Panasonic CS-KE12NB41, CS-KE18NB4UW, CU-KE12NK1, CU-KE18NKU, CZ-18BT1U User Manual

TECHNICAL & SERVICE MANUAL

CS-KE12NB41 & CZ-18BT1U + CU-KE12NK1 CS-KE18NB4UW & CZ-18BT1U + CU-KE18NKU
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
Indoor Model No.
Body (Panel)
CS-KE12NB41 (CZ-18BT1U)
CS-KE18NB4UW (CZ-18BT1U)
Product Code No.
Body (Panel)
1 852 361 05 (1 852 361 15)
1 852 361 07 (1 852 361 15)
Indoor Unit
Body
Panel
Outdoor Model No. Product Code No.
CU-KE12NK1
CU-KE18NKU
1 852 361 17
1 852 361 20
Outdoor Unit
CU-KE12NK1
Remote Controller
Wired Remote Controller
(Option)
CU-KE18NKU
REFERENCE NO. SM700880

SAFETY PRECAUTIONS

• Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them.
• The precautionary items here are divided into " Warning" and " Caution" items. Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the " Warning" table. However, even precautionary items identified as " Caution" also have the potential for serious consequences if not performed correctly. Important safety precautions are described for all items in both categories. Be sure to carefully follow all of them.
• Symbol Indication
: This symbol indicates items to which we need to pay attention.
In this triangle, a definite precautionary item is described.
: This symbol indicates the item to be prohibited.
In or close to this circle, a prohibited item is described.
: This symbol indicates the items requiring special attention or instruction.
In or close to this circle, a prohibited item is described.
• After doing repair work, perform a test run to confirm that there are no abnormalities. At the same time, explain the precautions in use to the user.
Warning
Before performing an overhaul, disconnect the power plug or power cable from the unit. Performing the work with the power supplied to the unit, may cause an electric shock.
When repair work or circuit inspection that requires power supply for the air conditioner, is to be performed, do not touch the charging section. Doing so may cause an electric shock.
Prohibit
For the step-up capacitor attached to the electric section, perform the repair work after sufficiently discharging it. Insufficient capacitor discharge may cause an electric shock.
Do not perform repair work on the electric sections with wet hands. Doing so may cause an electric shock.
Do not start or stop the air conditioner by means of connecting or disconnecting the power plug. Doing so may cause an electric shock or fire.
When conducting repair work only use components included in the parts list for the corresponding unit and perform the work with the appropriate tools. Incorrect or poor repair work may cause an electric shock or fire.
Never modify the unit. Doing so may cause an electric shock or fire.
Perform all electric work according to local applicable regulations related to electrical equipment or interior wiring regulation and make sure to use the exclusive circuit. Insufficient capacity to the electric circuit or defective arrangement results may cause an electric shock or fire.
Make sure to replace any power cable or lead wire showing any signs of scratch or deterioration. Failure to do so may cause an electric shock, overheating or fire.
Make sure that there is no dust on or slack in the power plug and insert fully into the socket. Dust or incomplete connections may cause an electric shock or fire.
Do not damage or process the power cord, as it may cause an electric shock or fire.
Prohibit
Prohibit
Prohibit
Prohibit
For the wiring between the indoor unit and outdoor unit, securely fix the specified cable onto the terminal plate. Poorly fixed wiring may cause a heat or fire.
After connecting the wiring between the indoor unit and outdoor unit, attach the terminal cover securely. Incomplete attachment of the terminal cover may cause overheating or fire.
2
Warning
If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite.
If refrigerant gas leaks during the work, ventilate the room. If refrigerant gas catches fire, harmful gas may be generated.
Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle. If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle, which may cause a unit breakdown."
When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in a well-ventilated place after sufficiently recovering the refrigerant gas. Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury.
When the work is to be performed in a high place (About 2 meters or more), make sure to wear a safety helmet, gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall.
When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit. Insufficient strength of the installation location and incomplete installation work may cause an injury due to the unit falling.
When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children. If a child swallows a battery, make sure that the child gets immediate medical attention.
Caution
Prohibit
Prohibit
Do not wash the air conditioner with water, as this may cause an electric shock or fire.
For the repair work in places with high humidity or moisture, make sure to ground the unit. Failure to do so may cause an electric shock.
Confirm that the component attachment position, wiring condition, soldering condition and connector connection are normal. If not, it may cause overheating or fire.
Confirm that the temperature around the compressor is not too high, and then perform the repair work. Failure to do so may cause a burn.
Perform welding work in a place with good ventilation. If the work is performed in a poorly ventilated area, it might cause a lack of oxygen.
If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it. Failure to do so may cause an injury due to the unit falling.
When the cleaning is to be performed, make sure to turn off the power and pull out the plug. Touching the fan that is rotating at high speed may result in an injury.
When the indoor unit is to be removed, do not place it on an incline. Doing so may cause wet furniture because water left inside may trickle down.
Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger.
Prohibit
Prohibit
Prohibit
After repairs, make sure to measure the insulation resistance and confirm that the value is 1 Mohm or more. Any insulation error may cause an electric shock.
After repairs, make sure to check the drainage of the indoor unit. Inappropriate drainage may cause wet furniture and floors due to water leakage.
3

