Part Number Cross Reference ..................................................................................................................................................4
Features and Applications ........................................................................................................................................................5
SA E-BUS Controller Dimensions ............................................................................................................................................6
SA Expansion Module Dimensions ..........................................................................................................................................7
SA E-BUS Controller Component Locations ...........................................................................................................................9
INSTALLATION AND WIRING ........................................................................................................10
Important Wiring Considerations ...........................................................................................................................................10
SA E-BUS Controller Wiring ...................................................................................................................................................11
Digital Room Sensor ..........................................................................................................................................................12
Space Temperature Sensor ...............................................................................................................................................13
Remote SAT Reset Signal .................................................................................................................................................13
Supply Air Temperature Sensor ................................................................................................. ........................................14
Entering Water Temperature Sensor .................................................................................................................................15
Entering Air Temperature Sensor .......................................................................................................................................16
Water Side Economizer Valve ...........................................................................................................................................17
Water Side Economizer Bypass Valve ..............................................................................................................................17
Supply Fan VFD Signal or Zoning Bypass Damper Actuator Signal .................................................................................18
SA Expansion Module Input Wiring ........................................................................................................................................20
SA Expansion Module Output Wiring .....................................................................................................................................21
SA Expansion Module Binary Inputs ................................................................................................................................23
Entering Air Humidity Sensor .............................................................................................................................................24
SA E-BUS Controller to Module Wiring .................................................................................................................................32
Two Condenser Head Pressure Module ............................................................................................................................34
Water Source Heat Pump Modules ...................................................................................................................................35
START-UP AND COMMISSIONING ................................................................................................. 36
Addressing & Powering Up .....................................................................................................................................................36
Before Applying Power ......................................................................................................................................................36
Power Wiring ....................................................................................................................................................................36
Programming the Controller ...................................................................................................................................................37
www.aaon.com
WattMaster Controls Inc.
8500 NW River Park Drive · Parkville , MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
WattMaster Form : AA-SA-EBUS-TGD-01D
Copyright March 2015 WattMaster Controls, Inc.
AAON Part Number: V10910
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK.
Copeland Digital Scroll™ is a registered trademark of Copeland Corporation,
Sidney, OH
EBTRON® is a registered trademark of Ebtron, Inc., Loris, SC.
Neither WattMaster Controls, Inc. nor AAON
assumes any responsibility for errors or omissions in this document.
This document is subject to change without notice.
®
Table of Contents
INPUTS AND OUTPUTS ................................................................................................................ 38
SA E-BUS Controller Inputs and Outputs ..............................................................................................................................38
SA Expansion Module Inputs and Outputs ............................................................................................................................39
SEQUENCE OF OPERATION ..........................................................................................................41
Occupied/Unoccupied Mode of Operation .........................................................................................................................41
HVAC Modes of Operation ................................................................................................................................................41
Stage Control Window .......................................................................................................................................................42
Air Cooled Condenser Fan Operation ...............................................................................................................................43
Water Side Economizer Operation (Valves 1 & 2) .............................................................................................................43
Water Cooled Condenser (Valve 3) ...................................................................................................................................43
Chilled Water Cooling ........................................................................................................................................................44
Coil Temperature Reset .....................................................................................................................................................44
Reheat Control ..................................................................................................................................................................45
Coil Temperature Offset .....................................................................................................................................................45
Stage Control Window .......................................................................................................................................................46
Modulating Hot Water or Steam Heating ...........................................................................................................................46
Air to Air Heat Pump Operation .........................................................................................................................................46
Water Source Heat Pump Operation .................................................................................................................................47
Off Mode ............................................................................................................................................................................47
Supply Air Temperature Setpoint Reset .............................................................................................................................47
Supply Fan Control ............................................................................................................................................................48
Duct Static Pressure Control .............................................................................................................................................48
Entering Air Lockouts ......................................................................................................... ................................................49
Supply Air Cutoffs ..............................................................................................................................................................49
SA E-BUS Controller Alarms .............................................................................................................................................50
Force Modes or Overrides .................................................................................................................................................53
VAV Terminal Unit Controller Compatibility ........................................................................................................................53
VAV/Zone System & Zoning System .................................................................................................................................53
LED Diagnostics .......................................................................................................................................................................54
Diagnostic LED Operation .......................................................................................................................................................55
System Confi gurations ............................................................................................................................................................56
Stand-Alone System Layout ..............................................................................................................................................57
Interconnected System Layout ..........................................................................................................................................58
Networked System Layout .................................................................................................................................................59
Temperature Sensor Testing ...................................................................................................................................................60
OE265 Series RH Sensor Testing .....................................................................................................................................61
OE275-01 Suction Pressure Transducer Testing for R410A Refrigerant ...........................................................................63
INDEX ............................................................................................................................................ 64
SA E-BUS Controller Technical Guide 3
Overview
Part Number Cross Reference
PART DESCRIPTION
SA E-BUS ControllerOE332-23E-VCMX-SA-AV07160
SA Expansion ModuleOE333-23-SA-AR96180
12-Relay Expansion ModuleOE358-23-12RR69180
Two Condenser Head Pressure ModuleOE370-23-HP2CR90230
Water Source Heat Pump Protection Module - 410A OE334-23-WPM-AR88350
Water Source Heat Pump Protection Module - 410A - 20% GlycolOE334-23-WPM-A20R99750
Water Source Heat Pump Protection Module - 410A - 40% GlycolOE334-23-WPM-A40R99760
Bypass & Slave Interface CardPL101824N/A
Bypass Damper ActuatorOE281-04N/A
CommLink 5 Communications InterfaceOE361-13V32950
Digital Room Sensor - Temp & HumidityOE217-01R83870
Digital Room Sensor - Temp. OnlyOE217-00R83860
Duct Static Pressure SensorOE271P87100
Duct Temperature Sensor - 12" ProbeOE231R44940 / P87140
Duct Temperature Sensor - 6" ProbeOE230R36340
IP Module KitOE415-02R66770
MiniLink Polling DeviceOE364-22N/A
Modular Service Tool SD - Operator InterfaceOE391-12V28140
Modular System Manager SD - Operator InterfaceOE392-12V36570
Entering Air RH Sensor - 3% - 0-5 VDC OutputOE265-14R34700
Entering Air Temperature SensorOE250R34650
Room Mounted RH Sensor - 3% - 0-5 VDC OutputOE265-11R34690
Standard Room Sensor - PlainOE210R31480
Standard Room Sensor - w/ OverrideOE211P87040
Standard Room Sensor - w/ Override & Slide AdjustOE213P94320
Standard Room Sensor - w/ Slide AdjustOE212P94100
Static Pressure Pickup TubeOE290S18780
Suction Pressure TransducerOE275-01R28390
USB-Link 2 KitOE366R71870
ORION
PART NO:
AAON TULSA
PART NO:
4
SA E-BUS Controller Technical Guide
Overview
Features and Applications
Features
The Series A Controller (OE332-23E-VCMX-SA)—SA E-BUS Controller—is designed with 6 analog inputs, 2 analog outputs, and 5 relay
outputs. Most common HVAC unit control applications can be confi gured using only the SA E-BUS Controller; however, if needed, the
SA E-BUS Controller’s input and output capabilities can be expanded
with the SA Expansion Module ( OE333-23-SA) or 12-Relay Expansion
Module (OE358-23-12R) by means of a modular cable. The SA Expansion Module provides an additional 4 analog inputs, 5 analog outputs,
8 binary inputs, and 4 confi gurable relays. The 12-Relay Expansion
Module provides an additional 12 confi gurable relays.
The SA E-BUS Controller can also use the Two Condenser Head Pressure Module ( OE370-23-HP2C) for those applications requiring Head
Pressure Control. The SA E-BUS Controller can also use the WSHP
Module (OE334-23-WPM-A) for W ater Source Heat Pump applications.
