General Information ......................................................................................................................................... 3
Data Sharing ................................................................................................................................................................................3
System Requirements ..................................................................................................................................................................3
Dimensions and Components ......................................................................................................................................................4
Connection and Wiring Information ................................................................................................................ 5
Confi guring the PT-Link II Controller ............................................................................................................... 6
PT-Link II Hardware Connection ..................................................................................................................................................6
Computer IP Address Set-up for Windows NT & XP ....................................................................................................................7
Computer IP Address Set-up for Windows Vista & 7 ...................................................................................................................8
Confi guring the PT-Link DIP Switches .........................................................................................................................................9
Connecting to the PT-Link II .......................................................................................................................................................10
Making Changes to the Confi guration File (confi g.csv) ..............................................................................................................12
Downloading Confi g.csv to the PT-Link II...................................................................................................................................13
Troubleshooting the PT-Link II Controller ..................................................................................................... 14
Addressing WattMaster Devices in a BACnet® Network. ...........................................................................................................14
PT-Link II Board LEDs ................................................................................................................................................................15
Troubleshooting Using RUINET .................................................................................................................................................18
Updating the PT-Link II Controller................................................................................................................. 19
Data Arrays .................................................................................................................................................... 23
Table 3: VCB-X Modular Data Array for Field Server ................................................................................................................23
Table 4: VCM-X Modular Data Array for Field Server................................................................................................................23
Table 5: VCM-X WSHP (Tulsa) & RNE Data Array for Field Server ..........................................................................................24
Table 6: VCM-X WSHP (Coil) Data Array for Field Server ........................................................................................................25
Table 7: VCM-X Data Array for Field Server..............................................................................................................................25
Table 8: SA Controller Data Array for Field Server ....................................................................................................................26
Table 9: VCM Data Array For Field Server ................................................................................................................................26
Appendix A - RJ-45 8P8C Cable for WattMaster Cross Over Networking - WattMaster Part #HZ000136 ............................ 27
Appendix F - VCM-X BACnet Parameters ...................................................................................................... 42
Appendix G - SA Controller BACnet Parameters .......................................................................................... 48
Appendix H - VCM BACnet Parameters ......................................................................................................... 52
WattMaster Controls, Inc.
8500 NW River Park Drive · Parkville, MO 64152
Toll Free Phone: 866-918-1100
PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com
Visit our web site at www.orioncontrols.com
Form: OR-PTLNK2BTL-TGD-01G Copyright April 2013 WattMaster Controls, Inc.
BACnet® is a registered trademark of ASHRAE Inc., Atlanta, GA.
WattMaster Controls, Inc. assumes no responsibility for errors or omissions.
This document is subject to change without notice.
PT-Link II BACnet® Technical Guide
General Information
The OE368-23B-BACNET2, PT -Link II BACnet® provides bi-directional communication between your BACnet® MS/TP protocol network and
up to four* of any of the following types of Orion controllers—RNE,
VCB-X, VCM-X, SA, VCM, MUA II, or VAV/CAV:
To determine what controller you have, you must look at the label located
on the controller EPROM. If the controller label does not match any of
the SS or Y numbers listed above, your controller will not work with
the PT-Link II BACnet®.
*NOTE: The PT-Link II BACnet® device can be used to con-
nect to four Orion controllers. If more than four Orion
controllers are present in a system, you will need one
or more additional PT-Link II BACnet® devices for
integration with a BACnet® protocol network.
**NOTE: Documentation is available for MUA II/VAV/CA V on
Table 1: PT-Link II BACnet® Interface
Technical Data
System Requirements
Data Sharing
The PT-Link II BACnet® interface provides the following data sharing
capabilities:
• Provides values from points on the Orion side of the
gateway to BACnet
originating from BACnet® objects.
• Allows BACnet
Orion controller side of the PT-Link II BACnet
standard BACnet® write services.
®
devices as if the values were
®
devices to modify point values on the
®
by using
• The PT-Link II BACnet
assembled as surface mount. Surface mount components
are included for your convenience.
• Computer running Microsoft Windows
system.
®
interface is packaged and
TM
operating
• Ethernet Crossover Cable (supplied).
• PT-Link II BACnet software—located on included CD-
ROM and downloadable from www.orioncontrols.com/
software-new.html.
• * RUINET software— located on included CD-ROM and
downloadable from www.orioncontrols.com/software-new.
html.
*NOTE: RUINET is only needed for initial confi guration if you
need to set the address above 255 or if your BACnet
lacks DIP switches. The confi g.csv fi le’s Server_DIP
parameter is initially set to Enabled which allows
the System_Node_ID (BACnet MAC Address) and
Node_ID (Device Instance) to be set using the DIP
Switches on the module.
