1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
2.INSTALLATION SITE SELECTION ................... 5
2-1. Indoor Unit
2-2. Outdoor Unit
3.HOW TO INSTALL THE INDOOR UNIT ............. 7
3-1. Remove the Rear Panel from the Unit
3-2. Make a Hole
3-3. Install the Rear Panel on the Wall
3-4. Remove the Grille to Install the Indoor Unit
3-5. Shape the Indoor Side Tubing
3-6. Wiring Instructions
3-7. Recommended Wire Length and Diameter
3-8. Wiring Instructions for Inter-unit Connections
3-9. Mounting
3-10. Drain Hose
5-1. Use of the Flaring Method
5-2. Flaring Procedure with a Flare Tool
5-3. Caution before Connecting Tubes Tightly
5-4. Connecting Tubing between Indoor and
Outdoor Units
5-5. Insulation of Refrigerant Tubing
5-6. Taping the Tubes
5-7. Finishing the Installation
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
For safe installation and trouble-free operation, you
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard
WARNING
CAUTION
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to
follow the instructions in this document.
SPECIAL PRECAUTIONS
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location for
easy maintenance.
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
*URXQGWKHXQLW following local electrical codes.
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When Connecting Refrigerant Tubing
:KHQSHUIRUPLQJpiping work
do not mix air except for specified refrigerant (R410A) in
refrigeration cycle. It causes
capacity down, and risk of
explosion and injury due to
high tension inside the refrige-
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
2
rant cycle.
5HIULJHUDQWJDVOHDNDJHPD\
cause fire.
'RQRWDGGRUUHSODFHUHIULJHUDQW
other than specified type.
It may cause product damage,
burst and injury etc.
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other heat
source, it can produce dangerously toxic gas.
The illustrations are based on the typical appearance of
a standard model. Consequently, the shape may differ
from that of the air conditioner that you are installing.
3
1. General
This booklet briefly outlines where and how to install the
air conditioning system. Please read over the entire set
of instructions for the indoor and outdoor units and make
sure all accessory parts listed are with the system before
beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Unit
Table 1
PartsFigureQ’tyPartsFigureQ’ty
Remote
controller
Remote control
holder
Tapping screw
1
1
Rawl plug
Truss-head
Phillips
5
/32 x5/8" (4x16 mm)
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
PartsFigureQ’ty
10
Clamp
8
Cushion
rubber*
1
4
AAA alkaline
battery
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the narrow
and wide tubing, fittings and insulation. Consult your
nearest sales outlet or air conditioning workshop.
1-4. Type of Copper Tube and Insulation Material
2
Drain hose
adapter
1
2.Foamed polyethylene insulation for the specified
copper tubes as required to precise length of tubing.
Wall thickness of the insulation should be not less
than 5/16" (8 mm).
3.Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. Refer to 3-6.
Wiring Instructions for details.
If you wish to purchase these materials separately from
a local source, you will need:
1.Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4"
(30 cm to 40 cm) to dampen vibration between units.
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
4
1-5. Additional Materials Required for Installation
1.Refrigeration (armored) tape
2.Insulated staples or clamps for connecting wire
(See local codes.)
3.Putty
4.Refrigeration lubricant
5.Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
WARNING
AVOID:
To prevent abnormal heat generation and the possibility of fire, do
not place obstacles, enclosures
and grilles in front of or surrounding the air conditioner in a way
that may block air flow.
Indoor unit
2" (5 cm)
min.
Outside drainage
Fig. 1
6" (15 cm)
min.
Drain hose
2" (5 cm)
min.
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length
(L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television,
radio, telephone, security system, or intercom. Electrical noise
from any of these sources may affect operation.
Front View
Fig. 2
INDOOR
UNIT
Elevation
difference (H)
Fig. 3a
CAUTION
For stable operation of the
air conditioner, do not
install wall-mounted type
indoor units less than 5'
(1.5 m) from floor level.
Tubing length (L)
OUTDOOR
UNIT
Indoor unit
Minimum height
from floor level
5' (1.5 m)
Floor level
Wall
Fig. 3b
Table 3
Max. Allowable Tubing Limit of TubingLimit of ElevationRequired Amount of
ModelLength at ShipmentLength (L)Difference (H)Additional Refrigerant
CS-KE18NKU25100500.27
CS-KE24NKU33100500.27
* If total tubing length becomes 25 to 100 ft. (Max.) or 33 to 100 ft. (Max.), charge additional refrigerant (R410A) by 0.27 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
(ft.)(ft.)(ft.)(oz./ft.)*
5
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)
damp, humid or uneven locations.