Each SA E-BUS Controller can be confi gured for control of VAV Units
(with or without VAV/Zone Controllers), Constant Volume Units, and
Make-Up Air Units. Features include the following:
• Modulating Cooling Output ( Copeland Digital
Scroll™ Compressor or Chilled Water Valve Control)
• Modulating Heating Output ( Hot Water Valve,
Steam Valve, SCR Electric Heat Control)
• Full Integration with the AAON
Hot Gas Reheat Valve Controller
®
MHGRV Modulating
• Confi gurable for Air to Air and Water Source Heat Pump
Applications
• Advanced Dehumidifi cation Capabilities
• Adaptive Supply Air Reset
• Selectable Control Sensor
• Fan Proving Interlock
• Dirty Filter Alarm
• Emergency Shutdown Input (Smoke Detector/Firestat or
other Shutdown Conditions)
• Water Side Economizer Option
• Remote Occupied Capabilities
• 7-Day, 2-Event-per-Day Scheduling
• 14 Holiday Event Scheduling
• Optimal Start Scheduling
• Trend Logging Capability
• Static Pressure Control for Filter Loading Applications
• Head Pressure Control (with optional Two Condenser Head
Pressure Module)
• Additional Water Safeties (with optional Water
Source Heat Pump Module)
Applications
Variable Air Volume Unit
The SA E-BUS Controller can be confi gured to control a VFD Supply
Fan for Duct Static Pressure control. If the unit is not equipped with a
VFD, but Duct Static Pressure control is needed, a modulating Zoning
Bypass Damper can be controlled by the SA E-BUS Controller.
VAV units are typically designed for occupied Cooling with Morning
W arm-up Heating. This option is available with the SA E-BUS Controller. The SA E-BUS Controller can also be used for a Zoning System that
needs Duct Static Pressure control and Occupied Cooling and Heating.
The SA E-BUS Controller also has the ability to be confi gured for Duct
Static Pressure Control by controlling the Supply Fan VFD for the purpose of maintaining proper Duct Static Pressure in response to varying
fi lter loading conditions.
The SA E-BUS Controller allows Dehumidifi cation Priority on a VAV
unit. This could be useful on a building with a very low internal sensible
load, but which has a high internal and/or external latent load. During
VAV Dehumidifi cation, the SA E-BUS Controller activates Cooling
based on the Evaporator Coil Temperature and activates
lating Hot Gas Reheat to warm the Supply Air Temperature to the Active
Supply Air Temperature Setpoint.
Constant Air Volume Unit
The SA E-BUS Controller can be confi gured to activate a Constant
Volume Supply Fan. In most cases, this is a very basic unit with Space
Temperature control.
Make-Up Air Unit
The SA E-BUS Controller can be confi gured for 100% Outdoor Air
control for Make-Up Air. All HVAC Modes are determined from the
Outdoor Air Sensors. The Outdoor Air Volume must always be at least
50% or higher to be confi gured for Outdoor Air control.
Single or Dual Cabinet Unit
The SA E-BUS Controller can control an SA Series Single Cabinet Unit
or an SA Series Dual Cabinet Unit. Wiring for Dual Cabinet Units is
shown and noted on applicable Single Cabinet Unit diagrams.
AAON® Modu-
SA E-BUS Controller Technical Guide
5
Overview
SA E-BUS Controller Dimensions
5.985.98
8.388.38
0.290.29
7.837.83
2.752.75
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”
RS-485 COMMUNICATION LOOP. WIRE
RS-485 COMMUNICATION LOOP. WIRE
“R”TO“R”,“T”TO“T”“SHLD”TO“SHLD”
“R”TO“R”,“T”TO“T”“SHLD”TO“SHLD”
www.aaon.com
www.orioncontrols.com
www.orioncontrols.com
SACONTROLLERE-BUS
SACONTROLLERE-BUS
Orion No.:OE332-23E-VCMX-SA
OE332-23-VCMX-AVCM-X CONTROLLER
Orion No.:OE332-23E-VCMX-SA
AI1 = SPC (SPACE TEMPERATURE SENSOR)
AI1= SPC (SPACETEMPERATURE SENSOR)
AI1= SPC (SPACETEMPERATURE SENSOR)
AI2
= SAT (SUPPLYAIR TEMPERATURE SENSOR)
= SAT(SUPPLYAIRTEMPERATURE SENSOR)
AI2
= SAT(SUPPLYAIRTEMPERATURE SENSOR)
AI2
AI3
= EWT (ENTERING WATERTEMPERATURE SENSOR)
= EWT(ENTERING WATERTEMPERATURE SENSOR)
AI3
= RAT(RETURNAIRTEMPERATURE SENSOR)
AI3
AI4
= EAT (ENTERINGAIR TEMPERATURE SENSOR)
= EAT(ENTERINGAIRTEMPERATURE SENSOR)
AI4
= OAT(OUTDOORAIRTEMPERATURE SENSOR)
AI4
AI5
= NOT USED
= NOTUSED
AI5
AI5
= SUCTION PRESSURE SENSOR
AI7
= SPACE TEMPERATURE SENSOR SLIDEADJUST
= SPACETEMPERATURE SENSOR SLIDEADJUST
AI7
AI7
= SPACETEMPERATURE SENSOR SLIDEADJUST
OR VOLTAGE RESETSOURCE
OR VOLTAGE RESETSOURCE
OR VOLTAGE RESETSOURCE
A01
= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
= WATER SIDE ECONOMIZER VALVE 1A&1B (2-10 VDC)
A01
A01
= ECONOMIZER (2-10 VDC OUTPUT)
A02
= SUPPLY FAN VFD (0-10 VDC OUTPUT)
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
A02
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
E-BUS
CONNECTOR
CONNECTOR
ANALOG INPUT
ANALOG INPUT
ANALOG INPUT
JUMPER
JUMPER
JUMPER
SETTINGS
SETTINGS
SETTINGS
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
AI1
AI1
AI1
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
4-20mA
AI2
AI2
AI2
0-10V
0-10V
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI3
4-20mA
AI3
0-10V
0-10V
AI3
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI4
AI4
4-20mA
0-10V
0-10V
AI4
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI5
AI5
4-20mA
0-10V
0-10V
AI5
0-10V
0-5V
0-5V
0-5V
THERM
THERM
THERM
4-20mA
4-20mA
AI7
AI7
4-20mA
0-10V
0-10V
AI7
0-10V
0-5V
0-5V
0-5V
ANALOG INPUTJUMPER SETTINGS
ANALOG INPUTJUMPER SETTINGS
MUSTBE SETAS SHOWN FOR
MUSTBE SETAS SHOWN FOR
ANALOG INPUT JUMPER SETTINGS
PROPER OPERATION
PROPER OPERATION
MUST BE SETAS SHOWN FOR
PROPER OPERATION
PRESSURE
STATIC
STATIC
STATIC
PRESSURE
PRESSURE
WattMaster Label
WattMaster Label
#LB102060-01-A
WattMaster Label
#LB102033-01
Rev.: 1A
#LB102060-01-A
Rev.: 1A
LEDBLINKCODES
LED BLINK CODES
LEDNAMESTATUS1STATUS2
LED NAMESTATUS1 STATUS2
NORMALOPERATION01
NORMAL OPERATION01
SATFAIL12
SAT FAIL12
EATFAIL22
EAT FAIL22
SPCFAIL32
SPC FAIL32
MECHCOOLFAIL13
MECH COOL FAIL13
MECHHEATFAIL23
MECH HEAT FAIL23
FANPROOFFAIL33
FAN PROOF FAIL33
DIRTYFILTER43
DIRTY FILTER43
WATERFLOWALARM63
WATER FLOW ALARM63
DRAINPANALARM73
DRAIN PAN ALARM73
EMERGENCYSHUTDOWN53
EMERGENCY SHUTDOWN53
LOWSAT14
LOW SAT14
HIGHSAT24
HIGH SAT24
CONT.TEMPCOOLFAIL34
