• Press for < 5 second to operate Automatic
operation mode. Used when the remote control
cannot be used.
• Press for ≥ 5 second to operate Cooling
operation mode and compressor force to on
(“beep” sound will heard). Used when test
running or servicing.
• Within 20 second of Cooling operation, press
continuously for 5 second to enter various
setting mode. “beep, beep” sound will be heard.
(Used to toggle remote control signal receiving
sound or select remote control transmission
code).
Operation Indication Lamps (LED)
•
POWER
(Green) ............. Lights up in operation,
blinks in Automatic
Operation judging and
Hot Start operation.
•
TIMER
(Orange) ............ Lights up in Timer
Setting.
•
QUIET
(Orange) ............. Lights up in Quiet
Operation.
•
POWERFUL
•
ION
•
SUPER
ALLERU-BUSTER
(Orange) ...... Lights up in Powerful
Operation.
(Green) .................. Lights up in Ionizer
Operation.
(Blue) ... Lights up in operation.
Operation Mode
• Heating, Cooling, Soft Dry and Automatic
Operation.
Powerful Operation
• Reaches the desired room temperature quickly.
Random Auto Restart Control
• Unit will be restarted, when resume from power
failure, at previous setting.
Indoor Fan Speed Control
• Manual control fan speed (High, Medium and
Low).
• Automatic fan speed.
Airflow Direction Control
• Vertical airflow control can be adjusted
automatically or manually by remote control.
• Horizontal airflow can be manually adjusted by
hand.
Anti-Freezing Control
• To prevent indoor heat exchanger from freezing.
Starting Current Control
• To reduce the starting current.
Time Delay Safety Control
• Restarting is inhibited for appro. 3 minutes.
7 Minutes Time Save Control
• To reduce the built up humidity inside the room.
Anti-Dew Formation Control
• Anti-Dew Formation Control for indoor unit
discharge area.
30 Minutes Time Save Control
• Heating operation only.
Timer Operation
• Delay OFF/ON Timer control.
Quiet Operation
• To provide quiet operation.
Ionizer Operation
• Generate and discharge negative ion.
Hot-Start Control
• To prevent cold air being discharge during
Heating operation starts.
Anti Cold Draft Control
• To prevent the cold draft during Heating mode
operation in thermo off condition.
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium (Blue Coat)
Fin TypeSlit FinCorrugated Fin
Row / Stage(Plate fin configuration, forced draft)
Tube materialCopperCopper
Fin materialAluminium (Pre Coat)Aluminium (Blue Coat)
Fin TypeSlit FinCorrugated Fin
Row / Stage(Plate fin configuration, forced draft)
FPI2116
Size (W × H × L)mm610 × 315 × 25.4720 × 504 × 36.38
• Automatic operation can be set using remote control.
• This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature.
• After judged the temperature, the operation mode is determined by referring to the below standard.
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
• Operation mode will be determine again for judgement after 1 hour of operation, if the room temperature reaches to set
temperature and compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room temperature does not reach to set temperature (Compressor keeps running)
eventhough after 1 hour from automatic operation mode started.
(For 8.5.3. to 8.5.7. information applies only to Cooling and Soft Dry Operation)
8.5.3. 7 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
• This phenomenon is to reduce the built up humidity inside a room.
8.5.4. 60 Seconds Forced Operation
• Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake
air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
8.5.5. Starting Current Control
• When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
• The reason of the difference is to reduce the starting current flow.
8.5.6. Anti-Freezing Control
• If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the compressor turns off.
The fan speed setting remains the same.
• This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form
returning to the compressor.
• Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery).
• Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.
Deice starts to prevent frosting at outdoor heat exchanger.
• Normal Deicing
Deice operations detection commences after 30 minutes of Heating operation starts or 60 minutes after previous deice
operation. If the TRS (Thermal Reed Switch) senses the outdoor piping temperature drops to -3°C (TRS CLOSE) or less for
50 sec. continuously during compressor is in operation, deice will start.
(There is no detection during Outdoor Fan stops.)
