OMRON E5AN User Guide

OMRON Corporation
Phone: 01943 602001 Fax: 01943 816796
n
Industrial Automation Company
E5AN Temperature Controller
Temperature Controller
User's Manual
Cat. No. H112-E1-02A
Cat. No. H112-E1-02A
Authorized Distributor:
PO Box 1 Ilkley West Yorkshire LS29 8EU
Phone: 01943 602001 Fax: 01943 816796
Website: www.issltd.co.uk Email: sales@issltd.co.uk
i
nstrumentation
Systems & Services
Note: Specifications subject to change without notice.
Ltd
Printed in Japan
0703-0.3M (1099) (B)
User's Manual
i
Tel: (01943) 602001- WWW.ISSLTD.CO.UK - Fax: (01943) 816796
i
Preface
The temperature controller E5AN allows the user to carry out the following:
Select from many types of temperature, nonĆcontact temperature sensor and analog input
Select heating and cooling control in addition to standard control
Select AT (autoĆtuning) and ST (selfĆtuning) as tuning functions
Use multiĆSP and the run/stop function according to event input (for units equipped
with the event input function)
Use the HBA (heater burnout alarm) function (for units equipped with the heater burnout alarm function)
Use the communications function (for units equipped with the communications function)
Calibrate sensor input
The E5AN features a watertight construction (NEMA4X : equivalent to IP66).
The E5AN conforms to UL/CSA/IEC safety standards and EMC standards.
* This User's Manual describes how to use the E5AN.
Before using your E5AN, thoroughly read and understand this manual in order to ensure correct use. Also, store this manual in a safe place so that it can be retrieved whenever necessary.
* For an additional description of the communications function, also refer to the
E5AN/EN/CN/GN Temperature Controller, Communications Function User's Manuals (Cat. No. H102).
E OMRON, 1999
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Neverthe­less, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Moreover, because
I
PRECAUTIONS
When the product is used under the circumstances or environment described in this manual, always adhere to the limitations of the rating and functions. Also, for safety, take countermeasures such as fitting fail safe installations.
DO NOT USE :
In circumstances or environments that have not been described below in this manual.
For control in nuclear power, railway, aircraft, vehicle, incinerator, medical, entertainment,
or safety applications.
Where death or serious property damage may occur, or where extensive safety precautions are required.
II
SAFETY PRECAUTIONS
JSafety Signal Words
This manual uses the following signal words to mark safety precautions for the E5AN. These precautions provide important information for the safe application of the product. You must be sure to follow the instructions provided in all safety precautions.
Indicates information that, if not heeded, could possibly result in loss of life or
WARNING
CAUTION
JSafety Precautions
serious injury.
Indicates information that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.
CAUTION
F Electric Shock Warning
Do not touch the terminals while the power is ON. Doing so may cause an electric shock.
Do not allow metal fragments or lead wire scraps to fall inside this product. These may cause electric shock, fire or malfunction.
Never disassemble, repair or modify the product. Doing so may cause electric shock, fire or malfunction.
Do not operate this product in flammable and explosive gas atmospheres.
The life expectancy of the output relays varies greatly with the switching capacity and other switching conditions. Always use the output relays within their rated load and electrical life expectancy. If an outĆ put relay is used beyond its life expectancy, its contacts may become fused or burned.
Use this product within the rated load. Not doing so may cause damage or fire.
Use this product within the rated supply voltage. Not doing so may cause damage or fire.
Tighten the terminal screws to a torque of 0.74 to 0.90 Nm Loose screws may cause malfunction.
Set all settings according to the control target of the product. If the settings are not appropriate for the control target, the product may operate in an unexpected manĆ ner, resulting in damage to the product or resulting in accidents.
To maintain safety in the event of a product malfunction, always take appropriate safety measures, such as installing an alarm on a separate line to prevent excessive temperature rise. If a malfunction prevents proper control, a major accident may result.
III
NOTICE
Be sure to observe these precautions to ensure safe use.
(1) Do not wire unused terminals. (2) Be sure to wire properly with correct polarity of terminals. (3) To reduce induction noise, separate the highĆvoltage or largeĆcurrent power lines from other lines,
and avoid parallel or common wiring with the power lines when you are wiring to the terminals. We recommend using separating pipes, ducts, or shielded lines.
(4) Do not use this product in the following places:
Places subject to dust or corrosive gases (in particular, sulfide gas and ammonia gas)
Places subject to high humidity, condensation or freezing
Places subject to direct sunlight
Places subject to vibration and large shocks
Places subject to splashing liquid or oily atmosphere
Places directly subject to heat radiated from heating equipment
Places subject to intense temperature changes
(5) To allow heat to escape, do not block the area around the product. (Ensure that enough space is
left for the heat to escape.)
Do not block the ventilation holes on the casing.
(6) When you draw out or draw in the internal mechanism or the terminal unit from the housing,
never touch electrical components inside or subject the internal mechanism to shock. (7) Cleaning: Do not use paint thinner or the equivalent. Use standard grade alcohol to clean the product. (8) Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. (9) Allow as much space as possible between the E5AN and devices that generate powerful highĆfreĆ
quency noise (e.g. highĆfrequency welders, highĆfrequency sewing machines) or surges. (10) When executing selfĆtuning, turn the load (e.g. heater) ON simultaneously or before you turn the
the main unit ON. If you turn the the main unit ON before turning the load ON, correct selfĆtuning
results and optimum control may no longer be obtained. (11) Use a 100 to 240 VAC (50/60 Hz), 24 VAC (50/60 Hz) or 24 VDC power supply matched to the power
specifications of the E5AN. Also, make sure that rated voltage is attained within two seconds of
turning the power ON. (12) Attach a surge suppressor or noise filter to peripheral devices that generate noise (in particular,
motors, transformers, solenoids, magnetic coils or other equipment that have an inductance comĆ
ponent). (13) When mounting a noise filter on the power supply, be sure to first check the filter's voltage and
current capacity, and then mount the filter as close as possible to the E5AN. (14) Use within the following temperature and humidity ranges:
Temperature: Ć10 to 55_C, Humidity: 25 to 85% (with no icing or condensation)
If the E5AN is installed inside a control board, the ambient temperature must be kept to under 55_C, including the temperature around the E5AN. If the E5AN is subjected to heat radiation, use a fan to cool the surface of the E5AN to under 55_C.
(15) Store within the following temperature and humidity ranges:
Temperature: Ć25 to 65_C, Humidity: 25 to 85% (with no icing or condensation)
(16) Never place heavy objects on, or apply pressure to the E5AN as it may cause it to deform and deteriĆ
orate during use or storage. (17) Avoid using the E5AN in places near a radio, television set, or wireless installation. These devices
can cause radio disturbances which adversely affect the performance of the E5AN. (18) Allow at least 30 minutes for the E5AN to warm up. (19) Locate a switch or circuit breaker and clearly indicate its position so that the operator can immediĆ
ately turn the E5AN OFF.
IV
Conventions Used in This Manual
JMeanings of Abbreviations
The following abbreviations are used in parameter names, figures and in text explanations. These abbreviations mean the following:
Symbol
PV Process value
SP Set point
SV Set value
AT AutoĆtuning
ST SelfĆtuning
EU Engineering unit *1
*1 EU" stands for Engineering Unit. EU is used as the minimum unit for engineering units
such as _C, m, and g. The size of EU varies according to the input type. For example, when the input temperature setting range is -200 to +1300_C, 1 EU is 1_C, and when the input temperature setting range is -20.0 to +500.0_C, 1 EU is 0.1_C. In the case of analog input, the size of EU varies according to the decimal point position of the scaling setting, and 1 EU becomes the minimum scaling unit.
Term
JHow to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays and alphabet characters.
ABCDEFGHI JKLM
NOPQRSTUVWXYZ
V
JHow This Manual is Organized
Purpose Related title Description
D Learning about the
E5AN
Chapter 1 INTRODUCTION This chapter describes the
features, names of parts and typical functions.
D Setting up the E5 A N
D Basic operations
D Applied operations
D Calibration
D Appendix
Chapter 2 PREPARATIONS This chapter describes instalĆ
lation and wiring.
Chapter 3 BASIC OPERATION and Chapter 5 PARAMETERS
Chapter 4 APPLIED OPERATION and Chapter 5 PARAMETERS
Chapter 6 CALIBRATION This chapter describes calĆ
These chapters describe basic control examples.
These chapters describe advanced functions to fully use E5AN.
ibration method.
This chapter describes the unit specifications. There is also a parameter operations list to be used as a backup guide to the parameter setĆ tings.
VI
Table of Contents
Preface I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Precautions II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions III. . . . . . . . . . . . . . . . . . . . . . . . . . .
Notice IV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conventions Used in This Manual V. . . . . . . . . . . . . .
CHAPTER 1 INTRODUCTION 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Names of Parts 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Front panel 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to use keys 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 I/O Configuration and Main Functions 1-4. . . . . . . . . . . . . . . . . . . . . .
I/O configuration 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main functions 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 How Setup Levels Are Configured and Operating
the Keys on the Front Panel 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting parameters 1-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fixing settings 1-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Communications Function 1-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 2 PREPARATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Installation 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Panel cutout 2-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up the option units 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Draw out 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Wiring Terminals 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminal arrangement 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Precautions when wiring 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Requests at Installation 2-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
To ensure prolonged use 2-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
To reduce the influence of noise 2-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
To ensure high–precision measurement 2-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About waterproofing 2-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 3 BASIC OPERATION 3-1. . . . . . . . . . . . . . . . . . . . . . . .
3.1 Initial Setup Examples 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Setting the Input Type 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input type 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Selecting _C/_F 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature unit 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Selecting PID Control or ON/OFF Control 3-6. . . . . . . . . . . . . . . . . . .
3.5 Setting Output Specifications 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control period 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Direct/reverse operation 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 Setting the SP 3-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the SP 3-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7 Executing ON/OFF Control 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ON/OFF Control 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 Determining PID Constants (AT, ST, manual setup) 3-12. . . . . . . . . . .
AT.(auto-tuning) 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ST (self-tuning) 3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ST start conditions 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ST stable range 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual setup 3-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.9 Alarm Outputs 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm type 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm value 3-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.10 Heater Burnout Alarm (HBA) 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HBA detection 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating conditions 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup 3-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to calculate detection current values 3-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 3-21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.11 Requests during Operation 3-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 4 APPLIED OPERATION 4-1. . . . . . . . . . . . . . . . . . . . . .
4.1 Shifting Input Values 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shifting input 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to calculate input shift values (2-point shift) 4-3. . . . . . . . . . . . . . . . . . . . . . . . .
1-point shift method 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-point shift method 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example of 2-point temperature input shift 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Alarm Hysteresis 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standby sequence 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm latch 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Close in alarm/open in alarm 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Setting Scaling Upper and Lower Limits (analog input) 4-8. . . . . . . .
Analog input 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Executing Heating and Cooling Control 4-10. . . . . . . . . . . . . . . . . . . . .
Heating and cooling control 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 To Use Event Input 4-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting event input 4-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to use multi-SP 4-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting by key operation 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Executing run/stop control 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6 Setting the SP Upper and Lower Limit Values 4-15. . . . . . . . . . . . . . .
Set point limitter 4-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup 4-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7 Executing the SP Ramp Function
(limiting the SP change rate) 4-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SP ramp 4-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8 To Move to the Advanced Function Setting Level 4-19. . . . . . . . . . . .
4.9 Using the Key Protect Level 4-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Key protect 4-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 5 PARAMETERS 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conventions Used in this Chapter 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Meanings of icons used in this chapter 5-2. . . . . . . . . . . . . . . . . . . . . . . . . .
About parameter display 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Order in Which Parameters Are
Described in This Chapter 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protect Level 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation Level 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment Level 5-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Setting Level 5-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Advanced Function Setting Level 5-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communications Setting Level 5-43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 6 CALIBRATION 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Parameter Structure 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 User Calibration 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Calibrating Thermocouples 6-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Calibrating Analog Input 6-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Calibrating Platinum Resistance Thermometers 6-8. . . . . . . . . . . . .
6.6 Checking Indication Accuracy 6-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
APPENDIX A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SPECIFICATIONS A-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ratings A-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Characteristics A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CURRENT TRANSFORMER (CT) A-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ERROR DISPLAY A-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PARAMETER OPERATIONS LIST A-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation level A-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment level A-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Setting Level A-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Advanced function setting level A-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protect level A-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communications Setting Level A-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SENSOR INPUT SETTING AND INDICATION RANGES A-11. . . . . . . . . .
SETUP LEVELS DIAGRAM A-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PARAMETER FLOW A-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INDEX
CHAPTER1
CHAPTER 1
INTRODUCTION
CHAPTER 1 INTRODUCTION
1.1 Names of Parts 1Ć2. . . . . . . . . . . . . . . . . . . . . . . .
Front panel 1Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Display 1Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to use keys 1Ć3. . . . . . . . . . . . . . . . . . . . . . .
1.2 I/O Configuration and Main Functions 1Ć4. . .
I/O configuration 1Ć4. . . . . . . . . . . . . . . . . . . . . . .
Main functions 1Ć5. . . . . . . . . . . . . . . . . . . . . . . .
1.3 How Setup Levels Are Configured and Operating the Keys on the Front Panel 1Ć6. . .
Selecting parameters 1Ć8. . . . . . . . . . . . . . . . . . .
Fixing settings 1Ć8. . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Communications Function 1Ć9. . . . . . . . . . . . . .
1–1
CHAPTER 1 30P AAAAAAA
1.1 Names of Parts
JFront panel
Operation indicators
Temperature unit
No.1 display
JDisplay
F No.1 display
F No.2 display
F Operation
indicators
No.2 display
Level key
Up keyDown keyMode key
Displays the process value or parameter type. ăLights for approximately one second during startup.
Displays the set point, parameter operation read value or the manipulated variable. ăLights for approximately one second during startup.
(1) ALM1 (alarm 1)
Lights when alarm 1 is ON. ALM2 (alarm 2) Lights when alarm 2 is ON. ALM3 (alarm 3) Lights when alarm 3 is ON.
(2) HB (heater burnout alarm display)
Lights when a heater burnout is detected.
(3) OUT1, OUT2 (control output 1, control output 2)
Lights when control output 1 and/or control output 2 are ON. HowĆ ever, whenever control output 1 is the current output, OUT1 stays off.
(4) STOP (stop)
Lights when operation is stopped. During operation, this indicator lights when an event or the run/stop function is stopped.
(5) CMW (communications writing control)
Lights when communications writing is enabled" and is out when it is disabled."
1–2
F Temperature unit
The temperature unit is displayed when the display unit parameter is set
to a temperature. Indication is determined by the currently selected temĆ
perature unit" parameter set value. When this parameter is set to _C",
 " is displayed, and when set to _F",  " is displayed.
Flashes during ST operation.
JHow to use keys
F (level) key
F (mode) key
F (up) key
F (down) key
F + key
combination
The following describes the basic functions of the front panel keys.
