Please file and use this manual together with the Service Manual for Model No. CU-2E15PBE, CU-2E18PBE, CU-3E18PBE,
CU-4E23PBE, CU-4E27PBE, CU-5E34PBE, Order No. PAPAMY1301048CE, PAPAMY1303046CE
This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to service
or repair the products dealt with in this service information by anyone else could result in serious injury or death.
PRECAUTION OF LOW TEMPERATURE
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
14.1 Auto OFF/ON Button .................................. 62
2
1. Safety Precautions
Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing.
Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and
main circuit for the model installed.
The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage,
and the seriousness is classified by the following indications.
WARNING
CAUTION
The items to be followed are classified by the symbols:
Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Do not modify the machine, part, material during repairing service.
2. If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties.
This symbol denotes item that is PROHIBITED from doing.
WARNING
3. Do not wrench the fasten terminal. Pull it out or insert it straightly.
Engage dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water
4.
leakage, electrical shock or fire.
5. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.
Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage,
6.
fire or electrical shock.
Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
7.
done, the set will drop and cause injury.
For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single
8.
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
This equipment is strongly recommended to install with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
9.
Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.
Do not use joint cable for indoor / outdoor connection cable. Use the specified Indoor/Outdoor connection cable, refer to installation
10.
instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor / outdoor connection. Clamp the cable so that
no external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.
Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
11.
cause heat-up or fire at the connection point of terminal, fire or electrical shock.
When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration
12.
cycle (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).
Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb
13.
up to outdoor unit and cross over the handrail and causing accident.
This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and
14.
telephone. Otherwise, it may cause electric shock in case equipment breakdown or insulation breakdown.
15. Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.
Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with
16.
other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the
17.
flare may break and cause refrigerant gas leakage.
For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant. Using of existing (R22) piping, flare nut
and tools may cause abnormally high pressure in the refrigerant cycle (piping), and possibly result in explosion and injury.
18.
Thickness or copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm.
It is desirable that the amount of residual oil less than 40 mg/10 m.
During installation, install the refrigerant piping properly before run the compressor. (Operation of compressor without fixing refrigeration
19.
piping and valves at opened condition will caused suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion,
injury etc).
3
WARNING
During pump down operation, stop the compressor before remove the refrigeration piping. (Removal of compressor while compressor is
20.
operating and valves are opened will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc.)
After completion of installation or service, confirm there is no leakage or refrigerant gas. It may generate toxic gas when the refrigerant
21.
contacts with fire.
22. Ventilate if there is refrigerant gas leakage during operation. It may cause toxic gas when refrigerant contacts with fire.
23. Do not insert your fingers or other objects into the unit, high speed rotating fan may cause injury.
24. Must not use other parts except original parts described in catalog and manual.
25. Using of refrigerant other than the specified type may cause product damage, burst and injury etc.
CAUTION
Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of
1.
the unit, it may cause fire.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
2.
furniture.
Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may
3.
break and cause refrigerant gas leakage.
4. Do not touch outdoor unit air inlet and aluminium fin. It may cause injury.
5. Select an installation location which is easy for maintenance.
Pb free solder has a higher melting point than standard solder; typically the melting point is 50°F – 70°F (30°C – 40°C) higher.
6.
Please use a high temperature solder iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100°F / 600°C).
Power supply connection to the room air conditioner.
Use power supply cord 3 x 1.5 mm
Connect the power supply cord of the air conditioner to the mains using one of the following method.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
In some countries, permanent connection of this air conditioner to the power supply is prohibited.
7.
1) Power supply connection to the receptacle using power plug.
Use an approved 15/16A (1.0 ~ 1.5HP) power plug with earth pin for the connection to the socket.
2) Power supply connection to a circuit breaker for the permanent connection.
Use an approved 16A circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.0 mm contact
gap.
Do not release refrigerant during piping work for installation, servicing, reinstallation and during repairing a refrigerant parts.
8.
Take care of the liquid refrigerant, it may cause frostbite.
2
(1.0 ~ 1.5HP) type designation 60245 IEC 57 or heavier cord.
9. Installation or servicing work: It may need two people to carry out the installation or servicing work.
10. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.
11. Do not sit or step on the unit, you may fall down accidentally.
Do not touch the sharp aluminium fins or edges of metal parts.
12.
If you are required to handle sharp parts during installation or servicing, please wear hand glove.
Sharp parts may cause injury.
4
2. Specifications
Model
Performance Test Condition EUROVENT
Power Supply
Min. Mid. Max. Min. Mid. Max.
Capacity
Running Current A – 2.75 – – 2.65 –
Input Power W 240 550 740 240 550 740
Annual Consumption kWh – 275 – – 275 –
EER
Cooling
ErP
Indoor Noise (H / L / QLo)
Outdoor Noise (H / L / QLo)
Heating
ErP
Indoor Noise (H / L / QLo)
Outdoor Noise (H / L / QLo)
Ú3 Low Temp. : Capacity (kW) / I. Power (W) / COP 3.48 / 1.19k / 2.92
Ú4 Extr Low Temp. : Capacity (kW) / I. Power (W) / COP2.88 / 1.21k / 2.38
Pdesign kW 2.5
SEER (W/W) 5.8
Annual
Consumption
Class A+
Power Factor % – 91 – – 90 –
Capacity
Running Current A – 4.00 – – 3.85 –
Input Power W 230 800 1.35k 230 800 1.35k
COP
Pdesign kW 2.7
Tbivalent °C -10
SCOP (W/W) 4.0
Annual
Consumption
Class A+
Power Factor % – 91 – – 90 –
Max Current (A) / Max Input Power (W) 8.00 / 1.75k
Starting Current (A) 4.00
Indoor CS-E9PB4EA
Outdoor CU-E9PB4EA
Phase, Hz Single, 50
V 220 230
kW 0.85 2.50 3.00 0.85 2.50 3.00
BTU/h 2900 8530 10200 2900 8530 10200
kcal/h 730 2150 2580 730 2150 2580
W/W 3.54 4.55 4.05 3.54 4.55 4.05
BTU/hW 12.08 15.51 13.78 12.08 15.51 13.78
kcal/hW 3.04 3.91 3.49 3.04 3.91 3.49
kWh 151
dB-A 34 / 26 / 23 34 / 26 / 23
Power Level dB 50 / – / – 50 / – / –
dB-A 45 / – / – 45 / – / –
Power Level dB 60 / – / – 60 / – / –
kW 0.85 3.20 4.80 0.85 3.20 4.80
BTU/h 2900 10900 16400 2900 10900 16400
kcal/h 730 2750 4130 730 2750 4130
W/W 3.70 4.00 3.56 3.70 4.00 3.56
BTU/hW 12.61 13.63 12.15 12.61 13.63 12.15
kcal/hW 3.17 3.44 3.06 3.17 3.44 3.06
kWh 945
dB-A 35 / 28 / 25 35 / 28 / 25
Power Level dB 51 / – / – 51 / – / –
dB-A 46 / – / – 46 / – / –
Power Level dB 61 / – / – 61 / – / –
5
Model
Indoor CS-E9PB4EA
Outdoor CU-E9PB4EA
Type Hermetic Motor (Rotary)
Compressor
Motor Type Brushless (4 poles)
Output Power W 900
Type SIROCCO FAN
Material ABS
Motor Type DC / Transistor (8-poles)
Input Power W –
Output Power W 40
QLo
Indoor Fan
Speed
Cool rpm 330
Heat rpm 410
Cool rpm 370
Lo
Heat rpm 440
Cool rpm 460
Me
Heat rpm 510
Cool rpm 560
Hi
Heat rpm 580
Cool rpm 600
SHi
Heat rpm 630
Type Propeller Fan
Material PP
Motor Type DC (8-poles)
Input Power W –
Outdoor Fan
Output Power W 40
Speed Hi
Cool rpm 840
Heat rpm 760
Moisture Removal L/h (Pt/h) 1.5 (3.2)
3
/min (ft3/min) 6.7 (240)
3
/min (ft3/min) 7.3 (260)
3
/min (ft3/min) 8.8 (310)
3
/min (ft3/min) 10.5 (370)
3
/min (ft3/min) 11.2 (400)
3
/min (ft3/min) 30.5 (1075)
Indoor
Airflow
Outdoor
Airflow
QLo
Lo
Me
Hi
SHi
Hi
Cool m
Heat m3/min (ft3/min) 8.0 (280)
Cool m
Heat m3/min (ft3/min) 8.5 (300)
Cool m
Heat m3/min (ft3/min) 9.7 (340)
Cool m
Heat m3/min (ft3/min) 10.8 (380)
Cool m
Heat m3/min (ft3/min) 11.7 (410)
Cool m
Heat m3/min (ft3/min) 28.9 (1020)
Control Device Expansion Valve
Refrigeration
Cycle
Refrigerant Oil cm3 FV50S (450)
Refrigerant Type g (oz) R410A, 1.13k (39.9)
Dimension
Weight
Height (I/D / O/D /
PANEL)
Width (I/D / O/D /
PANEL)
Depth (I/D / O/D /
PANEL)
Net (I/D / O/D /
PANEL)
mm (inch) 260 (10-1/4) / 622 (24-1/2) / 51 (2-1/32)
mm (inch) 575 (22-21/32) / 824 (32-15/32) / 700 (27-9/16)
mm (inch) 575 (22-21/32) / 299 (11-25/32) / 700 (27-9/16)
Length range (min – max) m (ft) 3 (9.8) ~ 20 (65.6)
I/D & O/D Height different m (ft) 15.0 (49.2)
Piping
Additional Gas Amount g/m (oz/ft) 20 (0.2)
Length for Additional Gas m (ft) 7.5 (24.6)