• Overload Deicing
During heating operation, if the outdoor Fan OFF duration (due to overload control) is accumulated up to 60 minutes and
after compressor starts for 1 minutes, deicing starts.
• Deicing ends when
1. 12 minutes after deicing operation starts;
2. TRS senses the outdoor piping temperature rises to 4°C (TRS OPEN).
Deicing will not end immediately as time delay (Td) is valid as shown below.
• Once deicing operation starts, it will not end for 60 seconds.
• After deicing operation, compressor stops for 30 seconds and 4-way valve stays at cooling position for 10 seconds.
1. Indoor fan will rotate alternately between off and on as shown in below diagram.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the
start of compressor. This cause the room temperature to achieve the setting temperature quickly.
4. During compressor stop, indoor fan will operate at Lo- for the beginning 20 seconds to prevent higher volume of refrigerant
in liquid form returning to the compressor.
5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the room.
This is to obtain the actual reading of the intake air temperature.
6. When the compressor resume operation, indoor fan will operate at Me fan speed (after 70 seconds from the restart of
compressor) to provide comfort and lesser noise environment.
• Auto Fan Speed during Soft Dry operation:
1. Indoor fan will rotate alternately between off and Lo-.
2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose.
3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.
This is to obtain the actual reading of intake air temperature.
• The Ionizer operation is to provide fresh air effect to user by producing minus ion in discharge air.
8.12.1. Operation Control
1. Ionizer individual operation
a. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at the remote control is pressed, the
Ionizer and indoor fan operations will turn on. Only ION LED will illuminates. Power LED maintain off. (1 → 2)
b. Ionizer individual operation can be turned off by pressing the ION button again. (2 → 1)
c. Fan speed can be adjusted later by customer during this operation.
d. Vertical airflow direction can be adjusted using remote control during Ionizer individual operation.
e. During Ionizer individual operation, operated mode (Auto, Cool, Dry, Heat) can be activated by turning on the OFF/ON
operation button. (2 → 4)
f. If power failure occur during Ionizer individual operation, after power resume, Ionizer operation will be activated immediately.
g. When the Ionizer circuit feedback process error occur for 24 times (about 11hr 30 min.), Ionizer and Air Circulation
operations will turn off with ION LED blinks continuously.
(For details, please refer to Ionizer Error detection control)
2. Operation mode & Ionizer operation.
a. When air-conditioner unit is at “ON” condition and ION operation button at the remote control is pressed, the Ionizer
operation will turn on. ION & Power LED will illuminate. (3 → 4)
b. Ionizer operation stops when:
• ION operation button is press again.
• Stopped by OFF/ON operation button.
• Timer OFF activates.
• Ionizer circuit feedback signal shows error.
c. Ionizer operation status is not memorized when the air conditioner has been switched off. The air-conditioner will operate
without ionizer operation when it is turned on again. However, if power failure occurs during Ionizer operation together with
Cooling operation, air-conditioner will start to operate at Cooling operation with Ionizer operation when the power is
resumed.
• Read the following “SAFETY PRECAUTIONS” carefully before installation.
• Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit
for the model to be installed.
• The caution items stated here must be followed because these important contents are related to safety. The meaning of each
indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the
seriousness is classified by the following indications.
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties only.
The items to be followed are classified by the symbols:
Symbol with background white denotes item that is PROHIBITED from doing.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6. Use the specifi ed cable (1.5 mm2) and connect tightly for indoor/outdoor connection. Conne ct tightly and clamp the cable so that no
external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnorm al high pressure in the refrigeration cycle, explosion and injury.
9. Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock.
10. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with
other electrical applian ces. Otherwise, it will cause fire or electrical shock.
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
1.Selection of the installation location.
Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.
2. Power supply connection to the room air conditioner.
Connect the power supply cord of the room air conditioner to the mains using one of the following method.
Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency.
In some countries, permanent connection of this room air conditioner to the power supply is prohibited.
1. Power supply connection to the receptacle using a power plug.
Use an approved 15A/16A power plug with earth pin for the connection to the socket.
2. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker for the permanent
connection. It must be a double pole switch with a minimum 3 mm contact gap.
3. Do not release refrigerant.
Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the
liquid refrigerant, it may cause frostbite.
