Before operating the unit, please read these operating
instructions thoroughly and keep them for future reference.
The included Installation Instructions should be kept and read
by the installer before installation.
Remote control is packaged in the indoor unit and removed
by the installer before installation.
2-23
Comment utiliser l’appareil
Climatiseur
Avant d’utiliser l’appareil, veuillez lire ce mode d’emploi dans
son intégralité et conservez-le pour toute référence ultérieure.
Le manuel d’installation inclus doit être conservé et lu par
l’installateur avant l’installation.
La télécommande est emballée dans l’unité intérieure et
retirée par l’installateur avant l’installation.
Instrucciones de funcionamiento
Climatizador de aire
Antes de utilizar la unidad, sírvase leer atentamente estas
instrucciones de funcionamiento y conservarlas para futuras
consultas.
El instalador debe guardar y leer las Instrucciones de
instalación incluidas antes de la instalación.
El mando a distancia viene embalado en la unidad interior y
debe ser retirado por el instalador antes de la instalación.
24-45
46-67
EspañolFrançaisEnglish
ACXF55-18840
Provides maximum comfort with optimal
FAN SPEED
FAN SPEED
energy saving methods.
Use remote
control within 8 m
from the remote
control receiver of
the indoor unit.
* Remote control display
and functions may
vary depending on the
model.
Quick Guide
Inserting the batteries
B
Pull out the back cover
1
A
of remote control.
Insert AAA or R03
2
batteries.
Close the cover.
3
1
2
3
2
A
Clock setting
Press
1
time .
and
• Press and hold
for approximately
5 seconds to show
time in 12-hour
(am/pm) or 24 hour
indication.
Confi rm .
2
set the
Thank you for purchasing
Panasonic Air Conditioner.
Table of contents
Safety precautions
How to use
To learn more
Cleaning instructions
Troubleshooting
Information
..........
4-15
.........................
......................
...............
............................
.....
16-17
18
19-20
21-23
68
Accessories
• Remote control
• AAA or R03 batteries × 2
• Remote control holder
• Screws for remote control
holder × 2
The illustrations in this manual are for
explanation purposes only and may differ
from the actual unit. They are subject
to change without notice for future
improvement.
English
B
Basic operation
Press
1
to select
the desired mode.
AUTOHEAT
DRY
COOL
Press
2
to start/
stop the operation.
POWER
• Please note that
the
indication
is on display to
start the unit.
Select the desired
3
temperature.
Up
Down
Selection range:
16.0 °C ~ 30.0 °C /
60 °F ~ 86 °F.
• Press and hold
approximately 10 seconds
to switch the temperature
indication in °C or °F.
for
3
Safety precautions
Air inlet
Air inlet
Air outlet
Air outlet
To prevent personal injury, injury to others
or property damage, please comply with the
following:
Incorrect operation due to failure to follow
instructions below may cause harm or
damage, the seriousness of which is
classifi ed as below:
This appliances is not intended for
accessibility by the general public.
This sign
Air inlet
warns of
death or
serious injury.
This sign
warns of
injury or
damage to
property.
Power supply
Air outlet
WARNING
CAUTION
The instructions to be followed are classifi ed
by the following symbols:
This symbol denotes an
action that is PROHIBITED.
These symbols denote
actions COMPULSORY.
Indoor unit
Air outlet
Remote control
Outdoor unit
Air inlet
WARNING
Indoor unit and outdoor unit
This appliance can be used by
children aged from 8 years and
above and persons with reduced
physical, sensory or mental
capabilities or lack of experience
and knowledge if they have been
given supervision or instruction
concerning use of the appliance
in a safe way and understand the
hazards involved.
Children shall not play with the
appliance. Cleaning and user
maintenance shall not be made by
children without supervision.
Please consult authorised dealer or
specialist to clean the internal parts,
repair, install, remove and reinstall
the unit. Improper installation and
handling will cause leakage, electric
shock or fi re.
Confi rm with authorised dealer or
specialist on usage of any specifi ed
refrigerant type. Using refrigerant
type other than the specifi ed may
cause product damage, burst and
injury etc.
Do not use means to accelerate
the defrosting process or to clean,
other than those recommended by
manufacturer.
Any unfi t method or using
incompatible material may cause
product damage, burst and serious
injury.
Do not install the unit in a potentially
explosive or fl ammable atmosphere.
Failure to do so could result in fi re.
4
Do not insert your fi ngers
or other objects into the air
conditioner indoor or outdoor
unit, rotating parts may cause
injury.
Do not touch the outdoor unit during
lightning, it may cause electric
shock.
Do not expose yourself directly to
cold air for a long period to avoid
excess cooling.
Do not sit or step on the unit,
you may fall down accidentally.
Remote control
Do not allow infants and small
children to play with the remote
control to prevent them from
accidentally swallowing the batteries.
Power supply
Do not use a modifi ed
cord, joint cord,
extension cord or
unspecifi ed cord to
prevent overheating
and fi re.
