Omron E5C2 specifications

Analogue Temperature Controller
E5C2
DIN-sized (48 x 48 mm) Temperature Controller with Analog Setting
• Compact, low-cost Temperature Controller.
• Consecutive mounting possible using mounting adapter.
• Incorporates a plug-in socket, thus allows to DIN-track and flush mounting.
Model Number Structure
Model Number Legend
E5C2- @ @ @ @
12345
1. Model name
2. Control output
R: Relay Q: Voltage
3. Control method
20: ON-OFF control 40: P control
®
4. Input type
K: K-type thermocouple L: J-type thermocouple P: Platinum resistance thermometer (PT100) G: Thermistor (THE)
5. Special type
Blank: Standard type D, DIN: Special types
Ordering Information
Temperature Controllers
Setting method
Analog setting No indication ON/OFF Relay E5C2-R20K
Note: When placing an order, specify the standard temperature range and supply voltage in addition to the model number.
(e.g., E5C2-R20K 0
Accessories (Order Separately)
Front Connecting Socket P2CF-08 Back Connecting Socket (for flush mounting) P3G-08 Front Connecting Socket with Finger Protection P2CF-08-E Protective Cover (for finger protection) Y92A-48G
Indication
method
Control mode Output Model
P Relay E5C2-R40K
°C to 200°C 100/110 VAC)
Name Model
Thermocouple Platinum resistance
K (CA)
Chromel vs.
alumel
L (IC)
Iron vs.
constantan
E5C2-R20L-D E5C2-R40L-D
thermometer
E5C2-R20P-D E5C2-R20G E5C2-R40P-D ---
Pt100
Thermistor
THE
Controller
Temperature
Analogue Temperature Controller E5C2 I-7
Specifications
Ratings
Supply voltage 100/110/120 VAC (common), 200/220/240 VAC (common) (See note.)
Operating voltage range 90% to 110% of rated supply voltage Power consumption Approx. 2 VA Input Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor Control mode ON/OFF or P control Setting method Analog setting Indication method No indication Control output Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
Note: Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.
50/60 Hz (common)
Input Ranges
Input Thermocouple Platinum resistance
K (CA)
Chromel vs. alumel
Range °C 0 to 200 (5),
°F 32 to 392 (10),
Note: 1. Values in ( ) are the minimum unit.
2. Values in ( ) are the thermistor resistive value.
0 to 300 (10), 0 to 400 (10), 0 to 600 (20), 0 to 800 (20), 0 to 1,000 (25), 0 to 1,200 (25)
32 to 572 (20), 32 to 752 (20), 32 to 1,112 (40), 32 to 1,472 (50), 32 to 1,832 (50), 32 to 2,192 (50)
L (IC)
Iron vs. constantan
0 to 200 (5), 0 to 300 (10), 0 to 400 (10)
32 to 392 (10), 32 to 572 (20), 32 to 752 (20)
thermometer
Pt100 THE
–50 to 50 (2), –20 to 80 (2), 0 to 50 (1), 0 to 100 (2), 0 to 200 (5), 0 to 300 (10), 0 to 400 (10)
32 to 212 (5), 32 to 392 (10)
Thermistor (see note 2)
–50 to 50 (2) (6 k at 0°C), 0 to 100 (2) (6 k at 0°C), 50 to 150 (2) (30 k at 0°C)
---
Characteristics
Setting accuracy ±2% FS max. Hysteresis Approx. 0.5% FS (fixed) Proportional band 3% FS (fixed) Control period Approx. 20 s Reset range (see note 1) 5 ±1% FS min. Insulation resistance 20 M min. (at 500 VDC) Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts Vibration resistance Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Shock resistance
Life expectancy Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load) Ambient temperature Operating: –10°C to 55°C (with no icing or condensation) Ambient humidity Operating: 45% to 85% Degree of protection Front panel: IEC standard IP40 (see note 2)
Weight Approx. 200 g (with flush-mounting adapter)
Note: 1. No reset function is incorporated by any E5C2 model with ON/OFF control.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions
2
Malfunction: 147 m/s Destruction: 294 m/s
Terminals: IEC standard IP00
, 3 times each in 6 directions
2
, 3 times each in 6 directions
I-8 Analogue Temperature Controller E5C2
Nomenclature
Operation Indicator
Indicator Output
Red Lit ON
Not lit OFF
Dimensions
Temperature setting knob
RESET adjustment shaft No reset function is incorporated by any E5C2 model with ON/OFF control.