CONT. TEMP COOL FAIL34
CONT.TEMPHEATFAIL44
CONT. TEMP HEAT FAIL44
PUSHBUTTONOVR15
PUSH BUTTON OVR15
ZONEOVR25
ZONE OVR25
OUTPUTFORCEACTIVE06
OUTPUT FORCE ACTIVE06
WARNING!POLARITYMUST BE OBSERVED
WARNING!POLARITYMUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
OR THE CONTROLLER WILLBE DAMAGED
WARNING! POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
2
2
IC
IC
2
IC
EXPANSION
EXPANSION
EXPANSION
AAON No.:
AAON No.:
24 VAC POWER ONLY
RELAY CONTACT
RATING IS 1AMP
RELAYCONTACT
RELAYCONTACT
MAX @ 24 VAC
RATING IS 1AMP
RATING IS 1AMP
MAX @ 24 VAC
MAX @ 24 VAC
RELAY
RELAY
COMMON
RELAY
COMMON
COMMON
FAN
FAN
FAN
RELAY 2
RELAY2
RELAY2
RELAY 3
RELAY3
RELAY3
RELAY 4
RELAY4
RELAY4
RELAY 5
RELAY5
RELAY5
V07160
V07160
24 VAC POWER ONLY
24 VAC POWER ONLY
2
2
IC DIGITAL
IC DIGITAL
2
IC DIGITAL
SENSOR
SENSOR
SENSOR
OBSERVE
POLARITY
1.49
WARNING
4.104.10
0.700.70
Figure 1: OE332-23E-SA E-BUS Controller – SA E-BUS Controller Dimensions
6
SA E-BUS Controller Technical Guide
0.980.98
8.38
7.83
0.29
Overview
SA Expansion Module Dimensions
5.98
0.98
2.75
24 VAC
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE
OBSERVED OR
POLARITY
WARNING
OBSERVE
THE BOARD
WILL BE
DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUT
TO VCM-X INPUT
GND
TERMINALSAI5 & GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY 1 =RELAY 3 =
RELAY 2 =RELAY 4 =
RELAY1 =RELAY3 =
IT IS SUGGESTED
THATYOU WRITE THE
DESCRIPTION OF
RELAY2 =RELAY4 =
THE RELAYOUTPUTS
YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITETHE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING INTHE BOXESPROVIDEDABOVEWITHAPERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUSTBE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
www.orioncontrols.com
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT
BI2
= WATER PROOF OF FLOW - B - N.O. INPUT
BI3
= AIR PROOF OF FLOW - N.O. INPUT
BI4
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI1= HOOD ON - N.O. INPUT
BI5
= EMERGENCY SHUTDOWN - N.C. INPUT
= DIRTYFILTER - N.O. INPUT
BI2
BI6
= DRAIN PAN OVERFLOW -A - N.O. INPUT
= PROOF OF FLOW - N.O. INPUT
BI3
BI7
= DRAIN PAN OVERFLOW - B - N.O. INPUT
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI8
= DIRTY FILTER - N.O. INPUT
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
= SMOKE DETECTOR - N.C. INPUT
BI7
ALL BINARY INPUTS MUST BE 24 VAC ONLY.
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALLBINARYINPUTS MUSTBE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
AO2
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1=BUILDING PRESSURE CONTROLVFD OR
= MODULATING COOLING STAGE 2 SIGNAL
AO3
DAMPERACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
AO2
= MODULATING HEATING SIGNAL
= WSE BYPASS 2ASIGNAL
AO4
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
AO3
= MODULATING COOLING/DIGITALSCROLL
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
AO4
= RETURNAIR DAMPERACTUATOR
= GROUND FOR ANALOG OUTPUTS
GND
(0-10 VDC)
= GROUND FOR ANALOG OUTPUTS
GND
AO5
= RETURNAIR BYPASS DAMPERACTUATOR
(0-10 VDC)
GND
= GROUND FORANALOG OUTPUTS
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
GND
= GROUND FORANALOG OUTPUTS
AI2
= INDOOR AIR RH SENSOR (0-5 VDC)
AI3
= SUCTION PRESSURE A(0-5 VDC)
AI4
= SUCTION PRESSURE B (0-5 VDC)
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
GND
= GROUND FOR ANALOG INPUTS
= INDOORAIR RH SENSOR (0-5 VDC)
AI2
GND
= GROUND FOR ANALOG INPUTS
= CO2 (0-10 VDC)
AI3
= BUILDING STATIC PRESSURE (0-5 VDC)
AI4
= GROUND FORANALOG INPUTS
GND
= GROUND FORANALOG INPUTS
GND
I2C
EXPANSION
#LB102034-01
AAON No.:
WattMaster Label
#LB102061-A
Rev.: 1C
EXPANSION
R96180
RELAY CONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAYCONTACTRATING IS 1AMP
RELAY 1
MAX @ 24 VAC
RELAY 2
RELAY1
RELAY 3
RELAY2
RELAY 4
RELAY3
RELAY
RELAY4
COMMON
RELAYCOMMON
I2C
SA
0.70
4.10
Figure 2: OE333-23-SA – SA Expansion Module Dimensions
Figure 4: OE332-23E-SA – SA E-BUS Controller Component Locations
SA E-BUS Controller Technical Guide
9
Installation & Wiring
Important Wiring Considerations
Zone
Zone
General
Correct wiring of the SA E-BUS Controller is the most important
factor in the overall success of the controller installation process. In
general, most SA E-BUS Controllers are factory installed and wired at
the AAON
®
factory.
Controller Mounting
When the controller is to be fi eld mounted, it is important to mount the
controller in a location that is free from extreme high or low temperatures,
moisture, dust, and dirt. See Table 1 for a list of the required operating
conditions for the SA E-BUS Controller and associated modules.
The SA E-BUS Controller is housed in a plastic enclosure. It is designed
to be mounted by using the 3 mounting holes in the enclosure base. The
SA E-BUS Controller needs to be installed in an environment which can
maintain a temperature range between -30°F and 150°F not to exceed
90% RH levels (non-condensing). It is important to mount the controller
in a location that is free from extreme high or low temperatures, moisture,
dust, and dirt. Be careful not to damage the electronic components when
mounting the controller.
Considerations
The SA E-BUS Controller and associated modules must be connected
to a 24 VAC power source of the proper size for the calculated VA load
requirements. All transformer sizing should be based on the VA rating
listed in Table 1.
Device
Control
OE332-23E-SA E-BUS
Controller
SA E-BUS Controller
OE333-23-SA
SA Expansion Module24VAC
OE358-23-12R
12-Relay Expansion
Module
OE370-23-HP2C
Two Condenser Head
Pressure Module
OE334-23-WPM-A
Water Source Heat Pump
Module
24VAC8
24VAC15
24VAC5
24VAC8
Voltage
VA Load
-30°F to
150°F
-30°F to
10
150°F90% RH
-30°F to
150°F
-30°F to
150°F
-30°F to
150°F
Temperature
(Non-
Humidity
Condensing)
90% RH
90% RH
90% RH
90% RH
Warning: When using a single transformer to power more
than one controller or expansion module, the correct polarity must
always be maintained between the boards. Failure to observe correct
polarity will result in damage to the SA E-BUS Controller and
associated modules.