To prevent overheating, fi re or
electric shock:
•
Do not share the same power outlet
with other equipment.
•
Do not operate with wet hands.
•
Do not over bend the power supply
cord.
•
Do not operate or stop the unit by
inserting or pulling out the power
plug.
If the supply cord is damaged,
it must be replaced by the
manufacturer, service agent or
similarly qualifi ed persons in order to
avoid a hazard.
It is strongly recommended to be
installed with Earth Leakage Circuit
Breaker (ELCB) or Residual Current
Device (RCD) to prevent electric
shock or fi re.
To prevent overheating, fi re or
electric shock:
•
Insert the power plug properly.
•
Dust on the power plug should be
periodically wiped with a dry cloth.
Stop using the product if any
abnormality/failure occurs and
disconnect the power plug or turn off
the power switch and breaker.
(Risk of smoke/fi re/electric shock)
Examples of abnormality/failure
•
The ELCB trips frequently.
•
Burning smell is observed.
•
Abnormal noise or vibration of the
unit is observed.
•
Water leaks from the indoor unit.
•
Power cord or plug becomes
abnormally hot.
•
Fan speed cannot be controlled.
•
The unit stops running immediately
even if it is switched on for
operation.
•
The fan does not stop even if the
operation is stopped.
Contact your local dealer
immediately for maintenance/repair.
This equipment must be earthed to
prevent electrical shock or fi re.
Prevent electric shock by switching
off the power supply and unplug:
-Before cleaning or servicing,
-When extended non-use, or
-During abnormally strong
lightning activity.
EnglishSafety precautions
5
Safety precautions
CAUTION
Indoor unit and outdoor unit
Do not wash the indoor unit with
water, benzine, thinner or scouring
powder to avoid damage or
corrosion at the unit.
Do not use for preservation of
precise equipment, food, animals,
plants, artwork or other objects. This
may cause quality deterioration, etc.
Do not use any combustible
equipment in front of the airfl ow
outlet to avoid fi re propagation.
Do not expose plants or pet directly
to airfl ow to avoid injury, etc.
Do not touch the sharp
aluminium fi n, sharp parts may
cause injury.
Do not switch ON the indoor unit
when waxing the fl oor. After waxing,
aerate the room properly before
operating the unit.
Do not install the unit in oily and
smoky areas to prevent damage to
the unit.
Do not dismantle the unit for
cleaning purpose to avoid injury.
Do not step onto an unstable bench
when cleaning the unit to avoid
injury.
Do not place a vase or water
container on the unit. Water may
enter the unit and degrade the
insulation. This may cause an
electric shock.
Do not open window or door for
long time during operation, it may
lead to ineffi cient power usage and
uncomfortable temperature changes.
Prevent water leakage by ensuring
drainage pipe is:
-Connected properly,
-Kept clear of gutters and containers,
or
-Not immersed in water
After a long period of use or use with
any combustible equipment, aerate
the room regularly.
After a long period of use, make
sure the installation rack does not
deteriorate to prevent the unit from
falling down.
Remote control
Do not use rechargeable (Ni-Cd)
batteries. It may damage the remote
control.
To prevent malfunction or damage of
the remote control:
•
Remove the batteries if the unit
is not going to be used for a long
period of time.
•
New batteries of the same type
must be inserted following the
polarity stated.
Power supply
Do not disconnect the plug by pulling
the cord to prevent electric shock.
6
WARNING
This appliance is fi lled with
R32
(mild fl ammable refrigerant).
If the refrigerant is leaked and
exposed to an external ignition
source, there is a risk of fi re.
Indoor unit and outdoor unit
The appliance shall be installed,
and/or operated in a room with fl oor
area larger than Amin (m²) and
keep away from ignition sources,
such as heat/sparks/open fl ame
or hazardous areas such as gas
appliances, gas cooking, reticulated
gas supply systems or electric
cooking appliances, etc.(Refer to
Table A of Installation instructions
table for Amin (m²))
Be aware that refrigerant may
not contain an odour, highly
recommended to ensure suitable
fl ammable refrigerant gas detectors
are present, operating and able to
warn of a leak.
Keep any required ventilation
openings clear of obstruction.
Do not pierce or burn as the
appliance is pressurized. Do not
expose the appliance to heat, fl ame,
sparks, or other sources of ignition.
Else it may explode and cause injury
or death.
Precaution for using R32
refrigerant
The basic installation work procedures
are the same as conventional refrigerant
(R410A, R22) models.
Since the working pressure is
higher than that of refrigerant R22
models, some of the piping and
installation and service tools are
special. Especially, when replacing
a refrigerant R22 model with a
new refrigerant R32 model, always
replace the conventional piping and
fl are nuts with the R32 and R410A
piping and fl are nuts on the outdoor
unit side.
For R32 and R410A, the same fl are
nut on the outdoor unit side and pipe
can be used.