NO
Hot air
Exhaust fan
Heat source
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5a or 5b)
provide a solid base (level concrete pad, concrete block,
4" 1'4" (10 40 cm) or 6" 1'4" (15 40 cm) beams
or equal), a minimum of 4" (10 cm) or 6" (15 cm) above
ground level to reduce humidity and protect the unit
against possible water damage and decreased service
life. (Figs. 5c and 5d or 5e)
CAUTION
install cushion rubber under unit’s feet to reduce
A solid base must not cover
the hole of the bottom plate.
vibration and noise. (Fig. 5f)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
install in a location where no antenna of a television
or radio exists within 10' (3 m).
(CU-KE18NKU)
Air intake
Concrete
or equal
About 1'4" (40 cm)
About 4" (10 cm)
Anchor bolts
(4 pcs.)
Min. 4" (10 cm)
Outdoor unit
(CU-KE18NKU)
Air intakeMin. 4" (10 cm)
Min.
2" (5 cm)
Air discharge
(CU-KE24NKU)
Air intakeMin. 6" (15 cm)
Min.
4" (10 cm)
Air discharge
Drain holes
Fig. 4
Valve
side
Min. 10"
(25 cm)
Min.
1'4" (40 cm)
Fig. 5a
Valve
side
Min. 10"
(25 cm)
Min.
1'8" (50 cm)
Fig. 5b
Obstacle above
Min.
7' (2 m)
Air discharge
Ground
Obstacle above
Min.
7' (2 m)
Air discharge
Ground
Min. 6" (15 cm)
Air intake
Min.
7' (2 m)
Obstacle
Min. 4" (10 cm)
Air intake
Min.
7' (2 m)
Obstacle
(CU-KE24NKU)
Air intake
Concrete
or equal
About 1'4" (40 cm)
Fig. 5d
Fig. 5e
Anchor bolts
(4 pcs.)
Min. 6" (15 cm)
About 6" (15 cm)
Fig. 5c
Cushion rubber
Fig. 5f
6
3. How to Install the Indoor Unit
3-1. Remove the Rear Panel from the Unit
(1) Remove and discard the set screw on the rear
panel. (Fig. 6)
(2) Press the 2
marks on the frame cover and disen-
gage the stationary tabs from the frame. (Fig. 7)
(3) Remove the rear panel.
NOTE
Tubing can be extended in 5 directions as shown in Fig.
8. Select the direction you need providing the shortest
run to the outside unit.
When left tubing is to be done, switch the drain hose
and drain cap. (For details, refer to “Switching drain
hose and drain cap” on page 15.)
3-2. Make a Hole
(1) Place the rear panel from the indoor unit on the wall
at the location selected. Make sure the panel is horizontal, using a carpenter’s level or tape measure to
measure down from the ceiling. Wait until after cutting the hole before attaching the rear panel to the
wall.
(2) Determine which side of the unit you should make
the hole for tubing and wiring. (Fig. 9)
NOTE
Left
tubing
Set screw only for transportation
Fig. 6
Rear panel
Fig. 7
Left-rear
tubing
marks
Right-rear
tubing
(recommended)
Right tubing
In the case of left-rear tubing, use the measurement
points 2-3/8" (60 mm) from the edge of the rear panel for
precise placement of the hose outlet. (Fig. 9)
(3) Before making the hole, check carefully that no
studs or pipes are directly run behind the spot to be
cut.
CAUTION
Also avoid areas where electrical wiring or conduits are
located.
The above precautions are also applicable if tubing
goes through the wall in any other location.
Downward tubing
Fig. 8
2-3/8" (60 mm)
Fig. 9
7
g
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and
Fig. 10.
Table 4
Hole Dia.
3-5/32" (80 mm)
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a
slight angle 1/4" (6 mm) shorter than the thickness of
the wall. (Fig. 11)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert the pipe in the wall. (Fig.
12)
3-3. Install the Rear Panel on the Wall
Be sure to confirm that the wall is strong enough to suspend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 8 screws
provided. (Fig. 13)
NOTE
Hole should be made at a slight downward slant to the
outdoor side.
Indoor
side
Outdoor
side
Fig. 10
PVC pipe (Locally purchased)
Cut at sli
ht angle
Fig. 11
INSIDEOUTSIDE
Wall
Plastic cover
(Locally purchased)
PVC pipe
Slight
angle
If you are not able to line up the holes in the rear
panel with the beam locations marked on the wall,
use rawl plugs or toggle bolts to go through the
holes on the panel or drill 3/16" (5 mm) dia. holes in
the panel over the stud locations and then mount the
rear panel.
(2) Double check with a carpenter’s level or tape mea-
sure that the panel is level. This is important to
install the unit properly. (Fig. 14)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise
and vibration.
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" (4.8 mm) dia. holes in the wall. Insert rawl
plugs for appropriate mounting screws. (Fig. 15)
Fig. 12
Fig. 13
Fig. 14
3/16"
(4.8 mm) dia. hole
Rawl plug
Fig. 15
8
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.