Table of Contents

Page
SAFETY PRECAUTIONS
TABLE OF CONTENTS
1. OPERATING RANGE
2. SPECIFICATIONS
2-1. Unit Specifications 2-2. Major Component Specifications 2-3. Other Component Specifications
3. DIMENSIONAL DATA
4. REFRIGERANT FLOW DIAGRAM
4-1. Refrigerant Flow Diagram
5. PERFORMANCE DATA
5-1. Temperature Charts 5-2. Cooling Capacity 5-3. Cooling Capacity (Low Ambient) 5-4. Heating Capacity
..............................................................................................................
.....................................................................................................................
...................................................................................................................
.............................................................................................................
...................................................................................................................
............................................................................................................
................................................................................................................
................................................................................................................
.......................................................................................
.......................................................................................
...................................................................................................
.........................................................................................
2
4
6
7 13 17
18
21
23 27 29 31
6. ELECTRICAL DATA
6-1. Electrical Characteristics 6-2. Electric Wiring Diagrams
7. MAINTENANCE
7-1. Address Setting of the Remote Control Unit 7-2. Disconnecting and Connecting Positive Connector for Outdoor Unit 7-3. Disassembly Procedure
8. FUNCTIONS
8-1. Operation Functions 8-2. Protective Functions
9. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE)
9-1. Precautions before Performing Inspection or Repair 9-2. Method of Self-Diagnostics 9-3. Checking the Indoor and Outdoor Units 9-4. Trouble Diagnosis of Fan Motor 9-5. Noise Malfunction and Electromagnetic Interference
....................................................................................................
....................................................................................................
.......................................................................
......................................................................................................
...........................................................................................................
...........................................................................................................
...........................................................
.................................................................................................
..............................................................................
...........................................................................................
..........................................................
..................................
33 35
38 39 40
47 49
51 51 53 57 59
4
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance 10-2. Checking Continuity of Fuse on PCB Ass'y
11. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT
11-1. Characteristics of New Refrigerant R410A 11-2. Checklist before Servicing 11-3. Tools Specifically for R410A 11-4. Tubing Installation Procedures 11-5. In Case of Compressor Malfunction 11-6. In Case Refrigerant is Leaking 11-7. Charging Additional Refrigerant 11-8. Retro-Fitting Existing Systems
...................................................................................................
................................................................................................
............................................................................................
....................................................................................
............................................................................................
..........................................................................................
............................................................................................
Page
...............................................................................
.........................................................................
.........................................................................
60 61
62 63 64 64 65 67 68 68
APPENDIX A Operating Instructions
(CS-KE12NB41 & CZ-18BT1U + CU-KE12NK1 CS-KE18NB4UW & CZ-18BT1U + CU-KE18NKU)
APPENDIX B INSTALLATION INSTRUCTIONS
(CS-KE12NB41 & CZ-18BT1U + CU-KE12NK1 CS-KE18NB4UW & CZ-18BT1U + CU-KE18NKU)
APPENDIX C Operating Instructions
(CZ-RD515U)
APPENDIX D INSTALLATION INSTRUCTIONS
(CZ-RD515U)
............................................................................................
.............................................................................
............................................................................................
.............................................................................
A-1
A-2
A-3
A-4
5

1. OPERATING RANGE

Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
95 °F DB / 71 °F WB
67 °F DB / 57 °F WB
80 °F DB / 67 °F WB
– DB / – WB
115 °F DB
0 °F DB
75 °F DB / 65 °F WB
– DB / 0 °F WB
6