Press this key to select the setting levels. The setting level is selected in
order operation level" ←→ adjustment level", initial setting level" ←→
communications setting level".
Press this key to select parameters within each level.
Each press of this key increases values displayed on the No.2 display. HoldĆ
ing down this key speeds up the incrementation.
Each press of this key decreases values displayed on the No.2 display. HoldĆ
ing down this key speeds up the decrementation.
This key combination sets the E5AN to the protect level." For details on
the protect level, see Chapter 5 Parameters.
1–3
1.2 I/O Configuration and Main Functions
JI/O configuration
OUT1
Temperature input/ analog input
HBA
CT input
Event input 2ch
SP input from external digital switch function and Run/Stop function
Controller
Control output 1
Control output 2
Heating and cooling
Standard
Alarm 3
Alarm 2
Alarm 1
Input error
Communications function
HBA
OUT2
ALM3
ALM2
ALM1
HB
Control output 1
Alarm output 3
Alarm output 2
Alarm output 1
1–4
JMain functions
The following introduces the main functions of the E5AN. For details on
each function and how to use the functions, see Chapter 3 onwards.
F Input sensor
types
F Control output
F Alarms
ĂThe following input sensors can be connected for temperature input:
Thermocouple : K, J, T, E, L, U, N, R, S, B NonĆcontact temperature sensor type : ES1A
: KĂ(10 to 70_C), KĂ(60 to 120_C), KĂ(115 to 165_C), ăK (160 to 260_C)
Platinum resistance thermometer
: Pt100, JPt100
Analog input : 0 to 50 mV
ĂControl output is either relay, voltage or current output depending on
the model of E5AN.
ĂIf heating and control output 2 control is selected on the E5ANĆj3jjj,
alarm 3 output is used as control output 2 side output. Therefore, use alarm 1, 2 if an alarm is needed in heating and cooling control.
ĂSet the alarm type and alarm value, or upperĆ and lowerĆlimit alarms.
ĂIf necessary, a more comprehensive alarm function can be achieved by
setting the standby sequence", alarm hysteresis" and close in alarm/ open in alarm" alarm latch ON/OFF parameters.
ĂWhen the input error output is set to ON", alarm output 1 turns ON
when an input error occurs.
F Control
adjustment
F Event input
F HBA
F Communications
function
ĂOptimum PID constants can be set easily by AT (autoĆtuning) and ST
(selfĆtuning).
ĂWhen equipped with the option event input unit E53ĆAKB, the following
functions can be achieved by event input: Set point selection (multiĆSP max. 4 points) and run/stop
ĂThe heater burnout alarm (HBA) function is supported.
1
ĂCommunications according to CompoWay/F*
ported when the option communications unit E53ĆAK01, or E53ĆAK03 is mounted in the E5AN. Communications are carried out over the RSĆ485 interface.
*1ăCompoWay/F is a generalĆpurpose serial communicationsĆbased uniĆ
fied communications procedure developed by OMRON. CompoWay/F uses
commands compliant with the wellĆestablished FINS, together with a uniĆ
fied frame format on OMRON programmable controllers to facilitate
communications between personal computers and components.
*2ăSysway communication does not support alarm 3 output.
and Sysway*2 are supĆ
1–5
1.3 How Setup Levels Are Configured and Operating the Keys on the Front Panel
Parameters are divided into groups, each called a level". Each of the set values (setup items) in these levels are called a parameter." The parameĆ ters on the E5AN are divided into the following seven levels:
Power ON
Operation level Adjustment level
key
Less than 1 second
+ key
+ key
The PV display flashes.
key
1 second min.
Initial setting level
key
1 second min.
Advanced function setting level
key
3 seconds min.
Password input set value “–169”
Password input set value “1201”
Calibration level
key
Less than 1 second
key
The PV display flashes after one second.
Control stops.
Communica- tions setting level
* The key pressing time can
be changed in ”protect level move time” (advanced function level).
Control in
Progress
+ key 3 seconds min.
Protect level
Control in progress Control stopped
Control Stopped
Protect level f - Operation level f - Adjustment level f - Initial setting level - f Advanced function setting level - f
*
Calibration level - f Communications setting level - f
* : To activate the advanced function setting level, set the Protect level"
of the Initial/Communications protect" to 0".
f : Indicates items that can be set.
1–6
Of these levels, the initial setting level, communications setting level, advanced function setting level and calibration level can be used only when control has stopped. Note that controller outputs are stopped when any of these four levels are selected.
F Protect level
ĂTo move the mode at this level, simultaneously press the and
keys for at least three seconds. This level is for preventing unwanted or accidental modification of parameters. Protected levels will not be disĆ played, and so the parameters in that level cannot be modified.
Ă* The key pressing time can be changed in "protect level move time"
(advanced function level).
F Operation level
F Adjustment level
F Initial setting
level
ĂThis level is displayed when turning the power ON. It can be moved to
the protect level, initial setting level and adjustment level from this level.
ĂNormally, select this level during operation. During operation, the proĆ
cess value and manipulated variable can be monitored, and the set point, alarm value and upperĆ and lowerĆlimit alarms can be monitored and modified.
ĂTo move the mode at this level, press the key for less than one
second.
ĂThis level is for entering set values and offset values for control. This
level contains parameters for setting the AT (autoĆtuning), communicaĆ tions writing enable/disable, hysteresis, multiĆSP, input shift values, heater burnout alarm (HBA) and PID constants. It can be moved to the top parameter of the initial setting level, protect level and operation level from here.
ĂTo move the mode at this level, press the
seconds in the operation level or adjustment level. The PV display flashes after one second. This level is for specifying the input type, selectĆ ing the control method, control period, setting direct/reverse action and alarm type. It can be moved to the advanced function setting level or communications setting level from this level. To return to the operation level, press the key for at least one second. To move to the commuĆ nications setup level, press the key for less than one second.
key for at least three
F Advanced
function setting level
F Communications
setting level
ĂTo activate the advanced function setting level, after setting the ProĆ
tect level" of the Initial/Communications protect" to 0", input the
password (-169") in the initial setting level. ĂIt can be moved to the calibration level or initial level from this level. ĂThis level is for setting the automatic return of display mode, MV limitĆ
ter, event input assignment, standby sequence, alarm hysteresis, ST
(selfĆtuning) and for moving to the user calibration level.
ĂTo move the mode at this level, press the key for less than one second
in the initial setting level. When the communications function is used,
set the communications conditions in this level. Communicating with a
personal computer (host computer) allows set points to be read and writĆ
ten, and manipulated variables to be monitored.
1–7
F Calibration level
ĂTo move the mode at this level, enter the password 1201" in the
advanced function setting level. This level is for offsetting deviation in
the input circuit. ĂIt can not be moved to other levels by operating the keys on the front
panel from the calibration level. To cancel this level, turn the power OFF
then back ON again.
JSelecting
parameters
JFixing settings
ĂTo select parameters in each level, press the key. Each press of the
key advances to the next parameter. For details on each parameter,
see Chapter 5.
Parameter
1
Parameter
2
Parameter
3
Parameter
n
ĂIf the key is pressed at the final parameter, the display returns to the
top parameter for the current level.
ĂTo change parameter settings or setup, specify the setting using the
or keys, and either leave the setting for at least two seconds or press
the key. This fixes the setting.
ĂWhen another level is selected, the parameter and setting on the display
are fixed.
ĂWhen the power is turned OFF, fix first the settings or parameter setup
(by pressing the
times not changed by merely pressing the
key). The settings and parameter setup are someĆ
or keys.
1–8
1.4 Communications Function
The E5AN can be provided with a communications function that allows you
to check and set controller parameters on a host computer. If the communicaĆ
tions function is required, mount the option unit E53ĆAK01 or E53ĆAK03 in
the E5AN. For details on the communications function, see the separate
Communications Functions User's Manual."
Follow the procedure below to move to the communications setting level.
(1) Press the
key for at least three seconds in the operation level".
The level moves to the initial setting level".
(2) Press the
key for less than one second. The initial setting level"
moves to the communications setting level".
(3) Pressing the
key advances the parameters as shown in the followĆ
ing figure.
(4) Press the
or keys to change the parameter setups.
Communications unit No.
Baud rate
Data bit
Stop bit
Parity
F Setting up
communications data
Set the E5AN communications specifications so that they match the comĆ munications setup of the host computer. In a multidrop 1:N configuration, match the setting data except the communications unit No. on all units. Unique communications unit Nos. must be set to each unit.
Parameter
Communications unit No. 0 to 99 1 None Baud rate 1.2, 2.4, 4.8, 9.6, 19.2 Data bit 7, 8 7 bit Stop bit 1, 2 2 bit Parity None, even, odd
Displayed
Characters
Set (monitor) Value Settings Default Unit
.... .,,,,
,,
9.6 kbps
Even None
1–9
1–10
CHAPTER2
CHAPTER 2
PREPARATIONS
CHAPTER 2 PREPARATIONS
2.1 Installation 2Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions 2Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Panel cutout 2Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up the option units 2-3. . . . . . . . . . . . . .
Mounting 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Draw out 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Wiring Terminals 2-6. . . . . . . . . . . . . . . . . . . . . .
Terminal arrangement 2-6. . . . . . . . . . . . . . . . .
Precautions when wiring 2-6. . . . . . . . . . . . . . .
Wiring 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Requests at Installation 2-10. . . . . . . . . . . . . . . .
To ensure prolonged use 2-10. . . . . . . . . . . . . . . .
To reduce the influence of noise 2-10. . . . . . . . .
To ensure high-precision measurement 2-10. .
About waterproofing 2-11. . . . . . . . . . . . . . . . . . .
2–1
2.1 Installation
JDimensions
(Unit: mm)
96
JPanel cutout
(Unit: mm)
92
+0.8 –
0
11.5
84.5 78
(96number of units -3.5)
+1.0
0
91
120 min.
0–
+0.8
92
+0.8
92
0–
ĂSeveral units cannot be group mounted close together vertically.
(Observe the recommended mounting space limits.)
ĂWhen group mounting several controllers, ensure that the surrounding
temperature does not exceed the allowable operating temperature listed in the specifications.
ĂThe recommended panel thickness is 1 to 8 mm.
ĂTo ensure waterproofing, enclose the unit in the waterproof packing
prior to mounting. Waterproofing is not possible when group mounting several units.
2–2
JSetting up the option units
C
If communications, event input and heater burnout functions are required, mount the communications unit (E53ĆAK01 or AK03) or the event input unit (E53ĆAKB). The heater burnout function is supported on either of these two option units.
F Option units
Name Model Function
F Assembling the unit
ommunications unit
Event input unit E53-AKB Event input
E53-AK01 Communications (RS-232C) E53-AK03 Communications (RS-485)
ĂTerminal label:x 1
(1)
(4)
(2)
(1)
Regular flat blade screwdriver (units: mm)
(3)
20 min.
(1) Insert the tools (see drawing above) into the slots (one on the top and
one on the bottom) and release the hooks.
(2) Insert the tool into the gap between the front and rear, and slightly
draw out the front panel. Then, draw out the front panel towards you holding it by its top and bottom sides.
(3) Match the upper and lower claws with the connection points and
insert the option unit. Mount the option unit in the center.
(4) Before you push the unit back into the case, make sure that the waterĆ
tight packing is in place. Push the unit back into the rear case until you hear a click. When you do this, hold down the hooks on the top and bottom of the rear case so that they are firmly hooked in place.
2–3
CHAPTER 2 PREPARATIONS
JMounting
Terminal cover
Adaptor
F How to attach the
E5AN on the panel
F How to attach the
terminal cover
(1) Insert the main unit through the mounting hole in the panel (1Ć8 mm
thickness). Pull the adapter along the body of the main unit from rear
case up to the panel and fasten temporarily.
(2) Tighten the upper and lower screws alternately with only one turn of
the screwdriver at a time to maintain an even torque balance.
Fit terminal cover E53-COV11 onto the upper and lower hooks.
Attach the terminal cover so that the OMRON mark of terminal Nos.1 to
10 faces down and the OMRON mark of terminal Nos.11 to 18 faces up. If
the cover is attached the other way round, the fixture can no longer be atĆ
tached.
2–4
2.1Installation
JDraw out
The main unit can be drawn out to perform maintenance without removĆ
ing the terminal compartment.
(1)
(2)
(3)
Prepare a screwdriver that can be used on the lower front screw of the unit.
(1) Loosen the lower front screw with a screwdriver (turning left) while
pushing the hook on the upper surface of the front panel.
(2) Grasp both sides of the front panel and draw (pull) it out.
(3) Ensure that the waterproof packing is in place before drawing in the
unit. ReĆtighten the lower front screw with a screwdriver (turning
right) to a torque of 0.3 to 0.5 Nm while pushing the hook on the
upper surface of the front panel.
2–5
CHAPTER 2 PREPARATIONS
2.2 Wiring Terminals
JTerminal
arrangement
AC100V to 240V AC/DC 24V (No polarity)
Relay output AC250V 5A (Resistive load)
Voltage output/ DC12V 40mA Current output
Alarm output AC250V 3A (Resistive load)
ALM1/Heater burnout/Input error
Input power
OUT1
ALM3/OUT2
ALM2
JPrecautions
when wiring
Event input
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17 18
EV2
CT
TC Pt
EV1
A B
B
+ + –
Analog input
RS-232C RS-485
SD
11
EV1 EV2
RD
12
SG
13
ĂSeparate input leads and power lines in order to protect the E5AN and
its lines from external noise.
ĂUse AWG28 or larger twisted pair cable.
AWG28 or larger Conductor cross-section
0.08042mm
2
or larger
B (+)
11
A (–)
12
Do not
13
use
JWiring
F Power supply
ĂIt's recommended to use solderless terminals when wiring the E5AN. ĂTighten the terminal screws using a torque no greater than 0.74 to 0.90
Nm.
ĂUse the following type of solderless terminals for M3.5 screws.
7.2 mm max.
7.2 mm max.
ĂConnect to terminal Nos. 1 to 2. The following table shows the specificaĆ
tions.
Input power supply E5AN
100 to 240 VAC, 50/60 Hz 9VA 24 VAC, 50/60 Hz 5VA 24 VDC (no polarity) 4W
ĂStandard insulation is applied to the power supply I/O sections. If reinĆ
forced insulation is required, connect the input and output terminals to a device without any exposed currentĆcarrying parts or to a device with standard insulation suitable for the maximum operating voltage of the power supply I/O section.
2–6
2.2Wiring Terminals
(with short-ci
it
F Input
F Control output 1
ĂConnect to terminal Nos.16 to 18 as follows according to the input type.
-
+
16 17
18
thermometer
16 17
18
Thermocouple Platinum resistance
16 17
18
Analog input
-
v
+
ĂTerminal Nos. 3 to 4 are for control output. The following diagrams
show the available outputs and their internal equalizing circuits.
