Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
1 - 1
1 Introduction
1-1Introduction
Thank you for choosing the KPG or KPL (hereafter described KP inverter) Grid Connect Photovoltaic
Inverter. This communication manual describes essential information regarding communication of the KP
inverter.
The KP inverter is designed for use in Grid Connect Solar Systems. The installation must always be carried out
by qualified personnel with knowledge of electrical systems and according to national standards for electrical
installations.
• This communication manual is intended for Users and Installers of the KP inverter.
• Read this manual carefully and make sure that you understand it well to ensure that you are using the
communication of KP inverter.
• Keep this manual in a safe location so that it is available for reference when required.
• For detail description such as function, performance, and usage of the KP inverter, refers to the manual of the
KP inverter.
1 - 2
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
1 Introduction
1-2Read and Understand This Manual
1-2 Read and Understand This
Read and understand this manual before using the KP inverter. Please consult your OMRON representative if
you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for specified
period from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING
NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS.
ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL
OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS
OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH
CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability
is asserted.
Manual
1
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING
THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY
HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE,
MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
1 - 3
1 Introduction
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and
limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of
the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to
be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be
suitable for the products:
• Uses involving potential chemical contamination or electrical interference, or conditions or uses not described in
this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment,
amusement machines, vehicles, safety equipment, and installations subject to separate industry or government
regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY
WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE
WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
1 - 4
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
1 Introduction
Disclaimers
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not
constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual
application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
CHANGE IN SPECIFICATIONS
1-2 Read and Understand This
Manual
Product specifications and accessories may be changed at any time based on improvements and other reasons.
Consult with your OMRON representative at any time to confirm actual specifications of purchased product.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are
shown.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility
is assumed for clerical, typographical, or proofreading errors, or omissions.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
COPYRIGHT AND COPY PERMISSION
This document shall not be copied for sales or promotions without permission.
This document is protected by copyright and is intended solely for use in conjunction with the product. Please notify
us before copying or reproducing this document in any manner, for any other purpose. If copying or transmitting this
document to another, please copy or transmit it in its entirety.
1
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
1 - 5
1 Introduction
1 - 6
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
2 - 1
2 Settings
2-1Outline of communications functions
The KP inverter are equipped with an RS232C/RS-485 port, which allows remote monitoring and remote
operations over networks.
The following protocol is supported:
ModelSuported protocol
KPG
KP
L
The KP inverter has the following communications functions:
Reading settings and data
Executing operation commands
CompoWay/F is OMRON's unified communications protocol for general-purpose serial communications. This
unified format has a proven track record with OMRON Programmable Controllers, has FINS-compliant
commands (see note), and simplifies communications between the host computer and components.
Note:
FINS (Factory Interface Network service) is a messaging protocol for communications between Controllers in
OMRON FA networks.
Compoway/F
Compoway/F, MODBUS
Modbus is a standard communications control method that conforms to the Modicon Company’s RTU-mode
Modbus Protocol (PI-MBUS-300 Revision J).
Supports functions are similar to the CompoWay/F Read Variable Area, Write Variable Area, Operation
Command.
2-2Cable Connections
Refer the manual of each inverter for cable connections.
2 - 2
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
2-3Communications settings
2-3-1Communication settings for KP40G
Communication protocol settings
You can use only Compoway/F on KP40G.
There is no setting for communication protocol.
2 Settings
2-3 Communications settings
2
Node number (Unit number) settings
Node number can be set by setting switch as shown figure.
Baud rate settings
Baud rate is fixed 19200bps.
2-3-2Communication settings for KP100G
Communication protocol settings
You can use only Compoway/F on KP100G.
Always set TYPE1 as protocol on communication settings menu of Data Logger.
Node number (Unit number) and baud rate settings
Node number and baud rate can be set by menu of communication settings on Data Logger of the inverter.