2. SPECIFICATIONS

2-1. Unit Specifications

2-1-1.
Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1
Voltage Rating
Total Capacity
Sensible Capacity Latent Capacity
Performance
Air Circulation (Hi/Me/Lo) ft Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
EER BTU/h/W 9.44 COP W/W ­SEER BTU/Wh 16 HSPF BTU/Wh -
Electrical Rating
Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity A 20 Controls / Temperature Control Control Unit Timer
Indoor / OutdoorFan Speeds
Airflow Direction (Indoor) Horizontal
Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control
Features
Operation Sound
Refrigerant Tubing Connections
Refrigerant inch (mm) Tube Diameter inch (mm) Wired Remote Controller (Option) CZ-RD515U
Indoor : Hi/Me/Lo Outdoor : Hi
Narrow tube Wide tube
BTU/h
kW
BTU/h BTU/h
3
/min (m3/h)
Vertical
dB-A dB-A
ft (m)Max. allowable tubing length at shipment
11,900
235(399) / 206(350) / 194(330)
V A
12.6
WPower Input
1,260
%Power Factor 87
A20
( 3,000 to 11,900 )
3.5
( 0.9 to 3.5 )
( 2.5 to 12.6 ) ( 250 to 1,260 )
24-Hour ON or OFF Timer, 1-Hour OFF Timer
34 / 32 / 31
115V Single-Phase 60Hz
Cooling
7,200 4,700
4.26
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Auto and 3 steps / Auto (Hi, Me, Lo)
Washable, Anti-Mold
DC Rotary (Inverter)
R410A / 2.43 (1,100)
Electric Expansion Valve
47
Heating
13,600
268(455) / 247(420) / 224(381)
104 to 126
1,460
-
Auto
Flare Type
25 (7.5) 1/4 (6.35) 3/8 (9.52)
( 3,000 to 13,600 )
4.0
( 0.9 to 4.0 )
14.6
( 2.5 to 14.6 ) ( 250 to 1,460 )
35 / 34 / 32
-
-
-
87
-
2.74
-
8.5
49
7
Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth 28-1/8 (714)
Weight Ib. (kg)
Net Shipping
Shipping Volume
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth
Weight Ib. (kg)
Net Shipping
Shipping Volume
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80 °F DB / 67 °F WB
Outdoor air temperature 95 °F DB / 75 °F WB
Indoor Unit
(CS-KE12NB41 & CZ-18BT1U)
inch (mm) (313)12-5/16
inch (mm) 22-5/8 (575) inch (mm)
(625)24-19/32 (625)24-19/32
inch (mm) -
inch (mm) 24-13/16 (630) inch (mm)
-
­(18.7)41.3
Ib. (kg)
cu.ft (m
3
)
-
-
Body
(CS-KE12NB41)
11-5/32 (283)
22-5/8 (575)
11-13/32 (290)
35.3 (16)
41.9 (19)
4.59 (0.13)
Outdoor Unit
(CU-KE12NK1)
inch (mm) (548)21-9/16
Individual Unit
inch (mm) inch (mm) inch (mm)
inch (mm) inch (mm)
(720)28-11/32 (265)10-7/16 (596)23-15/32
(866)34-3/32 (368)14-1/2 (35.0)77.2
Ib. (kg)
cu.ft (m
3
)
(38.0)83.8
(0.18)6.35
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Heating: Indoor air temperature 70 °F DB
Outdoor air temperature 47 °F DB / 43 °F WB
Panel
(CZ-18BT1U)
1-9/16 (40)
24-19/32 (625) 24-19/32 (625)
4-1/8 (105)
26-3/16 (665)
26-11/16 (678)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
8
2-1-2.
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU
Voltage Rating
Total Capacity
Sensible Capacity Latent Capacity
Performance
Air Circulation (Hi/Me/Lo) ft Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
EER BTU/h/W 9.41 COP W/W ­SEER BTU/Wh 16 HSPF BTU/Wh -
Electrical Rating
Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity A 15 Controls / Temperature Control Control Unit Timer
Indoor / OutdoorFan Speeds
Airflow Direction (Indoor) Horizontal
Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control
Features
Operation Sound
Refrigerant Tubing Connections
Refrigerant inch (mm) Tube Diameter inch (mm) Wired Remote Controller (Option) CZ-RD515U
Indoor : Hi/Me/Lo Outdoor : Hi
Narrow tube Wide tube
BTU/h
kW
BTU/h BTU/h
3
/min (m3/h)
Vertical
dB-A dB-A
ft (m)Max. allowable tubing length at shipment
17,500
5.15
341(579) / 294(500) / 253(430)
V A
WPower Input
1,860
%Power Factor 97
A 17.5
( 4,000 to 17,500 ) ( 1.2 to 5.15 )
8.3
( 1.2 to 8.3 ) ( 250 to 1,860 )
24-Hour ON or OFF Timer, 1-Hour OFF Timer
44 / 40 / 36
230V Single-Phase 60Hz
Cooling
10,600
6,900
4.89
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Auto and 3 steps / Auto (Hi, Me, Lo)
Washable, Anti-Mold
DC Twin Rotary (Inverter)
R410A / 2.87 (1,300)
Electric Expansion Valve
51
Heating
20,400
383(651) / 324(551) / 265(450)
187 to 253
2,340
-
Auto
Flare Type
25 (7.5) 1/4 (6.35) 1/2 (12.7)
( 4,400 to 20,400 )
6.0
( 1.3 to 6.0 )
10.5
( 1.3 to 10.5 ) ( 270 to 2,340 )
44 / 40 / 36
-
-
-
97
-
2.56
-
8.5
52
< 230V >
9
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth
Weight Ib. (kg)
Shipping Volume
Net Shipping
inch (mm)
inch (mm) inch (mm) inch (mm)
inch (mm) inch (mm)
Ib. (kg)
cu.ft (m
Indoor Unit
(CS-KE18NB4UW & CZ-18BT1U)
(313)12-5/16
(625)24-19/32 (625)24-19/32
-
-
­(18.7)41.3
-
3
)
-
Individual Unit
Body
(CS-KE18NB4UW)
11-5/32 (283)
22-5/8 (575) 22-5/8 (575)
24-19/32 (625) 24-19/32 (625)
11-13/32 (290)
24-13/16 (630)
28-1/8 (714)
26-11/16 (678)
35.3 (16)
41.9 (19)
4.59 (0.13)
< 230V >
Panel
(CZ-18BT1U)
1-9/16 (40)
4-1/8 (105)
26-3/16 (665)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth
Weight Ib. (kg)
Net Shipping
Shipping Volume
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80 °F DB / 67 °F WB
Outdoor air temperature 95 °F DB / 75 °F WB
Outdoor Unit
(CU-KE18NKU)
inch (mm) (670)26-3/8
inch (mm) inch (mm) inch (mm)
inch (mm) inch (mm)
Ib. (kg)
3
cu.ft (m
)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Heating: Indoor air temperature 70 °F DB
Outdoor air temperature 47 °F DB / 43 °F WB
(880)34-21/32 (285)11-7/32 (733)28-27/32
(1,012)39-27/32 (379)14-29/32 (44.0)97.0 (48.0)105.8
(0.28)9.88
10
2-1-3.
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU
Voltage Rating
Total Capacity
Sensible Capacity Latent Capacity
Performance
Air Circulation (Hi/Me/Lo) ft Moisture Removal (High) Pints/h Available Voltage Range Running Amperes
EER BTU/h/W 9.41 COP W/W ­SEER BTU/Wh 16 HSPF BTU/Wh -
Electrical Rating
Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity A 15 Controls / Temperature Control Control Unit Timer
Indoor / OutdoorFan Speeds
Airflow Direction (Indoor) Horizontal
Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control
Features
Operation Sound
Refrigerant Tubing Connections
Refrigerant inch (mm) Tube Diameter inch (mm) Wired Remote Controller (Option) CZ-RD515U
Indoor : Hi/Me/Lo Outdoor : Hi
Narrow tube Wide tube
BTU/h
kW
BTU/h BTU/h
3
/min (m3/h)
Vertical
dB-A dB-A
ft (m)Max. allowable tubing length at shipment
17,500
5.15
341(579) / 294(500) / 253(430)
V A
WPower Input
1,860
%Power Factor 98
A 17.5
( 4,000 to 17,500 ) ( 1.2 to 5.15 )
9.1
( 1.2 to 9.1 ) ( 250 to 1,860 )
24-Hour ON or OFF Timer, 1-Hour OFF Timer
44 / 40 / 36
208V Single-Phase 60Hz
Cooling
10,600
6,900
4.89
Microprocessor / I.C. Thermister
Wireless Remote Control Unit
Auto and 3 steps / Auto (Hi, Me, Lo)
Washable, Anti-Mold
DC Twin Rotary (Inverter)
R410A / 2.87 (1,300)
Electric Expansion Valve
51
Heating
20,400
383(651) / 324(551) / 265(450)
187 to 253
2,340
-
Auto
Flare Type
25 (7.5) 1/4 (6.35) 1/2 (12.7)
( 4,400 to 20,400 )
6.0
( 1.3 to 6.0 )
11.5
( 1.3 to 11.5 ) ( 270 to 2,340 )
44 / 40 / 36
-
-
-
98
-
2.56
-
8.5
52
< 208V >
11
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU
Dimensions & Weight (Indoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth
Weight Ib. (kg)
Shipping Volume
Net Shipping
inch (mm)
inch (mm) inch (mm) inch (mm)
inch (mm) inch (mm)
Ib. (kg)
cu.ft (m
Indoor Unit
(CZ-KE18NB4UW & CZ-18BT1U)
(313)12-5/16
(625)24-19/32 (625)24-19/32
-
-
­(18.7)41.3
-
3
)
-
Individual Unit
Body
(CS-KE18NB4UW)
11-5/32 (283)
22-5/8 (575) 22-5/8 (575)
24-19/32 (625) 24-19/32 (625)
11-13/32 (290)
24-13/16 (630)
28-1/8 (714)
26-11/16 (678)
35.3 (16)
41.9 (19)
4.59 (0.13)
< 208V >
Panel
(CZ-18BT1U)
1-9/16 (40)
4-1/8 (105)
26-3/16 (665)
6.0 (2.7)
7.7 (3.5)
1.65 (0.04)
Dimensions & Weight (Outdoor Unit)
Unit Dimensions Height
Width Depth
Package Dimensions Height
Width Depth
Weight Ib. (kg)
Net Shipping
Shipping Volume
Remarks: Rating conditions are:
Cooling: Indoor air temperature 80 °F DB / 67 °F WB
Outdoor air temperature 95 °F DB / 75 °F WB
Outdoor Unit
(CU-KE18NKU)
inch (mm) (670)26-3/8
inch (mm) inch (mm) inch (mm)
inch (mm) inch (mm)
Ib. (kg)
3
cu.ft (m
)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Heating: Indoor air temperature 70 °F DB
Outdoor air temperature 47 °F DB / 43 °F WB
(880)34-21/32 (285)11-7/32 (733)28-27/32
(1,012)39-27/32 (379)14-29/32 (44.0)97.0 (48.0)105.8
(0.28)9.88
12

