• Press 3 to increase or decrease the temperature.
• The temperature can be set between 16°C ~ 30°C
• Recommended temperature:
Cooling Model
COOL –> 26°C ~ 28°C
DRY –> 1°C ~ 2° C
lower than the
room temperature
• During AUTO Operation, press 3 to select:-
• Operation with 2°C higher than the standard
temperature.
• Operation with the standard temperature.
• Operation with 2°C lower than the standard
temperature.
● Standard Temperature
Indoor
temperature
23°C
• Once the Automatic Operation is selected, the indoor
temperature sensor operates automatically to select
the desired operation mode with Cooling or Soft Dry.
• After the operation mode has been selected, the
mode does not change.
Indoor
temperature
23°C
20°C
• At the beginning of the automatic operation, Heating,
Cooling or Soft Dry is automatically selected according
to the indoor temperature.
• After the operation mode has been selected, the
mode does not change.
Heat Pump Model
COOL –> 26°C ~ 28°C
DRY –> 1°C ~ 2° C
HEAT –>20°C ~ 24°C
Cooling Model
Operation
Cooling
Soft Dry
Heat Pump Model
Operation
Cooling
Soft Dry
Heating
lower than the
room temperature
Standard
temperature
25°C
22°C
Standard
temperature
25°C
22°C
21°C
● Operation Details
COOL – Cooling Operation
• To set the room temperature at your preference
cooling comfort.
AUTO – Automatic Operation
• Sense indoor temperature to select the optimum
mode.
• Temperature is not displayed on the remote control
during AUTO operation.
DRY – Soft Dry Operation
• A very gentle Cooling Operation, prior to
dehumidification. It does not lower the room
temperature.
• During Soft Dry operation, the indoor fan operates at
Low Fan Speed.
HEAT – Heating Operation
(for Heat Pump Model only)
• Heat is obtained from outdoor air to warm up the
room. When the outdoor ambient air temperature
falls, the heating capacity of the unit might be
reduced.
• Defrosting Operation
Depend on the outdoor temperature, the operation
occasionally stops to melt the frost on the outdoor
unit.
FAN – Air Circulation Operation
(for Cooling Model only)
• Heated air rises and collects at the top of the room.
The air circulation circulates the heated air downward,
thus increasing heating effectiveness. When the unit
is installed floor mounted, you should set the
temperature higher than that of ceiling mounted.
FAN– Low Fan Speed
FAN– Medium Fan Speed
FAN– High Fan Speed
AUTO
FAN – Automatic Fan Speed
The speed of the indoor fan is adjusted
automatically according to the operation.
The indoor fan stops occasionally during
cooling operation.
■ Vertical Airflow Direction
● Manual Operation
• Press and hold the Manual Airflow Direction
Selection Button 5 , then release the button at
the desired airflow direction.
• Cooling / Soft Dry/
Heating (for Heat-Pump Model only)
The airflow direction can be adjusted as desired
by using the remote control. This is effective
when you want to cool yourself directly, such as
when coming out of the bath. The louver can be
adjusted within a range between the horizontal
and 25 degrees downward at Cooling and Soft
Dry Operation, and between the horizontal and
45 degrees downward at Heating Operation.
(for Heat-Pump Model only)
Horizontal
Downward
● Automatic Operation
• Press the Auto Airflow Direction Button 6.
• Cooling / Soft Dry
The louver will automatically swing up and down
to create the feeling of a refreshing breeze.
• Heating (for Heat-Pump Model only)
When the discharge air temperature is low such
as at starts of heating operation, the air blows at
horizontal level.
As the temperature rises, the hot air blows in a
downwards direction.
■ Setting the Horizontal Airflow Direction
• Adjust it manually
● Use this air conditioner under the following
conditions:
Cooling Model
(Unit in °C)
DBT: Dry Bulb Temp
WBT: Wet Bulb Temp
Maximum Temperature
Minimum Temperature
IndoorOutdoor
DBT
WBT
DBT
32
23
16
11
WBT
43
26
16
11
Heat Pump Model
(Unit in °C)
Outdoor
DBT: Dry Bulb Temp
WBT: Wet Bulb Temp
Maximum Temperature-Cooling
(Maximum Temperature-Heating)
• If the unit is not going to be used for an extended
period of time, turn off the main power supply. If it is
left at the ON position, approximately 2.0 W of
electricity will be used even if the indoor unit has been
turned off with the remote control.
• If operation is stopped, then restart immediately, the
unit will resume operation only after 3 minutes.
