Orion PREHEAT-X User Manual

Factory Packaged Controls
PREHEAT-X Controller
Technical Guide
PART NUMBER CROSS REFERENCE TABLE
PART DESCRIPTION
PREHEAT-X Controller OE377-26-00061 V48510 V48510 VCC-X Controller OE338-23B-VCCX V43420 N/A VCB-X Controller OE332-26B-VCBX V28940 J00142 VCM-X E-BUS Controller OE332-23E-VCMX V07150 31422 Leaving Air Temperature Sensor OE231 P87140 28503 Entering Air Temperature Sensor OE250 P87150 N/A EBC E-BUS Cables - varying lengths EBC-XXXF V167XX N/A HSSC Cables - varying lengths HSSC-XXXF Varies N/A
WattMaster Controls Inc. 8500 NW River Park Drive · Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 · FAX: (816) 505-1101 · E-mail: mail@wattmaster.com Visit our web site at www.orioncontrols.com WattMaster Form: AA-PREHEATX-TGD-01C
ORION
www.aaon.com
AAON® Manual Part No.: V48520 Copyright April 2015 WattMaster Controls, Inc.
®
AAON
is a registered trademark of AAON, Inc., Tulsa, OK. Neither WattMaster Controls, Inc. nor AAON® assumes any responsibility for errors or omissions in this document. This document is subject to change without notice.
AAON
TULSA
AAON
TABLE OF CONTENTS
GENERAL INFORMATION ................................................................................................................4
Overview ..................................................................................................................................................................4
Features ...................................................................................................................................................................4
INSTALLATION & WIRING ............................................................................................................... 5
Important Wiring Considerations ..............................................................................................................................5
Input Wiring ..............................................................................................................................................................6
Output Wiring ...........................................................................................................................................................7
INPUTS/OUTPUTS ........................................................................................................................... 8
OPERATION MODES ........................................................................................................................ 9
Stand-Alone Mode ...................................................................................................................................................9
Communicating Mode ..............................................................................................................................................9
LCD DISPLAY SCREENS ................................................................................................................12
TROUBLESHOOTING ..................................................................................................................... 21
LED Diagnostics ....................................................................................................................................................21
Troubleshooting Conditions & Alarms ..........................................................................................................................21
Temperature Sensors ...................................................................................................................................................22
APPENDIX A - Temperature Sensors ............................................................................................ 23
Leaving Air Temperature Sensor Installation .........................................................................................................23
Leaving Air Temperature Sensor Wiring Chart .......................................................................................................24
APPENDIX B - PREHEAT-X BACnet ............................................................................................... 25
PREHEAT-X BACnet MS/TP Connection ..............................................................................................................25
PREHEAT-X BACnet Points...................................................................................................................................26
PREHEAT-X Technical Guide
3
OVERVIEW
General Information
Overview
The OE377-26-00061 PREHEAT-X Controller (AAON Part No. V48510) is designed to control fi xed stages of Preheat and optional modulating Preheat to maintain a desired Preheat Leaving Air T em­perature Setpoint. See Figure 1 for dimensions.
The controller can be used as a stand-alone controller or communi­cating with an AAON Unit Controller. The PREHEAT-X controller connects to an AAON unit controller via a modular cable. See Figur e 2, page 5 for wiring details.
5.73
5.24
2.62
Features
The PREHEAT-X Controller:
Can be operated as a stand-alone controller or communicating with the VCC-X, VCB-X, and VCM-X E-BUS Controllers
Monitors the Preheater Leaving Air Temperature and Leaving Air Reset Signal and controls to maintain Setpoint
Contains a 2 x 8 LCD character display and 4 buttons that allow for status display and setpoint changes
NOTE: The PREHEAT-X Controller contains no user-
serviceable parts. Contact qualifi ed technical personnel if your operating correctly.