PT-Link II Interface 3
Revised 10/11/12
PT-Link II BACnet® Technical Guide
Setting Up Your PT-Link II
Quick Guide
The following steps will get you up and running in no time:
1. Familiarize yourself with the PT-Link II components (Figure 1).
2. Connect your PT-Link II to the Controller(s) on your system (up
to four) and connect your PT-Link II to the BACnet Network
(Figure 2).
3. If the BACnet address doesn’t need to be any higher than 255,
then you can use the DIP switch settings to confi gure your PT-Link II. Skip to page 9. Set the DIP Switches, wait 4 minutes,
and you’ll be up and running. If the address needs to be higher
than 255, or your BACnet module does not have DIP switches,
continue with Step 4.
4. Copy the contents of the PT Link II CD to your PC’s Desktop.
You can also download the fi les from http://orioncontrols.com/software-new.html under PT-Link II Setup Files. These fi les
include RUINET.
BACnet
Communications
Wiring Terminal
®
2.37
5. Connect your PT-Link II to your computer using an Ethernet
connection (Figures 3 & 4).
6. Change your PCs IP Address. Follow the directions that match
your current operating system - Windows NT, XP, Vista, or 7.
See directions on pages 7 & 8.
7. Obtain the following from your Building Automation System
Integrator: the BACnet MAC address (System Node ID), your
server’s baud rate, and the Client Node ID.
8. Using RUINET, edit the Confi g.csv fi le and verify PT Link II communications. Follow the directions on pages 10-13.
9. If you run into any problems, follow the instructions in the
Troubleshooting section starting on page 14 of this guide.
4.25
1.31
Configuration
DIP Switches
BACnet
®
Protocessor
Module
Ethernet
Port
4.70
4.31
0.27
O
N
2
1
RX TX
www.protocessor.com
485
RSGND
ON
O
N
4
2
3
345
678
1
Protocol Coprocessor
PROTOCESSOR
www.orioncontrols.com
OE368-23B-BACNET
PT-LINK II PROTOCOL
TRANSLATOR
FOR BACNET
LED BLINK CODES (NORMAL)
LOOP
PROTO
LED 1
LED 2
TIMER
WATCH DOG
H-BEAT
WattMaster Label
#LB102082
Rev. 01A
=RAPID BLINK
=RAPID BLINK
=BLINKS QTY
CONTROLLERS
=STEADYBLINK
=STEADYBLINK
= ON SOLID
= STEADY BLINK
GND
+24 VAC
2.61
DRIVER
COMM
R
SH
T
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
MADE IN USA
4.82
0.20 Dia.
Local Loop
Communications
Driver Chip
Local Loop
Communications
Wiring Terminal
Communications
LED
Diagnostic
LED #1
Diagnostic
LED #2
Power
LED
Mounting Hole
Typ. 3 PL.
USB
24 VAC Power
Terminal
Port
Figure 1: PT-Link II BACnet® Dimensions and Components
4
Revised 5/11/11
PT-Link II Interface
MS/TP Connection
®
BACnet
ToNetwork
RSGND
ON
O
O
N
N
4
2
3
2
345
678
1
1
RX TX
Protocol Coprocessor
www.protocessor.com
PROTOCESSOR
PT-Link Interface
www.orioncontrols.com
OE368-23B-BACNET
PT-LINK II PROTOCOL
TRANSLATOR
FOR BACNET
LED BLINK CODES (NORMAL)
LOOP
=RAPID BLINK
PROTO
=RAPID BLINK
LED 1
=BLINKS QTY
CONTROLLERS
LED 2
=STEADYBLINK
TIMER
=STEADYBLINK
WATCH DOG
= ON SOLID
H-BEAT
=STEADYBLINK
WattMaster Label
GND
#LB102082
Rev. 01A
+24VAC
MS/TP Connection
®
BACnet
ToNetwork
485
DRIVER
COMM
R
SH
T
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
MADE IN USA
PT-Link II BACnet® Technical Guide
Connection and Wiring Information
IMPORTANT WIRING NOTE:
Use the Daisy-Chain Topology As Shown in This Diagram.
DO NOT Use a Star Topology with Multiple Units Tied
Directly to the PT-Link II.
Up To 4 Controllers
Can Be Interconnected.
Controller’s Address
Cannot Be Higher Than 16.