DBT
(30)
(16)
32
16
Indoor
WBT
23
11
DBT
WBT
43
26
(-)
(24)
(18)
16
11
(-)
(-5)
(-6)
5
3
2
SELEC
1
4
SETTING THE TIMER
• Press the Timer Selection Button 1.
• Timer indicator on the indoor unit will light up.
• Select one of the following five types of operation.
Each time the button is pressed, the operation mode
is shifted in the arrow direction.
Delay OFF TimerExample :
OFF
Delay ON TimerExample :
Delay OFF andExample :
ON TimerOperation stops after
OFF
Delay ON andExample :
OFF TimerOperation starts after
• Then press the Timer Setting Button 2 or 3 to the
desired number of hours.
(Number of hours which can be set : 1 ~ 12)
• Press the Timer Set/Cancel Button 4.
A
U
TO
C
OO
L
D
R
Y
F
A
N
C
O
FF
H
T
F
O
A
E
N
N
S
P
M
O
E
F
E
F
D
P
H
O
N
OFF/ON
M
O
D
E
S
L
E
E
A
P
F
A
N
S
P
B
E
E
D
TIM
ER
AUTO
T
A
S
I
R
ET/C
S
W
AN
I
N
C
G
E
L
R
E
S
E
T
Operation Stops
H
ON
H
OFF
after 1 hour
ON Timer.
Operation starts after
6 hours.
1 hour and re-starts
after another 5 hours.
10 hours, and then
stops after another 8
hours.
H
H
ON
H
H
ON
CONVENIENCE OPERATION
■ Sleep Mode Operation
To obtain a comfortable room temperature while sleeping:-
• Press 5.
• Sleep mode indicator on the indoor unit will light up.
• To cancel this operation, press once more.
● Sleep Mode Operation Details
• When the room temperature reaches the set temperature,
the airflow volume will change to low automatically.
• Sleep Mode Operation time is 8 hours.
• When used together with the timer, the timer has a priority.
Cooling Model
Temperature
S
T
e
e
m
t
p
t
e
i
r
n
a
g
t
u
r
e
Sleep
Operation
button is
pressed.
0~1 hour ← 1 hour →
Approx. 0.5°C
increase.
Approx.
0.5°C
increase.
• Cooling or Soft Dry
Operation for sleep shift
operation will start to
Sleep shift
avoid overcooling.
operation
starts.
after approx. 8 hours of sleep shift
operation, it will stop automatically.
Heat Pump Model
Temperature
S
T
e
e
m
t
p
t
e
i
r
n
a
g
t
u
r
e
Sleep
Operation
button is
pressed.
0~1 hour
Approx. 0.5°C
increase.
Approx.
0.5°C
increase.
Sleep shift
operation starts.
Approx. 2°C
decrease.
← 1 hour →
← 1 hour →
after approx. 8 hours of sleep shift
operation, it will stop automatically.
• Cooling or Soft Dry
Operation for sleep shift
operation will start to
avoid overcooling.
• Heating operation for
sleep shift operation will
start to avoid overheating.
Approx. 3°C
decrease.
Time
CARE AND MAINTENANCE
■ Cleaning the Indoor Unit and Remote
Control
• Wipe gently with a soft, dry cloth.
• Do not use water hotter than 40˚C or polishing fluid
to clean the unit.
■ Cleaning the Air Filter
(Recommendation:- If the unit is operated in a dusty
environment, clean the filters every two weeks,
continuous use of this dirty filters will reduce cooling
or heating efficiency)
1
Remove dirt using a vacuum cleaner.
2
Wash back of the air filter with water.
3
If badly soiled, wash it with soap or a mild household
detergent.
4
Let it dry and reinstall it.
Be sure the “FRONT” mark is facing you.
* Damaged air filter.
Consult the nearest authorized dealer.
Part No.: CWD001088.
• Do not use benzene, thinner, scouring powder or
Time
clothes soaked in caustic chemical to clean the
unit.
● Clean the air filters, re-insert and operate the air
conditioners.
● Is the discharged air cold / warm?
Operation is normal if 15 minutes after the start of
operation, the difference between the air intake and
outlet vents temperature is:-
Cooling Model
COOL –> 8°C or above
Heat Pump Model
COOL –> 8°C or above
HEAT –> 14°C or above
● Are the air intake or outlet vents of the indoor or
● Are the remote control batteries weak?
outdoor units obstructed?
If the remote control display appears weak, replace
the batteries.