PREHEAT-X Controller is not
5.04
0.21
ALARM
ALARM
M
M
MENU
www.aaon.com
www.aaon.com
www.orioncontrols.com
www.orioncontrols.com
OE377-26-00061 PREHEAT-X AAON No.: V48510
OE377-26-00061 PREHEAT-X AAON No.: V48510
ANALOG INPUTS
ANALOG INPUTS
LAT1
LAT1
LAT2
LAT2
EAT
OAT
0-10V RESET
0-10V RESET
GND
GND
GND
GND
BINARY INPUTS
BINARY INPUTS
ENABLE
ENABLE
EMERG. SHUTDOWN
EMERG. SHUTDOWN
FUTURE USE
FUTURE USE
RS-485 COMM
RS-485 COMM
T(-)
T(-)
MSTP
SHLD
SHLD
BACnet
R(+)
R(+)
WattMaster Label
E-BUS
#LB102XXX-A
Rev.: 1A
CONNECT
E-BUS
WattMaster Label
CONNECT
#S 000062W
Rev.: 1D
MENU
ALARM CONTACT
ALARM CONTACT
HEAT
OUTPUTS
HEAT
OUTPUTS
CONTACTRATING IS
1 AMP MAX
CONTACTRATING IS
@ 24 VAC
1 AMP MAX
@ 24 VAC
ANALOG
ANALOG
OUTPUTS
OUTPUTS
E-BUS
E-BUS
CONNECT
CONNECT
DOWN
DOWN
RLYCOMM
RLYCOMM
0-10V MOD. SCR
0-10V MOD. SCR
GND
GND
2.04
0.57
4.09
UP
UP
HEAT1
HEAT1
HEAT2
HEAT2
HEAT3
HEAT3
HEAT4
HEAT4
HEAT5
HEAT5
HEAT6
HEAT6
ENTER
ENTER
5.63
GND
GND
PWM +
PWM +
PWM -
PWM -
+24 VAC
+24 VAC
Note: iDepth s 1.49 inches.
Figure 1: OE377-26-00061 PREHEAT-X Controller Dimensions (In Inches)
4
PREHEAT-X Technical Guide
WIRING
Important Wiring Considerations
Important Wiring Considerations
Please read carefully and apply the following information when wiring the
requires the following electrical connections:
1.
2.
3. Leaving Air Temperature Sensors, Entering Air
4. All 24 VAC wiring must be connected so that all ground
PREHEAT-X Controller. The PREHEAT-X Controller
18 gauge minimum wire unless otherwise noted.
24 VAC power connection with an appropriate VA rating.
Temperature Sensor, and Heat Enable must have 24 gauge minimum wire.
wires remain common. Failure to follow this procedure can result in damage to the module and connected devices.
5. All wiring is to be in accordance with local and national electrical codes and specifi cations.
6. Check all wiring leads at the terminal block for tightness. Be sure that wire strands do not stick out and touch adjacent terminals. Confi rm that all transducers required for your system are mounted in the appropriate location and wired into the correct terminals.
WARNING: Observe polarity! All boards must be wired
GND-to-GND and 24 VAC-to-VAC. Failure to observe polarity could result in damage to the board.
PREHEAT-X Technical Guide
5
WIRING
Inputs Wiring
Inputs Wiring
The PREHEA T-X Controller works as Stand-Alone or communicat­ing with the VCM-X E-BUS, VCB-X, or VCC-X Controller. For connection to a VCM-X E-BUS, VCB-X, or VCC-X Controller, use an E-BUS Cable connecting to the appropriate E-BUS ports on those controllers. The Reset Input and Heat Enable are only used in Stand-Alone Mode. See Figure 2 below for Inputs Wiring.
Mount Inside PREHEAT-X
Leaving Air 2
Temperature Sensor
Mount Inside PREHEAT-X
Box Wall
Entering Air
Temperature Sensor
Make Splice Connections
Inside Sensor
Enclosure
As Shown. Seal All
Conduit Fittings
With Silicone
Mount Sensor Outdoors
In Shaded Protected
Area & In Upright
Position As Shown
Reset In
Signal (24 VAC)
NOTE: Reset In And Heat
Enable Inputs Are Used In
Stand-Alone Mode Only
Leaving Air 1
Temperature Sensor
Box Wall