Current
+V
+
3
L
4
+V
+
3
4
GND
3
L
4
VoltageRelay
+ –
GND
ĂThe following table shows the specifications for each output type.
Output type Specifications
Relay 250 VAC, 5A (resistive load) electrical life : 100,000 operations
Voltage (PNP)
protection)
Current DC4–20mA load : 600max. resolution : approx. 2600
DC12V "15%FS 21mA max.
rcu
DC12V – 20% 40mA max.
+15%
F Alarm
output/Control output 2
ĂThe voltage output (control output) is not electrically insulated from the
internal circuits. When using a grounding thermocouple, do not connect the control output terminals to the ground. If the control output termiĆ nals are connected to the ground, errors will occur in the measured temĆ perature values as a result of leakage current.
ĂOn the E5ANĆV3VVVĂ,Ăalarm output 1 (ALM1) is between terminal
Nos. 9 and 10, alarm output 2 (ALM2) is between terminal Nos. 7 and 8 and alarm output 3 (ALM3) is between terminal Nos. 5 and 6. When utilizing heating and cooling control, alarm output 2 becomes alarm output 3 and alarm output 3 is not available. When the input error output is set to ON", alarm output 1 turns ON when an input error occurs.
ĂWhen the option unit E53AKĆ01 or E53-AK03 is mounted on the E5AN,
an OR of alarm output 1 and the heater burnout alarm will be output. To disable alarm output 1 and output only the heater burnout alarm on terminals 7 and 8, set the mode of the alarm output 1 to 0.
ĂThe interior equivalent circuits of alarm output 1, 2 and 3 are shown in
the following diagram.
5
ALM3/OUT2
6
7
ALM2
8
9
ALM1/Heater burnout alarm/Input error
10
2–7
CHAPTER 2 PREPARATIONS
ĂRelay specifications are as follows:
SPSTĆNO : 3Aą250VAC
F CT input
F Event input
ĂWhen the option unit E53ĆAKB, E53ĆAK01, or E53ĆAK03 is mounted on
the E5AN and the heater burnout function is used, connect a current transformer (CT) across terminal Nos. 14 and 15.
14
CT
15
ĂWhen the option event input unit E53ĆAKB is mounted on the E5AN
and event input is used, connect to terminal Nos. 11 to 13.
11
12
13
EV1
EV2
ĂUse event inputs under the following conditions:
Contact input ON: 1 kΩ max., OFF: 100 kΩ min. No-contact input ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
F Communications
(RS–232C)
Polarities during noĆcontact input are as follows:
11
+
12
13
+
EV1
EV2
ĂWhen the option communications unit E53ĆAK01 is mounted in the
E5AN for communications, connect the communications cable to termiĆ nal Nos. 11, 12 and 13.
SD
11
RD
12
13
RS-232C
SG
2–8
2.2Wiring Terminals
Communications unit connection diagram
Host computer RS232C : 25P
E5AN
ĂThe RSĆ232C connection is 1:1
ĂThe maximum cable length is 15 m. Use the RSĆ232C optical interface
cable (Z3RN) as an extension cable if necessary.
ĂUse shielded, twisted pair cable (AWG28 min.).
F Communications
(RS–485)
ĂWhen the E53ĆAK03 is mounted in the E5AN for communications, conĆ
nect the communications cable to terminal Nos. 11 and 12. Specify both ends of the transmission path including the host computer as the end node (that is, connect terminators to both ends). The maximum terminal resistance is 54 Ohms.
1112B(+)
RS-485
A(–)
Communications unit connection diagram
Host computer RS-485
+
FG
A<B : “1” mark A>B : “0” space
Shielded cable
E5AN (No.1)
RS-485
No
Abbr.
A (–)12 B (+)11
E5AN (No.31)
RS-485
No
Abbr.
A (–)12 B (+)11
Terminator (120Ω, 1/2 W)
ĂThe RSĆ485 connection can either be 1:1 or 1:N. Up to 32 units including
the host computer can be connected 1:N. Use shielded, twisted pair cable (AWG28 min.) and keep the total cable length to within 500m.
Cable reference diagram
AWG28 min. Conductor area cross-section
2
0.081mm
min.
2–9
CHAPTER 2 PREPARATIONS
2.3 Requests at Installation
JTo ensure
prolonged use
Use the temperature in the following operating environment:
Temperature : -10 to +55°C (icing and condensation not allowed)
Humidity : 25 to 85%
When the temperature controller is incorporated in a control panel, make
sure that the controller's ambient temperature and not the panel's ambiĆ
ent temperature does not exceed 55°C.
The life of electronic equipment such as temperature controllers is inĆ
fluenced not only by the life determined by the relay switching count but
also by the life of the electronic components used internally. The service
life of components is dependent on the ambient temperature: the higher
the ambient temperature becomes, the shorter the service life becomes,
and vice versa. For this reason, the service life of the temperature controlĆ
ler can be extended by lowering its internal temperature.
Gang-mounting two or more temperature controllers, or mounting temperĆ
ature controllers above each other may cause heat to build up inside the temĆ
perature controllers, which will shorten their service life. When mounting
temperature controllers like this, forced cooling measures such as a cooling
fan for cooling the temperature controllers must be taken into consideration.
Prevent only the terminal block from being cooled. Otherwise, this may
result in a measurement error.
JTo reduce the
influence o f noise
JTo ensure
high–precision measurement
To reduce induction noise, the leads on the temperature controller's terĆ
minal block must be wired separately from large-voltage/large-current
power leads. Also, avoid wiring leads in parallel with power leads or in the
same wiring path. Other methods such as separating conduits and wiring
ducts, or using shield wire are also effective.
Attach a surge absorber or noise filter to peripheral equipment that generĆ
ates noise (in particular, motors, transformers, solenoids, or other equipĆ
ment that has a magnetic coil or other inductance component).
When a noise filter is used at the power supply, first check the voltage or
current, and attach the noise filter as close as possible to the temperature
controller.
Also, install the temperature controller as far away as possible from equipĆ
ment that generates strong, high frequency (e.g. high-frequency welders,
high-frequency sewing machines) or surges.
When the thermocouple leads are extended, be sure to use a compensating
lead wire matched to the type of thermocouple.
When the platinum resistance detector leads are extended, use the lead
having the smallest resistance to equalize the resistance of the three leads.
Install the temperature controller so that it is horizontal.
If there is a large error in the measurement values, make sure that input
compensation has been set correctly.
2–10
2.3Requests at Installation
JAbout
waterproofing
The protective structure of this controller conforms to the following stanĆ
dards. Parts that are not indicated as being protected or that are indicated
as IPj0 are not waterproof.
Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IP20
Terminals: IP00
2–11
CHAPTER 2 PREPARATIONS
2–12
CHAPTER3
CHAPTER 3
BASIC OPERATION
CHAPTER 3 BASIC OPERATION
3.1 Initial Setup Examples 3Ć2. . . . . . . . . . . . . . . . .
3.2 Setting the Input Type 3Ć4. . . . . . . . . . . . . . . . .
Input type 3Ć4. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Selecting _C/_F 3Ć5. . . . . . . . . . . . . . . . . . . . . . . .
Temperature unit 3Ć5. . . . . . . . . . . . . . . . . . . . . .
3.4 Selecting PID Control or ON/OFF Control 3Ć6
3.5 Setting Output Specifications 3Ć7. . . . . . . . . . .
Control period 3Ć7. . . . . . . . . . . . . . . . . . . . . . . . .
Direct/reverse operation 3Ć7. . . . . . . . . . . . . . . .
3.6 Setting the SP 3Ć9. . . . . . . . . . . . . . . . . . . . . . . . .
Changing the SP 3Ć9. . . . . . . . . . . . . . . . . . . . . . .
3.7 Executing ON/OFF Control 3Ć10. . . . . . . . . . . . .
ON/OFF Control 3Ć10. . . . . . . . . . . . . . . . . . . . . . .
Setup 3Ć11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 Determining PID Constants
(AT, ST, manual setup) 3Ć12. . . . . . . . . . . . . . . . .
AT.(autoĆtuning) 3Ć12. . . . . . . . . . . . . . . . . . . . . . .
ST (selfĆtuning) 3Ć13. . . . . . . . . . . . . . . . . . . . . . . .
ST start conditions 3Ć14. . . . . . . . . . . . . . . . . . . . .
ST stable range 3Ć14. . . . . . . . . . . . . . . . . . . . . . . .
Manual setup 3Ć15. . . . . . . . . . . . . . . . . . . . . . . . . .
3.9 Alarm Outputs 3Ć17. . . . . . . . . . . . . . . . . . . . . . . . .
Alarm type 3Ć17. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm value 3Ć18. . . . . . . . . . . . . . . . . . . . . . . . . . .
3.10 Heater Burnout Alarm (HBA) 3Ć19. . . . . . . . . . .
HBA detection 3Ć19. . . . . . . . . . . . . . . . . . . . . . . . .
Operating conditions 3Ć19. . . . . . . . . . . . . . . . . . .
Setup 3Ć20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How to calculate detection
current values 3Ć21. . . . . . . . . . . . . . . . . . . . . . . . .
Example 3Ć21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.11 Requests during Operation 3Ć22. . . . . . . . . . . . . .
3–1
3.1 Initial Setup Examples
On previous controllers, sensor input type, alarm type and control period were set by the DIP switches. These hardware settings are now set in paĆ rameters in setup menus. The tween setup menus, and the amount of time that you hold the keys down for determines which setup menu you move to. This section describes two typical examples.
F Typical example 1
Input type :0 K thermocouple -200 to 1300_C Control method :ON/OFF control Alarm type :2 upper limit Alarm value 1 :20_C (deviation) Set point :100_C
Setup procedure
Initial setting level
Set input specifications
Power ON
and keys are used to switch beĆ
Power ON
Operation level
Process value/ set point
Press key for at least three seconds.
Control stops.
Initial setting level
Check input type.
Input type
Set control specifications
Set alarm type
Operation level
Set alarm values
Start operation
Check that control is ON/OFF control.
Check alarm type.
Operation level
Press keys to set set point to “100_C”.
Make sure that control is running.
Press keys to set alarm value to “20_C”.
Press key for at least one second.
Start operation
In ON/OFF control
In PID control
Alarm 1 type
Control starts.
Process value/set point
During run During stop
Alarm value 1
3–2
F Typical example 2
Input type : 4 T thermocouple -200 to 400 _C Control method : PID control Calculate PID constants by AT
(auto-tuning) execution. Alarm type : 2 upper limit Alarm value 1 : 30_ C (deviation) Set point : 150_C
Setup procedure
Power ON
Initial setting level
Set input specifications
Set control specifications
Set alarm type
Adjustment level
AT execution
(when PID control is selected)
Operation level
Set alarm values
PV/SP After AT execution
During AT execution
While AT is being executed, SP will flash After AT execution
During AT execution
Operation level
Initial setting level
Press keys to select input type.
Press keys to select PID control.
Press keys to set ST to OFF.
Check the control period.
Check alarm type.
Operation level
Press keys to set set point to “150_C”.
Adjustment level
Execute AT (auto-tuning).
Operation level
Make sure that set point is “150_C”.
Make sure that control is running.
Power ON
Press key for at least three seconds.
Control stops.
Input type
In ON/OFF control
In PID control
To execute ST To cancel ST
Control period (heat) (unit: se­conds)
Alarm 1 type
Press key for at least one second.
Process value/ set point
Press key for less than 1 second.
To execute AT To cancel AT
Press key for less than 1 second.
Control starts.
Process value/ set point
During run During stop
Process value/ set point
Start operation
Press keys to set alarm value to “30_C”.
Start program execution
Alarm value 1
3–3
CHAPTER 3 BASIC OPERATION
pp
p
ES1A
3.2 Setting the Input Type
The E5AN supports four input types: platinum resistance thermometer, thermocouple, nonĆcontact temperature sensor and analog inputs. Set the input type matched to the sensor used in the input type" parameter. The E5AN specifications support two types of inputs, platinum resistance thermometer input types and thermocouple input type, whose set values differ. Check the type of E5AN at purchase.
JInput type
Operation Procedure
Operation level
Initial setting level
Input type
Setting the input type thermocouple KĆ20.0 to 500.0_C".
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) Press the
using K thermocouple (Ć20.0 to 500.0_C), enter 1" as the set value.
Hint: The set value is fixed if you do not operate the keys on the front panel
for two seconds after changing the parameter, or by pressing the
or keys.
List of Input Types
Input type Name
Platinumresistance thermometerinput type thermometer
Thermocouple input type
Platinum resistance
Input type Name
Thermocouple K 0 -200 to 1300 (_C) / -300 to 2300 (_F)
Non-contact temperature sensor ES1A
Analog input 0 to 50mV 16 For scaling use ranges from -1999 to 9999
key to enter the set value of the desired sensor. When
Set
Value
Pt100 0 -200 to 850 (_C) / -300 to 1500 (_F)
1 -199.9 to 500.0 (_C)/ -199.9 to 900.0 (_F) 2 0.0 to 100.0 (_C) / 0.0 to 210.0 (_F)
JPt100 3 -199.9 to 500.0 (_C)/ -199.9 to 900.0 (_F)
4 0.0 to 100.0 (_C) / 0.0 to 210.0 (_F)
Set
Value
1 -20.0 to 500.0 (_C) / 0.0 to 900.0 (_F)
J 2 -100 to 850 (_C) / -100 to 1500 (_F)
3 -20.0 to 400.0 (_C) / 0.0 to 750.0 (_F)
T 4 -200 to 400 (_C) / -300 to 700 (_F)
17 -199.9 to 400.0 (_C)/ -199.9 to 700.0 (_F) E 5 0 to 600 (_C) / 0 to 1100 (_F) L 6 -100 to 850 (_C) / -100 to 1500 (_F)
U 7 -200 t o 400 (_C) / -300 to 700 (_F)
18 -199.9 to 400.0 (_C)/ -199.9 to 700.0 (_F)
N 8 -200 t o 1300 (_C) / -300 to 2300 (_F) R 9 0 to 1700 (_C) / 0 to 3000 (_F)
S 10 0 to 1700 (_C) / 0 to 3000 (_F) B 11 100 to 1800 (_C) / 300 to 3200 (_F)
10 to 70_C 12 0 to 90 (_C) / 0 to 190 (_F)
60 to 120_C 13 0 to 120 (_C) / 0 to 240 (_F) 115 to 165_C 14 0 to 165 (_C) / 0 to 320 (_F) 160 to 260_C 15 0 to 260 (_C) / 0 to 500 (_F)
Input Temperature Setup Range
Input Temperature Setup Range
or -199.9 to 999.9.
3–4
Shaded ranges indicate default settings.
3.3Selecting _C/_F
3.3 Selecting _C/_F
JTemperature unit
Operation Procedure
Operation level
Initial setting level
Selecting _C/_F
ĂSelect either _C" or _F" as the temperature unit.
ĂSet the temperature unit in the temperature unit" parameter of initial
setting level". Default is 
Select _C".
