Panasonic CS-A18BTP, CU-A18BBP5, CU-C18BBP5 Service Manual

Page 1
ORDER NO. MAC0208029C8
AIR CONDITIONER
CS-A18BTP CU-A18BBP5 CS-A18BTP CU-C18BBP5
CONTENTS
Page Page
1 SERVICE INFORMATION 3 2 FEATURES 3 SPECIFICATION (HEAT PUMP TYPE ) 4 SPECIFICATION (COOLING ONLY TYPE ) 5 TECHNICAL DRAWING 6 CIRCUIT DIAGRAM 7 OPERATING INSTRUCTION 8 REFRIGERATION CYCLE 9 OPERATION RANGE 10 PIPE LENGTH 11 OPERATIN G CHARACTERIS TIC 12 FAN PERFORMANCE 13 SAFETY DEVICE 14 COMPONE NT SPECIFICA TION 15 CAPACITY AND POWER CONSUMPTION 16 DISCHARG E AND SUCTION PRESSURE 17 POSITION OF THE CENTRE GRAVITY
18 REACHING DISTANCE 39
4
19 SOUND DATA
8
20 TWIN AND TRIPLE 21 WIRING MISTAKE PREVENTI ON
9
10
22 TEST OPERATION AND SELF DIAGNOSIS
12
23 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH 24 GROUP CONTROL
24 26
25 TROUBLE SHOOTING
28
26 EMERGEN CY OPERATIO N
29
27 CONTROL 28 WIRED REMOTE CONTROL INSTALLATION MANUAL
31 32
29 WIRELESS REMOTE CONTROL INSTALLATION MANUAL
33
30 INSTALLATION (INDOOR UNIT) 31 INSTALLATION (OUTDOOR UNIT)
34 35
32 REPLACEMENT PARTS
37
33 HEA TING CAPACITY PERFORMANCE DATA
38
© 2002 Matsushita Industrial Corporation Sdn. Bhd. (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law.
40 42 47 48 52 53 54 59 60 70 75 82
91 101 110
Page 2
34 COOLING CAPACITY PERFORMANCE DATA 111
2
Page 3
1 SERVICE INFORMATION
Caution:
Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
Notice of Address setting for NEW Ceiling / NEW Outdoor Unit.
The new Ceiling / new Outdoor models are possible to have address setting for twin / triple control or group control automatically when main power supply is switched on.
(Manual address setting is also possible by using DSW1 switch on the indoor unit P.C. board.) However,
only possible when proper wiring connection is made and indoor unit must be of original unit
1.1. Example of trouble during test operation
If the below phenomenon is found during test operation, wrong address setting is possible. Therefore, please inspect the address setting.
1. LCD display of the wired remote control is not illuminated although the main power supply switch is ‘on’.
2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoor unit cannot be operated. (But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control OFF/ON button is ‘on’.) (For normal operation, the outdoor unit will only start its operation after 3 to 5 minutes upon pressing the OFF/ON button.)
3. P.C. board had memorized wrong setting information. a. If main power supply is switched on with the wrong connection. b. When changing the connection or combination of units due to re-installation etc.
When changing the system from twin to triple (triple to twin).
• •
When changing the system from group control to normal one to one system.
• •
When making the replacement of units of master and slave etc.
• •
this address setting is
.
1.2. Caution during test operation
Do not touch the remote control button and do not change any wirings for one minute when the main power supply switch is ‘on’. (Because the unit is having automatic address setting during the first one minute.)
1.3. Caution during automatic address setting
When the main power supply switch is ‘on’, the P.C. board will automatically memorize the connecting system. Consequently, when initial power supply is ‘on’, there mustn’t be any interchanging of units even of the same type and same
capacity unit. Therefore, connection of the unit to another system is prohibited.
3
Page 4
2 FEATURES
2.1. New design
2.1.1. Gentle curved styling
The base has gentle curves which express a functional
• •
beauty. It spreads the air quietly over a wide area.
2.2. Such quietness!
2.2.1. Several new mechanism add up to low 36 dB noise (A18BT - High Fan Speed)
1. Delta throat fan
A delta throat (projection) has been attached to the fan outlet to suppress the generation of vortexes. This helps maintain air flow sped even at lower fan speeds and is effective in reducing noise.
3. Adoption of wing-shaped vanes
The vanes of the fan have been changed to
• •
aerodynamicshaped vanes, so that the air flow more smoothly over the vane surfaces and noise is thus suppressed.
Side filters have been adopted in the pipe partitions.
• •
These allow the air intake space to be increased and also further reduce noise.
2.2.2. Automatic swinging louvre
The horizontal air flow angle is a wide 100 degrees
• •
(manual). The louvre can swing automatically (through 70 degrees vertically) using the remote control. This increases the area of comfortable air flow and warms the air even to floor level.
2. Reflux orifice
The orifice at the intake port is equipped with an air flow guide which minimizes the flow disturbances which occur at the orifice and inside the impeller.
This reduces pressure losses inside the casing and also helps reduce noise.
2.2.3. Newly-shaped louvre
The newly-shaped louvre and air outlet effectively distribute
• •
the air flow. During cooling, this stops warm air from collecting near the louvre, and prevents freezing.
4
Page 5
2.3. Easy installation
2.3.1. Easy suspension
A suspension bolt fixing bracket with 4-point support is
• •
attached to the main unit, which increases the space available for installation.
2.3.2. Two installation methods : standard and wall
In addition to the standard (1) ceiling installation, a wall (2)
• •
installation method (using a wall-hanging bracket) is available for cases where the ceiling is too high for the main unit to be suspended.
2.5.2. Maintenance is possible from underneath the unit.
If the bottom panel is detached, the drain pan can then be
• •
removed and installed from underneath the unit, and inspection and servicing of component such as the control panel also becomes easier.
2.6. Auto fan mode (indoor unit)
Auto fan mode is added besides high, medium and low. It
• •
automatically adjusts the fan speed according to the indoor units temperature.
2.4. Piping
2.4.1. 3-direction pipe lead-out
The refrigerant piping can lead out in one of three directions
• •
(right, rear-right and top-right), and the drain pipe direction can be selected from four directions (right, rear-right, left and rear-left).
2.5. Easy maintenance
2.5.1. Long life filter (standard equipment)
In general office environments, cleaning (maintenance) is
• •
not required until after approximately 2,500 hours of operation, thus reducing maintenance work.
For optimum comfort, it is recommended to clean the air
• •
filter every 1-1/2 months.
2.7. Hot start system (heat pump models)
2.8. Automatic changeover function (heat pump models)
The unit automatically switches between cooling and
• •
heating in accordance with operating load in order to maintain a comfortable indoor temperature.
2.9. Greatly improved workability increases system renewal capability
Pipes that are one size larger can also be connected for
• •
renewal.
If renewing the system, existing refrigerant pipes can be
− −
utilized so that only the indoor and outdoor units need to be replaced.
For example, liquid and gas pipes from 10 years ago
− −
can be connected to current pipes with the same size or one size larger. Effective utilization of materials reduces working time and trouble. (Adaptor sockets are not supplied.)
5
Page 6
Additional refrigerant charging unnecessary for 10 m
• •
All models do not require any additional charging of
− −
refrigerant for 10 m of pipe length. This makes installation much easier.
Drain water dripping-prevention structure
• •
The base of the outdoor unit is provided with a single
− −
drain hole in order to prevent drain water from leaking out of the unit. By connecting a drain elbow and a discharge pipe, water leakages can be prevented even when the unit is installed to a wall.
Master unit and slave-units can be set automatically in
− −
twin and triple systems. No address setting is necessary.
Multiple indoor units can be operated simultaneously
− −
with a single remote control. Note that individual operation is not possible.
Separate indoor/outdoor unit power supplies
• •
The power supply can be connected to (1) just the outdoor units, or (2) to both the indoor and outdoor units.
Easy test operation
• •
Test operation can be carried out for both indoor and outdoor units.
Automatic setting initialization function (Remote control
• •
and Indoor unit) In accordance with the indoor and outdoor units connected and the connection methods, conditions such as the connection configuration (twin or triple format) and remote­control functions such as automatic louvre operation and cooling or heating mode are automatically detected and set instantly.
Long pipe design for refrigerant pipes
• •
Maximum piping length of 25m for all models.
− −
2.10. A brand-new control method using the latest in technology
Easier power supply wiring connection
• •
Power supply wiring and other wiring tasks can be carried out more easily.
Twin non-polar wires used to connect indoor and
− −
outdoor units.
