Orion SA E-BUS User Manual

Factory Packaged Controls
LED BLINK CODES
LED NAME STATUS1 STATUS2
NORMALOPERATION 0 1
SATFAIL 1 2
EATFAIL 2 2
SPCFAIL 3 2
MECHCOOL FAIL 1 3
MECHHEAT FAIL 2 3
FANPROOF FAIL 3 3
DIRTYFILTER 4 3
WATERFLOW ALARM 6 3
DRAINPAN ALARM 7 3
EMERGENCYSHUTDOWN 5 3
LOWSAT 1 4
HIGHSAT 2 4
CONT.TEMP COOL FAIL 3 4
CONT.TEMP HEAT FAIL 4 4
PUSHBUTTON OVR 1 5
ZONEOVR 2 5
OUTPUTFORCE ACTIVE 0 6
SA E-BUS Controller
Technical Guide
SA E-BUS Controller Code: Y200921
Requires System Manager Code: Y200921SM Version 1.0 and up
Requires Service Tool Code: Y200921HH Version 1.0 and up
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T” TO“T” “SHLD” TO “SHLD”
www.aaon.com
www.orioncontrols.com
SA CONTROLLERE-BUS
Orion No.:OE332-23E-VCMX-SA
AI1 = SPC (SPACETEMPERATURE SENSOR)
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI2
= EWT (ENTERING WATERTEMPERATURE SENSOR)
AI3
= EAT(ENTERING AIR TEMPERATURE SENSOR)
AI4 AI5
= NOT USED
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
4-20mA
AI1
0-10V 0-5V
THERM
4-20mA
AI2
0-10V 0-5V
THERM
4-20mA
AI3
0-10V 0-5V
THERM
4-20mA
AI4
0-10V 0-5V
THERM 4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V 0-5V
ANALOG INPUT JUMPER SETTINGS MUST BE SETAS SHOWN FOR PROPER OPERATION
WattMaster Label
STATIC
#LB102060-01-A
PRESSURE
Rev.: 1A
EXPANSION
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
IC
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07160
24 VAC POWER ONLY
I C DIGITAL
SENSOR
Table of Contents
OVERVIEW ....................................................................................................................................... 4
Part Number Cross Reference ..................................................................................................................................................4
Features and Applications ........................................................................................................................................................5
SA E-BUS Controller Dimensions ............................................................................................................................................6
SA Expansion Module Dimensions ..........................................................................................................................................7
12-Relay Expansion Module Dimensions ................................................................................................................................8
SA E-BUS Controller Component Locations ...........................................................................................................................9
INSTALLATION AND WIRING ........................................................................................................10
Important Wiring Considerations ...........................................................................................................................................10
SA E-BUS Controller Wiring ...................................................................................................................................................11
Digital Room Sensor ..........................................................................................................................................................12
Space Temperature Sensor ...............................................................................................................................................13
Remote SAT Reset Signal .................................................................................................................................................13
Supply Air Temperature Sensor ................................................................................................. ........................................14
Entering Water Temperature Sensor .................................................................................................................................15
Entering Air Temperature Sensor .......................................................................................................................................16
Water Side Economizer Valve ...........................................................................................................................................17
Water Side Economizer Bypass Valve ..............................................................................................................................17
Supply Fan VFD Signal or Zoning Bypass Damper Actuator Signal .................................................................................18
SA Expansion Module Input Wiring ........................................................................................................................................20
SA Expansion Module Output Wiring .....................................................................................................................................21
Suction Pressure Transducer ............................................................................................................................................22
SA Expansion Module Binary Inputs ................................................................................................................................23
Entering Air Humidity Sensor .............................................................................................................................................24
Indoor Wall-Mounted Humidity Sensor ..............................................................................................................................25
Modulating Heating Device ................................................................................................................................................26
Modulating Cooling Device ................................................................................................................................................27
12-Relay Expansion Module .............................................................................................................................................30
ADDITIONAL APPLICATIONS ........................................................................................................32
SA E-BUS Controller to Module Wiring .................................................................................................................................32
Two Condenser Head Pressure Module ............................................................................................................................34
Water Source Heat Pump Modules ...................................................................................................................................35
START-UP AND COMMISSIONING ................................................................................................. 36
Addressing & Powering Up .....................................................................................................................................................36
Before Applying Power ......................................................................................................................................................36
Controller Addressing ........................................................................................................................................................36
Power Wiring ....................................................................................................................................................................36
Initialization ........................................................................................................................................................................37
Operating Summary ..........................................................................................................................................................37
Programming the Controller ...................................................................................................................................................37
www.aaon.com
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville , MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com WattMaster Form : AA-SA-EBUS-TGD-01D Copyright March 2015 WattMaster Controls, Inc.
AAON Part Number: V10910
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK. Copeland Digital Scroll™ is a registered trademark of Copeland Corporation, Sidney, OH EBTRON® is a registered trademark of Ebtron, Inc., Loris, SC.
Neither WattMaster Controls, Inc. nor AAON assumes any responsibility for errors or omissions in this document. This document is subject to change without notice.
®
Table of Contents
INPUTS AND OUTPUTS ................................................................................................................ 38
SA E-BUS Controller Inputs and Outputs ..............................................................................................................................38
SA Expansion Module Inputs and Outputs ............................................................................................................................39
SEQUENCE OF OPERATION ..........................................................................................................41
Operation Modes ......................................................................................................................................................................41
Occupied/Unoccupied Mode of Operation .........................................................................................................................41
HVAC Modes of Operation ................................................................................................................................................41
Vent Mode Operation .........................................................................................................................................................41
Cooling Mode Operation ....................................................................................................................................................41
Stage Control Window .......................................................................................................................................................42
Modulating Cooling ............................................................................................................................................................42
DX Cooling .......................................................................................................................................................................42
Air Cooled Condenser Fan Operation ...............................................................................................................................43
Water Side Economizer Operation (Valves 1 & 2) .............................................................................................................43
Water Cooled Condenser (Valve 3) ...................................................................................................................................43
Chilled Water Cooling ........................................................................................................................................................44
External Cooling ................................................................................................................................................................44
Dehumidifi cation Mode ......................................................................................................................................................44
