Omron KM50-C Instruction Manual

KM50-C
KM50-C
INSTRUCTION MANUAL
All Rights Reserved
Smart Power Monitor
EN
INSTRUCTION MANUAL
9911216-0 A
Nomenclature
KM50-C
Temperature unit
Action indication
UP key
SHIFT key
P
OUT1 STOP
UP
SHIFT MODE ENTER
1st display 2nd display
ENTER key
MODE key
Display Screen
1) 1st display Displays the measurement value or type of setting data.
2) 2nd display Displays the unit or the parameter name of the measurement data or setting data.
3) Operation display
OUT1: STOP:
The light turns ON in conjunction with the output set to the OUT1 terminal.
Lights ON when power is supplied after the time measurement function stops following back-up power failure during power OFF. Lights OFF by setting time data. When using the product with lights ON, measurement data log cannot be recorded.
(Key): Lights ON at protect setting.
4) Temperature unit When selecting Celsius in the temperature unit setting, °C is shown. When choosing Fahrenheit, °F is shown.
Segment display
R
7SEG 11SEG
7SEG 11SEG
aAbBcCdDeEfFgGhHiIGJHKlLIMNNoOpPJQK abcdefghijk lmnopqr
S
T
U
V
W
X
Y
Z
0
1
2
3
4
5
6
s
t
u
W
X
Y
y
Z
Y
1
2
3
4
5
6
s
t
u
v
w
x
y
z
0
1
2
3
4
5
6
9
7
8
9
7
8
9
7
8
Basic usage
Setting Examples
Applicable circuit type: 1-phase 3-wire Dedicated CT type: 5ACT Time: March 5, 2010, 17:15
A. After checking the wiring, turn ON the power supply.
Hm50c” is displayed and EEPROM is read (“wait” is displayed for 16 sec max). When the power is turned ON for the first time, “e-t1” is displayed and STOP turns ON because time has not been set. 3 sec later, active power in measure­ment mode is displayed. (STOP remains ON).
B. Set applicable circuit type to 1-phase 3-wire.
1. Press the M key for more than 3 sec to go to applicable circuit type “00.typ” in operation setting mode.
2. Press the U key to shift to setting state. Press the U key to change the applicable circuit type from “3p3w” to “1p3w”, and then press the O key to confirm.
C. Set dedicated CT type to 5ACT.
1. Press the S key to move to dedicated CT type “01.c.rg”.
2. Press the U key to shift to setting state. Press the U key to change the dedicated CT type from “100a” to “5a”, and then press the O key.
D. Set the time to March 5, 2010, 17:15.
To use the log function, time setting is required.
1. Press the S key to move to time setting “11.tim”.
2. Press the U key to shift to setting state. Check that the year is "2010”, and then press the O key. Change the value of Month/Date with the U key and shift the digit with the S
3. key to change the value from
4.
Change the value of Hour-Minute with the U key and shift the digit with the S
01 01
to
03 05
, and then press the O key.
key to change the value from “00-00” to “17-15”, and then press the O key. The content of the time setting will be saved and STOP will be turned OFF.
5. Press the M key for more than 3 sec to move to measurement mode (measurement start). When you move to measurement mode, the setting will be saved and “save” is displayed. This completes the basic settings.
Mode configuration and key operation
1) Mode configuration
Mode Group Meaning
Measurement mode
Protect setting mode Limit the function
Operation
Setting
setting mode
mode
Communication setting mode
Basic level Pro level
Basic level Pro level Set the Pro level function
Read the measurement data of the basic level
Read the measurement data of the Pro level
Set the basic level function
Set the communication function
Necessity of operation
and setting
Operate only at reading Operate only at reading Set only when needed
Setting required at first setting Set only when needed Set only when using the
communication function
2) Key operation Monitoring state is a state in which setting value is displayed in protect setting mode and setting mode. Setting state is a state in which setting can be changed.