Please carefully read and apply the following information when wiring
the SA E-BUS Controller or its associated modules. See Figure 5 on
page 11 for the SA E-BUS Controller wiring diagram. See Figures 16
and 17 on pages 20 and 21 for SA Expansion Module wiring. And see Figure 25 on page 31 for 12-Relay Expansion Module wiring.
1. All wiring is to be in accordance with local and national
electrical codes and specifi cations.
2. Minimum wire size for 24 VAC wiring should be 18-gauge.
3. Minimum wire size for all sensors should be 24-gauge.
Some sensors require 2-conductor wire and some require
3-or 4-conductor wire.
4. Be sure that all wiring connections are properly inserted
and tightened into the terminal blocks. Do not allow wire
strands to stick out and touch adjoining terminals which
could potentially cause a short circuit.
5. When communication wiring is to be used to interconnect
SA E-BUS Controllers together or to connect to other
communication devices, all wiring must be plenum-rated,
minimum 18-gauge, 2-conductor, twisted pair with shield.
WattMaster can supply communication wire that meets this
specifi cation and is color coded for the network or localloop. Please consult your WattMaster distributor for
information. If desired, Belden #82760 or equivalent wire
may also be used.
6. Before applying power to the SA E-BUS Controller, be sure
to recheck all wiring connections and terminations
thoroughly.
Table 1: Voltage and Environment Requirements
10
SA E-BUS Controller Technical Guide
Installation & Wiring
SA E-BUS Controller Wiring
SA E-BUS Controller
The Series A Controller (OE332-23E-SA)—SA E-BUS Controller—is
designed with 6 analog inputs, 2 analog outputs, and 5 relay outputs.
Most common HVAC unit control applications can be confi gured us-
ing only the SA E-BUS Controller; however, if needed, the SA E-BUS
Controller’s input and output capabilities can be expanded with the SA
Expansion Module ( OE333-23-SA) or 12-Relay Expansion Module
( OE358-23-12R) by means of a modular cable.
For Stand Alone Applications,
Connect To System Manager. For Network
Applications Connect To Next Controller And/Or
MiniLink PD On Local Loop.
SA E-BUS Controller
RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T”TO “T” “SHLD” TO “SHLD”
SACONTROLLERE-BUS
Orion No.:OE332-23E-VCMX-SA
AI1 = SPC (SPACETEMPERATURE SENSOR)
AI2
= SAT(SUPPLY AIR TEMPERATURE SENSOR)
AI3
= EWT (ENTERING WATERTEMPERATURE SENSOR)
AI4
= EAT(ENTERING AIR TEMPERATURE SENSOR)
AI5
= NOT USED
AI7
= SPACETEMPERATURE SENSOR SLIDE ADJUST
OR VOLTAGE RESETSOURCE
A01
= WATER SIDE ECONOMIZER VALVE 1A &1B (2-10 VDC)
A02
= SUPPLYFAN VFD (0-10 VDC OUTPUT)
E-BUS
CONNECTOR
ANALOG INPUT
JUMPER
SETTINGS
THERM
LED NAMESTATUS1 STATUS2
4-20mA
AI1
AI2
AI3
AI4
AI5
AI7
ANALOG INPUTJUMPER SETTINGS
MUSTBE SET AS SHOWN FOR
PROPER OPERATION
STATIC
PRESSURE
NORMALOPERATION01
0-10V
0-5V
SATFAIL12
THERM
EATFAIL22
4-20mA
SPCFAIL32
0-10V
MECHCOOL FAIL13
0-5V
MECHHEAT FAIL23
THERM
4-20mA
FANPROOF FAIL33
0-10V
DIRTYFILTER43
0-5V
WATERFLOW ALARM63
THERM
DRAINPAN ALARM73
4-20mA
0-10V
EMERGENCYSH UTDOWN 53
0-5V
LOWSAT14
THERM
HIGHSAT24
4-20mA
CONT.TEMP COOL FAIL34
0-10V
CONT.TEMP H EAT FAIL44
0-5V
PUSHBUTTON OVR15
THERM
4-20mA
ZONEOVR25
0-10V
OUTPUTFORCE ACTIVE06
0-5V
WattMaster Label
#LB102060-01-A
Rev.: 1A
EXPANSION
All Comm Loop Wiring Is
Straight Thru
T to T, R to R & SHLD to SHLD
See Individual
Component Wiring
Diagrams For Detailed
Wiring Of Analog Inputs
And Outputs
AI1 SETAI2 SET AI3 SET
AI4 SETAI5 SETAI7 SET
Local Loop
RS-485
9600 Baud
Jumpers
NOTE: Only one SA E-BUS Controller is required whether
the SA Unit is a Single Cabinet or Dual Cabinet Unit. Additional
wiring for Dual Cabinet Units is shown and noted as such on the
applicable Single Cabinet Unit Diagrams.
Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
1 Amp Maximum Load.
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAY
COMMON
FAN
RELAY2
RELAY3
RELAY4
RELAY5
AAON No.:
V07160
LED BLINK CODES
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILLBE DAMAGED
2
IC
2
IC DIGITAL
SENSOR
R - 24VAC
G - Fan ON/OFF Only
Relay Output Contacts
R2 Thru R5 May Be User Configured
For The Following:
1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command
(VAV Boxes)
4 - Reversing Valve (Air To Air Heat
Pumps)
5 - Reheat Control (Dehumidification)
6 - Preheater For Low Ambient
Protection
7 - Alarm
8 - Override
9 - Occupied
10 - Water Side Economizer
A Total Of 20 Relays Are Available
Note:
By Adding Expansion Modules.
Expansion Module Relay Outputs Are
User-Configurable As Listed Above.
GND
Line Voltage
24VAC
Size Transformer For
Correct Total Load.
SA Controller = 8 VA
Splice If Required
Connect To
Expansion Module
(When Used)
OE271
Static Pressure
Transducer
Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere
Note:
Only One SA Controller is Required Whether The SA Unit is a Single Cabinet
Or Dual Cabinet Unit. Additional Wiring For Dual Cabinet Units is Shown and
Noted As Such On The Applicable Single Cabinet Unit Diagrams.
Figure 5: OE332-23E-SA E-BUS Controller – SA E-BUS Controller Wiring
SA E-BUS Controller Technical Guide
Connect To Digital Room Sensor - See Digital Room Sensor
Wiring Diagram.
Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.
11
Installation & Wiring
Digital Room Sensor Wiring
Digital Room Sensor
The OE217-00 Digital Room Sensor is used to sense Space Temperature
and the OE217-01 Digital Room Sensor is used to sense Space Temperature and Space Humidity. The Sensor connects to the SA E-BUS
Controller with the TSDRSC modular cable. It should be mounted at approximately 5 ft. above the fl oor on the wall in an area that does not have
drafts or is exposed to direct sunlight. See Figure 6 for wiring details.
Note: TheConnects
Directly To TheController Using
TSDRSC Cable
AOf The Appropriate
Length.
160 Feet.
Digital Room Sensor
SA E-BUS
The Maximum Length Allowed Is
Zone
Zone
I1 SET
AI1
AI2 SET AI3 SET
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
4-20mA
AI2
0-10V
0-5V
THERM
4-20mA
AI3
0-10V
0-5V
THERM
EMERGENCY SHUTDOWN
4-20mA
AI4
0-10V
0-5V
THERM
4-20mA
AI5
0-10V
0-5V
THERM
4-20mA
AI7
0-10V
0-5V
ANALOG INPUT JUMPER SETTINGS
MUST BE SETAS SHOWN FOR
PROPER OPERATION
STATIC
WattMaster Label
#LB102033-01
PRESSURE
24 VAC POWER ONLY
WARNING!POLARITY MUST BE OBSERVED
OR THE CONTROLLER WILL BE DAMAGED
I2C
EXPANSION
I2C DIGITAL
SENSOR
OVERRIDEALARM
Display
Override
Digital Room Sensor
Figure 6: OE217-00 & OE217-01 – Digital Room Sensor Wiring
SA E-BUS Controller
TSDRSC Cable
Note: No Additional Wiring is Required For
Dual Cabinet Units.