(1) Press the key for at least three seconds to move from the operaĆ
(2) Select the temperature unit" parameter by pressing the key.
Input type
Temperature unit
(3) To return to the operation level" press the key for at least one
: _C".
tion level" to the initial setting level".
Press the or keys to select either _C" or _F".
: _C : _F
second.
3–5
CHAPTER 3 BASIC OPERATION
3.4 Selecting PID Control or ON/OFF Control
The E5AN supports two control methods, 2ĆPID control and ON/OFF
control. The control method is selected by the PID / ON/OFF" parameter
in the initial setting level". When this parameter is set to  ", 2ĆPID
control is set, and when set to 
F 2ĆPID control
PID control is set by AT (autoĆtuning), ST (selfĆtuning) or manual setup.
For PID control, set the PID constants in the proportional band (P)", inĆ
tegral time (I)" and derivative time (D)" parameters.
F ON/OFF control
In ON/OFF" control, the control output is turned ON when the process
value is lower than the current set point, and the control output is turned
OFF when the process value is higher than the current set point (reverse
operation).
", ON/OFF control is set (default).
3–6
3.5 Setting Output Specifications
3.5Setting Output Specifications
JControl period
JDirect/reverse
operation
Control period (OUT1)
Control period (OUT2)
ĂSet the output period (control period). Though a shorter period provides
better control performance, it is recommended to set the control period to 20 seconds or more taking the life expectancy in the case of relay outĆ put into consideration. If necessary, readjust the control period by trial operation, for example, when the control period parameters are set to their defaults.
ĂSet the control period in the control period (OUT1)" and control periĆ
od (OUT2)" parameters (initial setting level). Default is 20 seconds".
ĂWhenever control output 1 is the current output, control period
(OUT1)" cannot be used.
ĂThe control period (OUT2)" parameter can be used only in heating and
cooling control.
ĂDirect operation" refers to control where the manipulated variable is
increased according to the increase in the process value. Alternatively, Reverse operation" refers to control where the manipulated variable is decreased according to the increase in the process value.
Manipulated variable
100%
0%
Low temperature
Set value
Direct operation
For example, when the process value (PV) (temperature) is lower than
the set point (SP) (temperature) in a heating control system, the manipĆ
ulated variable increases by the difference between the PV and SP valĆ
ues.
Accordingly, this becomes reverse operation" in a heating control sysĆ
tem, or alternatively, direct operation" in a cooling control system.
High temperature
Manipulated variable
100%
0%
Low temperature
High temperature
Set value
Reverse operation
ĂDirect/reverse operation is set in the direct/reverse operation" parameĆ
ter (initial setting level). The direct/reverse operation" parameter deĆ fault is reverse operation".
3–7
CHAPTER 3 BASIC OPERATION
Operation Procedure
Operation level
Initial setting level
Input type
Temperature unit
Control period (heat)
Direct/reverse operation
In this example, monitor the input type", temperature unit", direct/reĆ
verse operation" and control period (OUT1)" parameters.
input type" =  ": K thermocouple
temperature unit" =  ": _C
direct/reverse operation" =  ": reverse operation
control period (OUT1)" = 20 (secs)"
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) The input type is displayed. When you are setting the input type for
the first time, 
": K thermocouple is set. (0" is set in the case of a
platinum resistance thermometer.) To select a different sensor, press
the or keys.
(3) Select the temperature unit" parameter by pressing the
key. DeĆ
fault is  ": _C. To select  ": _F, press the key.
(4) Select the control period (heat) parameter by pressing the key.
Default is 20".
(5) Select the direct/reverse operation" parameter by pressing the
key. Default is  ": reverse operation. To select  ": direct opĆ
eration, press the
key.
(6) To return to the operation level" press the key for at least one
second.
Operation level
PV/SP
3–8
3.6 Setting the SP
3.6Setting the SP
Operation level
JChanging the SP
Operation Procedure
Operation level
The operation level" is displayed when the E5AN is turned ON. The upĆ
per display (No.1 display) displays the process value, and the lower display
(No.2 display) displays the set point.
ĂThe set point cannot be changed when the operation/adjustment
protection" parameter is set to 3". For details, see 4.9 Using the Key Protect Levels."
ĂTo change the set point, press the
rameter (operation level), and set the desired set value. The new set point is selected two seconds after you have specified the new value.
ĂMulti-SP is used to switch between two or four set points.
In this example, change the set point from 0_C" to 200_C".
(1) Normally, the PV/SP" parameter is displayed. The set point is 0_C".
(2) Use the
keys to set the set point to 200_C".
or keys in the PV/SP" paĆ
3–9
CHAPTER 3 BASIC OPERATION
3.7 Executing ON/OFF Control
In ON/OFF" control, the control output turns OFF when the currently controlled temperature reaches a preset set point. When the manipulated variable turns OFF, the temperature begins to fall and the control turns ON again. This operation is repeated at a certain point. At this time, how much the temperature must fall before control turns ON again is deterĆ mined by the hysteresis (OUT1)" parameter. Also, how much the manipĆ ulated variable must be adjusted in response in the increase or decrease in the process value is determined by direct/reverse operation" parameter.
JON/OFF Control
F Hysteresis
ĂSwitching between 2ĆPID control and ON/OFF control is carried out by
the PID / ON/OFF" parameter (initial setting level). When this paramĆ eter is set to  ", 2ĆPID control is selected, and when set to  ", ON/OFF control, is selected. Default is 
ĂIn ON/OFF control the hysteresis is used as a differential for switching
the output ON when the temperature moves away from the required set point, and is used give stability around the set point. The control output (OUT1) and control output (OUT2) functions are set in the hysteresis (OUT1) and hysteresis (OUT2) functions respectively.
ĂIn standard control (heating or cooling control), the hysteresis
(OUT1)" setting is used as the hysteresis setting in the adjustment level regardless of the control type, heating control or cooling control.
".
Hysteresis (OUT1)
F 3-position
control
Parameters
ON
OFF PV
Set point
ĂIn heating and cooling control, a dead band (an area where both control
outputs are 0") can be set to either the heating or cooling side. So, 3Ćposition control is made possible.
Dead band
Hysteresis (OUT1)
ON
Heating side
OFF
Set point
Symbol Parameter Name: Level Description
Standard/heating and cooling:
Initial setting level
PID / ON/OFF:
Initial setting level
Direct/reverse operation:
Initial setting level
Dead band:
Adjustment level
Cooling coefficient:
Adjustment level
Hysteresis (OUT1):
Adjustment level
Hysteresis (OUT2):
Adjustment level
Hysteresis (OUT2)
Cooling side
PV
For specifying control method For specifying control method For specifying control method Heating and cooling control Heating and cooling control ON/OFF control ON/OFF control
3–10
3.7Executing ON/OFF Control
JSetup
To execute ON/OFF control, set the set point," PID / ON/OFF" and
hysteresis" parameters.
Setting the PID / ON/OFF parameter
Operation Procedure
In this example, check first that the PID / ON/OFF" parameter is set to
Operation level
PV
(1) Press the key for at least three seconds to move from the operaĆ
(2) Display the input type" parameter in the initial setting level.
Initial setting level
Input type
(3) Select the PID / ON/OFF" parameter by pressing the key.
(4) Check that the set value is  " (default).
(5) To return to the operation level" press the key for at least one
PID ON/OFF
" in the initial setting level".
tion level" to the initial setting level".
second.
Setting the SP
Operation Procedure
Operation level
Next, set the set point value.
In this example, set the set point value (200). The lower display (No.2 disĆ
play) shows the set value (SP value).
(1) Select PV/SP" at the operation level.
PV/SP
(2) Use the keys to set the SP value. (For example, 200) To set the
value either press the key or wait more than two seconds.
3–11
CHAPTER 3 BASIC OPERATION
3.8 Determining PID Constants (AT, ST, manual setup)
JAT.
(auto-tuning)
ĂWhen you execute autoĆtuning, the optimum PID constants for the set
point during program execution are automatically set by forcibly changĆ ing the manipulated variable to calculate the characteristics (called the limit cycle method") of the control target.
ĂTo execute AT (autoĆtuning), specify 
(autoĆtuning), specify 
ĂAT (autoĆtuning) cannot be executed during ON/OFF control.
ĂThe result of AT (autoĆtuning) is mirrored in the proportional band
(P)," integral time (I)" and derivative time (D)" parameters in the adĆ justment level".
Adjustment level
Proportional band
Integrated time
Derivative time
: AT cancel".
: AT execute", and to cancel AT
F Description
AT (autoĆtuning) is started when the AT execute/cancel" parameter is set
to ON". During execution of AT, the No.1 display for the AT execute/canĆ
cel" parameter blinks. When AT ends, the AT execute/cancel" parameter
turns OFF, and the No.1 display stops blinking.
AT execute/cancel No.1 display
During AT execution
If you move to the operation level" during AT execution, the No.2 display
blinks to indicate that AT is being executed.
PV/SP No.2 display
During AT execution
Only the communications writing", run/stop" and AT execution/canĆ
cel" parameters can be changed during AT execution. Other parameters
cannot be changed.
3–12
3.8Determining PID Constants (AT, ST, manual setup)
Operation Procedure
Adjustment Level
AT execute/ cancel
Operation level
PV
JST (self-tuning)
Execute autoĆtuning (AT).
(1) Press the key for less than one second to move from the operaĆ
tion level" to the adjustment level".
(2) Press the
key to start execution of AT (autoĆtuning).
" is displayed during AT execution.
(3) 
(4) To return to the operation level," press the
" is displayed when AT ends.
key.
The ST (selfĆtuning) function executes tuning from the start of program execution to calculate PID constants matched to the control target. Once the PID constants have been calculated, ST is not executed when the next control operation is started as long as the set point remains unĆ changed.
Operation Procedure
Initial setting level
Input type
ST
ST
ST (selfĆtuning) is executed when the ST" parameter is set to ON" in the initial setting level". When the ST function is in operation, be sure to turn the power supply of the load connected to the control output ON simultaneously with or before starting operation of the E5AN.
Execute selfĆtuning (ST).
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) Select the ST" parameter by pressing the key.
(3) Press the key to select  " (default).
(4) To return to the operation level," press the key. The temperaĆ
ture display blinks during selfĆtuning (ST) execution.
PID parameters
When control characteristics are already known, the PID parameters can be set diĆ rectly to adjust control. PID parameters are set in the proportional band" (P), integrated time" (I) and derivative time" (D) parameters in the adjustment level".
3–13
CHAPTER 3 BASIC OPERATION
JST start
conditions
Self-tuning by step response tuning (SRT) is started when the following conditions are met after program execution is started and the set point is changed.
At Start of Program Execution When Set Point Is Changed
1. The set point at the start of program execu­tion differs from the set point (See Note 1) when the previous SRT was executed.
2. The difference between the temperature at start of program execution is larger than (current proportional band 1.27+4_C) or the (ST stable range) whichever is larger.
3. The temperature at the start of program execution is smaller than the set point during reverse operation, and is larger than the set point during direct operation.
4. No reset from input error
1. The new set point differs from the set point (See Note 1) used when the previous SRT was executed.
2. The set point change width is larger than (cur­rent proportional band 1.27+4_C) or the ( ST stable range) whichever is larger.
3. During reverse operation, the new set point is larger than the set point before the change; and during direct operation, the new set point is smaller than the set point before the change.
4. The temperature is in a stable state (See Note 2). (An equilibrium state is acceptable when the output is 0% when the power is turned ON.)
Note:
(1) The previous SRT-implemented set point is called the set point obĆ
tained by calculating the PID constant by the previous SRT.
(2) In this state, the measurement point is within the ST stable range.
(3) In this state, the change width of the PV every 60 seconds is at the
ST stable range or less.
JST stable range
Operation Procedure
Advanced function setting level
ST stable range
PID constants are not modified for the currently preset set point by self-
tuning (ST) in the following instances:
(1) When the PID constants have been changed manually with ST set
to ON.
(2) When auto-tuning (AT) has been executed.
The ST stable range is a condition for determining the conditions under which ST (selfĆtuning) functions. In this example, let's set the ST stable range to 20_C.
(1) Select the ST stable range" parameter by pressing the key in the
advanced function setting level".
(2) Set to 20_C (deviation) using the keys.
3–14
3.8Determining PID Constants (AT, ST, manual setup)
JManual setup
Operation Procedure
Adjustment level
AT execute/ cancel
Proportional band
Integrated time
The individual PID constants can be manually set in the Proportional band", integral time", and Derivative time" parameters in the adjustĆ ment level".
In this example, set the proportional band" parameter to 10.0", the inĆ tegrated time" parameter to 250" and the derivative time" parameter to 45".
(1) Press the key to move from the operation level" to the adjustĆ
ment level".
(2) Select proportional band" by pressing the
(3) Use the
keys to set the parameter to 10.0".
(4) Select integrated time" by pressing the
key.
key.
(5) Use the keys to set the parameter to 250".
(6) Select derivative time" by pressing the
(7) Use the
keys to set the parameter to 45".
(8) To return to the operation level," press the
key.
key.
Derivative time
Proportional Op­eration
When PID constants I (integral time) and D (derivative time) are set to 0", control is executed according to proportional operation. The default set point becomes the center value of the proportional band. Related parameter manual reset value" (adjustment level)
3–15
CHAPTER 3 BASIC OPERATION
When P (proportional band) is adjusted
When P is
Set Value
increased
When P is
Set Value
decreased
When I (integral time) is adjusted
When I is increased
When I is decreased
Set Value
Set Value
When D (derivative time) is adjusted
When D is increased
When D is decreased
Set Value
Set Value
The curve rises gradually, and a long stable time is achieved, preventing overshoot.
Overshoot and hunting occur, howev­er the set point is quickly reached after which the curve stabilizes.
It takes a long time for the process val­ue to reach the set point. It takes time to achieve a stable state, however there is little overshoot/undershoot and hunting.
Overshoot/undershoot and hunting occur, and the curve rises quickly.
Overshoot/undershoot and stable time are reduced, however , fine hunt­ing occurs on changes in the curve it­self.
Overshoot/undershoot increase, and it takes time for the process value to reach the set point.
3–16
3.9 Alarm Outputs
|H|
|
ĂAlarm output conditions are determined by the combination of alarm
type" and alarm hysteresis."
ĂThe following describes the alarm type", alarm value", upperĆlimit
alarm" and lowerĆlimit alarm" parameters.
JAlarm type
Set
Value
0 Alarm function OFF Output OFF
1
*1
2 Upper-limit (deviation)
3 Lower-limit (deviation)
4
*1
5
*1
6
7
8 Absolute-value upper-limit
9 Absolute-value lower-limit
10
11
*1 : The upperĆ and lowerĆlimit values, expressed as L" and H", can be set independently for each alarm
point with set values 1, 4 and 5.