The mixing of different refrigerants
within a system is prohibited. Models
that use refrigerant R32 and R410A
have a different charging port thread
diameter to prevent erroneous
charging with refrigerant R22 and for
safety.
Therefore, check beforehand. [The
charging port thread diameter for
R32 and R410A is 1/2 inch.]
Must always ensure that foreign
matter (oil, water, etc.) does not
enter the piping. Also, when storing
the piping, securely seal the opening
by pinching, taping, etc. (Handling of
R32 is similar to R410A.)
•
Operation, maintenance, repairing
and refrigerant recovery should be
carried out by trained and certifi ed
personnel in the use of fl ammable
refrigerants and as recommended
by the manufacturer. Any personnel
conducting an operation, servicing
or maintenance on a system or
associated parts of the equipment
should be trained and certifi ed.
English
Safety precautions
7
Safety precautions
•
Any part of refrigerating circuit
(evaporators, air coolers, AHU,
condensers or liquid receivers) or
piping should not be located in the
proximity of heat sources, open
fl ames, operating gas appliance or
an operating electric heater.
•
The user/owner or their authorised
representative shall regularly check
the alarms, mechanical ventilation
and detectors, at least once a
year, where as required by national
regulations, to ensure their correct
functioning.
•
A logbook shall be maintained. The
results of these checks shall be
recorded in the logbook.
•
In case of ventilations in occupied
spaces shall be checked to confi rm
no obstruction.
•
Before a new refrigerating system
is put into service, the person
responsible for placing the system
in operation should ensure that
trained and certifi ed operating
personnel are instructed on the
basis of the instruction manual
about the construction, supervision,
operation and maintenance of the
refrigerating system, as well as the
safety measures to be observed,
and the properties and handling of
the refrigerant used.
•
The general requirement of
trained and certifi ed personnel are
indicated as below:
a) Knowledge of legislation,
regulations and standards
relating to fl ammable
refrigerants; and,
b) Detailed knowledge of and
skills in handling fl ammable
refrigerants, personal protective
equipment, refrigerant
leakage prevention, handling
of cylinders, charging, leak
detection, recovery and
disposal; and,
c) Able to understand and to apply
in practice the requirements
in the national legislation,
regulations and Standards; and,
d) Continuously undergo regular
and further training to maintain
this expertise.
1. Installation (Space)
•
Product with fl ammable
refrigerants, shall not be installed in
an unventilated space, if that space
is smaller than Amin (m²).
•
In case of fi eld charge, the effect
on refrigerant charge caused by
the different pipe length has to be
quantifi ed, measured and labelled.
•
Must ensure the installation of pipework shall be kept to a minimum.
Avoid use dented pipe and do not
allow acute bending.
•
Must ensure that pipe-work shall be
protected from physical damage.
•
Must comply with national gas
regulations, state municipal rules
and legislation. Notify relevant
authorities in accordance with all
applicable regulations.
•
Must ensure mechanical
connections be accessible for
maintenance purposes.
•
In cases that require mechanical
ventilation, ventilation openings
shall be kept clear of obstruction.
•
When disposal of the product, do
follow to the precautions in #12 and
comply with national regulations.
Always contact to local municipal
offi ces for proper handling.
8
2. Servicing
2-1. Service personnel
•
The system is inspected, regularly
supervised and maintained by
a trained and certifi ed service
personnel who is employed by the
person user or party responsible.
•
Ensure the actual refrigerant
charge size is in accordance with
the room size within which the
refrigerant containing parts are
installed.
•
Ensure refrigerant charge not to
leak.
•
Any qualifi ed person who is
involved with working on or
breaking into a refrigerant circuit
should hold a current valid
certifi cate from an industry-
accredited assessment authority,
which authorizes their competence
to handle refrigerants safely in
accordance with an industry
recognised assessment
specifi cation.
•
Servicing shall only be performed
as recommended by the equipment
manufacturer. Maintenance and
repair requiring the assistance of
other skilled personnel shall be
carried out under the supervision of
the person competent in the use of
fl ammable refrigerants.
•
Servicing shall be performed
only as recommended by the
manufacturer.
2-2. Work
•
Prior to beginning work on
systems containing fl ammable
refrigerants, safety checks are
necessary to ensure that the risk
of ignition is minimised. For repair
to the refrigerating system, the
precautions in #2-2 to #2-8 must
be followed before conducting
work on the system.
•
Work shall be undertaken under
a controlled procedure so as to
minimize the risk of a fl ammable
gas or vapour being present while
the work is being performed.
•
All maintenance staff and others
working in the local area shall be
instructed and supervised on the
nature of work being carried out.
•
Avoid working in confi ned spaces.
Always ensure away from source,
at least 2 meter of safety distance,
or zoning of free space area of at
least 2 meter in radius.
•
Wear appropriate protective
equipment, including respiratory
protection, as conditions warrant.