4. Installation work.
It may need two people to carry out the installation work.
5. Do not install this appliance in a laundr y room or other location where water may drip from the ceiling, etc.
10.5.1. SELECT THE BEST LOCATION
(Refer to “Select the best location”
section)
10.5.2. HOW TO FIX INSTALLATION
PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
10.5.3. TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the wall.
Caution
When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
The centre of installation plate should be at more than 450 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit’s left side is 74 mm.
From installation plate right edge to unit’s right is 94 mm.
:
For left side piping, piping connection for liquid should be
about 15 mm from this line.
:
For left side piping, piping connection for gas should be
about 45 mm from this line.
:
For left side piping, piping connecting cable should be
about 800 mm from this line.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the arrows marked on the lower left
and right side of the installation plate. The meeting point
of the extended line is the centre of the hole. Another
method is by putting measuring tape at position as
shown in the diagram above. The hole centre is
obtained by measuring the distance namely 150 mm
and 125 mm for left and right hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
1. The inside and outside connecting cable can be connected
without removing the front grille.
2. Connecting cable between indoor unit and outdoor unit
shall be approved polychloroprene sheathed 3 (C7DK,
C9DK, C12DK) or 5 (A7DK, A9DK, A12DK) × 1.5 mm
flexible cord, type designation 245 IEC 57 or heavier cord.
• Ensure the color of wires of outdoor unit and the
terminal Nos. are the same to the indoor’s respectively.
• Earth lead wire shall be longer than the other lead wires
as shown in the figure for the electrical safety in case of
the slipping out of the cord from the anchorage.
INSTALLATION OF SUPER ALLERU-BUSTER FILTER
1. Open the front panel.
2. Remove the air filters.
2
3. Remove Supersonic air purifying device.
4. Open the Supersonic air purifying device frame.
5. Insert the super alleru-buster filter and close the Supersonic
air purifying device frame as shown in illustration at below.
• Secure the cable onto the control board with the holder
(clamper).
HOW TO TAKE OUT FRONT GRILLE
Please follow the steps below to take out front grille if
necessary such as when servicing.
1. Open the intake grille and remove the screw at the front of
the front grille.
50
2. Set the vertical airflow direction louver to the horizontal
position.
3. Slide down the 2 caps on the front grille as shown in the
illustration at right, and then remove the 2 mounting screws.
4. Pull the lower section of the front grille towards you to
remove the front grille.
When reinstalling the front grille, first set the vertical
airflow direction louver to the horizontal position and
then carry out above steps 2 - 3 in the reverse order.
10.6.1. SELECT THE BEST LOCATION
(Refer to “Select the best location”
section)
10.6.2. INSTALL THE OUTDOOR UNIT
AUTO SWITCH OPERATION
The below operations will be performed by pressing the
“AUTO” switch.
1. AUTO OPERATION MODE
The Auto operation will be activated immediately once the
Auto Switch is pressed.
2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING
PURPOSE)
The Test Run operation will be activated if the Auto Switch
is pressed continuously for more than 5 sec. to below 10
sec. A “pep” sound will occur at the fifth sec., in order to
identify the starting of Test Run operation
3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
The ON/OFF of Remote Controller receiving sound can be
change over by the following steps:
a) Release the Auto Switch after Test Run operation is
activated.
b) Then, within 20 sec. after (a), press Auto Switch for more
than 5 sec..A “beep” “beep” sound will occur at the fifth
sec., then release the Auto Switch.
c) Within 20 sec. after (b), press Auto Switch again.
Everytime Auto Switch is pressed (within 20 sec. interval),
remote controller receiving sound status will be reversed
between ON and OFF.
Long “beep” sound indicates that remote controller
receiving sound is OFF.
Short “beep” sound indicates that remote controller
receiving sound is ON.
• After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally
by bolt nut. (ø10 mm).
2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly with
bolt or nails.
10.6.3. CONNECTING THE PIPING
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe. (In case of using long
piping)
Connect the piping
• Align the center of piping and sufficiently tighten the flare
nut with fingers.
