Panasonic cs-ke18nku, cs-ke24nku operating instructions

APPENDIX B
CS-KE18NKU + CU-KE24NKU CS-KE24NKU + CU-KE24NKU
INSTALLATION INSTRUCTIONS
(852-6-4190-579-00-1)
A-2
INSTALLATION INSTRUCTIONS Split System Air Conditioner
This air conditioner uses the refrigerant R410A.
NOTE
External diameter of service port R410A: 5/16"
Model Combinations
Combine indoor and outdoor units only as listed below.
Model No.
Indoor Unit Outdoor Unit
CS-KE18NKU CU-KE18NKU
CS-KE24NKU CU-KE24NKU
Power Source: 60 Hz, single-phase, 230/208 V
Contents
Page
IMPORTANT!
Please Read Before Starting .................................. 2
1. GENERAL .......................................................... 4
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 5
2-1. Indoor Unit 2-2. Outdoor Unit
3. HOW TO INSTALL THE INDOOR UNIT ............. 7
3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Remove the Grille to Install the Indoor Unit 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Recommended Wire Length and Diameter 3-8. Wiring Instructions for Inter-unit Connections 3-9. Mounting 3-10. Drain Hose
4. HOW TO INSTALL THE OUTDOOR UNIT ....... 17
4-1. Wiring Instructions for the Outdoor Unit
5. REFRIGERANT TUBING .................................. 18
5-1. Use of the Flaring Method 5-2. Flaring Procedure with a Flare Tool 5-3. Caution before Connecting Tubes Tightly 5-4. Connecting Tubing between Indoor and
Outdoor Units 5-5. Insulation of Refrigerant Tubing 5-6. Taping the Tubes 5-7. Finishing the Installation
6. AIR PURGING................................................... 20
Air Purging with a Vacuum Pump (for Test Run)Basic Functions of the Service ValvesPump DownService Valve Connections
7. REMOTE CONTROLLER INSTALLATION
POSITION ......................................................... 24
7-1. Mounting on a Wall
8. ADDRESS SWITCH .......................................... 25
8-1. Address Setting of the Remote Controller
CV6233187211
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
When Installing…
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard
WARNING
CAUTION
or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improp­er installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
Select an installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
Keep the fire alarm and the air
CAUTION
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
outlet at least 1.5 m away from the unit.
WARNING
 'RQRWVXSSO\SRZHUWRWKHXQLWXQWLODOOZLULQJDQGWXELQJ
are completed or reconnected and checked.
 +LJKO\GDQJHURXVHOHFWULFDOYROWDJHVDUHXVHGLQWKLV
system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
 *URXQGWKHXQLW following local electrical codes.
 &RQQHFWDOOZLULQJWLJKWO\/RRVHZLULQJPD\FDXVHRYHU
heating at connection points and a possible fire hazard.
 7RSUHYHQWSRVVLEOHKD]DUGVIURPLQVXODWLRQIDLOXUH
the unit must be grounded.
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
When Connecting Refrigerant Tubing
 :KHQSHUIRUPLQJpiping work
do not mix air except for speci­fied refrigerant (R410A) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high tension inside the refrige-
WARNING
 9HQWLODWHWKHURRPZHOOLQWKHHYHQWWKDWUHIULJHUDQW
gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
2
rant cycle.
 5HIULJHUDQWJDVOHDNDJHPD\
cause fire.
 'RQRWDGGRUUHSODFHUHIULJHUDQW
other than specified type. It may cause product damage, burst and injury etc.
 8VHWKHIODUHPHWKRGIRUFRQQHFWLQJWXELQJ
 $SSO\UHIULJHUDQWOXEULFDQWWRWKHPDWFKLQJVXUIDFHVRI
the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
 &KHFNFDUHIXOO\IRUOHDNVEHIRUHVWDUWLQJWKHWHVWUXQ
 'RQRWOHDNUHIULJHUDQWZKLOHSLSLQJZRUNIRUDQLQVWDOODWLRQ
or re-installation, and while repairing refrigeration parts. Handle liquid refrigerant carefully as it may cause frost­bite.