•
Ensure that the conditions within
the area have been made safe
by limit of use of any fl ammable
material. Keep all sources of
ignition and hot metal surfaces
away.
English
Safety precautions
9
Safety precautions
2-3. Checking for presence of
refrigerant
•
The area shall be checked with an
appropriate refrigerant detector
prior to and during work, to
ensure the technician is aware of
potentially fl ammable atmospheres.
•
Ensure that the leak detection
equipment being used is suitable
for use with fl ammable refrigerants,
i.e. non sparking, adequately
sealed or intrinsically safe.
•
In case of leakage/spillage
happened, immediately ventilate
area and stay upwind and away
from spill/release.
•
In case of leakage/spillage
happened, do notify persons down
wind of the leaking/spill, isolate
immediate hazard area and keep
unauthorized personnel out.
2-4. Presence of fi re extinguisher
•
If any hot work is to be conducted
on the refrigeration equipment or
any associated parts, appropriate
fi re extinguishing equipment shall
be available at hand.
•
Have a dry powder or CO2 fi re
extinguisher adjacent to the
charging area.
2-5. No ignition sources
•
No person carrying out work in
relation to a refrigeration system
which involves exposing any pipe
work that contains or has contained
fl ammable refrigerant shall use
any sources of ignition in such a
manner that it may lead to the risk
of fi re or explosion. He/She must
not be smoking when carrying out
such work.
•
All possible ignition sources,
including cigarette smoking, should
be kept suffi ciently far away from
the site of installation, repairing,
removing and disposal, during
which fl ammable refrigerant
can possibly be released to the
surrounding space.
•
Prior to work taking place, the
area around the equipment is to
be surveyed to make sure that
there are no fl ammable hazards or
ignition risks.
•
“No Smoking” signs shall be
displayed.
2-6. Ventilated area
•
Ensure that the area is in the open
or that it is adequately ventilated
before breaking into the system or
conducting any hot work.
•
A degree of ventilation shall
continue during the period that the
work is carried out.
•
The ventilation should safely
disperse any released refrigerant
and preferably expel it externally
into the atmosphere.
10
2-7. Checks to the refrigeration
equipment
•
Where electrical components are
being changed, they shall be fi t
for the purpose and to the correct
specifi cation.
•
At all times the manufacturer’s
maintenance and service
guidelines shall be followed.
•
If in doubt consult the
manufacturer’s technical
department for assistance.
•
The following checks shall be
applied to installations using
fl ammable refrigerants.
-
The charge size is in accordance
with the room size within which
the refrigerant containing parts
are installed.
-
The ventilation machinery and
outlets are operating adequately
and are not obstructed.
-
If an indirect refrigerating circuit is
being used, the secondary circuit
shall be checked for the presence
of refrigerant.
-
Marking to the equipment
continues to be visible and
legible. Markings and signs that
are illegible shall be corrected.
-
Refrigeration pipe or components
are installed in a position where
they are unlikely to be exposed
to any substance which may
corrode refrigerant containing
components, unless the
components are constructed of
materials which are inherently
resistant to being corroded or are
properly protected against being
so corroded.
2-8. Checks to electrical devices
•
Repair and maintenance to
electrical components shall include
initial safety checks and component
inspection procedures.
•
Initial safety checks shall include
but not limit to:-
-
That capacitors are discharged:
this shall be done in a safe
manner to avoid possibility of
sparking.
-
That there no live electrical
components and wiring are
exposed while charging,
recovering or purging the system.
-
That there is continuity of earth
bonding.
•
At all times the manufacturer’s
maintenance and service guidelines
shall be followed.
•
If in doubt consult the
English
manufacturer’s technical
department for assistance.
•
If a fault exists that could
compromise safety, then no
electrical supply shall be connected
to the circuit until it is satisfactorily
dealt with.
•
If the fault cannot be corrected
immediately but it is necessary to
continue operation, an adequate
Safety precautions
temporary solution shall be used.
•
The owner of the equipment must
be informed or reported so all
parties are advised thereinafter.
11
Safety precautions
3. Repairs to sealed components
•
During repairs to sealed
components, all electrical supplies
shall be disconnected from the
equipment being worked upon prior
to any removal of sealed covers,
etc.
•
If it is absolutely necessary to
have an electrical supply to
equipment during servicing, then
a permanently operating form of
leak detection shall be located at
the most critical point to warn of a
potentially hazardous situation.
•
Particular attention shall be paid
to the following to ensure that by
working on electrical components,
the casing is not altered in such a
way that the level of protection is
affected.This shall include damage
to cables, excessive number of
connections, terminals not made
to original specifi cation, damage to
seals, incorrect fi tting of glands, etc.
•
Ensure that apparatus is mounted
securely.
•
Ensure that seals or sealing
materials have not degraded such
that they no longer serve the
purpose of preventing the ingress
of fl ammable atmospheres.
