1. GENERAL INFORMATION ................................................................................. 4
1.1 Overview and System Requirements ................................................................................................................4
1.1.1 Data Sharing ............................................................................................................................................4
1.1.4 System Requirements .............................................................................................................................4
2. SETTING UP YOUR PT-LINK II ......................................................................... 5
2.2 Connection and Wiring Information ...................................................................................................................6
2.3 Confi guring the PT-Link DIP Switches ..............................................................................................................7
2.3.1. Set the BACnet MS/TP Baud Rate ..........................................................................................................7
2.3.2. Set the BACnet MS/TP MAC Address .....................................................................................................7
4. UPDATING THE SOFTWARE ........................................................................... 16
4.1 Updating the PT-Link II Controller ...................................................................................................................16
4.1.1 Programming the PT-Link II with BootLoader ........................................................................................16
4.1.2 Finding What COM Port Number the PT-Link II is Using .......................................................................18
4.1.3 Changing the USB COM Port Number ..................................................................................................19
4.2 Updating the Field Server Software ................................................................................................................20
WattMaster Controls, Inc.
8500 NW River Park Drive · Parkville, MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
Form: OR-PTLNK3BTL-TGD-01D
Copyright June 2015 WattMaster Controls, Inc.
BACnet® is a registered trademark of ASHRAE Inc., Atlanta, GA.
FieldServer is a Registered Trademark of FieldServer T echnologies, Milpetas, CA
WattMaster Controls, Inc. assumes no responsibility for errors or omissions.
This document is subject to change without notice.
6.3 VCM-X & SA Data Arrays ................................................................................................................................30
6.4 VCM Data Array ..............................................................................................................................................31
8.3 Setting a Password for the FS-GUI .................................................................................................................65
9. NODE ID (DEVICE INSTANCE) & MAC ADDRESS ........................................... 67
The OE368-23B-BACNET3, PT -Link II BACnet® provides bi-directional communication between your BACnet® MS/TP protocol network and
up to four* of any of the following types of Orion controllers—VCM-X,
VCB-X, RNE, SA, VCM, MUA II, or VAV/CAV:
SA Controller (Y200921)
VCM Controller (SS1016, Y200409, Y200616, Y200822)
**VAV/CAV Controller (SS1003, Y200301) and
MUA II Controller (SS1004, Y200405)
To determine what controller you have, you must look at the label located
on the controller. NOTE: The label is located on the EPROM on older
devices. If the controller label does not match any of the SS or Y numbers
listed above, your controller will not work with the PT -Link II BACnet®.
*NOTE: The PT-Link II BACnet® device can be used to con-
nect to four Orion controllers. If more than four Orion
controllers are present in a system, you will need additional PT-Link II BACnet® devices.
1.1.2 Scheduling
• Allows BACnet
to the Orion controller side of the gateway by using
standard BACnet® services.
• Provides values from points on the Orion side of the
gateway to BACnet® devices as if the values were
originating from BACnet® objects.
• Allows BACnet
Orion controller side of the PT-Link II BACnet® by using
standard BACnet
®
devices to modify point values on the
®
write services.
1.1.4 System Requirements
• The PT-Link II BACnet
assembled for panel mounting. Panel mounting components
are included for your convenience.
• Computer running Microsoft Windows
system.
®
interface is packaged and
TM
operating
• Ethernet Crossover Cable (supplied).
• PT-Link II BACnet software—located on included CD-
ROM and downloadable from www.orioncontrols.com.
4
PT-Link II BACnet3 Interface
Page 5
2. QUICK PT-LINK SET-UP
2.1 Quick Start Guide
The following steps will get you up and running in no time:
1. Familiarize yourself with the PT-Link II components (Figure 1).
2. Connect your PT-Link II to the Controller(s) on your system (up
to four) and connect your PT-Link II to the BACnet Network
(Figure 2). NOTE: Controllers must be addressed as 1, 2, 3 & 4.
3. Obtain the following from your Building Automation System
Integrator: the BACnet MAC address (System Node ID) and the
MS/TP network baud rate. Also, relay to your System Integrator
that the BACnet Device Instance Number for the PT-Link will be
the MAC address + 50,000. If this Device Instance will not work,
then continue to the full setup.
®
BACnet
Communications
Wiring Terminal
2.37
4. Confi gure your PT Link DIP Switches. See Section 2.3, page 7.
• Set the BACnet MS/TP baud rate via the B Bank set of DIP
switches.
• Set the BACnet MS/TP MAC Address using the PT-Link A
Bank DIP switches. The BACnet MS/TP MAC Address
MUST be set between 1 and 127.
4.25
1.31
Configuration
DIP Switches
®
BACnet
Protocessor
Module
Ethernet
Port
4.70
4.31
0.27
O
N
2
1
IAEZH004
Made in USA
RSGND
345
678
485
DRIVER
Local Loop
Communications
Driver Chip
ON
O
N
4
2
3
1
COMM
R
SH
T
Local Loop
Communications
Wiring Terminal
Communications
LED
4.82
Diagnostic
LED #1
Diagnostic
LED #2
Power
LED
2.61
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
MADE IN USA
0.20 Dia.
Mounting Hole
Typ. 3 PL.
USB
24 VAC Power
Terminal
Port
Figure 1: PT-Link II BACnet® Dimensions and Components
PT-Link II BACnet3 Interface
5
Page 6
2. QUICK PT-LINK SET-UP
2.2 Connection and Wiring Information
Zone
Zone
MS/TP Connection
ToNetwork
BACnet
®
MS/TP Connection
ToNetwork
BACnet
®
PT-Link Interface
485
RSGND
ON
O
O
N
N
4
2
345
678
2
3
1
1
Caution: The BACnet
®
Communication Terminal Block
Line Voltage
DRIVER
COMM
R
SH
T
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
MADE IN USA
24 VAC
(10 VA)
Must Be Disconnected Before
Connecting The Modular
Service Tool. After
Programming The
Controller(s), Disconnect The
Service Tool and Then
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD
(G) To SHLD (G) & R To R
Reconnect The
Communication Terminal
Block.
Note: All Programming Of
Controllers Must Be Done
Using The Modular Service
Tool. The Modular System
Manager Should Not Be
Used On A System That
Modular Service Tool
Mode
Selection
STATUS
SETPOINTS
SCHEDULES
OVERRIDES
ALARMS
CONFIGURATION
BALANCE - TEST
ON
UP
PREV
DOWN
ESC
ENTER
13
2
708
DEC
NEXT
CLEAR
654
9
MINUS
-
Has A PT-Link Installed.
Wiring Notes:
1.) All wiring to be in accordance with local and national electrical
codes and specifications.
IMPORTANT WIRING NOTE:
Use the Daisy-Chain Topology As Shown in This Diagram.
DO NOT Use a Star Topology with Multiple Units Tied
Directly to the PT-Link II.
Up To 4 Controllers
Can Be Interconnected.
Address Controllers
As Shown.
Controller
Address 1
T
SHLD
R
24 VAC
(8 VA)
Line Voltage
Controller
Address 3Address 4
24 VAC
(8 VA)
Line Voltage
Controller
Address 2
24 VAC
(8 VA)
Line Voltage
Controller
24 VAC
(8 VA)
Line Voltage
2.) All communication wiring to be 18 gauge minimum, 2 conductor
twisted pair with shield. Use Belden #82760 or equivalent.
Figure 2: PT-Link II BACnet® InterfaceWiring
6
PT-Link II BACnet3 Interface
Page 7
2. QUICK PT-LINK SET-UP
2.3 Confi guring the PT-Link DIP Switches
The DIP Switches allow you to set the protocol between BACnet MS/TP
and BACnet IP, set the BACnet MS/TP Baud Rate, and set the BACnet
MS/TP MAC address, and set the BACnet MS/TP device instance. You
can obtain the MAC address, Device Instance, and baud rate from your
Building Automation System (BAS) Integrator. The DIP Switches are
shown in Figure 3.
NOTE: Y ou must cycle power after making changes to the DIP
Switch Settings for the settings to take effect.
2.3.1 Set the BACnet MS/TP Baud Rate
“B” bank DIP switches B1 – B4 is used to set the BACnet MS/TP baud
rate of the PT -Link. This matches the baud rate required by the Building
Management System for BACnet MS/TP.
CAUTION: DIP Switch 8 in Bank A must always remain off
for proper operation.
2.3.2 Set the BACnet MS/TP MAC Address
1. Only (1) MAC address is set for the PT-Link regardless of how
many devices are connected to it.
2. Set the BACnet MS/TP MAC addresses of the PT-Link to a value
between 1 and 127 (MAC Master Addresses). This is so that the BMS
Front End can fi nd the PT-Link via the BACnet auto discovery func-
tion. MAC addresses from 128 to 255 cannot be auto discovered by
the BMS Front End.
3. Set “A” bank DIP switches A1 – A7 to assign a MAC Address to
the PT-Link for BACnet MS/TP. Please refer to Section 9, page 67
for the complete range of MAC Addresses and DIP switch settings.
NOTE: The BACnet Device’s Instance is generated by adding
the MAC address to the Node Offset, which defaults to
50,000. If the Device Instance must be set to something
other than in the range of 50,001 to 50,127, see Section
3.3.2, page 12 to change the Node Offset value.
PT-Link II BACnet3 Interface
7
Page 8
3. PT-LINK CONFIGURATION
3.1 Graphical User Interface
Zone
Zone
The PT-Link is confi gured using a Graphic User Interface (GUI)
which is a password protected web browser-based interface that uses
a combination of technologies and devices to provide a platform from
which you can gather and process information. The GUI allows you
to do the following:
• Change the BACnet Device Instance to something other
than 50,001 to 50,127
• Check the status and diagnostics of the PT-Link,
such as network settings, connection information, node
information, map descriptors, and error messages
• Monitor the PT-Link’s internal data and parameters
• Change or update the PT-Link’s internal data and
parameters
• Restart the PT-Link
The following items are needed to be able to run the GUI:
• PC Requirements—a computer with a web browser that
connects over the Ethernet on port 80*
*NOTE: Computer and network fi rewalls must be
opened for Port 80 to allow the GUI to function.
• Software Requirements—Mozilla Firefox 13.0 and up,
Microsoft Internet Explorer 8 & 9**, Google Chrome 19.0
and up, Opera 11 and up, or Safari 4.1 and up
**NOTE: Internet Explorer 8 does have some limitations
in terms of graphical features. Some effects such as rounded
corners and semi-opaque backgrounds are not supported.
So, although technical functionality is operational, the looks
might be slightly different
8
PT-Link II BACnet3 Interface
Page 9
3. PT-LINK CONFIGURATION
Ethernet Cable
Ethernet Hub
Or Switch
Connect Ethernet
Cable To
Ethernet
Connect
Ethernet
Cables To
Ethernet Hub
Ports
1
2
3
4
Ethernet Cable
Connect Ethernet
Crossover Cable
To PT-Link Ethernet
Port
PT-Link BACnet
485
DRIVER
COMM
R
SH
T
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
MADE IN USA
Computer
1
2
34567
8
O
N
O
N
1
2
3
4
ON
RSGND
5308
1210
5308
IAEZH004
Made in USA
3.2 PT-Link II Ethernet Connection
You have two options for connecting the PT-Link II to your PC via
Ethernet:
1.) You may connect the PT-Link II directly to your PC by
using a standard CAT5 or crossover cable (by others) as
shown. See Figure 4 for details.
2.) You can also connect both your PC and the PT-Link II to
an Ethernet Hub or Ethernet Switch with standard CAT5
cables. See Figure 5 for details.
Computer
Connect Ethernet
Crossover Cable Directly
To PC Ethernet Card Port
Locate a CA T5 cable and plug one end into your computer’s Ethernet port.
If connecting directly, plug the other end of the Cable into the Ethernet
port on the PT -Link II. If connecting through an Ethernet Hub or Switch,
plug the other end of the PC cable into the hub, and use a second CAT5
cable to connect the PT-Link II to the hub as well.
Power up the PT-Link II by plugging in the power cable. The PT-Link
II may take up to three minutes to power up completely. Once the PTLink II is powered up, you should notice that the RUN LED is blinking
continuously on the ProtoCessor Board. See Figure 28, page 23 for a
diagram showing the location of the ProtoCessor RUN LED.
Ethernet Crossover Cable
PT-Link BACnet
IAEZH004
Made in USA
RSGND
1210
ON
O
O
N
N
4
2
2
3
34567
8
1
1
5308
5308
Connect Ethernet
Crossover Cable
To PT-Link Ethernet
Port
Figure 4: Connecting With Crossover Cable
485
DRIVER
COMM
R
SH
T
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
MADE IN USA
Figure 5: Connecting With Ethernet Cable & Hub
PT-Link II BACnet3 Interface
9
Page 10
3. PT-LINK CONFIGURATION
3.3 IP Address Confi guration
3.3.1 Computer IP Address Set-up for
Windows XP, Vista, 7 & 8
In order for the PT -Link II to communicate properly, it is imperative to
set the IP address of both the PT-Link II as well as the computer to be
within the same netmask. You need to change the IP address on your
computer. The following instructions will explain how to con fi gure the IP
address for Microsoft® Windows XP, V ista, 7, and 8 operating systems.
3.3.1.1 Computer IP Address Set-up for
Windows NT & XP
1.) Click <start>; then click<Control Panel>.
2.) Double-click on the Network Connections icon.
The Network Connections Window will appear (Figure 6).
Zone
Zone
Figure 6: Network Connections Window
NOTE: If any wireless connections are listed, disable them
by right-clicking the connection and selecting
<Disable>.
3.) In the Network Connections Window, double-click the Local Area Connections entry. The Local Area Connection Status Window will appear (Figure 7).
Figure 7: Local Area Connection Status Window
4.) As shown in Figure 7, click <Properties> in the lower
left of the window. The Local Area Connection Properties Window will appear.
10
Figure 8: Local Area Connection Properties Window
5). As shown in Figure 8, in the Connection Items list box,
be sure the Internet Protocol (TCP/IP) is checked. Select the
Internet Protocol (TCP/IP) item to highlight it and then click
<Properties>. The Internet Protocol Properties Window will
appear.