Coil Temperature Reset .....................................................................................................................................................44
Reheat Control ..................................................................................................................................................................45
Coil Temperature Offset .....................................................................................................................................................45
Heating Mode ...................................................................................................................................................................46
Stage Control Window .......................................................................................................................................................46
Modulating Hot Water or Steam Heating ...........................................................................................................................46
External Heat .....................................................................................................................................................................46
Air to Air Heat Pump Operation .........................................................................................................................................46
Water Source Heat Pump Operation .................................................................................................................................47
Morning Warm-Up Mode ...................................................................................................................................................47
Off Mode ............................................................................................................................................................................47
Supply Air Temperature Setpoint Reset .............................................................................................................................47
Supply Fan Control ............................................................................................................................................................48
Duct Static Pressure Control .............................................................................................................................................48
Pre-Heater Operation ........................................................................................................................................................49
Entering Air Lockouts ......................................................................................................... ................................................49
Supply Air Cutoffs ..............................................................................................................................................................49
SA E-BUS Controller Alarms .............................................................................................................................................50
VAV/Zone Controller Alarms ..............................................................................................................................................51
Scheduling .........................................................................................................................................................................52
Internal Trend Logging .......................................................................................................................................................52
Force Modes or Overrides .................................................................................................................................................53
VAV Terminal Unit Controller Compatibility ........................................................................................................................53
VAV/Zone System & Zoning System .................................................................................................................................53
TROUBLESHOOTING ..................................................................................................................... 54
LED Diagnostics .......................................................................................................................................................................54
Diagnostic LED Operation .......................................................................................................................................................55
APPENDIX ..................................................................................................................................... 56
System Confi gurations ............................................................................................................................................................56
Stand-Alone System Layout ..............................................................................................................................................57
Interconnected System Layout ..........................................................................................................................................58
Networked System Layout .................................................................................................................................................59
Temperature Sensor Testing ...................................................................................................................................................60
OE265 Series RH Sensor Testing .....................................................................................................................................61
OE271 Pressure Sensor Testing .......................................................................................................................................62
OE275-01 Suction Pressure Transducer Testing for R410A Refrigerant ...........................................................................63
INDEX ............................................................................................................................................ 64
SA E-BUS Controller Technical Guide 3
Overview
Part Number Cross Reference
PART DESCRIPTION
SA E-BUS Controller OE332-23E-VCMX-SA-A V07160 SA Expansion Module OE333-23-SA-A R96180 12-Relay Expansion Module OE358-23-12R R69180 Two Condenser Head Pressure Module OE370-23-HP2C R90230 Water Source Heat Pump Protection Module - 410A OE334-23-WPM-A R88350 Water Source Heat Pump Protection Module - 410A - 20% Glycol OE334-23-WPM-A20 R99750 Water Source Heat Pump Protection Module - 410A - 40% Glycol OE334-23-WPM-A40 R99760 Bypass & Slave Interface Card PL101824 N/A Bypass Damper Actuator OE281-04 N/A CommLink 5 Communications Interface OE361-13 V32950 Digital Room Sensor - Temp & Humidity OE217-01 R83870 Digital Room Sensor - Temp. Only OE217-00 R83860 Duct Static Pressure Sensor OE271 P87100 Duct Temperature Sensor - 12" Probe OE231 R44940 / P87140 Duct Temperature Sensor - 6" Probe OE230 R36340 IP Module Kit OE415-02 R66770 MiniLink Polling Device OE364-22 N/A Modular Service Tool SD - Operator Interface OE391-12 V28140 Modular System Manager SD - Operator Interface OE392-12 V36570 Entering Air RH Sensor - 3% - 0-5 VDC Output OE265-14 R34700 Entering Air Temperature Sensor OE250 R34650 Room Mounted RH Sensor - 3% - 0-5 VDC Output OE265-11 R34690 Standard Room Sensor - Plain OE210 R31480 Standard Room Sensor - w/ Override OE211 P87040 Standard Room Sensor - w/ Override & Slide Adjust OE213 P94320 Standard Room Sensor - w/ Slide Adjust OE212 P94100 Static Pressure Pickup Tube OE290 S18780 Suction Pressure Transducer OE275-01 R28390 USB-Link 2 Kit OE366 R71870
ORION
PART NO:
AAON TULSA
PART NO:
4
SA E-BUS Controller Technical Guide
Overview
Features and Applications
Features
The Series A Controller (OE332-23E-VCMX-SA)—SA E-BUS Con­troller—is designed with 6 analog inputs, 2 analog outputs, and 5 relay outputs. Most common HVAC unit control applications can be con­ gured using only the SA E-BUS Controller; however, if needed, the SA E-BUS Controller’s input and output capabilities can be expanded with the SA Expansion Module ( OE333-23-SA) or 12-Relay Expansion Module (OE358-23-12R) by means of a modular cable. The SA Expan­sion Module provides an additional 4 analog inputs, 5 analog outputs, 8 binary inputs, and 4 confi gurable relays. The 12-Relay Expansion Module provides an additional 12 confi gurable relays.
The SA E-BUS Controller can also use the Two Condenser Head Pres­sure Module ( OE370-23-HP2C) for those applications requiring Head Pressure Control. The SA E-BUS Controller can also use the WSHP Module (OE334-23-WPM-A) for W ater Source Heat Pump applications.
Each SA E-BUS Controller can be confi gured for control of VAV Units (with or without VAV/Zone Controllers), Constant Volume Units, and Make-Up Air Units. Features include the following:
Modulating Cooling Output ( Copeland Digital
Scroll™ Compressor or Chilled Water Valve Control)
Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
Full Integration with the AAON
Hot Gas Reheat Valve Controller
®
MHGRV Modulating
Confi gurable for Air to Air and Water Source Heat Pump
Applications
Advanced Dehumidifi cation Capabilities
Adaptive Supply Air Reset
Selectable Control Sensor
Fan Proving Interlock
Dirty Filter Alarm
Emergency Shutdown Input (Smoke Detector/Firestat or
other Shutdown Conditions)
Water Side Economizer Option
Remote Occupied Capabilities
7-Day, 2-Event-per-Day Scheduling
14 Holiday Event Scheduling
Optimal Start Scheduling
Trend Logging Capability
Static Pressure Control for Filter Loading Applications
Head Pressure Control (with optional Two Condenser Head
Pressure Module)
Additional Water Safeties (with optional Water
Source Heat Pump Module)
Applications
Variable Air Volume Unit
The SA E-BUS Controller can be confi gured to control a VFD Supply Fan for Duct Static Pressure control. If the unit is not equipped with a VFD, but Duct Static Pressure control is needed, a modulating Zoning Bypass Damper can be controlled by the SA E-BUS Controller.
VAV units are typically designed for occupied Cooling with Morning W arm-up Heating. This option is available with the SA E-BUS Control­ler. The SA E-BUS Controller can also be used for a Zoning System that needs Duct Static Pressure control and Occupied Cooling and Heating. The SA E-BUS Controller also has the ability to be confi gured for Duct Static Pressure Control by controlling the Supply Fan VFD for the pur­pose of maintaining proper Duct Static Pressure in response to varying lter loading conditions.
The SA E-BUS Controller allows Dehumidifi cation Priority on a VAV unit. This could be useful on a building with a very low internal sensible load, but which has a high internal and/or external latent load. During VAV Dehumidifi cation, the SA E-BUS Controller activates Cooling based on the Evaporator Coil Temperature and activates lating Hot Gas Reheat to warm the Supply Air Temperature to the Active Supply Air Temperature Setpoint.
Constant Air Volume Unit
The SA E-BUS Controller can be confi gured to activate a Constant Volume Supply Fan. In most cases, this is a very basic unit with Space Temperature control.
Make-Up Air Unit
The SA E-BUS Controller can be confi gured for 100% Outdoor Air control for Make-Up Air. All HVAC Modes are determined from the Outdoor Air Sensors. The Outdoor Air Volume must always be at least 50% or higher to be confi gured for Outdoor Air control.
Single or Dual Cabinet Unit
The SA E-BUS Controller can control an SA Series Single Cabinet Unit or an SA Series Dual Cabinet Unit. Wiring for Dual Cabinet Units is shown and noted on applicable Single Cabinet Unit diagrams.