Symbol
O
ENTER key
M
MODE key
S
SHIFT key
U
UP key
M+S
(Press the S
key while holding
the M key)
M+U
(Press the
U key while
holding the M key)
MO
Basic Meaning
Mode switchingDetermination
Mode switchingCancel
Transition
Shift to
setting state Change the setting value
Reverse transition
Change the setting value in reverse
Mode switching
Mode State
Measurement mode
Protect setting mode, Setting mode
Operation setting mode
Communication setting mode
Measurement mode
Setting mode
Measurement mode, Setting mode
Measurement mode
Setting mode
Measurement mode
Setting mode
Measurement mode, Setting mode
Measurement mode
Setting mode
Measurement mode Setting mode
Measurement mode
Protect setting mode
Operation
Measurement history (current day)
Setting state Determine the setting value. Monitoring state
Monitoring state Move to operation setting mode. Present measurement value,
measurement history
Measurement history
Monitoring state Move to measurement mode. Setting state Cancel setting state.
Pro level Move to “PROLV” of the basic level.
Present measurement value
Measurement history
Monitoring state Change parameters. Setting state Change digits. Present measurement value
Measurement history
Monitoring state Shift to setting state. Setting state Change the setting value. Basic level (“PROLV”
remains displayed) Present measurement value
Measurement history
Monitoring state Change parameters in reverse. Setting state Change digits in reverse.
Measurement history
Setting state Present measurement value,
measurement history Monitoring state Move to measurement mode.
press for more than 3 sec
click click
click press for more
than 3 sec click press for more than 3 sec click
click
click click click click click click click click click
click click click
click click click press for more
than 3 sec press for more than 3 sec
Clear the currently displayed MAX and MIN value of the present day.
Move to communication setting mode.
Move to operation setting mode.
Move to present measurement value.
Change parameters. Switch measurement history display.
Move to measurement history. Move from measurement history.
Move to Pro level.
Change parameters in reverse. Switch the measurement history display.
Transit measurement history in reverse. Change the setting value in reverse.
Move to protect setting mode.
Setting mode
Operation setting modeBasic level
Item Setting range (1st display)
Applicable circuit type
Dedicated CT type Rated primary side current value VT
VT primary side
setting
voltage value VT secondary side
voltage value Current low-cut value Unit Pulse output unit Unit Display refresh period off is instantly updated.Unit
Averaging times. Simple
measurement
setting
CO
Charge conversion setting (Rate setting and price unit setting)
Pulse conversion 1 setting
Pulse conversion target,
factor, decimal point position and display unit)
Pulse conversion 2 setting
Pulse conversion target,
factor, decimal point position and display unit)
Time setting (Year, month/day, hour/minute)
Initialization
Moving average time Setting
Simple measurement
Fixed voltage value. Fixed power factor value.
conversion factor
2
1p2w, 1p3w, 3p3w 00.typ 3p3w
5a, 50a, 100a, 200a, 400a, 600a 5
to
9999 02.sct 5
none, 220, 440, 3300, 6600, 11000, 22000, 33000
110, 220 110
0.1
to
19.9
1, 10, 100, 1k, 2k, 5k, 10k, 20k, 50k, 100k off, 0.5, 1.0, 2.0, 4.0 06.ref 1.0 off, 2, 4, 8, 16, 32, 64, 128, 256, 512, 1024 off, on 08.smp off
to
9999.9 vlt 110.0
0.0
to
1.00 pf 1.00
0.00
0.000
to
99.999 10.co2 0.387
0.000
to
99.999
jpy, usd, eur, cny, krw
to
z, 0
to
to
to
to
z, 0
to
z, 0
to
to to
9,  , -, (Space)
9999
to
9,  , -, (Space)
9999
to
9,  , -, (Space)
2099
12 31 23-59
a c-t.d, c-1.d, c-2.d, c-t.a, c-1.a, c-2.a
0000 0000, 000.0, 00.00, 0.000 a
c-t.d, c-1.d, c-2.d, c-t.a, c-1.a, c-2.a 0000 0000, 000.0, 00.00, 0.000 a
2010 01 01 00-00
set, max, min, integ, m.pro, log, all 15.ini set
001120 16.avt 120
2nd display Initial value
01.c.rg 100a
03.v.rg none
v.rg2
04.cut 0.6
05.pl5 100
07.avg 8
11.chg 10.000 jpy
12.cv1 c-1.d 0001 0000 m3-1
13.cv2 c-2.d 0001 0000 m3-2
14.tim 2010 01 01 00-00
Remarks
1p2w: 1-phase 2-wire, 1p3w: 1-phase 3-wire, 3p3w: 3-phase 3-wire
Effective only when the dedicated CT type is 5A. When the simple measurement is ON, sequentially
measure the reactive voltage, VT primary voltage, and VT secondary voltage. Unit: V
:
%
:
Wh
At ON, set voltage and power factor, Frequency is 50 Hz fixed.