PT-Link II BACnet3 Interface
Page 11
3. PT-LINK CONFIGURATION
3.3 IP Address Confi guration
3.3.1.2 Computer IP Address Set-up for
Windows Vista, 7 & 8
1.) Click<start>; then click<Control Panel> (Vista &
Windows 7). Click<start>; then right-click for<All apps>.
Click<All apps> and then click<Control Panel>
(Windows 8).
2.) Click on the Network and Internet icon.
3.) ClickNetwork and Sharing Center.
4.) From the shaded box in the left side of the window, select
Manage Network Connections (Vista) or Change adapter
settings (Windows 7).
5.) Right-click on the Local Area Connection icon and select
<Properties> for the drop down window.
Figure 9: Internet Protocol Properties Window
6).Select the radio button in front of Use the following
IP address (Figure 9) and write down the current defaults
so that you can re-enter them when you fi nish confi guring the PT-Link and then typein the following
information:
a.) IP address 192.168.1.5
b.) Subnet mask 255.255.255.0
c.) Default Gateway is blank
7.) Click<OK> until all of the above network confi guration
windows are closed. You may have to reboot the computer
before the new values are valid.
6.) ChooseInternet Protocol Version 4 (TCP/IPv4) by
highlighting it and then click <Properties>. The Internet Protocol Properties Window will appear (Figure 9).
7.) Select the radio button in front of Use the following IP address (Figure 9) and write down the current defaults so that you can re-enter them when you fi nish confi guring the PT-Link and then type in the following
information:
a.) IP address 192.168.1.5
b.) Subnet mask 255.255.255.0
c.) Default Gateway is blank
8.) Click<OK> until all of the above network confi guration
windows are closed. You may have to reboot the computer
before the new values are valid.
PT-Link II BACnet3 Interface
11
Page 12
3. PT-LINK CONFIGURATION
3.3 IP Address Confi guration
3.3.2 BACnet MS/TP - Setting Node_
Offset to Assign Specifi c Device
Instances
After setting your PC to be on the same subnet as the PT-Link,
open a web browser on your PC and enter the IP address of
the PT-Link; the default address is 192.168.1.24. (Figure 10).
1. If the IP address of the PT-Link has been changed by previous
confi guration, you will need to get the assigned IP address from the
network administrator or use the FieldServer ToolBox to fi nd the
IP Address.
2. The confi guration page will be displayed as your landing page.
(Figure 10)
3. The node offset can be changed on the confi guration page.
Zone
Zone
Figure 10: BACnet MS/TP Settings for Node_Offset
4. The Node_Offset fi eld will be presented displaying the current
value (default = 50,000).
5. Change the value of Node_Offset to establish the desired Device
Instance value, and click <Submit>.
Device Instance = Node_Offset +
A bank DIP switch setting
(A1-A7)
12
PT-Link II BACnet3 Interface
Page 13
3. PT-LINK CONFIGURATION
3.4 Changing the Confi g.csv File
NOTE: You may need Administration rights to perform this
function. See the Password Section, page 65.
1.) Open your web browser, and type the IP Address of the PT-Link,
which defaults to <192.168.1.24>, and press <ENTER>. The GUI
will launch. See Figure 11.
Figure 11: The FS-GUI Main Screen
3.) Refer to the File Transfer Window below (Figure 13). In the Con-fi guration Tab, under Retrieve, click the confi g.csv fi le in order to save
it to a destination and then open it.
2.) In the Navigation Window on the left of the FS-GUI Screen, click
<Setup> and then click<File Transfer>. See Figure 12.
Figure 12: Navigation Window - File Transfer
Figure 13: File Transfer - Confi guration Tab
4.) Open the confi g.csv fi le in Notepad. See Figure 14.
WARNING: Only edit the confi g.csv fi le using Notepad. DO
NOT use Excel. Using Excel to edit the confi g.csv fi le will
corrupt its contents!
PT-Link II BACnet3 Interface
Figure 14: Confi g.csv File
13
Page 14
3. PT-LINK CONFIGURATION
3.4 Changing the Confi g.csv File
Zone
Zone
5.) Near the top of the text fi le under ‘System_Node_ID’, change the
BACnet MAC address from the default of 11 (Figure 15). You can
obtain this address to enter from your Building Automation System
(BAS) Integrator.
Figure 15: System Node ID
6.) If you need to change the server baud rate, under ‘Connections’,
change the Server_Baud (Figure 16). Possible Baud Rate values are
(9600, 19200, 38400, and 76800). The default Baud Rate is 38400. You
can obtain the correct baud rate from your BAS Integrator.
8.) The last change you may need to make is the Node_ID under ‘Client
Side Nodes’ which is the BACnet Device Instance Number (Figure 18).
The default is 1.Y ou can obtain the Node ID from your BAS Integrator.
Figure 18: Client Node ID
9.) Once all changes have been made to the text fi le, while still in
Notepad, click<File> in the upper left and then click<Save>. Now
close the fi le and return to the FS-GUI Screen open in your browser.
NOTE: Do not rename the fi le. The fi le must always be named
“confi g.csv”; otherwise, it will be ignored by the PT-
Link.
Figure 16: Server Baud Rate
7.) Inside the text fi le under ‘Connections’, change the ‘Server_DIP’
parameter from ‘Enabled’ to ‘Disabled’. (See Figure 17).
Figure 17: Server Dip Switch
14
PT-Link II BACnet3 Interface
Page 15
3. PT-LINK CONFIGURATION
3.4 Changing the Confi g.csv File
10.) In theFile Transfer Window under Update Confi guration, click
<Choose Files> or <Browse>and locate the confi g.csv fi le you just
saved. Then click <Submit>. See Figure 19. Wait until the message,
“Confi guration update complete” appears and then click the <System
Restart> button at the bottom of the File Transfer W indow to activate
the new confi guration fi le.
3.4.1 Verifying Communications
1. ) In the Navigation Window on the left of the FS-GUI Main Screen,
click
<View> and then click <Data Arrays>. See Figure 20.
Figure 20: Navigation Window - View Data Arrays
Figure 19: Update Confi guration
NOTE: The following fi les can also be udpated in File Transfer W indow:
Firmware Files: The FieldServer Firmware contains the application
program commonly referred to as the DCC or the PCC. This program
contains the protocol drivers applicable to the application and the FieldServer Operating System Kernel. A Firmware update is only required
when updated fi les are received from FieldServer support. Firmware fi les have a *.bin extension. The procedure for updating these is the
same as for the confi guration fi les, but the update needs to be made in
the Firmware Tab.
General (Other) Files: Other fi les that can be updated include the FS-
GUI image and other fi les described in driver manuals. The procedure for
updating these is the same as for the confi guration fi les, but the update
needs to be made in the General Tab.
2. ) Click on the Controller name. In this case, it is DA_C160_I0, a
VCM-X Controller. The Controller’s Data Array Table will display.
See Figure 21.
Figure 21: VCM-X Data Array Table
3 ) You can now cross reference the values shown in Figure 21 with
the listed parameter names in the appropriate Data Array Table for your
controller type. These tables can be found on pages 28-31.
3.4.2 FS-GUI Reference Guide
PT-Link II BACnet3 Interface
An FS-GUI Reference Guide can be found in Section 8, page 64.
15
Page 16
4. UPDATING THE SOFTWARE
4.1 Updating the PT-Link II Controller
Zone
Zone
4.1.1 Programming the PT-Link II with
BootLoader
The PT-Link II is equipped with the ability to update its software with
the use of a computer. You will need the following before you begin:
• PT-Link II in need of an update (powered up,
no other connections necessary)
• Computer running Microsoft Windows
system
TM
operating
•Prism 2 software from www.orioncontrols.com
• Latest version of PT-Link II software (e-mailed from our
tech support staff or downloaded from any of our websites)
and software sheet
•USB Driver Setup.exe fi le from PT-Link II CD or
downloaded from any of our websites.
• USB cable
Follow these simple steps to update the PT-Link II:
1.) Turn on your computer and download the latest Prism 2 software
from www.orioncontrols.com.
2.) Either download the PT -Link II update fi le from http://techsupport.
wattmaster.com or save the fi le to your computer from the e-mail you
received from Tech Support. Record the path and name of the fi le for
later use. Also, print the software sheet provided for future reference.
8.) In the Job-Sites Window, from the Serial Port drop down list, select
the correct COM port. If you don’t know the COM port number or if
the number is 10 or higher, follow the directions on pages 18 and 19.
9.) From Prism 2’s Communications tab, select “Flash Selected
Controller.”
10.) The Flash Controller Window will appear.
3.) Run the USB Driver Setup.exe fi le (found on the PT-Link II CD or
downloaded from any of our websites) so that Prism can communicate
to the PT Link II. Unzip the fi le to the directory where you saved your
PT-Link II software.
4.) Plug the USB cable into the computer’s and PT-Link II’s USB
ports.
5.) A message will pop-up from the lower menu bar of Windows that
reads, “Found New Hardware.” Click on this message and follow the
instructions that appear to install the USB drivers.
6.) Open Prism 2 and Login with the User Name, admin and the Password, admin. If successful, “Administrator Access” will appear at the
lower right of the Prism program. NOTE: If using a Prism 2 version
prior to 4.0, the Login is fl ash. If successful, “Level 4 Access” will ap-
pear at the lower right of the Prism program.
7.) Click on the <Job-Site> icon. The Job-Sites Window will appear. In the Type of CommLink Dialog Box, select “CommLink 5.”
11.) From the Flash Controller Window’s Connection tab, select
“Direct”. Keep the Flash Controller Window open.
12.) Cycle power to the PT-Link II and within 5 seconds, click the
<Get Info> button in the Flash Controller W indow. The PT-Link II in-
formation will now appear in the window under the <Get Info> button.
16
PT-Link II BACnet3 Interface
Page 17
4. UPDATING THE SOFTWARE
4.1 Updating the PT-Link II Controller
13.) The Application ID should be SS1035 and the Application V ersion
should match the software version you will be updating to.
14.) In the HEX File fi eld, enter the path and name of the HEX fi le you
downloaded and/or copied to your hard drive. Use the Browse button
(...) to the right of the fi eld if you need help in locating the fi le.
15.) Now, cycle power to the PT-Link II once again and within 5
seconds click on the <Program HEX> button (shown above). If successful, you should see the Progress Application HEX bar showing the
progress percentage.
16.) When the bar shows 100% completed, verify the PT-Link II’s
software is running by observing the Timer LED blinking.
17.) Verify the PT -Link II’ s Application Version by once again cycling
power to the PT-Link II and within 5 seconds clicking the <Get Info>
button.
18.) Verify all fi elds are correct in the information below the <Get
Info> button and under “Finalization Data.” The “Int Flash Length”
and “Checksum” values should match the values provided with the
software sheet.
PT-Link II BACnet3 Interface
17
Page 18
4. UPDATING THE SOFTWARE
4.1 Updating the PT-Link II Controller
Zone
Zone
4.1.2 Finding What COM Port Number
the PT-Link II is Using
1. Left-click on <Start>, located on the bottom
left of the Windows Tool Bar.
2. Select<Control Panel>.
3. Double-click the System Icon.
6. Click on the plus sign next to Ports to see all of the
common ports.
7. Locate the USB Serial Port (COM#). The COM# in
parentheses is the port it is located on. Write this COM
port number down. You will need to know this when
setting up the Prism software.
8. If the COM port number is 10 or greater, go to
“Changing the USB COM Port Number” on page 19.
4. Click the <Hardware> tab.
18
5. Click the <Device Manager> button.
PT-Link II BACnet3 Interface
Page 19
4. UPDATING THE SOFTWARE
4.1 Updating the PT-Link II Controller
4.1.3 Changing the USB COM Port
Number
When the PT-Link II is fi rst plugged in, it will be assigned a COM port
number to be used for communicating with the Prism software. If the
port number is 10 or greater, it needs to be changed to a value less than
10 to be recognized by Prism.
1. Click<Start>, click<Control Panel>, click
<System>, click the <Hardware> tab, and then
click <Device Manager> to get to the Device
Manager Window.
2. Click on the plus sign next to Ports to see all of the
COM ports.
4. To assign a port number less than 10, click on
<Advanced>. The Advanced Settings Window
will appear.
5. In the COM Port Number drop box, select which
COM port you wish to use. Make sure you select a
COM port number that is not currently in use (you can
see the ports in use in the Device Manager Window).
Select a port that is less than 10.
NOTE: Windows
that has ever been installed on your computer. So if
there are no available ports below 10, choose a port
number less than 10 for a device listed that you know
you are not currently using.
®
will assign a port number to every device
3. Right-click on “USB Serial Port (COM#)” and select
<Properties>. In the Properties Window, select the
<Port Settings> tab.
6. Once you select the correct COM port number, click
<OK> and close any windows opened in the process
of changing the port number. Make note of this number
because you will need it for your Prism setup.
PT-Link II BACnet3 Interface
19
Page 20
Zone
Zone
4. UPDATING THE SOFTWARE
4.2 Updating the Field Server Software
Zone
Zone
1.) Extract and save the update fi le you receive from Field Server onto
your PC.
2.) Open your web browser, and type the IP Address of the PT-Link,
which defaults to <192.168.1.24>, and press <ENTER>. The GUI
will launch. Click <Diagnostic and Debugging>. The Main Screen
will appear. See Figure 22.
Figure 22: The FS-GUI Main Screen
4.) Refer to the File Transfer W indow below (Figure 24). In the General
Tab, click <Browse> and locate the fi le you saved in Step 1. Then click on <Submit>. When the download is complete, click on the <System
Restart> button.
Figure 24: File Transfer - General Tab
3.) In the Navigation Window on the left of the FS-GUI Screen, click
<Setup> and then click<File Transfer>. See Figure 23.
Figure 23: Navigation Window - File Transfer
20
PT-Link II BACnet3 Interface
Page 21
5. TROUBLESHOOTING
5.1 Troubleshooting Communications
5.1.1 Check Wiring and Settings
No COMS on WattMaster side
If TX/RX are not fl ashing rapidly, then there is a COM issue on the
WattMaster side and you need to check the following things:
• Visual observations of LEDs on ProtoNode.