12
SA E-BUS Controller Technical Guide
Installation & Wiring
GND
TMP
Space Temperature Sensor
OVR
R
E
L
O
C
R
E
M
R
O
A
W
AUX
Wire Required For
Sensors With Slide
Adjust Option Only
Set Jumper For THERM
When Space Sensor Slide
Adjust Is Wired To AI7
AI1
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply
Air Temperature Reset Signal Option (By
Others) May Be Connected To An AI7 On
The SA E-BUS Controller. Only One Option
Is Allowed, Not Both.
AI1
AI7
GND
SA E-BUS Controller
Note: No Additional Wiring is
Required For Dual Cabinet
Units.
AI7 SET
Remote Supply Air
Temperature Reset Signal
(By Others)
0-5 VDC or 0-10 VDC Signal
GND
Note:
Either The Slide Offset Option For The Space Temperature
Sensor Or The Remote Supply Air Temperature Reset
Signal Option (By Others) May Be Connected To AI7 On
The SA E-BUS Controller. Only One Option Is Allowed,
Not Both.
Regardless of Whether the Remote
SAT Reset Signal Has Been
Configured For 0-5 or 0-10 VDC,
Jumper Must Be Set For 0-10V
AI7
GND
SA E-BUS Controller
AI1
AI1 SET AI2 SET AI3 SET
AI4 SET AI5 SET AI7 SET
AI2
AI3
AI4
AI5
AI7
Note: No Additional Wiring
is Required For Dual Cabinet
Units.
AI7 SET
SAT & Remote SAT Reset Signal Wiring
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor is typically used for constant volume HVAC unit applications controlling one
zone. The Space T emperature Sensor is a 10K T ype III thermistor sensor
and should be mounted approximately 5 feet above the fl oor in the space
that is to be controlled. The Space Temperature Sensor is available as a
sensor only, sensor with override button, sensor with slide adjust, and
sensor with slide adjust and override confi gurations.
When the Remote Supply Air T emperature Reset Signal option is needed,
the Slide Offset option on the Room Sensor cannot be used. Only one
of these options may be used on the SA E-BUS Controller.
See Figure 7 below for complete Space Temperature Sensor wiring
details.
Remote SAT Reset Signal
A Remote Supply Air T emperature Reset Signal can be connected to AI7
for applications requiring remote reset of the Supply Air Temperature
Setpoint.
When the Slide Offset option on the Room Sensor is used, the Remote
Supply Air Temperature Reset Signal cannot be used. Only one of these
options may be used on the SA E-BUS Controller.
The SA E-BUS Controller can accept either a 0-5 VDC signal or a 0-10
VDC signal on this input.
See Figure 8 below for complete Remote SAT Reset Signal wiring
details.
Figure 7: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring
Figure 8: Remote Supply Air Temperature Reset Signal Wiring
SA E-BUS Controller Technical Guide
13
Installation & Wiring
SAT Sensor Wiring
Zone
Zone
Supply Air Temperature Sensor
The OE231 Supply Air Temperature Sensor must be wired as shown
in Figure 9 below for proper operation. The Supply Air Temperature
Sensor is a 10K Type III thermistor sensor. The Supply Air Temperature Sensor should be mounted in the unit discharge plenum or in the
supply air duct.
Supply Air Temperature Sensor
Mount In HVAC
Unit Supply
Air Duct
Note: No Additional Wiring
is Required For Dual Cabinet
Units.
NOTE: For Dual Cabinet Units, mount the Supply Air
Temperature Sensor in a Supply Air Ducting area that is common
to both SA Units.
AI1 SET AI2 SET AI3 SET
AI2
GND
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure The Jumper Is
Set For THERM On AI2 For
Supply Air Temperature
Sensor When Used
Figure 9: OE231 – Supply Air Temperature Sensor Wiring
SA E-BUS Controller
14
SA E-BUS Controller Technical Guide
Installation & Wiring
Entering Water Temperature Sensor Wiring
Entering Water Temperature Sensor
The OE233 Entering W ater T emperature Sensor must be wired as shown
in Figure 10 below for proper operation. The Entering Water Tempera-
ture Sensor is a 10K Type III thermistor sensor. The Entering Water
Temperature Sensor should be mounted in the entering water piping.
Entering Water
Temperature Sensor
(Strap On)
Note: No Additional Wiring
is Required For Dual Cabinet
Units.
AI3
GND
NOTE: For Dual Cabinet Units, mount the Entering Water
Temperature Sensor in an Entering Water Piping area that is
common to both SA Units.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
SA E-BUS Controller
Be Sure Jumper Is Set
For THERM
On AI3 For Entering
Water Temperature Sensor
Butt Splice Or Wire Nut Wire Leads And
Extend Wire To Controller Terminals. Connect
One Wire Lead To Entering Water
Temperature Terminal (AI3) At The Controller.
Secure Other Wire Lead To Ground Terminal
At The Controller. See Note 3.
Secure Sensor Element And Thermal
Mastic Strip To Pipe With Supplied
Wire Tie. Be Sure To Tighten Wire Tie
Snugly To Ensure Good Thermal
Contact.
Sensing Element
(Supplied)
Entering Water Temperature Sensor
Wire Tire
(Supplied)
Thermal Mastic Strip
(Supplied)
Notes:
1.)Sensor Should Be Mounted At
Location Along Pipe Length
That Best Represents Desired
Temperature Reading.
2.)Sensing Element Shown
Mounted To Top Of Pipe. The
Sensor Element May Be Located
At Any Location Around Pipe.
3.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
Entering Water Pipe
See Note 1 & 2.
Thermal Mastic
PlaceBetween Pipe
And Sensing Element. Pipe Should
Be Clean And Smooth To Provide
Proper Thermal Contact With
Sensing Element.
Caution:
For Accurate Temperature
Readings It Is Necessary To
Place Insulation Over The
Sensor After Installation.
This Prevents The Ambient
Temperature From Affecting
The Sensor. Insulation
Should Cover The Sensor
And Extend 6“ to 12”
Beyond Each End Of The
Sensor.
Figure 10: OE233 – Entering Water Temperature Sensor Installation & Wiring
SA E-BUS Controller Technical Guide
15
Zone
Installation & Wiring
Entering Air Temperature Sensor Wiring
Zone
Entering Air Temperature Sensor
The OE231 Entering Air Temperature Sensor must be wired as shown
in Figure 11 below for proper operation of the SA E-BUS Controller.
The Entering Air Temperature Sensor is a 10K Type III thermistor sensor. The sensor should be mounted as shown in an area that is protected
from the elements and direct sunlight.
Entering Air
Temperature Sensor
Mount In Entering
Air Stream
NOTE: For Dual Cabinet Units, mount the Entering Air
Temperature Sensor in an Entering Air Duct area that is common
to both SA Units.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI4
GND
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Be Sure Jumper Is Set
For THERM
On AI4 For Entering
Air Temperature Sensor
Note: No Additional Wiring
is Required For Dual Cabinet
Units.
Figure 11: OE231 – Entering Air Temperature Sensor Wiring
SA E-BUS Controller
16
SA E-BUS Controller Technical Guide
Installation & Wiring
3 (Y)
3 (Y)
5 (U)
5 (U)
2 (+)
2 (+)
1 (-)
1 (-)
Water Side Economizer Wiring
Water Side Economizer (WSE) Valve(s)
The Water Side Economizer Valve(s) must be wired as shown in Figure
12 below for proper operation of the SA E-BUS Controller. The Water
Side Economizer V alve(s) connects to AO1 on the SA E-BUS Controller .