2-2. Major Component Specifications

2-2-1. Indoor Unit
Indoor Unit (Body) CS-KE12NB41
Control PCB
Part No.
Controls
Control Circuit Fuse
Fan
Type Q'ty ... Dia. and Length
Fan Motor
Type Model ... Q'ty No. of Poles
Rough Measure RPM (Cool / Heat)
Rating Voltage / Nominal Output
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type Over- Current Protection Over- Heat Protection
Run Capacitor Micro F
inch (mm)
Ohm
VAC
CB-CS-KE12NB4U
Microprocessor
250V 3A
Turbo
1 ... D12-5/8 / L5-3/4 (D322/L147)
DC Motor
SIC-62FW-D866-2 ... 1
8
470 / 520
DC160V / 23W
-
Internal Controller
Ye s Ye s
-
-
Drain Pump
Model ... Q'ty
Rating Voltage, Hz
(Ambient Temp. 68 °F (20 °C))
Safty Device
Heat Exchanger Coil
Coil
Rows Fins per inch
Input
Type Open
W
Ohm
°F (°C)
2
(m2)
ft
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
PLD-12115ST-1 ... 1
Aluminum Plate Fin / Copper Tube
Indoor Unit (Panel) CZ-18BT1U
Flap Motor
Type Stepping Motor
Model ... Q'ty
Rating
Coil Resistance Ohm
(Ambient Temp. 77 °F (25 °C))
Each Pair of Terminal : 380 +/- 7%
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
AC115V, 60Hz
10.8
101 +/- 10%Coil Resistance
Thermal Fuse
293 (145)
2
18.1
2.94 (0.273) Face Area
MPZN-12V ... 2
DC 12V
13
Indoor Unit (Body) CS-KE18NB4UW
Control PCB
Part No.
Controls
Control Circuit Fuse
Fan
Type Q'ty ... Dia. and Length
Fan Motor
Type Model ... Q'ty No. of Poles
Rough Measure RPM (Cool / Heat)
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type Over- Current Protection Over- Heat Protection
Run Capacitor Micro F
inch (mm)
Ohm
VAC
CB-CS-KE18NB4U
Microprocessor
250V 3A
Turbo
1 ... D12-5/8 / L5-3/4 (D322/L147)
DC Motor
SIC-62FV-D866-2 ... 1
8
650 / 720
DC340V / 20WRating Voltage / Nominal Output
-
Thermal Fuse
Ye s Ye s
-
-
Drain Pump
Model ... Q'ty
Rating Voltage, Hz
Input
W
PLD-12230ST-1 ... 1
AC208 to 240V, 60Hz
Ohm
(Ambient Temp. 68 °F (20 °C))
Safty Device
Type Open
°F (°C)
Heat Exchanger Coil
Coil
Aluminum Plate Fin / Copper Tube
Rows Fins per inch
2
(m2)
ft
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Indoor Unit (Panel) CZ-18BT1U
Flap Motor
Type Stepping Motor
Model ... Q'ty
Rating
Coil Resistance Ohm
(Ambient Temp. 77 °F (25 °C))
Each Pair of Terminal : 380 +/- 7%
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
MP24ZN-12V ... 2
10.8
333 +/- 10%Coil Resistance
Thermal Fuse
293 (145)
2
18.1
2.94 (0.273) Face Area
DC 12V
14
2-2-2. Outdoor Unit
Outdoor Unit CU-KE12NK1
Control PCB
Part No.
Controls
Control Circuit Fuse
Compressor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount Coil Resistance (Ambient Temp. 68 °F (20 °C))
Safety Device
CT (Peak current cut-off control) Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Overload Relay
Run Capacitor
Crankcase Heater
Pints (cc)
Ohm
Model
Operation Temp.
Micro F
VAC
CB-CU-KE12NK1
Microprocessor
125V 25A
DC Rotary (Hermetic)
G4C090LU1ER / 900W
FV50S ... 0.68 (320)
U - V :
0.81
V - W :
W - U :
0.81
0.81
Ye s Ye s Ye s
CS-7L115
Open : 239 °F (115 °C), Close : 203 °F (95 °C)
-
-
115V 20W
Fan
Type
Q'ty ... Dia. inch (mm)
Fan Motor
Type Model ... Q'ty No. of Poles
Rough Measure RPM (Cool / Heat)
Nominal Output
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type Over- Current Protection
Run Capacitor
Heat Exchanger Coil
Coil
Rows Fins per inch
Face Area
W
Ohm
Micro F
VAC
2
ft
(m2)
Propeller
1 ... D15-3/4 (D400)
DC Motor
SIC-67FV-F460-1... 1
8
750 / 750
50
RED - WHT :
WHT - BLU :
BLU - RED :
77.5
77.5
77.5
Internal Controller
Ye s
-
-
Aluminum Plate Fin / Copper Tube
2
18.1
3.95 (0.367)
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
15
Outdoor Unit CU-KE18NKU
Control PCB
Part No.
Controls
Control Circuit Fuse
Compressor
Type
Compressor Model / Nominal Output
Compressor Oil ... Amount Coil Resistance (Ambient Temp. 68 °F (20 °C))
Safety Device
CT (Peak current cut-off control) Compressor Discharge Temp. Control
Operation cut-off control in abnormal ambient Temp.
Overload Relay
Run Capacitor
Crankcase Heater
Pints (cc)
Ohm
Model
Operation Temp.
Micro F
VAC
CB-CU-KE18NKU
Microprocessor
250V 25A
DC Twin Rotary (Hermetic)
C-6RVN93H0M / 1,050W
FV50S ... 0.74 (350)
R - S :
0.482
S - T :
0.482
T - R :
0.482
Ye s Ye s Ye s
CS-7L115
Open : 239 °F (115 °C), Close : 203 °F (95 °C)
-
-
-
Fan
Type
Q'ty ... Dia. inch (mm)
Fan Motor
Type Model ... Q'ty No. of Poles
Rough Measure RPM (Cool / Heat)
Nominal Output
Coil Resistance
(Ambient Temp. 68 °F (20 °C))
Safety Device
Type Over- Current Protection
Run Capacitor
Heat Exchanger Coil
Coil
Rows Fins per inch
Face Area
W
Ohm
Micro F
VAC
2
ft
(m2)
Propeller
1 ... D16-17/32 (D420)
DC Motor
SIC-67FV-F460-1 ... 1
8
820 / 850
50
RED - WHT :
WHT - BLU :
BLU - RED :
77.5
77.5
77.5
Internal Controller
Ye s
-
-
Aluminum Plate Fin / Copper Tube
2
21.2
5.49 (0.510)
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
16