(Figure 28, page 23)
• Check baud rate, parity, data bits, stop bits
• Check WattMaster device address
• Verify wiring
• Verify all the WattMaster devices that were discovered
in FST Web Confi gurator. (page 12)
NOTE: If the problem still exists, a Diagnostic Capture
needs to be taken and sent to W attMaster Technical
Support. See page 26.
Field COM problems
• Visual observations of LEDs on PT-Link. (Figure 27,
page 22)
5.1.2 Verifying Communications
1. ) In the Navigation Window on the left of the FS-GUI Main Screen,
click <View> and then click <Data Arrays>. See Figure 25.
Figure 25: Navigation Window - View Data Arrays
2. ) Click on the Controller name. In this case, it is DA_C160_I0, a
VCM-X Controller. The Controller’s Data Array Table will display.
See Figure 26.
NOTE: If the problem still exists, a Diagnostic Capture
needs to be taken and sent to W attMaster Technical
Support. See page 26.
Figure 26: VCM-X Data Array Table
3 ) You can now cross reference the values shown in Figure 26 with
the listed parameter names in the appropriate Data Array Table for your
controller type. These tables can be found on pages 28-31.
PT-Link II BACnet3 Interface
21
Page 22
5. TROUBLESHOOTING
5.2 Troubleshooting LEDs
5.2.1 PT-Link II Board LEDs
The PT-Link II BACnet® is equipped with LEDs that can be used for
troubleshooting. There are eight LEDs on the PT -Link board. See Figure 27 for the locations of the LEDs on the PT -Link board. The LED descriptions and functions are listed in the following paragraphs.
POWER LED
When the PT-Link II BACnet® is powered up, the “POWER” LED
should light up and stay on continuously. If it does not light up, check
to be sure that you have 24 VAC connected to the board, that the wiring
connections are tight, and that they are wired for correct polarity. The 24
V AC power must be connected so that all ground wires remain common.
If after making all these checks the “POWER” LED still does not light
up, please contact WattMaster Controls Technical Support at our Toll
Free number—866-918-1100—for assistance.
LOOP LED
When power is applied to the PT-Link II BACnet®, the “LOOP” LED
will also light up. The LED should fl icker rapidly, indicating that the
PT-Link is trying to communicate with the controllers on the loop. A
“fl icker” is defi ned as a brief moment when the LED turns off and
back on. If the “LOOP” LED does not operate as indicated above, fi rst
power down the unit and then reapply power. If this does not work,
please contact WattMaster Controls Technical Support at our Toll Free
number—866-918-1100—for assistance.
Zone
Zone
LED 1
When power is fi rst applied, “LED 1” will be off temporarily and then
will blink one time for each controller it is communicating with. For
example, if you have 4 controllers on the loop connected to the PT -Link,
“LED 1” will blink 4 times. If the amount of blinks does not match the
number of controllers connected to the loop, it indicates there is a communications problem. The best way to fi nd out which board is not com-
municating is to go to each controller and look at its “COMM” LED. The
“COMM” LED should be solid and will fl icker occasionally indicating
communication with the PT-Link II BACnet®. If the “COMM” LED
does not fl icker, there is no communication with that controller.
LED 2
When power is fi rst applied, “LED 2” will be off temporarily and then
will blink slowly indicating that the PT -Link baseboard is communicating
with the ProtoCessor Module. If “LED 2” does not blink, check that the
ProtoCessor Module is installed correctly on the PT -Link baseboard and
that the “PWR” LED is lit up on the ProtoCessor Module.
PROTO LED
When the PT-Link II is fi rst powered up, the “PROTO” LED should
blink rapidly and may appear to be on solid. This LED verifi es com-
munication with the board and the ProtoCessor. If the LED doesn’t
light up, check that the ProtoCessor is installed correctly and fi rmly
connected to the Base Board. The “PWR” LED should also be lit on
the ProtoCessor Module.
Figure 27: PT-Link II BACNET® LED Locations
WATCH DOG LED
The “W-DOG” LED is used for troubleshooting by W attMaster Controls
Technical Support. The “W-DOG” LED should always be on solid.
HEARTBEAT LED
The “H-BEAT” LED blinks to show the PT-Link II board software is
running. If the LED doesn’t light up, and all other checks have been
made, please contact W attMaster Controls T echnical Support at our T oll
Free number—866-918-1100—for assistance.
TIMER LED
The “TIMER” LED is used for troubleshooting by W attMaster Controls
Technical Support. The “TIMER” LED should always be blinking
steadily.
22
PT-Link II BACnet3 Interface
Page 23
5. TROUBLESHOOTING
5.2 Troubleshooting LEDS
5.2.2 PT-Link Module LEDs
Refer to Figure 28 for LED locations.
PWR LED
When the PT -Link II is fi rst powered up, the “PWR” green LED should
light up and stay on continuously. If the LED doesn’t light up, check
that the ProtoCessor is installed correctly and fi rmly connected to the
Base Board.
RX & TX LEDs
During normal operation, the “RX” LED will fl ash when a message is
received on the fi eld port of the ProtoCessor and the “TX” LED will fl ash when a message is sent on the fi eld port of the ProtoCessor The
“TX” and “RX” LEDs work together to indicate that communication
is being established with the desired protocol network. If both LEDs
are blinking, then communication is working properly. If not, check
the protocol network wiring and the baud rate in the confi guration fi le.
RUN LED
Upon powerup, the “RUN” LED should light up and stay solid for 15
seconds. It should then blink steadily, signifying normal operation. The
Protocessor will be able to access RUINET once this LED starts fl ashing.
RUN2 LED
The “RUN2” LED should blink steadily after power up, signifying
normal operation. The Protocessor will be able to access RUINET once
this LED starts fl ashing.
SYS ERR LED
The “SYS ERR” LED will go on solid 15 seconds after power up and
then shut off. A steady red light will indicate there is a system error on
the ProtoCessor. If this occurs, immediately report the related “system
error” shown in the error screen of the Remote User Interface to FieldServer Technologies for evaluation.
NODE OFFLINE LED
The “NODE OFFLINE” amber LED will go on solid 15 seconds after
power up and then shut off. A steady amber light indicates the ProtoCessor is not communicating with a device that it is polling.
Figure 28: PT-Link II BACnet3® LED Locations
NOTE: If all of these tests are made and the controller still doesn’t
operate, please contact W attMaster Controls T echnical
Support at our T oll Free number—866-918-1100—for
assistance.
Figure 29: PT-Link II BACnet3® Components
PT-Link II BACnet3 Interface
23
Page 24
Zone
5. TROUBLESHOOTING
5.3 Troubleshooting the PT-Link Controller
Zone
5.3.1 Addressing WattMaster Devices
in a BACnet® Network
Each PT-Link II BACnet® generates only one BACnet® device regardless of the number of W attMaster controls connected to it. This
device will have all the properties of all the WattMaster controls
connected. The instance of the device is equal to the unit address. The
properties of each control can be differentiated by an offset of 500.
Examples:
1.) Properties of the controller address as 1 will range
from 0 to 499.
2.) Properties of the controller address as 2 will range
from 500 to 999.
3.) Properties of the controller address as 3 will range
from 1000 to 1499.
To search for the instance of a specifi c property, follow the next
formula:
Property Instance = ((Controller Address – 1) * 500) + Instance
Number from table.
Example:
5.3.2 CAS BACnet Explorer for Validating PT-Link in the Field
Sierra Monitor Corporation has arranged a complimentary 2-week
fully functional copy of CAS BACnet Explorer (through Chipkin
Automation) that can be used to validate BACnet MS/TP communications of PT-Link in the fi eld without having to have the BMS
Integrator on site. A Serial or USB to RS-485 converter is needed
to test BACnet MS/TP.
5.3.2.1 Downloading the CAS Explorer
and Requesting an Activation Key
To request the complementary BACnet CAS key, go to http://app.
chipkin.com/activation/twoweek/ and fi ll in all of the information.
See Figure 30. Enter Vendor Code “WattMaster2BACnet”. Once
completed, the email address that was submitted will be registered.
1.) The PT-Link II BACnet® has a Node ID equal to fi ve.
2.) Two VCM controllers connected and addressed to one
and four.
3.) Searching for the Outdoor Temperature of each
controller.
4.) Instance of the Outdoor Temperature in the VCM table
equal to AI: 54.
5.) Client will only see Device 5.
6.) Under Device 5 it will see AI: 54 for the Outdoor
Temperature of the unit addressed as 1 and AI: 1554
for the Outdoor Temperature of the unit addressed as 4.
NOTE: To simplify the calculation, we recommend that the
WattMaster controllers be addressed in sequential
order from one to the last controller without any
unused address(es) in between.
Figure 30: Requesting a Two-Week Trial
24
PT-Link II BACnet3 Interface
Page 25
5. TROUBLESHOOTING
5.3 Troubleshooting the PT-Link Controller
Go to the website http://www.chipkin.com/technical-resources/
cas-bacnet-explorer/, and download and install the CAS BACnet
Explorer to your PC.
Open CAS BACnet Explorer. In the CAS Activation form, enter
the email address that was registered, and click on “Request a key”.
The CAS key will then be emailed to the registered address. Cut/
paste the key from the email into the Product key fi eld and click
<Activate>. See Figure 31.
5.3.2.2 CAS BACnet MS/TP Setup
1. Using the Serial or USB to RS-485 converter, connect it to your
PC and the 3 Pin BACnet MS/TP connector on PT-Link FPC-N34.
2. Open CAS Explorer.
3. Click on
4. Check the BACnet MS/TP box and uncheck the BACnet/IP and
BACnet Ethernet boxes
5. Set the BACnet MS/TP MAC address to 0.
6. Set the BACnet MS/TP Baud Rate to 38400.
7. Click
8. On the bottom right-hand corner, make sure that the BACnet
MS/TP box is green
9. Click on discover.
10. Check all 4 boxes.
11. Click<Send>.
<Settings>.
<Ok>.
5.3.3.1 Viewing Diagnostic Information
Figure 31: Requesting an Activation Key
1. T ype the IP address of the PT-Link into your web browser or use
the FieldServer Toolbox to connect to the PT-Link
2. Click on
and then click on <Connections>. See Figure 32.
3. If there are any errors showing in the Connections Window, please
refer to Section 5.1.1, page 21 for the relevant wiring and settings.
<Diagnostics and Debugging> then click on <View>,
Figure 32: Connections Window
PT-Link II BACnet3 Interface
25
Page 26
5. TROUBLESHOOTING
5.4 FieldServer Diagnostic Utilities
Zone
Zone
5.4.1 Diagnostic Capture Procedures
1. Once the Diagnostic Capture is complete, email it to
support@protocessor.com. The Diagnostic Capture will
allow us to rapidly diagnose the problem.
2. Ensure that FieldServer Toolbox is Loaded on the PC
that is currently being used, or download FieldServer Toolbox.zip at http://www.protocessor.com/tech-support/
utilities-and-design-documents.php
3. Extract the executable fi le and complete the installation.
4. Disable any wireless Ethernet adapters on the
PC/Laptop. See Figure 33.
5. Disable fi rewall and virus protection software if
possible.
6. Connect a standard Cat 5 Ethernet cable between the PC
and ProtoNode.
7. Double-click on the FS Toolbox Utility.
8. Click on the diagnose icon of the desired device.
See Figure 34.
Figure 33: Ethernet Port Location
Figure 34: FieldServer Toolbox - Diagnostic Icon
26
PT-Link II BACnet3 Interface
Page 27
5. TROUBLESHOOTING
5.4 FieldServer Diagnostic Utilities
9. Select Full Diagnostic. See Figure 35.
Figure 35: Full Diagnostic
10. If desired, the default capture period can be changed.
See Figure 36.
11. Click on
<Start Diagnostic>. Figure 36.
11. Wait for the Capture period to fi nish. The Diagnostic Test Complete Window will appear. Figure 37.
Figure 37: Diagnostic Test Complete Window
12. Once the Diagnostic test is complete, a .zip fi le will be saved on the PC.
13. Clickto launch explorer and have it point directly at the
correct folder.
14. Send the Diagnostic zip fi le to support@fi eldserver.com.
<Open> in the Diagnostic Test Complete Window
Figure 36: Set Capture Period and Start Diagnostic
NOTE: When using Celsius scaling, all temperature values will
need to be divided by 10 by the BMS to properly read
the status and setpoint values, e.g., a value of 200º C
needs to be divided by 10 for an actual value of 20º C.
BACnet Properties for the VCB-X Controller
Param-
eter
Bad or
Missing 12
Relay
Expansion
Board.
Alarm
Group 1
Alarm
Group 2
Alarm
Group 3
Alarm
Status
Application
Software
Version
Unit ModeUnitModeAI:123See Unit Mode
Building
Pressure
Building
Pressure
Setpoint
Building
Pressure
Control
Deadband
CO
2
CO
2
Sensor
Calibration
Deadband
Offset
NameObjectDescription
Mis12RlyBI: 376The 12 Relay
Expansion Board
is confi gured but
not detected.
AlmGrp1AI: 104See Alarm
AlmGrp2AI: 105See Alarm
AlmGrp3AI: 106See Alarm
AlmStsAI: 1Indicates that
there is an alarm.
AppVerAI: 99Current version
of the software
in the unit.
BuildPrAI:272Current value of
the Building
Pressure Sensor.
RfPrStAV:118Current Building
Pressure
Setpoint.
RfPrDbAV:358Value above
and below the
Building Pres-
sure Setpoint
where no control
change occurs.
CO2AI:271Current CO2
Level.
CO2OstAV: 348If the CO2
Sensor is reading
incorrectly, you
can use this
option to enter
an offset value
to adjust the
Sensor’s CO2
reading.
Limits
Group Bits on
page 43.
Group Bits on
page 43.
Group Bits on
page 43.
0 = Off
1 = On
See Alarm
Group Bits on
page 43.
Bits on page
43.