0-10 VDC
GND
+
-
Heat Enable
W1
Emergency
Shutdown
AIN1 AIN2 AIN3
RST GND GND
BIN1
BIN2
PREHEAT-X CONTROLLER
(OE377-26-00061)
ALARM
ALARM
UP
UP
M
M
MENU
www.aaon.com
www.aaon.com
www.orioncontrols.com
www.orioncontrols.com
OE377-26-00061 PREHEAT-X AAON No.: V48510
OE377-26-00061 PREHEAT-X AAON No.: V48510
ANALOG INPUTS
ANALOG INPUTS
LAT1
LAT1
LAT2
LAT2
EAT
OAT
0-10V RESET
0-10V RESET
GND
GND
GND
GND
BINARY INPUTS
BINARY INPUTS
ENABLE
ENABLE
EMERG. SHUTDOWN
EMERG. SHUTDOWN
FUTURE USE
FUTURE USE
RS-485 COMM
RS-485 COMM
T(-)
T(-)
MSTP
SHLD
BACnet
SHLD
R(+)
R(+)
WattMaster Label
WattMaster Label
E-BUS
#LB102XXX-A
CONNECT
Rev.: 1A
E-BUS
#S 000062W
CONNECT
Rev.: 1D
MENU
ALARM CONTACT
ALARM CONTACT
HEAT
OUTPUTS
HEAT
OUTPUTS
CONTACTRATING IS
1 AMP MAX
CONTACTRATING IS
@ 24 VAC
1 AMP MAX
@ 24 VAC
ANALOG
ANALOG
OUTPUTS
OUTPUTS
E-BUS
E-BUS
CONNECT
CONNECT
DOWN
DOWN
HEAT1
HEAT1
HEAT2
HEAT2
HEAT3
HEAT3
HEAT4
HEAT4
HEAT5
HEAT5
HEAT6
HEAT6
RLYCOMM
RLYCOMM
0-10V MOD. SCR
0-10V MOD. SCR
PWM +
GND
GND
+24 VAC
+24 VAC
GND
PWM +
PWM -
PWM -
GND
ENTER
ENTER
GND
24VAC
40 VA
Transformer
Minimum
N.C.
SAFETIES
(BY OTHERS)
COM
Figure 2: PREHEAT-X Inputs Wiring Diagram
6
Line
PREHEAT-X Technical Guide
WIRING
Outputs Wiring
The PREHEA T-X Controller works as Stand-Alone or communicat­ing with the VCM-X E-BUS, VCB-X, or VCC-X Controller. For connection to a VCM-X E-BUS, VCB-X, or VCC-X Controller , use an E-BUS Cable connecting to the appropriate E-BUS ports on those controllers. See Figure 3 below for Outputs Wiring.
Outputs Wiring
PREHEAT-X CONTROLLER
(OE377-26-00061)
ALARM
ALARM
UP
UP
M
M
MENU
www.aaon.com
www.aaon.com
www.orioncontrols.com
www.orioncontrols.com
OE377-26-00061 PREHEAT-X AAON No.: V48510
OE377-26-00061 PREHEAT-X AAON No.: V48510
ANALOG INPUTS
ANALOG INPUTS
LAT1
LAT1
LAT2
LAT2
EAT
OAT
0-10V RESET
0-10V RESET
GND
GND
GND
GND
BINARY INPUTS
BINARY INPUTS
ENABLE
ENABLE
EMERG. SHUTDOWN
EMERG. SHUTDOWN
FUTURE USE
FUTURE USE
RS-485 COMM
RS-485 COMM
T(-)
T(-)
MSTP
SHLD
SHLD
BACnet
R(+)
R(+)
WattMaster Label
WattMaster Label
E-BUS
#LB102XXX-A
CONNECT
Rev.: 1A
E-BUS
#S 000062W
CONNECT
Rev.: 1D
MENU
ALARM CONTACT
ALARM CONTACT
HEAT
OUTPUTS
HEAT
OUTPUTS
CONTACTRATING IS
1 AMP MAX
CONTACTRATING IS
@ 24 VAC
1 AMP MAX
@ 24 VAC
ANALOG
ANALOG
OUTPUTS
OUTPUTS
E-BUS
E-BUS
CONNECT
CONNECT
DOWN
DOWN
HEAT1
HEAT1
HEAT2
HEAT2
HEAT3
HEAT3
HEAT4
HEAT4
HEAT5
HEAT5
HEAT6
HEAT6
RLYCOMM
RLYCOMM
0-10V MOD. SCR
0-10V MOD. SCR
PWM +
PWM +
GND
GND
+24 VAC
+24 VAC
GND
PWM -
PWM -
ENTER
ENTER
GND
Note:
All Relay Outputs Are Normally Open And Rated For 24 VAC Power Only. 1 Amp Maximum Load.
Alarm
Relay Contact
Heat 1 Relay Heat 2 Relay
Heat 3 Relay
Heat 4 Relay Heat 5 Relay
Heat 6 Relay
Modulating SCR
(0-10 VDC)
+ –
PWM SSR
+ –
EBC E-BUS Cable
Connects To
VCC-X Or VCB-X Controller’s
Expansion Port
Figure 3: PREHEAT-X Outputs Wiring Diagram
PREHEAT-X Technical Guide
GND
24VAC
40 VA
Transformer
Minimum
Line
HSSC E-BUS Cable
Connects To
VCM-X Controller’s
Expansion Port
7
INPUTS & OUTPUTS
Inputs and Outputs
I/O Map
See Table 1 below to reference the inputs and outputs that are avail- able on the PREHEAT-X Controller.