2-3. Other Component Specifications

Indoor Unit CS-KE12NB41 & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE12NK1 CU-KE18NKU
• Indoor air temp sensor
(Model:KTEC-35-S98)
• Indoor heat exchanger sensor
(Model:PT2M-51H-S3)
• Compressor temp sensor
(CU-KE12NK1 (CU-KE18NKU
...
Model:DTN-TKS274Y TH2)
...
Model:DTN-TKS293B)
10
9
8
7
6
5
Resistance (k ohm)
4
3
2
1
0
59 68 77 86 95 104
50
(10) (15) (20) (25) (30) (35) (40)
Temperature °F (°C)
200
180
160
140
120
100
Resistance (k ohm)
80
60
40
20
0
32 50 68 86 104 122 140 158 176 194 (0) (10) (20) (30) (40) (50) (60) (70) (80) (90)
Temperature °F (°C)
• Outdoor air temp sensor
(CU-KE12NK1 (CU-KE18NKU
...
Model:DTN-TKS269B)
...
Model:TKS295B)
• Outdoor heat exchanger sensor
(CU-KE12NK1 (CU-KE18NKU
40
...
Model:DTN-TKS274Y TH1)
...
Model:TKS292B)
35
30
25
20
Resistance (k ohm)
15
10
5
0
-
4 5 14 23 32 41 50 59 68
(
-
20)(-15)(-10) (-5) (0) (5) (10) (15) (20)
17
Temperature °F (°C)

3. DIMENSIONAL DATA

Indoor Unit CS-KE12NB41 & CZ-18BT1U CS-KE18NB4UW & CZ-18BT1U
7-11/16
8
4-29/32
A View
1-3/16
21/32
3-1/8
(534)
AA
21-1/32
23-5/8 (600)
Suspension bolt pitch
Ceiling opening dimensions
Center of
panel
7
(flared)
1/4" (flared)
dia.
dia. 1/2"
23-5/8 (600)
21-1/32 (534)
Ceiling opening dimensions
Suspension bolt pitch
12-7/16
12-7/8
5
22-5/8 (575)
6-5/16 6-11/16
2-3/32
1-25/32
11-5/32 (283)
8-15/32
1-3/16 (30)
3
6
1-25/32
4-19/32
Less than 31/32 Less than 31/32
The length of the suspension
2
14-3/32 (358)
24-19/32 (625)
2
25/32
bolts should be selected so that
there is a gap of 1-3/16" or
the ceiling (21/32" or more
below the lower surface of the
main unit), as shown in the
figure at right. If the suspension
bolts is too long, it will contact
the ceiling panel and the unit
cannot be installed.
24-19/32 (625)
13-5/32 (334)
2
1
5-9/16
2-3/4 1-9/32
2
(liquid tube)
Air intake
Discharge outlet
Refrigerant tubing
1
2
3
(gas tube)
Refrigerant tubing
Drain tube connection port VP20 (outer dia. 1")
Power supply port
Suspension bolt hole (4 - 1/2" x 1-1/8" hole)
4
5
6
7
Fresh air intake duct connection port (dia. 3-7/8")
8
22-5/8 (575)
18
2-3/32
3-5/8
7-23/32
1-27/32 1-3/32
Unit : inch (mm)
Outdoor Unit CU-KE12NK1
3-19/32
10-13/16
21-3/16
ID:23/32
28-11/32 (720) 2-1/8
4-ID:15/16
3-19/32
15/32
11-13/32
10-7/16 (265)
12-7/16
Wide tube service valve dia.3/8" (9.52)
Narrow tube service valve dia.1/4" (6.35)
19
5/8
21-9/16 (548)
4-9/32 2-5/32
6-3/32
Unit : inch (mm) (852-0-0010-12700-0)
Outdoor Unit CU-KE18NKU
23-15/16 5-11/32
1-3/8
11-17/32
ID:23/32
34-21/32(880)
4-ID:15/16
15/32
2-17/32
12-7/32
11-7/32(285)
13-5/32
Wide tube service valve dia.1/2" (12.70)
Narrow tube service valve dia.1/4" (6.35)
1-13/16
20
23/32
2-13/32
26-3/8(670)
6-17/32
4-3/8 2-5/32
3/32
5-23/32
Unit : inch (mm) (852-0-0010-13200-0)

4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram

Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1
Indoor unit Outdoor unit
Heat exchanger
Strainer
Wide tube
O.D. 3/8" (9.52 mm)
Narrow tube
O.D. 1/4" (6.35 mm)
Wide tube service valve
Muffler
Narrow tube service valve
Strainer
4-way valve
Muffler
Accumulator
High pressure
switch
H.P.
Electric
expansion
valve
M
Capillary tube for split flow
Compressor
Heat exchanger
Cooling cycle (Defrosting cycle)
Heating cycle
21
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU
Indoor unit Outdoor unit
Heat exchanger
Strainer
Wide tube
O.D.
1/2"
(12.7mm)
Narrow tube
O.D. 1/4" (6.35 mm)
Wide tube service valve
Muffler
Narrow tube service valve
Strainer
4-way valve
Accumulator
High pressure
switch
H.P.
Electric
expansion
valve
M
Capillary tube for split flow
Compressor
Heat exchanger
Cooling cycle (Defrosting cycle)
Heating cycle
22