-.20.20
.010.1
-500
ppm
500
ppm
BACnet Properties for the VCB-X Controller
Param-
eter
CO
2
Minimum
Setpoint
CO
2
Maximum
Setpoint
Bad CO
Sensor
Coil
Tempera-
ture
Coil
Tempera-
ture Offset
Bad Coil
Pressure
Sensor
Coil Tem-
perature
Setpoint
NameObjectDescription
CO2MinLvAV:287This is the
CO2
MaxLv
CO2AlmBI: 368Failure of the
2
CoilTpAI: 181Current coil
ColTpOftAV:284If the Coil
ColPrAlmBI: 367Failure of the
CoilTpStAI: 334This is the
AV:288This is the CO2
threshold CO
level at which
the Economizer
begin to be reset
level at which
the Economizer
be reset to the
Economizer Max
Position in High
CO2 . In between
Max CO2 levels
the Economizer
Position will be
proportionally
reset between the
confi gured Min
Damper Position
Position in High
Sensor is reading
incorrectly, use
this offset to adjust the Sensor’s
Coil Pressure
Sensor. W ill shut
calculated Coil
Dehumidifi cation
Min Damper
Position
Setpoint will
higher.
Min Damper
Position will
the Min and
Min Damper
and the Max
CO2 .
CO2 Sensor.
temperature
reading.
Temperature
Temperature.
unit down.
current
Suction
Temperature
target during
Mode.
Limits
02000
2
02000
-100100
32
PT-Link II BACnet3 Interface
Page 33
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Param-
eter
Low Coil
Temperature
Setpoint
Limit
High Coil
Temperature
Setpoint
Limit
Com-
pressor
Discharge
Tempera-
ture
Bad Com-
pressor
Discharge
Sensor
Control
Mode
NameObjectDescription
LoClTpStAV:295This is the low-
est that the Coil
Temperature will
be reset to during
Space Humid-
ity Reset of the
Coil Suction
Temperature
Setpoint. If no
coil temperature
reset is required,
this value should
be set the same
as the High Coil
Temperature
Setpoint.
HiClTpStAV:296This is the high-
est that the Coil
Temperature will
be reset to during
Space Humid-
ity Reset of the
Coil Suction
Temperature
Setpoint. If no
coil temperature
reset is required,
this value should
be set the same
as the Low Coil
Temperature
Setpoint.
DschgTpAI: 331Current value of
the Compressor
Discharge T em-
perature Sensor.
DschgAlmBI: 369Failure of the
Digital Compres-
sor Discharge
Temperature
Sensor.
CtrlModAI: 971=Constant
Limits
3570
3570
Volume
2=Supply Air
Cooling Only
3=Outdoor
Temp Control
4=Single Zone
VAV
5=Supply Air
Tempering
6=Space Temp
Control w/
High OA
Content
Unoccupied
BACnet Properties for the VCB-X Controller
Param-
eter
Control
Tem-
perature
Cooling
Failure
Control
Tem-
perature
Heating
Failure
High
Control
Mode
Tempera-
ture
Low Control Mode
Tempera-
ture
Cooling
Low Reset
Source
NameObjectDescription
CtrlTpCFBI: 108Activated if the
control tempera-
ture does not get
within 5°F to the
occupied cooling
setpoint in an
hour in the cool-
ing mode. This
alarm is not used
in 100% outside
air units or sup-
ply air control.
CtrlTpHFBI: 109Activated if the
control tempera-
ture does not get
within 5°F to the
occupied heating
setpoint in an
hour in the heat-
ing mode. This
alarm is not used
in 100% outside
air units or sup-
ply air control.
HiCtrlMdBI: 377 Occurs when the
Controlling Sen-
sor Temperature
rises above the
Cooling Mode
Enable Setpoint
plus the Control
Mode High
Alarm Offset.
Applies only to
Space or Return
Air Temperature
controlled units.
LoCtrlMdBI: 378 Occurs when the
Controlling Sensor Temperature
falls below the
Heating Mode
Enable Setpoint
minus the Con-
trol Mode Low
Alarm Offset.
Applies only to
Space or Return
Air Temperature
controlled units.
ClLoRtAV: 326If doing Supply
Air Setpoint
Reset, this is
the Low Reset
Source value in
Cooling that will
correspond to
the Supply Air
Cool High Reset
Setpoint.
Limits
1 150
PT-Link II BACnet3 Interface
33
Page 34
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
Zone
Zone
BACnet Properties for the VCB-X Controller
Param-
eter
Cooling
High Reset
Source
Condenser
Control
Signal
Controlling
Sensor
High
Alarm
Offset
Controlling
Sensor
Low Alarm
Offset
Control
Status
Control
Tempera-
ture
Cooling
Enabled
NameObjectDescription
ClHiRtAV: 327If doing Supply
Air Setpoint
Reset, this is
the High Reset
Source value in
Cooling that will
correspond to
the Supply Air
Cooling Setpoint
(Low Reset).
CdCtrSg1AI:280Condenser Fan
Signal 1 Status.
CTpHiAlmAV: 349If the tem-
perature of the
controlling sen-
sor rises above
the Occupied
Cooling Setpoint
by this value,
a High Control
Temp Alarm
will occur. Only
applies if confi g-
ured for Space
or Return Air
Temp Control, or
as Single Zone
VAV.
CTpLoAlmAV: 350If the tempera-
ture of the con-
trolling sensor
falls below the
Occupied Heat-
ing Setpoint by
this value, a Low
Control Temp
Alarm will oc-
cur. Only applies
if confi gured for
Space or Return
Air Temp Con-
trol, or as Single
Zone VAV.
CtrlStsAI: 4Current
operational
status.
CtrlTpAI: 9Current value of
the control
temperature
sensor.
ClEnbl AI: 6Status that
indicates
mechanical
cooling is
enabled to
operate.
Limits
1 150
050
050
See Control
Status Bits on
page 43.
BACnet Properties for the VCB-X Controller
Param-
eter
Mechani-
cal Cooling
Lockout
Mechani-
cal Cooling
Alarm
Cooling
Setpoint
Mirror
Cool
Staging
Window
Adaptive
Defrost
Interval
Adjust-
ment
Dewpoint
Setpoint
NameObjectDescription
MchClLktAV: 342The VCB-X
will Lockout
Mechanical
Cooling when
the Outdoor Air
Temperature
is below this
Setpoint.
MchClAlmBI: 94Compressor Re-
lays are enabled
but the Supply
Air Temperature
has not fallen
5°F within a
user-adjustable
time period. This
does not apply
for Modulating
Cooling.
ClStAI: 7Occupied
Cooling Mode
Enable
Setpoint.
ClStgWdwAV: 340In Cooling
Mode, if the
Supply Air
Temperature
drops below the
Active Supply
Air Cooling
Setpoint minus
this Staging Win-
dow, a Cooling
Stage will be
deactivated after
its Minimum
Run Time.
AptDfrAV: 356Adjustment to
the Heat Pump
Defrost Interval
depending on
whether the
Defrost Mode
lasts 10 minutes
or less than 10
minutes.
RhDewpStAV:282On a MUA unit,
if the outdoor
dewpoint rises
above this
setpoint, the unit
will
activate Dehu-
midifi cation.
Limits
-30100
130
0 Min30
Min
3580
34
PT-Link II BACnet3 Interface
Page 35
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
0%100%
0%100%
2
Limits
-3080
Param-
eter
Digital
Compres-
sor Cutoff
Digital
Com-
pressor
Lockout
Dirty Filter
Alarm
Economiz-
er Enabled
Economiz-
er Enable
Setpoint
Economiz-
er Position
Max
Economiz-
er in Heat
Mode
Max
Econo-
mizer in
High CO2
Mode
Minimum
Econo-
mizer
Position
NameObjectDescription
DigCmpCfBI: 379Occurs if the
DigCmpLkBI: 380Occurs if fi ve
DrtFlAlmBI: 96Alarm that
EcoEnblAI: 15Status that
EcoEnbStAV:283The economizer
EcoPosAI: 16Current position
MaxEcoHtAV: 353Max position
MaxEcoCOAV: 354The maximum
MinEcoStAV: 151Minimum
digital compres-
sor discharge
temperature rises
above 268°F
or the sensor
is shorted. The
compressor is
disabled.
Digital Compres-
sor Cutoffs
occur within
four hours. The
compressor will
be locked out.
indicates the
fi lters are dirty.
indicates the
economizer is
enabled.
is enabled if the
outdoor drybulb,
dewpoint, or
wetbulb temperature falls below
this setpoint.
of the econo-
mizer damper.
the Economizer
Damper can
open in the Heat-
ing Mode. Takes
priority over
Max Position in
High CO
Economizer
Minimum Posi-
tion can be reset
up to during CO
position of the
economizer in
the occupied
value the
override.
mode.
.
2
0100
BACnet Properties for the VCB-X Controller
Param-
eter
Force
Econo-
mizer
Emergency
Heat
Enabled
Exhaust
Fan CFM
Missing
Exhaust
CFM
Sensor
Exhaust
Fan Speed
Missing
EM1
Expansion
Module
Fan
Starting
Delay
Leaving
H2O
Offset
Water
Proof
of Flow
Failure
NameObjectDescription
FrcEconoAV: 267Overrides all
EmHtEnblBI: 364Shows the Emer-
EtCFM
ExtCfmSrBI: 371Indicates that the
EtFnSpdAI: 273Current value of
MisEM1BI: 366Indicates that the
FanDly AI: 25Indicates the
LvH2OOstAV: 347If the Leaving
H2OProfBI: 382Indicates no
AI:194Current Exhaust
other Outdoor
Air Damper
position com-
mands so as to
maintain this
fi xed position.
Confi guring
for “Auto” will
restore normal
unit control of
the Outdoor Air
Damper/Econo-
mizer operation.
gency Heat is
enabled based on
the Compressor
Heating Lockout.
Airfl ow
Measurement
Exhaust CFM
Sensor is not
detected.
the VFD relief
fan signal.
EM1 Expansion
Module is not
communicating
with the VCB-X
Controller.
current fan status
related to request
to run, fan start-
ing delay or POF
failure.
Water Tempera-
ture Sensor is
reading incorrectly, use this to
enter an offset to
adjust the Sensor’s T empera-
ture.
Proof of Water
Flow.
Limits
0%100%
Auto=65535
0=No Request
1=Fan
Running
2=Fan Start
Delay
3=POF Failure
-100100
PT-Link II BACnet3 Interface
35
Page 36
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
Zone
Zone
BACnet Properties for the VCB-X Controller
Param-
eter
Force
HVAC
Mode
Head
Pressure
Head
Pressure
Setpoint
Head
Pressure
Setpoint
in Cooling
Mode
Head
Pressure
Setpoint
in Reheat
Mode
High Head
Pressure
SAT
Heating
Low Reset
Source
SAT
Heating
High Reset
Source
Heating
Enabled
NameObjectDescription
FrcHvacMAV: 262Overrides
normal controller
operation in
order to force
the unit into this
desired mode.
Confi guring
for “Auto” will
restore normal
unit control of
the mode of
operation.
HeadPrAI:276Current value of
the Head
Pressure
Reading.
HeadPrStAI:279Current Head
Pressure
Setpoint.
ClHdPrStAV:293This is the Head
Pressure Setpoint
the unit will
control to in the
Cooling Mode.
HtHdPrStAV:294This is the Head
Pressure Setpoint
the unit will
control to in the
Dehumidifi cation
Reheat Mode.
HiHedPrBI: 381Indicates the
Head Pressure is
too high.
HtLoRtAV: 328If doing Supply
Air Setpoint
Reset, this is
the Low Reset
Source value in
Heating that will
correspond to the
Supply Air Heat-
ing High Reset
Setpoint.
HtHiRtAV: 329If doing Supply
Air Setpoint
Reset, this is
the High Reset
Source value in
Cooling that will
correspond to
the Supply Air
Cooling Setpoint
(Low Reset).
HtEnblAI: 30Status that
indicates that
mechanical heat-
ing is enabled to
operate.
Limits
0=Auto
1=Vent
2=Cool
3=Heat
4=Vent
Dehum.
5=Cool
Dehum.
6=Heat
Dehum.
240
PSI
240
PSI
1 150
1
420
PSI
420
PSI
150
BACnet Properties for the VCB-X Controller
Param-
eter
Heating
Setpoint
Mirror
Heat
Staging
Window
Mechani-
cal Heating
Lockout
Mechani-
cal Heating
Alarm
Heat Pump
Compres-
sor Heating
Outdoor
Lockout
Heat Pump
Defrost
Interval
Heat
Wheel
Defrost
Setpoint
Indoor
Humidity
NameObjectDescription
HtStAI: 31Occupied
Heating Mode
Enable Setpoint.
HtStgWdwAV: 341In the Heat-
ing Mode, if
the Supply Air
Temperature
rises above the
Active Supply
Air Heating
Setpoint plus the
Heating Stage
Off Window
value, a Heating
stage will be
deactivated after
its Minimum
Run Time.
MchHtLktAV: 343The VCB-X
will Lockout
Mechanical
Heating when
the Outdoor Air
Temperature
is above this
Setpoint.
MchHtAlmBI: 95Heating Mode
has been initiated
but the Supply
Air Temperature
has not risen
5°F within a
user-adjustable
time period. This
does not apply
for Modulating
Heating.
HpLktAV: 351Compressor
Heating will be
locked out when
the Outdoor Air
Temperature
is below this
Setpoint.
HpDfrIntAV: 355The Heat Pump
Defrost Interval
is the length of
time that must
be met between
Defrost Modes.
DfrstAV: 346The unit will go
into Heat Wheel
Defrost Mode
when the Out-
door Air is below
this setpoint.
InRhAI: 67Current value
of the Indoor
Humidity
Sensor.
Limits
150
-30150
-30100
10
Min
050
120
Min
36
PT-Link II BACnet3 Interface
Page 37
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Param-
eter
Indoor
Humidity
Setpoint
High
Indoor
Humidity
Reset
Limit
Indoor
Humidity
Setpoint
Mirror
Leaving
Water
Tempera-
ture
Low
Ambient
Relay
Setpoint
Mode
Select
Deadband
Modulat-
ing
Cooling
Position
Modulat-
ing Gas
Valve
Position
Modulat-
ing
Heating
Position
NameObjectDescription
InRhStAV:289If Coil Temp
HiInRhAV:292During Coil
InRhStMAI: 114Mirror of the
LvWtrTpAI:278Leaving Water
LWAmbntAV:285Temperature at
MdSelDbAV: 339This Setpoint
MdClPosAI: 115Current position
MdGs
VPos
MdHtPosAI: 116Current position
AI:274Current
Reset is being
used this is also
the lowest Space
RH value that
corresponds to
the Hi Coil Temp
Setpoint.