Controller
Controller
24 VAC
(10 VA)
Line Voltage
Caution: The BACnet
Communication Terminal Block
Must Be Disconnected Before
Connecting The Modular Service
Tool. After Programming The
Controller(s), Disconnect The
Service Tool and Then Reconnect
The Communication Terminal
Note: All Programming Of
Controllers Must Be Done
Using The Modular Service
Tool. The Modular System
Manager Should Not Be Used
On A System That Has A PTLink Installed.
Wiring Notes:
1.) All wiring to be in accordance with local and national electrical codes
and specifications.
2.) All communication wiring to be 18 gauge minimum, 2 conductor twisted
pair with shield. Use Belden #82760 or equivalent.
®
UP
Mode
Selection
NEXT
PREV
STATUS
SETPOINTS
DOWN
CLEAR
ESC
SCHEDULES
ENTER
OVERRIDES
13
2
ALARMS
654
CONFIGURATION
BALANCE - TEST
9
708
DEC
MINUS
ON
-
Modular Service Tool
Typical Terminal Blocks. All
Wiring To Be T To T, SHLD
(G) To SHLD (G) & R To R
T
SHLD
R
24 VAC
(8 VA)
Line Voltage
Controller
24 VAC
(8 VA)
Line Voltage
24 VAC
(8 VA)
Line Voltage
Controller
24 VAC
(8 VA)
Line Voltage
Figure 2: PT-Link II BACnet® InterfaceWiring
PT-Link II Interface
Revised 8/31/11
5
PT-Link II BACnet® Technical Guide
Ethernet Cable
Ethernet Hub
Connect Ethernet
Cable To Ethernet
Hub Port
Connect Ethernet
Cables To Ethernet
Hub Ports
Desktop Or Laptop PC
1
2
3
4
Ethernet Cable
Connect Ethernet
Crossover Cable
To PT-Link Ethernet
Port
PT-Link BACnet
485
DRIVER
COMM
R
SH
T
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
MADE IN USA
www.orioncontrols.com
WattMaster Label
#LB102082
Rev. 01A
OE368-23B-BACNET
PT-LINK II PROTOCOL
TRANSLATOR
FOR BACNET
+24VAC
GND
LOOP
LED 1
LED 2
=RAPID BLINK
=BLINKS QTY
CONTROLLERS
=STEADYBLINK
PROTO
TIMER
WATCH DOG
H-BEAT
=RAPID BLINK
=STEADYBLINK
= ON SOLID
= STEADY BLINK
LED BLINK CODES (NORMAL)
PROTOCESSOR
ProtocolCoprocessor
www.protocessor.com
1
2
345
678
O
N
O
N
1
2
3
4
ON
RX TX
RSGND
PT-Link II Ethernet Connection
PT-Link II Hardware Connection
You have two options for connecting the PT-Link II to your PC via
Ethernet:
1.) You may connect the PT-Link II directly to your PC by
using a crossover cable (by others) as shown. See Figure 3
for details.
2.) You can also connect both your PC and the PT -Link II to an
Ethernet Hub with standard CAT5 cables. See Figure 4
for details.
Desktop Or Laptop PC
Connect Ethernet
Crossover Cable Directly
To PC Ethernet Card Port
Locate a CAT5 cable and plug one end into your computer’s Ethernet
port (use a crossover cable if connecting directly to the PT-Link II).
If connecting directly, plug the other end of the Cable into the Ethernet
port on the PT -Link II. If connecting through an Ethernet Hub, plug the
other end of the PC cable into the hub, and use a second CAT5 cable to
connect the PT-Link II to the hub as well.
Power up the PT -Link II by plugging in the power cable. The PT-Link II
may take up to three minutes to power up completely. Once the PT-Link
II is powered up, depending on which type of BACnet module you have,
you should notice that the green GP105 LED remains on or the RUN
LED is blinking continuously on the ProtoCessor Board. See Figure 25 and 27 on pages 16 & 17 for a diagram showing the location of the
ProtoCessor RUN or GP105 LED.
Ethernet Crossover Cable
PT-Link BACnet
485
www.orioncontrols.com
TRANSLATOR
FOR BACNET
=RAPID BLINK
=RAPID BLINK
=BLINKS QTY
=STEADYBLINK
=STEADYBLINK
= ON SOLID
= STEADY BLINK
CONTROLLERS
DRIVER
COMM
R
SH
T
LOOP
PROTO
LED1
LED2
TIMER
W_DOG
H-BEAT
POWER
GND
MADE IN USA
+24VAC
RSGND
ON
O
O
N
N
OE368-23B-BACNET
4
2
345
678
2
3
1
1
PT-LINK II PROTOCOL
RX TX
LED BLINK CODES (NORMAL)
LOOP
ProtocolCoprocessor
www.protocessor.com
PROTO
P
LED 1
ROTO
LED 2
C
TIMER
ESSOR
WATCH DOG
H-BEAT
WattMasterLabel
#LB102082
Rev. 01A
Connect Ethernet
Crossover Cable
To PT-Link Ethernet
Port
Figure 3: Connecting With Crossover Cable
Figure 4: Connecting With Ethernet Cable & Hub
6
Revised 4/25/11
PT-Link II Interface
Computer IP Address Set-up for
Windows XP, Vista, and 7
In order for the PT -Link II to communicate properly , it is imperative to set
the IP address of both the PT -Link II as well as the computer to be within
the same netmask. You need to change the IP address on your computer .