When Servicing
 7XUQWKHSRZHU2)) DWWKHPDLQSRZHUER[PDLQV
before opening the unit to check or repair electrical parts and wiring.
 .HHS\RXUILQJHUVDQGFORWKLQJDZD\IURPDQ\PRYLQJ
parts.
 &OHDQXSWKHVLWHDIWHU\RXILQLVKUHPHPEHULQJWRFKHFN
that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
CAUTION
 9HQWLODWHDQ\HQFORVHGDUHDVZKHQLQVWDOOLQJRUWHVWLQJ
the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
 &RQILUPXSRQFRPSOHWLQJLQVWDOODWLRQWKDWQRUHIULJHUDQW
gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
 'RQRWWRXFKWKHDLULQOHWRUWKHVKDUSDOXPLQXP
fins of the outdoor unit. You may get injured.
 'RQRWVLWRUVWHSRQWKHXQLW\RXPD\IDOOGRZQ
accidentally.
 'RQRWVWLFNDQ\REMHFWLQWRWKH)$1&$6(
You may be injured and the unit may be damaged.
NOTE
The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing.
3
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Unit
Table 1
Parts Figure Q’ty Parts Figure Q’ty
Remote controller
Remote control holder
Tapping screw
1
1
Rawl plug
Truss-head Phillips
5
/32 x5/8" (4x16 mm)
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
Parts Figure Q’ty
10
Clamp
8
Cushion rubber*
1
4
AAA alkaline battery
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop.
1-4. Type of Copper Tube and Insulation Material
2
Drain hose
adapter
1
2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16" (8 mm).
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-6. Wiring Instructions for details.
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub­ing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
Table 2
Model
CS-KE18NKU 1/4" (6.35 mm) 0.0314" (0.8 mm) 1/2" (12.70 mm) 0.0314" (0.8 mm)
CS-KE24NKU 1/4" (6.35 mm) 0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)
Outer Dia. Thickness Outer Dia. Thickness
Narrow Tube Wide Tube
CAUTION
*Packed in the outdoor unit.
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
4
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes.)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
WARNING
AVOID:
To prevent abnormal heat genera­tion and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surround­ing the air conditioner in a way that may block air flow.
Indoor unit
2" (5 cm)
min.
Outside drainage
Fig. 1
6" (15 cm) min.
Drain hose
2" (5 cm)
min.
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 3 and Fig. 3a.
install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.
Front View
Fig. 2
INDOOR UNIT
Elevation difference (H)
Fig. 3a
CAUTION
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5' (1.5 m) from floor level.
Tubing length (L)
OUTDOOR UNIT
Indoor unit
Minimum height from floor level
5' (1.5 m)
Floor level
Wall
Fig. 3b
Table 3
Max. Allowable Tubing Limit of Tubing Limit of Elevation Required Amount of
Model Length at Shipment Length (L) Difference (H) Additional Refrigerant
CS-KE18NKU 25 100 50 0.27
CS-KE24NKU 33 100 50 0.27
* If total tubing length becomes 25 to 100 ft. (Max.) or 33 to 100 ft. (Max.), charge additional refrigerant (R410A) by 0.27 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
(ft.) (ft.) (ft.) (oz./ft.)*
5
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)damp, humid or uneven locations.
NO
Hot air
Exhaust fan
Heat source
DO:
choose a place as cool as possible.choose a place that is well ventilated.allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5a or 5b)
provide a solid base (level concrete pad, concrete block,
4" 1'4" (10 40 cm) or 6" 1'4" (15 40 cm) beams or equal), a minimum of 4" (10 cm) or 6" (15 cm) above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Figs. 5c and 5d or 5e)
CAUTION
install cushion rubber under unit’s feet to reduce
A solid base must not cover the hole of the bottom plate.
vibration and noise. (Fig. 5f)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
install in a location where no antenna of a television
or radio exists within 10' (3 m).
(CU-KE18NKU)
Air intake
Concrete or equal
About 1'4" (40 cm)
About 4" (10 cm)
Anchor bolts (4 pcs.)
Min. 4" (10 cm)
Outdoor unit
(CU-KE18NKU)
Air intake Min. 4" (10 cm)
Min.