Can be set only at simple measurement ON. Can be set only at simple measurement ON. Unit
:
kg-CO2/kWh
Sequentially set the rate and price unit display. 4-digit price unit can be set.
Sequentially set the pulse conversion target, conver­sion factor, display unit. 4-digit display unit can be set.
c-t.d: Sum of pulse input counts
:
Pulse input count 1
c-1.d
:
Pulse input count 2
c-2.d
:
Sum of total pulse input counts
c-t.a c-1.a
:
Total pulse input count 1
c-2.a
:
Total pulse input count 2
Year, month/day, and hour/minute should be set continuously. If it was canceled in process, all values will return to previous values. As soon as setting hour and minute, the settings are reflected.
:
Initialize all setting values except time setting.
set max: Initialize all the max value of parameters of
the present day.
:
Initialize all the min value of parameters of
min
the present day.
:
Initialize the total integral power consumption.
integ m.pro: Initialize the measurement values in the Pro
level in measurement mode of the present day.
log: Initialize all the measurement histories. all
:
Initialize set values other than clock time and all measurement histories.
Set the moving average time of the Moving average Current. Cancel it during the input or set a value out of the range, come back before a change.
Description
:
Sec
Operation setting modePro level
Item
Event input setting p.csp
Event input 1 NPN/PNP input mode setting
Event input 2 NPN/PNP input mode setting
Event input 1 N-O/N-C input mode setting
Event input 2 N-O/N-C input mode setting
Measurement start time (*1)
Measurement end time (*1)
Output terminal 1 function setting
Active power alarm output (Upper/lower thresholds, hysteresis and OFF-/ON-delay)
Regenerated power alarm output (Upper/lower thresholds, hysteresis and OFF-/ON-delay)
Current alarm output (Upper/lower thresholds, hysteresis and OFF-/ON-delay)
Voltage alarm output (Upper/lower thresholds, hysteresis and OFF-/ON-delay)
Power factor alarm output (Upper/lower thresholds, hysteresis and OFF-/ON-delay)
Reactive power alarm output (Upper/lower thresholds, hysteresis and OFF-/ON-delay)
Integral power consumption saving selection
Automatic rotation setting
Measurement parameter display selection
Display lighting time Incorrect voltage wiring detection Simple temperature setting
*1 It applies to the pulse input count, power consumption rate, pulse input ON time. *2 When thresholds or hysteresis is set, the operating value which is converted from the setting value (%) is displayed.
Automatic rotation Transition time
Temperature unit Temperature correction value
Setting range (1st display)
p.csp, h-on, 3-st
npn, pnp 31.pn1 pnp
npn, pnp 32.pn2 pnp
n-o, n-c 33.in1 n-o
n-o, n-c 34.in2 n-o
00-00 to 23-59
00-01 to 24-00
off, p.out, alarm
0.0
to
150.0
0.0
to
19.9
0.0
to
99.9
0.0
to
150.0
0.0
to
19.9
0.0
to
99.9
0.0
to
120.0
0.0
to
19.9
0.0
to
99.9
0.0
to
120.0
0.0
to
19.9
0.0
to
99.9
0
to
100
0
to
19
0.0
to
99.9
0.0
to
150.0
0.0
to
19.9
0.0
to
99.9
-w, var.d, var.g, var.a
off, on 61.rtt off 1
to
99 rtim 3
off, on 62.d.sl
to
99 63.dsp 0
0 off, on 64.v-e on c, f 65.d-u c
to
-50.0
2nd display
30.ei5 p.csp
35.5tc 00-00
36.etc 24-00
50.o1 p.out
52.p.al
53.r.al
54.a.al
55.v.al
56.pf.a
57.q.al
60.i.sl -w
50.0 t.ad 0.0
(*2)
(*2)
(*2)
(*2)
(*2)
(*2)
Initial value
See the remarks.