Drain Hose
Indoor Heat
Exchanger
Outdoor
Heat
Exchanger
Air Filter
Power Supply Cord A Nil
Indoor
Operation
Range
Outdoor
Operation
Range
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
Ú3 Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
Ú4 Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C
5 Standby power consumption ≤0.7W (when switched OFF by remote control, except under self protection control).
6 Specifications are subjected to change without prior notice for further improvement.
Inner Diameter mm 30
Length mm 193
Fin Material Aluminium (Pre Coat)
Fin Type Slit Fin
Row × Stage × FPI 2 × 10 × 18
Size (W × H × L) mm 1330:1270 × 210 × 25.4
Fin Material Aluminium
Fin Type Corrugated Fin
Row × Stage × FPI 2 × 28 × 17
Size (W × H × L) mm 36.4 × 588 × 606.6
Material –
Type –
Power Supply Outdoor
Thermostat Electronic Contol
Protection Device Electronic Contol
Dry Bulb Wet Bulb
Cooling
Heating
Cooling
Heating
Indoor CS-E9PB4EA
Outdoor CU-E9PB4EA
Maximum °C 32 23
Minimum °C 16 11
Maximum °C 30 –
Minimum °C 16 –
Maximum °C 43 26
Minimum °C -10 –
Maximum °C 24 18
Minimum °C -10 –
7
Model
Performance Test Condition EUROVENT
Power Supply
Min. Mid. Max. Min. Mid. Max.
Capacity
Running Current A – 4.40 – – 4.20 –
Input Power W 240 890 1.20k 240 890 1.20k
Annual Consumption kWh – 445 – – 445 –
EER
Cooling
ErP
Indoor Noise (H / L / QLo)
Outdoor Noise (H / L / QLo)
Heating
ErP
Indoor Noise (H / L / QLo)
Outdoor Noise (H / L / QLo)
Ú3 Low Temp. : Capacity (kW) / I. Power (W) / COP 4.06 / 1.77k / 2.29
Ú4 Extr Low Temp. : Capacity (kW) / I. Power (W) / COP 3.37 / 1.66k / 2.03
Pdesign kW 3.4
SEER (W/W) 5.6
Annual
Consumption
Class A+
Power Factor % – 92 – – 92 –
Capacity
Running Current A – 6.70 – – 6.50 –
Input Power W 230 1.42k 2.00k 230 1.42k 2.00k
COP
Pdesign kW 3.0
Tbivalent °C -10
SCOP (W/W) 3.8
Annual
Consumption
Class A
Power Factor % – 96 – – 95 –
Max Current (A) / Max Input Power (W) 9.20 / 2.00k
Starting Current (A) 6.70
Indoor CS-E12PB4EA
Outdoor CU-E12PB4EA
Phase, Hz Single, 50
V 220 230
kW 0.85 3.40 4.00 0.85 3.40 4.00
BTU/h 2900 11600 13600 2900 11600 13600
kcal/h 730 2920 3440 730 2920 3440
W/W 3.54 3.82 3.33 3.54 3.82 3.33
BTU/hW 12.08 13.03 11.33 12.08 13.03 11.33
kcal/hW 3.04 3.28 2.87 3.04 3.28 2.87
kWh 213
dB-A 34 / 26 / 23 34 / 26 / 23
Power Level dB 50 / – / – 50 / – / –
dB-A 45 / – / – 45 / – / –
Power Level dB 60 / – / – 60 / – / –
kW 0.85 4.50 5.60 0.85 4.50 5.60
BTU/h 2900 15300 19100 2900 15300 19100
kcal/h 730 3870 4820 730 3870 4820
W/W 3.70 3.17 2.80 3.70 3.17 2.80
BTU/hW 12.61 10.77 9.55 12.61 10.77 9.55
kcal/hW 3.17 2.73 2.41 3.17 2.73 2.41
kWh 1105
dB-A 35 / 28 / 25 35 / 28 / 25
Power Level dB 51 / – / – 51 / – / –
dB-A 47 / – / – 47 / – / –
Power Level dB 62 / – / – 62 / – / –
8
Model
Indoor CS-E12PB4EA
Outdoor CU-E12PB4EA
Type Hermetic Motor (Rotary)
Compressor
Motor Type Brushless (4 poles)
Output Power W 900
Type SIROCCO FAN
Material ABS
Motor Type DC / Transistor (8-poles)
Input Power W –
Output Power W 40
Cool rpm 330
Heat rpm 410
Cool rpm 370
Lo
Heat rpm 460
Cool rpm 460
Heat rpm 530
Cool rpm 560
Hi
Heat rpm 600
Cool rpm 600
Heat rpm 650
Indoor Fan
Speed
QLo
Me
SHi
Type Propeller Fan
Material PP
Motor Type DC (8-poles)
Input Power W –
Outdoor Fan
Output Power W 40
Speed Hi
Cool rpm 600
Heat rpm 560
Moisture Removal L/h (Pt/h) 2.0 (4.2)
3
/min (ft3/min) 6.7 (240)
3
/min (ft3/min) 7.3 (260)
3
/min (ft3/min) 8.8 (310)
3
/min (ft3/min) 10.5 (370)
3
/min (ft3/min) 11.2 (400)
3
/min (ft3/min) 33.0 (1165)
Indoor
Airflow
Outdoor
Airflow
QLo
Lo
Me
Hi
SHi
Hi
Cool m
Heat m3/min (ft3/min) 8.0 (280)
Cool m
Heat m3/min (ft3/min) 8.8 (310)
Cool m
Heat m3/min (ft3/min) 10.0 (350)
Cool m
Heat m3/min (ft3/min) 10.8 (380)
Cool m
Heat m3/min (ft3/min) 12.0 (420)
Cool m
Heat m3/min (ft3/min) 30.6 (1080)
Control Device Expansion Valve
Refrigeration
Cycle
Refrigerant Oil cm3 FV50S (450)
Refrigerant Type g (oz) R410A, 1.13k (39.9)
Dimension
Weight
Height (I/D / O/D /
PANEL)
Width (I/D / O/D /
PANEL)
Depth (I/D / O/D /
PANEL)
Net (I/D / O/D) /
PANEL
mm (inch) 260 (10-1/4) / 695 (27-3/8) / 51 (2-1/32)
mm (inch) 575 (22-21/32) / 875 (34-15/32) / 700 (27-9/16)
mm (inch) 575 (22-21/32) / 320 (12-5/8) / 700 (27-9/16)
Length range (min – max) m (ft) 3 (9.8) ~ 20 (65.6)
I/D & O/D Height different m (ft) 15.0 (49.2)
Piping
Additional Gas Amount g/m (oz/ft) 20 (0.2)
Length for Additional Gas m (ft) 7.5 (24.6)
Drain Hose
Indoor Heat
Exchanger
Outdoor
Heat
Exchanger
Air Filter
Power Supply Cord A Nil
Indoor
Operation
Range
Outdoor
Operation
Range
1. Cooling capacities are based on indoor temperature of 27°C Dry Bulb (80.6°F Dry Bulb), 19.0°C Wet Bulb (66.2°F Wet Bulb) and outdoor air
temperature of 35°C DRY BULB (95°F Dry Bulb), 24°C Wet Bulb (75.2°F Wet Bulb)
2. Heating capacities are based on indoor temperature of 20°C Dry Bu
Dry
Ú3 Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
Ú4 Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C
5 Standby power consumption ≤0.7W (when switched OFF by remote control, except under self protection control).
6 Specifications are subjected to change without prior notice for further improvement.
Inner Diameter mm 30
Length mm 193
Fin Material Aluminium (Pre Coat)
Fin Type Slit Fin
Row × Stage × FPI 2 × 10 × 18
Size (W × H × L) mm 1330:1270 × 210 × 25.4
Fin Material Aluminium
Fin Type Corrugated Fin
Row × Stage × FPI 2 × 31 × 17
Size (W × H × L) mm 36.4 × 651 × 640
Material –
Type –
Power Supply Outdoor
Thermostat Electronic Contol
Protection Device Electronic Contol
Dry Bulb Wet Bulb
Cooling
Heating
Cooling
Heating
Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
Indoor CS-E12PB4EA
Outdoor CU-E12PB4EA
Maximum °C 32 23
Minimum °C 16 11
Maximum °C 30 –
Minimum °C 16 –
Maximum °C 43 26
Minimum °C -10 –
Maximum °C 24 18
Minimum °C -10 –
lb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
10
Multi Split Combination Possibility:
o A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15PBE, CU-2E18PBE.
o A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18PBE.
o A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE.
o A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E27PBE.
o A single outdoor unit enables air conditioning of up to five separate rooms for CU-5E34PBE.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-2E15PBE.
(Total nominal capacity of indoor units is between 3.2kW to 5.6kW)
1) Two CS-E7PKEW only (Total nominal cooling capacity is
2) One CS-E7PKEW and one CS-E9PKEW. (Total nominal cooling capacity is 4.5kW)
Remarks for CU-3E18PBE / CU-4E23PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-3E18PBE.