2" (5 cm)
Air discharge
(CU-KE24NKU)
Air intake Min. 6" (15 cm)
Min.
4" (10 cm)
Air discharge
Drain holes
Fig. 4
Valve side Min. 10" (25 cm)
Min. 1'4" (40 cm)
Fig. 5a
Valve side Min. 10" (25 cm)
Min. 1'8" (50 cm)
Fig. 5b
Obstacle above
Min.
7' (2 m)
Air discharge
Ground
Obstacle above
Min.
7' (2 m)
Air discharge
Ground
Min. 6" (15 cm)
Air intake
Min.
7' (2 m)
Obstacle
Min. 4" (10 cm)
Air intake
Min.
7' (2 m)
Obstacle
(CU-KE24NKU)
Air intake
Concrete or equal
About 1'4" (40 cm)
Fig. 5d
Fig. 5e
Anchor bolts (4 pcs.)
Min. 6" (15 cm)
About 6" (15 cm)
Fig. 5c
Cushion rubber
Fig. 5f
6
3. How to Install the Indoor Unit
3-1. Remove the Rear Panel from the Unit
(1) Remove and discard the set screw on the rear
panel. (Fig. 6)
(2) Press the 2
marks on the frame cover and disen-
gage the stationary tabs from the frame. (Fig. 7)
(3) Remove the rear panel.
NOTE
Tubing can be extended in 5 directions as shown in Fig.
8. Select the direction you need providing the shortest
run to the outside unit.
When left tubing is to be done, switch the drain hose
and drain cap. (For details, refer to “Switching drain hose and drain cap” on page 15.)
3-2. Make a Hole
(1) Place the rear panel from the indoor unit on the wall
at the location selected. Make sure the panel is hori­zontal, using a carpenter’s level or tape measure to measure down from the ceiling. Wait until after cut­ting the hole before attaching the rear panel to the wall.
(2) Determine which side of the unit you should make
the hole for tubing and wiring. (Fig. 9)
NOTE
Left tubing
Set screw only for transportation
Fig. 6
Rear panel
Fig. 7
Left-rear tubing
marks
Right-rear tubing (recommended)
Right tubing
In the case of left-rear tubing, use the measurement points 2-3/8" (60 mm) from the edge of the rear panel for precise placement of the hose outlet. (Fig. 9)
(3) Before making the hole, check carefully that no
studs or pipes are directly run behind the spot to be cut.
CAUTION
Also avoid areas where elec­trical wiring or conduits are located.
The above precautions are also applicable if tubing goes through the wall in any other location.
Downward tubing
Fig. 8
2-3/8" (60 mm)
Fig. 9
7
g
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and Fig. 10.
Table 4
Hole Dia.
3-5/32" (80 mm)
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a slight angle 1/4" (6 mm) shorter than the thickness of the wall. (Fig. 11)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert the pipe in the wall. (Fig.
12)
3-3. Install the Rear Panel on the Wall
Be sure to confirm that the wall is strong enough to sus­pend the unit.
See either Item a) or b) below depending on the wall type.
a) If Wooden Wall
(1) Attach the rear panel to the wall with the 8 screws
provided. (Fig. 13)
NOTE
Hole should be made at a slight downward slant to the outdoor side.
Indoor side
Outdoor side
Fig. 10
PVC pipe (Locally purchased)
Cut at sli
ht angle
Fig. 11
INSIDE OUTSIDE
Wall
Plastic cover
(Locally purchased)
PVC pipe
Slight angle
If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use rawl plugs or toggle bolts to go through the holes on the panel or drill 3/16" (5 mm) dia. holes in the panel over the stud locations and then mount the rear panel.
(2) Double check with a carpenter’s level or tape mea-
sure that the panel is level. This is important to install the unit properly. (Fig. 14)
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise and vibration.
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" (4.8 mm) dia. holes in the wall. Insert rawl plugs for appropriate mounting screws. (Fig. 15)
Fig. 12
Fig. 13
Fig. 14
3/16" (4.8 mm) dia. hole
Rawl plug
Fig. 15
8
Loading...
+ 18 hidden pages