AAON® Modu-
SA E-BUS Controller Technical Guide
5
Overview
SA E-BUS Controller Dimensions
5.985.98
8.388.38
0.290.29
7.837.83
2.752.75
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
RS-485 COMMUNICATION LOOP. WIRE
RS-485 COMMUNICATION LOOP. WIRE
“R” TO R”, T” TO “T” “SHLD” TOSHLD”
“R” TO R”, T” TO “T” SHLD” TO“SHLD”
www.aaon.com
www.orioncontrols.com
www.orioncontrols.com
SA CONTROLLERE-BUS
SA CONTROLLERE-BUS
Orion No.:OE332-23E-VCMX-SA
OE332-23-VCMX-A VCM-X CONTROLLER
Orion No.:OE332-23E-VCMX-SA
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI2
= SAT (SUPPLYAIR TEMPERATURE SENSOR)
= SAT (SUPPLYAIR TEMPERATURE SENSOR)
AI2
= SAT (SUPPLYAIR TEMPERATURE SENSOR)
AI2
AI3
= EWT (ENTERING WATERTEMPERATURE SENSOR)
= EWT (ENTERING WATERTEMPERATURE SENSOR)
AI3
= RAT (RETURNAIR TEMPERATURE SENSOR)
AI3
AI4
= EAT (ENTERINGAIR TEMPERATURE SENSOR)
= EAT (ENTERINGAIR TEMPERATURE SENSOR)
AI4
= OAT (OUTDOORAIR TEMPERATURE SENSOR)
AI4
AI5
= NOT USED
= NOT USED
AI5
AI5
= SUCTION PRESSURE SENSOR
AI7
= SPACE TEMPERATURE SENSOR SLIDEADJUST
= SPACE TEMPERATURE SENSOR SLIDEADJUST
AI7
AI7
= SPACE TEMPERATURE SENSOR SLIDEADJUST
OR VOLTAGE RESETSOURCE
OR VOLTAGE RESETSOURCE
OR VOLTAGE RESETSOURCE
A01
= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
A01
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
A02
A02
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
E-BUS
E-BUS
CONNECTOR
CONNECTOR
ANALOG INPUT
ANALOG INPUT
ANALOG INPUT
JUMPER
JUMPER
JUMPER
SETTINGS
SETTINGS
SETTINGS
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
AI1
AI1
AI1
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
AI2
AI2
AI2
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI3
4-20mA
AI3
0-10V
0-10V
AI3
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI4
AI4
4-20mA
0-10V
0-10V
AI4
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI5
AI5
4-20mA
0-10V
0-10V
AI5
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI7
AI7
4-20mA
0-10V
0-10V
AI7
0-10V
0-5V
0-5V
0-5V
ANALOG INPUT JUMPER SETTINGS
ANALOG INPUT JUMPER SETTINGS
MUST BE SETAS SHOWN FOR
MUST BE SETAS SHOWN FOR
ANALOG INPUT JUMPER SETTINGS
PROPER OPERATION
PROPER OPERATION
MUST BE SETAS SHOWN FOR PROPER OPERATION
PRESSURE
STATIC
STATIC
STATIC
PRESSURE
PRESSURE
WattMaster Label
WattMaster Label
#LB102060-01-A
WattMaster Label
#LB102033-01
Rev.: 1A
#LB102060-01-A
Rev.: 1A
LED BLINK CODES
LED BLINK CODES
LED NAME STATUS1 STATUS2
LED NAME STATUS1 STATUS2
NORMAL OPERATION 0 1
NORMAL OPERATION 0 1
SAT FAIL 1 2
SAT FAIL 1 2
EAT FAIL 2 2
EAT FAIL 2 2
SPC FAIL 3 2
SPC FAIL 3 2
MECH COOL FAIL 1 3
MECH COOL FAIL 1 3
MECH HEAT FAIL 2 3
MECH HEAT FAIL 2 3
FAN PROOF FAIL 3 3
FAN PROOF FAIL 3 3
DIRTY FILTER 4 3
DIRTY FILTER 4 3
WATER FLOW ALARM 6 3
WATER FLOW ALARM 6 3
DRAIN PAN ALARM 7 3
DRAIN PAN ALARM 7 3
EMERGENCY SHUTDOWN 5 3
EMERGENCY SHUTDOWN 5 3
LOW SAT 1 4
LOW SAT 1 4
HIGH SAT 2 4
HIGH SAT 2 4
CONT. TEMP COOL FAIL 3 4
CONT. TEMP COOL FAIL 3 4
CONT. TEMP HEAT FAIL 4 4
CONT. TEMP HEAT FAIL 4 4
PUSH BUTTON OVR 1 5
PUSH BUTTON OVR 1 5
ZONE OVR 2 5
ZONE OVR 2 5
OUTPUT FORCE ACTIVE 0 6
OUTPUT FORCE ACTIVE 0 6
WARNING! POLARITY MUST BE OBSERVED
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
OR THE CONTROLLER WILL BE DAMAGED
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
2
2
IC
IC
2
IC
EXPANSION
EXPANSION
EXPANSION
AAON No.:
AAON No.:
24 VAC POWER ONLY
RELAY CONTACT RATING IS 1AMP
RELAY CONTACT
RELAY CONTACT
MAX @ 24 VAC
RATING IS 1AMP
RATING IS 1AMP
MAX @ 24 VAC
MAX @ 24 VAC
RELAY
RELAY
COMMON
RELAY
COMMON
COMMON
FAN
FAN
FAN
RELAY 2
RELAY 2
RELAY 2
RELAY 3
RELAY 3
RELAY 3
RELAY 4
RELAY 4
RELAY 4
RELAY 5
RELAY 5
RELAY 5
V07160
V07160
24 VAC POWER ONLY
24 VAC POWER ONLY
2
2
IC DIGITAL
IC DIGITAL
2
IC DIGITAL
SENSOR
SENSOR
SENSOR
OBSERVE
POLARITY
1.49
WARNING
4.104.10
0.700.70
Figure 1: OE332-23E-SA E-BUS Controller – SA E-BUS Controller Dimensions
6
SA E-BUS Controller Technical Guide
0.980.98
8.38
7.83
0.29
Overview
SA Expansion Module Dimensions
5.98
0.98
2.75
24 VAC
24 VAC POWER ONLY
POWER ONLY
WARNING! POLARITY MUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILL BE DAMAGED
MUST BE OBSERVED OR
POLARITY
WARNING
OBSERVE
THE BOARD WILL BE DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-A VCM-X EXPANSION MODULE
PR OUT
TO VCM-X INPUT
GND
TERMINALS AI5 & GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY 1 = RELAY 3 =
RELAY 2 = RELAY 4 =
RELAY 1 = RELAY 3 =
IT IS SUGGESTED THATYOU WRITE THE DESCRIPTION OF
RELAY 2 = RELAY 4 =
THE RELAYOUTPUTS YOUARE USING IN
IT IS SUGGESTED
THE BOXES
THATYOU WRITE THE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM 4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
www.orioncontrols.com
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT BI2
= WATER PROOF OF FLOW - B - N.O. INPUT
BI3
= AIR PROOF OF FLOW - N.O. INPUT
BI4
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI1 = HOOD ON - N.O. INPUT
BI5
= EMERGENCY SHUTDOWN - N.C. INPUT
= DIRTY FILTER - N.O. INPUT
BI2
BI6
= DRAIN PAN OVERFLOW -A - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
BI3
BI7
= DRAIN PAN OVERFLOW - B - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI8
= DIRTY FILTER - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
= SMOKE DETECTOR - N.C. INPUT
BI7
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
AO2
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1 = BUILDING PRESSURE CONTROL VFD OR
= MODULATING COOLING STAGE 2 SIGNAL
AO3
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
AO2
= MODULATING HEATING SIGNAL
= WSE BYPASS 2ASIGNAL
AO4
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
AO3
= MODULATING COOLING/DIGITALSCROLL
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
AO4
= RETURN AIR DAMPERACTUATOR
= GROUND FOR ANALOG OUTPUTS
GND
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
AO5
= RETURN AIR BYPASS DAMPERACTUATOR
(0-10 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
AI3
= SUCTION PRESSURE A(0-5 VDC)
AI4
= SUCTION PRESSURE B (0-5 VDC)
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
= INDOOR AIR RH SENSOR (0-5 VDC)
AI2
GND
= GROUND FOR ANALOG INPUTS
= CO2 (0-10 VDC)
AI3
= BUILDING STATIC PRESSURE (0-5 VDC)
AI4
= GROUND FOR ANALOG INPUTS
GND
= GROUND FOR ANALOG INPUTS
GND
I2C
EXPANSION
#LB102034-01
AAON No.:
WattMaster Label
#LB102061-A
Rev.: 1C
EXPANSION
R96180
RELAY CONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY CONTACT RATING IS 1AMP
RELAY 1
MAX @ 24 VAC
RELAY 2
RELAY 1
RELAY 3
RELAY 2
RELAY 4
RELAY 3
RELAY
RELAY 4
COMMON
RELAY COMMON
I2C
SA
0.70
4.10
Figure 2: OE333-23-SA – SA Expansion Module Dimensions
SA E-BUS Controller Technical Guide
1.49
7
Overview
12-Relay Expansion Module Dimensions
Figure 3: OE358-23-12R – 12-Relay Expansion Module Dimensions
8
SA E-BUS Controller Technical Guide
Overview
SA E-BUS Controller Component Locations
Figure 4: OE332-23E-SA – SA E-BUS Controller Component Locations
SA E-BUS Controller Technical Guide
9
Installation & Wiring
Important Wiring Considerations
Zone
Zone
General
Correct wiring of the SA E-BUS Controller is the most important factor in the overall success of the controller installation process. In general, most SA E-BUS Controllers are factory installed and wired at the AAON
®
factory.