See the remarks.
See the remarks.
See the remarks.
See the remarks.
See the remarks.
See the remarks.
Remarks
:
Electric power consumption rate,
h-on
:
Pulse input ON time
npn
:
None voltage input
:
Voltage input
pnp npn
:
None voltage input
pnp
:
Voltage input
:
Normally open
n-o
:
Normally close
n-c
:
Normally open
n-o
:
Normally close
n-c
Time setting later than the measurement end time cannot be made.
Time setting earlier than the measurement start time cannot be made.
p.out: Integral power consumption pulse output, alarm: Alarm output,When selecting “alarm”, the screen
moves to the ON/OFF setting of various alarm outputs. Sequentially set the upper/lower thresholds, hysteresis and
OFF-/ON-delay. Upper threshold: 80.0, Lower threshold: 0.0%, Hysteresis: 5.0, OFF-delay: 3.0 sec, ON-delay: 0.0 sec
Sequentially set the upper/lower thresholds, hysteresis and OFF-/ON-delay. Upper threshold: 80.0, Lower threshold: 0.0%, Hysteresis: 5.0, OFF-delay: 3.0 sec, ON-delay: 0.0 sec
Sequentially set the upper/lower thresholds, hysteresis and OFF-/ON-delay. Upper threshold: 110.0, Lower threshold: 0.0%, Hysteresis: 5.0, OFF-delay: 3.0 sec, ON-delay: 0.0 sec
Sequentially set the upper/lower thresholds, hysteresis and OFF-/ON-delay. Upper threshold: 110.0, Lower threshold: 0.0%, Hysteresis: 5.0, OFF-delay: 3.0 sec, ON-delay: 0.0 sec
Sequentially set the upper/lower thresholds, hysteresis and OFF-/ON-delay. Upper threshold: 100, Lower threshold: 0, Hysteresis: 5, OFF-delay: 3.0 sec, ON-delay: 0.0 sec
Sequentially set the upper/lower thresholds, hysteresis and OFF-/ON-delay. Upper threshold: 80.0, Lower threshold: 0.0%, Hysteresis: 5.0, OFF-delay: 3.0 sec, ON-delay: 0.0 sec
-w: Integral regenerated power consumption var.d: Integral leading reactive power consumption var.g: Integral lagging reactive power consumption var.a: Integral total reactive power consumption
At ON, set the transition time. Can be set only at automatic rotation ON. Set it for each parameter of the measurement mode.
For the charge conversion value, pulse conversion 1 and 2, integral regenerated power consumption, integral leading/lagging/total reactive power consumptions and simple temperature, these initial values are off
0 is
always lighting, Unit
Sequentially set the temperature unit and the temperature correction value. c:
Celsius
,
Unit: °C
,3-st: 3-STATE
: Min
, f:
Fahrenheit
,
.
Unit: °F
Communication setting mode
Item Setting range (1st display) 2nd display Initial value Remarks
Protocol select compf: CompoWay/F,modb: Modbus Unit No. Baud rate Data bit length (*1) Unit: bit Stop bit length (*2) Unit: bit Vertical parity Time to wait for sending
*1 When protocol is Modbus, data bit length is 8-bit fixed. *2 When protocol is Modbus, stop bit length cannot be set due to automatic setting.