5. PERFORMANCE DATA

5-1. Temperature Charts

Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1
Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 115V)
(1) Low pressure performance chart
Hi FanLo Fan
131
(0.9)
psig(MPaG)
102
(0.7)
73
Low pressure at wide tube service valve
(0.5)
(2) Operating current performance chart
15
14
13
12
Indoor Air Temp.86°F (30°C)
Indoor Air Temp.86
F (27
°
80°F (2C)
80
75°F (2C)
75°F (24°C)
77
(25)
86
(30)
Outdoor inlet air DB temp. °F(°C)
Hi FanLo Fan
Indoor Air Temp.86°F (30°C)
Indoor Air Temp.86
(35)
F (30
°
C)
°
95
F (30
°
F (27
°
80°F (27°C)
80
75°F (24°C)
75°F (24°C)
C)
°
104
(40)
C)
°
C)
°
Operating current (A)
11
10
77
(25)
86
(30)
95
(35)
104
(40)
Outdoor inlet air DB temp. °F(°C)
(3) Indoor discharge air performance chart
68
(20)
59
(15)
50
(10)
41 (5)
32
Indoor discharge air temperature °F(°C)
(0)
77
(25)
Outdoor inlet air DB temp.
NOTE
Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
Hi FanLo Fan
F (30
Indoor Air Temp.86°F (30°C)
Indoor Air Temp.86
80°F (2C)
80
7F (2C)
75°F (24°C)
86
(30)
F (27
°
95
(35)
°
°
C)
°F(°C)
C)
°
104
(40)
23
Indoor Unit CS-KE12NB41 & CZ-18BT1U Outdoor Unit CU-KE12NK1
Heating Characteristics (RH : 85%, Indoor fan speed : High fan) (60Hz, 115V)
(1) High pressure performance chart
(2) Operating current performance chart
508
(3.5)
435
psig(MPaG)
(3.0)
Indoor Air Temp.73°F (23°C)
363
(2.5)
290
(2.0)
218
High pressure at wide tube service valve
(1.5)
(
17
70°F (21°C)
63°F (17°C)
23
-
5)32(0)41(5)50(10)59(15)68(20)77(25)
Outdoor inlet air DB temp. °F(°C)
16
15
14
13
Operating current (A)
12
11
23
-
(
(3) Indoor discharge air performance chart
131 (55)
122 (50)
113 (45)
104 (40)
95
(35)
86
(30)
77
(25)
Indoor discharge air temperature °F(°C)
68
23
(20)
-
(
Indoor Air Temp.73°F (23°C)
70°F (21°C)
63°F (17°C)
5)32(0)41(5)50(10)59(15)68(20)77(25)
Outdoor inlet air DB temp. °F(°C)
Indoor Air Temp.73°F (23°C)
70°F (21°C)
63°F (17°C)
5)32(0)41(5)50(10)59(15)68(20)77(25)
Outdoor inlet air DB temp. °F(°C)
NOTE
Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "8-2. Protective Functions Overload prevention during heating.")
24
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU
Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)
(1) Low pressure performance chart
Hi FanLo Fan
131
(0.9)
psig(MPaG)
102
(0.7)
73
Low pressure at wide tube service valve
(0.5)
(2) Operating current performance chart
10
Indoor Air
Indoor Air Temp.86
77
(25)
86
(30)
Outdoor inlet air DB temp. °F(°C)
Hi FanLo Fan
9
Indoor Air
8
Indoor Air Temp
Temp.86°F (30°C)
F (27
°
80°F (2C)
80
75°F (2C)
75°F (24°C)
(35)
Temp.86°F (30°C)
F (30
°
C)
°
95
F (30
°
.86
F (27
°
80°F (27°C)
80
75°F (24°C)
75°F (24°C)
C)
°
104
(40)
C)
°
C)
°
7
Operating current (A)
6
5
77
(25)
86
(30)
95
(35)
104
(40)
Outdoor inlet air DB temp. °F(°C)
(3) Indoor discharge air performance chart
68
(20)
59
(15)
50
(10)
41 (5)
32
Indoor discharge air temperature °F(°C)
(0)
77
(25)
Outdoor inlet air DB temp. °F(°C)
NOTE
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
Hi FanLo Fan
Indoor Air
Indoor Air Temp.86
86
(30)
Temp.86°F (30°C)
°
F (27
°
80°F (2C)
80
7F (2C)
75°F (24°C)
95
(35)
C)
°
F (30
°
C)
104
(40)
25
Indoor Unit CS-KE18NB4UW & CZ-18BT1U Outdoor Unit CU-KE18NKU
Heating Characteristics (RH : 85%, Indoor fan speed : High fan) (60Hz, 230V)
(1) High pressure performance chart
(2) Operating current performance chart
508
(3.5)
435
psig(MPaG)
(3.0)
Indoor Air Temp.73°F (23°C)
70°F (21°C)
363
(2.5)
290
(2.0)
218
High pressure at wide tube service valve
(1.5)
(
12
63°F (17°C)
23
-
5)32(0)41(5)50(10)59(15)68(20)77(25)
Outdoor inlet air DB temp. °F(°C)
11
10
9
8
Operating current (A)
7
6
23
-
(
(3) Indoor discharge air performance chart
131 (55)
122 (50)
113 (45)
104 (40)
95
(35)
86
(30)
77
(25)
Indoor discharge air temperature °F(°C)
68
23
(20)
-
(
Indoor Air Temp.73°F (23°C)
70°F (21°C)
63°F (17°C)
5)32(0)41(5)50(10)59(15)68(20)77(25)
Outdoor inlet air DB temp. °F(°C)
Indoor Air Temp.73°F (23°C)
70°F (21°C)
63°F (17°C)
5)32(0)41(5)50(10)59(15)68(20)77(25)
Outdoor inlet air DB temp. °F(°C)
NOTE
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.
• Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in heating mode. (Refer to "8-2. Protective Functions Overload prevention during heating.")
26