NOTE: For Dual Cabinet Units, wire the Second Cabinet’s WSE
Valve Actuator in parallel with the First Cabinet’s WSE Valve
Actuator.
Note: Required For Dual SA Unit
Applications Only.
WSE Valve 1B - Actuator
GND
24 VAC
2-10 VDC
Water Side Economizer (WSE) Bypass
Valve
The W ater Side Economizer Bypass Valve(s) must be wired as shown in
Figure 13 below for proper operation of the SA E-BUS Controller. The
W ater Side Economizer Bypass Valve(s) are wired to AO4 and AO5 on
the SA Expansion Module.
NOTE: For Dual Cabinet Units, wire the Second Cabinet’s WSE
Bypass Valve Actuator to AO5 on the SA Expansion Module.
24 VAC Power Source
Sized For Actuator(s) VA Load
WSE Valve 1A - Actuator
GND
24 VAC
2-10 VDC
AO1
GND
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET
AI7
AI7 SET
2 Way Modulating Water Side Economizer Valve
WSE Valve 1B
2 Way Modulating Water Side Economizer Valve
Figure 12: Water Side Economizer Valve Wiring
Figure 13: Water Side Economizer Bypass Valve Wiring
SA E-BUS Controller
WSE Valve 1A
SA E-BUS Controller Technical Guide
17
Installation & Wiring
+
+
_
_
Supply Fan VFD Signal
Zone
Zone
Supply Fan VFD Signal or Zoning
Bypass Damper Actuator Signal
The Supply Fan VFD or Zoning Bypass Damper Actuator Signal is a
0-10 VDC output from AO2 on the SA E-BUS Controller. This signal
output can be connected to the Supply Fan Variable Frequency Drive to
modulate the Supply Fan speed and control Duct Static Pressure utilizing
the Duct Static Pressure Sensor connected to the SA E-BUS Controller .
Alternatively, it can be connected to a Zoning Bypass Damper Actuator
that will modulate the Zoning Bypass Damper Actuator to control Duct
Static Pressure utilizing the Duct Static Pressure Sensor connected to the
SA E-BUS Controller . A Duct Static Pressure Sensor must be connected
in order for the VFD or Zoning Bypass Damper Actuator to operate. See
Figures 14 and 15 for detailed wiring.
0-10 VDC Input From AO2
GND
Shield
Supply Fan Variable Frequency Drive #1
(By Others)
0-10 VDC Input From AO2
GND
Shield
Caution: Variable Frequency Drive units can cause large transient
noise spikes which can cause interference to be propagated on other
electronic equipment. Use shielded wire wherever possible and route
all sensor and controller wiring away from the Variable Frequency
Drive and the HVAC Unit electrical wiring.
NOTE: For Dual Cabinet Units, VFD #2 must be wired in
parallel to VFD #1 as shown in Figure 14 below.
AI1 SET AI2 SET AI3 SET
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
Supply Fan Variable Frequency Drive #2
Caution:
The VFD Unit Must Be Configured For 0-10 VDC Input.
The Input Resistance At The VFD Must Not Be Less
Than 1000 Ohms When Measured At The VFD
Terminals With All Input Wires Removed.
Figure 14: Supply Fan VFD Wiring
(By Others)
Note: Required For Dual SA Unit
Applications Only.
Note:
Wire To The VFD Using 18 GA Minimum 2
Conducter Twisted Pair With Shield Cable.
Wire Shield To GND As Shown
AO2
GND
Shield
SA E-BUS Controller
18
SA E-BUS Controller Technical Guide
3 (Y)
5 (U)
2 (+)
1 (-)
Supply Fan VFD Signal or Zoning
Bypass Damper Actuator Signal
When the Bypass Damper is used (Zoning applications), be sure the
Bypass Duct and Damper are designed so that Supply Air will bypass
to the Entering Air Duct, ensuring equal airfl ow to both cabinets.
24 VAC Power Source
Sized For Actuator VA Load
Installation & Wiring
Zoning Bypass Damper Actuator
AI1 SET AI2 SET AI3 SET
Note: No Additional Wiring
is Required For Dual Cabinet
Units.
Bypass Damper Actuator
(Belimo Actuator Shown)
GND
24 VAC
0-10 VDC
Belimo Actuator Wiring
Shown. Consult Factory For
Other Manufacturer Wiring
Instructions
Figure 15: Zoning Bypass Damper Actuator Wiring
AI1
AI2
AI3
AI4
AI5
AI4 SET AI5 SET AI7 SET
AI7
AO2
GND
SA E-BUS Controller
SA E-BUS Controller Technical Guide
19
Installation & Wiring
SA Expansion Module Input Wiring
Zone
Zone
SA Expansion Module
Two different Expansion Modules are available for use with the SA EBUS Controller to provide additional inputs and outputs beyond those
found on the SA E-BUS Controller.
The SA Expansion Module ( OE333-23-SA E-BUS Controller) provides
8 Binary Inputs, 4 Analog Inputs, 5 Analog Outputs, and 4 Confi gurable
Relay Outputs. See Figures 16 and 17 for complete wiring details.
10 VA Minimum Power Required
For SA Expansion Module
See Suction Pressure
Transducer Wiring Details For
Complete Wiring Information.
See Humidity Sensor Wiring
Details For Complete Wiring
Information.
Entering Air
Humidity Sensor
VAC OR DC
GND
0-5V
Indoor Air
Humidity Sensor
VOUT (0-5V)
GND
24 VAC
GND
Additional Suction
Pressure Sensor Required
On Dual Units Only.
Suction Pressure
Transducer #2
Suction Pressure
Transducer #1
Splice Wire As Required To Reach
From Transducer Location To
Expansion Module Location
Water Proof of Flow A- N.O. Input
Water Proof of Flow B - N.O. Input
Air Proof Of Flow - N.O. Input
Remote Forced Occupied - N.O. Input
Emergency Shutdown - N.C. Input
Drain Pan Overflow A - N.O. Input
Drain Pan Overflow B - N.O. Input
Dirty Filter - N.O. Input
VIN
WH
BK
RD
RD
WH
BK
The 12-Relay Expansion Module ( OE358-23-12R) provides for 12
Dry Contact Confi gurable Relay Outputs. See Figure 25 for complete
wiring details.
The expansion modules can be used individually or together to provide
the required inputs and outputs for your specifi c applications.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Module must be wired in such a way that the expansion
module and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.
24 VAC
GND
GND
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE
OBSERVED OR
POLARITY
WARNING
OBSERVE
THE BOARD
WILL BE
DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUTGND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 =RELAY3 =
B 1I
B 2I
B 3I
B 4I
B 5I
B 6I
B 7I
BI8
AI1
AI2
AI3
AI4
RELAY2 =RELAY4 =
RELAY1 =RELAY3 =
ITIS SUGGESTED
THATYOU WRITE THE
DESCRIPTION OF
RELAY2 =RELAY4 =
THE RELAYOUTPUTS
YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITETHE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING INTHE BOXESPROVIDEDABOVEWITHAPERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUST BE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUSTBE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
#LB102034-01
AAON No.:
R96180
www.orioncontrols.com
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
TO VCM-X INPUTTERMINALSAI5 & GND
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
BI2
= AIR PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1= HOOD ON - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
BI5
= DIRTYFILTER - N.O. INPUT
BI2
= DRAIN PAN OVERFLOW -A - N.O. INPUT
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
= DRAIN PAN OVERFLOW - B - N.O. INPUT
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= DIRTY FILTER - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5
= REMOTE FORCED COOLING - N.O. INPUT
BI6
NOTE:
= SMOKE DETECTOR - N.C. INPUT
BI7
ALL BINARY INPUTS MUSTBE 24 VAC ONLY.