Controller Mounting
When the controller is to be fi eld mounted, it is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. See Table 1 for a list of the required operating conditions for the SA E-BUS Controller and associated modules.
The SA E-BUS Controller is housed in a plastic enclosure. It is designed to be mounted by using the 3 mounting holes in the enclosure base. The SA E-BUS Controller needs to be installed in an environment which can maintain a temperature range between -30°F and 150°F not to exceed 90% RH levels (non-condensing). It is important to mount the controller in a location that is free from extreme high or low temperatures, moisture, dust, and dirt. Be careful not to damage the electronic components when mounting the controller.
Considerations
The SA E-BUS Controller and associated modules must be connected to a 24 VAC power source of the proper size for the calculated VA load requirements. All transformer sizing should be based on the VA rating listed in Table 1.
Device
Control
OE332-23E-SA E-BUS
Controller
SA E-BUS Controller
OE333-23-SA
SA Expansion Module 24VAC
OE358-23-12R
12-Relay Expansion
Module
OE370-23-HP2C
Two Condenser Head
Pressure Module
OE334-23-WPM-A
Water Source Heat Pump
Module
24VAC 8
24VAC 15
24VAC 5
24VAC 8
Voltage
VA Load
-30°F to 150°F
-30°F to
10
150°F 90% RH
-30°F to 150°F
-30°F to 150°F
-30°F to 150°F
Temperature
(Non-
Humidity
Condensing)
90% RH
90% RH
90% RH
90% RH
Warning: When using a single transformer to power more than one controller or expansion module, the correct polarity must always be maintained between the boards. Failure to observe correct polarity will result in damage to the SA E-BUS Controller and associated modules.
Please carefully read and apply the following information when wiring the SA E-BUS Controller or its associated modules. See Figure 5 on page 11 for the SA E-BUS Controller wiring diagram. See Figures 16 and 17 on pages 20 and 21 for SA Expansion Module wiring. And see Figure 25 on page 31 for 12-Relay Expansion Module wiring.
1. All wiring is to be in accordance with local and national electrical codes and specifi cations.
2. Minimum wire size for 24 VAC wiring should be 18-gauge.
3. Minimum wire size for all sensors should be 24-gauge. Some sensors require 2-conductor wire and some require 3-or 4-conductor wire.
4. Be sure that all wiring connections are properly inserted and tightened into the terminal blocks. Do not allow wire strands to stick out and touch adjoining terminals which could potentially cause a short circuit.
5. When communication wiring is to be used to interconnect SA E-BUS Controllers together or to connect to other communication devices, all wiring must be plenum-rated, minimum 18-gauge, 2-conductor, twisted pair with shield. WattMaster can supply communication wire that meets this specifi cation and is color coded for the network or local loop. Please consult your WattMaster distributor for information. If desired, Belden #82760 or equivalent wire may also be used.
6. Before applying power to the SA E-BUS Controller, be sure to recheck all wiring connections and terminations thoroughly.
Table 1: Voltage and Environment Requirements
10
SA E-BUS Controller Technical Guide
Installation & Wiring
SA E-BUS Controller Wiring
SA E-BUS Controller
The Series A Controller (OE332-23E-SA)—SA E-BUS Controller—is designed with 6 analog inputs, 2 analog outputs, and 5 relay outputs. Most common HVAC unit control applications can be confi gured us- ing only the SA E-BUS Controller; however, if needed, the SA E-BUS Controller’s input and output capabilities can be expanded with the SA Expansion Module ( OE333-23-SA) or 12-Relay Expansion Module ( OE358-23-12R) by means of a modular cable.
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller And/Or
MiniLink PD On Local Loop.
SA E-BUS Controller
RS-485 COMMUNICATION LOOP. WIRE “R” TO “R”, “T”TO “T” “SHLD” TO “SHLD”
SA CONTROLLERE-BUS
Orion No.:OE332-23E-VCMX-SA
AI1 = SPC (SPACETEMPERATURE SENSOR) AI2
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI3
= EWT (ENTERING WATERTEMPERATURE SENSOR)
AI4
= EAT(ENTERING AIR TEMPERATURE SENSOR)
AI5
= NOT USED
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
LED NAME STATUS1 STATUS2
4-20mA
AI1
AI2
AI3
AI4
AI5
AI7
ANALOG INPUTJUMPER SETTINGS MUSTBE SET AS SHOWN FOR PROPER OPERATION
STATIC
PRESSURE
NORMALOPERATION 0 1
0-10V 0-5V
SATFAIL 1 2
THERM
EATFAIL 2 2
4-20mA
SPCFAIL 3 2
0-10V
MECHCOOL FAIL 1 3
0-5V
MECHHEAT FAIL 2 3
THERM
4-20mA
FANPROOF FAIL 3 3
0-10V
DIRTYFILTER 4 3
0-5V
WATERFLOW ALARM 6 3
THERM
DRAINPAN ALARM 7 3
4-20mA 0-10V
EMERGENCYSH UTDOWN 5 3
0-5V
LOWSAT 1 4
THERM
HIGHSAT 2 4
4-20mA
CONT.TEMP COOL FAIL 3 4
0-10V
CONT.TEMP H EAT FAIL 4 4
0-5V
PUSHBUTTON OVR 1 5
THERM
4-20mA
ZONEOVR 2 5
0-10V
OUTPUTFORCE ACTIVE 0 6
0-5V
WattMaster Label
#LB102060-01-A
Rev.: 1A
EXPANSION
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
See Individual
Component Wiring
Diagrams For Detailed
Wiring Of Analog Inputs
And Outputs
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
Local Loop
RS-485
9600 Baud
Jumpers
NOTE: Only one SA E-BUS Controller is required whether the SA Unit is a Single Cabinet or Dual Cabinet Unit. Additional wiring for Dual Cabinet Units is shown and noted as such on the applicable Single Cabinet Unit Diagrams.
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07160
LED BLINK CODES
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
2
IC
2
IC DIGITAL
SENSOR
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts R2 Thru R5 May Be User Configured For The Following:
1 - Heating Stages 2 - Cooling Stages 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Air To Air Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Preheater For Low Ambient Protection 7 - Alarm 8 - Override 9 - Occupied 10 - Water Side Economizer
A Total Of 20 Relays Are Available
Note:
By Adding Expansion Modules. Expansion Module Relay Outputs Are User-Configurable As Listed Above.
GND
Line Voltage
24VAC
Size Transformer For Correct Total Load. SA Controller = 8 VA
Splice If Required
Connect To Expansion Module (When Used)
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure Port (Bottom Tube) and Route To Static Pressure Pickup Probe Located In Unit Discharge. Leave Port Marked “Lo” Open To Atmosphere
Note: Only One SA Controller is Required Whether The SA Unit is a Single Cabinet Or Dual Cabinet Unit. Additional Wiring For Dual Cabinet Units is Shown and Noted As Such On The Applicable Single Cabinet Unit Diagrams.
Figure 5: OE332-23E-SA E-BUS Controller – SA E-BUS Controller Wiring
SA E-BUS Controller Technical Guide
Connect To Digital Room Sensor - See Digital Room Sensor Wiring Diagram.
Warning: 24 VAC Must Be Connected So That All Ground Wires Remain Common. Failure To Do So Will Result In Damage To The Controllers.
11
Installation & Wiring
Digital Room Sensor Wiring
Digital Room Sensor
The OE217-00 Digital Room Sensor is used to sense Space Temperature and the OE217-01 Digital Room Sensor is used to sense Space Tem­perature and Space Humidity. The Sensor connects to the SA E-BUS Controller with the TSDRSC modular cable. It should be mounted at ap­proximately 5 ft. above the fl oor on the wall in an area that does not have drafts or is exposed to direct sunlight. See Figure 6 for wiring details.