Adoption of connection error prevention circuits for drive
− −
wires and signal wires. If a connection error is made, the relay does not operate and current does not flow to the circuit boards.
2.11. Wired Remote Control
The new design includes an easily-visible red pilot lamp.
• •
The power can be turned on and off at a single touch, without opening the cover.
Has a build-in thermistor, allowing indoor temperature
• •
detection in accordance with indoor conditions by switching with main unit thermistor.
Twin non-polar wires make installation work easy. (10 m
• •
cable supplied as accessory.)
Twin and Triple operation
• •
Simultaneous air conditioning of wide spaces and
− −
corners is possible. Indoor units of different horsepowers can even be used in combination.
6
Page 7
2.12. Wireless Remote Control
2.13. Group Control Equipment
New design with compact size. (Operation range within
• •
approximately 8 m.)
Built-in timer with ON/OFF timer setting (within 24 hours)
• •
Wired Wireless
Heat Pump CZ-RD51P CZ-RL51P
Cooling CZ-RD51P CZ-RL01P
NOTE: Both of the above remote control is packed separately from the indoor unit.
7
Page 8
3 SPECIFICATION (HEAT PUMP TYPE )
3.1. CS-A18BTP / CU-A18BBP5
ITEM / MODEL Indoor Unit Outdoor unit
Main Body CS-A18BTP CU-A18BBP5
Remote CZ-RD51P (Wired)
Control CZ-RL51P (Wireless)
Cooling Capacity kW 5.0
BTU/h 17,100
Heating Capacity kW 5.6
BTU/h 19,100 Refrigerant Charge-less m 10 Standard Air Volume for High, m3/min 14 Hi 43 Medium and Low Speed cfm 494 1518 Outside Dimension (H x W x D) mm 210 x 1245 x 700 685 x 800 x 300
inch 8-17/32 x 49-1/64 x 27-9/16 26-31/32 x 31-1/2 x 11-13/16
Net Weight kg 33 56
lbs 73 123
Piping Connection
Compressor Type, Number of Set - Hermetic-1 (Rotary), 1
Fan Type, Number of Set Sirocco fan-4 Propeller fan-1
Air-heat Exchanger Slit-fin type Louvre-fin type Refrigerant Control Cool Capillary tube -
Refrigerant Oil (Charged) litre - M60 (0.67) Refrigerant (Charged) kg - (2.0)
Running Adjustment
Safety Devices Internal protector for compressor, Internal thermostat for fan motor,
Noise Level dB (A) Hi 40 Lo 36 Heating:55 Cooling:54
Refrigerant Gas mm (inch) O.D Ø 12.7 (1/2) Flared Type
Liquid mm (inch) O.D Ø 6.35 (1/4) Flared Type
Drain mm O.D Ø 20 I.D Ø 20 x 1
Starting Method - Direct on-line starting Motor Type - 2-pole single phase induction
motor Input kW - Cool/Heat 2.31/2.30 Rated Output kW - 1.5
Motor Type 4-pole single phase induction motor 4-pole single phase induction
motor Input kW 0.08 0.11 Rated Output kW 0.03 0.045
Heat - Capillary tube
oz (71) Control Switch Wireless or Wired Remote Control ­Room Temperature Thermostat (Main Body) -
Crankcase heater, High and heating pressure switch, Current
transformer
Power level dB Hi 57 Lo 53 Heating:68 Cooling:67
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B. (44.6°F D.B.), 6°C W.B. (42.8°F W.B.)
ELECTRICAL DATA (50Hz)
ITEM / MODEL CS-A18BTP, CU-A18BBP5
Condition by JIS B 8615 Volts V 220 230 240 Phase Single Single Single Power Consumption kW Cool 1.90 1.90 1.90
Heat 1.88 1.88 1.88
Running Current A Cool 8.7 8.5 8.4
Heat 8.6 8.4 8.3 Starting Current A 38 40 42 Power Factor % Cool 99 97 94
Heat 99 97 94 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220, 230, 240V 50Hz
8
Page 9
4 SPECIFICATION (COOLING ONLY TYPE )
4.1. CS-A18BTP / CU-C18BBP5
ITEM / MODEL Indoor Unit Outdoor unit
Main Body CS-A18BTP CU-C18BBP5
Remote CZ-RD51P (Wired)
Control CZ-RL01P (Wireless)
Cooling Capacity kW 5.0
BTU/h 17,100 Refrigerant Charge-less m 10 Standard Air Volume for High, m3/min Hi 17 Me 15 Lo 14 Hi 43 Medium and Low Speed cfm 600 530 494 1518 Outside Dimension (H x W x D) mm 210 x 1,245 x 700 685 x 800 x 300
inch 8-17/32 x 49-1/64 x 27- 9/16 26-31/32 x 31-1/2 x 11-13/16
Net Weight kg 33 52
lbs 73 115
Piping Connection Refrigerant Gas mm (inch) O.D Ø 12.7 (1/2) Flared Type
Liquid mm (inch) O.D Ø 6.35 (1/4) Flared Type
Drain mm O.D Ø 20 I.D Ø 20 x 1
Compressor Type, Number of Set - Hermetic-1 (Rotary), 1
Starting Method - Direct on-line starting Motor Type - 2-pole single phase induction
Input kW - Cool 2.31 Rated Output kW - 1.5
Fan Type, Number of Set Sirocco fan-4 Propeller fan-1
Motor Type 4-pole single phase induction motor 4-pole single phase induction
Input kW 0.08 0.11
Rated Output kW 0.03 0.045 Air-heat Exchanger Slit-fin type Louvre-fin type Refrigerant Control Capillary tube ­Refrigerant Oil (Charged) litre - M60 (0.67) Refrigerant (Charged) kg - (1.6)
oz (56)
Running Adjustment
Safety Devices Internal protector for compressor, Internal thermostat for fan motor,
Noise Level dB (A) Hi 40 Lo 36 Cooling: 54
Control Switch Wireless or Wired Remote Control ­Room Temperature Thermostat (Main Body) -
Crankcase heater, High pressure switch, Current transformer
Power level dB Hi 57 Lo 53 Cooling: 67
motor
motor
1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air temperature of 35°C D.B. (95°F D.B.), 24°C W.B. (75.2°F W.B.)
ELECTRICAL DATA (50Hz)
ITEM / MODEL CS-A18BTP, CU-C18BBP5
Condition by JIS B 8615 Volts V 220 230 240 Phase Single Single Single Power Consumption kW Cool 1.90 1.90 1.90 Running Current A Cool 8.7 8.5 8.4 Starting Current A 38 40 42 Power Factor % Cool 99 97 94 *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor. Panasonic Power source AC, 1~220, 230, 240V, 50Hz
9
Page 10
5 TECHNICAL DRAWING
10
Page 11
11
Page 12
6 CIRCUIT DIAGRAM
1213141516171819202122
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 21
Page 22
Page 23
23
Page 24
7 OPERATING INSTRUCTION
7.1. Wired Remote Control (OPTIONAL PARTS)
NOTES:
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
• •
The illustration above is for explanatory purposes only. The appearance will be different during actual operation.
• •
Do not operate the remote control with wet hands. Otherwise, electric shock or malfunction may occur.
• •
Do not press the remote control buttons with sharp object as this may damage the remote control.
• •
Buttons marked with * are not needed for normal operation. If one of these buttons is pressed by mistake, press the same
• •
button once more to cancel the operation.
When the power resumed after power failure, the unit will restart automatically with all the previous settings preserved by the
• •
memory function. (Auto restart function)
24
Page 25
7.2. Wireless Remote Control (OPTIONAL PARTS)
NOTES:
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
• •
The illustration above is for explanatory purpose only. The appearance will be different during actual operation.
• •
If using the wireless remote control in conjunction with the wired remote control, the settings made from the wireless remote
• •
control will appear on the wired remote control display (except when making timer settings).
Buttons marked with * are not needed for normal operation. If one of these buttons is pressed by mistake, press the same
• •
button once more to cancel the operation.
When the power resumed after power failure, the unit will restart automatically with all previous settings preserved by the
• •
memory function. (Auto restart function)
25
Page 26
8 REFRIGERATION CYCLE
CS-A18BTP/CU-A18BBP5
26
Page 27
CS-A18BTP/CU-C18BBP5
27
Page 28
9 OPERATION RANGE
Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the rated voltage.