Temp Reset, this
is the highest
Space RH value
that corresponds
to the Low Coil
Temp Setpoint.
InRhSt “read
only.”
Temperature
Value
which the Low
Ambient Relay
will activate in
the Occupied
or Unoccupied
Mode.
is added to and
subtracted from
the HVAC Mode
Setpoints to de-
termine when the
unit enters and
leaves a mode of
operation.
of the modulat-
ing
cooling signal
(Chilled water or
digital
compressor).
position of
MODGAS
modulating gas
valve control.
of the modulat-
ing
heating signal
(hot water or
SCR heat).
Limits
0100
0100
-3070
110
BACnet Properties for the VCB-X Controller
Param-
eter
Missing
MODGAS
Module
Morning
Warm-Up
Return Air
Target
Setpoint
Occupied
Cooling
Setpoint
Occupied
Heating
Setpoint
Hood On
Outdoor
Air
Cooling
Setpoint
Hood On
Outdoor
Air
Heating
Setpoint
Outdoor
Air CFM
NameObjectDescription
MisMDGAS BI: 375Alarm that
indicates that
the MODGAS
module is not
communicating
with the VCB-X
Controller.
WmupTgAV:281If confi gured,
upon entering the
occupied mode,
the Warm-up
Demand will be
activated if the
return air tem-
perature is one
degree below
this setpoint.
OcpClStAV: 42If the control
temperature rises
one degree above
this setpoint,
the control will
activate the
cooling demand.
If the control
temperature is
the Supply Air
Sensor, then the
cooling demand
is always active.
OcpHtStAV: 43If the control
temperature
drops one degree
below
this setpoint,
the control will
activate the
heating demand.
If the
control
temperature
is the Supply
Air Sensor, then
there is no
heating
demand.
OaClStAV:45This is the Cool-
ing Mode Enable
Setpoint used
only in Hood On
Mode.
OaHtStAV:46This is the Heat-
ing Mode Enable
Setpoint used
only in Hood On
Mode.
OaCFMAI: 193Current Outdoor
Airfl ow
Measurement
Limits
5090
1110
1110
1110
1110
PT-Link II BACnet3 Interface
37
Page 38
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
Zone
Zone
BACnet Properties for the VCB-X Controller
Param-
eter
Minimum
Desired
Outdoor
Air CFM
Missing
Outdoor
Air CFM
Sensor
Outdoor
Humidity
Outdoor
Air
Dewpoint
Outdoor
Air Tem-
perature
Outdoor
Air
Tempera-
ture Offset
Minimum
Outside
Air CFM
Deadband
Outdoor
Air Tem-
perature
Sensor
Lost
Outdoor
Wetbulb
Preheat
Relay
Setpoint
Proof
of Flow
Alarm
NameObjectDescription
OACfmMinAV:291Minimum Out-
door Airfl ow
CFM Setpoint
OaCfmAlmBI: 370Indicates
Outdoor Air
CFM Sensor is
not detected.
OaRhAI:52Current value
of the Outdoor
Humidity
Sensor.
OaDewPtAI: 332Current calcu-
lated Outdoor
Air Dewpoint.
OaTpAI: 54Current value
of the
outdoor
temperature
sensor.
OaTpOstAV: 53If the Outdoor
Temperature
Sensor is reading
incorrectly, use
this to enter an
offset to adjust
the Sensor’s
Temperature.
OacfmDbAV: 359The Deadband
is used both
above and below
the Outdoor Air
CFM setpoint
to help prevent
hunting.
OaTpAlmBI: 117Indicates a
failure of the
Outdoor Air
Temperature
Sensor.
OaWtblAI: 55Current calcu-
lated value of the
outdoor wetbulb
temperature.
PreHtAmbAV:286 If the Supply Fan
is energized this
is the tempera-
ture at which the
Preheat Relay
will activate.
Operates only
in the Occupied
Mode.
PofAlmBI: 26Indicates no
Proof of Water
Flow.
Limits
.10K 200K
-100100
101000
-3070
BACnet Properties for the VCB-X Controller
Param-
eter
Reheat
Enabled
Reheat
Valve
Position
Missing
Reheat
Module
Return Air
CFM
Missing
Return
Air CFM
Sensor
Return Air
Damper
Position
Return Air
Humidity
Return Air
Tempera-
ture
Return Air
Tempera-
ture Sensor
Offset
Bad Return
Air Sensor
Return
Bypass
Damper
Position
Schedule
Force
Current
Slide
Adjust
Offset
NameObjectDescription
RehtEnblBI: 363Modulating
RtVlvPosAI:277Current position
MisMH-
GRV
RaCFMAI:275Current Return
RaCfmSrBI: 373Indicates
RaDmpAI: 336Current Return
RaRHAI: 337Current value of
RaTpAI: 64Current value of
RaTpOstAV: 65If the Return
RaTpAlmBI: 365Indicates a failure
RetBydmpAI: 335Current Return
SchdFrcAV: 660 = Auto (uses
SldAdOfsAI: 338Current Slide
BI: 374Indicates that the
Hotgas Reheat
Enabled.
of MHGRV
modulating hot
gas reheat valve.
MHGRV Module
is not
communicating
with the VCB-X
Controller.
Airfl ow
Measurement.
that the Return
Air CFM Sensor
is not detected.
Air Damper
position.
the Return Air
Humidity Sensor.
the return tem-
perature sensor.
Temperature
Sensor is reading
incorrectly, use
this to enter an
offset to adjust
the Sensor’s
Temperature.
of the Return Air
Sensor.
Bypass Damper
position.
controller’s
schedule)
1 = Forced
Occupied
2 = Forced
Unoccupied
Adjust Offset
value.
Limits
-100100
02
38
PT-Link II BACnet3 Interface
Page 39
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Param-
eter
Smoke
Alarm /
Emergency
Shutdown
Space
Tempera-
ture
Space
Tempera-
ture Offset
Space
Tempera-
ture Sensor
Lost
Static
Pressure
Static
Pressure
Setpoint
Static
Pressure
Setpoint
Deadband
Suction
Pressure
High
Suction
Pressure
Alarm
Low
Suction
Pressure
Alarm
Supply Air
CFM
High
Supply Air
Tempera-
ture Alarm
NameObjectDescription
SmokeAlmBI: 119Indicates the
SpcTpAI:72Current value of
SpcTpOstAV:71If the Space
SpcTpAlmBI: 101Indicates
StaticPrAI:270Current Static
StatPrStAV:290Current Static
DuctPrDbAV:357Value above and
SucPrAI: 333Current Suction
HiSucPrBI: 352Indicates
LoSucPrBI: 383Indicates
SaCFMAI:195Current Supply
HiSaAlmBI: 33The Supply Air
Smoke sensor
has been acti-
vated. This will
shut down the
unit.
the space tem-
perature sensor.
Temperature
Sensor is reading
incorrectly, use
this option to
enter an offset
to adjust the
Sensor’s
Temperature.
a failure of the
Space Tempera-
ture Sensor.
Pressure.
Pressure
Setpoint.
below the Duct
Static Pressure
Setpoint where
no control
change occurs.
Pressure value.
Suction Pressure
is above the
High Suction
Pressure Cool-
ing (Heating)
Setpoint.
Suction Pressure
is below the Low
Suction Pressure
Cooling (Heat-
ing) Setpoint.
Airfl ow
Measurement.
has risen above
the High SAT
Cutof
f Setpoint.
Heating stages
begin to deacti-
vate and the fan
continues to run.
Limits
-100100
.103.0
.010.5
BACnet Properties for the VCB-X Controller
Param-
eter
Low Sup-
ply Air
Tempera-
ture Alarm
Supply Air
Cooling
Setpoint
Supply Air
Cool High
Reset
Supply Air
Heat High
Reset
Supply Air
Heating
Setpoint
Supply Air
Tempera-
ture
Bad
Supply Air
Tempera-
ture Sensor
Low
Supply
Air Temp
Cutoff
High
Supply
Air Temp
Cutoff
NameObjectDescription
LoSaAlmBI: 37The Supply Air
has fallen below
the Low SAT
Cutoff Setpoint
and cooling
stages will begin
to deactivate.
If the unit is in
Economizer,
Vent, or Heating
Mode the Supply
Fan will shut off.
SaClStAV:77Supply Air Cool-
ing Setpoint. If
Supply Air Reset
is confi gured,
this is the Low
SAT Cooling
Reset Value.
SaClRtAV: 324 If Supply Air Re-
set is confi gured,
this is the High
SAT Cooling
Reset Value.
SaHtRtAV: 325 If Supply Air Re-
set is confi gured,
this is the High
SAT Heating
Reset Value.
SaHtStAV :78Supply Air Heat-
ing Setpoint. If
Supply Air Reset
is confi gured,
this is the Low
SAT Heating
Reset Value.
SaTpAI:83Current value of
the Supply Air
Temperature
Sensor.
SaTpAlmBI: 2Indicates a fail-
ure of the Supply
Air Temperature
Sensor.
LoSaCfAV: 344Cooling will be
disabled if the
Supply Air Tem-
perature falls
below this value.
See sequence for
more details.
HiSaCfAV: 345Heating will be
disabled if the
Supply Air Tem-
perature rises
above this value.
See sequence for
more details.
Limits
3080
0 100
0 250
40240
0100
0
250
PT-Link II BACnet3 Interface
39
Page 40
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
Zone
Zone
BACnet Properties for the VCB-X Controller
Param-
eter
Supply Air
Tempera-
ture Offset
Current
Supply Air
Temperature
Setpoint
Cooldown
Mode
Supply Air
Setpoint
Missing
Supply
Air CFM
Sensor
Warmup
Mode
Supply Air
Setpoint
SZ VA V
Integral
Constant
Title 24
Econo-
mizer
Feedback
Title 24
Sensor
Alarm
Title
24 Not
Economiz-
ing When
It Should
Title 24
Economiz-
ing When
It Should
Not
NameObjectDescription
SaTpOstAV:80If the Supply Air
Temperature
Sensor is reading
incorrectly, use
this offset to adjust the Sensor’s
Temperature.
SaTpStMAI: 82Current SAT
Cooling or
Heating
setpoint if there
is no reset
source;
Current calculated SAT
setpoint with
Reset Source.
SaCldnStAV: 362Cooling will be
controlled to
this Supply Air
Setpoint during
Cool-Down.
SaCfmSrBI: 372Indicates the
Supply Air CFM
Sensor is not
detected.
SaWmupStAV: 361Heating will be
controlled to
this Supply Air
Setpoint during
Morning Warm-
Up.
SZVAVFnlAV: 360This is the
Integral Constant
for controlling
the SZ VAV Fan
Speed.
T24EcFbAI: 384Current position
of feedback from
Economizer
actuator.
T24TpAlmBI: 385Outside Air
or Supply Air
Temperature
Sensor is shorted
or missing.
T24NEWSBI: 386Economizer is
enabled but not
following the
desired Econo-
mizer position
commanded.
T24EWISNBI: 387Economizer is
not enabled but
the feedback
signal indicates
a position more
open than the
minimum.
Limits
-100100
3080
40240
010
BACnet Properties for the VCB-X Controller
Param-
eter
Title 24
Damper
Failure
Title 24
Excess
Outdoor
Air
Unoc-
cupied
Cooling
Offset
Unoc-
cupied
Heating
Offset
VFD
Position
VFD Min
Position in
Cool Mode
NameObjectDescription
T24DpAlmBI: 388Economizer is
enabled but not
within 10% of
desired position
within 150
seconds.
T24ExsOABI: 389Economizer
feedback is lost
or Economizer
is not follow-
ing commanded
position.
UnClOstAV: 124In Unoccupied
Mode, this
offsets the
Occupied Cool-
ing Setpoint by
this user adjust-
able amount. If
no Unoccupied
Cooling is
desired, use the
default setting
of 30°F for this
setpoint.
UnHtOstAV:125In Unoccupied
Mode, this
offsets the
Occupied Heat-
ing Setpoint by
this user adjust-
able amount. If
no Unoccupied
Heating is
desired, use the
default setting
of 30°F for this
setpoint.
VfdBwPosAI:88Current
position of the
VFD blower fan
signal.
VFDClMinAV: 319In Single Zone
VAV confi gura-
tion, this is the
fan speed at
which the VFD
will start when
Cooling is
initiated. In a
VAV confi gura-
tion this is the
lowest fan speed
allowed in the
Cooling Mode.
In CAV and
MUA confi gura-
tions this should
be set to 100%.
Limits
0%100%
030
030
40
PT-Link II BACnet3 Interface
Page 41
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Param-
eter
VFD Min
Position in
Heat Mode
VFD Min
Position in
Vent Mode
Remote
VFD
Position
Setpoint
OnBoard
Relay
Status
On Board
Relay 1
On Board
Relay 2
On Board
Relay 3
On Board
Relay 4
On Board
Relay 5
On Board
Relay 6
Expansion
Module
Relay 1
Expansion
Module
Relay 2
NameObjectDescription
VFDHtMinAV: 320In Single Zone
VAV confi gura-
tion, this is the
fan speed at
which the VFD
will start when
Heating is
initiated. In a
VAV confi gura-
tion this is the
lowest fan speed
allowed in the
Heating Mode.
In CAV and
MUA confi gura-
tions this should
be set to 100%.
VFDVtMinAV: 322Speed at which
the VFD will op-
erate in the Vent
Mode in Single
Zone VAV.
FrcFanSpAV: 266Override to
force the VFD to
this percentage
speed. Confi gur-
ing “Auto” will
restore normal
unit control of
the VFD speed.
OnRlysAI:44See page 47.
OnRly1BI: 127Current status
of VCB-X Main
Board relay 1.
OnRly2BI: 128Current status
of VCB-X Main
Board relay 2.
OnRly3BI: 129Current status
of VCB-X Main
Board relay 3.
OnRly4BI: 130Current status
of VCB-X Main
Board relay 4.
OnRly5BI: 131Current status
of VCB-X Main
Board relay 5.
OnRly6BI: 259Current status
of VCB-X Main
Board relay 6.