Note: The Connects Directly To The Controller Using
TSDRSC Cable
A Of The Appropriate Length. 160 Feet.
Digital Room Sensor
SA E-BUS
The Maximum Length Allowed Is
Zone
Zone
I1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
4-20mA
AI2
0-10V 0-5V
THERM 4-20mA
AI3
0-10V 0-5V
THERM
EMERGENCY SHUTDOWN
4-20mA
AI4
0-10V 0-5V
THERM 4-20mA
AI5
0-10V 0-5V
THERM 4-20mA
AI7
0-10V 0-5V
ANALOG INPUT JUMPER SETTINGS MUST BE SETAS SHOWN FOR PROPER OPERATION
STATIC
WattMaster Label
#LB102033-01
PRESSURE
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
I2C
EXPANSION
I2C DIGITAL
SENSOR
OVERRIDE ALARM
Display
Override
Digital Room Sensor
Figure 6: OE217-00 & OE217-01 – Digital Room Sensor Wiring
SA E-BUS Controller
TSDRSC Cable
Note: No Additional Wiring is Required For
Dual Cabinet Units.
12
SA E-BUS Controller Technical Guide
Installation & Wiring
GND
TMP
Space Temperature Sensor
OVR
R
E
L
O
C
R
E
M
R
O
A
W
AUX
Wire Required For Sensors With Slide Adjust Option Only
Set Jumper For THERM
When Space Sensor Slide
Adjust Is Wired To AI7
AI1
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Note:
Either The Slide Offset Option For The Space Temperature Sensor Or The Remote Supply Air Temperature Reset Signal Option (By Others) May Be Connected To An AI7 On The SA E-BUS Controller. Only One Option Is Allowed, Not Both.
AI1
AI7
GND
SA E-BUS Controller
Note: No Additional Wiring is
Required For Dual Cabinet Units.
AI7 SET
Remote Supply Air
Temperature Reset Signal
(By Others)
0-5 VDC or 0-10 VDC Signal
GND
Note:
Either The Slide Offset Option For The Space Temperature Sensor Or The Remote Supply Air Temperature Reset Signal Option (By Others) May Be Connected To AI7 On The SA E-BUS Controller. Only One Option Is Allowed, Not Both.
Regardless of Whether the Remote
SAT Reset Signal Has Been
Configured For 0-5 or 0-10 VDC,
Jumper Must Be Set For 0-10V
AI7
GND
SA E-BUS Controller
AI1
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Note: No Additional Wiring is Required For Dual Cabinet Units.
AI7 SET
SAT & Remote SAT Reset Signal Wiring
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor is typi­cally used for constant volume HVAC unit applications controlling one zone. The Space T emperature Sensor is a 10K T ype III thermistor sensor and should be mounted approximately 5 feet above the fl oor in the space that is to be controlled. The Space Temperature Sensor is available as a sensor only, sensor with override button, sensor with slide adjust, and sensor with slide adjust and override confi gurations.
When the Remote Supply Air T emperature Reset Signal option is needed, the Slide Offset option on the Room Sensor cannot be used. Only one of these options may be used on the SA E-BUS Controller.
See Figure 7 below for complete Space Temperature Sensor wiring details.
Remote SAT Reset Signal
A Remote Supply Air T emperature Reset Signal can be connected to AI7 for applications requiring remote reset of the Supply Air Temperature Setpoint.
When the Slide Offset option on the Room Sensor is used, the Remote Supply Air Temperature Reset Signal cannot be used. Only one of these options may be used on the SA E-BUS Controller.
The SA E-BUS Controller can accept either a 0-5 VDC signal or a 0-10 VDC signal on this input.
See Figure 8 below for complete Remote SAT Reset Signal wiring details.
Figure 7: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring
Figure 8: Remote Supply Air Temperature Reset Signal Wiring
SA E-BUS Controller Technical Guide
13
Installation & Wiring
SAT Sensor Wiring
Zone
Zone
Supply Air Temperature Sensor
The OE231 Supply Air Temperature Sensor must be wired as shown in Figure 9 below for proper operation. The Supply Air Temperature Sensor is a 10K Type III thermistor sensor. The Supply Air Tempera­ture Sensor should be mounted in the unit discharge plenum or in the supply air duct.
Supply Air Temperature Sensor
Mount In HVAC
Unit Supply
Air Duct
Note: No Additional Wiring is Required For Dual Cabinet Units.
NOTE: For Dual Cabinet Units, mount the Supply Air Temperature Sensor in a Supply Air Ducting area that is common to both SA Units.
AI1 SET AI2 SET AI3 SET
AI2
GND
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure The Jumper Is
Set For THERM On AI2 For
Supply Air Temperature
Sensor When Used
Figure 9: OE231 – Supply Air Temperature Sensor Wiring
SA E-BUS Controller
14
SA E-BUS Controller Technical Guide
Installation & Wiring
Entering Water Temperature Sensor Wiring
Entering Water Temperature Sensor
The OE233 Entering W ater T emperature Sensor must be wired as shown in Figure 10 below for proper operation. The Entering Water Tempera- ture Sensor is a 10K Type III thermistor sensor. The Entering Water Temperature Sensor should be mounted in the entering water piping.
Entering Water
Temperature Sensor
(Strap On)
Note: No Additional Wiring
is Required For Dual Cabinet Units.
AI3
GND
NOTE: For Dual Cabinet Units, mount the Entering Water Temperature Sensor in an Entering Water Piping area that is common to both SA Units.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
SA E-BUS Controller
Be Sure Jumper Is Set
For THERM
On AI3 For Entering
Water Temperature Sensor
Butt Splice Or Wire Nut Wire Leads And Extend Wire To Controller Terminals. Connect One Wire Lead To Entering Water Temperature Terminal (AI3) At The Controller. Secure Other Wire Lead To Ground Terminal At The Controller. See Note 3.
Secure Sensor Element And Thermal Mastic Strip To Pipe With Supplied Wire Tie. Be Sure To Tighten Wire Tie Snugly To Ensure Good Thermal Contact.
Sensing Element (Supplied)
Entering Water Temperature Sensor
Wire Tire (Supplied)
Thermal Mastic Strip (Supplied)
Notes:
1.)Sensor Should Be Mounted At Location Along Pipe Length That Best Represents Desired Temperature Reading.
2.)Sensing Element Shown Mounted To Top Of Pipe. The Sensor Element May Be Located At Any Location Around Pipe.
3.)All Wiring To Be In Accordance With Local And National Electrical Codes And Specifications.
Entering Water Pipe See Note 1 & 2.
Thermal Mastic
Place Between Pipe And Sensing Element. Pipe Should Be Clean And Smooth To Provide Proper Thermal Contact With Sensing Element.
Caution: For Accurate Temperature Readings It Is Necessary To Place Insulation Over The Sensor After Installation. This Prevents The Ambient Temperature From Affecting The Sensor. Insulation Should Cover The Sensor And Extend 6“ to 12” Beyond Each End Of The Sensor.
Figure 10: OE233 – Entering Water Temperature Sensor Installation & Wiring
SA E-BUS Controller Technical Guide
15
Zone
Installation & Wiring
Entering Air Temperature Sensor Wiring
Zone
Entering Air Temperature Sensor
The OE231 Entering Air Temperature Sensor must be wired as shown in Figure 11 below for proper operation of the SA E-BUS Controller. The Entering Air Temperature Sensor is a 10K Type III thermistor sen­sor. The sensor should be mounted as shown in an area that is protected from the elements and direct sunlight.
Entering Air
Temperature Sensor
Mount In Entering
Air Stream
NOTE: For Dual Cabinet Units, mount the Entering Air Temperature Sensor in an Entering Air Duct area that is common to both SA Units.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI4
GND
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure Jumper Is Set
For THERM
On AI4 For Entering
Air Temperature Sensor
Note: No Additional Wiring is Required For Dual Cabinet Units.