(Total nominal capacity of indoor units is between 4.5kW to 9.0kW)
1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW)
2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW)
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-4E27PBE.
(Total nominal capacity of indoor units is between 4.5kW to 13.6kW)
1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW)
2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW)
CS-E12GFEW-2
CS-E12PD3EA
CS-E12PB4EA
CS-E15PKEW
4.0kW
CS-XE15PKEW
CS-E18PKEW
CS-XE18PKEW
CS-ME18PD3EA
5.0kW
CS-ME18PB4EA
CS-E18GFEW
CS-E18GFEW-2
CS-E21PKEW
6.0kW
CS-XE21PKEW
CS-ME21PB4EA
7.0kW CS-E24PKEW ● ● ● ● ● ● ● ● ●
indoor units
1 room maximum
pipe length (m)
Allowable elevation (m) 15 15
Total allowable pipe
length (m)
Total pipe length for
maximum chargeless
length (m)
Additional gas
amount over
chargeless length (g/m)
CU-4E27PBE CU-5E34PBE
● ● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ● ●
From 4.5kW
to 13.6kW
25 25
70 80
45 45
20 20
OUTDOOR UNIT
From 4.5kW
to 17.5 kW
Note: “●” : Available
12
Indoor Unit : CS-ME5PKE, CS-E7/9/12PKEW, CS-E9/12GFEW, CS-ME9/12PB4EA, CS-ME9/12PD3EA,
CS-E9/12PD3EA, CS-E9/12PB4EA
Outdoor Unit : CU-2E15PBE
2 Room 1 Room
Indoor Unit Capacity (kW) Total Indoor Capacity (kW) Indoor Unit Capacity (kW) Total Indoor Capacity (kW)
1.6 + 1.6 3.2 1.6 1.6
1.6 + 2.0 3.6 2.0 2.0
1.6 + 2.5 4.1 2.5 2.5
1.6 + 2.8 4.4 2.8 2.8
1.6 + 3.2 4.8 3.2 3.2
2.0 + 2.0 4.0
2.0 + 2.5 4.5
2.0 + 2.8 4.8
2.0 + 3.2 5.2
2.5 + 2.5 5.0
2.5 + 2.8 5.3
2.8 + 2.8 5.6
Indoor Unit : CS-ME5PKE, CS-E7/9/12PKEW, CS-E9/12GFEW, CS-ME9/12PB4EA, CS-ME9/12PD3EA,
CS-E9/12PD3EA, CS-E9/12PB4EA
Outdoor Unit : CU-2E18PBE
2 Room 1 Room
Indoor Unit Capacity (kW) Total Indoor Capacity (kW) Indoor Unit Capacity (kW) Total Indoor Capacity (kW)
1.6 + 1.6 3.2 1.6 1.6
1.6 + 2.0 3.6 2.0 2.0
1.6 + 2.5 4.1 2.5 2.5
1.6 + 2.8 4.4 2.8 2.8
1.6 + 3.2 4.8 3.2 3.2
2.0 + 2.0 4.0
2.0 + 2.5 4.5
2.0 + 2.8 4.8
2.0 + 3.2 5.2
2.5 + 2.5 5.0
2.5 + 2.8 5.3
2.5 + 3.2 5.7
2.8 + 2.8 5.6
2.8 + 3.2 6.0
3.2 + 3.2 6.4
13
Indoor Unit : CS-ME5PKE, CS-E7/9/12/15/18PKEW, CS-E9/12/18GFEW, CS-ME9/12/18PB4EA,
CS-ME9/12/18PD3EA, CS-E9/12PD3EA, CS-E9/12PB4EA
Outdoor Unit : CU-3E18PBE
3 Room 2 Room 1 Room
Indoor Unit Capacity
(kW)
1.6 + 1.6 + 1.6 4.8 1.6 + 3.2 4.8 1.6 1.6
1.6 + 1.6 + 2.0 5.2 1.6 + 4.0 5.6 2.0 2.0
1.6 + 1.6 + 2.5 5.7 1.6 + 5.0 6.6 2.5 2.5
1.6 + 1.6 + 2.8 6.0 2.0 + 2.5 4.5 2.8 2.8
1.6 + 1.6 + 3.2 6.4 2.0 + 2.8 4.8 3.2 3.2
1.6 + 1.6 + 4.0 7.2 2.0 + 3.2 5.2 4.0 4.0
1.6 + 1.6 + 5.0 8.2 2.0 + 4.0 6.0 5.0 5.0
1.6 + 2.0 + 2.0 5.6 2.0 + 5.0 7.0
1.6 + 2.0 + 2.5 6.1 2.5 + 2.5 5.0
1.6 + 2.0 + 2.8 6.4 2.5 + 2.8 5.3
1.6 + 2.0 + 3.2 6.8 2.5 + 3.2 5.7
1.6 + 2.0 + 4.0 7.6 2.5 + 4.0 6.5
1.6 + 2.0 + 5.0 8.6 2.5 + 5.0 7.5
1.6 + 2.5 + 2.5 6.6 2.8 + 2.8 5.6
1.6 + 2.5 + 2.8 6.9 2.8 + 3.2 6.0
1.6 + 2.5 + 3.2 7.3 2.8 + 4.0 6.8
1.6 + 2.5 + 4.0 8.1 2.8 + 5.0 7.8
1.6 + 2.8 + 2.8 7.2 3.2 + 3.2 6.4
1.6 + 2.8 + 3.2 7.6 3.2 + 4.0 7.2
1.6 + 2.8 + 4.0 8.4 3.2 + 5.0 8.2
1.6 + 3.2 + 3.2 8.0 4.0 + 4.0 8.0
1.6 + 3.2 + 4.0 8.8 4.0 + 5.0 9.0
2.0 + 2.0 + 2.0 6.0
2.0 + 2.0 + 2.5 6.5
2.0 + 2.0 + 2.8 6.8
2.0 + 2.0 + 3.2 7.2
2.0 + 2.0 + 4.0 8.0
2.0 + 2.0 + 5.0 9.0
2.0 + 2.5 + 2.5 7.0
2.0 + 2.5 + 2.8 7.3
2.0 + 2.5 + 3.2 7.7
2.0 + 2.5 + 4.0 8.5
2.0 + 2.8 + 2.8 7.6
2.0 + 2.8 + 3.2 8.0
2.0 + 2.8 + 4.0 8.8
2.0 + 3.2 + 3.2 8.4
2.5 + 2.5 + 2.5 7.5
2.5 + 2.5 + 2.8 7.8
2.5 + 2.5 + 3.2 8.2
2.5 + 2.5 + 4.0 9.0
2.5 + 2.8 + 2.8 8.1
2.5 + 2.8 + 3.2 8.5
2.5 + 3.2 + 3.2 8.9
2.8 + 2.8 + 2.8 8.4
2.8 + 2.8 + 3.2 8.8
Total Indoor Capacity
(kW)
Indoor Unit Capacity
(kW)
Total Indoor Capacity
(kW)
Indoor Unit Capacity
(kW)
Total Indoor Capacity
(kW)
14
Indoor Unit : CS-ME5PKE, CS-E7/9/12/15/18/21PKEW, CS-E9/12/18GFEW, CS-ME9/12/18/21PB4EA,
o Wider output power range
o Energy saving
o Quick Cooling
o Quick Heating
o More precise temperature control
Environment Protection
o Non-ozone depletion substances refrigerant (R410A)
Long Installation Piping
o Long piping up to 20 meters
Easy to use remote control
Quality Improvement
o Random auto restart after power failure for safety restart operation
o Gas leakage protection
o Prevent compressor reverse cycle
o Inner protector to protect compressor
o Noise prevention during soft dry operation
Operation Improvement
o Quiet mode to reduce the indoor unit operating sound
o Powerful mode to reach the desired room temperature quickly
o 24-hour timer setting
Serviceability Improvement
o Breakdown Self Diagnosis function
23
4. Location of Controls and Components
4.1 Indoor Unit
4.2 Outdoor Unit
4.3 Remote Control
24
5. Dimensions
5.1 Indoor Unit
25
5.2 Outdoor Unit
5.2.1 CU-E9PB4EA
5.2.2 CU-E12PB4EA
26
6. Refrigeration Cycle Diagram
6.1 CS-E9PB4EA CU-E9PB4EA
27
6.2 CS-E12PB4EA CU-E12PB4EA
28
7. Block Diagram
7.1 CS-E9PB4EA CU-E9PB4EA
29
7.2 CS-E12PB4EA CU-E12PB4EA
30
8. Wiring Connection Diagram
8.1 Indoor Unit
31
8.2 Outdoor Unit
8.2.1 CU-E9PB4EA
Resistance of Compressor Windings
MODEL CU-E9PB4EA
CONNECTION 5RD132XBE21 (Ω)
U-V 1.897
U-W 1.907
V-W 1.882
Note: Resistance at 20°C of ambient temperature.
32
8.2.2 CU-E12PB4EA
Resistance of Compressor Windings
MODEL CU-E12PB4EA
CONNECTION 5RD132XBA21 (Ω)
U-V 1.897
U-W 1.907
V-W 1.882
Note: Resistance at 20°C of ambient temperature.