The following instructions will explain how to confi gure the IP address
for Microsoft® Windows XP, Vista, and 7 operating systems.
Computer IP Address Set-up for Windows
NT & XP
1.) Click <start>; then click<Control Panel>.
2.) Double-click on the Network Connections icon.
The Network Connections Window will appear (Figure 5).
PT-Link II BACnet® Technical Guide
IP Address Confi guration
Figure 6: Local Area Connection Status Window
Figure 5: Network Connections Window
NOTE: If any wireless connections are listed, disable them
by right-clicking the connection and selecting
<Disable>.
3.) In the Network Connections Window, double-click the Local Area Connections entry. The Local Area Connection Status Window will appear (Figure 6).
4.) As shown in Figure 6, click <Properties> in the lower
left of the window. The Local Area Connection Properties Window will appear.
Figure 7: Local Area Connection Properties Window
PT-Link II Interface
5). As shown in Figure 7, in the Connection Items list box,
be sure the Internet Protocol (TCP/IP) is checked. Select the
Internet Protocol (TCP/IP) item to highlight it and then click
<Properties>. The Internet Protocol Properties Window will
appear.
7
PT-Link II BACnet® Technical Guide
IP Address Confi guration
Figure 8: Internet Protocol Properties Window
6).Select the radio button in front of Use the following
IP address (Figure 8) and write down the current defaults
so that you can re-enter them when you fi nish confi guring the PT-Link and then typein the following
information:
a.) IP address 192.168.1.5
b.) Subnet mask 255.255.255.0
c.) Default Gateway is blank
7.) Click<OK> until all of the above network confi guration
windows are closed. You may have to reboot the computer
before the new values are valid.
Computer IP Address Set-up for
Windows Vista & 7
1.) Click<start>; then click<Control Panel>.
2.) Click on the Network and Internet icon.
3.) ClickNetwork and Sharing Center.
4.) From the shaded box in the left side of the window, select
Manage Network Connections (Vista) or Change adapter
settings (Windows 7).
5.) Right-click on the Local Area Connection icon and select
<Properties> for the drop down window.
6.) ChooseInternet Protocol Version 4 (TCP/IPv4) by
highlighting it and then click <Properties>. The Internet Protocol Properties Window will appear (Figure 8).
7.) Select the radio button in front of Use the following IP address (Figure 8) and write down the current defaults so that you can re-enter them when you fi nish confi guring the PT-Link and then type in the following
information:
a.) IP address 192.168.1.5
b.) Subnet mask 255.255.255.0
c.) Default Gateway is blank
9.) Click<OK> until all of the above network confi guration
windows are closed. You may have to reboot the computer
before the new values are valid.
8
PT-Link II Interface
PT-Link II BACnet® Technical Guide
Confi guring the PT-Link DIP Switches
PT-Link DIP Switch Confi guration
If the BACnet address doesn’t need to be any higher than 255, then
follow these directions to use the DIP Switch settings to confi gure your
PT-Link II. The DIP Switches are shown in Figure 9.
The confi g.csv fi le’s ‘Server_DIP’ parameter will default to ‘Enabled’
which will allow the System_Node_ID (BACnet MAC Address) and
Node_ID (Device Instance) to be set using the DIP Switches on the
module. See Figure 17 on page 12. With this capability, RUINET is
not needed for the initial confi guration. Set the DIP Switches, power up
the PT-Link II, wait 4 minutes, and your PT-Link II BACnet is ready.
FFP-485
DIP
Switch
Bank A
The DIP Switches allow you to set the Baud Rate, Node-ID (Device
Instance), and MAC address on the Field RS-485 protocol as well as to
automatically download confi guration fi les for certain protocols.
The DIP Switches are designated by Bank A & B. Bank A is used to
select both the MAC Address and Device Instance – if using the DIP
switches these will always be the same. The maximum legal value is
255. See Appendix C for each possible combination for the addresses.
Bank B is used to set the Server Baud rate. For setting serial fi eld pro-
tocol baud rate, the DIP Switches B1 – B4 can be set for the following
speeds. See Table 2 for Server Baud rate settings.