Figure 11: OE231 – Entering Air Temperature Sensor Wiring
SA E-BUS Controller
16
SA E-BUS Controller Technical Guide
Installation & Wiring
3 (Y)
3 (Y)
5 (U)
5 (U)
2 (+)
2 (+)
1 (-)
1 (-)
Water Side Economizer Wiring
Water Side Economizer (WSE) Valve(s)
The Water Side Economizer Valve(s) must be wired as shown in Figure 12 below for proper operation of the SA E-BUS Controller. The Water
Side Economizer V alve(s) connects to AO1 on the SA E-BUS Controller .
NOTE: For Dual Cabinet Units, wire the Second Cabinet’s WSE Valve Actuator in parallel with the First Cabinet’s WSE Valve Actuator.
Note: Required For Dual SA Unit Applications Only.
WSE Valve 1B - Actuator
GND
24 VAC
2-10 VDC
Water Side Economizer (WSE) Bypass Valve
The W ater Side Economizer Bypass Valve(s) must be wired as shown in Figure 13 below for proper operation of the SA E-BUS Controller. The W ater Side Economizer Bypass Valve(s) are wired to AO4 and AO5 on the SA Expansion Module.
NOTE: For Dual Cabinet Units, wire the Second Cabinet’s WSE Bypass Valve Actuator to AO5 on the SA Expansion Module.
24 VAC Power Source
Sized For Actuator(s) VA Load
WSE Valve 1A - Actuator
GND
24 VAC
2-10 VDC
AO1
GND
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET
AI7
AI7 SET
2 Way Modulating Water Side Economizer Valve
WSE Valve 1B
2 Way Modulating Water Side Economizer Valve
Figure 12: Water Side Economizer Valve Wiring
Figure 13: Water Side Economizer Bypass Valve Wiring
SA E-BUS Controller
WSE Valve 1A
SA E-BUS Controller Technical Guide
17
Installation & Wiring
+
+
_
_
Supply Fan VFD Signal
Zone
Zone
Supply Fan VFD Signal or Zoning Bypass Damper Actuator Signal
The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a 0-10 VDC output from AO2 on the SA E-BUS Controller. This signal output can be connected to the Supply Fan Variable Frequency Drive to modulate the Supply Fan speed and control Duct Static Pressure utilizing the Duct Static Pressure Sensor connected to the SA E-BUS Controller . Alternatively, it can be connected to a Zoning Bypass Damper Actuator that will modulate the Zoning Bypass Damper Actuator to control Duct Static Pressure utilizing the Duct Static Pressure Sensor connected to the SA E-BUS Controller . A Duct Static Pressure Sensor must be connected in order for the VFD or Zoning Bypass Damper Actuator to operate. See Figures 14 and 15 for detailed wiring.
0-10 VDC Input From AO2
GND Shield
Supply Fan Variable Frequency Drive #1
(By Others)
0-10 VDC Input From AO2
GND Shield
Caution: Variable Frequency Drive units can cause large transient noise spikes which can cause interference to be propagated on other electronic equipment. Use shielded wire wherever possible and route all sensor and controller wiring away from the Variable Frequency Drive and the HVAC Unit electrical wiring.
NOTE: For Dual Cabinet Units, VFD #2 must be wired in parallel to VFD #1 as shown in Figure 14 below.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Supply Fan Variable Frequency Drive #2
Caution:
The VFD Unit Must Be Configured For 0-10 VDC Input. The Input Resistance At The VFD Must Not Be Less Than 1000 Ohms When Measured At The VFD Terminals With All Input Wires Removed.
Figure 14: Supply Fan VFD Wiring
(By Others)
Note: Required For Dual SA Unit Applications Only.
Note:
Wire To The VFD Using 18 GA Minimum 2 Conducter Twisted Pair With Shield Cable. Wire Shield To GND As Shown
AO2
GND
Shield
SA E-BUS Controller
18
SA E-BUS Controller Technical Guide
3 (Y)
5 (U)
2 (+)
1 (-)
Supply Fan VFD Signal or Zoning Bypass Damper Actuator Signal
When the Bypass Damper is used (Zoning applications), be sure the Bypass Duct and Damper are designed so that Supply Air will bypass to the Entering Air Duct, ensuring equal airfl ow to both cabinets.
24 VAC Power Source
Sized For Actuator VA Load
Installation & Wiring
Zoning Bypass Damper Actuator
AI1 SET AI2 SET AI3 SET
Note: No Additional Wiring is Required For Dual Cabinet Units.
Bypass Damper Actuator
(Belimo Actuator Shown)
GND
24 VAC
0-10 VDC
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturer Wiring
Instructions
Figure 15: Zoning Bypass Damper Actuator Wiring
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
AO2 GND
SA E-BUS Controller
SA E-BUS Controller Technical Guide
19
Installation & Wiring
SA Expansion Module Input Wiring
Zone
Zone
SA Expansion Module
Two different Expansion Modules are available for use with the SA E­BUS Controller to provide additional inputs and outputs beyond those found on the SA E-BUS Controller.
The SA Expansion Module ( OE333-23-SA E-BUS Controller) provides 8 Binary Inputs, 4 Analog Inputs, 5 Analog Outputs, and 4 Confi gurable Relay Outputs. See Figures 16 and 17 for complete wiring details.
10 VA Minimum Power Required
For SA Expansion Module
See Suction Pressure Transducer Wiring Details For Complete Wiring Information.
See Humidity Sensor Wiring Details For Complete Wiring Information.
Entering Air
Humidity Sensor
VAC OR DC
GND
0-5V
Indoor Air
Humidity Sensor
VOUT (0-5V)
GND
24 VAC
GND
Additional Suction Pressure Sensor Required On Dual Units Only.
Suction Pressure
Transducer #2
Suction Pressure
Transducer #1
Splice Wire As Required To Reach From Transducer Location To Expansion Module Location
Water Proof of Flow A- N.O. Input
Water Proof of Flow B - N.O. Input
Air Proof Of Flow - N.O. Input
Remote Forced Occupied - N.O. Input
Emergency Shutdown - N.C. Input
Drain Pan Overflow A - N.O. Input
Drain Pan Overflow B - N.O. Input
Dirty Filter - N.O. Input
VIN
WH
BK
RD
RD WH
BK
The 12-Relay Expansion Module ( OE358-23-12R) provides for 12 Dry Contact Confi gurable Relay Outputs. See Figure 25 for complete wiring details.
The expansion modules can be used individually or together to provide the required inputs and outputs for your specifi c applications.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to­24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Module must be wired in such a way that the expansion module and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
24 VAC
GND
GND
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITY MUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILL BE DAMAGED
MUST BE OBSERVED OR
POLARITY
WARNING
OBSERVE
THE BOARD WILL BE DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUT GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 = RELAY3 =
B 1I
B 2I
B 3I
B 4I
B 5I
B 6I
B 7I
BI8
AI1
AI2
AI3
AI4
RELAY2 = RELAY4 =
RELAY1 = RELAY 3 =
ITIS SUGGESTED THATYOU WRITE THE DESCRIPTION OF
RELAY2 = RELAY 4 =
THE RELAYOUTPUTS YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITE THE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM 4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
#LB102034-01
AAON No.:
R96180
www.orioncontrols.com
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
TO VCM-X INPUT TERMINALS AI5 & GND
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
BI2
= AIR PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1 = HOOD ON - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
BI5
= DIRTY FILTER - N.O. INPUT
BI2
= DRAIN PAN OVERFLOW -A - N.O. INPUT
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
= DRAIN PAN OVERFLOW - B - N.O. INPUT
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= DIRTY FILTER - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
= SMOKE DETECTOR - N.C. INPUT
BI7
ALL BINARY INPUTS MUSTBE 24 VAC ONLY.
