Omron E5C2 specifications

Analogue Temperature Controller
E5C2
DIN-sized (48 x 48 mm) Temperature Controller with Analog Setting
• Compact, low-cost Temperature Controller.
• Consecutive mounting possible using mounting adapter.
• Incorporates a plug-in socket, thus allows to DIN-track and flush mounting.
Model Number Structure
Model Number Legend
E5C2- @ @ @ @
12345
1. Model name
2. Control output
R: Relay Q: Voltage
3. Control method
20: ON-OFF control 40: P control
®
4. Input type
K: K-type thermocouple L: J-type thermocouple P: Platinum resistance thermometer (PT100) G: Thermistor (THE)
5. Special type
Blank: Standard type D, DIN: Special types
Ordering Information
Temperature Controllers
Setting method
Analog setting No indication ON/OFF Relay E5C2-R20K
Note: When placing an order, specify the standard temperature range and supply voltage in addition to the model number.
(e.g., E5C2-R20K 0
Accessories (Order Separately)
Front Connecting Socket P2CF-08 Back Connecting Socket (for flush mounting) P3G-08 Front Connecting Socket with Finger Protection P2CF-08-E Protective Cover (for finger protection) Y92A-48G
Indication
method
Control mode Output Model
P Relay E5C2-R40K
°C to 200°C 100/110 VAC)
Name Model
Thermocouple Platinum resistance
K (CA)
Chromel vs.
alumel
L (IC)
Iron vs.
constantan
E5C2-R20L-D E5C2-R40L-D
thermometer
E5C2-R20P-D E5C2-R20G E5C2-R40P-D ---
Pt100
Thermistor
THE
Controller
Temperature
Analogue Temperature Controller E5C2 I-7
Specifications
Ratings
Supply voltage 100/110/120 VAC (common), 200/220/240 VAC (common) (See note.)
Operating voltage range 90% to 110% of rated supply voltage Power consumption Approx. 2 VA Input Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor Control mode ON/OFF or P control Setting method Analog setting Indication method No indication Control output Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
Note: Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.
50/60 Hz (common)
Input Ranges
Input Thermocouple Platinum resistance
K (CA)
Chromel vs. alumel
Range °C 0 to 200 (5),
°F 32 to 392 (10),
Note: 1. Values in ( ) are the minimum unit.
2. Values in ( ) are the thermistor resistive value.
0 to 300 (10), 0 to 400 (10), 0 to 600 (20), 0 to 800 (20), 0 to 1,000 (25), 0 to 1,200 (25)
32 to 572 (20), 32 to 752 (20), 32 to 1,112 (40), 32 to 1,472 (50), 32 to 1,832 (50), 32 to 2,192 (50)
L (IC)
Iron vs. constantan
0 to 200 (5), 0 to 300 (10), 0 to 400 (10)
32 to 392 (10), 32 to 572 (20), 32 to 752 (20)
thermometer
Pt100 THE
–50 to 50 (2), –20 to 80 (2), 0 to 50 (1), 0 to 100 (2), 0 to 200 (5), 0 to 300 (10), 0 to 400 (10)
32 to 212 (5), 32 to 392 (10)
Thermistor (see note 2)
–50 to 50 (2) (6 k at 0°C), 0 to 100 (2) (6 k at 0°C), 50 to 150 (2) (30 k at 0°C)
---
Characteristics
Setting accuracy ±2% FS max. Hysteresis Approx. 0.5% FS (fixed) Proportional band 3% FS (fixed) Control period Approx. 20 s Reset range (see note 1) 5 ±1% FS min. Insulation resistance 20 M min. (at 500 VDC) Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts Vibration resistance Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Shock resistance
Life expectancy Electrical: 100,000 operations min. (3 A at 110 VAC, resistive load) Ambient temperature Operating: –10°C to 55°C (with no icing or condensation) Ambient humidity Operating: 45% to 85% Degree of protection Front panel: IEC standard IP40 (see note 2)
Weight Approx. 200 g (with flush-mounting adapter)
Note: 1. No reset function is incorporated by any E5C2 model with ON/OFF control.
2. The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions
2
Malfunction: 147 m/s Destruction: 294 m/s
Terminals: IEC standard IP00
, 3 times each in 6 directions
2
, 3 times each in 6 directions
I-8 Analogue Temperature Controller E5C2