NOTE: Y ou must cycle power after making changes to the DIP
NOTE: The preferred method of confi guration is to use the DIP
Switches on the Protocessor board unless your address
setting needs to be greater than 255.
1.) In order to communicate and program the PT-Link II you will
need to install RUINET software on your computer. If you do not
have the software, it is available for downloading at www.orioncontrols.com/software-new.html under PT-Link II Software
WARNING: Make sure to load RUINET onto your hard drive
and run the program from your hard drive. DO NOT under any
circumstances run RUINET from your cd drive.
2.) If RUINET is in the desktop directory (if it isn’t, locate its directory), double-click on RUINET, and the RUINET program should
run. Initially, you might see the screen below (Figure 10).
Figure 10: Update FieldServer Date and Time
3.) Type <Y> to sync the Date/Time on your PC. The following
screen will appear (Figure 11). Press any key to continue.
4.) The following screen may appear (Figure 12). Type <I> for
Specify IP Address and the message “Enter IP Address of the Field
Server to Connect to” will appear on the screen.
Figure 12: RUINET PT-Link Specify IP Address
5.) Type the IP Address of <192.168.1.24> and press <Enter>.
6.) If you have only one PT-Link connected to the network, then RUINET will automatically connect to that particular PT-Link; otherwise,
a menu will appear to allow the selection of the desired PT-Link.
NOTE: If RUINET is unable to establish a connection, there
are a few simple procedures you can perform to try to
determine the problem. T o verify your network cables,
observe the green LED displayed directly above and
to the right of the Ethernet port. This LED should be
on if the 10 BaseT cable is good. Secondly, observe
the red LED displayed directly above and to the left
of the Ethernet port. This LED should be solid while
RUINET is running. If the LEDs are lit as expected,
and RUINET still does not receive replies, then the
netmask is probably incorrect. If this does not help,
then your Ethernet setup on your PC is possibly not
compatible. Ensure that you have an Ethernet adapter
installed in your software confi guration and that it is
confi gured to run the TCP/IP protocol. If you are still
unable to connect, please contact W attMaster Controls.
Figure 11: FieldServer Date and Time Updated
10
Revised 4/25/11
PT-Link II Interface
PT-Link II BACnet® Technical Guide
Changing the Confi g.csv File
7.) On subsequent connections, a list of PT-Links that have been recently connected may appear under the message “Recently connected
to FieldServers. Select the required PT-Link by typing the Number or
Letter in the left hand column. (Figure 13).
Figure 13: RUINET PT-Link Selection Menu
8.) Once connected, you will see the RUINET Main Menu (Figure 14).
Unless you need to make changes to the confi g.csv fi le (steps 7 through
15), you are now ready to send and receive fi les to and from the PT -Link.
9.) Type the letter <U> to upload the Confi g fi le (Figure 15), then type
<U> again (Figure 16) for Upload.
Figure 15: RUINET PT-Link Main Menu - Upload
Figure 14: RUINET PT-Link II Main Menu
PT-Link II Interface
Figure 16: RUINET PT-Link Upload
10.) You will get confi rmation that the upload is complete. Type<N>
to open the fi le in Notepad.
WARNING: Only edit the confi g.csv fi le using Notepad. DO
NOT use Excel. Using Excel to edit the confi g.csv fi le will cor-
rupt its contents!
11
PT-Link II BACnet® Technical Guide
Changing the Confi g.csv File
11.) Inside the text fi le under ‘Connections’, you must change the
‘Server_DIP’ parameter from ‘Enabled’ to ‘Disabled’ and then you
can use RUINET to confi gure the addresses and baud rate. (See Figure 17).
Figure 17: Changing the ‘Server_DIP’ parameter
12.) Inside the text fi le you can change the System_Node_ID (the
BACnet MAC address) which defaults to 11 (Figure 18). You can
obtain this information from your Building Automation System
(BAS) Integrator.
13.) If the server baud rate needs to be changed, go to the
‘Connections’ section and only change the SERVER_BAUD
(Figure 19). Possible Baud Rate values are (9600, 19200, 38400,
76800). The default Baud Rate is 38400. You can obtain this
information from your BAS Integrator.
Figure 19: Changing the Baud Rate in Notepad
14.) The last change you may need to make is the Node_ID under
‘Client Side Nodes’ which is the BACnet Device Instance Number
(Figure 20). The default is 1.You can obtain this information from
your BAS Integrator.