When vertical parity is NONE, the length is 2, when vertical parity is ODD or EVEN, the length is 1.
compf, modb 80.psl compf CompoWay/F: 0
1.2k, 2.4k, 4.8k, 9.6k, 19.2k, 38.4k 7, 8 83.len 7 1, 2 84.sbt 2 none, odd, even 85.prt even
to
99 86.sdw 20
0
to
99, Modbus: 1
to
99
81.u.no
82.bps 9.6k
1
Unit: bps
Unit: ms
Protectedmode
Setting content
Displayed value transition
0Yes 1Yes 2Yes
Move to setting mode Move to pro level
Yes Yes Yes
Limit content
Yes Yes
No
Clear measurement history
Yes
No No
Yes: Permission / No: Prohibited
Change setting content
Yes
No No
Pro Level
Basic Level
Power ON
State Transition
Basic Level
Pro Level
Protect
Setting Mode
Measurement Mode
Setting Mode
Operation Setting Mode
Communication Setting Mode
Power ON
Measurement Mode
Basic Level
Pro Level
M+SM+S
*Example of 3-phase 3-wire When the setting is 1-phase 2-wire, the current 2, 3 and the voltage 2, 3 are not displayed. When the setting is 1-phase 3-wire, the 2nd. display of current and voltage changes. (e.g.
Total integral power
Active power
0.000 0.0 0.000 0.000 0.000 0.0 0.0
*1 *1 *1 *1
Pulse input count
consumption
M+SM+S
kw kwh a-r a-5 a-t v-r5 v-st
S
Electric power consumption rate
cnt
0
0.000
Hwh p
S
*4*4 *4
Product information
SSS S
c1flk
Current 1 Current 2 Current 3
M+S
S
SS
M+S
S
v2.0
M+S
M+S
S
*3*2 *3 *3
Pro Level
M+S
U
M
Pulse input ON time
M+S
00-00
h-on
S
Simple temperature
C
0.0
temp
M+S M+S MS
Time
Total integral regenerated power consumption
Total integral total reactive power consumption
The measurement mode can display a past measured value. (*1 to *4) While it is in condition to display a past measured value, display the date and time and a measured value in turn. Please refer to a right figure.
Active power
*1
Example of active powerAlternately displays the time when maximum and minimum values were
recorded, and the maximum and minimum values, for each day.
Reactive power displays only the maximum and minimum values of the
current day.
*5
When selecting others than “none, sequentially set VT primary side voltage and VT secondary voltage.
*10
0.000
kw
U
M
Maximum value
UU
02 25
00-00
M+U
U
03 04
00-00
M+U
U
03 05
00-00
M+U
VT setting
none
03.v.rg
U
M
at “none” :O
VT primary side voltage value
At selection excluding “none”
none
03.v.rg
Output terminal 1 function setting
p.out
50.o1
U
M
At selection excluding “alarm
p.out
At “alarm:O
50.o1
Example of output terminal 1 function settingWhen selecting
alarm, set each alarm to ON/OFF.
M+S
S
M+S
S
M+S
S
O
Minimum value
02 25
00-00
M+U
U
03 04
00-00
M+U
U
03 05
00-00
M+U
VT secondary side voltage value
:O
110
v.rg2
Active power alarm output
O
off
p.al
Regenerated power alarm output
off
r.al
Simple measurement
*6
U
08.smp
When the simple measurement is ON, sequentially set the fixed voltage value and fixed power factor value.
Volt age
Current
alarm output
alarm output
O
O
off
a.al
a-sa-n)
M+S
S
M+S
Pulse conversion value 2
S
Moving average current 1
M+S
0.000 0.000 0.000
S
M+S
ma-r ma-s
Pulse conversion value 1
S
M+S
S
S
M+S
Moving average current 2
Charge conversion value
jpym3-1m3-203 05
Moving average current 3
M+S
S
CO
exchanged
2
value
S
0.0000.0000.0000.00017-15 55.0
M+S
ma-t
co2
Voltage 1 Voltage 2
M+S
S
Frequency
S
M+S
M+S
S
hz
Please refer to figure *1 to *4 for the transition that is in an internal state of *1 to *4.