• Further tighten the flare nut with torque wrench in specified
Decide piping length and then cut by using pipe cutter. Remove
burrs from cut edge. Make flare after inserting the flare nut
(located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque
wrench to the specified torque as stated in the table.
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder
entering the pipe.
3. Please make flare after inserting the flare nut onto the
copper pipes.
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
10.6.5. CONNECT THE CABLE TO THE OUTDOOR UNIT
1. Remove the control board cover from the unit by loosening the screw.
2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (C7DK, C9DK, C12DK)
or 5 (A7DK, A9DK, A12DK) × 1.5 mm
3. Secure the cable onto the control board with the holder (clamper).
4. Attach the control board cover back to the original position with the screw.
2
flexible cord, type designation 245 IEC 57 or heavier cord.
1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
with thickness 6 mm or above.
DISPOSAL OF OUTDOOR UNIT DRAIN WATER
• If the drain elbow is used, the unit should be placed on a
stand which is taller than 3cm.
• If the unit is used in an area where temperature falls below
0° C for 2 or 3 days in succession, it is recommended not to
use a drain elbow, for the drain water freezes and the fan
will not rotate.
CHECK THE DRAINAGE
• Open front panel and remove air filters.
(Drainage checking can be carried out without removing the
front grille.)
• Pour a glass of water into the drain tray-styrofoam.
• Ensure that water flows out from drain hose of the indoor
unit.
EVALUATION OF THE PERFORMANCE
• Operate the unit at cooling operation mode for fifteen
minutes or more.
• Measure the temperature of the intake and discharge air.
• Ensure the difference between the intake temperature and
the discharge is more than 8°C.
54
CHECK ITEMS
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut
connection?
Is the connecting cable being fixed to terminal board firmly?
Is the connecting cable being clamped firmly?
Is the drainage OK?
(Refer to “Check the drainage” section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Required tools: hexagonal wrench, adjustable wrench, torque
wrenches, wrench to hold the joints and gas leak detector.
The additional gas for air purging has been charged in the
outdoor unit.
However, if the flare connections have not been done correctly
and there gas leaks, a gas cylinder and the charge set will be
needed.
The air in the indoor unit and in the piping must be purged. If air
remains in the refrigeration pipings, it will affect the
compressor, reduce the cooling capacity, and could lead to a
malfunction.
Service port cap
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas
leakage from the refrigeration cycle.
Procedure:
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve counter-
clockwise approximately 90°, wait 10 seconds, and
then set it to closed position.
• Be sure to use a hexagonal wrench to operate the valve
stem.
3. Check for gas leakage.
6. Set the 3-way valve to the opened position.
7. Mount the valve stem nuts to the 2-way and 3-way
valves.
8. Check for gas leakage.
• At this time, especially check for gas leakage from the 2-
way and 3-way’s stem nuts, and from the service port
cap.
• Check the flare connection for gas leakage.
4. Purge the air from the system
• Set the 2-way valve to the open position and remove the
cap from the 3-way valve’s service port.
• Using the hexagonal wrench to press the valve core pin,
discharge for three seconds and then wait for one
minute.
Repeat this three times.
5. Use torque wrench to tighten the service port cap to a
Caution
If gas leakage is discovered in step (3) above, take
the following measures:
Tighten the piping connections. If the leaks stop,
continue working from step (4).
If the gas leaks do not stop when the connections are
retightened, repair the location of the leak, discharge
all of the gas through the service port, and then
recharge with the specified amount of gas from a gas
cylinder.
1. Connect the charge hose to the charging cylinder.
• Connect the charge hose which you disconnected from
the vacuum pump to the valve at the bottom of the
cylinder.
2. Purge the air from the charge hose.
• Open the valve at the bottom of the cylinder and press
the check valve on the charge set to purge the air (be
careful of the liquid refrigerant).
3. Open the valve (Low side) on the charge set and charge
the system with liquid refrigerant.
• If the system cannot be charged with the specified
amount of refrigerant, it can be charged with a little at a
time (approximately 150 g each time) while operating
the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and
then repeat the procedure. (pumping down-pin)
This is different from previous proced ures. Because you are
charging with liquid refrigerant from the gas side, absolutely do
no attempt to charge with large amoun t of liquid refrigerant
while operating the air conditioner.