Figure 18: Changing the BACnet MAC address
12
Revised 4/25/11
Figure 20: Changing the Node ID in Notepad
PT-Link II Interface
PT-Link II BACnet® Technical Guide
Verifying PT-Link Communications
15.) Once the changes are made to the text fi le, click
upper left and then click<Save>. Now close the fi le and return to
the RUINET Main Menu.
16.) From the RUINET Main Menu, type<D> to Download the new
confi g.csv fi le to the FieldServer (Figure 21).
<File> in the
Figure 21: Download new Confi g.csv fi le
NOTE: The utility will indicate when downloading is
complete. DO NOT reset the PT-Link until this mes-
sage is displayed, as this will corrupt the PT-Link.
NOTE: The Remote Filename option must always be named
“confi g.csv” for confi gurations; otherwise, it will be
ignored by the PT-Link.
18.) Once the download is complete, restart the PT-Link II by
cycling power or press<Esc> to get back to the RUINET Main Menu
and then type<!> option to save the new confi guration fi le and restart
RUINET. It is possible to do multiple downloads to the PT-Link II
before resetting it. There will be a start-up period where you will be
unable to connect to the PT Link.
19.) From the RUINET Main Menu, type<A> for the Data Array
Overview. The Data Array Overview Screen will display (Figure 23).
17.) At the next screen, (Figure 22), type<D> again.
Figure 22: Download new Confi g.csv fi le
Figure 23: Data Array Overview Screen
20.) This screen (Figure 23) will verify communication to the HVAC
units. Lines 1 & 2 should always be present. After a start-up period
of approximately 4 minutes, you will see 1 additional line for each
HVAC unit. This screen represents the PT Link II communicating
with 1 HVAC unit.
21.) Once these steps have been completed and you have verifi ed
that the reconfi gured PT Link II has established communication to the
HVAC unit(s), it can now be added to the BAS network.
PT-Link II Interface
13
PT-Link II BACnet® Technical Guide
Troubleshooting the PT-Link Controller
Addressing WattMaster Devices in a
BACnet
Each PT-Link II BACnet® generates only one BACnet® device regardless of the number of WattMaster controls connected to it. This device
will have all the properties of all the WattMaster controls connected.
The instance of the device is equal to the unit address. The properties
of each control can be differentiated by an offset of 500.
Examples:
1.) Properties of the controller address as 1 will range
from 0 to 499.
2.) Properties of the controller address as 2 will range
from 500 to 999.
3.) Properties of the controller address as 3 will range
from 1000 to 1499.
To search for the instance of a specific property, follow the next
formula:
Property Instance = ((Controller Address – 1) * 500) + Instance
Number from table.
®
Network.
Example:
1.) The PT-Link II BACnet® has a Node ID equal to fi ve.
2.) Two VCM controllers connected and addressed to one and
four.
3.) Searching for the Outdoor Temperature of each controller.
4.) Instance of the Outdoor Temperature in the VCM table
equal to AI: 54.
5.) Client will only see Device 5.
6.) Under Device 5 it will see AI: 54 for the Outdoor
Temperature of the unit addressed as 1 and AI: 1554 for the
Outdoor Temperature of the unit addressed as 4.
NOTE: To simplify the calculation, we recommend that the
WattMaster controllers be addressed in sequential order from one to the last controller without any unused
address(es) in between.
14
PT-Link II Interface
Troubleshooting the PT-Link II Controller
PT-Link II Board LEDs
The PT-Link II BACnet® is equipped with LEDs that can be used for
troubleshooting. There are eight LEDs on the PT -Link board. See Figure 24 for the locations of the LEDs on the PT -Link board. The LED descriptions and functions are listed in the following paragraphs.
POWER LED
When the PT-Link II BACnet® is powered up, the “POWER” LED
should light up and stay on continuously. If it does not light up, check
to be sure that you have 24 VAC connected to the board, that the wiring
connections are tight, and that they are wired for correct polarity. The 24
V AC power must be connected so that all ground wires remain common.
If after making all these checks the “POWER” LED still does not light
up, please contact WattMaster Controls Technical Support at our Toll
Free number—866-918-1100—for assistance.
LOOP LED
When power is applied to the PT-Link II BACnet®, the “LOOP” LED
will also light up. The LED should fl icker rapidly, indicating that the
PT-Link is trying to communicate with the controllers on the loop. A
“fl icker” is defi ned as a brief moment when the LED turns off and
back on. If the “LOOP” LED does not operate as indicated above, fi rst
power down the unit and then reapply power. If this does not work,
please contact WattMaster Controls Technical Support at our Toll Free
number—866-918-1100—for assistance.