•
Replacement parts shall be in
accordance with the manufacturer’s
specifi cations.
NOTE: The use of silicon sealant
may inhibit the effectiveness of some
types of leak detection equipment.
Intrinsically safe components do not
have to be isolated prior to working
on them.
4. Repair to intrinsically safe
components
•
Do not apply any permanent
inductive or capacitance loads to
the circuit without ensuring that
this will not exceed the permissible
voltage and current permitted for
the equipment in use.
•
Intrinsically safe components are
the only types that can be worked
on while live in the presence of a
fl ammable atmosphere.
•
The test apparatus shall be at the
correct rating.
•
Replace components only with
parts specifi ed by the manufacturer.
Unspecifi ed parts by manufacturer
may result ignition of refrigerant in
the atmosphere from a leak.
5. Cabling
•
Check that cabling will not be
subject to wear, corrosion,
excessive pressure, vibration,
sharp edges or any other adverse
environmental effects.
•
The check shall also take into
account the effects of aging or
continual vibration from sources
such as compressors or fans.
6. Detection of fl ammable
refrigerants
•
Under no circumstances shall
potential sources of ignition be
used in the searching or detection
of refrigerant leaks.
•
A halide torch (or any other detector
using a naked fl ame) shall not be
used.
12
7. Leak detection methods
The following leak detection
methods are deemed acceptable for
all refrigerant systems.
•
No leaks shall be detected when
using detection equipment with a
capability of 10−6 Pa·m3/s or better,
for example, a helium sniffer.
•
Electronic leak detectors may
be used to detect fl ammable
refrigerants, but the sensitivity may
not be adequate, or may need recalibration.
(Detection equipment shall be
calibrated in a refrigerant-free
area.)
•
Ensure that the detector is not a
potential source of ignition and is
suitable for the refrigerant used.
•
Leak detection equipment shall
be set at a percentage of the
LFL of the refrigerant and shall
be calibrated to the refrigerant
employed and the appropriate
percentage of gas (25 % maximum)
is confi rmed.
•
Leak detection fl uids are suitable
for use with most refrigerants but
the use of detergents containing
chlorine shall be avoided as
the chlorine may react with the
refrigerant and corrode the copper
pipe-work.
•
If a leak is suspected, all naked
fl ames shall be removed/
extinguished.
•
If a leakage of refrigerant is found
which requires brazing, all of the
refrigerant shall be recovered from
the system, or isolated (by means
of shut off valves) in a part of the
system remote from the leak.
Oxygen free nitrogen (OFN) shall
then be purged through the system
both before and during the brazing
process.
OFN = oxygen free nitrogen,
type of inert gas.
8. Removal and evacuation
•
When breaking into the refrigerant
circuit to make repairs – or for
any other purpose – conventional
procedures shall be used. However,
it is important that best practice
is followed since fl ammability is
a consideration. The following
procedure shall be adhered to:
remove refrigerant -> purge the
circuit with inert gas -> evacuate ->
purge again with inert gas -> open
the circuit by cutting or brazing
•
The refrigerant charge shall be
recovered into the correct recovery
cylinders.
•
The system shall be “fl ushed” with
OFN to render the unit safe.
•
This process may need to be
repeated several times.
•
Compressed air or oxygen shall not
English
be used for this task.
•
Flushing shall be achieved by
breaking the vacuum in the system
with OFN and continuing to fi ll until
the working pressure is achieved,
then venting to atmosphere, and
fi nally pulling down to a vacuum.
•
This process shall be repeated until
no refrigerant is within the system.
•
When the fi nal OFN charge is used,
Safety precautions
the system shall be vented down
to atmospheric pressure to enable
work to take place.
•
This operation is absolutely vital if
brazing operations on the pipe work
are to take place.
•
Ensure that the outlet for the
vacuum pump is not close to
any ignition sources and there is
ventilation available.
13
Safety precautions
9. Charging procedures
•
In addition to conventional
charging procedures, the following
requirements shall be followed.
-
Ensure that contamination of
different refrigerants does not
occur when using charging
equipment.
-
Hoses or lines shall be as short
as possible to minimize the
amount of refrigerant contained
in them.
-
Cylinders shall be kept upright.
-
Ensure that the refrigeration
system is earthed prior to
charging the system with
refrigerant.
-
Label the system when charging
is complete (if not already).
-
Extreme care shall be taken
not to over fi ll the refrigeration
system.
•
Prior to recharging the system it
shall be pressure tested with OFN
(refer to #7).
•
The system shall be leak tested on
completion of charging but prior to
commissioning.
•
A follow up leak test shall be carried
out prior to leaving the site.
•
Electrostatic charge may
accumulate and create a hazardous
condition when charging and
discharging the refrigerant.To
avoid fi re or explosion, dissipate
static electricity during transfer by
grounding and bonding containers
and equipment before charging/
discharging.