*2 : Set value : 1 UpperĆ and lowerĆlimit alarm
*3 : Set value : 4 UpperĆ and lowerĆlimit range
*4 : Set value : 5 UpperĆ and lowerĆlimit alarm with standby sequence
*For the above upperĆ and lowerĆlimit alarm Ć In cases 1 and 2, the alarm is normally OFF if upperĆ and lowerĆlimit values of hysteresis overlap.
Cases 1 and 2 example: Ć In case 3, the alarm is normally OFF.
Alarm Output Operation
Alarm Type
Upper- and lower-limit (deviation)
Upper- and lower-limit range (deviation)
Upper- and lower-limit alarm with standby sequence (deviation)
Upper-limit alarm with standby sequence (deviation)
Lower-limit alarm with standby sequence(deviation)
Absolute-value upper-limit with standby sequence
Absolute-value lower-limit with standby sequence
Case 1 Case 2 Case 3 (Normally ON)
LHSP LHSP
H < 0, L > 0
|H| < |L|
Case 1 Case 2 Case 3 (Normally OFF)
LHSP LHSP
H < 0, L > 0
|H| < |L|
H > 0, L < 0
|H| > |L|
H > 0, L < 0
|H| > |L|
When alarm value
X is positive
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
*5
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
LHSP
LHSP
LH
SP
SP
X
SP
LH
SP LH
SP
SP
X
SP
X
0
X
0
X
0
X
0
LHSP
LHSP
LHSP
LHSP
X
X
H < 0, L < 0
H < 0, L > 0
H > 0, L < 0
H < 0, L < 0 H < 0, L > 0
H > 0, L < 0
|H| y |L|
x |L
|H| y |L|
|H| x |L|
3.9Alarm Outputs
When alarm value
X is negative
*2
ON OFF
ON OFF
*3
*4
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
X
SP
X
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
*5 : Set value : 5 UpperĆ and lowerĆlimit alarm with standby sequence
The alarm is normally OFF if upperĆ and lowerĆlimit values of hysteresis overlap.
3–17
CHAPTER 3 BASIC OPERATION
ĂAlarm types are set independently for each Alarm type 1 to 3" (initial
setting level). The default value is 2 : UpperĆlimit alarm".
JAlarm value
Lower-limit alarm value
Upper-limit alarm value
Alarm value
ĂAlarm values are indicated by X" in the table on the previous page.
When the upper and lower limits are set independently, H" is displayed for upper limit values, and L" is displayed for lower limit values.
ĂTo set the upperĆ and lowerĆlimit alarm values for deviation, set the upĆ
per and lower limits in each of the alarm upper limit 1 to 3", and alarm lower limit 1 to 3" parameters (operation level).
Operation Procedure
Initial setting level
Operation level
Input type
Alarm 1 type
PV/SP
Alarm value 1
Set alarm 1" to the upperĆlimit alarm. The following shows related paĆ rameters and setups. In this example, the alarm output is active when the set point is exceeded by 10_C". (The temperature unit in this example is _C".)
Alarm 1 type" = 2: upperĆlimit alarm (deviation)" Alarm value 1" = 10"
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) Select the alarm 1 type" parameter by pressing the key. Check
that the alarm type" parameter is set to 2" (default, upperĆlimit alarm).
(3) To return to the operation level" press the key for at least one
second.
(4) Select alarm value 1" by pressing .
(5) Use the keys to set the parameter to 10".
3–18
3.10 Heater Burnout Alarm (HBA)
3.10Heater Burnout Alarm (HBA)
JHBA detection
To CT terminal
Heater lead
JOperating
conditions
ĂHeater burnout detection works as follows.
(1) Connect the current transformer (CT) to terminal Nos. 14 and 15,
and insert the heater lead through the CT hole. For specifications, models and external dimensions of current transformers that can be used on this controller, see Appendix, About Current TransĆ former (CT)."
(2) When current flows through this lead, the current transformer
generates AC current proportional to the current value. The E5AN measures this AC current to calculate the current flowing to the heater.
(3) If the heater is burned out, the current measured at the current
transformer decreases. This value is compared with the value set as the heater burnout set value", and the output becomes active as the heater burnout alarm.
ĂSet the heater burnout set value in the heater burnout detection" paĆ
rameter (adjustment level). To monitor the current value of the current transformer, use the heater current monitor" parameter.
ĂWhen HBA function, is not used set the heater burnout" parameter
(advanced function setting level) to OFF".
ĂThe HBA function can be used when the option unit E53ĆAKB,
E53ĆAK01, or E53ĆAK03 is mounted on the E5AN. Be sure to connect the CT to the E5AN, and pass the heater lead through the CT hole.
ĂTurn the heater ON at the same time as or before turning the E5AN ON.
If the heater is turned ON after turning the E5AN ON, the heater burnĆ out alarm will activate.
ĂControl is continued even if the heater burnout alarm is active. (That is,
the E5AN attempts to control the heater on which the heater burnout alarm has not occurred.)
ĂThe heater burnout alarm is detected when the control output is continĆ
uously ON for 190 ms or more.
ĂThe rated current value may sometimes differ slightly from the actual
current flowing to the heater. Check the current value in an actual operĆ ating state in the heater current monitor" parameter.
ĂIf there is little difference between the current in a normal state and the
current in the burnout state, detection may become unstable. On a heatĆ er of current 10.0 A or less, maintain a difference of 1.0 A or more. On a heater of current 10.0 A or more, maintain a difference of 2.5 A or more.
ĂThe HBA function cannot be used when the heater is controlled by a
phase control system or cycle control system. Also, 3Ćphase heaters canĆ not be used.
When heater burnout is detected on a 3Ćphase heater, use the K2CUĆFjjAĆjGS
(with gate input terminal). See the respective data sheet for details.
3–19
CHAPTER 3 BASIC OPERATION
JSetup
To activate the heater burnout alarm, set the HBA used" parameter (adĆ vanced function setting level) to ON" and the heater burnout set value in the heater burnout detection" parameter (adjustment level).
Operation Procedure
In this example, set the heater burnout detection" parameter to 2.5".
Moving to the advanced function setting level
Operation level
PV/SP
The default of the heater burnout" parameter is already ON", so set the heater burnout detection" parameter.
(1) Move to the advanced function setting level.
Initial setting level
Input type
Press the tion level" to the initial setting level".
(2) Then move to advanced function setting level" by pressing the
key.
Move to advanced function setting level
(3) Use the
the initial setting level" to the advanced function setting level". The top parameter in the advanced function setting level" is disĆ
Advanced function setting level
played.
(4) Select the HBA used" parameter by pressing the
Make sure that this parameter is set to ON" (default).
HBA used
Next, set the heater current value monitor" parameter.
key for at least three seconds to move from the operaĆ
keys to input the password (-169"), and move from
key.
Setting heater burnout detection
Operation level
PV/SP
Adjustment level
AT execute/cancel
(5) Press the
(6) Press the key for less than one second to move from the operaĆ
(7) Select the heater current value monitor" parameter by pressing the
Heater current value monitor
(8) Select the heater burnout detection" parameter by pressing the
Heater burnout detection
(9) For example, set 2.5". To return to the operation level", press the
key for at least one second to move from the advanced function setting level" to the initial setting level" and then to the operation level".
tion level" to the adjustment level".
key. Check the current value. Next, set the heater burnout detecĆ
tion" parameter.
key. Set the current value as a reference value. Set this set value so that there is a large difference between the current flowing to the heater lead when heater operation is normal and the current flowing when a heater burnout occurs.
key for less than one second.
3–20
3.10Heater Burnout Alarm (HBA)
JHow to calculate
detection current values
ĂCalculate the set value by the following equation:
Set value =
(current value at normal operation + current value at heater burnout)
2
ĂTo set the value of the heater burnout when two or more heaters are conĆ
nected through the CT, use the curent value of the smallest heater conĆ nected. OR the current value when one of the heaters burns out if all the heaters have the same current value.
ĂMake sure that the following conditions are satisfied:
Heater of current 10.0 A or less:
Current value at normal operation Ć
current value at heater burnout y 1 A
(When the resultant current is less than 1 A, detection is unstable.)
Heater of current 10.0 A or more:
Current value at normal operation Ć
current value at heater burnout y 2.5 A
(When the resultant current is less than 2.5 A, detection is unstable.)
ĂThe setting range is 0.1 to 49.9 A. Heater burnout is not detected when
the set value is 0.0" or 50.0". When the set value is 0.0", the heater burnout alarm is set to OFF", and if the set value is 50.0", the heater burnout alarm is set to ON".
ĂSet the total current value at normal heater operation to 50 A or less.
When set to 55.0 A",  " is displayed in the heater current moniĆ tor" parameter.
JExample
Heater
1KW
E5AN 14 15
Heater
E5AN 14 15
CT
1KWx3
CT
Example 1 When using a 200 VAC, 1 kW heater
Control output
Example 2 When using three 200 VAC, 1 kW heaters
Control output
AC200V
AC200V
1000
Current during normal operation =
+ 5AĂ(t 10A)
200
Current at heater burnout = 0A
5 ) 0
Set value =
2
+ 2.5A
(current at normal operation Ć current at heater
burnout )
Current at normal operation =
Current at burnout of one heater =
Set value =
+ 5ĂĆĂ0 + 5AĂ(y 1A))
15 ) 10
2
+ 12.5A
1000
3 + 15AĂ(y 10A)
200
1000
2 + 10A
200
(current at normal operation Ć current at heater
burnout )
+ 15ĂĆĂ10 + 5AĂ(y 2.5A))
Parameters
Symbol Parameter : Level Description
Heater current value monitor:
Adjustment level
Heater burnout detection:
Adjustment level
Heater burnout hysteresis:
Advanced function setting level
Heater burnout latch:
Advanced function setting level
For heater current value monitor
For HBA detection
For HBA detection
For HBA detection
3–21
CHAPTER 3 BASIC OPERATION
3.11 Requests during Operation
1) About four seconds is required for outputs to turn ON when the power
is turned ON. Take this into consideration when the temperature conĆ
troller is incorporated into a sequence circuit.
2) Allow at least 30 minutes for warming up.
3) When self-tuning is used, turn the temperature controller and load
(e.g. heater) ON simultaneously or turn the load ON before the temĆ
perature controller. If the load is turned ON before the temperature
controller, correct self-tuning and optimum control are no longer
possible.
When operation is started after warm-up, turn the power OFF once
after warm-up is completed, and then turn the temperature controlĆ
ler and load ON simultaneously. (Instead of turning the temperature
controller power ON again, moving from the STOP to the RUN mode
also is possible.)
4) The temperature controller may be subject to the influence of radio
interference if used near a radio, TV or wireless equipment.
3–22
CHAPTER4
CHAPTER 4
APPLIED OPERATION
4.1 Shifting Input Values 4Ć2. . . . . . . . . . . . . . . . . . .
Shifting input 4Ć2. . . . . . . . . . . . . . . . . . . . . . . . .
How to calculate input shift values
(2Ćpoint shift) 4Ć3. . . . . . . . . . . . . . . . . . . . . . . . . .
1Ćpoint shift method 4Ć4. . . . . . . . . . . . . . . . . . . .
2Ćpoint shift method 4Ć4. . . . . . . . . . . . . . . . . . . .
Example of 2Ćpoint temperature
input shift 4Ć5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Alarm Hysteresis 4Ć6. . . . . . . . . . . . . . . . . . . . . .
Standby sequence 4Ć6. . . . . . . . . . . . . . . . . . . . . .
Alarm latch 4Ć6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Close in alarm/open in alarm 4Ć7. . . . . . . . . . . .
4.3 Setting Scaling Upper and Lower Limits
(analog input) 4Ć8. . . . . . . . . . . . . . . . . . . . . . . . .
Analog input 4Ć8. . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Executing Heating and Cooling Control 4Ć10. .
Heating and cooling control 4Ć10. . . . . . . . . . . . .
Setup 4Ć11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 To Use Event Input 4Ć12. . . . . . . . . . . . . . . . . . . .
Setting event input 4Ć12. . . . . . . . . . . . . . . . . . . . .
How to use multiĆSP 4Ć12. . . . . . . . . . . . . . . . . . .
Setting by key operation 4Ć13. . . . . . . . . . . . . . . .
Setup 4Ć13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Executing run/stop control 4Ć14. . . . . . . . . . . . . .
4.6 Setting the SP Upper and
Lower Limit Values 4Ć15. . . . . . . . . . . . . . . . . . . . .
Set point limitter 4Ć15. . . . . . . . . . . . . . . . . . . . . . .
Setup 4Ć16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7 Executing the SP Ramp Function
(limiting the SP change rate) 4Ć17. . . . . . . . . . . .
SP ramp 4Ć17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8 To Move to the Advanced Function
Setting Level 4Ć19. . . . . . . . . . . . . . . . . . . . . . . . . .
4.9 Using the Key Protect Level 4Ć20. . . . . . . . . . . . .
Key protect 4Ć20. . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 4 APPLIED OPERATION
4–1
4.1 Shifting Input Values
JShifting input
F 1-point shift
Operation Procedure
ĂThe input shift type matched to the sensor currently selected in the
input type" parameter is displayed.
Ă2Ćpoint shift is applied only for nonĆcontact temperature sensors.
ĂWith 1Ćpoint shift, only the value set to the Temperature input shift"
parameter (adjustment level) is applied to the entire temperature input range. For example, if the input shift value is set to 1.2_C", the process value is treated as 201.2_C" after input shift is applied when the proĆ cess value is 200_C.
Temperature
Upper-limit value
Lower-limit value
0
After shift
Before shift
Input shift value
Input
100
In this example, shift the input of the K sensor by 1_C" by 1Ćpoint input
shift.
Operation level
Adjustment level
Operation level
Temperature input shift
Operation level
(1) Press the key to move from the operation level" to the adjustĆ
ment level".
(2) Select the temperature input shift" parameter by pressing the
key.
(3) Use the keys to set 1.0".
(4) To return to the operation level," press the key. The process
value is 1_C larger than before shift is applied.
4–2
F 2-point shift
Upper-limit temperature input shift value
Lower-limit temperature input shift value
ĂThe input temperature range of nonĆcontact temperature sensors can
be shifted by setting an individual value for the upper and lower points of the sensor range. This means that the shift can be applied equally across the range with separate values for each end of the range. For example, if the upperĆlimit value is set to 2_C" and the lowerĆlimit value is set to 1_C", the sensor range is shifted by an average of 1.5_C at 50% input.
ĂSet the upperĆlimit value in the upperĆlimit temperature input shift
value" parameter and the lowerĆlimit value in the lowerĆlimit temperaĆ ture input shift value" parameter.
Temperature
Upper-limit value
Upper-limit temperature input shift value
After shift
Before shift
Lower-limit value
0
Lower-limit temperature input shift value
JHow to calculate input shift values (2-point shift)
When the nonĆcontact temperature sensor model ES1A is connected to the E5AN, an offset of several to several tens of a degree can occur. For this reason, offset the readout value by 1Ćpoint or 2Ćpoint shift as described in this item. This offset occurs as a bias current for detecting controller sensor error flows to the output impedance of the nonĆcontact temperature sensor. 2Ćpoint shift can be carried out only on nonĆcontact temperature sensors, and cannot be set for other input types.
