Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of −100°C or less is ±2°C ±1 digit maximum. The indication
accuracy of the U, L1, and L2 thermocouples at any temperature is
The indication accuracy of the B thermocouple at a temperature of 400
The indication accuracy of the R and S thermocouples at a temperature of 200
The indication accuracy of the W thermocouple at any temperature is (
±2°C ±1 digit maximum.
°C or less is unrestricted.
°C or less is ±3°C ±1 digit maximum.
±0.3% of the indicated value or ±3°C, whichever is greater) ±1 digit
maximum.
The indication accuracy of the PLII thermocouple at any temperature is (
±0.3% or ±2°C, whichever is greater) ±1 digit maximum.
2. The sampling period of the standard model with CT and remote SP inputs is 250 ms.
Digital ControllerE5AK/E5EK5
■ Output Unit Ratings and Characteristics
Relay output5 A at 250 VAC (resistive load)
SSR output1 A at 75 to 250 VAC (resistive load)
Voltage outputNPN: 40 mA at 12 VDC (with short-circuit protection)
Linear current output4 to 20 mA, permissible load impedance: 600
Linear voltage output0 to 10 VDC, permissible load impedance: 1 k
Note: An output relay (1 A at 250 VAC) is mounted on the position-proportional model. (When replacing, use the E53-R.)
NPN: 20 mA at 24 VDC (with short-circuit protection)
PNP: 20 mA at 24 VDC (with short-circuit protection)
WeightE54-CT1: approx. 11.5 g; E54-CT3: approx. 50 g
Accessories (E54-CT3 only)Armature: 2; Plug: 2
50 Hz, 98 m/s
2
(10G)
■ Heater Burnout Alarm
Max. heater currentSingle-phase 50 A VAC (see note 1)
Heater current value display accuracy
Heater burnout alarm setting range0.1 to 49.9 A (in units of 0.1 A) (see note 2)
Min. detection ON time190 ms (see note 3)
Note: 1. Use the K2CU-F@@A-@GS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than 190 ms.
±5% FS±1 digit max.
6Digital Controller E5AK/E5EK
Nomenclature
E5AK
Operation Indicators
OUT1
•
Lights when the pulse output
function assigned to control output
1 turns ON.
•
OUT2
Lights when the pulse output
function assigned to control output
2 turns ON.
• SUB1
Lights when the output function
assigned to auxiliary output 1
turns ON.
• SUB2
Lights when the output function
assigned to auxiliary output 2
turns ON.
• MANU
Lights when the manual operation
mode.
• STOP
Lights during operation has
stopped.
• RMT
Lights during remote operation.
• AT
Flashes during auto-tuning.
• RSP
Lights during remote SP operation.
• Bar Graph
On a standard model (E5AKAA2), this bar graph indicates the
manipulated variable (heat) in
10% increments per single segment. On a position-proportional
model (E5AK-PRR2), this bar
graph indicates the valve opening
in 10% increments per single segment.
No. 1 Display
Displays the process value or parameter symbols.
No. 2 Display
Displays the set point, manipulated
variable, or parameter settings.
Up Key/Down Key
Press to increase or decrease the
value on the No.2 display.
Display Key
Press for less than 1 s to shift the
display to the next parameter. When
this key is pressed for 1 s or more,
the menu screen will be displayed in
any case.
A/M Key
Press to select the auto operation or
manual operation.
E5EK
Operation indicators
Display Key
A/M Key
No. 1 display
No. 2 display
Up Key/Down Key
Digital ControllerE5AK/E5EK7
Dimensions
Note: All units are in millimeters unless otherwise indicated.
E5AK
E5EK
96 × 96
Panel Cutouts
91 × 91
120 min.
Note:1. Recommended panel thickness is 1 to 8 mm.
2. Maintain the specified vertical and horizontal
mounting space between each Unit. Units must
not be closely mounted vertically or horizontally.
Panel Cutouts
60 min.
120 min.
110 min.
Note:1. Recommended panel thickness is 1 to 8 mm.
2. Maintain the specified vertical and horizontal
mounting space between each Unit. Units must
not be closely mounted vertically or horizontally.
Accessories (Order Separately)
Terminal Cover
E53-COV0809E53-COV08
8Digital Controller E5AK/E5EK
Current Transformer
E54-CT1E54-CT3
5.8 dia.
40x40
Installation
Note: Always turn off the power supply to the Digital Controller before changing any switch settings.
■ Settings
On a standard model, set up the Output Units for control outputs 1
and 2 before mounting the Controller.
On a position-proportional model, the Relay Output Unit is already
set. Therefore, this setup operation is unnecessary. (Do not replace
with other Output Units.)
When setting up the Output Units, draw out the internal mechanism
from the housing and insert the Output Units into the sockets for control outputs 1 and 2.
Setting Up the Option Unit
•E5AK
1. Remove the power board and option boards in the order shown in
the following diagram.
2.36 dia.
12 dia.
Two, M3 (depth: 4)
Setting Up the Output Unit
Removing the Output Unit
To replace the Output Unit, use a flat-blade screwdriver to push up
the Output Unit.
2. Insert the Option Units into the sockets for options 1 to 3. The following diagram shows the relationship between the Option Units
and mounting positions.