PT-Link II BACnet® Technical Guide
LED 1
When power is fi rst applied, “LED 1” will be off temporarily and then
will blink one time for each controller it is communicating with. For
example, if you have 4 controllers on the loop connected to the PT -Link,
“LED 1” will blink 4 times. If the amount of blinks does not match the
number of controllers connected to the loop, it indicates there is a communications problem. The best way to fi nd out which board is not com-
municating is to go to each controller and look at its “COMM” LED. The
“COMM” LED should be solid and will fl icker occasionally indicating
communication with the PT-Link II BACnet®. If the “COMM” LED
does not fl icker, there is no communication with that controller.
LED 2
When power is fi rst applied, “LED 2” will be off temporarily and then
will blink slowly indicating that the PT -Link baseboard is communicating
with the ProtoCessor Module. If “LED 2” does not blink, check that the
ProtoCessor Module is installed correctly on the PT -Link baseboard and
that the “PWR” LED is lit up on the ProtoCessor Module.
PROTO LED
When the PT-Link II is fi rst powered up, the “PROTO” LED should
blink rapidly and may appear to be on solid. This LED verifi es com-
munication with the board and the ProtoCessor. If the LED doesn’t
light up, check that the ProtoCessor is installed correctly and fi rmly
connected to the Base Board. The “PWR” LED should also be lit on
the ProtoCessor Module.
Figure 24: PT-Link II BACNET® LED Locations
WATCH DOG LED
The “W-DOG” LED is used for troubleshooting by W attMaster Controls
Technical Support. The “W-DOG” LED should always be on solid.
HEARTBEAT LED
The “H-BEAT” LED blinks to show the PT-Link II board software is
running. If the LED doesn’t light up, and all other checks have been
made, please contact W attMaster Controls T echnical Support at our T oll
Free number—866-918-1100—for assistance.
TIMER LED
The “TIMER” LED is used for troubleshooting by W attMaster Controls
Technical Support. The “TIMER” LED should always be blinking
steadily.
PT-Link II Interface
Revised 8/13/12
15
PT-Link II BACnet® Technical Guide
Troubleshooting the PT-Link II Controller - OE368-23B-BACnet
ProtoCessor Module LEDs
Refer to Figure 25 for LED locations. NOTE: If your BACnet module
does not have DIP switches, refer to Figure 27 on page 17.
PWR LED
When the PT -Link II is fi rst powered up, the “PWR” green LED should
light up and stay on continuously. If the LED doesn’t light up, check
that the ProtoCessor is installed correctly and fi rmly connected to the
Base Board.
UNUSED LEDs
15 seconds after powering up, the 4 unused LEDs will turn on solid for
5 seconds, then turn off.
RX & TX LEDs
During normal operation, the “RX” LED will fl ash when a message is
received on the fi eld port of the ProtoCessor and the “TX” LED will fl ash when a message is sent on the fi eld port of the ProtoCessor The
“TX” and “RX” LEDs work together to indicate that communication
is being established with the desired protocol network. If both LEDs
are blinking, then communication is working properly. If not, check
the protocol network wiring and the baud rate in the confi guration fi le.
RUN LED
The “RUN” LED will fl ash 20 seconds after power up, signifying normal
operation. The Protocessor will be able to access RUINET once this
LED starts fl ashing. During the fi rst 20 seconds, the LED should be off.
CONFIG ERR LED
The “CONFIG ERR” LED will go on solid 15 seconds after power
up. It will turn off after 5 seconds. A steady amber light will indicate a
confi guration error exists in the active confi guration. See the Error Screen
in the Remote User Interface for a description of the confi guration error.
NODE OFFLINE LED
The “NODE OFFLINE” LED will go on solid 15 seconds after power
up. It will turn off after 5 seconds. If the Node Offl ine LED stays on
solid, a node offl ine condition has occurred.
NOTE: If all of these tests are made and the controller still doesn’t
operate, please contact W attMaster Controls T echnical
Support at our T oll Free number—866-918-1100—for
assistance.
+
–
G
SYS ERR LED
The “SYS ERR” LED will go on solid 15 seconds after power up. It
will turn off after 5 seconds. A steady red light will indicate there is a
system error on the ProtoCessor. If this occurs, immediately report the
related “system error” shown in the error screen of the Remote User
Interface to FieldServer Technologies for evaluation.
COMM ERR
The “COMM ERR” LED will go on solid 15 seconds after power
up. It will turn off after 5 seconds. A steady red light will indicate a
communications problem if there is a confi gured node connected to the
ProtoCessor that is offl ine. To establish the cause of the error, go to the
error screen of the Remote User Interface interface.