Total integral leading reactive power consumption
M+S
0.0
-kwh
S
0.0
kvh.a
*1
*2
On monthly display, the 1st. display alternately displays Year-Month of when the integral power consumption was recorded, and the value of integral power consumption. The 2nd. display alternately displays “how many months ago” and a unit. On daily display, the 1st. display alternately displays Month/Day of when the integral power consumption was recorded, and the value of integral power consumption. The 2nd. display alternately displays “how many days ago” and a unit. On hourly display, the 1st. display alternately displays Date-Hour of when the integral power consumption was recorded, and the integral power consumption. The 2nd. display alternately displays “how many hours ago” and a unit.
off
08.smp
M
at OFF : O
ON時:O
on
O
off
v.al
Total integral lagging reactive power consumption
Month/Day
Hour-Minute
Total integral power consumption 10-digit display
M+S
Fixed voltage value.
110.0
vlt pf
Power factor alarm output
off
pf.a
0.0
kvh.d
S
0.0
kvh.g
Alternate display
(1.5 sec auto)
Total integral power consumption
0.0
kwh
U
M
00000
00000
S
Fixed power factor value.
O
Reactive power alarm output
O
off
q.al
M+S
1.00
O
OM
(3 sec min.)
MAX/MIN
*2
Year-Month
Active power
Month/Day
Day-Hour
Monthly integral power consumption for past 13 months
M+U
M+U
M+U
M+S
10-03
0 m
SSS
U
U
09-02
-13 m
U
10-02
- 1 m
Charge
*7
conversion setting
10.000
U
Rate setting
10.000
Sequentially set the rate and price unit.For the price unit, after choosing from options, user can
change it to any unit.
*11
Example of active power alarm outputSequentially set upper/lower thresholds, hysteresis and OFF-/ON-delay.The second displays of upper/lower thresholds and hysteresis switch to operating values
calculated from the threshold after 1.5 sec.
Months ago
Days ago
Hours ago
Daily integral power consumption for past 8 days
03 05
M+U
02 25
- 8 d
M+U
03 04
- 1 d
M+U
11.chg
M
O O
rate
Active power alarm output
U
Upper threshold
Alternate display
(1.5 sec auto)
Alternate display
(1.5 sec auto)
Alternate display
(1.5 sec auto)
0 d
U
U
U
Price unit setting (Selection)
80.0
52.p.al
M
O
80.0
ov.th
M+S
jpy
Lower threshold
Protect
Setting Mode
Protect setting
0
prtct
unit
Integral power
Integral power
Integral power
M+U
M+U
M+U
0.0
un.th
*3
consumption
Unit
consumption
Unit
*4
consumption
Unit
Hourly integral power consumption for past 25 hours
5-17
0 h
U
U
4-16
-25 h
U
5-16
- 1 h
Price unit setting (Arbitrariness)
jpy
unit
Hysteresis OFF-delay ON-delay
O
5.0
al.hys
O
O
Reactive power
S
0.000prolv
kvar
*1 *1
Month/Day
Hour-Minute
Month/Day
Days ago
O
3.0
of.dly
Setting Mode
Operation Setting Mode
Basic Level
M
(3 sec min.)
0.000
a-r
M
Measurement stop
Measurement start
M
(3 sec min.)
Pro Level
Communication Setting Mode
M+SM+SM+S
M+S
S
S
Alternate display
(1.5 sec auto)
Alternate display
(1.5 sec auto)
Voltage 3
Power factor
1.00
Current 
MAX/MIN/AVE
Electric power
consumption rate
*3
0.0
v-tr
pf
S
M+SM+SM+S
Unit
Current
U
Maximum value Minimum value
UU
M+S
03 05
00-00
M+U
U
02 25
00-00
M+U
U
03 04
00-00
M+U
U
03 05
00-00
M+U
Alternately displays the time when maximum and minimum values were
recorded, and the maximum and minimum values, for each day.