Power Supply
MODEL Unit Main Power Applicable Voltage
Phase, Volts Hz Max Min
A18BB 1~220 50 242 198
1~230 50 253 207 1~240 50 264 216
Indoor and Outdoor Temperature
Cooling only type
• •
Model 50Hz CU-C18BBP5
Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)
Max Min Max Min
Cooling 50/60 32/23 21/15 43/- -5/-
Heat pump type
• •
Model 50Hz CU-A18BBP5
Operating Hz Indoor Temp. (D.B./W.B.) (°C) Outdoor Temp. (D.B./W.B.) (°C)
Cooling 50 32/23 21/15 43/- -5/­Heating 50 27/- 16/- 24/18 -10/-
Max Min Max Min
28
Page 29
10 PIPE LENGTH
CORRECTION OF COOLING CAPACITY AND HEATING CAPACITIES
■■■■
Correction of cooling and heating capacities according to the connecting pipe length. The data of cooling capacities (marked on the name plate) are based on 5 meters connecting pipe and horizontal installation. For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
REFRIGERANT ADDITIONAL CHARGE
■■■■
Piping installation by standard piping
1.
At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 10m.
• •
(Refer to the following table) But when the piping length exceeds 10m, additional charge is required according to the following table.
Example: CU-C18BBP5
In case of 11m long pipe (one way), the amount of refrigerant to be replenished is: (11 - 10) x 20 = 20g
29
Page 30
Cooling only type
Model Name Standard piping specification
Liquid piping (dia.mm) Gas piping (dia.mm) Gas charge-less length
(m)
CU-C18BBP5 6.35 12.70 10 20
Additional gas volume
(g/m)
Heat pump type
Model Name Standard piping specification
Liquid piping (dia.mm) Gas piping (dia.mm) Gas charge-less length
CU-A18BBP5 6.35 12.70 10 20
Piping installation by existing piping
2.
(m)
Additional gas volume
(g/m)
The above models change the liquid pipe size of the previous series. It is to use the existing piping by adjusting the refrigerant gas volume.
Please do correct piping installation referring to the above table.
Attention
Please do not decrease the gas piping size. (It causes the breakdown of the compressor).
• •
The equivalent piping length and the cooling and heating capacity change rate are same as the standard piping specification.
• •
30
Page 31
11 OPERATING CHARACTERISTIC
Model Main Power Source Compressor Motor Indoor Unit Fan
Voltage Frequency S.C. R.C. (A) IPT (kW) R.C. IPT R.C. IPT
(v) (Hz) (A) Cool/Heat Cool/Heat (A) (kW) (A) (kW)
HEAT PUMP
MODEL
COOLING
ONLY MODEL
CS-A18BTP 220 50 38 8.0 / 8.0 1.75 / 1.73 0.25 0.05 0.50 0.10 CU-A18BBP5 230 50 40 7.8 / 7.8 1.75 / 1.73 0.25 0.05 0.50 0.10
240 50 42 7.7 / 7.7 1.75 / 1.73 0.25 0.05 0.50 0.10
Model Main Power Source Compressor Motor Indoor Unit Fan
Voltage Frequency S.C. R.C. (A) IPT (kW) R.C. IPT R.C. IPT
(v) (Hz) (A) Cool/Heat Cool/Heat (A) (kW) (A) (kW) CS-A18BTP 220 50 38 8.0 / - 1.75 / - 0.25 0.05 0.50 0.10 CU-C18BBP5 230 50 40 7.8 / - 1.75 / - 0.25 0.05 0.50 0.10
240 50 42 7.7 / - 1.75 / - 0.25 0.05 0.50 0.10
Legend : S.C. = Starting Current, R.C. = Running Current, IPT = Power Consumption
Motor
Motor
Outdoor unit Fan
Motor
Outdoor unit Fan
Motor
31
Page 32
12 FAN PERFORMANCE
CS-A18BTP
ITEM / MODEL Indoor Unit Outdoor Unit
MODE Hi Me Lo Hi Air Volume m3/min 17 15 14 43 Running Current A 0.40 0.35 0.28 0.5 Power Consumption kW 0.08 0.07 0.06 0.11 Fan Speed r/min 1145 995 950 660
CS-A18BTP CU-A18BBP5,
CU-C18BBP5
32
Page 33
13 SAFETY DEVICE
INDOOR UNIT
Indoor unit CS-A18BTP
For Fan Motor Protection, OFF °C 135 Internal Protector (49F) ON °C 85 For Control Protection, Fuse CUT A 3.15
OUTDOOR UNIT
Outdoor Unit Heat pump model 50Hz CU-A18BBP5
For Refrigerant Cycle, OFF MPa ­High Pressure Switch (63H1) ON MPa ­For
Compressor Over Current Protection
Discharge Temp. Compressor °C - Protection, OFF Discharge Temp. Thermistor (Th1) Liquid Compression Protection, Crankcase
Heater Compressor
Protection, Internal Protector
For Fan Motor Protection, OFF °C 135 Internal Protector (49F) ON °C 85 Heating Pressure switch (Heat OFF MPa 2.35 pump only) (Fan speed) (63H2) ON MPa 2.25 Cooling
Control, Heat Exchanger Outlet Temp. Thermistor (Th2)
For Control Protection, Fuse CUT A 6.3
1MPa = 10.2 kgf/cm * Head Thermostat only for CU-A28BBP8 / CU-C28BBP8
2
Heat pump model
Cooling only model
Cooling only 50Hz CU-C18BBP5
model 60Hz
OFF A 15.5
(Heat pump)
OFF A 15.5
(Cooling 50Hz
only) A -
60Hz
RESET - Automatic
Input power W -
OFF °C 50Hz 150
°C 60Hz -
ON °C 50Hz 90
°C 60Hz -
Trip time 50Hz 3-10sec/44A
60Hz -
Control method
-
33
Page 34
14 COMPONENT SPECIFICATION
Compressor
Model Heat pump model 50Hz CU-A18BBP5
Cooling only model 50Hz CU-C18BBP5 Compressor Model 50Hz 2K32C225CUA Compressor Type
No. of Cylinders Revolution r/min 2,900
Piston Diplacement m3/h 7.27 Motor Type Starting Method Direct on-line Starting
Rated Output kW 1.5 Poles 2 Insulation Class E
Oil Type M60
Charge L 0.67
Evaporator
Models CS-A18BTP Tube Material Outer Diameter mm 7.0 Thickness mm 0.27 Row 2 No. of Tubes/Row 12 Fin Material Aluminium Thickness mm 0.105 Fin Pitch NO./inch 18 Fin Surface Z Slit fin Total Face Area m
Fan Type Sirocco Fan
No. of /Unit 4
Fan Motor Starting Method Direct on-line Starting
Rated Output kW 0.030 Poles 4 Phase Single-Phase Insulation Class E
2
ROTARY
1
0.258
Condenser
Models Heat pump model CU-A18BBP5
Cooling only model CU-C18BBP5 Tube Material Copper Tube Outer Diameter mm 9.52 Thickness mm 0.3 Row 2 No. of Tubes/Row 34 Fin Material Aluminium Thickness mm 0.105 Fin Pitch NO./inch 14 Fin Surface AX-Louvre fin Total Face Area m
Fan Type Propeller Fan
No. of /Unit 1
Fan Starting Method Direct on-line Starting Motor Rated Output kW 0.045
Poles 4 Phase Single-Phase Insulation Class E
2
0.61
34
Page 35
15 CAPACITY AND POWER CONSUMP TION
15.1. HEATING PERFORMANCE
Model Heating capacities are based on conditions below.
CS-A18BTP Heating capacity
5.0 kW
Inlet Air Outdoor Temperature (°C W.B.)
External Static Pressure
(Pa) Air Volume (m
14 20 3.86 1.39 4.62 1.60 5.60 1.88 6.72 2.22
3
/min)
1 phase, 50Hz, 220V Indoor temperature 20°C D.B. Outdoor temperature 7°CD.B.6°CW.B. Standard air volume 14m
Entering Air Dry
Bulb (°C)
15 4.09 1.32 4.90 1.50 5.88 1.79 6.83 2.11
25 3.64 1.47 4.37 1.69 5.32 1.97 6.44 2.31
H.C. IPT H.C. IPT H.C. IPT H.C. IPT
3
/min
-6°C 0°C 6°C 12°C
Inlet Air Outdoor Temperature (°C W.B.)
External Static Pressure
(Pa) Air Volume (m
3
/min)
14 20 3.86 1.41 4.62 1.62 5.60 1.90 6.72 2.24
Entering Air Dry
Bulb (°C)
15 4.09 1.33 4.90 1.52 5.88 1.81 6.83 2.13
25 3.64 1.48 4.37 1.71 5.32 2.00 6.44 2.34
-6 6 -6 6
H.C. IPT H.C. IPT H.C. IPT H.C. IPT
H.C. = Heating Capacity IPT = Power Consumption
35
Page 36
15.2. COOLING PERFORMANCE
Model Cooling capacities are based on conditions below.