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALL BINARYINPUTS MUST BE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
AO2
= MODULATING COOLING STAGE 1 SIGNAL
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1 = BUILDING PRESSURE CONTROL VFD OR
AO3
= MODULATING COOLING STAGE 2 SIGNAL
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
AO2
= MODULATING HEATING SIGNAL
= WSE BYPASS 2ASIGNAL
AO4
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
AO3
= MODULATING COOLING/DIGITALSCROLL
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
AO4
= RETURN AIR DAMPERACTUATOR
GND
= GROUND FOR ANALOG OUTPUTS
(0-10 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
AO5
= RETURN AIR BYPASS DAMPERACTUATOR
(0-10 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
= INDOOR AIR RH SENSOR (0-5 VDC)
AI2
= SUCTION PRESSURE A(0-5 VDC)
AI3
= SUCTION PRESSURE B (0-5 VDC)
AI4
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG INPUTS
GND
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG INPUTS
GND
AI3
= CO2 (0-10 VDC)
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
GND
= GROUND FOR ANALOG INPUTS
EXPANSION
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY
RELAY4
COMMON
RELAY COMMON
WattMaster Label
I2C
#LB102061-A
Rev.: 1C
EXPANSION
RELAY1
RELAY2
RELAY3
RELAY4
I2C
SA
SA Expansion Module
Figure 16: OE333-23-SA – SA Expansion Module Input Wiring
20
SA E-BUS Controller Technical Guide
Modular Cable
Connect To SA E-BUS
Controller
Modular Cable
Connect To Next Expansion
Module (When Used)
Installation & Wiring
SA Expansion Module Output Wiring
The SA Expansion Module must be connected to 24 VAC as shown in the wiring diagram below. Please see Table 1 on page 10 for correct VA requirements to use when sizing the transformer(s) used for powering the expansion module.
24 VAC
GND
10 VA Minimum Power
Required For SA
Expansion Module
SA Expansion
Module
POLARITY
WARNING
OBSERVE
Modular Cable
Connect To Expansion
Module (When Used)
Modular Cable
Connect To SAE-BUS
Controller
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC­to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Module must be wired in such a way that the expansion module and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
24 VAC
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITY MUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE OBSERVED OR THE BOARD WILLBE DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUT GND
+V SIG GND
RELAY1 = RELAY 3 =
RELAY2 = RELAY 4 =
RELAY1 = RELAY 3 =
ITIS SUGGESTED THATYOU WRITE THE DESCRIPTION OF
RELAY2 = RELAY 4 =
THE RELAYOUTPUTS YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITE THE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUSTBE SET AS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUSTBE SET AS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM 4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
#LB102034-01
www.orioncontrols.com
TO VCM-X INPUT TERMINALSAI5 & GND
SUCTION PRESSURE TRANSDUCER CONNECTION FOR HVAC UNITS WITHOUT DIGITALCOMPRESSOR
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
BI2
=AIR PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1 = HOOD ON - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
BI5
= DIRTY FILTER - N.O. INPUT
BI2
= DRAIN PAN OVERFLOW -A - N.O. INPUT
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
= DRAIN PAN OVERFLOW - B - N.O. INPUT
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= DIRTY FILTER - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5 BI6
= REMOTE FORCED COOLING - N.O. INPUT
NOTE:
BI7
= SMOKE DETECTOR - N.C. INPUT
ALL BINARYINPUTS MUST BE 24 VAC ONLY.
BI8
= REMOTE DEHUMIDIFICATION - N.O. INPUT
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALL BINARYINPUTS MUST BE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
AO2
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1 = BUILDING PRESSURE CONTROL VFD OR
= MODULATING COOLING STAGE 2 SIGNAL
AO3
DAMPERACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
= MODULATING HEATING SIGNAL
AO2
= WSE BYPASS 2ASIGNAL
AO4
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
= MODULATING COOLING/DIGITALSCROLL
AO3
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
= RETURNAIR DAMPER ACTUATOR
AO4
= GROUND FORANALOG OUTPUTS
GND
(0-10 VDC)
= GROUND FORANALOG OUTPUTS
GND
AO5
= RETURNAIR BYPASS DAMPER ACTUATOR
(0-10 VDC)
GND
= GROUND FORANALOG OUTPUTS
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
GND
= GROUND FORANALOG OUTPUTS
= INDOORAIR RH SENSOR (0-5 VDC)
AI2
= SUCTION PRESSUREA (0-5 VDC)
AI3
= SUCTION PRESSURE B (0-5 VDC)
AI4
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
= GROUND FORANALOG INPUTS
GND
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
= GROUND FORANALOG INPUTS
GND
AI3
= CO2 (0-10 VDC)
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
GND
= GROUND FORANALOG INPUTS
GND
= GROUND FORANALOG INPUTS
I2C
EXPANSION
WattMaster Label
AAON No.:
R96180
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY
RELAY4
COMMON
RELAY COMMON
#LB102061-A
Rev.: 1C
I2C
EXPANSION
RELAY1
RELAY2
RELAY3
RELAY4
Compressor Controller
SA
Digital
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only.
R1
R2
R3
R4
A1O
AO2
AO3
AO4
AO5
GND
+
COM
Also please note that when wiring the SA Expansion Module, its contacts must be wired as wet contacts (connected to 24 VAC).
Relay Output Contacts R1 Through R4 May Be User-Configured For The Following:
1 - Heating Stages 2 - Cooling Stages 3 - Warm-up Mode Command (VAV Boxes) 4 - Reversing Valve (Heat Pumps) 5 - Reheat Control (Dehumidification) 6 - Preheater For Low Ambient Protection 7 - Alarm 8 - Override 9 - Occupied 10 - Water Side Economizer
Note:
A Total Of 20 Relays Are Available By Adding Expansion Modules. Expansion Module Relay Outputs Are User Configurable As Listed Above.
Configurable Relay Output #1
Configurable Relay Output #2
Configurable Relay Output #3
Configurable Relay Output #4
Or Digital Scroll Compressor
(1.5 5, 0 10 r 2 10 VDC Input)
Note:
See Digital Scroll Wiring Detail For More Information.
Digital Scroll Compressor Only
GND
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions
Note:
1.) The Modulating Cooling Output Voltage Must Be Configured For
1.5 - 5 VDC Operation When YouAre Setting Up The SA Controller Operating Parameters For The Copeland Digital Compressor.
-
Modulating Heating Signal
(0 to 10 or 2-10 VDC Input)
+
COM
Modulating
Cooling Stage 1
Chilled Water Valve
--o-
+
COM
Modulating Cooling Stage 2
(1.5 - 5 VDC Input)
+
COM
WSE Bypass Valve A
Actuator
(2-10 VDC)
1 COM
2 +
3Y1
WSE Bypass Valve B
Actuator
(2-10 VDC)
1 COM
2 +
3Y1
Stage 1
Note:
1.) The Modulating Cooling Device Used Must Be Capable Of Accepting Either A 0­10 VDC, 2-10 VDC or
1.5-5.0 VDC Input. The Modulating Cooling
Output Voltage Is User Configurable For These Voltages. The Modulating Heating Devices Used Must Be Capable of Accepting Either A 0-10 VDC or 2­10 VDC Input. The Modulating Heating Output Voltage Is User­Configurable For These Voltages. These Voltage Outputs Must Also Be Configured When You Are Setting Up The SA Controller(s) Operating Parameters.
2.) Each Modulating Heating Or Cooling Device Used On The SA Controller Must Have (1) Relay Output Configured For Each Device Used, In Order To Enable The Modulating Heating And/Or Cooling Device's Sequence. This Relay Output Must Be Configured When Setting Up The SA Controller Operating Parameters.
Note:
See WSE Bypass Wiring Detail For More Information.
Figure 17: OE333-23-SA – SA Expansion Module Output Wiring
SA E-BUS Controller Technical Guide
21
Installation & Wiring
Suction Pressure Transducer Wiring
Zone
Zone
Suction Pressure Transducer
The OE275-01 Suction Pressure Transducer always wires directly to the Digital Scroll Compressor Controller. See Figure 18 below for wiring details.
24 VAC
GND
10 VA Minimum Power Required
For SA Expansion Module
Note:
1.) Suction Pressure Transducer(s) Are Only Required For Installations With The Dehumidification Option Installed.
