Panasonic CW-XC51LE Service Manual

Service Manual
Order No RAC0008058C4
Room Air Conditioner
CW-XC51LE
2001 PT. National Gobel Air Conditioner Division.
All right reserved. Unauthorized copying and distribution is a violation of law.
! WARNING
Specification
Model CW-XC51LE Phase Double Voltage 220 V Frequency 50 Hz Cooling Capacity 1.47 kW
5000 Btu/h Running Current 2.1 A Input Power 440 Watt EER 11.1 Btu/W.h Starting Current Compressor Output Fan Motor Output Moisture Removal 0.9 Ltr/h
Noise Level Indoor High 46 dB
Low 41 dB
Outdoor High 50 dB
Low 47 dB Air Circulation 5.1 m3/min Dimension Height : 340 mm
Width : 525 mm
Depth : 610 mm Net Weight 29 Kg Gross weight 31 Kg Refrigerant (R-22) 330 g
Note : Specification are subject to change without notice, for further improvement.
There are special components used in this equipment which are important for safety. These parts are marked by ! in the Schematic Diagrams, Circuit Board Diagrams, Exploded Views and Replacement Part List. It is essential that these critical parts should be replaced with the manufacturer’s parts to prevent shock, fire or other hazards. Do not modify the original design without permission of the manufacturer.
IMPORTANT SAFETY NOTICE
Panasonic
PanasonicPanasonic
Panasonic
PanasonicPanasonic
PanasonicPanasonic
Panasonic
- 1 -
CONTENTS
1 Functions ........................................................... 2
2 Refrigerant Cycle diagram ............................... 4
3 Block Diagram ................................................... 4
4 Wiring Diagram .................................................. 5
5 Air Conditioner Performance Evaluation ....... 5
6 Troubleshooting Guide ..................................... 6
7 Operation Details ............................................... 7
8 Operating instructions ..................................... 10
9 Air ConditionerInstallation ............................. 15
10 Care and Maintenance ................................. 17
11 Service Information ....................................... 18
12 Exploded View .............................................. 19
13 Replacement Part List .................................. 20
14 Electronic Part List ........................................ 21
15 Electronic Circuit / Indicator Complete ...... 21
16 Electronic Circuit / Main ............................... 22
17 Technical Data .............................................. 22
18 Electronic Circuit Diagram ........................... 23
1 Functions
1.1 Remote Control
OPERATION
TEMP/TIMER
TIMER
SET/
CANCEL
MODE JET MODE
FAN SPEED
Panasonic
Signal Transmitter
Operation OFF/ON
Operation Mode Selection
Fan Speed Selection
Jet Mode Operation OFF/ON
OPERA-
TION
FAN
SPEED
JET
MODE
High Fan Speed or Low Fan Speed
Jet Mode operation for fast cooling
MODE
Cooling Operation Mode or Fan Operation Mode
TIIMER
To set delay OFF Timer.
TEMP/ TIMER
Cooling Operation Mode
- Temperature Setting ( 16oC ~ 30oC )
SET/
CANCEL
To start delay OFF or cancelation
Timer Operation Setting
Room Temperature and Timer Setting
Delay OFF Timer OFF/ON
Timer Setting
- Timer Setting ( 1 ~ 12 hours )
- 2 -
1.1 Main Unit
Operation OFF/ON
Remote Control signal Receiving Sound
Operation Indicator Light (LED’S)
OPERA-
TION
Can be enable/disable by pressing down Operation OFF/ON button for 10 seconds.
MODE COOL (Green)
FAN (Orange)
Lights up in Cooling Mode Operation. Lights up in Fan Mode Operation.
FAN SPEED HIGH (Orange)
MED (Orange) LOW (Orange)
Lights up in High Fan Speed Operation. Lights up in Medium Fan Speed Operation. Lights up in Low fan Speed Operation.
TIMER (Orange)
Lights up in Timer Setting.
JET MODE (Orange)
Lights up in Jet Mode Operation.
Operation Mode Selection
Fan Speed Selection
Jet Mode Operation OFF/ON
Jet Mode operation for fast cooling
FAN
SPEED
JET
MODE
High Fan Speed or Low Fan Speed
MODE
Cooling Operation Mode or Fan Operation Mode
TIIMER
To set delay OFF Timer.
Timer Operation Setting
Room Temperature and Timer Setting
TEMP/ TIMER
Cooling Operation Mode
- Temperature Setting ( 16oC ~ 30oC )
Timer Setting
- Timer Setting ( 1 ~ 12 hours )
SET/
CANCEL
To start delay OFF or cancelation
Delay OFF Timer OFF/ON
Random Auto Restart Control
Random auto restart after power failure at previous setting mode.
Freeze Prevention Control
Freeze prevention control for the Evapora­tor. (Cooling Operation Only)
Starting Current Control
Fan Motor is delayed for 1.6 seconds when Compressors starts simultaneously.
Time Delay safety Control
Restarting is inhibited for approximately 3 minutes.
60 Secs. Forced Operation Control
Once the compressor is activated, it does not stop within the first 60 seconds. However, it stops immediately with remote control stop signal.