33
9. Electronic Circuit Diagram
9.1 Indoor Unit
34
9.2 Outdoor Unit
9.2.1 CU-E9PB4EA
35
9.2.2 CU-E12PB4EA
36
10. Printed Circuit Board
10.1 Indoor Unit
10.1.1 Main Printed Circuit Board
37
10.1.2 Display Printed Circuit Board
38
10.2 Outdoor Unit
10.2.1 CU-E9PB4EA
39
10.2.2 CU-E12PB4EA
40
11. Installation Instruction
11.1 Indoor Unit
11.1.1 Selecting the Location for the Indoor Unit
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1 The indoor unit must be within a maintenance space.
2 The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading
of air throughout the room.
3 Recommended installation height for indoor unit shall be at least 2.5 m.
* If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is
decreased.
4 The installation position must be able to support a load four times the indoor unit weight.
5 The indoor unit must be away from heat and steam sources, but avoid installing it near an entrance.
6 The indoor unit must allow easy draining.
7 The indoor unit must allow easy connection to the outdoor unit.
8 Place the indoor unit according to the height from the ceiling shown in the illustration below.
9 The indoor unit must be from at least 3m away from any noise-generating equipment. The electrical wiring
must be shielded with a steel conduit.
10 If the power supply is subject to noise generation, add a suppressor.
11 Do not install the indoor unit in a laundry. Electric shocks may result.
Note
Thoroughly study the following installation locations
1 In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the turbo
fan, the fin of the heat exchanger and the drain pump, resulting in heat exchange reduction, spraying,
dispersing of water drops, drain pump malfunction, etc.
In these cases, take the following actions:
oMake sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so
that it draws oily steam which should not flow into the suction of the air conditioner.
oMake enough distance from the cooking room to install the air conditioner in such place where it may not
suck in oily steam.
2 Avoid installing the air conditioner in such
circumstances where cutting oil mist or iron
powder exist especially in factories, etc.
3 Avoid places where inflammable gas is
generated, flows-in, contaminated, or leaked.
4 Avoid places where sulphurous acid gas or
corrosive gas can be generated.
5 Avoid places near high frequency generators.
41
Model Name Height in ceiling
E9*****
E12*****
280 mm or more
11.1.2 Installation of Indoor Unit
This air conditioner uses a drain up motor.
Horizontally install the unit using a level gauge.
CEILING OPENING DIMENSIONS AND
BOLT LOCATION
The paper model for installation expand or shrink
according to temperature and humidity.
Check on dimensions before using it.
During the installation care must be taken
Caution
not to damage electric wires.
The dimensions of the paper model for installation
are the same as those of the ceiling opening
dimensions.
Be sure to discuss the ceiling drilling work with the
workers concerned.
POSITIONS OF AIR CONDITIONER BODY AND CEILING SURFACE
HANGING
11.1.3 Refrigerant Piping
Refrigerant is charged to the outdoor unit. For details, see the manual for installation work of outdoor unit.
(Additional charging, etc.)
1 Brazing for piping.
a. Execute brazing before tightening the flare
nut.
b. Brazing must be executed while blowing
nitrogen gas. (This prevents generation of
oxidized scale in copper pipe.)
2 When there is a lot of brazings for long piping,
install a strainer midway of the piping. (The
strainer is locally supplied.)
3 Use clean copper pipe with inner wall surface
free from mist and dust. Blow nitrogen gas or
air to blow off dust in the pipe before
connection.
4 Form the piping according to its routing. Avoid
bending and bending back the same piping
point more than three times. (This will result in
hardening of the pipe).
5 After deforming the pipe, align centers of the
union fitting of the indoor unit and the piping,
and tighten them firmly with wrenches.
6 Connect pipe to the service valve or ball valve
which is located below the outdoor unit.
7 After completed the piping connection, be sure to check if there is gas leakage in indoor and outdoor
connection.
42
Vacuum drying
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit.
The vacuum drying must be carried out by using the service ports of both the liquid and gas side valves.
CAUTION
Use two wrenches and tighten with regular torque.
Flare nut fastening torque N•m (kgf•cm)
ø6.35 mm 18 (180) ø12.7 mm 55 (560) ø19.05 mm 100 (1020)
ø9.52 mm 42 (430) ø15.88 mm 65 (660)
Liquid side piping Gas side piping
ø6.35 mm (1/4") ø12.7 mm (1/2")
11.1.4 Indoor Unit Drain Piping
During drain piping connection, be careful not to exert extra force on the drain port at the indoor unit.
The outside diameter of the drain connection at the indoor unit is 32 mm.
Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings.
Be sure to perform heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thickness more than 8 mm (local supply).
Drain piping must have down-slope (1/50 to 1/100); be sure not to provide up-and-down slope to prevent reversal
flow.
Be sure to check no air trap on drain hose and to ensure smooth water flow and no abnormal sound.
The height of drain may be possible up to
750 mm.
When drain set piping, install as shown in the
figure below.
The air conditioner uses a drain up motor to drain water. Use the following procedure to test the drain
Drain Test
up motor operation.
Connect the main drain pipe to exterior and leave it provisionally until the test comes to an end.
Feed water to the flexible drain hose and check the piping for leakage.
Be sure to check the drain up motor for normal operating and noise when electric wiring is complete.
When the test is complete, connect the flexible drain hose to the drain port.
Pour about 600-700cc of water in the drain pan of the indoor unit. (Pour from the position specified in the drawing
by using a water supply bottle or other suitable tool.)
Press the drain pump test run on pcb to start the drain motor, and verify water drainage.
(The drain motor will automatically stop after operating for about five minutes.)
43
11.1.5 Heat Insulation
Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation
work leads to water leakage.
1 Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
2 Precautions in high humidity circumstance.
This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been
confirmed that there are no faults. However, if it is operated for a long time in high humid atmosphere (dew
point temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material
according to the following procedure:
o Heat insulation material to be prepared… Adiabatic glass wool with thickness 10 to 20 mm.
o Stick glass wool on all air conditioners that are located in ceiling atmosphere.
o In addition to the normal heat insulation (thickness: more than 8 mm) for refrigerant piping (gas piping:
thick piping) and drain piping, add a further of 10 mm to 30 mm thickness material.
Wall seal
When the outdoor unit is installed on a higher
position than the indoor unit, install the trap so as
not to instill rain water into the wall by transmitting
in piping.
Stuff the space among piping, the electric wire,
and- the drain hose with “Putty” and seal the
penetration wall hole.
Make sure that rain water do not instill into the
wall.
11.1.6 Connecting the Cable to the Indoor
Remove the mounting screw, remove the control
box cover, and then connect the wires by
following the procedure given in the illustration.
Connection cable between indoor unit and
outdoor unit shall be approved polychloroprene
sheathed 4 x 1.5 mm
designation 60245 IEC 57 or heavier cord.
Allowable connection cable length of each indoor
unit shall be 30 m or less.
Secure the connection cable onto the control
board with the holder (clamper).
Ensure the colour of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s
respectively.
Earth wire shall be Yellow/Green (Y/G) in colour
and longer than other AC wires for safety reason.
2
flexible cord, type
44
11.1.6.1 Wire Stripping and Connection Requirement
11.1.7 Installation of Decorative Panel
The decorative panel has its installation direction. Confirm the direction by displaying the piping side.
1 Remove the air inlet grille by moving the catchers to center.
2 Fitting the decorative panel
oTemporarily secure the fixing screws (3
pcs.) before fitting the decorative panel.
(For temporarily securing the front grille.)
oPlace decorative panel on the screws (3
pcs.) before fitting, move decorative
panel as illustrated and tighten all the
screws (4 pcs.).
Check before hand the height from the ceiling to
the unit.
The front grille fitting direction is determined by
the unit direction.
Only use the screws with the length of 35mm
which is provided, to fix the decorative panel.
Do not use other screw which is longer it may
cause damage to the drain-pan and other
components.
45
3 Fit the decorative panel and ceiling wall together and confirm no gap in between. Readjust indoor unit height,
if there is a gap between ceiling wall and decorative panel.
4 Open the indoor control box cover. (2 pcs)
5 Insert firmly the connector of cosmetic louver
to indoor pcb CN-STM1, CN-STM2 and
CN-DISP.
Be caution not to clamp the cord in between
control board and control board cover.
6 After complete, install back removed part
follow opposite procedure.
Be sure to hook the air inlet grill string,
to prevent grill from falling and causing
injury from it.
46
11.2 Outdoor Unit
11.2.1 Select the Best Location
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which
could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a
short circuit of the discharged air.
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
11.2.1.1 Indoor/Outdoor Installation
Diagram
Example: For E9*****
If the unit is installed at 10 m distance, the quantity of
additional refrigerant should be 50 g .... (10-7.5) m x
20 g/m = 50 g.
11.2.2 Install the Outdoor Unit
After selecting the best location, start installation
to Indoor/Outdoor Unit Installation Diagram.
1 Fix the unit on concrete or rigid frame firmly
and horizontally by bolt nut (ø10 mm).
2 When installing at roof, please consider strong
wind and earthquake.
Please fasten the installation stand firmly with
bolt or nails.
Model A B C D
E9***** 540 mm 160 mm 18.5 mm 330 mm
E12***** 613 mm 131 mm 16 mm 360.5 mm
47
11.2.3 Connect the Piping
11.2.3.1 Connecting the Piping to Indoor Unit
Please make flare after inserting flare nut (locate at
joint portion of tube assembly) onto the copper pipe.
(In case of using long piping)
Connect the piping
Align the center of piping and sufficiently tighten
the flare nut with fingers.