10. Decommissioning
•
Before carrying out this procedure,
it is essential that the technician
is completely familiar with the
equipment and all its details.
•
It is recommended good practice
that all refrigerants are recovered
safely.
•
Prior to the task being carried
out, an oil and refrigerant sample
shall be taken in case analysis is
required prior to re-use of reclaimed
refrigerant.
•
It is essential that electrical power
is available before the task is
commenced.
a) Become familiar with the
equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure
ensure that:
•
mechanical handling equipment
is available, if required, for
handling refrigerant cylinders;
•
all personal protective equipment
is available and being used
correctly;
•
the recovery process is
supervised at all times by a
competent person;
•
recovery equipment and
cylinders conform to the
appropriate standards.
d) Pump down refrigerant system,
if possible.
e) If a vacuum is not possible,
make a manifold so that
refrigerant can be removed from
various parts of the system.
f) Make sure that cylinder is
situated on the scales before
recovery takes place.
g) Start the recovery machine and
operate in accordance with
manufacturer’s instructions.
h) Do not over fi ll cylinders. (No
more than 80 % volume liquid
charge).
14
i) Do not exceed the maximum
working pressure of the cylinder,
even temporarily.
j) When the cylinders have been
fi lled correctly and the process
completed, make sure that the
cylinders and the equipment
are removed from site promptly
and all isolation valves on the
equipment are closed off.
k) Recovered refrigerant shall
not be charged into another
refrigeration system unless it has
been cleaned and checked.
•
Electrostatic charge may accumulate
and create a hazardous condition
when charging or discharging the
refrigerant.To avoid fi re or explosion,
dissipate static electricity during
transfer by grounding and bonding
containers and equipment before
charging/discharging.
11. Labelling
•
Equipment shall be labelled stating
that it has been de-commissioned
and emptied of refrigerant.
•
The label shall be dated and signed.
•
Ensure that there are labels on the
equipment stating the equipment
contains fl ammable refrigerant.
12. Recovery
•
When removing refrigerant from
a system, either for servicing
or decommissioning, it is
recommended good practice that all
refrigerants are removed safely.
•
When transferring refrigerant
into cylinders, ensure that only
appropriate refrigerant recovery
cylinders are employed.
•
Ensure that the correct number
of cylinders for holding the total
system charge are available.
•
All cylinders to be used are
designated for the recovered
refrigerant and labelled for that
refrigerant (i.e. special cylinders for
the recovery of refrigerant).
•
Cylinders shall be complete
with pressure relief valve and
associated shut-off valves in good
working order.
•
Recovery cylinders are evacuated
and, if possible, cooled before
recovery occurs.
•
The recovery equipment shall
be in good working order with a
set of instructions concerning the
equipment that is at hand and
shall be suitable for the recovery of
fl ammable refrigerants.
•
In addition, a set of calibrated
weighing scales shall be available
and in good working order.
•
Hoses shall be complete with leakfree disconnect couplings and in
good condition.
•
Before using the recovery machine,
check that it is in satisfactory
working order, has been properly
maintained and that any associated
electrical components are sealed
to prevent ignition in the event
of a refrigerant release.Consult
manufacturer if in doubt.
•
The recovered refrigerant shall be
returned to the refrigerant supplier
in the correct recovery cylinder, and
the relevant Waste Transfer Note
arranged.
•
Do not mix refrigerants in recovery
units and especially not in cylinders.
•
If compressors or compressor oils
are to be removed, ensure that
they have been evacuated to an
acceptable level to make certain
that fl ammable refrigerant does not
remain within the lubricant.
•
The evacuation process shall be
carried out prior to returning the
compressor to the suppliers.
•
Only electric heating to the
compressor body shall be
employed to accelerate this
process.
•
When oil is drained from a system,
it shall be carried out safely.
English
Safety precautions
15
How to use
FAN SPEEDFAN SPEED
To adjust airfl ow direction
To adjust airfl ow direction
(CS-FZ25/35/50UKE)
Indicator
CS-FZ25/35/50UKE
CS-FZ60UKE
FAN SPEED
POWER
TIMER
AIR SWING
Upper direction
• Do not adjust the fl ap by hand.
• For lateral direction, it is manually
adjustable as shown.
To adjust airfl ow direction
To adjust airfl ow direction
(CS-FZ60UKE)
Upper direction
AIR SWING
Lateral direction
• Do not adjust the fl ap by hand.
To adjust fan speed
AUTO
FAN
• For AUTO, the indoor fan speed is automatically
adjusted according to the operation mode.
• To have low noise priority operation, select the
lowest fan speed (
).
Not used
in normal
operations.
16
Press to restore
the remote
control to default
setting.
To switch between powerful/quiet
POWERFUL:
To reach the preset temperature quickly
• This operation stops automatically after 20 minutes.
QUIET:
To enjoy quiet operation
• This operation reduces airfl ow noise.
See "To learn more..." for details.