5-2. Cooling Capacity

Indoor Unit : CS-KE12NB41 & CZ-18BT1U
Outdoor Unit : CU-KE12NK1
Power Supply : 115V Single Phase 60Hz
< Cooling Capacity >
RATING CAPACITY: 11,900 BTU/h AIR FLOW RATE: 235 CFM
INDOOR OUTDOOR
o
ENT. TEMP.
WB DB 65 75 85 95 105 115
59 76 (24.4) SHC 7,210 7,300 7,440 7,480 7,660 6,930
(15.0) 80 (26.7) SHC 8,120 8,210 8,350 8,400 8,530 7,830
63 76 (24.4) SHC 7,940 7,800 7,710 7,570 7,070 5,840
(17.2) 80 (26.7) SHC 8,850 8,720 8,580 8,490 7,980 6,750
67 76 (24.4) SHC 6,660 6,570 6,480 6,380 5,880 4,740
(19.4) 80 (26.7) SHC 7,570 7,480 7,390 7,300 6,750 5,650
71 76 (24.4) SHC 5,330 5,290 5,200 5,150 4,560 3,550
(21.7) 80 (26.7) SHC 6,250 6,200 6,110 6,060 5,470 4,460
F (oC) AMBIENT TEMP. oF (oC)
TC 8,350 8,570 8,800 8,930 9,210 7,830
CI
72 (22.2) SHC 6,340 6,430 6,570 6,610 6,800 6,060
84 (28.9) SHC 8,350 8,570 8,800 8,930 9,210 7,830 88 (31.1) SHC 8,350 8,570 8,800 8,930 9,210 7,830
TC 12,230 12,030 11,790 11,580 10,580 7,950
CI
72 (22.2) SHC 7,070 6,930 6,840 6,700 6,200 4,970
84 (28.9) SHC 9,720 9,590 9,450 9,360 8,850 7,620 88 (31.1) SHC 10,590 10,450 10,360 10,230 9,720 7,950
TC 12,460 12,290 12,070 # 11,900 10,700 8,040
CI
72 (22.2) SHC 5,790 5,700 5,610 5,520 4,970 3,870
84 (28.9) SHC 8,440 8,350 8,260 8,170 7,620 6,520 88 (31.1) SHC 9,310 9,220 9,130 9,040 8,490 7,390
TC 12,640 12,490 12,300 12,170 10,770 8,100
CI
72 (22.2) SHC 4,460 4,420 4,330 4,280 3,690 2,680
84 (28.9) SHC 7,120 7,070 6,980 6,930 6,340 5,330 88 (31.1) SHC 7,980 7,940 7,850 7,800 7,210 6,200
TC 12,730 12,610 12,450 12,370 10,780 8,120
(18.3) (23.9) (29.4) (35.0) (40.6) (46.1)
0.79 0.93 1.06 1.16 1.25 1.07
0.80 0.94 1.08 1.18 1.25 1.07
0.82 0.96 1.10 1.20 1.25 1.07
0.84 0.98 1.13 1.22 1.25 1.07
75 76 (24.4) SHC 4,050 4,010 3,960 3,920 3,370 2,450
(23.9) 80 (26.7) SHC 4,970 4,920 4,880 4,830 4,280 3,370
84 (28.9) SHC 5,840 5,790 5,740 5,700 5,150 4,240 88 (31.1) SHC 6,700 6,660 6,610 6,570 6,020 5,100
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
NOTE
1.
Rating conditions (#)
: Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB : Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
27
Indoor Unit : CS-KE18NB4UW & CZ-18BT1U
Outdoor Unit : CU-KE18NKU
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity >
RATING CAPACITY: 17,500 BTU/h AIR FLOW RATE: 341 CFM
INDOOR OUTDOOR
o
ENT. TEMP.
WB DB 65 75 85 95 105 115
59 76 (24.4) SHC 10,330 10,470 10,600 10,730 10,930 9,010
(15.0) 80 (26.7) SHC 11,590 11,720 11,860 11,990 12,190 9,520
63 76 (24.4) SHC 11,590 11,390 11,190 11,000 9,540 7,480
(17.2) 80 (26.7) SHC 12,850 12,650 12,450 12,260 10,800 8,740
67 76 (24.4) SHC 9,870 9,740 9,540 9,340 7,880 6,020
(19.4) 80 (26.7) SHC 11,130 10,930 10,800 10,600 9,070 7,280
71 76 (24.4) SHC 7,950 7,880 7,750 7,610 6,090 4,430
(21.7) 80 (26.7) SHC 9,210 9,140 9,010 8,870 7,350 5,690
75 76 (24.4) SHC 6,160 6,090 5,960 5,890 4,430 2,970
(23.9) 80 (26.7) SHC 7,420 7,350 7,220 7,150 5,690 4,230
F (oC) AMBIENT TEMP. oF (oC)
(18.3) (23.9) (29.4) (35.0) (40.6) (46.1)
TC 12,260 12,550 12,830 13,060 13,460 9,520
CI
72 (22.2) SHC 9,140 9,270 9,400 9,540 9,740 7,810
84 (28.9) SHC 12,260 12,550 12,830 13,060 13,380 9,520 88 (31.1) SHC 12,260 12,550 12,830 13,060 13,460 9,520
TC 18,110 17,790 17,400 17,000 14,080 9,650
CI
72 (22.2) SHC 10,400 10,200 10,000 9,800 8,340 6,290
84 (28.9) SHC 14,040 13,850 13,650 13,450 11,990 9,650 88 (31.1) SHC 15,240 15,110 14,840 14,640 13,180 9,650
TC 18,510 18,220 17,860 # 17,500 14,220 9,750
CI
72 (22.2) SHC 8,680 8,480 8,340 8,140 6,620 4,830
84 (28.9) SHC 12,320 12,190 11,990 11,790 10,330 8,480 88 (31.1) SHC 13,510 13,380 13,180 12,980 11,530 9,670
TC 18,820 18,570 18,260 17,940 14,290 9,810
CI
72 (22.2) SHC 6,750 6,690 6,550 6,420 4,900 3,240
84 (28.9) SHC 10,470 10,330 10,200 10,070 8,540 6,890 88 (31.1) SHC 11,660 11,530 11,390 11,260 9,740 8,080
TC 19,010 18,800 18,530 18,260 14,280 9,810
CI
84 (28.9) SHC 8,610 8,540 8,410 8,340 6,890 5,430 88 (31.1) SHC 9,800 9,740 9,670 9,540 8,080 6,620
1.15 1.34 1.54 1.72 1.67 1.30
1.17 1.37 1.57 1.75 1.67 1.30
1.19 1.40 1.60 1.79 1.67 1.30
1.22 1.43 1.64 1.83 1.67 1.30
1.25 1.46 1.68 1.87 1.67 1.30
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
NOTE
1.
Rating conditions (#)
: Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB : Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.
3. Above data represents the value when the operation frequency of a compressor is fixed.
28

5-3. Cooling Capacity (Low Ambient)