[Preparations]
(1) Set to the temperature range matching the input specifications of the
nonĆcontact temperature sensor. (ES1A is supported only in thermoĆ couple input types on the E5AN.)
(2) Prepare a thermometer capable of measuring the temperature of the
control target as shown in Figure 1 so that 1Ćpoint shift or 2Ćpoint shift can be carried out.
Input
100
Non-contact temperature sensor
(A) E5AN Temperature controller
(C) Control target
(B) Thermometer
Figure 1 Configuration When Compensating a Non-contact
T emperature Sensor
4–3
CHAPTER 4 APPLIED OPERATION
J1-point shift
method
Adjustment level
Upper-limit tem­perature input shift value
Lower-limit tem­perature input shift value
(1) In the configuration shown in Figure 1, bring the set point to near the
value at which the temperature of the control target is to be conĆ trolled. Assume that the control target temperature (C) and the conĆ trol target temperature (B) are matching.
(2) Check the control target temperature (B) and the controller readout
(A). Take the following value as the input shift value, and set the same numerical values to 
" and  ".
control target temperature (B) Ć controller readout (A)
Figure 2 shows the effect of 1Ćpoint temperature input shift.
(3) After setting the input shift values, check controller readout (A) and
control target temperature (B). If they are almost the same, this comĆ pletes temperature input shift.
Controller readout (A)
Temperature readout after shift (e.g. 120_C)
Temperature readout before shift (e.g. 110_C)
After shift
Input shift value (e.g. 10_C)
Before shift
J2-point shift
method
Temperature readout after input shift X2 (e.g. 110_C)
Temperature readout before input shift Y2 (e.g. 105_C)
Temperature readout of
0
Near set point (e.g. 120_C)
control target (B)
Figure2 1-point Temperature Input Shift
Use 2Ćpoint input shift if you want to increase the accuracy of the readout values across the range of the sensor.
(1) Shift the controller readout by two points, near room temperature
and near the value at which the temperature of the control target is to be controlled. For this reason, bring the control target temperature to near room temperature and to near the set point, and check control target temperature (B) and controller readout (A).
(2) Using equations (1) and (2) calculate the upperĆ and lowerĆlimit temĆ
perature input shift values from the readout and temperature to be shifted that you obtained in step 1. Figure 3 shows the effect of shift by 2Ćpoint temperature input shift.
Controller readout (A)
Set temperature upper limit YH (e.g. 260_C)
After shift
Upper-limit temperature input shift value
Before shift
4–4
Temperature readout before input shift Y1 (e.g. 40_C)
Temperature readout after input shift X1 (e.g. 25_C)
Lower-limit temperature input shift value
Figure3 2-point Temperature Input Shift
X1 room temperature
0
(e.g. 25_C)
Set temperature lower limit YL (e.g. 0_C)
Temperature readout of control target (B)
Near X2 set point (e.g. 110_C)
4.1Shifting Input Values
ĂUse the following equation to calculate the lowerĆlimit temperaĆ
ture input shift value.
ĂYLĂĆĂY1Ă
+
ĂY2ĂĆĂY1Ă
{(X2ĂĆĂY2)ĂĆĂ(X1ĂĆĂY1)}) (X1ĂĆĂY1)...equationĂ1
ĂUse the following equation to calculate the upperĆlimit temperaĆ
ture input shift value.
ĂYHĂĆĂY1Ă
+
ĂY2ĂĆĂY1Ă
{(X2ĂĆĂY2)ĂĆĂ(X1ĂĆĂY1)}) (X1ĂĆĂY1)...equationĂ2
(3) After setting the calculated values to  " and  ", check conĆ
troller readout (A) and control target temperature (B).
(4) Although the input shift was carried out at two points, close to room
temperature (ambient temperature), and near to the set point, select
points close to each end of the sensor range to improve accuracy across
the full range of the sensor measurement range.
JExample of
2-point temperature input shift
Adjustment level
Lower-limit tempera­ture input shift value
Upper-limit tempera­ture input shift value
In this example, we use the ES1A K 0 to 260_C specification.
YL an YH in equations 1 and 2 are set temperature lower limit YL is 0_C
and set temperature upper limit YH is 260_C. Check the temperature of
the control target.
When the room temperature X1 is 25_C, the readout on the controller Y1
is 40_C, and when the temperature near the set point X2 is 110_C, the
readout on the controller Y2 becomes105_C.
LowerĆlimit temperature input shift value
Ă0ĂĆĂ40Ă
+
Ă105ĂĆĂ40Ă
{(110ĂĆĂ105)ĂĆĂ(25ĂĆĂ40)}) (25ĂĆĂ40) +Ă Ć27.3(°C)
UpperĆlimit temperature input shift value
Ă260ĂĆĂ40Ă
+
Ă105ĂĆĂ40Ă
{(110ĂĆĂ105)ĂĆĂ(25ĂĆĂ40)}) (25ĂĆĂ40) +Ă 52.7(°C)
4–5
CHAPTER 4 APPLIED OPERATION
4.2 Alarm Hysteresis
ĂThe hysteresis of alarm outputs when alarms are switched ON/OFF can
be set as follows:
JStandby
sequence
ON
OFF
Upper-limit alarm
Alarm hysteresis
Alarm value
ON
OFF
Lower-limit alarm
Alarm value
Alarm hysteresis
ĂAlarm hysteresis is set independently for each alarm in the alarm hysĆ
teresis 1 to 3" parameters (advanced function setting level). Default is 0.2EU".
ĂStandby sequence" is a function which allows the alarm outputs to be
temporarily disabled while the first alarm condition occurs. From here on, the alarm output is active for future alarm conditions.
ĂFor example, in a standard heating application, if you used the standard
low alarm", the alarm would be active from switching the controller ON. However, with Standby Sequence", the alarm output is disabled during the first warmup, and the temperature has to rise above the alarm set point before the alarm can become active. Then, if the temperĆ ature falls below the alarm set point, the output is active.
F Restart
JAlarm latch
ĂThe standby sequence is canceled when an alarm is output. It is, howĆ
ever, restarted later by the standby sequence" parameter (advanced function setting level). For details, see the standby sequence" parameter in Chapter 5, Parameters."
ĂAlarm latch" is a function where alarm output once turned ON stays
ON regardless of the temperature.
ĂThe alarm latch can be canceled by turning the power OFF. (Note, howĆ
ever, that it can also be canceled by switching to the initial setting level, communications setting level, advanced function setting level or calĆ ibration level.
4–6
4.2Alarm Hysteresis
Close in
Open in
JClose in alarm/
open in alarm
F Summary of
alarm operations
ĂWhen the E5AN is set to close in alarm," the status of the alarm output
is normally open. When set to open in alarm," the status of the alarm output is output inverted or nomally closed.
ĂAlarm type and close in alarm (normally open)/open in alarm (normally
closed) can be set independently for each alarm.
ĂClose in alarm/open in alarm is set in the alarm 1 to 3 open in alarm"
parameters (advanced function setting level). Default is  : close in alarm".
Alarm Output Function Output Alarm LCD
Close in alarm
Open in alarm
ON ON Lit
OFF OFF Out
ON OFF Lit
OFF ON Out
Alarm output turns OFF (relay contact open) at a power interruption and
for about two seconds after the power is turned ON regardless of the close
in alarm/open in alarm setting
The figure below visually summarizes the above description of alarm
operations (when alarm type is set to lowerĆlimit alarm with standby
sequence" and E5AN is set to close in alarm").
Alarm type: lower-limit alarm with standby sequence
Parameters
PV
Alarm value
Alarm hysteresis
Time
Standby sequence
Alarm
output
canceled
ON OFF
ON (closed) OFF (open)
When alarm 1 open in alarm" (advanced function setting level) is set to
open in alarm", the heater burnout alarm and input error output also beĆ
come open in alarm."
Symbol Parameter : Level Description
Alarm 1 to 3 hysteresis:
V
V
Advanced function setting level
Standby sequence reset method:
Advanced function setting level
Alarm 1 to 3 open in alarm:
Advanced function setting level
Alarm
Alarm
Alarm
V : , , or
4–7
CHAPTER 4 APPLIED OPERATION
4.3 Setting Scaling Upper and Lower Limits (analog input)
JAnalog input
Scaling upper limit
Scaling lower limit
Decimal point
ĂWhen an analog input (voltage input) is selected, scaling matched to the
control is possible.
ĂScaling is set in the scaling upper limit", scaling lower limit" and decĆ
imal point" parameters (initial setting level). These parameters cannot be used when temperature input type is selected.
ĂThe scaling upper limit" parameter sets the physical quantity to be
expressed by the upper limit value of input, and the scaling lower limit" parameter sets the physical quantity to be expressed by the lowerĆlimit value of input. The decimal point" parameter specifies the number of digits past the decimal point.
ĂThe following figure shows a scaling example of 0 to 5 mV input. After
scaling, the humidity can be directly read.
Readout (humidity)
50 mV
Upper-limit value (95.0%)
Lower-limit value (10.0%)
0 mV
0
100%FS
Input (0 to 50 mV)
4–8
4.3Setting Scaling Upper and Lower Limits (analog input)
Operation Procedure
Initial setting level
Input type
Scaling upper limit
Scaling lower limit
Decimal point
In this example, the scaling upperĆ and lowerĆlimits is set so that inputs 0 to 50 mV become 10.0% to 95.0%.
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) Select scaling upper limit" by pressing .
(3) Use the keys to set the parameter to 950".
(4) Select scaling lower limit" by pressing
.
(5) Use the keys to set the parameter to 100".
(6) Select the decimal point position by pressing .
(7) Use the keys to set the parameter to 1".
(8) To return to the operation level" press the key for at least one
second.
4–9
CHAPTER 4 APPLIED OPERATION
4.4 Executing Heating and Cooling Control
JHeating and
cooling control
F Dead band
Output
Heating and cooling control can be used on E5ANĆj3jjj controllers. Heating and cooling control operates when 
: heating and cooling" is selected in the standard/heating and cooling" parameter. Select the stanĆ dard heating control or cooling control according to the following table:
Setting Output
Control Method
standard control Reverse operation Control output (heat) ­standard control Direct operation Control output (cool) -
Heating and cooling
control
Heating and cooling
control
Direct/reverse
operation
Reverse operation Control output (heat) Control output (cool)
Direct operation Control output (cool) Control output (heat)
Control output 1 Control output 2
(The parameter default is heating control (standard).)
ĂWhen heating and cooling control is selected, the dead band" and coolĆ
ing coefficient" parameters can be used.
The dead band is set with the set point as its center on the E5ANĆj3jj. The dead band width is the set value of the dead band" parameter (adjustĆ ment level). Setting a negative value produces an overlap band. Default is 0.0 EU."
Dead band: dead band width = positive
Output
Overlap band: dead band width = negative
F Cooling
coefficient
Heating side
00
Set point
Cooling side
PV PV
Heating side Cooling side
Set point
If the heating and cooling characteristics of the control target greatly difĆ fer, preventing satisfactory control characteristics from being obtained by the same PID constants, adjust the proportional band (P) at the cooling side using the cooling coefficient to balance control between the heating and cooling sides. In heating and cooling control, P at the heating or coolĆ ing side is calculated by the following formula:
Heating side P = P Cooling side P = Pcooling coefficient
The cooling coefficient is applied to Control output 1 side P to obtain conĆ trol whose characteristics (Control output 2 side P) differ from those on the Control output 1 side.
4–10
4.4Executing Heating and Cooling Control
Output
Control output 1 side P
00
JSetup
To set heating and cooling control, set the standard/heating and cooling",
dead band" and cooling coefficient" parameters.
Setting heating and cooling control
Operation Procedure
Initial setting level
Standard/heating and cooling
standard/heating and cooling" = heating and cooling"
(1) Press the key for at least three seconds to move from the operaĆ
(2) Select standard heating and cooling control" in the initial setting
Output
Control output 1 side P1.0
Control output 2 side P
PV PV
Set point
Control output 1 side P0.8
tion level" to the initial setting level".
level".
: Standard control
: Heating and cooling control
Control output 1 side P1.0
Control output 1 side P
Set point
Control output 1 side P1.5
Control output 2 side P
Setting dead band
Operation Procedure
Adjustment level
Dead band
Setting cooling coefficient
Operation Procedure
Adjustment level
Cooling coefficient
Dead band" = 5"
(1) Select dead band" in the adjustment level".
(2) Use the keys to set the parameter to 5.0".
The setting range is Ć199.9 to 999.9.
Cooling coefficient = 10
(1) Select cooling coefficient" in the adjustment level".
In this example, set the parameter to 10".
(2) Use the
keys to set the parameter to 10.00".
The setting range is 0.01 to 99.99.
4–11
CHAPTER 4 APPLIED OPERATION
4.5 To Use Event Input
JSetting event
input
E5AN
11
12
13
EV1
EV2
+ + –
EV1 EV2
Run/stop control is executed by event input assignments 1 and 2. The following table shows the number of multiĆSP uses" displays which
functions are assigned to event inputs 1 and 2. The number of multiĆSP uses" parameter is used when the number of preset set points is 2 or 4. This parameter determines display or nonĆdisĆ play of the event input assignment 1" and event input assignment 2" parameters.
Number
of
Multi-SP
Uses
0 NONE or STOP 1” NONE or RUN/STOP switching 1”
1 – (not displayed) NONE or S TOP
2 – (not displayed)
*1 “STOP (RUN/STOP) switching” can be set only on one of event input assignments 1 or 2. The
event input on the side that is set can be used. The setting on the other side becomes “NONE”.
Event input
assignment 1
Setting Event Input Function
Event input
assignment 2
Event input 1
function
Multi–SP 2 set points (set point 0/1 switch­ing)
Multi–SP 4 set points
(set point 0/1/2/3 switching)
Event input 2
function
NONE or RUN/STOP switch­ing
When you are setting two external input set points, set in the number of multiĆSP uses" parameter.
ĂTo select set points (0/1)
Two set points can be selected when the number of multiĆSP uses" is set to 1" (default). This setting need not be changed. Set point 0 or 1 is specified by the ON/OFF state of event input 1.
JHow to use multi-SP
F When multi-SP is
used by event input
MultiĆSP" is a function for setting set points 0 to 3 in advance, and selectĆ ing these set points by a combination of event inputs 1 and 2.
MultiĆSP can be used when the option event input unit E53ĆAKB is mounted on the E5AN and number of multiĆSP uses" is set to 1" or 2".
When “number of multi-SP uses” is set to “1”
Event input 1 Selected Set Point
OFF Set point 0
ON Set point 1
When “number of multi-SP uses” is set to “2”
Event input 1 Event input 2 Selected Set Point
OFF OFF Set point 0
ON OFF Set point 1
OFF ON Set point 2
ON ON Set point 3
* Event input can be used when the option event input unit E53ĆAKB is
mounted in the E5AN. Select event input ON/OFF while the E5AN is turned ON. Judgment of event input ON/OFF is carried out on event inputs of 50 ms or more.