MnExRly1BI:311Current status of
Relay 1 on the
EM1 Expansion
Module.
MnExRly2BI:312Current status of
Relay 2 on the
EM1 Expansion
Module.
Limits
0%100%
0%100%
0%100%
Auto=65535
BACnet Properties for the VCB-X Controller
Param-
eter
Expansion
Module
Relay 3
Expansion
Module
Relay 4
Expansion
Module
Relay 5
12 Relay
Expansion
Module
Relay 1
12 Relay
Expansion
Module
Relay 2
12 Relay
Expansion
Module
Relay 3
12 Relay
Expansion
Module
Relay 4
12 Relay
Expansion
Module
Relay 5
12 Relay
Expansion
Module
Relay 6
12 Relay
Expansion
Module
Relay 7
12 Relay
Expansion
Module
Relay 8
12 Relay
Expansion
Module
Relay 9
NameObjectDescription
MnExRly3BI:313Current status of
Relay 3 on the
EM1 Expansion
Module.
MnExRly4BI:314Current status of
Relay 4 on the
EM1 Expansion
Module.
MnExRly5BI:315Current status of
Relay 5 on the
EM1 Expansion
Module.
RlExRly1BI:299Current status of
Relay 1 on the
12 Relay Expan-
sion
Module.
RlExRly2BI:300Current status of
Relay 2 on the
12 Relay Expan-
sion
Module.
RlExRly3BI:301Current status of
Relay 3 on the
12 Relay Expan-
sion
Module.
RlExRly4BI:302Current status of
Relay 4 on the
12 Relay Expan-
sion
Module.
RlExRly5BI:303Current status of
Relay 5 on the
12 Relay Expan-
sion
Module.
RlExRly6BI:304Current status of
Relay 6 on the
12 Relay Expan-
sion
Module.
RlExRly7BI:305Current status of
Relay 7 on the
12 Relay Expan-
sion
Module.
RlExRly8BI:306Current status of
Relay 8 on the
12 Relay Expan-
sion
Module.
RlExRly9BI:307Current status of
Relay 9 on the
12 Relay Expan-
sion
Module.
Limits
PT-Link II BACnet3 Interface
41
Page 42
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Param-
eter
12 Relay
Expansion
Module
Relay 10
12 Relay
Expansion
Module
Relay 11
12 Relay
Expansion
Module
Relay 12
NameObjectDescription
RlExRly10BI:308Current status of
Relay 10 on the
12 Relay Expan-
sion
Module.
RlExRly11BI:309Current status of
Relay 11 on the
12 Relay Expan-
sion
Module.
RlExRly12BI:310Current status of
Relay 12 on the
12 Relay
Expansion
Module.
Limits
Zone
Zone
42
PT-Link II BACnet3 Interface
Page 43
7. PARAMETER TABLES
7.1 VCB-X BACnet Parameters
7.1.1 VCB-X PT-Link II BACnet®
Property Identifi er:
The PT-Link II BACnet® Link amends the following property identity
to the BACnet® property identifi er.
Bad Supply Air Sensor (0),
Bad Return Air Sensor (1),
Bad Outside Air Sensor (2),
Bad Space Sensor (3),
Bad Main Expansion Board (4),
Bad Coil Temp Sensor (5),
Bad Co2 Sensor (6),
Bad Discharge Sensor (7),
Bad OA CFM Sensor (8),
Bad Exhaust CFM Sensor (9),
Bad Supply CFM Sensor (10),
Bad Return CFM Sensor (11),
Bad Reheat Module (12),
Bad ModGas Module (13),
Bad Relay Expansion Module (14),
Missing EM2 Expansion Board (15)
}
VcbxAlarmGroup2Bits ::= BIT STRING {
Mechanical Cooling Failure (0),
Mechanical Heating Failure (1),
Fan Proving Alarm (2),
Dirty Filter Alarm (3),
Emergency Shutdown Alarm (4),
Economizer Air Temperature Failure (5),
Not Economizing When It Should (6),
Economizing When It Should Not (7),
Economizer Damper Failure (8),
Economizer Excess Outdoor Air (9)
}
VcbxAlarmGroup3Bits ::= BIT STRING {
High Supply Air Cutoff (0),
Low Supply Air Cutoff (1),
High Control Mode Signal Alarm (2),
Low Control Mode Signal Alarm (3),
Digital Compressor Cutoff Alarm (4),
Digital Compressor Lockout Alarm (5),
High Head Pressure (6),
Loop Water Proof of Flow (7),
Low Suction Pressure (8),
Unsafe Suction Pressure (9),
Low Leaving Water Temp (10)
}
VcbxOnBoardRelaysBits ::= BIT STRING {
On Board Relay 1 (0),
On Board Relay 2 (1),
On Board Relay 3 (2),
On Board Relay 4 (3),
On Board Relay 5 (4)
On Board Relay 6 (5)
}
PT-Link II BACnet3 Interface
43
Page 44
Zone
7. PARAMETER TABLES
7.2 VCM-X Modular BACnet Parameters
Zone
NOTE: The following points for the VCM-X Modular , VCM-X
WSHP & RNE Controllers are additional points. All
points and property identifi ers in the VCM-X Control-
ler table (Section 7.5, page 48) also apply to the VCMX Modular, VCM-X WSHP, and RNE Controllers.
BACnet Properties for VCM-X Modular
ParameterNameObjectDescriptionLimits
Modulating
Compressor 2
Head Pressure
Signal 1 on
Head Pressure
Module 1
Head Pressure
Signal 2 on
Head Pressure
Module 1
Condenser
Fan Signal 1
On Head Pressure Module 1
Condenser
Fan Signal 2
On Head Pressure Module 1
Title 24
Economizer
Feedback
Title 24
Economizer
Alarms
Condenser
Fan Signal 1
On Head Pressure Module 2
Condenser
Fan Signal 2
On Head Pressure Module 2
Head Pressure
Signal 1 on
Head Pressure
Module 2
MdCmp2AI: 206Current position
of the 2nd Stage
of Compressor
Modulation.
HdPr1AI: 207Head Pressure
Signal 1 on Head
Pressure Module 1
HdPr2AI: 208Head Pressure
Signal 2 on Head
Pressure Module 1
CdFan1AI: 209Condenser Fan
Signal 1 On Head
Pressure Module 1
CdFan2AI: 210Condenser Fan
Signal 2 On Head
Pressure Module 1
T24EcFbAI: 384Current posi-
tion of feedback
from Economizer
actuator.
AlmGrp5AI: 391Alarms for the 24
Title Economizer
CdFan21AI: 392Condenser Fan
Signal 1 On Head
Pressure Module 2
CdFan22AI: 393Condenser Fan
Signal 2 On Head
Pressure Module 2
HdPr21AI: 394Head Pressure
Signal 1 on Head
Pressure Module 2
BACnet Properties for VCM-X Modular
ParameterNameObjectDescriptionLimits
Head Pressure
Signal 2 on
Head Pressure
Module 2
Remote VFD
Reset
Bad Return
Air Sensor
Title 24
Sensor Alarm
Title 24 Not
Economiz-
ing When It
Should
Title 24
Economiz-
ing When It
Should Not
Title 24
Damper
Failure
Title 24
Excess
Outdoor Air
HdPr22AI: 395Head Pressure
Signal 2 on Head
Pressure Module 2
RmVFDPosAV: 258Remote VFD
Position Reset
RaTpAlmBI: 365Alarm that indicates
a failure in the Re-
turn Air Sensor.
T24TpAlmBI: 385Outside Air or
Supply Air Tem-
perature Sensor is
shorted or missing.
T24NEWSBI: 386Economizer is
enabled but not fol-
lowing the desired
Economizer position commanded.
T24EWISNBI: 387Economizer is not
enabled but the
feedback signal
indicates a position
more open than the
minimum.
T24DpAlmBI: 388Economizer is en-
abled but not with-
in 10% of desired
position within 150
seconds.
T24ExsOABI: 389Economizer
feedback is lost or
Economizer is not
following com-
manded position.
-1100
44
PT-Link II BACnet3 Interface
Page 45
7. PARAMETER TABLES
7.3 VCM-X WSHP (Tulsa) & RNE BACnet Parameters
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
ParameterNameObjectDescriptionLimits
Modulating
Compressor 2
Head Pressure
Signal 1 on
Head Pressure
Module 1
Head Pressure
Signal 2 on
Head Pressure
Module 1
Condenser Fan
Signal 1 On
Head Pressure
Module 1
Condenser Fan
Signal 2 On
Head Pressure
Module 1
Water Temp. AWaterTpAAI: 220Current water
Water Temp. BWaterTpBAI: 221Current water
Condenser Fan
Signal 1 On
Head Pressure
Module 2
Condenser Fan
Signal 2 On
Head Pressure
Module 2
Head Pressure
Signal 1 on
Head Pressure
Module 2
Head Pressure
Signal 2 on
Head Pressure
Module 2
MdCmp2AI: 206Current position
of the
2nd Stage of
Compressor
Modulation.
HdPr1AI: 207Head Pressure
Signal 1 on
Head Pressure
Module 1
HdPr2AI: 208Head Pressure
Signal 2 on
Head Pressure
Module 1
CdFan1AI: 209Condenser Fan
Signal 1 On
Head Pressure
Module 1
CdFan2AI: 210Condenser Fan
Signal 2 On
Head Pressure
Module 1
temperature of
refrigerant for
System A.
temperature of
refrigerant for
System B.
CdFan21AI: 392Condenser Fan
Signal 1 On
Head Pressure
Module 2
CdFan22AI: 393Condenser Fan
Signal 2 On
Head Pressure
Module 2
HdPr21AI: 394Head Pressure
Signal 1 on
Head Pressure
Module 2
HdPr22AI: 395Head Pressure
Signal 2 on
Head Pressure
Module 2
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
ParameterNameObjectDescriptionLimits
Remote VFD
Reset
Title 24 Econo-
mizer Alarms
Compressor A1
Low Suction
Pressure Alarm
Compressor A1
Lockout Alarm
Compressor A2
Low Suction
Pressure Alarm
Compressor A2
Lockout Alarm
Compressor B1
Low Suction
Pressure Alarm
Compressor B1
Lockout Alarm
Compressor B2
Low Suction
Pressure Alarm
RmVFDPosAV:
258
AlmGrp5AI: 391 Alarms for the 24
A1LSPAlmBI: 222Alarm that
A1LktAlmBI: 223Alarm that
A2LSPAlmBI: 224Alarm that
A2LktAlmBI: 225Alarm that
B1LSPAlmBI: 226Alarm that
B1LktAlmBI: 227Alarm that
B2LSPAlmBI: 228Alarm that
Remote VFD
Position Reset
Title Economizer
indicates
Suction Pressure
for Compressor
A1 is below the
Low Suction
Pressure
Cooling (Heat-
ing) Setpoint.
indicates
Compressor A1
is locked out.
indicates
Suction Pressure
for Compressor
A2 is below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
indicates
Compressor A2
is locked out.
indicates
Suction Pressure
for Compressor
B1 is below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
indicates
Compressor B1
is locked out.
indicates
Suction Pressure
for Compressor
B2 is below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
-1100
PT-Link II BACnet3 Interface
45
Page 46
Zone
7. PARAMETER TABLES
Zone
7.3 VCM-X WSHP Tulsa & RNE BACnet Parameters
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
ParameterNameObjectDescriptionLimits
Compressor 4
Lockout Alarm
Low Water
Temperature 1
Alarm
Low Water
Temperature 2
Alarm
Proof of Water 1
Flow Alarm
Proof of Water 2
Flow Alarm
Module
Communica-
tions Alarm
Bad Return Air
Sensor
Title 24 Economizer Feedback
B2LktAlmBI: 229Alarm that
indicates
Compressor B2
is locked out.
LWT1AlmBI: 230Alarm that
indicates water
temperature is
below the
Leaving Water
Safety Setpoint
(Heating only)
for System A.
LWT2AlmBI: 231Alarm that
indicates water
temperature is
below the
Leaving Water
Safety Setpoint
(Heating only)
for System B
POWF1Alm BI: 232Alarm that
indicates no
Proof of Water
Flow for System
A (A1/A2)
POWF2Alm BI: 233Alarm that
indicates no
Proof of Water
Flow for System
B (B1/B2)
ComMAlmBI: 234Alarm that
indicates that one
or more Modules
are not
communicating
with the VCM-X
WSHP Control-
ler.
RaTpAlmBI: 365Alarm that
indicates
a failure in the
Return Air Sen-
sor.
T24EcFbAI: 384Current position
of feedback from
Economizer
actuator.
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
ParameterNameObjectDescriptionLimits
Title 24
Sensor Alarm
Title 24 Not
Economizing
When It Should
Title 24 Economizing When It
Should Not
Title 24 Damper
Failure
Title 24 Excess
Outdoor Air
T24TpAlmBI: 385Outside Air
or Supply Air
Temperature
Sensor is shorted
or missing.
T24NEWSBI: 386Economizer is
enabled but not
following the
desired Econo-
mizer position
commanded.
T24EWISN BI: 387Economizer is
not enabled but
the feedback
signal indicates
a position more
open than the
minimum.
T24DpAlmBI: 388Economizer is
enabled but not
within 10% of
desired position
within 150
seconds.
T24ExsOABI: 389Economizer
feedback is lost
or Economizer
is not follow-
ing commanded
position.
46
PT-Link II BACnet3 Interface
Page 47
7. PARAMETER TABLES
7.4 VCM-X WSHP (Coil) BACnet Parameters
BACnet Properties for VCM-X WSHP (Coil)
ParameterNameObjectDescriptionLimits
Modulating
Compressor 2
Head Pressure 1HdPr1AI: 207Head Pressure
Head Pressure 2HdPr2AI: 208Head Pressure
Condenser
Fan 1
Condenser
Fan 2
Water Temp. AWaterTpAAI: 220Current water
Remote VFD
Reset
Compressor A
Low Suction
Pressure Alarm
Compressor A
Lockout Alarm
Compressor B
Low Suction
Pressure Alarm
Compressor B
Lockout Alarm
Low Water
Temperature
Alarm
MdCmp2AI: 206Current
CdFan1AI: 209Condenser
CdFan2AI: 210Condenser
RmVFDPosAV:
A1LSPAlmBI: 222 Alarm that
A1LktAlmBI: 223
B1LSPAlmBI: 226
B1LktAlmBI: 227
LWT1AlmBI: 230
258
position of the
2nd Stage of
Compressor
Modulation.
for
1st
Compressor
for
2nd
Compressor
Fan 1
Signal Status
Fan 2
Signal Status
temperature.