CS-A18BTP Cooling capacity
5.0 kW
Entering Temperature Air Entering Condenser (°C D.B.)
Air 25 30 35 40 43
Temperature TC TC TC TC TC
D.B. W.B. kW kW kW kW kW
23 19 5.41 5.15 4.88 4.56 4.24
25 19 5.46 5.22 4.94 4.60 4.30
27 19 5.51 5.30 5.00 4.65 4.35
29 19 5.62 5.39 5.07 4.71 4.41
32 19 5.69 5.45 5.12 4.75 4.46
1 phase, 50Hz, 240V Indoor temperature 27°C D.B. 19 °CW.B. Outdoor temperature 35°C D.B. Standard air volume 14m
17 5.13 4.90 4.60 4.30 4.00
22 5.84 5.56 5.27 4.97 4.66 17 5.15 4.93 4.65 4.34 4.04
22 5.92 5.64 5.35 5.03 4.74 17 5.18 4.96 4.70 4.37 4.09
22 5.99 5.72 5.43 5.09 4.82 17 5.25 5.02 4.77 4.43 4.10
22 6.03 5.77 5.44 5.13 4.85 17 5.29 5.07 4.82 4.46 4.11
22 6.05 5.80 5.45 5.15 4.87
3
/min
Entering Temperature Air Entering Condenser (°C D.B.)
Air 25 30 35 40 43
Temperature IPT IPT IPT IPT IPT
D.B. W.B. kW kW kW kW kW
17 1.52 1.66 1.79 1.93 2.01
23 19 1.57 1.71 1.85 1.95 2.07
22 1.60 1.74 1.88 1.99 2.11 17 1.54 1.68 1.81 1.95 2.03
25 19 1.61 1.75 1.90 2.01 2.13
22 1.65 1.78 1.94 2.04 2.16 17 1.56 1.70 1.82 1.96 2.05
27 19 1.66 1.79 1.95 2.07 2.18
22 1.70 1.83 1.99 2.09 2.21 17 1.61 1.74 1.86 1.98 2.08
29 19 1.72 1.85 1.99 2.08 2.19
22 1.80 1.93 2.06 2.15 2.23 17 1.65 1.77 1.89 1.99 2.09
32 19 1.76 1.89 2.02 2.10 2.20
22 1.87 1.99 2.11 2.18 2.25
TC = Total Cooling Capacity IPT = Power Consumption
36
Page 37
16 DISCHARGE AND SUCTION PRESSURE
37
Page 38
17 POSITION OF THE CENTRE GRAVITY
MODEL NAME OUTSIDE DIMENSIONS NET WEIGHT CENTRE OF GRAVITY
WIDTH (mm) DEPTH (mm) HEIGHT (mm) kg X (mm) Y (mm) Z (mm) CU-A18BBP5 800 300 685 56 560 160 360 CU-C18BBP5 800 300 685 52 560 160 360
38
Page 39
18 REACHING DISTANCE
39
Page 40
19 SOUND DATA
40
Page 41
41
Page 42
20 TWIN AND TRIPLE
20.1. Twin and Triple Operation
Simultaneous air conditioning of wide spaces and corners is
• •
possible. Indoor units with different horsepowers can even be used in combination.
Master unit and slave-units can be set automatically in twin
• •
and triple systems. No address setting is necessary.
Multiple indoor units can be operated simultaneously with a
• •
single remote control unit. Note that individual operation is not possible.
20.1.1. Twin and triple operation setting
The master unit and slave units are set automatically when
• •
the power is turned on. At this time, the indoor unit which is connected to the remote control unit becomes the master unit. (If automatic setting is not possible, carry out the settings manually.)
No distinction is made between master unit and slave units
• •
(slave unit 1 and slave unit 2) at the indoor unit or remote control.
Install the remote control to the master unit. (It cannot be
• •
connected to slave units.) If indoor unit models with louvres and models without louvres have been connected together, use an indoor unit
with louvres as the master unit.
The remote control termostat can also be set.
• •
Optional circuit boards can only be installed to the master
• •
unit.
Setting the master unit and slave units can also be carried
• •
out manually by using DIP switches. However, manual settings will always take priority. If you have made manual settings but would like to return to using automatic settings, set all slave unit DIP switches (refer to the table below) to the OFF position, and then press the ADDRESS RESET button on the outdoor unit (SW3 on the outdoor unit printed circuit board). (Do not mix manual settings and automatic settings.)
42
Page 43
20.1.2. Automatic address setting for twin and triple systems
Procedure: Turn on the power supply for the indoor
and outdoor units.
Operation: Automatic address setting will start 10 to
30 seconds after the power supply is turned on, and will be completed after about 1 minute.
If the power supplies for the indoor unit and outdoor unit cannot be turned on at the same time, turn on the power supply for the outdoor unit, the indoor unit which is connected to the remote control, and then the other indoor units in that order.
If the order of turning on the power supply is incorrect, the master unit setting may overlap. In such a case, turn on the power supplies for all units in the correct order as given above, or carry out a twin/triple automatic address reset (press dip switch 3 on the outdoor unit continuously for 4 seconds or longer).
The indoor unit which is connected to the remote control will
• •
have priority for becoming the master unit.
The master unit thermostat will be used as the indoor
• •
temperature thermostat. If the master unit thermostat is turned on, the slave unit thermostats cannot be adjusted even if they happen to be on.
If address setting using the DIP switches is carried out after
• •
automatic address setting has been carried out, use DIP switch No. 3 (SW3) on the outdoor unit to carry out automatic address resetting.
If you would like to designate a particular indoor unit as the
• •
master unit because no master unit has been set, use the DIP switches on the slave units to make setting.
If automatic address setting is carried out once and then theslave unit address are set, the address will then be stored inside the EEPROM. Thus it is not necessary to repeat automatic address setting if the power is turned off and back on again.
20.1.3. DIP switch settings for twin/triple slave unit addresses
Procedure: Turn off the power supply, and then set
DIP switch 1-8 to ON. The unit will become slave unit 1. (Set DIP switches 1-1 and 1-8 both to ON. The unit will become slave unit 2.)
Turn on the power supply.
Operation: The unit will operate as slave unit 1.
Automatic address setting is not carried out at this time.
If the setting is made while the power is still turned on, it is easier to mis-combine the setting with group settings. So, the setting should be made while the power is turned off.
Only slave unit addresses can be set in this way. Master
• •
unit setting is not possible.
If you make the DIP switch settings after the power has
• •
been turned on, carry out twin/triple automatic address resetting.
Be sure to set DIP switch 1-8 to ON when setting twin/triple
• •
addresses. If DIP switch 1-1 is set to ON without setting 1­8 to ON, group addresses will be set instead, and the remote control open circuit error code (F26) will be displayed.
20.1.4. Automatic address resetting for twin/triple systems
Function:
Procedure: Press the ADDRESS RESET button SW3
Operations: The outdoor unit will reset the addresses
If an indoor unit has had its address set by the DIP switch (DIP switch 1-8 is ON), or if the remote control unit is connected to one of the indoor unit, then the addresses for those indoor units cannot be reset.
This reset the current twin/triple
• •
addresses which have been set automatically, and result in the reoccurance of automatic twin/triple address settings.
(push button switch) on the outdoor unit circuit board continuously until LEDs 2 to 8 on the outdoor unit circuit board are all illuminated (takes approximately 3.5 seconds).
for the indoor units which it is connected to, and will send an instruction to carry out automatic address setting again. If the indoor unit DIP switch have not been manually set for twin/triple address setting, the indoor units receive this command and clear their existing settings and carry out automatic address setting.
43
Page 44
The indoor units will not run for approximately 1 minute
• •
while automatic twin/triple address resetting is being carried
Do not turn off the power supply for at least 1 minute after
• •
automatic twin/triple address resetting has been carried out.
out.
20.2. Piping connections
The following table shows the pipe diameters for a twin-type system.