4–12
4.5To Use Event Input
JSetting by key
operation
JSetup
To select set points (0/1/2/3)
Operation Procedure
Set points 0 to 3 can be selected by changing the set value of the multiĆSP" parameter. The multiĆSP" display conditions are as follows:
ĂWhen the option event input unit E53ĆAKB is not mounted in the E5AN,
and multiĆSP" is set to ON"
ĂWhen the option event input unit E53ĆAKB is mounted in the E5AN, the
number of multiĆSP uses" is set to 0" and multiĆSP" is set to ON"
The following table shows the relationship between the multi SP" parameter set value and the selected set point.
Multi-SP Selected Set Point
0 Set point 0 1 Set point 1 2 Set point 2 3 Set point 3
Before setting the number of multi SP uses," cancel protection and move
to the advanced function setting level". For details on how to cancel
protection, see 4.9ĂUsing the Key Protect Level".
Operation level
PV/SP
Initial setting level
Input type
Move to advanced function setting level
Advanced function setting level
Parameter initialize
Number o f multi-SP uses setting
Number of multi-SP uses
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) Select Move to advanced function setting level" by pressing the
key.
(3) Use the key to enter Ć169" (password).
It can be moved to the advanced function setting level" by pressing
the key or leaving the setting for at least two seconds.
(4) Select Number of multiĆSP uses" by pressing the key.
(5) Use the key to set the parameter to 2".
(6) To return to the initial setting level" press the key for at least
one second.
(7) To return to the operation level" press the key for at least one
second.
Set points 0, 1, 2 and 3 are set according to the ON/OFF states of event
inputs 1 and 2.
E5AN
11
12
13
EV1
EV2
EV1
+
EV2
+
4–13
CHAPTER 4 APPLIED OPERATION
1
JExecuting run/
stop control
When event input assignment 1" or event input assignment 2" is set to
run/stop", control is started when event input 1 or 2 becomes OFF".
Control is stopped when this becomes ON".
While control is stopped, STOP lights.
Setting Input Contact State
Event input 1 or 2 ON STOP Event input 1 or 2 OFF RUN
Note: When number of multiĆSP uses" is set to 0" or 1" that is not the
set point setting, run/stop control is possible according to event
inputs.
Event input assignments 1 and 2 are as follows according to the number
of multiĆSP uses" setting.
Number
of
Multi-SP
Uses
0
2
Event input
assignment 1
NONE STOP NONE
STOP NONE
NONE NONE NONE NONE
– (setting data not displayed)
– (setting data not displayed)
– (setting data not displayed)
Setting Event Input Function
Event input
assignment 2
STOP
NONE
– (setting data not displayed)
Event input 1
function
RUN/STOP switching
Multi–SP 2 set points (set point 0/1 switch­ing)
Multi–SP 2 set points (set point 0/1 switch­ing)
Multi–SP 4 set points
(set point 0/1/2/3 switching)
Event input 2
function
RUN/STOP switching
NONE
RUN/STOP switching
NONE or RUN/STOP switch­ing
Parameters
ĂWhen the number of multiĆSP uses is set to either 1 or 2, and event input
assignment 1 or 2 is set to not displayed," the setting automatically becomes none."
ĂWhen the number of multiĆSP uses" is set to 0", and both input assignĆ
ments 1 and 2 can be set, RUN/STOP is assigned to only one event assignment. The other event assignment is automatically set to OFF.
ĂWhen the RUN/STOP function is used for event inputs, RUN/STOP at
the run level is not displayed.
Symbol Parameters : Level Description
Event input 1 assignment:
Advanced function setting level
Event input 2 assignment:
Advanced function setting level
Number of multi-SP uses:
Advanced function setting level
For event input function
4–14
4.6Setting the SP Upper and Lower Limit Values
4.6 Setting the SP Upper and Lower Limit Values
JSet point limitter
Changed to upper limit value
Input type changed
Set point Upper- and lower-limit values of the limitter
Sensor upper- and lower-limit values
The setting range of the set point is limited by the set point limitter. The
set point limitter is used to prevent the control target from reaching
abnormal temperatures. The upperĆ and lowerĆlimit values of this set
point limitter are set by the set point upper limit" and set point lower
limit" parameters in the initial setting level", respectively. However, note
that when the set point limitter is reset, the set point is forcibly changed
to the upperĆ or lowerĆlimit value of the set point limitter if the set point
is out of the limitter range. Also, when the input type and temperature
unit are changed, the set point limitter is forcibly reset to the sensor setĆ
ting range.
Sensor range
Set point limitter
Setting range
Changed to the new upper limit value
B
A
Ę
C
B
Ę(setting possible)
(setting impossible)
Set point
Set point
Set point
Parameters
Symbol
Parameters : Level Description
Set point upper limit : Initial setting level For limiting SP setting Set point lower limit : Initial setting level For limiting SP setting
4–15
CHAPTER 4 APPLIED OPERATION
JSetup
Setting the set point upper limit
Operation Procedure
Initial setting level
Input type
Set point upper limit
To set the set point upper and lower limits, set in the set point upper
limit" and set point lower limit" parameters in the initial setting level".
This example describes how to set the set point limitter Ć200 to 1300_C"
to input type K thermocouple.
-200 1300 Sensor range
Set point limitter
1000-100
Set the set point upper limit" parameter to 1000".
(1) Press the key for at least three seconds to move from the operaĆ
tion level" to the initial setting level".
(2) Select set point upper limit".
(3) Use the
keys to set the parameter to 1000".
Setting the set point lower limit
Operation Procedure
Set point lower limit
Set the set point lower limit" parameter to Ć100".
(1) Select set point lower limit" in the initial setting level".
(2) Use the keys to set the parameter to Ć100".
4–16
4.7Executing the SP Ramp Function (limiting the SP change rate)
4.7 Executing the SP Ramp Function (limiting the SP change rate)
JSP ramp
With the SP ramp function, the controller operates according to the value
(set point during SP ramp) limited by a change rate. The interval in which
the set point during SP ramp is limited is referred to as the SP ramp".
SP
SP after change
SP before change
Change point
SP ramp
SP ramp set value
Time unit of ramp rate (min.)
Time
The change rate during SP ramp is specified by the SP ramp set value"
parameter. The SP ramp set value" default is OFF", and the SP ramp
function is disabled.
Changing of the ramp set point can be monitored in the set point during
SP ramp" parameter (operation level). Use this parameter during moniĆ
toring of the SP ramp.
Operation is the same also during switching of the set points by multi-SP.
Parameters
Symbol Parameters : Level Description
MV upper limit :
Advanced function setting level
MV lower limit :
Advanced function setting level
Set point upper limit:
Initial setting level
Set point lower limit:
Initial setting level
SP ramp set value:
Advanced function setting level
For limiting manipulated variable
For limiting manipulated variable
For limiting SP setting
For limiting SP setting
For limiting SP change rate
4–17
CHAPTER 4 APPLIED OPERATION
F Operation at start
F Restrictions
during SP ramp operation
If the SP ramp function is enabled when the E5AN is turned ON, and when
run" is switched to from stop," the process value may reach the set point
after SP ramp in the same way as when the set point is changed. In this
case, operation is carried out with the process value regarded as the set
point before the change was made.
The direction of the SP ramp changes according to the relationship
between the process value and the set point.
Set point
PV
PV < SP
SP SP
SP ramp
PV
Set point
Time
Power ON
PV > SP
SP ramp
Same change rate
Power ON
ĂExecution of autoĆtuning starts after the end of SP ramp.
ĂWhen control is stopped or an error occurs, the SP ramp function is disĆ
abled.
Time
4–18
4.8To Move to the Advanced Function Setting Level
4.8 To Move to the Advanced Function Setting Level
In the default setting, the advanced function setting level is protected and
it can not be moved to this setting level. To move to this setting level, canĆ
cel first the protection applied by the protect level." See 4.9ĂUsing the
Key Protect Level".
(1) Press the and keys simultaneously for at least three seconds
in the operation level."
Protect level
“operation/adjustment protection”
“initial setting/commu­nications protection”
Ă* The key pressing time can be changed in "protect level move time"
(advanced function level).
(2) The controller moves to the protect level, and operation/adjustment
protection" is displayed.
Operation level
Initial setting level
Advanced function setting level
PV/SP
Input type
Move to advanced function setting level
(3) Press the key once to move to initial setting/communications
protection."
(4) Set the set value to 0"
(5) Press the and keys simultaneously to return to the operaĆ
tion level."
(6) Press the key for at least three seconds to move to the initial setĆ
ting level" from the operation level."
(7) Select the Move to advanced function setting level" parameter by
pressing the key.
(8) Use the keys to input the password (-169"), and either
press the key or leave the setting for at least two seconds to move
to the advanced function setting level" from the initial setting
level."
4–19
CHAPTER 4 APPLIED OPERATION
L
l
level
4.9 Using the Key Protect Level
JKey protect
F Operation/adjust-
ment protection
ĂTo move to the protect level, press the and keys simultaneously
for at least three seconds.
Ă* The key pressing time can be changed in "protect level move time"
(advanced function level).
ĂThe protect level protects parameters that are not changed during conĆ
troller operation until operation is started to prevent them from being modified unintentionally.
ĂThe protect level setting restricts the range of parameters that can be
used.
The following table shows the relationship between set values and the
range of protection.
eve
PV f f f f
Operation
level
Adjustment level
PV/SP f Other
Set value
0 1 2 3
: Can be displayed and
changed f : Can be displayed : Cannot be displayed
and move to other levels
not possible
ĂWhen this parameter is set to 0", parameters are not protected.
ĂDefault is 0".
F Initial setting/
communications protection
F Setting change
protection
This protect level restricts movement to the initial setting level, commuĆ
nications setting level and advanced function setting level.
Set value
0 f f f 1 f f 2
Initial
setting level
Communications
setting level
Advanced function
setting level
f : Move to other
levels possible
: Move to other
levels not possible
ĂDefault is 1".
This protect level protects setup from being changed by operating the keys
on the front panel.
Set value Description
OFF Setup can be changed by key operation.
ON Setup cannot be changed by key operation. (The protect level can be
changed.)
ĂDefault is OFF".
4–20
CHAPTER5
CHAPTER 5
PARAMETERS
CHAPTER 5 PARAMETERS
Conventions Used in this Chapter 5Ć2. . . . . . . . . . . .
Meanings of icons used in this chapter 5Ć2. . . . . . . .
About parameter display 5Ć2. . . . . . . . . . . . . . . . . . . . .
About the Order in Which Parameters Are
Described in This Chapter 5Ć2. . . . . . . . . . . . . . . . . . .
Protect Level 5Ć3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation Level 5Ć4. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment Level 5Ć11. . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial Setting Level 5Ć19. . . . . . . . . . . . . . . . . . . . . . . . .
Advanced Function Setting Level 5Ć27. . . . . . . . . . . . .
Communications Setting Level 5Ć43. . . . . . . . . . . . . . .
5–1
Conventions Used in this Chapter
JMeanings of icons used in this chapter
Describes the functions of the parameter.
Function
Describes the setting range and defaults of the parameter.
Setting
Describes the monitor range.
Monitor
Describes the parameter operations.
Example of use
Describes related parameters and items.
See
JAbout parameter display
Parameters are displayed only when the Conditions of Use" on the right of the parameter headĆ ing are satisfied. However, note that the settings of protected parameters are still valid, and are not displayed regardless of the conditions of use.
The control must be 2-PID control.
Conditions of use
Displayed symbol
AT Execute/cancel
Parameter name
JAbout the Order in Which Parameters Are Described in This Chapter
Parameters are described level by level. The first page of each level lists the parameters available in that level. The parameter names in this list are listed in the order that they are displayed on the E5AN.
5–2
level
Protect Level
Three levels of protection are provided on the E5AN, operation/adjustment protection", initial setting/communications protection" and setting change protection." These protect levels preĆ vent unwanted operation of the keys on the front panel in varying degrees.
Power ON
Operation level
less than
1 second
To move from the operation Level to the protect level, press the and keys for at least three seconds.
Adjustment level
key
Control in progress
+ key 1 second min.
Protect level
3 seconds min.
Operation/adjustment protection
+ key
The settings of protected parameters are not displayed and so cannot be modified.
Protect level
Operation/adjustment protection
Initial setting/commuĆ nications protection
Setting change protection
Page
5-3
5-3
5-3
Initial setting/communications protection
Setting change protection
This parameter specifies the range of parameters to be protected. indicates the default.
FĂOperation/adjustment protection
The following table shows the relationship between set values and the range of
Function
Setting
protection.
Level
PV f f f f
Operation
PV/SP f Other
Adjustment level
Set value
0 1 2 3
: Can be displayed and changed f : Can be displayed : Cannot be displayed and move to
other levels not possible
ĂParameter items are not protected when the set value is set to 0".
FĂInitial setting/communications protection
Move to the initial setting level," communications setting level" and advanced
function setting level" is restricted.
Set value
0 f f f 1 f f 2
Initial
setting level
Communications
setting level
Advanced function
setting level
f : Move to other levels possible
: Move to other levels not
possible
FĂSetting change protection
Changes to setups by key operation are restricted.
Set value Description
OFF Setup can be changed by key operation.
ON Setup cannot be changed by key operation. (The protect level can be changed.)
5–3
CHAPTER 5 PARAMETERS
Operation Level
Display this level when you are to carry out control operations on the E5AN. You can set alarm values or monitor the manipulated variable in this level.
Power ON
Operation level
key
1 second
min.
Initial setting level
less than
1 sec.
Adjustment level
key
3 seconds min.key
No.1 display flashes.key
Control stops
Commu-
key
less than
1 sec.
nications setup level
Control in progress
Control stopped
This level is automatically displayed immediately after the E5AN is turned ON. To move to other levels, press the key or the and keys.
Operation level
Page
5-7
5-8
PV
PV/SP
Pag
5-5
5-5
Alarm value 2
UpperĆlimit alarm value 2
MultiĆSP
Set point during SP ramp
Heater current value monitor
Run/stop
Alarm value 1
UpperĆlimit alarm value 1
LowerĆlimit alarm value 1
5-5
5-6
5-6
5-7
5-7
5-8
5-8
LowerĆlimit alarm value 2
Alarm value 3
UpperĆlimit alarm value 3
LowerĆlimit alarm value 3
MV monitor (OUT1)
MV monitor (OUT2)
5-8
5-7
5-9
5-9
5-9
5-10
5–4
Operation Level
Function
Monitor
See
PV
The “additional PV display” parameter must be set to “ON”.
The process value is displayed on the No.1 display, and nothing is displayed (blank) on the No.2 display.
Monitor Range Unit
Process
Value
Input indication range (See page A-10.) EU
The decimal point position is dependent on the selected sensor.