4. Immediately disconnect the charge hose from the 3-
way valve’s service port.
• Stopping partway will allow the refrigerant to be
discharged.
• If the system has been charged with liquid refrigerant
while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
5. Mount the valve stem caps and the service port cap.
• Use torque wrench to tighten the service port cap to a
− Long “beep”: Turn OFF remote control signal receiving sound.
• After “Auto OFF/ON Button” is pressed, the 20s counter for various setting mode is restarted.
12.4.2. Select Remote Control Transmission Code
• There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor unit. The indoor unit
will only operate when received signal with same transmission code from remote control. This could prevent signal interference
when there are 2 or more indoor unit installed nearby together.
• To change remote control transmission code, short or open jumpers at the remote control printed circuit board.
• Under various setting mode, after select the transmission code combination of remote control, press any button of remote
control to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.
• After signal is received, the various setting mode is cancelled and return to normal operation.
12.5. Remote Control Reset
• When the batteries are inserted for the first time or the
batteries are replaced, you may notice the indications at
remote control’s display screen blink continuously and not
functionable. If this condition happens, try to reset the
remote control by pushing the reset terminal with a pointing
device.
• You may also do the reset to erase the setting at remote
control and restore back the default setting.
66
13 Troubleshooting Guide
13.1. Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
1CHASSY ASS’Y1CWD50K2112
2SOUND PROOF MATERIAL1CWG302255←
3FAN MOTOR BRACKET1CWD541075←
4SCREW - FAN MOTOR BRACKET2CWH551060←
5FAN MOTOR1CWA951388←0
6SCREW - FAN MOTOR MOUNT3CWH55406←
7PROPELLER FAN ASS’Y1CWH03K1020
8NUT - PROPELLER FAN1CWH56053←
28HOLDER CAPACITOR1CWH301038CWH301035
29CAPACITOR - FAN MOTOR1DS441205NPQA←0
30CABINET SIDE PLATE (L)1CWE041110A←
31CABINET SIDE PLATE (R)1CWE04C1042←
32CABINET FRONT PLATE1CWE06K1048←
33WIRE NET1CWD041057A←
34CABINET TOP PLATE1CWE031041A
36CONTROL BOARD COVER1CWH13C1099
1 min.1 sec.
Time Delay Safety Control2 min. 58 sec.0 sec.
Forced Operation60 sec.0 sec.
Time Save Control7 min.4.2 sec.
Anti-Freezing4 min.0 sec.
Auto Mode Judgement25 sec.0 sec.
Soft DryOFF6 min.36 sec.
ON10 min.60 sec.Soft Dry: 10 min. operation
Cooling40 sec.4 sec.
Deodorizing Control
Soft Dry40 sec.4 sec.
Comp. Reverse Rotation Detection5 min.30 sec.Comp. ON 5 min. and above
Comp./ Fan Motor Delay Timer1.6 sec.0 sec.
Powerful Mode Operation15 min.15 sec.
Random Auto Restart Control0 ~ 62 sec.0 ~ 6.2 sec.
TRS Recovery Detection12 min.72 sec.
Time Save Control (Heating)30 min.3 sec.
4 Way Valve Control (Delay)5 min.30 sec.
Deice Operation Occurs60 min.6 sec.60 min. after previous deice
Overload Deice Timer1 min.6 sec.Comp. ON continuously for 1 min. check
Deice End12 min.72 sec.Max. Operation time
Deice Operation (Extend)60 sec.0 sec.
Hotstart Finish30 sec.0 sec.
70 sec.7 sec.
20 sec.2 sec.
180 sec.18 sec.
360 sec.36 sec.
2 min.0 sec.
6 min.36 sec.
3 min.18 sec.
1 min.6 sec.
4 min.24 sec.Continuously 4 min. Comp. ON
50 sec.0 sec.TRS ON continuously for 50 sec. check
30 sec.3 sec.30 sec. Comp. OFF after deice
10 sec.1 sec.4-Way Valve ON 10 sec. later after deice