• •
Outdoor unit main pipe diameter (mm) Indoor unit combinations
3HP Indoor unit capacity (HP) 1.5 1.5
Liquid side: ø 9.52 Branch pipe
Gas side: ø 15.88 Gas side ø 12.7 ø 12.7
4HP Indoor unit capacity (HP) 2.0 2.0 1.5 2.5
Liquid side: ø 9.52 Branch pipe
Gas side: ø 19.05 Gas side ø 12.7 ø 12.7 ø 12.7 ø 15.88
5HP Indoor unit capacity (HP) 2.5 2.5 2.0 3.0
Liquid side: ø 9.52 Branch pipe
Gas side: ø 19.05 Gas side ø 15.88 ø 15.88 ø 12.7 ø 15.88
6HP Indoor unit capacity (HP) 3.0 3.0 2.0 4.0
Liquid side: ø 9.52 Branch pipe
Gas side: ø 19.05 Gas side ø 15.88 ø 15.88 ø 12.7 ø 19.05
The following table shows the pipe diameters for a triple-type system.
• •
Outdoor unit main pipe diameter (mm) Indoor unit combinations
6HP Indoor unit capacity (HP) 2.0 2.0 2.0 1.5 1.5 3.0
Liquid side: ø 9.52 Branch pipe
Gas side: ø 19.05 Gas side ø 12.7 ø 12.7 ø 12.7 ø 12.7 ø 12.7 ø 15.88
diameter
diameter
diameter
diameter
diameter
Liquid side ø 6.35 ø 6.35
Liquid side ø 6.35 ø 6.35 ø 6.35 ø 6.35
Liquid side ø 6.35 ø 6.35 ø 6.35 ø 9.52
Liquid side ø 9.52 ø 9.52 ø 6.35 ø 9.52
Liquid side ø 6.35 ø 6.35 ø 6.35 ø 6.35 ø 6.35 ø 9.52
The following table shows the equivalent pipe lengths and height differences for twin- and triple-type systems.
• •
Equivalent length L + la + lb + lc Within 50 m
Branch pipe diameter la, lb, (lc) Within 15 m
Branch pipe difference la - lb, lb - (lc), la - (lc) Within 10 m
Height difference H1 Within 30 m Height difference between indoor units H2 Within 1 m
Note:
1. Use the main pipe to gain any rise or fall required for the pipes.
2. The number of bends should be 8 or less in a single system (L + la, L + lb, L + lc), and 15 or less overall.
3. Branch pipes should be position horizontally.
The branch pipe shoud be horizontal to or perpendicular to the indoor unit.
• •
44
Page 45
20.3. Refrigerant charging
For twin and triple-type systems
• •
The pipe length is the total of the branch pipe (L) and the junction pipes (la lb lc in order from the thickest diameter). At the point where the pipe length exceeds 30 m, determine the amount of refrigerant for the remaining liquid-side pipe diameters and pipe lengths from the following table in order to charge the system.
45
Page 46
20.4. Wiring
46
Page 47
21 WIRING MISTAKE PREVENTION
Improved quality of installation work through adoption of an “Connection error prevention” circuit which prevents wiring mistakes
Connection errors with the control wires and the power supply wires will not only contribute to burning-out of the control circuit board, but can also cause large-scale working losses and affect reliability. If a circuit board with a “Connection error prevention” circuit is used, the relay will not operate if the wires have been connected incorrectly, so that current will not flow to the control circuit board. This is designed principally to conpensate human error during installation.
Prevention of connection errors
These units are equipped with connection error prevention circuits. If the units do not operate, it is possible that the connection error prevention circuits have been operated. In such cases, check that the power supply wires (connected to terminals 1 the control wires (connected to terminals 3 correctly. Normal operation should then commence.
Do not short the remote control wires to each other. (The protection circuit will be activated and the units will not operate.) Once
• •
the cause of the short is eliminated, normal operation will then be possible.
NOTE:
Wait one minute after turning on the indoor unit power supply before operating the remote control.
• •
If nothing at all appea rs in the remote control LCD, check the power supply for the indoor unit.
• •
Refer to TROUBLESHOOTINGchapter.
and 4 ) are connected correctly. If they are connected incorrectly, connect them
and 2 and
NOTE:
Do not allow any of the following connection, as such connection may damage the printed circuit board.
Do not connect anything except a relay to the timer input or fan speed output (connector CNT1 on printed circuit board).
• •
Do not connect U-NET transmission wires to terminals 3 and 4 of the indoor and outdoor units. (*1)
• •
Do not connect U-NET transmission wires to termin als A and B of the remote control.
• •
(1*) U-NET transmission wires are the communication wires used for the central control.
47
Page 48
22 TEST OPERATIO N AND SELF DIAGNOSIS
22.1. Test operation
Always use a properly-insulated tool to operate the switch
• •
on the circuit board. (Do not use your finger or any metallic object).
Never turn on the power supply until all installation work has
• •
been completed.
Turn on the circuit breaker before test operation extends
• •
past 12 hours. (The crankcase heater will be energized, which will warm the compressor and prevent liquid compression.)
For three-phase models, check that the phase is not
• •
reversed. (If the phase is reversed, the LED on the printed circuit board will flash.)
Check that the voltage is 198 V or higher when starting the
• •
unit. (The unit will not operate if the voltage is less than 198V.)
Carry out test operation for 5 minutes or more, using the
• •
remote control or the switch on the outdoor unit printed circuit board.
Always carry out cooling operation first during test
• •
operation, even during the warm season. (If heating is carried out first, problems with operation of the compressor will result.)
22.2. Test operation from the outdoor unit
22.3. Test operation using the wired remote control
1. Check that “COOL” is displayed on the operation mode
display, and then press the OFF/ON button to start test operation.
2. Within 1 minute of pressing the OFF/ON button, press the
TEST RUN button.
3. The pipe temperature (gas pipe) will then be displayed in
the temperature setting display of the remote control.
During outdoor unit emergency operation or test operation, the LEDs on the printed circuit board will flash.
To cancel test operation, press the TEST RUN button once more while test operation is being carried out. (Test operation will stop automatically after 30 minutes have passed.)
During group control, the number appearing in the timer
• •
display will change each time the air conditioner No. button is pressed, and the pipe temperature for the indoor unit corresponding to the number displayed will appear in the temperature setting display.
4. Check that the temperature in the pipe temperature display
starts dropping after operation has been continuing for some time.
48
Page 49
22.4. Test operation using the wireless remote control
<Air conditioner No.>
The air conditioner No. 01appears during normal
− −
installation and use. When using group control, a different number may appear. The air conditioner No. can be displayed by pressing the air conditioner No. button.
1. Within 1 minute of pressing the OFF/ON button, press to
cooling operation and then press the TEST RUN button.
If more than 1 minute passes, test operation cannot be
• •
started. In this case, press the OFF/ON button once more to repeat the operation.
Use the OPERATION button to change the operation.
• •
The current operation mode will appear in the operation mode display.
2. When test operation starts, “TEST RUN” will appear in the
timer display of the LCD, and operation will be carried out in accordance with the operation mode display (COOL or HEAT) appearing at that time. However, the number in the temperature setting display will not change.
(Cancelling test operation)
Press the OFF/ON button, the TEMP (UP/DOWN) button,
• •
the OPERATION button, the FAN SPEED button or the TEST RUN button to cancel test operation.
22.5. Self-diagnosis function
The wired remote control display and the self-diagnosis
• •
LEDs (red) on the outdoor unit printed circuit board indicate where the abnormality has occurred.
Recalling the error display.
• •
When an abnormality occurs at this unit, CHECK” flashes in the display.
Press the CHECK button while the display is flashing.
The timer display will change and an error code from F15 to F49 will appear in place of the time. (The temperature setting display will also change to show the air conditioner No.)
Press the TIMER SELECT/SET button while the error is displayed.
The F15 - F49 display will change to the detail display.
After checking the error display and the detail display, refer
• •
to the self-diagnosis error code table on the following page and check the location of the problem.
If the problem is repaired and operation returns to normal,
• •
the CHECK display on the remote control will be eliminated, but the self-diagnosis LED will remain illuminated until the operation starts again.
49
Page 50
How to display the past error message
If the CHECKdisplay on the wired remote control is not flashing, press the CHECK button continuously for 5 seconds or more to display the problem details for the last problem or the problem before that. You can then switch between the displays for the previous problem and the problem before that by pressing the TIMER FORWARD or BACK buttons. (Last problem display: 1F15 - 1F49 Second-last problem display: 2F15 - 2F49)
Press the CHECK button once more to return to the normal display.
An error code from 1F15 to 1F49 will be displayed. (The temperature setting display will also change to show the air conditioner No.)
If the TIMER SELECT/SET button is pressed while the error code from 1F15 to 1F49 is being displayed, the display screen will change to show the details of the last problem display. (If 2F15 to 2F49 is being displayed, the details of the second­last problem display will appear.)