RX & TX LEDs
PROTOCESSOR
BACNET
RUN LED
SYS ERR LED
COMM ERR LED
CONFIG ERR LED
NODE OFFLINE LED
PWR LED
Figure 25: PT-Link II BACNET® LED Locations
UNUSED
Figure 26: PT-Link II BACNET® Protocessor Components
16
Revised 11/2/11
PT-Link II Interface
Troubleshooting the PT-Link II Controller - OE368-23-BACnet
ProtoCessor Module LEDs
Refer to Figure 27 for LED locations. NOTE: If your BACnet module
has DIP switches, refer to Figure 25 on page 16.
PWR LED
When the PT -Link II is fi rst powered up, the “PWR” LED should light
up and stay on continuously. If the LED doesn’ t light up, check that the
ProtoCessor is installed correctly and fi rmly connected to the Base Board.
GPI05 LED
The “GPI05” LED will light up when the Base Board and the
ProtoCessor Module have established communications. This can
take up to 3 minutes depending on the number of units connected to the
PT -Link II. If it fails to light up after 3 minutes, check that the ProtoCessor is installed correctly and fi rmly to the Base Board.
LB LED
Once the unit is powered up, the “LB” LED must be blinking constantly.
If this LED is constantly on or off, the Module is not working properly
and needs to be replaced.
PT-Link II BACnet® Technical Guide
LA LED
Once the unit is powered up, the “LA” LED must be blinking constantly.
If this LED is constantly on or off, the Module is not working properly
and needs to be replaced.
TX & RX LEDs
The “TX” and “RX” LEDs work together to indicate that communication
is being established with the desired protocol network. If both LEDs
are blinking, then communication is working properly. If not, check
the protocol network wiring and the baud rate in the confi guration fi le.
D14 & D15 LEDs
The “D14” and “D15” LEDs work together to indicate that communication is being transmitted and received from the USB Port when
performing an update to the PT-Link software.
NOTE: If all of these tests are made and the controller
still doesn’t operate, please contact WattMaster
Controls Technical Support at our Toll Free number—866-918-1100—for assistance.
Figure 27: PT-Link II BACNET® LED Locations
PT-Link II Interface
17
PT-Link II BACnet® Technical Guide
Troubleshooting the PT-Link II Controller
Using RUINET
Before continuing with the troubleshooting, make sure the PT-Link is
connected correctly and the RUINET software is installed, running, and
functioning correctly.
Verifying Proper Communications
From the RUINET Main Screen, press <O> to go the Connection
Overview Screen. This screen supplies information on communication
between the PT-Link and remote devices. A number of aspect screens
are available, and some of the aspect screens have more than one page.
Use the space bar to toggle between aspects and use the <PgUp> and
<PgDn> keys to toggle between pages of the same aspect. The Con-
nection Overview and Settings Aspect Screen is shown in Figure 28.
The main purpose in this screen is to verify that messages and characters
are being transmitted and received. In addition, it shows the number of
communication errors. If the PT-Link connection “03” is the protocol
connection, verify that is communicating appropriately. If it is not, check
that the PT -Link LEDs are working properly , the unit is wired correctly ,
and the PT-Link is confi gured correctly (Baud Rate, Unit Address &
MAC Address). If the number of errors is constantly increasing, move
to the Error Screen by pressing the <Space Bar> 3 times to fi nd out
the cause of the errors. Use the <PgUp> and <PgDn> keys to toggle
between pages of the Error Screen.
Figure 28: Connection Overview Screen
Verifying Proper Values
To verify that the correct values for each unit are being communicated
to the PT-Link, move to the Data Array Overview Screen. To get to the
screen, press <A> from the RUINET Main Menu. See Figure 29 for
screen details.
In the Data Array Overview Screen (Figure 29) you will be able to see
the data arrays of all the units connected to the PT-Link denoted by an
array name “DA_XXX_IY”—Y being the address of the unit minus
one. The Address of the unit is determined by a set of DIP switches.
To view the values being communicated from a specifi c unit, move to
the Data Array Detail Screen (Figure 30) of the unit by entering the
number under which it is listed. For example, for the unit listed in the
third position, enter<03>.
To understand what each value means, look at the Data Array Tables
for the desired unit type, VCM-X, SA, or VCM. You can change the
writable values from this screen by using the modify command. T o use
the modify command, press <M> from the Data Array Detail Screen
and then enter the Offset you want to change followed by a space and
the new value.
Example: T o change the Cooling Supply Setpoint to 60 in the VCM, press
<M>, enter<58 60>, and then press <Enter>. This could be useful to
prove that the unit can take and keep the setpoints properly.
Figure 29: Data Array Overview Screen
18
Figure 30: Data Array Detail Screen
PT-Link II Interface
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.