2.) Modulating Cooling Output Voltage Must Be Configured For 1.5 - 5 VDC Operation When You Are Setting Up The SA Controller Operating Parameters For A Copeland Digital Compressor.
Wiring For Single Cabinet Unit
OE275-01
Suction Pressure Transducer
Splice Wire As Required To Reach From Transducer Location To Expansion Module Location
OE275-01
Suction Pressure Transducer
Additional Wiring For Dual Cabinet Units
Caution:
1.) The Schraeder Port Used For Installation Of The Suction Pressure Transducer Should Be Located In A Vertical Portion Of The Suction Line To Prevent Refrigerant Oil From Accumulating In The Sensor.
RD
WH
BK
RD
WH
BK
The Suction Pressure Transducer is used to measure suction pressure at the HVAC unit’s DX evaporator coil suction line. This suction line pressure is converted to saturated refrigerant temperature by the SA E­BUS Controller. This temperature is used by the SA E-BUS Controller to accurately control the compressors and reheat cycle components to provide optimum performance from the system during Dehumidifi ca- tion operation.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Module must be wired in such a way that the expansion module and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
24 VAC
POLARITY
WARNING
OBSERVE
Modular Cable
Connect To SA E-BUS
Controller
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITY MUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILL BE DAMAGED
MUST BE OBSERVED OR THE BOARD WILL BE DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUT
TO VCM-X INPUT
GND
TERMINALS AI5 & GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 = RELAY3 =
RELAY2 = RELAY4 =
RELAY1 = RELAY3 =
ITIS SUGGESTED THATYOU WRITE THE DESCRIPTION OF
RELAY2 = RELAY4 =
THE RELAYOUTPUTS YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITE THE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM 4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
BI2
= AIR PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1 = HOOD ON - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
BI5
= DIRTY FILTER - N.O. INPUT
BI2
= DRAIN PAN OVERFLOW -A - N.O. INPUT
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
= DRAIN PAN OVERFLOW - B - N.O. INPUT
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= DIRTY FILTER - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5 BI6
= REMOTE FORCED COOLING - N.O. INPUT
NOTE:
BI7
= SMOKE DETECTOR - N.C. INPUT
ALL BINARY INPUTS MUSTBE 24 VAC ONLY.
BI8
= REMOTE DEHUMIDIFICATION - N.O. INPUT
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALL BINARY INPUTS MUSTBE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
AO2
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1 = BUILDING PRESSURE CONTROL VFD OR
= MODULATING COOLING STAGE 2 SIGNAL
AO3
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
= MODULATING HEATING SIGNAL
AO2
= WSE BYPASS 2ASIGNAL
AO4
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
= MODULATING COOLING/DIGITALSCROLL
AO3
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
= RETURN AIR DAMPERACTUATOR
AO4
= GROUND FOR ANALOG OUTPUTS
GND
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
= RETURN AIR BYPASS DAMPERACTUATOR
AO5
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
AI3
= SUCTION PRESSURE A(0-5 VDC)
AI4
= SUCTION PRESSURE B (0-5 VDC)
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
AI3
= CO2 (0-10 VDC)
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
GND
= GROUND FOR ANALOG INPUTS
I2C
EXPANSION
EXPANSION
#LB102034-01
AAON No.:
R96180
www.orioncontrols.com
RELAYCONTACT RATING IS 1AMP MAX @ 24 VAC
RELAYCONTACT RATING IS 1AMP
RELAY1
MAX @ 24 VAC
RELAY2
RELAY1
RELAY3
RELAY2
RELAY4
RELAY3
RELAY
RELAY4
COMMON
RELAY COMMON
WattMaster Label
#LB102061-A
Rev.: 1C
I2C
SA
SA Expansion
Module
Figure 18: OE275-01 – Suction Pressure Transducer Wiring
22
SA E-BUS Controller Technical Guide
Modular Cable
Connect To Expansion
Module (When Used)
Installation & Wiring
SA Expansion Module Binary Inputs Wiring
SA Expansion Module Binary Inputs
The SA Expansion Module provides 8 Binary Inputs. See Figure 19 below for detailed wiring.
The transformer used for powering the SA Expansion Module must also be used to power the binary inputs.
10 VA Minimum Power Required
For SA Expansion Module
24 VAC
GND
Water Proof of Flow A - N.O. Input Water Proof of Flow B - N.O. Input
Air Proof Of Flow - N.O. Input Remote Forced Occupied-N.O. Input Emergency Shutdown - N.C. Input Drain Pan Overflow A - N.O. Input Drain Pan Overflow B - N.O. Input Dirty Filter - N.O. Input
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to­24VAC. Failure to observe polarity will result in damage to one or more of the boards. Expansion Module must be wired in such a way that the expansion module and the controller are always powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the expansion module.
POLARITY
WARNING
OBSERVE
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8
Warning: Do not apply any voltage greater than 24 VAC to the binary inputs. Higher voltages will damage the expansion module and possibly other components on the system.
24 VAC
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITY MUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILL BE DAMAGED
MUST BE OBSERVED OR THE BOARD WILL BE DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-A VCM-X EXPANSION MODULE
PR OUT
TO VCM-X INPUT
GND
TERMINALS AI5 & GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY 1 = RELAY 3 =
RELAY 2 = RELAY 4 =
RELAY1 = RELAY3 =
IT IS SUGGESTED THATYOU WRITE THE DESCRIPTION OF
RELAY2 = RELAY4 =
THE RELAYOUTPUTS YOUARE USING IN
IT IS SUGGESTED
THE BOXES
THATYOU WRITE THE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING IN THE BOXES PROVIDEDABOVE WITHA PERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM 4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
BI2
= AIR PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1 = HOOD ON - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
BI5
= DIRTY FILTER - N.O. INPUT
BI2
= DRAIN PAN OVERFLOW -A - N.O. INPUT
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
= DRAIN PAN OVERFLOW - B - N.O. INPUT
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= DIRTY FILTER - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
BI7
= SMOKE DETECTOR - N.C. INPUT
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
BI8
= REMOTE DEHUMIDIFICATION - N.O. INPUT
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALL BINARY INPUTS MUSTBE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
AO2
= MODULATING COOLING STAGE 1 SIGNAL
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1 = BUILDING PRESSURE CONTROL VFD OR
AO3
= MODULATING COOLING STAGE 2 SIGNAL
DAMPER ACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
= MODULATING HEATING SIGNAL
AO2
AO4
= WSE BYPASS 2ASIGNAL
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
= MODULATING COOLING/DIGITALSCROLL
AO3
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL (0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
= RETURN AIR DAMPERACTUATOR
AO4
= GROUND FOR ANALOG OUTPUTS
GND
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
= RETURN AIR BYPASS DAMPERACTUATOR
AO5
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
= INDOOR AIR RH SENSOR (0-5 VDC)
AI2
= SUCTION PRESSURE A(0-5 VDC)
AI3
= SUCTION PRESSURE B (0-5 VDC)
AI4
AI1 = OUTDOOR AIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG INPUTS
GND
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG INPUTS
GND
AI3
= CO2 (0-10 VDC)
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
GND
= GROUND FOR ANALOG INPUTS
I2C
EXPANSION
EXPANSION
#LB102034-01
AAON No.:
R96180
www.orioncontrols.com
RELAY CONTACT RATING IS 1AMP MAX @ 24 VAC
RELAYCONTACT RATING IS 1AMP
RELAY 1
MAX @ 24 VAC
RELAY 2
RELAY1
RELAY 3
RELAY2
RELAY 4
RELAY3
RELAY
RELAY4
COMMON
RELAY COMMON
WattMaster Label
#LB102061-A
Rev.: 1C
I2C
SA
Modular Cable
Connect To SA E-BUS
Controller
Modular Cable Connect To
Expansion Module
(When Used)
Figure 19: OE333-23-SA – SA Expansion Module 8 Binary Inputs Wiring
SA E-BUS Controller Technical Guide
SA Expansion
Module
23
Loading...
+ 51 hidden pages