Remote VFD
Position Reset
indicates
Suction
Pressure for
Circuit A is
below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
Alarm that indicates Circuit
A Compres-
sors are locked
out.
Alarm that
indicates
Suction
Pressure for
Circuit B is
below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
Alarm that indicates Circuit
B Compres-
sors are locked
out.
Alarm that
indicates water
temperature
is below the
Leaving Water
Safety Set-
point (Heating
only).
-1100
BACnet Properties for VCM-X WSHP (Coil)
ParameterNameObjectDescriptionLimits
Proof of Water
Flow Alarm
Module
Communica-
tions
Alarm
Bad Return Air
Sensor
Title 24 Economizer Feedback
Title 24
Sensor Alarm
Title 24 Not
Economizing
When It Should
Title 24 Economizing When It
Should Not
Title 24 Damper
Failure
Title 24 Excess
Outdoor Air
POWF1Alm BI: 232Alarm that
indicates no
Proof of Water
Flow.
ComMAlmBI: 234Alarm that
indicates that
one or more
Modules are
not commu-
nicating with
the VCM-X
WSHP
Controller.
RaTpAlmBI: 365Alarm that
indicates
a failure in
the Return Air
Sensor.
T24EcFbAI: 384Current
position of
feedback from
Economizer
actuator.
T24TpAlmBI: 385Outside Air
or Supply Air
Temperature
Sensor is
shorted or
missing.
T24NEWSBI: 386Economizer
is enabled but
not following
the desired
Economizer
position com-
manded.
T24EWISNBI: 387Economizer
is not enabled
but the feed-
back signal
indicates a
position more
open than the
minimum.
T24DpAlmBI: 388Economizer
is enabled but
not within
10% of de-
sired position
within 150
seconds.
T24ExsOABI: 389Economizer
feedback
is lost or
Economizer is
not following
commanded
position.
PT-Link II BACnet3 Interface
47
Page 48
7. PARAMETER TABLES
7.5 VCM-X BACnet Parameters
Zone
Zone
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescription
Alarm
Status
Control
Status
Occupied/
Mode
Enable
Cooling
Setpoint
Mirror
Control
Temperature
Duct Static
Pressure
Economizer
Position
Occupied/
Mode
Enable
Heating
Setpoint
Mirror
Modulating
Gas Valve
Position
On Board
Relays
Outdoor Air
Dewpoint
Outdoor Air
Humidity
Outdoor Air
Temperature
Outdoor Air
Wetbulb
Reheat
Valve
Position
Relief
Pressure
Return Air
Temperature
AlmStsAI: 1See Alarm
CtrlStsAI: 4Current operational
ClStAI: 7Occupied/ Mode
CtrlTpAI: 9Current value of the
DuctPrAI: 14Current value of the
EcoPosAI: 16Current position
HtStAI: 31Occupied/ Mode
MdHt-
2Pos
OnRlysAI: 44See page 53.
OaDwptAI: 47Current calculated
OaRhAI: 52Current value of the
OaTpAI: 54Current value of the
OaWtblAI: 55Current calculated
Rt2PosAI: 60Current position of
RfPrAI: 62Current value of the
RaTpAI: 64Current value of the
AI: 38Current position
status.
Enable Cooling
Setpoint Mirror.
control temperature
sensor.
duct static pressure
sensor.
of the economizer
damper.
Enable Heating
Setpoint
Mirror.
of MODGAS II
modulating gas
valve control.
outdoor air
dewpoint added on
version 1.09.
outdoor humidity
sensor.
outdoor tempera-
ture sensor.
value of the outdoor
wetbulb
temperature.
MHGRV modulat-
ing hot gas reheat
valve control.
building pressure
sensor.
return temperature
sensor.
Group Bits on
Limits
page 53.
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescription
Indoor
Humidity
Space
Temperature
Current
Supply Air
Setpoint
Supply Air
Temperature
Temperature
Demand
VFD
Blower Fan
VFD
Relief Fan
Application
Software
Version
Alarm
Group 1
Alarm
Group 2
Alarm
Group 3
Dewpoint
Setpoint
Mirror
External
Relays 1-2
External
Relays 3-4
Indoor Rh
Setpoint
Mirror
InRhAI: 67Current value of
SpcTpAI: 72Current value of the
SaTpStMAI: 82Current SAT
SaTpAI: 83Current value of the
TpDmndAI: 84Based on the
VfdBw-
Pos
VfdExPosAI: 89Current position of
AppVerAI: 99Current version of
AlrmGrp1AI: 104See Alarm
AlrmGrp2AI: 105See Alarm
AlrmGrp3AI: 106See Alarm
DptStMAI: 110Mirror of the DPtSt
ExRlys12AI: 111See page 53.
ExRlys34AI: 112See page 53.
InRhStMAI: 114Mirror of the
AI: 88Current position of
the indoor humidity
sensor.
space temperature
sensor.
Cooling or Heating
setpoint if there
is no reset source;
Current calculated
SAT setpoint with
Reset Source.
supply air
temperature sensor.
comparison
between the
current Control
Temperature and
the Heating or
Cooling Setpoint
Temperatures. Does
not work for supply
air control
the VFD blower fan
signal.
the VFD relief
fan signal.
the software in the
unit.
Group Bits on
Group Bits on
Group Bits on
“read only.”
InRhSt “read only.”
Limits
page 53.
page 53.
page 53.
48
PT-Link II BACnet3 Interface
Page 49
7. PARAMETER TABLES
7.5 VCM-X BACnet Parameters
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescription
Modulating
Cool
Position
Modulating
Heat
Position
Unit ModeUnitModeAI: 123See page 53.
Return Air
CO
Level
2
Bypass
Damper
Position
Return
Damper
Position
Coil
Temperature
Outdoor Air
CFM
Exhaust
CFM
Supply Air
CFM
Current
Calculated
OA CFM
setpoint
Dewpoint
Setpoint
Occupied/
Mode
Enable
Cooling
Setpoint
MdClPosAI: 115Current position of
MdHtPosAI: 116Current position of
CO2LevelAI: 150Current value of the
ByPas-
Dmp
RaDmpAI: 154Current position of
CoilTpAI: 181Current coil
OaCFMAI: 193Current Outdoor
EtCFMAI: 194Current Exhaust
SaCFMAI: 195Current Supply
OACfm-
StM
DptStAV: 13If the outdoor
OcpClStAV: 42If the control tem-
AI: 153Current position of
AI: 205Current calculated
the modulating
cooling signal
(Chilled water or
digital compressor).
the modulating
heating signal (hot
water or SCR heat).
CO2 sensor.
the bypass damper
signal.
the return damper
signal.
temperature reading
added on version
1.09.
Airfl ow
Measurement
Airfl ow
Measurement
Airfl ow
Measurement
Outdoor Air CFM
based on CO
dewpoint rises
above this setpoint,
the unit will
activate the
Dehumidifi cation
perature rises one
degree above this
setpoint, the control
will activate the
cooling demand. If
the control tempera-
ture is the Supply
Air Sensor, then the
cooling demand is
always active.
Demand.
level.
2
Limits
3580
099
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescription
Occupied/
Mode
Enable
Heating
Setpoint
Outdoor
Air Sensor
Offset
Return
Air Sensor
Offset
Schedule
Force
Space
Sensor
Offset
SAT
Cooling
Setpoint
SAT
Heating
Setpoint
Supply
Air Sensor
Offset
OcpHtStAV: 43If the control
temperature drops
one degree below
this setpoint,
the control will
activate the heating
demand. If the
control
temperature
is the Supply Air
Sensor, then there is
no heating demand.
OaTpOstAV: 53If the Outdoor
Temperature Sensor
is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
RaTpOstAV: 65If the Return Tem-
perature Sensor is
reading incorrectly,
you can use this
option to enter an
offset temperature
to adjust the Sen-
sor’s T emperature.
SchdFrcAV: 660 = Auto/
Unoccupied Mode
1 = Forced On
2 = Forced Off
SpcTpOstAV: 71If the Space
Temperature
Sensor is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
SaClStAV: 77Supply Air Setpoint
in Cooling Mode.
SaHtStAV: 78Supply Air Setpoint
in Heating Mode.
SaTpOstAV: 80If the Supply Air
Temperature Sensor
is reading incorrectly, you can use
this option to enter
an offset
temperature to
adjust the Sensor’s
Temperature.
099
-100100
-100100
02
-100100
4080
40200
-100100
Limits
PT-Link II BACnet3 Interface
49
Page 50
7. PARAMETER TABLES
7.5 VCM-X BACnet Parameters
Zone
Zone
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescription
Warm Up
Setpoint
Wet Bulb
Setpoint
Coil
Temperature
Setpoint
Relief
Pressure
Setpoint
Indoor
Humidity
Setpoint
Unoccupied
Cooling
Offset
Unoccupied
Heating
Offset
WmupStAV: 91In a VAV
application, upon
entering the oc-
cupied mode, the
Warm-up Demand
will be activated
if the return air
temperature falls
one degree below
this setpoint.
WtblStAV: 92The economizer is
enabled if the
outdoor tempera-
ture or wetbulb falls
below this setpoint.
CoilTpStAV: 107This is the coil
suction temperature
target during
dehumidifi cation
mode. Produces
dewpoint in the
supply air
approximately 10°F
above this setpoint.
RfPrStAV: 118This is the target
building pressure
to be maintained
by the VFD Relief
signal.
InRhStAV: 120If the indoor
humidity rises
above this setpoint,
the unit will acti-
vate the Dehumidi-
fi cation Demand.
UnClOstAV: 124During the
Unoccupied Mode
of Operation, this
Setpoint spreads the
Occupied Cooling
Setpoint out by
a user adjustable
amount. If you do
not want Cooling to
operate during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
UnHtOstAV: 125During the
Unoccupied Mode
of Operation, this
Setpoint spreads the
Occupied Heating
Setpoint out by
a user adjustable
amount. If you do
not want Heating to
operate during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
5090
080
3570
-0.20.2
0100
030
030
Limits
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescription
CO
Setpoint
Minimum
Outside Air
Setpoint
Static
Pressure
Setpoint
Preheater
Setpoint
Outdoor
Air CFM
Setpoint
Outdoor Air
CFM Reset
Limit
Supply Air
Cool High
Reset
Supply Air
Heat High
Reset
Cooling
Low Reset
Source
Cooling
High Reset
Source
Heating
Low Reset
Source
Heating
High Reset
Source
CO2StAV: 149When the CO2
2
MinEcoStAV: 151This is the
DuctPrStAV: 152This is the target
PreHtSpAV: 196Low Outside Air
OACfmStAV: 203Minimum desired
OACfmRs AV: 204Maximum desired
SaClRtAV: 324High Supply Air
SaHtRtAV: 325High Supply Air
ClLoRtAV: 326Low Cool Reset
ClHiRtAV: 327High Cool Reset
HtLoRtAV: 328Low Heat Reset
HtHiRtAV: 329High Heat Reset
level rises above
the CO2 Protection
Limit Max Level,
the Economizer’s
Minimum Position
will begin to reset
open proportionally
between the CO
Protection Limit
Max Level Setpoint
Range Setpoint.
minimum position
of the economizer
in the occupied
duct pressure to be
maintained by the
VFD blower signal.
Protection Setpoint
Outdoor Air CFM.
Outdoor Air CFM
when CO
Heating Reset Limit
Source Setpoint
Source Setpoint
Source Setpoint
Source Setpoint
and the Reset
modes.
Ambient
reaches
2
its reset limit.
Cooling Reset
Limit
03000
2
1100
0.013
0100
0.10 K200 K
0.10 K200 K
40150
40150
1150
1150
1150
1150
Limits
50
PT-Link II BACnet3 Interface
Page 51
7. PARAMETER TABLES
7.5 VCM-X BACnet Parameters
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescriptionLimits
Bad Supply
Air Sensor
Sensor
CO
2
Installed
Cooling
Enabled
Economizer
Enabled
Fan Start Up
Delay
Fan
Proving
Alarm
Heating
Enabled
High
Supply Air
Temperature
Alarm
Low Supply
Air
Temperature
Alarm
MODGAS
II
Connected
Proof of
Flow
Confi gured
REHEAT II
Connected
SaTpAlmBI: 2Alarm that
indicates a failure
in the
supply air sensor.
CO2CfgBI: 3Status that
indicates the CO2
function has been
confi gured.
ClEnbl BI: 6Status that indicates
mechanical cooling
is enabled.
EcoEnblBI: 15Status that indicates
the economizer is
enabled.
FanDly BI: 25Status that indicates
the fan is
commanded to run,
but it is in the start
up delay mode.
PofAlmBI: 26Alarm that
indicates a failure
in the fl ow of the
VFD blower.
HtEnblBI: 30Status that
indicates that
mechanical heating
is enabled.
HiSaAlmBI: 33The Supply Air
has risen above
the Hi SAT Cutoff
Setpoint. Heating
stages begin to deac-
tivate and the fan
continues to run.
LoSaAlmBI: 37The Supply Air has
fallen below the Hi
SAT Cutoff Setpoint
and cooling stages
will begin to deactivate. If the unit is in
Economizer, Vent,
or Heating Mode
the Supply Fan will
shut off.
MdHt2InsBI: 39Status that indicates
the MODGAS II
controller is
connected.
PofCfgBI: 57Status that indicates
the proof of fl ow
function has been
confi gured.
Rt2InsBI: 58Status that indicates
the MHGRV
controllers is
connected to the
system.
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescriptionLimits
Mechanical
Cooling
Alarm
Mechanical
Heating
Alarm
Dirty Filter
Detected
Control
Temperature
Cool Failure
Control
Temperature
Heat Failure
Outdoor Air
Temperature
Lost
Smoke
Detected
Alarm
Space
Temperature
Sensor Lost
MchClAlmBI: 94Compressor Relays
are enabled but
the Supply Air
Temperature has
not fallen 5°F w/in
a user-adjustable
time period. This
does not indicate
compressors are
active and will not
shut the unit down.
