause Trip cause Trip cause
① ② ③ ④ ⑤
Parameter initialization Motor selection
Start-up starting frequency Automatic voltage adjustment reference voltage Automatic voltage adjustment selection
Parameter lock
Parameter copy
Motor rated current Motor current
without load Motor primary resistance
Slip correctio n gain Slip correction
response time Parameter extraction Parameter No. - -
---
---
---
---
---
Motor capacity No. of motor poles
0.5010 Hz
380,400,440,460V 380
No automatic voltage adjust-
ment
- Automatic voltage adjustment
- No automatic voltage adjust­ment only when decelerating
No parameter lock All parameters locked Parameters that don’t need to
be set locked
Parameters not copied
Parameters read-out to panel
side
Parameters written in inverter
side
Parameters initialization on
operation panel
0 100A 0 100A
0 100Ω
01234567 01234567
Parameter settingNo. Parameter name
Factory setting
Check
4 poles,
*2
inverter capacity
*3
0.01 Hz 1
0.1 -
0.1 -
0.01 ­4 0
*1
*1
Parameters marked by      in the Chec k colu mn ar e trippe d for saf ety if modifie d or me morized. Rele ase the trip to use.
*2
Motor capacity is : 0.2kW, : 0.4kW, : 0.8kW.
*3
4-pole motor of same capacity as inverter rating set when shipped from the factory.
‑45‑
Page 46
Servicing (Repair)
Repair
Consult your Panasonic dealer for repairs of your Panasonic inverter.
Consult your machine or device manufacturer when the inverter is installed in a machine or device.
For your convenience: (Please fill in the blank when you need to consult for repairs.)
Date purchased
Shop purchased
Year/Month/Date
Phone number
Model number
Industrial and Appliance Motor Division, Motor Company, Matsushita Electric Industrial Co. , Ltd.
7-1-1 Morofuku, Daito-shi, Osaka, 574-0044 Japan Phone: 072-871-1212
IMAZZ S0796‑0
‑46‑
Page 47
MEMO
‑47‑
Page 48
MEMO
‑48‑
Page 49
MEMO
‑49‑
Page 50
‑50‑
Loading...