Cat. No. N147-E1-01 Three-phase Asymmetry and Phase-sequence Phase-loss Relay K8AB-PA 3
■ Specifications
Ambient operating temperature −20 to 60°C (with no condensation or icing)
Storage temperature −40 to 70°C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage humidity 25% to 85%
Altitude 2,000 m max.
Voltage fluctuation range 85% to 110% of rated input voltage
Input frequency 50/60 Hz ±5 Hz (AC power supply)
Output relays Resistive load 6 A at 250 VAC (cos φ = 1)
6 A at 30 VDC (L/R = 0 ms)
Inductive load 1 A at 250 VAC (cos φ = 0.4)
1 A at 30 VDC (L/R = 7 ms)
Minimum load 10 mA at 5 VDC
Maximum contact voltage 250 VAC
Maximum contact current 6 A AC
Maximum switching
capacity
1,500 VA
Mechanical life 10,000,000 operations
Electrical life Make: 50,000 times, Break: 30,000 times
Terminal screw tightening torque 1.2 N·m
Crimp terminals
Two solid wires of 2.5 mm
2
, two crimp terminals of 1.5 mm2 with insulation sleeves, can be
tightened together
Insulation resistance 20 MΩ (at 500 V) between charged terminals and exposed uncharged parts
20 MΩ (at 500 V) between any charged terminals (i.e., between input, output, and power
supply terminals)
Degree of protection Terminal section: IP20, Rear case: IP40
Case color Munsell 5Y8/1 (ivory)
Case material ABS resin (self-extinguishing resin) UL94-V0
Weight 200 g
Mounting Mounted to DIN Track or via M4 screws
Dimensions 22.5 (W) x 90 (H) x 100 (D) mm
Installation environment Overvoltage Category III, Pollution Degree 2
Application standards EN60255-5/-6
Safety standards EN60664-1
EMC EMI: EN61326 Industrial applications
Electromagnetic interference wave
CISPR11 Group 1, Class A: CISPR16-1/-2
Terminal interference wave voltage
CISPR11 Group 1, Class A: CISPR16-1/-2
EMS: EN61326 Industrial applications
Electrostatic discharge EN61000-4-2: 8 kV (in air)
Radiating radio-frequency electromagnetic field EN61000-4-3:
10 V/m 1 kHz sine wave amplitude modulation (80 MHz to 1 GHz)
Burst EN61000-4-4: 1 kV (I/O signal line), 2 kV (power line)
Surge EN61000-4-5: 1 kV with line (power line),
2 kV with ground (power line)
Conducted RF EN61000-4-6: 3 V (0.15 to 80 MHz)
Power frequency magnetic field immunity
EN61000-4-8: 30 A/m
Voltage dip/short interruptions
EN61000-4-11: 0.5 cycle, 0.180° each, polarity 100% (rated voltage)