■ When the Air Conditioner is Not Used
for an Extended Period of Time
1
To dry the internal parts of the indoor unit, operate
the unit for 2 - 3 hours using:-
2
Turn off the power supply and unplug.
3
Remove the remote control batteries.
■ Recommended Inspection
•
After used over several seasons, the unit will become
dirty and thus decreases the unit’s performance.
Depending on the operation conditions, a dirty unit
may produce odour and dust may pollute
dehumidification system. Therefore, a seasonal
inspection is recommended in addition to regular
cleaning. (Consult an authorized dealer).
Cooling Model
FAN operation
Heat Pump Model
COOL operation with
30°C set temperature
HELPFUL INFORMATION
■ Auto Operation
Press the Auto
Operation Button
AUTO OFF/ON
● Automatic Operation
• If the remote control fails to function or has been
misplaced, press the Auto Operation button to start
the Automatic operation.
• The Automatic operation will be activated
immediately once the Auto operation button is
pressed. However, temperature cannot be adjusted
in this operation.
• The power indicator on the indoor unit will blink until
the operation mode is selected automatically.
• To cancel this operation, press once more.
■ Timer Setting
• When power failure occurs, the timer setting will be
cancelled. Once power is resumed, reset the timer.
■ Thunder and Lightning
• This air conditioner is equipped with a built-in surge
protective device. However, in order to further
protect your air conditioner from being damaged by
abnormally strong lightning activity, you may switch
off the main power supply and unplug from power
socket.
■ Auto Restart Control
• If power is resumed after a power failure, the
operation will restart automatically after 3 - 4
minutes.
• Operation will be restarted automatically under the
previous operation mode and airflow direction when
power is resumed as the operation is not stopped
by the remote control.
• Otherwise, cooling or heating performance will be
reduced and electricity cost is wasted.
■ Outdoor Unit
• Do not block the air outlet vents. Otherwise, it will
lower the cooling or heating performance.
■ Timer and Sleep Mode
• To prevent wastage of electricity, use sleep mode
when sleeping or Timer when going out.
■ Avoid Direct Sunlight
• Keep curtains or drapes closed to avoid direct
sunlight during cooling operation.
TROUBLESHOOTING
■ Normal Operation
Is it okay?
• Air conditioner has been restarted, but does not
operate for 3 minutes.
• A sound like water flowing can be heard.
• It seems that fog is coming out from the air
conditioner.
• The room has a peculiar odour.
• The outdoor unit emits water or steam.
• During Automatic Airflow Volume setting,
indoor fan stops occasionally.
• (For Heat Pump Model only)
Operation stops for about 12 minutes during
heating (The power indicator blinks).
• (For Heat Pump Model only)
During heating operation, indoor fan may
run at on and off conditions.
■ Abnormal Operation
Is it okay?
• The air conditioner does not operate.
• Air conditioner produces loud noise during
operation.
• The air conditioner does not cool or warm
effectively.
• Remote control / display doesn’t work
This is the answer
• This is to protect the air conditioner. Wait until the air
conditioner begins to operate.
• This is the sound of refrigerant flowing inside the air
conditioner.
• Condensation occurs when the airflow from the air
conditioner cools the room.
• This may be a damp smell emitted by the wall,
carpet, furniture or clothing in the room.
• In COOL/DRY operation, moisture in the air
condenses into water on the cool surface of outdoor
unit piping that causes dripping.
• This is to remove the smell emitted by the
surroundings.
• This is to melt the frost which has accumulated on
the outdoor unit (defrosting operating). This will take
no longer than about 12 minutes. Water drips from
the outdoor unit. Wait until this operation ends.
(the power indicator will light up). (Frost will
accumulates on the outdoor unit when the outdoor
temperature is low and humidity is high.)
• This is to prevent undesired cooling effect during
heating operation.
Please check
• Has the circuit breaker been tripped?
• Has the power plug been removed from the wall
outlet?
• Is the timer being used correctly?
• Is the installation work slanted?
• Has the temperature been set incorrectly?
• Are the filters dirty?
• Are the intake or outlet vents of the outdoor unit
obstructed?
• Are all windows and doors closed?
• Batteries empty?
• Batteries correctly inserted (+) and (–)?
■ Call the Dealer Immediately
If the following conditions occur, turn off and unplug the
main power supply, and then call the dealer immediately.
• Abnormal noise is heard during operation.
• Water or foreign material gets into the remote
control by mistake.
• Water leak from the indoor unit.
• Switches or buttons do not operate properly.
• The circuit breaker switches off frequently.
• Power supply cord and plug become unusually
warm.
38
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.