= REMOTE DEHUMIDIFICATION - N.O. INPUT
BI8
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALLBINARYINPUTS MUSTBE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
AO2
= MODULATING COOLING STAGE 1 SIGNAL
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1=BUILDING PRESSURE CONTROLVFD OR
AO3
= MODULATING COOLING STAGE 2 SIGNAL
DAMPERACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
AO2
= MODULATING HEATING SIGNAL
= WSE BYPASS 2ASIGNAL
AO4
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
AO3
= MODULATING COOLING/DIGITALSCROLL
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
AO4
= RETURNAIR DAMPERACTUATOR
GND
= GROUND FOR ANALOG OUTPUTS
(0-10 VDC)
GND
= GROUND FOR ANALOG OUTPUTS
AO5
= RETURNAIR BYPASS DAMPERACTUATOR
(0-10 VDC)
GND
= GROUND FORANALOG OUTPUTS
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
GND
= GROUND FORANALOG OUTPUTS
= INDOOR AIR RH SENSOR (0-5 VDC)
AI2
= SUCTION PRESSURE A(0-5 VDC)
AI3
= SUCTION PRESSURE B (0-5 VDC)
AI4
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG INPUTS
GND
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
= GROUND FOR ANALOG INPUTS
GND
AI3
= CO2 (0-10 VDC)
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
GND
= GROUND FORANALOG INPUTS
GND
= GROUND FORANALOG INPUTS
EXPANSION
RELAYCONTACTRATING IS 1AMPMAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY
RELAY4
COMMON
RELAYCOMMON
WattMaster Label
I2C
#LB102061-A
Rev.: 1C
EXPANSION
RELAY1
RELAY2
RELAY3
RELAY4
I2C
SA
SA Expansion Module
Figure 16: OE333-23-SA – SA Expansion Module Input Wiring
20
SA E-BUS Controller Technical Guide
Modular Cable
Connect To SA E-BUS
Controller
Modular Cable
Connect To Next Expansion
Module (When Used)
Installation & Wiring
SA Expansion Module Output Wiring
The SA Expansion Module must be connected to 24 VAC as shown in
the wiring diagram below. Please see Table 1 on page 10 for correct VA
requirements to use when sizing the transformer(s) used for powering
the expansion module.
24 VAC
GND
10 VA Minimum Power
Required For SA
Expansion Module
SA Expansion
Module
POLARITY
WARNING
OBSERVE
Modular Cable
Connect To Expansion
Module (When Used)
Modular Cable
Connect To SAE-BUS
Controller
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VACto-24VAC. Failure to observe polarity will result in damage to one or more of
the boards. Expansion Module must be wired in such a way that the
expansion module and the controller are always powered together. Loss of
power to the expansion module will cause the controller to become
inoperative until power is restored to the expansion module.
24 VAC
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE
OBSERVED OR
THE BOARD
WILLBE
DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUTGND
+VSIGGND
RELAY1 =RELAY 3 =
RELAY2 =RELAY 4 =
RELAY1 =RELAY3 =
ITIS SUGGESTED
THATYOU WRITE THE
DESCRIPTION OF
RELAY2 =RELAY4 =
THE RELAYOUTPUTS
YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITETHE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING INTHE BOXESPROVIDEDABOVEWITHAPERMANENT
ANALOG INPUT
MARKER (SHARPIE®)
JUMPER SETTINGS
MUSTBE SET AS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER SETTINGS
MUSTBE SETAS
SHOWN FOR
PROPER
ANALOG INPUT
OPERATION
JUMPER
SETTINGS
THERM
ANALOG INPUT
4-20mA
JUMPER
AI1
0-10V
SETTINGS
0-5V
THERM
THERM
4-20mA
4-20mA
AI1
AI2
0-10V
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI2
4-20mA
0-10V
AI3
0-10V
0-5V
0-5V
THERM
THERM
4-20mA
AI3
4-20mA
0-10V
AI4
0-10V
0-5V
0-5V
THERM4-20mA
AI4
0-10V
I2C
0-5V
EXPANSION
I2C
WattMaster Label
EXPANSION
#LB102034-01
www.orioncontrols.com
TO VCM-X INPUTTERMINALSAI5 & GND
SUCTION PRESSURETRANSDUCER CONNECTIONFOR HVAC UNITS WITHOUTDIGITALCOMPRESSOR
BI1 = WATER PROOF OF FLOW -A - N.O. INPUT
= WATER PROOF OF FLOW - B - N.O. INPUT
BI2
=AIR PROOF OF FLOW - N.O. INPUT
BI3
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
BI1= HOOD ON - N.O. INPUT
= EMERGENCY SHUTDOWN - N.C. INPUT
BI5
= DIRTYFILTER - N.O. INPUT
BI2
= DRAIN PAN OVERFLOW -A - N.O. INPUT
BI6
= PROOF OF FLOW - N.O. INPUT
BI3
= DRAIN PAN OVERFLOW - B - N.O. INPUT
BI7
= REMOTE FORCED OCCUPIED - N.O. INPUT
BI4
= DIRTY FILTER - N.O. INPUT
BI8
= REMOTE FORCED HEATING - N.O. INPUT
BI5BI6
= REMOTE FORCED COOLING - N.O. INPUT
NOTE:
BI7
= SMOKE DETECTOR - N.C. INPUT
ALL BINARYINPUTS MUST BE 24 VAC ONLY.
BI8
= REMOTE DEHUMIDIFICATION - N.O. INPUT
NOTE:
AO1 = MODULATING HEATING SIGNAL
ALLBINARYINPUTS MUSTBE 24 VAC ONLY.
(0-10 VDC OR 2-10 VDC)
= MODULATING COOLING STAGE 1 SIGNAL
AO2
(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
AO1=BUILDING PRESSURE CONTROLVFD OR
= MODULATING COOLING STAGE 2 SIGNAL
AO3
DAMPERACTUATOR (0-10 OR 2-10 VDC)
(DIGITALCOMPRESSOR ONLY 1.5-5 VDC)
= MODULATING HEATING SIGNAL
AO2
= WSE BYPASS 2ASIGNAL
AO4
(0-10 VDC OR 2-10 VDC)
(0-10 VDC)
= MODULATING COOLING/DIGITALSCROLL
AO3
= WSE BYPASS 2B SIGNAL
AO5
SIGNAL(0-10 VDC, 2-10 VDC OR 1.5-5 VDC)
(0-10 VDC)
= RETURNAIR DAMPERACTUATOR
AO4
= GROUND FORANALOG OUTPUTS
GND
(0-10 VDC)
= GROUND FORANALOG OUTPUTS
GND
AO5
= RETURNAIR BYPASS DAMPERACTUATOR
(0-10 VDC)
GND
= GROUND FORANALOG OUTPUTS
AI1 = ENTERING AIR RH SENSOR (0-5 VDC)
GND
= GROUND FORANALOG OUTPUTS
= INDOORAIR RH SENSOR (0-5 VDC)
AI2
= SUCTION PRESSUREA (0-5 VDC)
AI3
= SUCTION PRESSURE B (0-5 VDC)
AI4
AI1= OUTDOORAIR RH SENSOR (0-5 VDC)
= GROUND FORANALOG INPUTS
GND
AI2
= INDOORAIR RH SENSOR (0-5 VDC)
= GROUND FORANALOG INPUTS
GND
AI3
= CO2 (0-10 VDC)
AI4
= BUILDING STATIC PRESSURE (0-5 VDC)
GND
= GROUND FORANALOG INPUTS
GND
= GROUND FORANALOG INPUTS
I2C
EXPANSION
WattMaster Label
AAON No.:
R96180
RELAYCONTACT
RATING IS 1AMP
MAX @ 24 VAC
RELAYCONTACTRATING IS 1AMPMAX @ 24 VAC
RELAY1
RELAY2
RELAY3
RELAY
RELAY4
COMMON
RELAYCOMMON
#LB102061-A
Rev.: 1C
I2C
EXPANSION
RELAY1
RELAY2
RELAY3
RELAY4
Compressor Controller
SA
Digital
Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
R1
R2
R3
R4
A1O
AO2
AO3
AO4
AO5
GND
+
COM
Also please note that when wiring the SA Expansion Module, its contacts
must be wired as wet contacts (connected to 24 VAC).