MchHtAlmBI: 95Heating Mode has
been initiated but
the Supply Air
Temperature has
not risen 5°F w/in
a user-adjustable
time period. This
does not indicate
heat stages are
active and will not
shut the unit down.
DrtFlAlmBI: 96Alarm that indicates
the fi lters are dirty.
CtrlTpCFBI: 108This alarm is
activated if the
control temperature
does not get within
5°F to the occupied
cooling setpoint
in an hour in the
cooling mode. This
alarm is not used
in 100% outside air
units or supply air
control.
CtrlTpHFBI: 109This alarm is
activated if the
control temperature
does not get within
5°F to the occupied
heating setpoint
in an hour in the
heating mode. This
alarm is not used
in 100% outside air
units or supply air
control.
OaTpAlmBI: 117Alarm that
indicates a failure
in the outdoor air
temperature.
SmokeAlmBI: 119Alarm that indicates
the Smoke sensor
has been activated.
SpcTpAlmBI: 101Alarm that indicates
a failure in the
space temperature
sensor.
PT-Link II BACnet3 Interface
51
Page 52
7. PARAMETER TABLES
7.5 VCM-X BACnet Parameters
BACnet Properties for the VCM-X Controller
ParameterNameObjectDescriptionLimits
On Board
Relay 1
On Board
Relay 2
On Board
Relay 3
On Board
Relay 4
On Board
Relay 5
Expansion
Relay 1
Expansion
Relay 2
Expansion
Relay 3
Expansion
Relay 4
Expansion
Relay 5
Expansion
Relay 6
Expansion
Relay 7
Expansion
Relay 8
Expansion
Relay 9
Expansion
Relay 10
Expansion
Relay 11
Expansion
Relay 12
Expansion
Relay 13
Expansion
Relay 14
Expansion
Relay 15
Expansion
Relay 16
OnRly1BI: 127Current status of
relay 1.
OnRly2BI: 128Current status of
relay 2.
OnRly3BI: 129Current status of
relay 3.
OnRly4BI: 130Current status of
relay 4.
OnRly5BI: 131Current status of
relay 5.
ExRly1BI: 133Current status of
relay 6.
ExRly2BI: 134Current status of
relay 7.
ExRly3BI: 135Current status of
relay 8.
ExRly4BI: 136Current status of
relay 9.
ExRly5BI: 137Current status of
relay 10.
ExRly6BI: 138Current status of
relay 11.
ExRly7BI: 139Current status of
relay 12.
ExRly8BI: 140Current status of
relay 13.
ExRly9BI: 141Current status of
relay 14.
ExRly10BI: 142Current status of
relay 15.
ExRly11BI: 143Current status of
relay 16.
ExRly12BI: 144Current status of
relay 17.
ExRly13BI: 145Current status of
relay 18.
ExRly14BI: 146Current status of
relay 19.
ExRly15BI: 147Current status of
relay 20.
ExRly16BI: 148Current status of
relay 21.
Zone
Zone
52
PT-Link II BACnet3 Interface
Page 53
7. PARAMETER TABLES
7.5 VCM-X BACnet Parameters
7.5.1 VCM-X PT-Link II BACnet®
Property Identifi er:
The PT-Link II BACnet® Link amends the following property identity
to the BACnet® property identifi er.
8.1 The FieldServer Graphical User
Interface (FS-GUI) with Confi guration
Parameter Page Navigation Tree
Open your web browser , and type the IP Address of the PT -Link, which
is <192.168.1.24>, and press <ENTER>. The FS-GUI Confi guration
Parameter Page will launch. See Figure 38.
Figure 38: The FS-GUI Main Screen
Refer to the Figure 39 to navigate the FS-GUI.
About
About allows you to check the current fi rmware of the Field Server
gateway plus version identifi cation of the interface and skin, plus contact
information. Skin is either the default FieldServer template or a specifi c
template specifi ed by the user.
Setup
Setup includes File Transfer, Network Settings, and Passwords.
File Transfer—Select “File Transfer” to upload fi les to the FS
gateway, including confi guration fi les, fi rmware, upgrades, and
more. Information regarding File Transfers can be found on page 13.
Network Settings—Select “Network Settings” to access and
modify network connection. See page 65 for further information.
Passwords—There are 2 levels of passwords that can be set, Admin
and User. See pages 65 and 66 for further information.
View
View includes Connections, Data Arrays, Nodes, and Map Descriptors.
Connections—This screen supplies information on communica-
tion between the FS and remote devices. A number of aspect screens
are available including settings, info stats, and error stats. The information on these screens cannot be changed and is for viewing only.
Data Arrays—The Data Array Screens can be used to view the
values in data arrays. The values can be changed by clicking the
<Enable Data Editing> button. You can then edit setpoints by
typing the new value and pressing <ENTER>. Note that if values
are being written into the array by a driver, then any modifi cations
made by grid editing will be overridden.
Nodes—On the Nodes Screens, information about the remote device
on each connection can be viewed. A number of aspect screens are
available, including settings, status, info stats, and error stats. The information on these screens cannot be changed and is for viewing only.
Map Descriptors—On the Map Descriptors Screens, informa-
tion on each individual Map Descriptor can be viewed. A number
of aspect screens are available, including settings, status, info stats,
and error stats. The information on these screens cannot be changed
and is for viewing only.
Figure 39: The Navigation Tree
Home or Root
The root of the navigation tree includes Status, Settings, and Info Stats.
Status allows you to check the status of the PT -Link gateway , including
the confi guration code, version, memory, gateway type, and more. Under
Settings, you can access important network information. The name of
the root—W attmaster MSTP v1.04i—is completely user defi nable. The
<Home> button is found at the left bottom of the FS-GUI Main Screen.
Press this button to return to FS-GUI Main Screen.
64
User Messages
The user message screens display FS messages generated by drivers
and the operating system.
Error Screen—User messages on this screen usually indicate
some problem with the confi guration or communication and should
be attended to.
Info Screen—User messages of an informational type will be
displayed on the this screen and no user action is usually required.
Driver Screen—Messages generated by protocol drivers will be
displayed on this screen. These messages convey protocol specifi c
information that can be useful for fi eld integration purposes.
Combined Screen—This screen contains all messages chronologi-
cally from all the above message screens.
PT-Link II BACnet3 Interface
Page 65
8. FS-GUI REFERENCE GUIDE
8. FieldServer Graphical User Interface
HELP or F1
The <Help> button is located at the bottom left of the FS-GUI Main
Screen. Or, simply press
<F1> for Help.
System Restart
The <System R estart> button is located at the bottom of the FS-GUI
Main Screen. System Restart will restart the FS Gateway.
8.2 Network Settings
1.) In the Navigation Window on the left of the FS-GUI Screen, click
<Setup> and then click <Network Settings>. See Figure 40. The
Networks Settings Window will appear.
NOTE: The FieldServer has to be restarted for any changed
settings to take effect. Also note that enabling the
DHCP client on an adapter will cause the static IP
address settings to be overruled by a DHCP server
on the network.
The FieldServer’s built in DHCP server can be enabled to establish
easy connection for Support purposes. Set the laptop or computer to
automatically obtain an IP address to use this feature. Note that the
Field Server DHCP server periodically checks for other DHCP servers
on the network and will disable itself should any other DHCP servers
exist on the network. This mode of operation is because the FieldServer
DHCP server is strictly for support purposes and does not have all of the
features of a commercial DHCP server. Setting the default gateway IP
address to your network gateway will ensure the FieldServer is reachable on the internet.
8.3 Setting a Passw ord for the FS-GUI
Access to the FS-GUI can be restricted by enabling a password. By
default, there are no passwords required to access the FS-GUI. There
are 2 access levels defi ned by 2 account names: Admin or User. The
Admin account has unrestricted access to the FS-GUI. The User account can view any FS-GUI information, but cannot make any changes
or restart the FS-GUI.
Figure 40: Setup - Network Settings
2.) In the Network Settings Window (Figure 41), the Ethernet adapter
settings of the FieldServer can be changed. The N1 and N2 (if supported)
adapter IP address, Netmask, and default Gateway can be changed by
entering values in the applicable fi elds and clicking on <Update IP
Settings>
NOTE: The only time you should change the IP address is
.
during the initial confi guration and/or during trouble-
shooting.
Figure 41: Network Settings Window
NOTE: The current Admin password (if set) is required to
change all passwords. In other words, you must log
in with the Admin password to change a password
unless the password function is disabled.
1.) In the Navigation Window on the left of the FS-GUI Screen, click
<Setup> and then click <Passwords>. See Figure 42. The Passwords
Window will appear.
Figure 42: Setup - Passwords
PT-Link II BACnet3 Interface
65
Page 66
Zone
Zone
8. FS-GUI REFERENCE GUIDE
8. FieldServer Graphical User Interface
2.) In the Passwords W indow, select <Admin> as the Account Name.
Then type a password in the New Password fi eld, retype the password
in the Confi rm Password fi eld and then click <Update Password>.
See Figure 43. If you are changing the Admin password, you must
type the current password in the Current Admin Password fi eld.
NOTE: The password must be less than 20 characters in
length. We recommend that the password be at least
8 characters in length and that 3/4 of the characters
should consist of the following: uppercase letters,
lower case letters, numbers, and symbols.
Figure 45: Clear Passwords
5.) In order to return to the Passwords Window, in the Navigation Window on the left of the FS-GUI Screen, click <Setup> and then click
<Passwords>. See Figure 46. The Passwords Window will appear.
Zone
Zone
Figure 43: Changing the Admin Password
3.) If the passwords match, the Authentication Window may will pop
up. You must type the User Name “Admin” and the password you just
created in the window to proceed. See Figure 44.
Figure 44: Authentication Log In
4.) After authentication takes place, the FS-GUI will return to the main
screen.
Figure 46: Setup - Passwords
6.) To create or update the User password, in the Passwords Window,
select <User> as the Account Name. Y ou must type the Admin password
in the Current Admin Password fi eld. Then type a password in the New
Password fi eld, retype the password in the Confi rm Password fi eld and
then click<Update Password>. See Figure 47.
NOTE: The password must be less than 20 characters in
length. We recommend that the password be at least
8 characters in length and that 3/4 of the characters
should consist of the following: uppercase letters,
lower case letters, numbers, and symbols.
NOTE: To disable password protection, clear the Admin
password by simply selecting<Admin> as the
Account Name, typing in the Admin password in the
Current Admin Password fi eld and leaving the last
two fi elds blank. Then click <Update Password>.
See Figure 45.
66
Figure 47: Changing the User Password
7.) If the user password update is successful, a message will pop up
confi rming the password update.
Product Model
Number: ProtoCessor FFP-485 (FPC-FD2)
Product Description: ProtoCarrier and ProtoCessor are products
supplied to OEMs to rapidly
implement BACnet in their products.
BACnet Protocol
Version: Version 1 Revision 4
BACnet Standarized Device Profi le (Annex L) -
[Note: FieldServer is a gateway device]
BACnet Application Specifi c Controller (B-ASC)
BACnet Interoperability Building Blocks
Supported (Annex K):
K.1.2 BIBB - Data Sharing - ReadProperty-B (DS-RP-B) K.1.4 BIBB - Data Sharing - ReadPropertyMultiple-B
(DS-RPM-B)
K.1.8 BIBB - Data Sharing - WriteProperty-B (DS-WP-B) K.1.10 BIBB - Data Sharing - WritePropertyMultiple-B
(DS-WPM-B)
K.1.12 BIBB - Data Sharing - COV-B (DS-COV-B) K.2.2 BIBB - Alarm and Event-Notifi cation Internal-B
(AE-N-I-B)
K.2.5 BIBB - Alarm and Event-ACK-B (AE-ACK-B) K.2.11 BIBB - Alarm and Event-Information-B
(AE-INFO-B)
K.5.1 BIBB - Device Management - Dynamic Device
Binding-A (DM-DDB-A)
K.5.2 BIBB - Device Management - Dynamic Device
Binding-B (DM-DDB-B)
K.5.4 BIBB - Device Management - Dynamic Object
Binding-B (DM-DOB-B)
K.5.6 BIBB - Device Management - Device
Communication Control-B (DM-DCC-B)
K.5.12 BIBB - Device Management - Time
Synchronization-B (DM-TS-B)
K.5.22 BIBB - Device Management – List Manipulation-B
(DM-LM-B)
70
PT-Link II BACnet3 Interface
Page 71
10. BACNET PICS STATEMENT
10. BACnet PICS Statement
Segmentation Capability: None
Object Types and Optional Properties Supported
Object TypeOptional Properties
Supported
Device ObjectLocation
Description
UTC Offset
Active COV Subscriptions
Analog InputReliability
Description
Analog OutputReliability
Description
Max_Pres_Value
Min_Press_Value
Analog OutputBinary InputReliability
Description
Active_Test
Inactive_Test
Binary OutputReliability
Description
Active_Test
Inactive_Test
Binary ValueReliability
Description
Active_Test
Inactive_Test
Multi State InputReliability
Description
State_Test
Multi State OutputReliability
Description
State_Test
Multi State ValueReliability
Description
State_Test
Notifi cation Class Object
For all of these properties, the following applies:
1.) Does not support BACnet CreateObject
2.) Does not support BACnet DeleteObject
3.) No proprietary properties exist
Data Link Layer Options:
MS/TP master (Clause 9), baud rate up to 76.8 Kbps MS/TP slave (Clause 9), baud rate up to 76.8 Kbps
Device Address Binding: Not supported
Character Sets Supported:
Where support for multiple character sets is indicated, this does not
imply that they can all be supported simultaneously.
ISO 10646 (UTF-8) / ANSI X3.4
PT-Link II BACnet3 Interface
71
Page 72
Form: OR-PTLNK3BTL-TGD-01D June 2015
All rights reserved. Printed in the USA Copyright 2015
WattMaster Controls, Inc. 8500 NW River Park Drive Parkville, MO 64152
Phone (816) 505-1100 www.orioncontrols.com Fax (816) 505-1101
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.