Operation indicator
Note: All units are in millimeters unless otherwise indicated.
48 x 48
Dimensions with Flush-mounting Adapter (Accessory), and Back Connecting Socket (Sold Separately)
Panel Cutout
Side-by-side Mounting of N Controllers
Terminal Arrangement (Bottom View)
44.8 x 44.8
Flush-mounting adapter
Panel
Y92F-30 Flush-mounting adapter
Tightening screw
(96) (see note)
P3G-08 Back con­necting socket
Note: 109 mm for US08 Back Connecting Socket
Controller
Temperature
60 min.
N23 456
+1
+1
+1
+1
L
93
141
189
0
0
0
237
+1
285
0
0
Note: 1. Recommended panel thickness is 1 to 4 mm.
2. Close side-by-side mounting is possible (in a single direction).
Analogue Temperature Controller E5C2 I-9
Accessories (Order Separately)
g
P2CF-08 Front Connecting Socket
Eight, M3.5 x 7.5 sems
Terminal Arrangement/ Internal Connections (Top View)
Mounting Holes
Two, 4.5 dia. or Two, M4
70 max.
50 max.
Tw o,
4.5-dia. holes
P3G-08 Back Connecting Socket (for Flush Mounting)
27 dia.
Protective Cover Y92A-48
The protective cover protects the front panel, particularly the setting section, against dust, dirt, and water drip. It also prevents the set val­ues from being altered due to accidental contact with the setting keys.
Note: Can also be
mounted to a DIN track.
20 max.
Note: A finger-protection model (P2CF-08-E) is also available.
Terminal Arrangement/ Internal Connections (Bottom View)
Note: A Protective Cover for fin
Appearance
Model Y92A-48B
er protection (Y92A-48G) is also available.
Installation
Connections
Input
Connect a thermocouple, the E52-THE@ Thermistor or platinum resistance thermometer to the E5C2 as shown in the following illus­tration.
Platinum resistance thermometer input
Thermocouple input
Thermistor input
Relay output
Power supply 100/110, 200/220, 110/120, 220/240 VAC 50/60 Hz
Output
If the load circuit is a heating control system, be sure to connect the load to terminals 4 and 5. If the load circuit is a cooling control sys­tem, be sure to connect the load to terminals 4 and 6. If the heating control system is connected to terminals 4 and 6 or the cooling con­trol system is connected to terminals 4 and 5, the temperature of the heating control system or cooling control system will be abnormal and a serious accident may result.
If the E5C2 is in frequent operation, such as proportional operation, add an appropriate external relay to the E5C2 by considering the capacity of the load and the life of the relay.
Power Supply
If a single power supply is used for the E5C2 and the load, the supply voltage of the power supply may vary greatly when the load is open or closed if the capacity of the power supply is not large enough. Make sure that the capacity of the power supply is large enough so that the supply voltage range will be always from 90% to 110% of the rated supply voltage.
The E5C2 operates at either 50 or 60 Hz.
I-10 Analogue Temperature Controller E5C2
Precautions
Mounting
Track Mounting (E5C2 with P2CF-08)
When mounting two or more E5C2 models with track-mounting sock­ets, leave a space of approximately 20 mm on both sides of the sock­ets where hooks are located.
Hook
Duct
P2CF-08
Panel
20
Flush Mounting
Insert E5C2 into the square hole of the panel and insert an adapter from the back so that there will be no space between E5C2 and the panel. Then, secure the E5C2 with a screw.
Tightening screw
The P3G-08 can be wired in the same way as the P2CF-08.
Dismounting
If flush mounted, loosen the screw of the adapter and disengage the hooks for dismounting.
Controller
Temperature
Temperature Setting
Do not turn the temperature setting knob of the E5C2 with excessive force, otherwise the stopper of the knob may break.
Others
Do not remove the housing of the E5C2, otherwise the housing may break.
To clean the surface of the E5C2, use a soft cloth wet with neutral detergent or alcohol. Do not use any organic solvent, such as paint thinner or benzine, strong acid or strong alkali to clean the surface of the E5C2, otherwise the surface of the E5C2 will become damaged.
Analogue Temperature Controller E5C2 I-11
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. H081-E1-02
In the interest of product improvement, specifications are subject to change without notice.
I-12 Analogue Temperature Controller E5C2