CANCEL
To maximise comfort while sleeping
This operation provides you with a comfortable environment while sleeping. It will
automatically adjust the sleep pattern temperature during the activation period. The indoor
unit indicator will dim when this operation is activated. This is not applicable if the indicator
brightness has been manually dimmed.
•
SLEEP
(Cancel)
This operation is incorporated with the
activation timer (0.5, 1, 2, 3, 4, 5, 6, 7, 8 or 9
hours).
This operation can be set together with timer.
Sleep operation has the priority over OFF
timer.
•
This operation can be cancelled by pressing
the respective button when the sleep timer
reaches 0.0h.
To set the timer
2 sets of ON and OFF timers are available to turn ON or OFF the unit at different preset
times.
213
ON
TIMER
OFF
Select ON or OFF
1
timer
• Each time pressed:
Cancel
SET
CANCEL
Example:
OFF at 22:00
• To cancel ON or OFF timer, press
or
to select respective or then
press
.
• If timer is cancelled manually or due to
power failure, you can restore the timer
again by pressing
respective
or then press .
or to select
• The nearest timer setting will be displayed
and will activate in sequence.
• Timer operation is based on the clock set
in the remote control and repeats daily
once set. For clock setting, please refer to
2 Set the time
Quick Guide.
English
How to use
3 Confi rm
Note
SLEEP
,
• Can be activated in all modes and can be
cancelled by pressing the respective button
again.
• Cannot be selected at the same time.
17
To learn more...
Operation mode
AUTO : During operation, the POWER indicator will blinks at initial.
HEAT : The POWER indicator blinks at the initial stage of this operation. Unit takes a while
COOL : Provides effi cient comfort cooling to suit your needs.
DRY: Unit operates at low fan speed to give a gentle cooling operation.
Energy saving temperature setting
Operating the unit within the recommended temperature range may save energy.
HEAT : 20.0 °C ~ 24.0 °C /
COOL: 26.0 °C ~ 28.0 °C /
Air fl ow direction
In COOL/DRY mode:
(CS-FZ25/35/50UKE)
If AUTO is set, the fl ap swings up/down automatically.
(CS-FZ60UKE)
If
AUTO is set, the fl ap swings left/right and up/down automatically.
In HEAT mode:
If AUTO is set, the horizontal fl ap is fi xed at the predetermined position. The vertical fl ap
swings left/right after the temperature rises.
Unit selects operation mode every 10 minutes according to the setting and room
temperatures.
to warm up.
• For system which HEAT mode has been locked, if operation mode other than
HEAT is selected, the indoor unit stops and the POWER indicator blinks.
68 °F ~ 75 °F.
79 °F ~ 82 °F.
Auto restart control
If power is resumed after a power failure, the operation will restart automatically after a
period of time with previous operation mode and airfl ow direction.
• This control is not applicable when TIMER is set.
Operating conditions
Use this air conditioner in the temperature range indicated in the table.
Temperature
COOL
HEAT
DBT: Dry bulb temperature, WBT: Wet bulb temperature
°C (°F)
DBTWBTDBTWBT
Max. 32 (89.6)23 (73.4)43 (109.4)26 (78.8)
Min. 16 (60.8)11 (51.8)-10 (14.0)-
Max. 30 (86.0)-24 (75.2)18 (64.4)
Min. 16 (60.8)--15 (5.0)-16 (3.2)
IndoorOutdoor
18
Cleaning instructions
To ensure optimal performance of the unit,
cleaning has to be carried out at regular intervals.
Dirty unit may cause malfunction and you may
see error code “H 99”. Please consult authorised
dealer.
• Switch off the power supply and unplug before
cleaning.
• Do not touch the aluminium fi n, sharp parts may
cause injury.
• Do not use benzine, thinner or scouring powder.
• Use only soap (
pH 7) or neutral household
detergent.
• Do not use water hotter than 40 °C / 104 °F.
Indoor unit
Wipe the unit gently with a soft,
dry cloth.
Coils and fans should be clean
for at least every 6 months by
authorised dealer.
Outdoor unit
Clear debris that surround the
unit.
Air fi lters
Once every 2 weeks
• Wash/rinse the fi lters gently
with water to avoid damage to
the fi lter surface.
• Dry the fi lters thoroughly under shade,
away from fi re or direct sunlight.
• Replace any damaged fi lters.
Remove air fi lterAttach air fi lter
Clear any blockage from the
drain pipe.
Air Purifying Filter
• Do not wash/rinse the fi lter with water.
• Replace the fi lter every 2 years or replace
any damaged fi lter.
Part no.: CZ-SA31P
Indoor unit
Front panel
Air Purifying Filter
(CS-FZ25/35UKE)
Air fi lters
Aluminium fi n
Air Purifying Filter
(CS-FZ50/60UKE)
Insert into the unit
POWER
TIMER
EnglishTo learn more... / Cleaning instructions
Air Purifying Filter
19
Cleaning instructions
Front panel
Wash gently and dry.