2-3-1 Communication settings for KP40G
COMMUNICATION SETTINGS
OK
[Setting procedure]
1
Use to select COMMUNICATION SETTINGS.
2
Press "OK" to set.
3
Use to select item which you set
4
Use to set node number and baud rate..
5
Press "OK" again to confirm.
PROTOCOL:TYPE1
NODE NO:1
BAUD RATE:19200bps
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
2 - 3
2 Settings
y
y
2-3-3Communication settings for KPL
Communication protocol settings
Select Compoway/F or MODBUS on KPL by LCD menu.
State display
RUN
ERR
MODEENT
<<>>
Normal Display
Pac 3.69kW
1.23/1.23/1.23kW
Push the MODE key
for 5 second
Mode selection display
Error occurs
Error doesn’t
occur
Error Displa
Fault E1-2
Grid 0V
Push the MODE key or
No operation for 150seconds
Push the ENT key
for 5 second
MODE
or
No oparation for 150second
LCD Check Displa
■■■
■■■ V1.23■■■
KP100L
■■■
>>
MODE
MODE
After five
seconds pass
ModeSelect
Setup [Check] ErrL
MODE
mode of Check Settings
Check:Country
GER
ENT
Setup:Language
[ENG]
ENT
Setup:COM_Prot
[Auto]
Setup:COM_Prot
Auto
ENT
ENT
ModeSelect
ErrLog [Setup]Che
MODE
mode of User’s setup
Setup:Language
ENG
<<
Setup:COM_Prot
Auto
<<
ENT
>>
>>
Node number (Unit number) and baud rate settings
Select communication protocol and set node number and baud rate by LCD menu.
[Setting procedure]
>>>>
ModeSelect
Check[ErrLog]Set
MODE
mode of Error
ErrLog:1.E1-0
No Utility
>>
Setup:Language
<<
>>
<<
When the setting has been setting,
Setup value does the blinking display.
ENT
[ITA]
Setup:COM_Prot
[Compoway]
<<<<<<
>>
<<
>>
<<
1
Push the MODE key for 5 second, and enter Mode Selection Display.
2
Push <</>> to select “Setup".
3
Push ENT key and enter mode of User’s setup.
<Protocol>
4
Select “Setup:Protocol” and .push ENT key.
5
User <</>> to change protocol. If you select “Auto”, protocol is detected automatically according to
communication command.
<Node number>
4
Select “Setup:COM_Unit” and .push ENT key.
5
User <</>> to change number.
2 - 4
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
<Baud rate>
4
Select “Setup: COM_232C” or “Setup: COM_485”, and .push ENT key.
5
User <</>> to change baud rate.
6
Push MODE key to confirm communication protocol
7
Push MODE key to rerun normal display.
2 Settings
2-3 Communications settings
2
Refer the user’s manual of KPL for more detail information.
2-3-3 Communication settings for KPooL
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
2 - 5
2 Settings
2 - 6
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
Compoway/F
This section describes how to use Compoway/F communications based on
communications commands.
Grid Connect Photovoltaic Inverter KPG/KPL Communication Manual
3 - 1
3 Compoway/F
3-1CompoWay/F Communications
Specifications
Communications Control Method
Programs can be created in the host computer (e.g., a personal computer) toset or monitor parameters in theKP
inverter. Therefore the descriptions in this section are from the standpoint of the host computer. For example,
"Read/Write" refers to the host computer reading or writing to the inverter.
Communications Specifications
InterfaceRS-485RS-232C
Transmission path
connections
Communications2-wire system half duplexHalf duplex
SynchronizationStart-stopsynchronization
Baud rate
*: default
Transmitted codeASCII
Data bit length7 bits
Stop bit length2 bits
Error detectionVertical parity (even) BCC (block check character)
Data transmission LSB first
Flow controlNone
Retry functionNone
Communications buffer
Response wait time after
RS-485 command
transmitted
Waiting time after RS-485
response
The next command waiting
time after simultaneous
broadcasting