Further tighten the flare nut with torque wrench in
specified torque as stated in the table.
11.2.3.2 Connecting the Piping to Outdoor Unit
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge. Make flare after
inserting the flare nut (locate at valve) onto the copper
pipe. Align center of piping to valve and then tighten
with torque wrench to the specified torque as stated in
the table.
11.2.3.3 Connecting the Piping to Outdoor Multi
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge. Make flare after
inserting the flare nut (locate at valve) onto the copper
pipe. Align center of piping to valve and then tighten
with torque wrench to the specified torque as stated in
the table.
* For Gas side piping please refer table and diagram below
Do not overtighten, overtightening may cause gas leakage
Piping size Torque
6.35 mm (1/4”) [18 N•m (1.8 kgf.m)]
9.52 mm (3/8”) [42 N•m (4.3 kgf.m)]
12.7 mm (1/2”) [55 N•m (5.6 kgf.m)]
15.88 mm (5/8”) [65 N•m (6.6 kgf.m)]
19.05 mm (3/4”) [100 N•m (10.2 kgf.m)]
* Kindly consult authorised dealer for connectivity validity.
11.2.4 Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND
PIPES in the following procedure.
1 Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
oBe sure to connect the end of the charging hose with the push pin to the service port.
48
2 Connect the center hose of the charging set to a vacuum pump.
3 Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4 Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note : BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5 Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6 Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7 Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN”
using a hexagonal wrench (4 mm).
8 Mount valve caps onto the 2-way valve and the 3-way valve.
oBe sure to check for gas leakage.
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in the step e above take
the following measure:
- If the leak stops when the piping connections are tightened further, continue working from step e.
- If the leak does not stop when the connections are retightened, repair location of leak.
- Do not release refrigerant during piping work for installation and reinstallation.
- Take care of the liquid refrigerant, it may cause frostbite.
11.2.5 Connect the Cable to the Outdoor Unit
(FOR DETAIL REFER TO WIRING DIAGRAM AT
UNIT)
1 Remove the control board cover from the unit
by loosening the screw.
2 Cable connection to the power supply through
Isolating Devices (Disconnecting means).
oConnect approved type polychloroprene
sheathed power supply cord 3 x
1.5 mm
2
type designation 60245 IEC 57
or heavier cord to the terminal board, and
connect the others end of the cord to
Isolating Devices (Disconnecting means).
3 Connection cable between indoor unit and
outdoor unit shall be approved
polychloroprene sheathed 4 x 1.5 mm
2
flexible
cord, type designation 60245 IEC 57 or
heavier cord. Allowable connection cable
length of each indoor unit shall be 30 m or
less.
4 Connect the power supply cord and
connection cable between indoor unit and
outdoor unit according to the diagram below.
5 Secure the power supply cord and connection
cable onto the control board with the holder.
6 Attach the control board cover back to the
original position with screw.
7 For wire stripping and connection
requirement, refer to instruction 10.1.6 of
indoor unit.
11.2.6 Pipe Insulation
1 Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2 If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E FOAM with thickness 6 mm or above.
49
11.2.6.1 Cutting and Flaring the Piping
1 Please cut using pipe cutter and then remove the burrs.
2 Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3 Please make flare after inserting the flare nut onto the copper pipes.
11.2.7 Disposal of Outdoor Unit Drain Water
If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm.
If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it is recommended
not to use a drain elbow, for the drain water freezes and the fan will not rotate.
11.2.8 Auto Switch Operation
The following operations can be performed by
pressing the “AUTO” switch.
1 AUTO OPERATION MODE
The Auto operation will be activated
immediately once the Auto Switch is pressed.
2 TEST RUN OPERATION (FOR PUMP
DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the
Auto Switch is pressed continuously for more
than 5 sec. to below 8 sec. A “pep” sound will
occur at the fifth sec., in order to identify the
starting of Test Run operation.
11.2.9 Changing the Remote Control Transmission Code
1 Press AUTO SW continuously for more than
11 sec to below 16 sec, A “pep”, “pep”, “pep”
sound will occur at the eleventh sec.
2 Press the “A/C RESET” button once remote
control signal will activate the remote control
transmission code setting mode.
3 Press “OFF/ON” button. The new Remo-Con
No. will be accepted and memorized, after
which the new Remo-Con No. can be used.
50
Remo-Con No. Change in Remote Control
1 Remove the batteries from the battery
compartment of the Remote Control.
2 On the left side of the battery compartment,
there is a small opening in the centre in which
Jumper (J_A) can be seen. In the accepted
Remo-Con PCB shown beside, Jumper (J_B)
can be seen.
J_A J_B Remo-Con No.
Short Open A(Default)
Open Open B
Short Short C
Open Short D
51
12. Operation Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal setting temperature and intake air
temperature.
12.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
12.1.2 Cooling Operation
12.1.2.1 Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C continue for 3 minutes.
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.3 Soft Dry Operation
12.1.3.1 Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.0°C continue for 3 minutes.
When compressor is OFF (Thermostat OFF) and AUTO FAN is set, the fan will stop periodically.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point.
12.1.4 Heating Operation
12.1.4.1 Thermostat control
Compressor is OFF when Intake Air Temperature - Internal Setting Temperature > +2.0°C continue for 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature <
Compressor OFF point.
52
12.1.5 Automatic Operation
This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
Every 10 minutes, the indoor temperature is judged.
For the 1st judgment
o If indoor intake temperature - remote control setting temperature ≥ 2°C, COOL mode is decided.
o If -2°C ≤ indoor intake temperature - remote control setting temperature < 2°C, DRY mode is decided.
o If indoor intake temperature - remote control setting temperature < -2°C, HEAT mode is decided.
For the 2nd judgment onwards
o If indoor intake temperature - remote control setting temperature ≥ 4°C, if previous operate in DRY mode,
then continue in DRY mode. otherwise COOL mode is decided.
o If -2.5°C ≤ indoor intake temperature - remote control setting temperature < 4°C, maintain with previous
mode.
o If indoor intake temperature - remote control setting temperature < -2.5°C, HEAT mode is decided.
12.2 Indoor Fan Motor Operation
12.2.1 Basic Rotation Speed (rpm)
A. Basic Rotation Speed (rpm)
i. Manual Fan Speed
[Cooling, Dry]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control ○ ○ ○ ○ ○
Tab Hi Me+ Me Me- Lo
[Heating]
Fan motor’s number of rotation is determined according to remote control setting.
Remote control ○ ○ ○ ○ ○
Tab SHi Me+ Me Me- Lo
ii Auto Fan Speed
[Cooling, Dry]
According to room temperature and setting temperature, indoor fan speed is determined automatically.
When set temperature is not achieved, the indoor fan will operate according to pattern below.
When set temperature achieved, the indoor fan speed will be fixed. When thermostat off, the fan stop periodically.
53
[Heating]
According to indoor pipe temperature, automatic heating fan speed is determined as follows.
B. Feedback control
Immediately after the fan motor started, feedback control is performed once every second.
During fan motor on, if fan motor feedback ≥ 2550 rpm or < 50 rpm continue for 10 seconds, then fan motor error
counter increase, fan motor is then stop and restart. If the fan motor counter becomes 7 times, then H19 - fan
motor error is detected. Operation stops and cannot on back.
12.3 Outdoor Fan Motor Operation
It starts when compressor starts operation and it stops 30 seconds after compressor stops operation.
During cooling operation, and outdoor ambient temperature is below 8°C, outdoor fan speed will be controlled
according to outdoor piping temperature as following:
OD Pipe Temperature
E9PB4EA E12PB4EA
A 28°C 26°C
B 33°C 33°C
During above condition, when indoor heat exchanger temperature is below 5°C, the outdoor fan will stop
according to outdoor piping temperature as following:
54
12.4 Airflow Direction
1. There is one type of airflow, vertical airflow (directed by horizontal vane).
2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat
exchanger temperature and intake air temperature) and manual (angles of direction can be adjusted using
remote control).
12.4.1 Vertical Airflow
Operation Mode Airflow Direction
Auto with Heat Exchanger A Upward fix 20
Heating
Cooling
Soft Dry
B Downward fix 58
Temperature C Upward fix 20
Manual 20 33 45 58 70
Auto 20 ~ 70
Manual 20 33 45 58 70
Auto 20 ~ 70
Manual 20 33 45 58 70
Automatic vertical airflow direction can be set using remote control; the vane swings up and down within the angles as stated
1.
above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as Figure 1
below. When the air conditioner is stopped using remote control, the vane will shift to close position.
Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and the positions
2.
of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the vane will shift to close
position.
Upper Vane Angle (°)
1 2 3 4 5
12.5 Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)
Purpose
o To provide quiet cooling operation compare to normal operation.
Control condition
o Quiet operation start condition
When “POWERFUL/QUIET” button at remote control is pressed twice.
POWERFUL/QUIET LED illuminates.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL/QUIET button is pressed again.
Stop by OFF/ON switch.
Timer “off” activates.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control contents
o Fan speed is changed from normal setting to quiet setting of respective fan speed.
Fan speed for quiet operation is reduced from setting fan speed.
55
12.6 Quiet Operation (Heating)
Purpose
o To provide quiet heating operation compare to normal operation.
Control condition
o Quiet operation start condition
When “POWERFUL/QUIET” button at remote control is pressed.