50
Page 51
51
Page 52
23 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH
23.1. Energy save setting
Upper and lower limit can be set for the setting temperature
• •
during cooling and heating operation. (The factory shipment setting has an upper limit of 31°C and a lower limit of 16°C.)
1. While operation is stopped, press the TEMP UP and TEMP DOWN buttons simultaneously.
23.2. Switching to the remote control thermistor
The temperature detection thermistor used for detecting the
• •
indoor temperature can be switched between the thermistor at the indoor unit and the thermistor at the remote control unit. (The factory shipment setting is at the indoor unit side.)
2. To set an upper limit Press the OPERATION button until HEAT is displayed.
Press the TEMP UP or TEMP DOWN button to set the temperature.
Press the SET button to complete the upper limit setting.
Example:
If the heating display is set to 28°C, setting the temperature to higher than 28°C will not be possible. * Upper and lower limits cannot be set at the same time.
3. To set a lower limit Press the OPERATION button until COOL is displayed.
Press the TEMP UP or TEMP DOWN button to set the temperature.
Press the SET button to complete the lower limit setting.
Example:
If the cooling display is set to 22°C, setting the temperature to lower than 22°C will not be possible. * Press the CANCEL button to cancel the setting.
1. While operation is stopped, press and hold the TEST RUN button, TEMP UP button and TEMP DOWN button simultaneously.
Press the FORWARD or BACK timer button to change the temperature detection setting.
2. Press the SET button to complete the setting. To change the setting, repeat the above operation.
52
Page 53
24 GROUP CONTROL
Setting group for 1 remote control unit
When using a remote control thermo stat, the thermostat
• •
setting is used for all indoor units in the group.
During group control, up to a maximum of 16 indoor units
• •
can be connected. (Do not mix heat pump units and cooling-only units.)
Do not mix manual settings and automatic settings. (manual
• •
settings take priority.)
The master unit and slave units can be centralized
• •
controlled during group control.
Automatic setting for group control
If the power supplies for indoor units which are connected
• •
are turned on simultaneously, the indoor unit numbers will
be determined automatically after approximately 1 minute. (DIP switch settings are not necessary.)
NOTE:
Correct wiring connections are a basic requirement for
• •
automatic setting. If the wires are connected incorrectly when the power is turned on, the settings will not be made correctly and operation will not be possible.
When address numbers are set automatically, you will not
• •
know which address number corresponds to which indoor unit.
Do not turn off the power supply for at least 1 minute during
• •
automatic address setting, otherwise the settings will not be made correctly.
Automatic address resetting for group control
Set the DIP switches 1 to 4 to OFF and stop the operation. Then press the AIR SWING AUTO”“OPERATIONand Air conditioner No.buttons simultaneously. Then addresses will be momentarily reset, and then automatic address setting will be carried out once more.
Note with regard to the Mini-cassette
When carrying out group control of a Mini-cassette system using a single wireless remote control, be sure to disconnect the connectors for all receptor circuit boards except the one for indoor unit. No. 1, before turning on the power. (The same action as for the slave units in twin and triple systems is necessary.)
53
Page 54
25 TROUBLESHOOTING
If test operation does not proceed correctly
Carry out test operation after approximately 12 hours have passed since the power was turned on (crankcase heater is energized). If operation is started by using the remote control within 1 minute of turning on the power, the outdoor unit settings will not be made correctly and correct operation will not be possible.
If the following symptoms occur after turning on the power, check the wiring connections once more.
For standard installation
• •
(System example)
Symptom:
Remote control unit... Display of No power supply
NOTE:
Indoor unit... LED1 on printed circuit board stays illuminated Outdoor unit... LED1 on printed circuit board stays illuminated
(When remote control display shows Power supply”)
(When remote control display shows No power supply”)
1. The main power is turned on while the indoor-outdoor transmission wires are not connected (open circuit at section A)
Symptom:
Remote control unit... CHECK” flashes
NOTE:
Indoor unit... LED2 on printed circuit board flashes Outdoor unit... LED3 and LED7 on printed circuit board flash
2. The main power is turned on while the indoor-outdoor power supply wires are not connected (open circuit at section B)
Symptom:
Remote control unit... Display of No power supply
NOTE:
Indoor unit... No display Outdoor unit... LED3 and LED7 on printed circuit board flash
3. The main power is turned on while the remote control unit connection cord is not connected (open circuit at section C)
Remedy
1. Turn off the main power.
2. Connect the disconnected wire correctly.
3. Turn on the main power.
4. After 1 minute, start the operation using the remote control. (Indoor unit operation will start according to the remote control setting.) (Outdoor unit operation will start after 3-5 minutes.)
NOTE:
The CHECKdisplay on the remote control and the flashing of LEDs on the printed circuit boards will not occur immediately. They will appear 3-6 minutes after the main power is turned on.
54
Page 55
1. The main power is turned on while the transmission wires between the indoor unit(s) are not connected (open circuit at section A)
Symptom:
Nothing abnormal appears on the remote contro l display. If operation is started in this condition, the combination of the 50BB outdoor unit and the 14BB4 indoor unit (master unit) will result in abnormal operation.
If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop.
Remote control... CHECKflashes
− −
Indoor unit (master)... The LEDs on the printed
− −
circuit board flash and operation stops
Indoor unit (slave)... LED1 on the printed circuit
− −
board illuminates and the unit does not operate at all
Outdoor unit... The LEDs on the printed circuit board
− −
flash and operation stops
2. The main power is turned on while the power supply wires between the indoor unit(s) are not connected (open circuit at section B)
Symptom:
Same as above. If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop.
Remote control... CHECKflashes
− −
Indoor unit (master)... The LEDs on the printed
− −
circuit board flash
Indoor unit (slave)... The LEDs on the printed circuit
− −
board do not illuminate and the unit does not operate at all
Outdoor unit... The LEDs on the printed circuit board
− −
flash and operation stops
3. The main power is turned on while the remote control
connection cord is not connected (open circuit at section C)
Symptom:
Remote control unit.. . Display of No power supply
− −
Indoor unit (master)... LED1 on the printed circuit
− −
board stays illuminated and the unit does not operate
Indoor unit (slave)... LED1 on the printed circuit
− −
board stays illuminated and the unit does not operate
Outdoor unit... LED1 on the printed circuit board
− −
stays illuminated and the unit does not operate
Remedy
1. Turn off the main power.
2. Connect the disconnected wires correctly.
3. Turn on the main power.
4. After 1 minute, start the operation using the remote control. (Indoor unitsoperation will start according to the remote control setting.) (Outdoor unit operation will start after 3-5 minutes.)
If slave units do not operate even after the wiring has been corrected (automatic addressing is not possible)
1. Check that DIP switches 1 to 4 and DIP switch 8 are all set to OFF, and then stop operation.
2. Press the ADDRESS RESET button (SW3) at the outdoor unit for approximately 4 seconds (The self-diagnosis LEDs 2 to 8 will illuminate in order, and the system is reset once they are all illuminated.)
The above procedure cannot be used to carry out automatic address resetting during group control.
55
Page 56
1. The main power is turned on while the transmission wires between the indoor unit and the outdoor unit are not connected (open circuit at section A)
Symptom:
Operation of indoor unit No. 1 and indoor unit No. 3 is possible. However, CHECKflashes in the remote control display for 3-5 minutes after the main power is turned on.
Remote control... CHECKflashes
− −
Indoor unit No. 2... LED2 on the printed circuit board
− −
flashes (both master and slave units)
Outdoor unit No. 2... LED3 and LED7 on the printed
− −
circuit board flash
2. The main power is turned on while the power supply wires between the indoor units are not connected (open circuit at section B)
Symptom:
Operation of indoor unit No. 1 and indoor unit No. 3 is possible However, if operation is then started in this condition, the combination of the 28BB outdoor unit and the 14BT indoor unit (master unit) will result in abnormal operation of indoor unit No. 2.
If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop
Remote control... CHECKflashes (indoor unit No.
− −
2 abnormality)
Indoor unit No. 2... LED2 on the printed circuit board
− −
flashes (both master and slave units)
Outdoor unit No. 2... The LEDs on the printed circuit
− −
board flash
3. The main power is turned on while the remote control connection cord is not connected (open circuit at section C)
Symptom:
Nothing abnormal appears on the remote contro l display, and operation of indoor unit. No. 1 and indoor
unit No. 2 is possible. However, indoor unit No. 3 cannot be operated.
Remedy
• •
1. Turn off the main power.
2. Connect the disconnected wires correctly.
3. Turn on the main power.
4. After 1 minute, start the operation using the remote control. (Indoor unitsoperation will start according to the remote control setting.) (Outdoor unitsoperation will start after 3-5 minutes.)