Compressor Reverse Rotation Protection Control.
To protect compressor from reverse rotation when there is an instantaneous power failure.
Over Load Protector
Overload protector will trip to protect the compressor when it is overheated.
Panasonic
- 3-
2 Refrigeration Cycle
2.1 CW-XC51LE
3 Block Diagram
3.1 CW-XC51LE
capillary tube
INDOOR SIDE
OUTDOOR SIDE
CONDENSOR
Intake air sensor
COMPRESSOR
EVAPORATOR
Overload Protector
Indicates the electronic control unit.
“C” Indicates the number of core wires. (Example : 7C = 7 core wires)
ZNR1
Transformer
Double Phase AC 220V 50 Hz
Electronic Controller
RY-PWR
Thermal Fuse (113oC)
Fuse (3.15A)
RY-H
RY-L
Indicator Complite
10 C
Fan
Motor
Comp.
7 C
4 C
Sensor
Wireless Remote Control Transmitter
- 4 -
4 Wiring Diagram
4.1 CW-XC51LE
POWER SUPPLY CORD 1φ
, 50Hz 220V
BLUE
YELLOW/GREEN
CAPACITOR
COM PRESSOR
RED
BLUE
BROWN
R S
C
RED
RED
OLP
YELLOW
YELLOW
TRANSFORMER
BLACK T1 (BLK)
BLACK T2 (BLK)
CN-T(WHT)
FUSE
ZNR
BLUE
RED
WHITE
C-FM (RED)
AC (WHT)
CN-DISP1 (WHT)
CN-DISP1 (WHT)
CN-DISP2 (WHT)
CN-DISP2 (WHT)
RY-H
RY-L
C C
CN-FM
(GRN)
7 5 3 1
YELLOW
ORANGE
RED
BLUE
YELLOW/GREEN
FAN MOTOR
CN-TH(YLW)
1 2 3 4
SENSOR (INTAKE.TEMP)
YELLOW
BLUE
RED
TRADE MARK
COMPRESSOR TERMINAL
10 9 8 7 6 5 4 3 2 1
w w w w w w w w w w w w w w w w w
7 6 5 4 3 2 1
RY-PWR
P L
ELECTRONIC CONTROLLER (RECEIVER AND DISPLAY)
10 9 8 7 6 5 4 3 2 1
7 6 5 4 3 2 1
WIRELESS
REMOTE CONTROL
REMARKS WHT : WHITE YLW : YELLOW BLK : BLACK GRN : GREEN
5 Air Conditioner Performance Evaluation
Suction & Discharge Air Temperature Difference
- 8 C and over
- 8 C and over
- Under 8oC
- Under 8oC
- Under 8oC
Current
- As specified.
- Higher than specified.
- Higher than specified.
- Lower than specified.
- Higher than specified by 50%
Determination
- Nothing wrong.
- Nothing wrong, outdoor temperature is too high, heat radiation is not efficient.
- something is preventing heat radiation.
- leakage of refrigerant or refrigerant systems is blocked.
- Compressor defect.
Remedy
- None
- Improve heat radiation.
- Excessive amount of refrigerant.
- Improve heat radiation.
- Locate and repair leak.
- Flush refrigeration cycle.
- Replace the compressor.
- 5 -
- 6 -
6 Troubleshooting Guide
Warning :
Disconnect unit from electrical power supply before making any electrical checks. Discharge the capacitor before checking it.
Check
1. Supply Voltage.
2. Fuse box or Circuit Breaker.
3. Power cord or wiring harness.
4. Temp. Setting.
1. Objects around fan.
2. Resistance between wires.
3. Capacitor Fan Motor.
1. Temperature setting.
2. Resistance between terminal and the compressor body.
3. Resistance between terminals.
4.
Overload Protector (OLP)
.
5.
Capacitor Compressor.
1. Thermostat setting.
2. Air filter dirty.
3.
Location of installation.
4.
Evaporator/Condensor coil
obstructed
.
5. Unit capacity to small or room to big.
6. Temperature and current difference.
1. Source of noise.
1. Unit installation.
2. Drain Tray-styrofoam pieces blocking drain channel.
Result
Less than 10% by rated. Open Contacts.
Pulled loose or shorted. Higher than room temperature.
Locked fan.
Shorted/Open circuit. Ohm Meter doesn't deflect.
Higher than room temperature. Shorted.
Shorted. Infinity between terminals
.
Ohm Meter doesn't deflect. Higher than room temperature.
Clogged or dirty. Sunlight hitting outdoor side obstacles.
Clogged or dirty. Not satisfied. Refer performance
evaluation. Vibration.
Intermitten noise.
Tilted to inside the room. Clogged.
Cause
Costumer restarted unit immidiatelly without waiting 3 minutes.
Fan hitting cowling of foreign materials. Frozen Bearings. Shorted or burned out.
Capacitor defect. Winding coil touch to the body Rare shorted or burn out.
Overload Protector (OLP) broken
.
Capacitor defect. Restricted air circulation.
Restricted heat exchanger. Restricted heat exchanger.