Indoor Unit : CS-KE12NB41 & CZ-18BT1U
Outdoor Unit : CU-KE12NK1
Power Supply : 115V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
RATING CAPACITY: 11,900 BTU/h AIR FLOW RATE: 235 CFM
INDOOR OUTDOOR
ENT. TEMP.
WB DB 0 5 15 25 35 45 55
59 76 (24.4) SHC 7,800 7,800 7,850 9,450 7,850 7,850 7,850
(15.0) 80 (26.7) SHC 8,720 8,720 8,720 9,590 8,760 8,760 8,760
63 76 (24.4) SHC 6,520 6,520 6,570 9,450 6,610 6,610 6,660
(17.2) 80 (26.7) SHC 7,440 7,440 7,480 9,590 7,530 7,530 7,530
67 76 (24.4) SHC 5,240 5,240 5,290 9,450 5,380 5,420 5,420
(19.4) 80 (26.7) SHC 6,160 6,160 6,200 9,530 6,290 6,340 6,340
71 76 (24.4) SHC 3,870 3,920 3,960 9,380 4,100 4,140 4,140
(21.7) 80 (26.7) SHC 4,780 4,830 4,880 9,380 5,010 5,060 5,060
75 76 (24.4) SHC 2,590 2,640 2,730 9,160 2,860 2,910 2,960
(23.9) 80 (26.7) SHC 3,500 3,550 3,640 9,160 3,780 3,820 3,870
o
F (oC) AMBIENT TEMP. oF (oC)
(-17.8) (-15.0) (-9.4) (-3.9) (1.7) (7.2) (12.8)
TC 9,530 9,550 9,560 9,590 9,600 9,590 9,570
CI
72 (22.2) SHC 6,930 6,930 6,980 8,580 6,980 6,980 6,980
84 (28.9) SHC 9,530 9,550 9,560 9,590 9,600 9,590 9,570 88 (31.1) SHC 9,530 9,550 9,560 9,590 9,600 9,590 9,570
TC 9,440 9,460 9,530 9,590 9,650 9,660 9,670
CI
72 (22.2) SHC 5,650 5,650 5,700 8,580 5,740 5,740 5,790
84 (28.9) SHC 8,300 8,300 8,350 9,590 8,400 8,400 8,400 88 (31.1) SHC 9,170 9,170 9,220 9,590 9,270 9,270 9,270
TC 9,250 9,290 9,410 9,530 9,620 9,670 9,720
CI
72 (22.2) SHC 4,370 4,370 4,420 8,580 4,510 4,560 4,560
84 (28.9) SHC 7,020 7,020 7,070 9,530 7,160 7,210 7,210 88 (31.1) SHC 7,890 7,890 7,940 9,530 8,030 8,080 8,080
TC 8,950 9,010 9,210 9,380 9,520 9,610 9,710
CI
72 (22.2) SHC 3,000 3,050 3,090 8,580 3,230 3,280 3,280
84 (28.9) SHC 5,650 5,700 5,740 9,380 5,880 5,930 5,930 88 (31.1) SHC 6,520 6,570 6,610 9,380 6,750 6,800 6,800
TC 8,590 8,650 8,930 9,160 9,360 9,480 9,620
CI
84 (28.9) SHC 4,370 4,420 4,510 9,160 4,650 4,690 4,740 88 (31.1) SHC 5,240 5,290 5,380 9,160 5,520 5,560 5,610
0.47 0.50 0.47 0.46 0.46 0.51 0.55
0.53 0.56 0.51 0.49 0.49 0.53 0.57
0.61 0.63 0.57 0.54 0.52 0.56 0.59
0.68 0.71 0.63 0.58 0.56 0.60 0.62
0.76 0.79 0.69 0.63 0.60 0.63 0.64
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
NOTE
1.
Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.
2. Above data represents the value when the operation frequency of a compressor is fixed.
29
Indoor Unit : CS-KE18NB4UW & CZ-18BT1U
Outdoor Unit : CU-KE18NKU
Power Supply : 230V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
RATING CAPACITY: 17,500 BTU/h AIR FLOW RATE: 341 CFM
INDOOR OUTDOOR
ENT. TEMP.
WB DB 0 5 15 25 35 45 55
59 76 (24.4) SHC 10,930 10,930 10,930 13,050 11,000 11,000 11,000
(15.0) 80 (26.7) SHC 12,190 12,190 12,190 13,470 12,190 12,260 12,190
63 76 (24.4) SHC 9,140 9,140 9,210 13,050 9,270 9,270 9,340
(17.2) 80 (26.7) SHC 10,400 10,400 10,400 13,480 10,530 10,530 10,600
67 76 (24.4) SHC 7,280 7,350 7,420 13,050 7,550 7,610 7,680
(19.4) 80 (26.7) SHC 8,540 8,610 8,680 13,380 8,810 8,870 8,870
71 76 (24.4) SHC 5,430 5,490 5,560 13,050 5,760 5,820 5,890
(21.7) 80 (26.7) SHC 6,690 6,690 6,820 13,160 7,020 7,080 7,150
75 76 (24.4) SHC 3,640 3,700 3,770 12,850 4,030 4,170 4,230
(23.9) 80 (26.7) SHC 4,900 4,960 5,030 12,850 5,290 5,360 5,490
o
F (oC) AMBIENT TEMP. oF (oC)
(-17.8) (-15.0) (-9.4) (-3.9) (1.7) (7.2) (12.8)
TC 13,400 13,430 13,440 13,470 13,500 13,520 13,510
CI
72 (22.2) SHC 9,740 9,740 9,740 11,860 9,740 9,800 9,800
84 (28.9) SHC 13,380 13,380 13,380 13,470 13,380 13,450 13,450 88 (31.1) SHC 13,400 13,430 13,440 13,470 13,500 13,520 13,510
TC 13,260 13,300 13,370 13,480 13,560 13,640 13,670
CI
72 (22.2) SHC 7,950 7,950 7,950 11,860 8,080 8,080 8,140
84 (28.9) SHC 11,590 11,590 11,590 13,480 11,720 11,720 11,790 88 (31.1) SHC 12,790 12,790 12,850 13,480 12,920 12,980 12,980
TC 12,980 13,040 13,170 13,380 13,530 13,670 13,760
CI
72 (22.2) SHC 6,090 6,160 6,220 11,860 6,360 6,420 6,420
84 (28.9) SHC 9,740 9,800 9,870 13,380 10,000 10,070 10,070 88 (31.1) SHC 11,000 11,000 11,060 13,380 11,190 11,260 11,330
TC 12,550 12,630 12,830 13,160 13,390 13,600 13,750
CI
72 (22.2) SHC 4,230 4,230 4,370 11,860 4,570 4,630 4,700
84 (28.9) SHC 7,880 7,950 8,010 13,160 8,210 8,280 8,340 88 (31.1) SHC 9,070 9,140 9,210 13,160 9,400 9,470 9,540
TC 12,010 12,110 12,380 12,850 13,150 13,440 13,650
CI
84 (28.9) SHC 6,090 6,160 6,220 12,850 6,490 6,620 6,690 88 (31.1) SHC 7,280 7,350 7,420 12,850 7,680 7,810 7,880
0.69 0.73 0.76 0.66 0.66 0.66 0.70
0.78 0.82 0.84 0.71 0.70 0.69 0.72
0.89 0.92 0.93 0.78 0.75 0.72 0.75
1.00 1.03 1.03 0.85 0.80 0.76 0.77
1.11 1.14 1.13 0.92 0.86 0.80 0.80
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)
NOTE
1.
Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics.
2. Above data represents the value when the operation frequency of a compressor is fixed.
30