If slave units do not operate even after the wiring has been corrected (automatic addressing is not possible)
1. Check that DIP switches 1 to 4 and DIP switch 8 are all set to OFF, and then stop operation.
2. Press the “AIRSWING AUTO”, “OPERATION” and “A/C No.buttons simultaneously. The addresses will be momentarily reset, and then automatic address setting will be carried out once more.
The above procedure cannot be used to carry out automatic address resetting of twin/triple control.
(Note on automatic address setting)
The printed circuit boards automatically store the connected system configuration when power is supplied. As a result, once the power has been turned on for these printed circuit boards, the units can not be changed about within the system, even if the units are of the same model and have same capacity.
56
Page 57
1. Automatic address setting (don’t need to set dip-switch) If the wiring is connected properly as above example, the address is set automatically by the main power supply. An indoor unit with remote control will be set as the master. If the power source is installed to indoor units and outdoor units separately, turn on the switch by following the procedure: outdoor unit, then indoor unit with control, and finally other indoor units.
When the slave units do not operate (when address cannot be set)
Reset the address by following the procedure: a. After making sure that dip-switches No. 1 to 4 and No.
8 are OFF, stop the operation.
b. Push address reset button (SW3) on the outdoor unit
PC board for 4 seconds. Self-diagnosis LED No. 2 to 8 will start blinking in order. And when all 7 pieces of LEDs (No. 2 ~ 8) are illuminated, the address for the slave unit has been reset.
Important: The address for the group control cannot be
reset, using the above mentioned procedure.
2. Manual address setting (by dip-switch DSW1) When setting the address manually, set the dip-switch of the PC board of the indoor unit as follows:
1. Automatic address setting (don’t need to set dip-switch) If the wiring is connected properly as above example, the AC numbers are set automatically by the main power supply. An indoor unit with remote control will be set as the master. If the power source is installed to indoor units and outdoor units separately, turn on the switch by following the
procedure: outdoor unit, then indoor unit with control, and finally other indoor units. The AC number will be set at random.
When the slave units do not operate (when address cannot be set)
57
Page 58
Reset the address by following the procedure: a. Make sure that dip-switches No. 1 to 4 and No. 8 are
OFF, stop the operation.
b. Simultaneously, push buttons “AIR SWING AUTO”,
OPERATIONand A/C No.. The address will be reset and new address will be set.
Important: The address for the Twin/Triple control cannot
be reset, using the above mentioned procedure.
2. Manual address setting (by dip-switch DSW1) When setting the address manually, set the dip-switch of the PC board of the indoor unit as follows:
Procedures of deleting memory for twin/triple control system
1. Switch off the main power supply.
2. Set the No. 8 pin of dip switch (DSW1) at the indoor unit’s P.C. board to ONposition.
3. Switch on the main power supply for a minute and then turn it off.
4. Set the No. 8 pin of dip switch (DSW1) to “OFF” position.
Procedures of deleting memory for group control system
1. Switch off the main power supply.
2. Set the No. 1 until No. 4 pin of dip switch (DSW1) at the indoor units P.C. board to ONposition. (Make sure No. 8 pin of dip switch (DSW1) is at OFF position)
3. Switch on the main power supply for a minute and then turn it off.
4. Set the No. 1 pin until No. 4 pin of dip switch (DSW1) to OFFposition.
(Important notice)
Above procedures are meant for deleting memory on indoor units P.C. board. And it is not for Address reset.
3. Manual address setting (by dip-switch DSW1) When setting the address manually, set the dip-switch of the PC board in the indoor unit as follows:
Indoor unit P.C. board layout
Below drawing shows the location of dip switch 1 (DSW1) on the indoor unit P.C. board.
Dip switch 1 (DSW1). [to be used for manual setting]
58
Page 59
26 EMERGENCY OPERATIO N
Emergency operation
Emergency operation of outdoor unit
• •
Emergency operation can be carried out by setting the DSW1 switch on the printed circuit board of the outdoor unit to the EMERGENCY position. However, emergency operation is only carried out when an abnormality is detected by the indoor/outdoor temperature thermistors. The resistance values of each thermistor are measured as shown in the table below to determine if there is an abnormality.
Thermistor resistance table
Temperature Resistance value (kΩ)±5%
Room temperature
thermistor
-20°C 205.8 197.8
-10°C 114.6 111.9
-5°C 87.3 85.4 0°C 67.0 65.8 5°C 51.8 51.0
10°C 40.4 39.9 15°C 31.7 30.7 20°C 25.1 25.0 25°C 20.0 20.0 30°C 16.1 16.0 40°C 10.4 10.6 50°C 6.9 7.1 60°C 4.7 4.9 70°C ---- 3.5 80°C ---- 2.5 90°C ---- 1.8
100°C ---- 1.4
Pipe temperature
thermistor
The pipe temperature thermistor resistance value are the same for the indoor and outdoor units.
<When a thermistor abnormality is judged to have occurred>
Set only the thermistor which shows an abnormality
− −
to the condition as shown in the table below to carry out emergency operation.
Thermistor Cooling mode Heating mode
Indoor unit Room temperature Fixed at 25°C
Pipe temperature Shorted Open
Thermistor Cooling mode Heating mode
Outdoor unit Discharge temperature Open Shorted
Heat exchanger outlet
temperature
Refer to the circuit diagram for the connection
− −
Shorted Open
locations for each thermistor.
If there is an abnormality in the room temperature
− −
thermistor, the temperature will be fixed at 25°C regardless of the remote control display.
NOTE:
Any abnormalities detected by the temperature
− −
thermistors are ignored during emergency operation, therefore, long-term operation in this mode should be avoided.
After emergency mode operation has been
− −
completed and normal operation is to be resumed, turn off the power supplies for the indoor and outdoor units and set the DSW1 switch to NORMAL position.
Self-diagnosis LEDs 4 to 6 will flash during
− −
emergency operation.
59
Page 60
27 CONTROL
Description of basic Functions
27.1. Cooling mode operation time chart
(*1) Outdoor unit fan start control during cooling
At the start of cooling mode and drying mode operation, the outdoor unit heat exchanger outlet temperature is detected in order to set the fan speed. Operation is carried out at the fan speed detected for 30 seconds.
After 30 seconds, the heat exchanger outlet temperature is detected and the outdoor unit fan speed is changed automatically.
(*2) Cooling low outdoor temperature protection
When the outlet temperature of the heat exchanger drops to less than 12°C for a continuous period of 10 minutes, the outdoor unit stops. This is cancelled after 3 minutes (re-start prevention)
Remote control displays and indoor unit operation continue during this time.
• •
The 10 minutes countdown is cleared if the compressor stops or if the temperature at the outdoor unit outlet rises to 13.5°Cor
• •
higher.
60
Page 61
27.2. Freezing prevention control
1. Operation During cooling mode operation, after 9 minutes have passed since the compressor turned on, the outdoor unit will stop its operation when the temperature detected by the indoor unit pipe temperature sensor is 2°C or lower. The indoor unit continues operating at the fan speed set by the remote control. (The remote control display does not change.)
2. Cancelling This control is cancelled when the temperature detected by the indoor unit pipe temperature sensor is 15°C or higher, however 3 minutes waiting of prevention control is necessary. (The 9 minutes countdown is cleared while the compressor is stopped.)
(The above illustration only shows the operation stops due to freezing prevention control of the indoor pipe temperature sensor.)
27.3. Heating mode operation time chart (Heat pump type)
61
Page 62
(*2) Outdoor unit fan control during heating mode operation
When the compr essor is on during heating mode operation (except during defrosting and when the liquid bypass valve is on), the outdoor unit fan is controlled by means of input (CN2) indicating whether the contact of the heating pressure switch on the outdoor unit circuit board is open or closed. (At the start of heating mode operation, the fan operates at HI speed.)
27.4. Hot starting
1. When heating mode operation starts a. Start
Hot start control commences when heating mode operation starts.
b. Operation
PREHEATappears on the remote control display. (Other displays remain unchanged.) The indoor unit fan stops. In addition, during hot starting, the louvre stays at the horizontal position (angle 0°).
c. Cancelling
Hot starting will be cancelled when the compressor is turned on or the indoor unit pipe temperature sensor is 18°C or higher or after 1 minute of operation.
After cancellation, the PREHEATdisplay on the remote control disappears and the louvre operation returns to the previous setting.
(However, for 2 minutes after cancellation, the indoor unit fan operates at LOW speed, and then returns to the previous setting.)