Moving average current displays only the maximum value. minimum value is non-compliant. (display "-"mark)
Pulse conversion 1
*8
setting
c-1.d
12.cv1
U
M
Pulse conversion target 1
c-1.d
Example of pulse conversion 1 settingSequentially set the pulse conversion target, factor, decimal point position
and display unit.
O
0.0
on.dly
Factor setting 1
O O O
targ
0001
slp
-- --
-----
S
M+U
02 25
00-00
M+U
03 04
00-00
M+U
03 05
00-00
M+U
Decimal point position setting 1
0000
Automatic rotation
U
Automatic rotation
transition time.
U
U
U
dp
off
61.rtt
M
atOFF:O
off
61.rtt
atON:O
Display unit setting 1
m3-1
Transition time
M+S
S
M+S
S
M+S
S
*12
When the automatic rotation is ON, set the
Applicable circuit type
M+SM+S
3p3w
00.typ
Event input setting
M+S
p.csp
30.ei5
Simple temperature setting
S
c
65.d-u
*13
Protocol select
compf
80.psl
SS S
*9
O
unit
O
3
rtim
Dedicated CT type
100a
S
01.c.rg
Pro Level
prolv
U
S S
M+S
S
M+S
Rated primary current value
Moving average time Setting
S
5
02.5ct
120
16.avt
S
none
03.v.rg 04.cut
5 6
Initialization
S
5et
M+S M+S
15.ini
VT setting
M+S
Current low-cut value
M+S
S
M+S
0.6
Time setting
S
2010
14.tim
*9 *8 *8
M+S
S
M+S
Pulse output unit
100
05.pl5
Pulse conversion 2 setting
S
c-2.d
13.cv2
M+S
S
M+S
Display refresh period
06.ref
Pulse conversion 1 setting
S
c-1.d
12.cv1
1.0
M+S
S
M+S
Averaging times
07.avg
Charge conversion setting
S
10.000
*7
8
11.chg
M+S
S
S
M+S
Simple measurement
off
08.5mp
conversion
CO
2
factor
0.387
10.co2
M
Event input 1 NPN/PNP input mode setting
M+S
pnp
Incorrect voltage wiring detection
S
31.pn1
on
64.v-e
S
M+S
O
Unit No.
1
8 lu.no
Time to wait for sending
SSS
20
86.5dw
MSMSMS
*4
Example of electric power consumption rate
The 1st. display alternately displays Month/Day
of when electric power consumption rate was re­corded, and the electric power consumption rate. The 2nd. display alternately displays days ago
M+S
S
M+S
Baud rate
9.6k
82.bp5
Vertical parity
even
85.prt
Electric power consumption rate
0.000
U
02 25
M+U
03 03
M+U
03 04
M+U
and a unit.
Event input 2 NPN/PNP input mode setting
Display lighting time
S
M+S
Hwh p
M
U
- 8 d
U
- 2 d
U
- 1 d
pnp
32.pn2
0
63.dsp
Data bit length
Stop bit length
M+S
S
M+S
83.len
84.5bt
S
7
2
how many
Event input 1 N-O/N-C input mode setting
n-o
33.in1
S
Measurement parameter display selection
on
62.d.sl
M+S
S
Event input 2
M+S
S
N-O/N-C input mode setting
Automatic rotation setting
*12
n-o
34.in2
off
61.rtt
M+S
S
M+S
Measurement start time
00-00
Integral power consumption saving selection
S
35.5tc
-w
60.i.sl
M+S
S
M+S
Measurement end time
24-00
Reactive power alarm output
S
36.etc
80.0
57.q.al
M+S
S
M+S
Output terminal 1 function setting
p.out
*10
Power factor alarm output
S
56.pf.a
50.o1
100
M+S
S
M+S
Active power alarm output
*11
Voltage alarm output
S
80.0
52.p.al
110.0
55.v.al
Please refer to figure *5 to *13 for the transition that is in an internal state of *5 to *13.