Remove the front panel
(For CS-FZ25/35/50UKE)(For CS-FZ60UKE)
Raise.
1
Close it securely
For both sides
POWER
TIMER
Pull out.
3
Slide to the
2
right or left.
Pull out.
2
Raise.
1
POWER
TIMER
POWER
TIMER
Close down.
2
Press both ends of the front panel.
3
Insert at
1
both sides.
20
Troubleshooting
The following symptoms do not indicate malfunction.
SymptomCause
POWER indicator blinks before the unit is
switched on.
POWER indicator blinks during HEAT mode
with no warm air supply (and fl ap is closed).
POWER indicator blinks and stops when
operate COOL/DRY mode.
TIMER indicator is always on.• The timer setting repeats daily once set.
Operation is delayed a few minutes after
restarting.
Cooling/heating capacity reduced during the
lowest fan speed setting.
Indoor fan stops occasionally during heating
operation.
Indoor fan stops occasionally during automatic
fan speed setting.
Airfl ow continues even after operation has
stopped.
The room has a peculiar odour.• This may be due to damp smell emitted by the wall,
Cracking sound during operation.• Changes of temperature caused the expansion/
Water fl owing sound during operation.• Refrigerant fl ow inside the unit.
Mist emerges from indoor unit.• Condensation effect due to cooling process.
Outdoor unit emits water/steam.• Condensation or evaporation occurs on pipes.
Dusts accumulated on the wall.• Due to air circulation or static electricity generated
Discoloration of some plastic parts.• Discoloration is subject to material types used in plastic
• This is a preliminary step in preparation for the
operation when the ON timer has been set.
When ON Timer is set, the unit may start earlier (up
to 35 minutes) before the actual set time in order to
achieve the desired temperature on time.
• The unit is in defrost mode (and AIR SWING is set to
AUTO).
• The system has locked to operate in HEAT mode only.
• The delay is a protection to the unit’s compressor.
• The low fan speed is low noise priority operation, so
cooling/heating capacity may be reduced (depending
on the condition). Increase the Fan Speed to increase
the capacity.
• To avoid unintended cooling effect.
• This helps to remove the surrounding odour.
• Extraction of remaining heat from the indoor unit
(maximum 30 seconds).
carpet, furniture or clothing.
contraction of the unit.
by the air conditioner. Some types of wall paper may
collect dusts easily (recommended to clean the area
around the air conditioner frequently).
parts, accelerated when exposed to heat, sun light, UV
light or environmental factor.
English
Check the following before calling for servicing.
SymptomCheck
Operation in HEAT/COOL mode is not working
effi ciently.
Noisy during operation.• Check if the unit has been installed at an incline.
Remote control does not work.
(Display is dim or transmission signal is weak.)
The unit does not work.• Check if the circuit breaker is tripped.
The unit does not receive the signal from the
remote control.
• Set the temperature correctly.
• Close all doors and windows.
• Clean or replace the fi lters.
• Clear any obstruction at the air inlet and air outlet
vents.
• Close the front panel properly.
• Insert the batteries correctly.
• Replace weak batteries.
• Check if timers have been set.
• Make sure the receiver is not obstructed.
• Certain fl uorescent lights may interfere with signal
transmitter. Please consult authorised dealer.
Cleaning instructions / Troubleshooting
21
Troubleshooting
When...
■ The remote control is missing or a malfunction has occurred
1.Raise the front panel.
2.Press the button once to use in AUTO mode.
3. Press and hold the button until you hear 1 beep, then release to use in
forced COOL mode.
4. Repeat step 3. Press and hold the button until you hear 2 beeps, then
release to use in forced HEAT mode.
5.Press the button again to turn off.
■ The indicators are too bright
• To dim or restore the unit’s indicator brightness, press
■ Conducting a seasonal inspection after extended non-use
• Check the remote control batteries.
• Check that there is no obstruction around the air inlet and outlet vents.
• Use Auto OFF/ON button to select COOL/HEAT operation. After 15 minutes of operation, it
is normal to have the following temperature difference between the air inlet and outlet vents:
COOL: ≥ 8 °C / 14.4 °F
■ The units are not going to be used for a long period of time
Activate HEAT mode for 2~3 hours to remove moisture left in the internal parts thoroughly to
•
prevent mould growth.
• Turn off the power supply and unplug.
• Remove the remote control batteries.
HEAT: ≥ 14 °C / 25.2 °F
and hold for 5 seconds.
NON SERVICEABLE CRITERIAS
TURN OFF THE POWER SUPPLY AND UNPLUG then please consult an authorised
dealer when in following conditions:
• Abnormal noise during operation.
• Water/foreign particles have entered the remote control.
• Water leaks from Indoor unit.
• Circuit breaker switches off frequently.
• Power cord becomes unnaturally warm.
• Switches or buttons are not functioning properly.
22
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.