POWERFUL/QUIET LED illuminates.
o Quiet operation stop condition
When one of the following conditions is satisfied, quiet operation stops:
POWERFUL/QUIET button is pressed again.
Stop by OFF/ON switch.
Timer “off” activates.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except
fan mode only.
During quiet operation, if timer “on” activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control contents
o Fan speed manual
Fan speed is changed from normal setting to quiet setting of respective fan speed.
Fan speed for quiet operation is reduced from setting fan speed.
o Fan Speed Auto
Indoor FM RPM depends on pipe temp sensor of indoor heat exchanger.
12.7 Powerful Mode Operation
When the powerful mode is selected, the internal setting temperature will shift lower up to 2°C (for Cooling/Soft
Dry) or higher up to 3.5°C (for Heating) than remote control setting temperature for 20 minutes to achieve the
setting temperature quickly.
12.8 Timer Control
There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time.
If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence.
12.8.1 ON Timer Control
ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier than
the setting time.
This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds to
determine the indoor intake air temperature and outdoor air temperature in order to judge the operation starting
time.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
12.8.2 OFF Timer Control
OFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time.
56
12.9 Auto Restart Control
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
This type of control is not applicable during ON/OFF Timer setting.
This control can be omitted by open the circuit of JP3 at indoor unit printed circuit board.
12.10 Indication Panel
LED POWER TIMER POWERFUL QUIET AIR SWING
Color Green Orange Orange Orange Orange
Light ON Operation ON Timer Setting ON POWERFUL Mode ON QUIET Mode ON AIR SWING ON
Light OFF Operation OFF Timer Setting OFF POWERFUL Mode OFF QUIET Mode OFF AIR SWING OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.
12.11 Drain Pump Control Operation
Drain pump control
This unit has built-in with drain pump.
Control content
During COOL/DRY mode.
o During COOL/DRY mode, drain pump starts 10 seconds after indoor fan motor starts.
o The drain pump is always ON.
After COOL/DRY mode, when unit turns OFF (power standby) or changes to HEAT mode.
o The drain pump turns ON for 90 seconds immediately.
Error judgment
o When float switch detects ON signal continuously for 2 minutes 30 seconds, error code H21 are shown.
o When float switch ON has operated 2 times within 20 minutes, error code H35 are shown.
57
13. Protection Control
13.1 Protection Control For All Operations
13.1.1 Restart Control (Time Delay Safety Control)
The Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on
again by pressing OFF/ON button at remote control within this period.
This control is not applicable if the power supply is cut off and on again.
This phenomenon is to balance the pressure inside the refrigerant cycle.
13.1.2 Total Running Current
1 When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor
operation will be decreased.
2 If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.
3 However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for
3 minutes.
Model E9PB4EA E12PB4EA
Operation Mode X (A) Y (A) X (A) Y (A)
Cooling / Soft Dry (A) 4.29
Cooling / Soft Dry (B/C) 3.86 6.56
Heating 5.64 8.23
4 The first 30 minutes of cooling operation, (A) will be applied.
14.70
7.00
14.70
13.1.3 IPM (Power transistor) Prevention Control
Overheating Prevention Control
1 When the IPM temperature rises to 120°C, compressor operation will stop immediately.
2 Compressor operation restarts after 3 minutes the temperature decreases to 110°C.
3 If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).
DC Peak Current Control
1 When electric current to IPM exceeds set value of 20.23 (E9), 30.0 (E12) ± 5.0A, the compressor will stop
operate. Then, operation will restart after 3 minutes.
2 If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will
restart after 1 minute.
3 If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after
1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer
LED will be blinking (“F99” is indicated).
58
13.1.4 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor top temperature. The changes of
frequency are as below.
If compressor top temperature exceeds 107°C, compressor will be stopped, occurs 4 times per 20 minutes, timer
LED will be blinking. (“F97” is indicated.)
13.1.5 Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.75A and 0.95A.
o During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 4°C.
o During Heating operations :
Indoor piping temperature - indoor suction is under 5°C.
Control contents
o Compressor stops (and restart after 3 minutes).
o If the conditions above happen 2 times within 20 minutes, the unit will:
Stop operation
Timer LED blinks and “F91” indicated.
13.1.6 Low Frequency Protection Control 1
When the compressor operate at frequency lower than 24 Hz continued for 20 minutes, the operation frequency
will be changed to 23 Hz for 2 minutes.
13.1.7 Low Frequency Protection Control 2
When all the below conditions comply, the compressor frequency will change to lower frequency.
Temperature, T, for: Cooling/Soft Dry Heating
Indoor intake air (°C) T < 14 or T ≥ 30 T < 14 or T ≥ 28
Outdoor air (°C) T < 13 or T ≥ 38 T < 4 or T ≥ 24
Indoor heat exchanger (°C) T < 30 T ≥ 0
59
13.2 Protection Control For Cooling & Soft Dry Operation
13.2.1 Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust base on outdoor air temperature.
13.2.2 Cooling Overload Control
Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation
frequency).
The compressor stop if outdoor pipe temperature exceeds 63°C.
If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise
protection).
13.2.3 Freeze Prevention Control 1
When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stop
operating.
Compressor will resume its operation after stop for 3 minutes and the indoor heat exchanger is higher than 5°C.
At the same time, indoor fan speed will be higher than during its normal operation.
If indoor heat exchanger temperature is higher than 13°C, the fan speed will return to its normal operation.
13.2.4 Freeze Prevention Control 2
Control start conditions
o During Cooling operation and soft dry operation
During thermo OFF condition, indoor intake temperature is less than 10°C or
Compressor stops for freeze prevention control
o Either one of the conditions above occurs 5 times in 40 minutes.
Control contents
o Operation stops
o Timer LED blinks and “H99” indicated
13.2.5 Dew Prevention Control 1
To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o Outdoor air temperature and Indoor pipe temperature judgment by microcontroller is fulfilled.
o When Cooling or Dry mode is operated more than 20 minutes or more.
This control stopped if:
o Compressor stopped.
o Remote control setting changed (fan speed / temperature).
o Outdoor air temperature and indoor intake temperature changed.
Fan speed will be adjusted accordingly in this control.
60
13.2.6 Odor Cut Control
To reduce the odor released from the unit.
o Start Condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o Control content
Depends on compressor conditions:
1. Compressor OFF → Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
2. Compressor ON → Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
13.3 Protection Control For Heating Operation
13.3.1 Intake Air Temperature Control
Compressor will operate at limited freq., if indoor intake air temperature is 30°C or above.
13.3.2 Outdoor Air Temperature Control
The Max current value is regulated when the outdoor air temperature rise above 14°C in order to avoid
compressor overloading.
13.3.3 Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown
below.
If the heat exchanger temperature exceeds 60°C, compressor will stop.
13.3.4 Low Temperature Compressor Oil Return Control
In heating operation, if the outdoor temperature falls below -10°C when compressor starts, the compressor
frequency will be regulated up to 600 seconds.
13.3.5 Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
13.3.6 Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor
and outdoor fan motor stop and operation LED blinks.
61
14. Servicing Mode
14.1 Auto OFF/ON Button
1 AUTO OPERATION MODE
The Auto operation will be activated immediately once the Auto OFF/ON button is pressed. This operation
can be used to operate air conditioner with limited function if remote control is misplaced or malfunction.
2 TEST RUN OPERATION (FOR PUMP DOWN/SERVICING PURPOSE)
The Test Run operation will be activated if the Auto OFF/ON button is pressed continuously for more than
5 seconds. A “beep” sound will heard at the fifth seconds, in order to identify the starting of Test Run
operation (Forced cooling operation). Within 5 minutes after Forced cooling operation start, the Auto OFF/ON
button is pressed for more than 5 seconds. A 2 “beep” sounds will heard at the fifth seconds, in order to
identify the starting of Normal cooling operation.
Within 5 minutes after Normal cooling operation start, the Auto OFF/ON button is pressed for more than
5 seconds. A 3 “beep” sounds will be heard at the fifth seconds, in order to identify the starting of Forced
heating operation.
The Auto OFF/ON button may be used together with remote control to set / change the advance setting of air
conditioner operation.
3 REMOTE CONTROL NUMBER SWITCH MODE
The Remote Control Number Switch Mode will be activated if the Auto OFF/ON button is pressed
continuously for more than 11 seconds (3 “beep” sounds will occur at 11th seconds to identify the Remote
Control Number Switch Mode is in standby condition) and press “AC RESET” button and then press any
button at remote control to transmit and store the desired transmission code to the EEPROM.
There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor
unit. The indoor unit will only operate when received signal with same transmission code from remote control.
This could prevent signal interference when there are 2 or more indoor units installed nearby together.
To change remote control transmission code, short or open jumpers at the remote control printed circuit
board.
During Remote Control Number Switch Mode, press any button at remote control to transmit and store
the transmission code to the EEPROM.
Remote Control Printed Circuit Board
Jumper A (J_A) Jumper B (JB) Remote Control No.
Short Open A (Default)
Open Open B
Short Short C
Open Short D
62
4 REMOTE CONTROL RECEIVING SOUND OFF/ON MODE
The Remote Control Receiving Sound OFF/ON Mode will be activated if the Auto OFF/ON button is pressed
continuously for more than 16 seconds (4 “beep” sounds will occur at 16th seconds to identify the Remote
Control Receiving Sound Off/On Mode is in standby condition) and press “AC Reset” button at remote
control.