Restricted air circulation.
Leakage of refrigerant or refrigerant systems is blocked. Faulty installation.
Fan hitting object. Refrigerant tubing touching
each other. Fan splash Drain water.
Restricted run off
.
Clogged or blocked.
Remedy
Consult to an electician. Repair open circuit. Wait for 3 minute. Repair or replace it.
Set it to lower. Adjust fan position setting
.
Remove foreign materials
. Replace wires. Replace capacitor fan motor.
Set it to lower. Replace compressor.
Replace compressor terminals. Replace Overload Protector. Replace capacitor compres­sor. Set it to lower. Clean or replace air filter. Consider to build an awning. Remove obstacle or reinstall unit. Clean by steam cleaner.
Replace the unit with bigger capacity. Locate and repair leak. Flush refrigeration cycle. Reinstall unit or reinforce the installation. Adjust fan position or remove foreign materials. About 1/2" Clearance.
Set the drain outlet downward, so that the drain water can run off.
Tilt unit to out side slightly. remove the foreign materials.
Trouble
Fan Motor and Compressor won't run.
Fan Motor won't run
Compressor won't run (Fan motor runs).
Insufficient Cooling
Noise
Water Dripping
7 Operation Details
7.1 Fan Mode Operation
Fan operation only. Fan in operation according to Remote Control or main Unit ( Touch panel) Setting.
7.1.1 Manual Setting of Fan Speed
Basic Fan Speed can be manually adjusted (Lo, Hi) by using the Fan Speed Selection Button/Pad at Remote Control or Main Unit (Touch Control Panel).
7.2 Cooling Mode Operation
Cooling in operation according to Remote Control or Main Unit ( Touch Control Panel) setting.
7.2.1 Time delay Safety Control ( 3 Minute)
When the compressor is stopped by Operation Switch at the Remote Control or Main Unit (Touch Control Panel), it restart after 3 minutes when the Operation Switch at the remote Control or Main Unit (Touch Control Panel) is turned ON.
When the setting temperature is reached during cooling operation, the compresor stops and it will not startfor 3 minutes.
Protection of compressor to balance the pressure in the refrigeration cycle for 3 minutes.
7.2.2 7 minutes Time Saved Control
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor On temperature and OFF temperature.
7.2.3 Starting Current Control
When the compressor and fan motor are simultaneously started, the fan motor will operate 1.6 second later.
7.2.4 Freeze Prevention Control
If the temperature of the indoor heat exchanger falls con­tinuously below 1°C for 3 minute or more, the compres­sor turns off to protect the heat exchanger from freezing. The fan spee setting remains the same. Compressor restarts when the heat exchanger tempera­ture rises to 12°C (Recovery).
* 3 Minutes waiting of Time Delay Safety control is valid for Cooling Operation.
7.2.5 Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and heat exchanger is - 15°C for 2 minutes, compressor will stop and restart automatically ( Time Delay Safety Control is valid).
Indoor Heat Exchanger Temperature
(°C)
Compressor OFF
Recovery
12
1
3 min
Compressor start for 5 Minutes
T -15° C for 2 Minutes
Compressor
OFF
Compressor
restarts (3 minutes
waiting)
T = Intake air temperature - Indoor heat exchanger temperature. This is to protect reverse rotation of the copressor when there is an instantaneous power failure.
- 7 -
7.3 Jet Mode Operation
7.2.6 Cooling Operation Time Diagram
This Operation automatically will be running under High Fan speed, even if the LED shown the Low Fan Speed.
Purpose of this operation is to cool down room temperature at faster speed compare to normal operation.
When Jet Mode button is pressed, target temperature is shifted -3
o
C from the previous setting, for remote control setting from 19oC to
16oC, setting temperature shifted only to 16oC, the minimum setting temperature.
Operation LED
Fan
Compressor
Basic Time
Intake Temperature
1.5oC
ON
OFF
Set
Temperature
3’
7’ 3’
60’
7’
60’
Operation Stop
a b c d e f g h i j k l
< Description of operation > b - c : Time Delay Safety Control ( waiting for 3 minutes). d - e : 7 Minutes Time Saved Control. g - h : 60 sec. forcible operation
Jet Mode operation will stop with the following condition :
- Jet Mode button is pressed again.
- Jet Mode operation has run for 15 minutes
- Stopped by OFF/ON switch
- Timer OFF activates.
7.4 Random Auto Restart Control
Restart time is decided randomly with 5 parameters :
- Intake air temperature.
- Setting temperature
- Fan speed
- Indoor heat exchanger temperature.
If there is a power failure, operation will be automatically restarted after 3 to 4 minutes when the power is resumed. It will start with
previous operation mode (Time Delay Safety Control is Valid). as the operation was not stopped by Remote Control or main Unit (Touch Control Panel).
Auto Restart Control is not available when Timer is set.
If Jet Mode is set during power failure, then after power resume, Jet Mode will not start automatically with previous operation mode.
The control can be omitted by opening jumper JX1 on Printed Circuit Main Board.
- 8 -
Loading...
+ 17 hidden pages