Relay Output Contacts R1 Through
R4 May Be User-Configured For The
Following:
A Total Of 20 Relays Are
Available By Adding Expansion
Modules. Expansion Module Relay
Outputs Are User Configurable As
Listed Above.
Configurable Relay Output #1
Configurable Relay Output #2
Configurable Relay Output #3
Configurable Relay Output #4
Or Digital Scroll Compressor
(1.5 5, 0 10 r 2 10 VDC Input)
Note:
See Digital Scroll
Wiring Detail For
More Information.
Digital Scroll Compressor Only
GND
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions
Note:
1.) The Modulating Cooling Output Voltage Must Be Configured For
1.5 - 5 VDC Operation When YouAre Setting Up The SA Controller
Operating Parameters For The Copeland Digital Compressor.
-
Modulating Heating Signal
(0 to 10 or 2-10 VDC Input)
+
COM
Modulating
Cooling Stage 1
Chilled Water Valve
--o-
+
COM
Modulating Cooling Stage 2
(1.5 - 5 VDC Input)
+
COM
WSE Bypass Valve A
Actuator
(2-10 VDC)
1 COM
2 +
3Y1
WSE Bypass Valve B
Actuator
(2-10 VDC)
1 COM
2 +
3Y1
Stage 1
Note:
1.) The Modulating
Cooling Device Used
Must Be Capable Of
Accepting Either A 010 VDC, 2-10 VDC or
1.5-5.0 VDC Input.
The Modulating
Cooling
Output Voltage
Is User Configurable For
These Voltages. The
Modulating Heating
Devices Used Must Be
Capable of Accepting
Either A 0-10 VDC or 210 VDC Input. The
Modulating Heating
Output Voltage Is UserConfigurable For These
Voltages. These Voltage
Outputs Must Also Be
Configured When You
Are Setting Up The SA
Controller(s) Operating
Parameters.
2.) Each Modulating
Heating Or Cooling
Device Used On The SA
Controller Must Have (1)
Relay Output Configured
For Each Device Used,
In Order To Enable The
Modulating Heating
And/Or Cooling Device's
Sequence. This Relay
Output Must Be
Configured When
Setting Up The SA
Controller Operating
Parameters.
Note:
See WSE Bypass Wiring
Detail For More
Information.
Figure 17: OE333-23-SA – SA Expansion Module Output Wiring
SA E-BUS Controller Technical Guide
21
Installation & Wiring
Suction Pressure Transducer Wiring
Zone
Zone
Suction Pressure Transducer
The OE275-01 Suction Pressure Transducer always wires directly to
the Digital Scroll Compressor Controller. See Figure 18 below for
wiring details.
24 VAC
GND
10 VA Minimum Power Required
For SA Expansion Module
Note:
1.) Suction Pressure Transducer(s) Are Only Required
For Installations With The Dehumidification Option
Installed.
2.) Modulating Cooling Output Voltage Must Be
Configured For 1.5 - 5 VDC Operation When You Are
Setting Up The SA Controller Operating Parameters
For A Copeland Digital Compressor.
Wiring For Single
Cabinet Unit
OE275-01
Suction Pressure Transducer
Splice Wire As Required To Reach
From Transducer Location To
Expansion Module Location
OE275-01
Suction Pressure Transducer
Additional Wiring
For Dual Cabinet
Units
Caution:
1.) The Schraeder Port Used For
Installation Of The Suction Pressure
Transducer Should Be Located In A
Vertical Portion Of The Suction Line To
Prevent Refrigerant Oil From
Accumulating In The Sensor.
RD
WH
BK
RD
WH
BK
The Suction Pressure Transducer is used to measure suction pressure
at the HVAC unit’s DX evaporator coil suction line. This suction line
pressure is converted to saturated refrigerant temperature by the SA EBUS Controller. This temperature is used by the SA E-BUS Controller
to accurately control the compressors and reheat cycle components to
provide optimum performance from the system during Dehumidifi ca-
tion operation.
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC.
Failure to observe polarity will result in damage to one or more of the boards. Expansion
Module must be wired in such a way that the expansion module and the controller are
always powered together. Loss of power to the expansion module will cause the
controller to become inoperative until power is restored to the expansion module.
24 VAC
POLARITY
WARNING
OBSERVE
Modular Cable
Connect To SA E-BUS
Controller
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PROUT
TO VCM-X INPUT
GND
TERMINALSAI5 & GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY1 =RELAY3 =
RELAY2 =RELAY4 =
RELAY1 =RELAY3 =
ITIS SUGGESTED
THATYOU WRITE THE
DESCRIPTION OF
RELAY2 =RELAY4 =
THE RELAYOUTPUTS
YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITETHE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING INTHE BOXESPROVIDEDABOVEWITHAPERMANENT
The SA Expansion Module provides 8 Binary Inputs. See Figure 19
below for detailed wiring.
The transformer used for powering the SA Expansion Module must also
be used to power the binary inputs.
10 VA Minimum Power Required
For SA Expansion Module
24 VAC
GND
Water Proof of Flow A - N.O. Input
Water Proof of Flow B - N.O. Input
Air Proof Of Flow - N.O. Input
Remote Forced Occupied-N.O. Input
Emergency Shutdown - N.C. Input
Drain Pan Overflow A - N.O. Input
Drain Pan Overflow B - N.O. Input
Dirty Filter - N.O. Input
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Module must be wired in such a way that the expansion
module and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power
is restored to the expansion module.
POLARITY
WARNING
OBSERVE
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
Warning: Do not apply any voltage greater than 24 VAC to the
binary inputs. Higher voltages will damage the expansion module
and possibly other components on the system.
24 VAC
24 VAC POWER ONLY
POWER ONLY
WARNING!POLARITYMUST BE
WARNING!
OBSERVED OR THE BOARD
POLARITY
WILLBE DAMAGED
MUST BE
OBSERVED OR
THE BOARD
WILL BE
DAMAGED
SA Expansion Module
Orion No.:OE333-23-SA
OE333-23-EM-AVCM-X EXPANSION MODULE
PR OUT
TO VCM-X INPUT
GND
TERMINALSAI5 & GND
SUCTION PRESSURE
+V
TRANSDUCER CONNECTION
SIG
FOR HVAC UNITS WITHOUT
GND
DIGITALCOMPRESSOR
RELAY 1 =RELAY 3 =
RELAY 2 =RELAY 4 =
RELAY1 =RELAY3 =
IT IS SUGGESTED
THATYOU WRITE THE
DESCRIPTION OF
RELAY2 =RELAY4 =
THE RELAYOUTPUTS
YOUARE USING IN
ITIS SUGGESTED
THE BOXES
THATYOU WRITETHE
PROVIDEDABOVE
DESCRIPTION OF
WITHA PERMANENT
THE RELAYOUTPUTS
MARKER (SHARPIE®)
YOUARE USING INTHE BOXESPROVIDEDABOVEWITHAPERMANENT