Press “Auto OFF/ON button” to toggle remote control receiving sound.
o Short “beep”: Turn OFF remote control receiving sound.
o Long “beep”: Turn ON remote control receiving sound.
After Auto OFF/ON Button is pressed, the 20 seconds counter for Remote Control Receiving Sound OFF/ON
Mode is restarted.
14.2 Remote Control Button
14.2.1 SET Button
To check remote control transmission code and store the transmission code to EEPROM:
o Press “Set” button continuously for 10 seconds by using pointer.
o Press “Timer Set” button until a “beep” sound is heard as confirmation of transmission code changed.
14.2.2 RESET (RC)
To clear and restore the remote control setting to factory default.
o Press once to clear the memory.
14.2.3 RESET (AC)
To restore the unit’s setting to factory default.
o Press once to restore the unit’s setting.
14.2.4 TIMER ▲
To change indoor unit indicator’s LED intensity.
o Press continuously for 5 seconds.
14.2.5 TIMER ▼
To change remote control display from Degree Celsius (°C) to Degree Fahrenheit (°F).
o Press continuously for 10 seconds.
63
14.3 Outdoor PCB Test Run Operation (For Pump Down/Servicing Purpose)
The Test Run operation will be activated by short-circuiting CN-S (Pin 1 and 2) at outdoor unit PCB after power
supplied to outdoor unit terminal 1 and 2. The unit forced to run rated frequency cooling operation mode.
14.3.1 CU-E9PB4EA
64
14.3.2 CU-E12PB4EA
65
15. Troubleshooting Guide
15.1 Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the refrigeration
cycle depends on various conditions, the standard values for them
are shown in the table on the right.
Normal Pressure and Outlet Air Temperature (Standard)
Cooling Mode0.9 ~ 1.2 (9 ~ 12) 12 ~ 16
Heating Mode 2.3 ~ 2.9 (23 ~ 29) 36 ~ 45
*Condition: • Indoor fan speed = High
mode and 7°C at the heating mode
• Compressor operates at rated frequency
Gas Pressure
MPa
2
G)
(kg/cm
• Outdoor temperature 35°C at the cooling
Outlet air
Temperature
(°C)
66
15.1.1 Relationship between the condition of the air conditioner and pressure and
electric current
Condition of the
air conditioner
Insufficient refrigerant
(gas leakage)
Clogged capillary tube or
Strainer
Low Pressure High Pressure
Ô Ô Ô Ô Ô Ô
Ô Ô Ô Ò Ò Ò
Cooling Mode Heating Mode
Electric current
during operation
Low Pressure High Pressure
Electric current
during operation
Short circuit in the indoor unit
Heat radiation deficiency
of the outdoor unit
Inefficient compression
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.
Ô Ô Ô Ò Ò Ò
Ò Ò Ò Ô Ô Ô
Ò Ô Ô Ò Ô Ô
67
15.2 Breakdown Self Diagnosis Function
15.2.1 Self Diagnosis Function (Three Digits Alphanumeric Code)
Once abnormality has occurred during operation,
the unit will stop its operation, and Timer LED
blinks.
Although Timer LED goes off when power supply
is turned off, if the unit is operated under a
breakdown condition, the LED will light up again.
In operation after breakdown repair, the Timer
LED will no more blink. The last error code
(abnormality) will be stored in IC memory.
15.2.2 To Make a Diagnosis
1 Timer LED start to blink and the unit
automatically stops the operation.
2 Press the CHECK button on the remote
controller continuously for 5 seconds.
3 “- -” will be displayed on the remote controller
display.
Note: Display only for “- -”. (No transmitting
signal, no receiving sound and no Power LED
blinking.)
4 Press the “TIMER” ▲ or ▼ button on the
remote controller. The code “H00” (no
abnormality) will be displayed and signal will
be transmitted to the main unit.
5 Every press of the button (up or down) will
increase abnormality numbers and transmit
abnormality code signal to the main unit.
6 When the latest abnormality code on the main
unit and code transmitted from the remote
controller are matched, power LED will light
up for 30 seconds and a beep sound
(continuously for 4 seconds) will be heard. If
no codes are matched, power LED will light up
for 0.5 seconds and no sound will be heard.
7 The breakdown diagnosis mode will be
canceled unless pressing the CHECK button
continuously for 5 seconds or operating the
unit for 30 seconds.
8 The LED will be off if the unit is turned off or
the RESET button on the main unit is pressed.
15.2.3 To Display Memorized Error
Code (Protective Operation)
1 Turn power on.
2 Press the CHECK button on the remote
controller continuously for 5 seconds.
3 “- -” will be displayed on the remote controller
display.
Note: Display only for “- -”. (No transmitting
signal, no receiving sound and no Power LED
blinking.)
4 Press the “TIMER” ▲ or ▼ button on the
remote controller. The code “H00” (no
abnormality) will be displayed and signal will
be transmitted to the main unit. The power
LED lights up. If no abnormality is stored in
the memory, three beeps sound will be heard.
5 Every press of the button (up or down) will
increase abnormality numbers and transmit
abnormality code signal to the main unit.
6 When the latest abnormality code on the main
unit and code transmitted from the remote
controller are matched, power LED will light
up for 30 seconds and a beep sound
(continuously for 4 seconds) will be heard. If
no codes are matched, power LED will light up
for 0.5 seconds and no sound will be heard.
7 The breakdown diagnosis mode will be
canceled unless pressing the CHECK button
continuously for 5 seconds or operating the
unit for 30 seconds.
8 The same diagnosis can be repeated by
turning power on again.
15.2.4 To Clear Memorized Error Code
after Repair (Protective
Operation)
1 Turn power on (in standby condition).
2 Press the AUTO button for 5 seconds (A beep
receiving sound) on the main unit to operate
the unit at Forced Cooling Operation modes.
3 Press the CHECK button on the remote
controller for about 1 second with a pointed
object to transmit signal to main unit. A beep
sound is heard from main unit and the data is
cleared.
15.2.5 Temporary Operation (Depending
On Breakdown Status)
1 Press the AUTO button (A beep receiving
sound) on the main unit to operate the unit.
(Remote control will become possible.)
2 The unit can temporarily be used until
repaired.
68
15.3 Error Codes Table
Diagnosis
display
H00 No memory of failure — Normal operation— —
H11
H12
H14
H15
H16
H19
H21
H23
H24
H27
H28
H30
H33
H35
H38
H97
H98
H99
F11
F90
F91
F93
Abnormality /
Protection control
Indoor/outdoor
abnormal
communication
Indoor unit capacity
unmatched
Indoor intake air
temperature sensor
abnormality
Compressor
temperature sensor
abnormality
Outdoor current
transformer (CT)
abnormality
Indoor fan motor
mechanism lock
Indoor float switch
operation abnormal
Indoor heat
exchanger
temperature sensor
abnormality
Indoor heat
exchanger
temperature sensor
2 abnormality
Outdoor air
temperature sensor
abnormality
Outdoor heat
exchanger
temperature sensor
1 abnormality
Outdoor discharge
pipe temperature
sensor abnormality
Indoor / outdoor
misconnection
abnormality
Indoor drain water
adverse current
abnormal
Indoor/Outdoor
mismatch (brand
code)
Indoor fan only
operation can
start by entering
into force cooling
operation
—
—
—
—
—
—
—
Problem Check location
Indoor/outdoor
communication not
establish
Total indoor capability
more than maximum limit
or less than minimum limit,
or number of indoor unit
less than two
Indoor intake air
temperature sensor open
or short circuit
Compressor temperature
sensor open or short circuit
Current transformer faulty
or compressor faulty
Indoor fan motor lock or
feedback abnormal
Indoor heat exchanger
temperature sensor open
or short circuit
Indoor heat exchanger
temperature sensor 2 open
or short circuit
Outdoor air temperature
sensor open or short circuit
Outdoor heat exchanger
temperature sensor 1 open
or short circuit
Outdoor discharge pipe
temperature sensor open
or short circuit
Fan motor lock or block
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
Check indoor heat exchanger
Air filter dirty
Air circulation short circuit
4-way valve
Lead wire and connector
Outdoor PCB faulty
Insufficient refrigerant or valve
close
Power transistor module faulty
or compressor lock
69
Diagnosis
display
F95
F96
F97
F98
F99
Abnormality /
Protection control
Outdoor cooling high
pressure protection
Power transistor
module overheating
protection
Compressor
overheating
protection
Total running current
protection
Outdoor direct
current (DC) peak
detection
Abnormality
Judgment
4 times happen
within 20 minutes
4 times happen
within 30 minutes
3 times happen
within 30 minutes
3 times happen
within 20 minutes
Continuous
happen for 7 times
Protection
Operation
—
—
— Compressor overheat
— Total current protection
—
Cooling high pressure
protection
Power transistor module
overheat
Power transistor module
current protection
Problem Check location
Check refrigeration system
Outdoor air circuit
PCB faulty
Outdoor air circuit (fan motor)
Insufficient refrigerant
Check refrigeration system
Power source or compressor
During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal
transmission is checked whether it is normal.
Malfunction Caused
Faulty indoor unit PCB.
Faulty outdoor unit PCB.
Indoor unit-outdoor unit signal transmission error due to wiring error.
Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the
During startup, error code appears when different types of indoor and outdoor units are interconnected.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit or outdoor unit PCBs mounted.
Indoor unit or outdoor unit PCBs defective.