Unit to save each measured value
The KM50 model has a function to save various measured values in EEPROM every five minutes, every day or every month. The list of measured values and saving units is shown below:
Measured value
Integral
power consumption
Active power, current, voltage and power factor (Maximum and minimum values)
Moving average current (Only the maximum values)
Pulse input count Electric power consumption rate Pulse input ON time
Integral regenerated power consumption Integral reactive power consumption
Total pulse count inputs
Saving
period
Save two days’ measured values every 5 min.
5 min.
Save 25 hours’ hourly values which are converted from
1 hour
measured values saved every 5 min.
Save 8 days’ values measured between 00:00 and 24:00.
1 day
Save 13 months’ values measured for a month.
1 month
Save 8 days’ values measured between 00:00 and 24:00.
1 day
(After saving, measured values are reset.)*
 ー
Save the current maximum values of the moving average time. (The moving average current with a product Ver.3.0.)
Save two days’ measured values every 5 min.
5 min.
Save 8 days’ values measured between 00:00 and 24:00.
1 day
Save two days’ measured values every 5 min.
5 min.
Save only items selected in the setting.
Overwrite save the measured value every 5 min.
5 min.
Note 1. At the time of power failure, the clock time data is retained for 7 days. Note 2. User can check the data every 5 min. only through communication.
Error indication
Description of error
KM50 internal clock time has not been set.
Built-in memory error (RAM error) (*1)
Display
e-t1
Indicates error at startup and “STOP” is turned ON. Measurement stops and operation disabled during error indication.
e-m1
Measurement stop, operation disabled
EEPROM error (*1) e-m2 Measurement stop, operation disabled Hardware repair (*2)
Operation
EEPROM data failed (*1) e-m3 Measurement stop, operation disabled Hardware repair (*2)
e-m4 Measurement stop, operation disabled Hardware repair (*2) e-s1 Displays error and measurement value
alternately and continues measurement.
alternately and continues measurement.
alternately and continues measurement.
alternately and continues measurement.
Time setting
2010
14.tim
U
M
Year Month/Day Hour/Minute
O
2010
14.tim
Sequentially set the year, month/day and hour/minute.
01 01
14.tim
O
00-00
14.tim
O
Calibration value error (*1) Excessive voltage input (*3)
Excessive current input (*3) e-s2 Displays error and measurement value
Frequency input error (*3) e-s3 Displays error and measurement value
Incorrect wiring detection (*4) e-s4 Displays error and measurement value
*1 When any of e-m1m4 errors occurs, all outputs stop and any key operation is not accepted. *2 Consult your OMRON representative. *3 An error will occur when the input of voltage exceeds 110% of the rated value, current exceeds 120% of
the rated value, frequency is below 45 Hz or more than 65 Hz.
*13
Simple temperature setting
c
65.d-u
U
M
Temperature Temperature unit
Sequentially set the temperature unit and
temperature correction value.
correction
value
OO
c
65.d-u
0.0
t.ad
When the voltage input is 20 V or less, frequency error isn’t displayed. When VT is set, the set value of secondary voltage becomes the rated voltage.
*4 For e-54 error, only when the incorrect voltage wiring detection is set to ON, the error is displayed.
Troubleshooting
Phenomenon Description Point to be checked
Voltage and current are measured but electric power is not correctly measured.
Has CT (Current Transformer) been correctly wired (not in reverse)?
Is the voltage phase sequence correct?
If negative electric power is measured, it might be all the CTs have been mounted oppositely. On the other hand, if the measured value is nearly 0, it might be one of the CTs has been mounted oppositely.
If the voltage phase sequence is not correct, electric power cannot be measured correctly. Perform correct wiring.
Regenerated power alarm output
M+S
80.0
*11
Current alarm output
S
*11*11*11*11
53.r.al
110.0
54.a.al
S
M+S
Remarks
Restoration method
Time setting
Hardware repair (*2)
Restore the input signal within to the rated range.
Restore the input signal within to the rated range.
Restore the input signal (voltage) within to the rated range.
Correct the input signal (voltage) wiring in phase sequence.
S
M+S
Loading...