Analog Inputs
1 Leaving Air Temperature 1 (LAT1) 2 Leaving Air Temperature 2 (LAT2) 3 Entering Air Temperature Sensor 4 Reset In (0-10 VDC)
Binary Inputs
1 Heat Enable 2 Emergency Shutdown 3 Future Use
Analog Outputs
1 0-10 VDC Mod SCR 2 PWM SSR
Relays
1 Alarm 2 Heat 1 3 Heat 2 4 Heat 3 5 Heat 4 6 Heat 5 7 Heat 6
NOTE: For AIN1 through AIN3, all T emperature Sensors must
be Thermistor Type III which provide 77.0°F @ 10K Ohms Resistance.
Reset Input (0-10 VDC)
Used only in stand-alone operation. The Leaving Air Temperature Setpoint can be reset by supplying a 0-10 VDC signal to the RST IN low voltage terminal block. This reset signal is optional and need only be used if you require resetting of the discharge air temperature.
Binary Inputs
Heat Enable Contact (HEAT EN)
This input is only required when the controller is used in stand-alone operation; it is not required when communicating with an AAON Unit Controller. The Heat Enable input is activated by a 24VAC signal supplied from a building automation system to enable the PREHEAT-X Controller. The controller will not operate without 24VAC being applied to this input terminal when used in a stand­alone confi guration. When the Heat Enable signal is lost or turned off, all stages de-activate immediately.
Emergency Shutdown Input
This wet contact (24 VAC) input is used to initiate shutdown of the HV AC unit when a N.C. Smoke Detector (by others), Firestat (by oth­ers), or other shutdown condition (by others) occurs and the contact is opened. The controller remains active and can initiate alarm relays.
Analog Outputs
Table 1: PREHEAT-X Controller Inputs & Outputs
Analog Inputs
Leaving Air Temperature 1 (LAT1)
When enabled, the PREHEAT-X Controller will control to a Leav­ing Air Temperature Setpoint. The Controller can be confi gured to use only LAT 1 for this purpose. Typically, the average of LAT1 and LAT2 is used.
Leaving Air Temperature 2 (LAT2)
When enabled, the PREHEAT-X Controller will control to a Leav­ing Air Temperature Setpoint. The Controller can be confi gured to use only LAT 2 for this purpose. Typically, the average of LAT1 and LAT2 is used.
Entering Air Temperature
When the Entering Air Temperature falls below the Entering Air Temperature Setpoint, preheat will be enabled.
8
0-10 VDC Modulating SCR
Depending on the type of Heat used, this output will supply a 0-10 VDC output signal for control of the modulating SCR Heat.
Pulse Width Modulating SSR
Depending on the type of Heat used, this output will supply a 12 V PWM Output Signal for control of the modulating SSR Heat.
Relay Outputs
Relay #1 - Alarm
This relay sends a signal when an alarm is enabled.
Relays #2 - 6—Fixed Stage Heat Outputs
PREHEAT-X Technical Guide
OPERATION MODES
Outputs and Operation Modes
Operation Modes
The PREHEA T -X Controller can be used stand-alone or communicat­ing with an AAON Unit Controller using a modular cable.
Stand-Alone Mode
When used in a stand-alone application, the PREHEA T -X Controller will modulate SCR or SSR Heat and stage any additional fi xed stages to maintain the Leaving Air T emperature setpoint con fi gured on the PREHEA T-X Controller LCD display . The PREHEA T-X Controller is activated by a 24VAC signal to the HEAT EN input.
Communicating Mode
When the PREHEA T-X Controller is connected and communicating with an AAON Unit Controller via a modular cable, the necessary information will be passed between the PREHEAT-X and the Main Unit Controller to properly operate in the Heating Mode.
If the communication is interrupted between the PREHEAT-X Controller and the Main Controller, both boards will show an alarm and the PREHEA T-X outputs will turn off. When communication is restored, the alarms will go away.
In this confi guration, the Leaving Air T emperature Setpoints and the Preheat Enable Sepoints are set using the Main Controller.
PREHEAT-X Technical Guide
9
Loading...
+ 19 hidden pages