Indoor-outdoor unit signal transmission error due to wrong wiring.
Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor
and outdoor units.
Troubleshooting
72
15.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor intake air
temperature sensor are used to determine sensor errors.
An input current, detected by Current Transformer CT, is below threshold value when the compressor is
operating at certain frequency value for 3 minutes.
Malfunction Caused
Lack of gas
Broken CT (current transformer)
Broken Outdoor PCB
Troubleshooting
75
15.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor
(feedback of rotation > 2550rpm or < 50rpm)
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to Hall IC malfunction.
Operation error due to faulty indoor unit PCB.
Troubleshooting
76
15.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality)
Malfunction Decision Conditions
During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger
temperature sensor are used to determine sensor errors.
15.4.12 H33 (Unspecified Voltage between Indoor and Outdoor)
Malfunction Decision Conditions
The supply power is detected for its requirement by the indoor/outdoor transmission.
Malfunction Caused
Wrong models interconnected.
Wrong indoor unit and outdoor unit PCBs used.
Indoor unit or outdoor unit PCB defective.
Troubleshooting
82
15.4.13 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked)
Malfunction Decision Conditions
The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor.
Malfunction Caused
Operation stops due to short circuit inside the fan motor winding.
Operation stops due to breaking of wire inside the fan motor.
Operation stops due to breaking of fan motor lead wires.
Operation stops due to Hall IC malfunction.
Operation error due to faulty outdoor unit PCB.
Troubleshooting
83
15.4.14 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED
flashing)
Malfunction Decision Conditions
Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is
operating in heating operation.
Phenomena: unit is stopping and re-starting very often in heating mode.
Malfunction Caused
Indoor heat exchanger thermistor
Clogged air filter or heat exchanger
Over-bent pipe (liquid side)
Troubleshooting
84
15.4.15 H99 (Indoor Freeze Prevention Protection: Cooling or Soft Dry)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
Freeze prevention control takes place (when indoor pipe temperature is lower than 2°C)
Malfunction Caused
Air short circuit at indoor unit
Clogged indoor unit air filter
Dust accumulation on the indoor unit heat exchanger
2/3 way valve closed
Faulty indoor unit fan motor
Refrigerant shortage (refrigerant leakage)
Clogged expansion valve or strainer
Faulty indoor pipe temperature sensor
Faulty indoor unit PCB
Troubleshooting
85
15.4.16 F11 (4-way Valve Switching Failure)
Malfunction Decision Conditions
When indoor heat exchanger is cold during heating (except deice) or when indoor heat exchanger is hot during
cooling and compressor operating, the 4-way valve is detected as malfunction.
* Check gas side pipe – for hot gas flow in cooling mode
86
15.4.17 F90 (Power Factor Correction Protection)
Malfunction Decision Conditions
To maintain DC voltage level supply to power transistor.
To detect high DC voltage level after rectification.
Malfunction Caused
During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry at
the outdoor unit main PCB senses abnormal DC voltage level for power transistors.
When DC voltage detected is LOW, transistor switching will turn ON by controller to push-up the DC level.
When DC voltage detected is HIGH (391Vdc – 425Vdc), active LOW signal will send by the controller to turn OFF
relay RY-C.
Troubleshooting
87
15.4.18 F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
The input current is low while the compressor is running at higher than the setting frequency.
Malfunction Caused
Lack of gas.
3-way valve close.
Troubleshooting
88
15.4.19 F93 (Compressor Rotation Failure)
Malfunction Decision Conditions
A compressor rotation failure is detected by checking the compressor running condition through the position
15.4.20 F95 (Outdoor High Pressure Protection: Cooling or Soft Dry)
Malfunction Decision Conditions
During operation of cooling or soft dry, when outdoor unit heat exchanger high temperature data is detected by
the outdoor unit heat exchanger thermistor.
Malfunction Caused
Outdoor heat exchanger temperature rise due to short-circuit of hot discharge air flow.
Outdoor heat exchanger temperature rise due to defective of outdoor fan motor.
Outdoor heat exchange temperature rise due to defective outdoor heat exchanger thermistor.
Outdoor heat exchanger temperature rise due to defective of outdoor unit PCB.
Troubleshooting
90
15.4.21 F96 (IPM Overheating)
Malfunction Decision Conditions
During operating of cooling and heating, when IPM temperature data (100°C) is detected by the IPM temperature
sensor.
Multi Models only
o Compressor Overheating: During operation of cooling and heating, when the compressor OL is activated.
o Heat Sink Overheating: During operation of cooling and heating, when heat sink temperature data (90°C) is
detected by the heat sink temperature sensor.
Malfunction Caused
IPM overheats due to short circuit of hot discharge air flow.
IPM overheats due to defective of outdoor fan motor.
IPM overheats due to defective of internal circuitry of IPM.
IPM overheats due to defective IPM temperature sensor.
Multi Models Only
o Compressor OL connector poor contact.
o Compressor OL faulty.
Troubleshooting
91
15.4.22 F97 (Compressor Overheating)
Malfunction Decision Conditions
During operation of cooling and heating, when compressor tank temperature data (112°C) is detected by the
compressor tank temperature sensor.
Malfunction Caused
Faulty compressor tank temperature sensor
2/3 way valve closed
Refrigerant shortage (refrigerant leakage)
Faulty outdoor unit PCB
Faulty compressor
Troubleshooting
92
15.4.23 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During operation of cooling and heating, when an input over-current (X value in Total Running Current Control) is
detected by checking the input current value being detected by current transformer (CT) with the compressor
running.
Malfunction Caused
Excessive refrigerant.
Faulty outdoor unit PCB.
Troubleshooting
93
15.4.24 F99 (DC Peak Detection)
Malfunction Decision Conditions
During startup and operation of cooling and heating, when inverter DC peak data is received by the outdoor internal
DC Peak sensing circuitry.
Malfunction Caused
DC current peak due to compressor failure.
DC current peak due to defective power transistor(s).
DC current peak due to defective outdoor unit PCB.
DC current peak due to short circuit.
Troubleshooting
94
16. Disassembly and Assembly Instructions
High Voltage is generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with
repair work. Failure to heed this caution may result in electric shocks.
16.1 Disassembly of Parts
1 Open the Intake Grille from the Front Grille by
moving the catchers to center (Fig.1).
2 Remove the Control Board Cover by removing
the screws (Fig. 2).
WARNING
Fig. 1
3 Release the (Fig. 3):
o CN-STM1 (WHT) connector.
o CN-STM2 (YLW) connector.
o CN-DISP (WHT) connector.
o CN-FM (WHT) connector.
o CN-TH1 (WHT) connector.
o CN-TH2 (BLU) connector.
o CN-DRMTR1 (BLU) connector.
o AC01 (BLK), AC02 (WHT) and
CN-DRMTR2 (RED) from Terminal
Board.
o G01 (GRN) screw.
o Two T-BLK connectors.
o CN-T1 (WHT).
o CN-T2 (
Fig. 2
Fig. 3
YLW).
95
4 To remove the Electronic Controller, release
the 6 hooks that hold it to the Control Board
(Fig. 4).
5 Remove the Front Grille by removing the
screw A and scr
(Fig. 5).
ews B, C & D half way open
6 Remove the Air Guider and Drain Pan
complete by removing the screws (Fig. 6).
Fig. 4
Fig. 5
7 Remove the Turbo Fan by removing the bolt
(Fig. 7).
Fig. 6
Fig. 7
96
8 Remove the Fan Motor by release the Fan
Motor lead wire connectors and Fan Motor
screws (Fig. 8).
Caution! When handling electronic controller, be careful of electrostatic discharge.
1 Remove the 5 screws of the Top Panel.
5 Remove the Control Board as follows:
Fig. 1
2 Remove the 8 screws of the Front Panel.
Fig. 2
3 Remove the screw of the Terminal Board
Cover.
4 Remove the Top Cover of the Control Board
by 4 hooks.
Fig. 4
Fig. 5
Fig. 3
Fig. 6
98
16.2.2 CU-E12PB4EA
1 Remove the 4 screws of the Top Panel.
4 Remove the Control Board.
Fig. 1
2 Remove the 10 screws of the Front Panel.
Fig. 2
3 Remove the Top Cover of the Electronic
Controller.
Fig. 4
5 Remove the 8 screws of the Electronic
Controller.
Fig. 5
Caution! When handling electronic controller, be careful of
electrostatic discharge.
Fig. 3
99
17. Service Data
M
Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced
heating mode.
17.1 Cool Mode Outdoor Air Temperature Characteristic
Condition
Indoor room temperature: 27°C DryBulb/19°C Wet Bulb
Unit setting: Standard piping length, forced cooling at 16°C, Hi fan
Compressor frequency: Rated for cooling operation
Voltage: 220V/230V
17.1.1 CS-E9PB4EA CU-E9PB4EA
230V220V
15.50
15.00
14.50
14.00
13.50
13.00
Outlet Air (°C)
12.50
12.00
14192429343944
Outdoor Air Temperature (°C)
3.00
2.80
2.60
2.40
2.20
2.00
1.80
Current (A)Low Pressure (
1.60
1.40
1.20
1.00
14192429343944
Outdoor Air Temperature (°C)
1.15
1.10
Pa)
1.05
1.00
0.95
0.90
0.85
0.80
0.75
0.70
14192429343944
Outdoor Air Temperature (°C)
100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.