<When hot start operation is cancelled by temperature>
62
Page 63
<When hot start operation is cancelled by time>
2. When defrosting is completed a. Start
Hot start control commences when defrosting is completed.
b. Operation
PREHEATappears on the remote control display. (Other displays remain unchanged) The indoor unit fan stops. In addition, during hot starting, the louvre stays at the horizontal position (angle 0°C).
c. Cancelling
Hot starting will be cancelled when the temperature detected by the indoor unit pipe temperature sensor is 18°C or higher, or after a maximum 1 minute has passed since defrosting was completed.
After cancellation, the PREHEATdisplay on the remote control disappears and the louvre operation returns to the previous setting.
(However, the indoor unit fan operates at LOW speed for 2 minutes after cancellation, and then returns to the previous setting.)
<When hot start operation is cancelled by temperature>
63
Page 64
<When hot start operation is cancelled by time>
27.5. Indoor unit fan control when thermostat is off during heating mode operation
When the thermostat of the indoor unit turns off during heating mode operation, the indoor unit fan operates for 2 minutes at LOW and then stops. In addition, 5 minutes after the thermostat of the indoor unit turns off, the indoor unit fan operates at LOW for 10 seconds, and at 3 minutes interval after that, it switches back to LOW operation for another 10 seconds.
27.6. Excess heat dissipation for indoor unit
The indoor unit fan continue its operation for 30 seconds after heating mode operation turns off in order to dissipate excess heat.
1. When heating mode operation has stopped
(LOW speed for 30 seconds)
2. When operation is set to a mode other than heating by means of the OPERATION button
3. If operation starts again during the 30 seconds mentioned at (1)
(The fan operates at LOW speed for the remainder of the 30 seconds and then hot start commences.)
64
Page 65
27.7. Defrost mode operation time chart
1. Start and completion of defrosting a. Start
During heating mode operation (including automatic heating), after the 45 minutes of defrosting cycle time has passed, defrosting starts if the temperature detected by the outdoor unit heat exchanger outlet sensor is 2°C or lower continuously for 5 minutes.
However, if the outdoor unit fan is stopped, the start of defrosting will be delayed by 5 minutes. Then, the defrosting cycle will be 50 minutes from the start of heating mode operation.
b. Completion
Defrosting mode operation will stop if the outdoor unit heat exchanger outlet sensor is 25°C or higher or after 12 minutes of operation.
c. Forced defrosting
If P8 on the outdoor unit circuit board is shorted while the compressor is on during heating mode operation and the temperature detected by the outdoor unit heat exchanger outlet sensor is 25°C or lower, defrosting is carried out regardless of the current starting conditions.
2. Operation a. During defrosting, the outdoor unit turns on the compressor and turns off the outdoor unit fan and the reversing valve. b. The indoor unit fan operates atLOW speed for 30 seconds upon defrosting starts, After this,the indoor unit fan turns off until
defrosting is completed. (During defrosting, the louvre of the indoor unit stays at horizontal position).
27.8. Indoor thermostat charateristics
1. Thermostat characteristics during cooling and heating modes.
Operation mode Setting temperature (To) Room temperature (°C)
Cooling 16 ON 18.0 ____
31 ON 33.0 ____
Heating *1 16 ON 18.0 20.0
29~31 ON 31.0 31.0
*1 (27~31) OFF 33.0 33.0
65
Operation Differential
2.0K 4.0K
OFF 16.0 ____
OFF 31.0 ____
OFF 20.0 22.0
Page 66
1* If jumper wire J3 on the indoor unit circuit board is disconnected, the thermostat characteristics
during heating become 2K or higher.
NOTE: If the remote control display setting temperature (To) is 29°C or higher, the heating thermostat turns
on when the room temperature is 31°C.
2. Thermostat characteristics during dry mode. During dry mode operation, cooling mode operation is carried out in accordance with the indoor temperature as shown in the
table below.
* When modes (2) and (3) are active, dry mode operation starts when the cooling thermostat turns on.
When modes (2) and (3) have been stopped, the 10 min./5 min. times have no relevance. However, if the indoor temperature is less than or equal to the remote control unit setting temperature, mode (4) is forcibly activated.
3. Thermostat characteristics during automatic changeover operation a. Settings at the start of automatic changeover operation
When operat ion changes from other modes to automatic changeover mode, operation starts at the temperature characteristics given in the table below.
b. Thermostat characteristic when switching between cooling and heating mode operation
Switching between cooling mode and heating mode operation is carried out as shown in the table below. However, during automatic changeover operation, the operation will not change within 10 minutes after the thermostat has
switched off, either cooling mode or heating mode. (The 10 minutes timer will be cancelled when operation is changed to other modes (manually) or when operation stops and
the thermostat turns on.)
66
Page 67
c. Thermostat characteristics during cooling mode and heating operation
The thermostat on/off characteristics in both operation modes are given in the table below.
67
Page 68
27.9. Indoor unit fan control
1. Fixing at LO, MED or HI When LO, MED or HI is set, the relay switches and operation is carried out at that setting.
2. Automatic fan speed When set to AUTO, the indoor unit fan operation changes as shown in the table below.
(Indoor temperature) - (Setting temperature) (Units: K)
Mode / Fan Speed HI MED LO
Cooling +3 or higher +1.5 ~ 3 Less than +1.5
Heating -3 or lower -1.6 ~ - 3 More than -1.5
Fan MED irrespective of temperature
27.10. Forced operation during restart
The compressor will not stop operating for 3 minutes after cooling mode operation starts, even if the indoor unit thermostat turns off. (However, the compressor will stop operating during this time if the indoor unit air intake temperature drops to 16°C and below during cooling mode operation.)
27.11. Louvre control (models with louvre)
1. When main power is turned on When the power is turned on, indoor unit louvre position detection is carried out twice and then the indoor unit louvre stops.
2. During initial operation When the OFF/ON button is pressed to start the operation, the louvre moves through one full cycle, and then swings automatically (if AUTO has been set using the remote control) or moves to the setting angle (if MANUAL has been set using the remote control).
3. When operation stops When the OFF/ON button is pressed to stop the operation, the louvre moves through one full cycle, and then stops in the down position, regardless of the remote control setting.
4. When thermostat is off When operation is stopped by the indoor thermostat, the louvre moves through one full cycle, and then stops in the horizontal position, regardless of the remote control setting.
68
Page 69
27.12. Outdoor unit fan excess heat dissipation control
1. When the operation is stopped while the compressor is in operation, the outdoor fan will run at SUPER HI fan speed for approximately 60 seconds and then stops.
27.13. Discharge temperature control
1. Operation When the discharge temperature sensor detects a tempe rature of 100°C or higher during cooling mode operation, the liquid bypass valve will be turned on.
2. Cancelling When the discharge temperature sensor detects a temperature of 70°C or lower, the liquid bypass valve will be turned off.
27.14. Emergency operation
When the emergency operation switch (DSW1) on the outdoor unit printed circuit board is set to emergency, the emergency operation is enabled. This allows normal operation to continue, with all abnormalities other than a discharge temperature abnormality, high pressure abnormality or overcurrent abnormality being ignored.
27.15. DIP switch settings
Indoor unit printed circuit board (DSW1)
• •
No. Setting type Factory shipment Remarks
1 Group address setting
(twin/triple address setting)
2 OFF 3 OFF 4 OFF 5 Automatic restart ON When set to ON,operation after a power outage resumes at the settings which were
6 Filter sign time OFF When set to ON, the filter sign times can be set to 2,500 times. 7 Louvre control ON When set to OFF, louvre control is disabled. 8 Twin/triple slave unit setting OFF When set to ON, the unit is designated as a slave unit.
OFF When group operation is being carried out using the remote control, this address is
set in order to control the order of starting for the indoor units. (If No. 8 is ON, twin/triple address setting is carried out.)
in effect before the outage. (The backup time is semipermanent.)
69
Page 70
28 WIRED REMOTE CONTROL INSTALLATION MANUAL
7071727374
Page 71
Page 72
Page 73
Page 74
Page 75
29 WIRELESS REMOTE CONTROL INSTALLATION MANUAL
75767778798081
Page 76
Page 77
Page 78
Page 79
Page 80
Page 81
Page 82
30 INSTALLATION (INDOOR UNIT)
828384858687888990
Page 83
Page 84
Page 85
Page 86
Page 87
Page 88
Page 89
Page 90
Page 91
31 INSTALLATION (OUTDOOR UNIT)
919293949596979899
Page 92
Page 93
Page 94
Page 95
Page 96
Page 97
Page 98
Page 99
Page 100
100
Loading...