FĂRelated parameters
Input type" (initial setting level) (p. 5Ć20) Set point upper limit" Set point lower limit" (initial setting level)
PV/SP
The process value is displayed on the No.1 display, and the set point is displayed on the No.2 display.
Function
See
Function
Monitor Range Unit
Process
Value
Set Point Set point lower limit to set point upper limit EU
Input indication range (See page A-10.) EU
Setting Range Unit
The decimal point position is dependent on the selected sensor.
Refer to the PV parameter
Multi-SP (set point 0 to 3)
The “multi-SP uses” parameter must be set to “ON”.
MultiĆSP allows you to set up to four set points (SP0 to 3) in adjustment level. These can be switched by operating the keys on the front panel or by external input signals (event input assignments). In the parameter, enter set points 0 to 3.
5–5
CHAPTER 5 PARAMETERS
Operation Level
Set point during SP ramp
This parameter monitors the set point during SP ramp.
Ramp" is a function for restricting the change width of the set point as a change rate. The set value is displayed when SP ramp set value" parameter (advanced function
Function
Monitor
See
setting level) is set. When the set point is out of the preset ramp, the set point is matched to the set point set in the PV/SP" parameter.
Monitor Range Unit
SP: Set point lower limit to set point upper limit EU
FĂRelated parameters
PV/SP" (operation level) (p. 5Ć5) SP ramp set value" (advanced function setting level) (p. 5Ć30) Set point upper limit" Set point lower limit" (initial setting level) (p. 5Ć22)
The “SP ramp set value” parameter must not be set to “OFF”.
Heater current value monitor
The “heater burnout” parameter must be set to “ON”.
This parameter measures the heater current value from the CT input used for detecting heater burnout.
Measures and displays the heater current value.
Function
Monitor Range Unit
0.0 to 55.0 A
Monitor
ĂWhen the current exceeds 55.0 A,  " is displayed.
FĂRelated parameter
Heater burnout detection" (adjustment level) (p. 5Ć13)
See
5–6
Operation Level
Run/Stop
This parameter specifies run and stop.
When  : run" is selected, control is running. When  : stop" is selected, conĆ trol is stopped. When control is stopped, the STOP display lights.
Function
See
Default is 
When the run/stop function is being controlled by event input, the run/stop function cannot be set by operating the keys on the front panel.
Alarm value 1 Alarm value 2 Alarm value 3
The run/stop function must not be set to event input assignments 1 and 2.
".
The alarm type must be set to either no alarm or a setting other than the upper- and lower­limit alarm. The control must be standard control. (Ony alarm value 3)
This parameter sets the input value X" in the alarm type list.
ĂThis parameter is used for setting the alarm values of alarm outputs 1, 2 to 3.
ĂDuring temperature input, the decimal point position is dependent on the currently
Function
Setting
See
selected sensor, and during analog input it is dependent on the decimal point" parameter setting.
Setting Range Unit Default
-1999 to 9999 EU 0
The alarm type must be set to other than upper and lower limit alarm.
FĂRelated parameters
Input type" (p. 5Ć20) Scaling upper limit" Scaling lower limit" Decimal point" (initial setting level) (p. 5Ć21) Alarm 1 to 3 type" (initial setting level) (p. 5Ć25) Alarm 1 to 3 open in alarm" Alarm 1 to 3 hysteresis" (p. 5Ć32 to 5Ć34) Standby sequence reset method" Alarm latch" (p. 5Ć31) (advanced function setting level)
5–7
CHAPTER 5 PARAMETERS
Operation Level
Upper-limit alarm value 1
Lower-limit alarm value 1
This parameter independently sets the upperĆ and lowerĆlimit alarm values when the mode for setting the upper and lower limits is selected for alarm 1 type (initial setting level).
ĂThis parameter sets the upper and lower limit values of alarm 1.
ĂDuring temperature input, the decimal point position is dependent on the currently
Function
Setting
See
selected sensor, and during analog input it is dependent on the decimal point"
parameter setting.
Setting Range Unit Default
-1999 to 9999 EU 0
FĂRelated parameters
Alarm 1 type" (initial setting level) (p. 5Ć25)
Standby sequence reset method" (p. 5Ć31) Alarm 1 open in alarm" (p. 5Ć32) Alarm
1 hysteresis" Alarm 1 latch" (p. 5Ć32) (advanced function setting level)
Alarm 1 type must be set to upper and lower limits, upper and lower limit range or upper­and lower-limit alarm with standby sequence.
Upper-limit alarm value 2
Lower-limit alarm value 2
This parameter independently sets the upperĆ and lowerĆlimit alarm values when the mode for setting the upper and lower limits is selected for alarm 2 type (initial setting level).
ĂThis parameter sets the upper and lower limit values of alarm 2.
ĂThe decimal point position is dependent on the currently selected sensor.
Function
Setting Range Unit Default
-1999 to 9999 EU 0
Setting
FĂRelated parameters
Alarm 2 type" (initial setting level) (p. 5Ć25)
See
Standby sequence reset method" (p. 5Ć31) Alarm 2 open in alarm" Alarm 2 hysterĆ
esis" Alarm 1 latch" (p. 5Ć33) (advanced function setting level)
Alarm 2 type must be set to upper and lower limits, upper and lower limit range or upper­and lower-limit alarm with standby sequence.
5–8
Operation Level
Upper-limit alarm value 3
The control must be standard control. Alarm 3 type must be set to upper and lower
Lower-limit alarm value 3
limits, upper and lower limit range or upper­and lower-limit alarm with standby sequence.
This parameter independently sets the upperĆ and lowerĆlimit alarm values when the mode for setting the upper and lower limits is selected for alarm 3 type (initial setting level).
ĂThis parameter sets the upper and lower limit values of alarm 3.
ĂThe decimal point position is dependent on the currently selected sensor.
Function
Setting Range Unit Default
-1999 to 9999 EU 0
Setting
FĂRelated Parameters
Alarm 3 type" (initial setting level) (p. 5Ć25)
See
Standby sequence reset method" (p. 5Ć31) Alarm 3 open in alarm" Alarm 3 hysterĆ
esis" Alarm 3 latch" (p. 5Ć34) (advanced function setting level)
MV monitor (OUT1)
Manipulated variable display must be set to “ON”.
This parameter is for monitoring the manipulated variable on the control output 1 side during operation.
ĂDuring standard control, the manipulated variable is monitored, and during heating
and cooling control, the manipulated variable on the heating side is monitored.
Function
Monitor
ĂDefault is OFF" and the manipulated variable is not displayed.
Control Monitor Range Unit
Standard 0.0 to 100.0 %
Heating and cooling 0.0 to 100.0 %
FĂRelated parameter
Manipulated variable display" (advanced function setting level) (p. 5Ć39)
See
5–9
CHAPTER 5 PARAMETERS
Operation Level
MV monitor (OUT2)
This parameter is for monitoring the manipulated variable on the control output 2 side during operation.
ĂDuring heating and cooling control, the manipulated variable on the control output
2 side (OUT 2" terminal output) is monitored.
Function
Control Monitor Range Unit
Heating and cooling 0.0 to 100.0 %
Monitor
FĂRelated parameters
Standard/heating and cooling" (initial setting level) (p. 5Ć23)
See
Manipulated variable display" (advanced function setting level) (p. 5Ć39)
The control must be heating and cooling con­trol. Manipulated variable display must be set to “ON”.
5–10
Adjustment Level
This level is for executing AT (autoĆtuning) or setting up the control. This level provides you with basic controller setup parameters for PID (proportional band, inteĆ gral time, derivative time) and heating and cooling control.
Power ON
Operation level
Less then 1 sec.
key
Adjustment level
Control in progress
To move to the adjustment level from the operation level, press the key for less than one second. ĂThe set points 0 to 3 in the adjustment level are set values for switching the set point during
multiĆSP input.
ĂHeater current value monitor and HBA detection are displayed when option unit
E5ANĆE53ĆAKB, E53ĆAK01, or E53ĆAK03 is mounted on the E5AN.
ĂYou can change adjustment level parameters by setting Operation/adjustment protection to
0". If the protect level is set to 1" to 3", adjustment level parameters cannot be displayed.
Adjustment level
AT execute/cancel
Communications writing
Page
5-12
5-12
LowerĆlimit temperaĆ ture input shift value
Proportional band
Page
5-15
5-16
Heater current value monitor
Heater burnout detection
Set point 0
Set point 1
Set point 2
Set point 3
Temperature input shift value
UpperĆlimit temperaĆ ture input shift value
5-13
5-13
5-14
5-14
5-14
5-14
5-15
5-15
Integral time
Derivative time
Cooling coefficient
Dead band
Manual reset value
Hysteresis (OUT1)
Hysteresis (OUT2)
5-16
5-16
5-17
5-17
5-18
5-18
5-18
5–11
CHAPTER 5 PARAMETERS
Adjustment Level
AT execute/cancel
This parameter executes AT (autoĆtuning).
ĂWhen autoĆtuning is executed the optimum PID parameters proportional band,"
integral time" and derivative time" for the set point during program execution are
Function
Example of use
See
automatically set by forcibly changing the manipulated variable to calculate the
characteristics of the control target.
ĂNormally, this parameter is set to  ". If you press the or keys, the paramĆ
eter is turned ON and AT is executed.
AT cannot be executed when control has stopped or during ON/OFF control.
ĂWhen AT execution ends, the parameter setting automatically returns to  ".
FĂRelated parameters
Proportional band" Integral time" Derivative time" (adjustment level) (p. 5Ć16)
PID / ON/OFF" (initial setting level) (p. 5Ć23)
The E5AN must be in operation, and control must be 2-PID control.
Function
Setting
See
Communications writing
The communication unit must be mounted on the E5AN.
This parameter enables/disables writing of parameters to the E5AN from the host
(personal computer) by communications.
ON : Writing enabled
OFF : Writing disabled
Default : OFF
FĂRelated parameters
MB command logic switching" (advanced function level) (p.5Ć42)
Communication unit No." Baud rate" Data bit" Parity" Stop bit" (communicaĆ
tions setting level) (p. 5Ć43)
5–12
Adjustment Level
Heater current value monitor
The “HBA used” parameter must be set to “ON”.
This parameter measures the current value of the heater from current transformer (CT) input to detect heater burnout.
This parameter measures and displays the current value of the heater.
Function
Monitor Range Unit
0.0 to 55.0 A
Monitor
Ă" " is displayed when 55.0A is exceeded.
FĂRelated parameters
Heater burnout detection" (adjustment level) (p. 5Ć13)
See
HBA used" (advanced function setting level) (p. 5Ć35)
Heater burnout detection
The “HBA used” parameter must be set to “ON”.
This parameter sets the current value for the heater burnout alarm output to become active.
ĂThis parameter outputs the heater burnout alarm when the heater current value falls
below this parameter setting.
Function
ĂWhen the set value is 0.0", the heater burnout alarm is OFF". When the set value
is 50.0", the heater burnout alarm is ON".
Setting Range Unit Default
0.0 to 50.0 A 0.0
Setting
FĂRelated parameters
HBA used" (advanced function setting level) (p. 5Ć35)
See
Heater current value monitor" (adjustment level) (p. 5Ć13)
Heater burnout latch" (advanced function setting level) (p. 5Ć35)
Heater burnout hysteresis" (advanced function setting level) (p. 5Ć35)
5–13
CHAPTER 5 PARAMETERS
Adjustment Level
Set point 0
Set point 1
The “number of multi-SP uses” parameter must be set to either “1” or “2”, and the “mul­ti-SP uses” parameter must be set to “ON”.
Set point 2
Set point 3
These parameters set the set points when the multiĆSP function is used.
The values set in these parameters can be selected by operating the keys on the front
panel or by event input.
Function
ĂWhen the set point has been changed, the set value of these parameters currently
set by multiĆSP is linked and changed.
ĂDuring temperature input, the decimal point position is dependent on the selected
sensor.
During analog input, the decimal point position is dependent on the setting of the
decimal point position" parameter.
Setting
See
Setting Range Unit Default
Set point lower limit to set point upper limit EU 0
FĂRelated parameters
Number of multiĆSP uses" (advanced function setting level) (p. 5Ć28)
Event input assignment 1" (advanced function setting level) (p. 5Ć29)
Event input assignment 2" (advanced function setting level) (p. 5Ć29)
MultiĆSP uses" (advanced function setting level) (p. 5Ć30)
PV/SP" (operation level) Input type" (operation level) (p. 5Ć5)
Input type" (initial setting level) (p. 5Ć20)
5–14
Adjustment Level
Temperature input shift
Sometimes an error between the set point and the actual temperature occurs. To offset this, a value obtained by adding an input shift value to the input is displayed as the measurement value and used for control.
The entire input range is shifted by a fixed rate (1Ćpoint shift). If the input shift value
is set to -1.0_C", the set point is controlled to a value obtained by subtracting 1.0_C
Function
Setting
See
from the actual temperature.
Setting Range Unit Default
-199.9 to 999.9 _C or _F 0.0
FĂRelated parameter
Input type" (initial setting level) (p. 5Ć20)
The “input type” parameter must be set to temperature input excluding a non-contact temperature sensor.
Upper-limit temperature input shift value
The “input type” parameter must be set to only the non-contact temperature sensor.
Lower-limit temperature input shift value
Whereas the entire input range is shifted by a fixed rate (1Ćpoint shift) in the temperature input shift" parameter, the input range is shifted by two points (2Ćpoint shift) at the upper and lower limits. 2Ćpoint shift enables more accurate offset of the input range compared with 1Ćpoint shift, if the input shift values at the upper and lower limits differ.
This parameter sets input shift values for each of the upper and lower limits (2Ćpoint
shift) of the input range.
Function
Setting Range Unit Default
-199.9 to 999.9 _C or _F 0.0
Setting
FĂRelated parameter
Input type" (initial setting level) (p. 5Ć20)
See
5–15
CHAPTER 5 PARAMETERS
Adjustment Level
Proportional band
The control must be 2-PID control.
Integral time
Derivative time
This parameter sets the PID parameters. Note that PID is automatically set when AT and ST are executed.
Proportional action : P refers to control in which the MV is proportional to the deviĆ
ation (control error).
Function
Integral action : I gives a control action that is proportional to the time integral
of the control error. With proportional control, there is norĆ
mally an offset (control error). So, proportional action is used
in combination with integral action. As time passes, this conĆ
trol error disappears, and the set point comes to agree with the
control temperature (process value).
Derivative action : D gives a control action that is proportional to the time derivaĆ
tive of the control error. As proportional control and integral
control correct for errors in the control result, the control sysĆ
tem will be late in responding to sudden changes in temperaĆ
ture. Derivative action enables control that is proportional to
a predicted process output to correct for future error.
Setting
See
Parameter Setting Range Unit Default
Proportional band 0.1 to 999.9 EU 8.0
Integral time 0 to 3999 Second 233
Derivative time 0 to 3999 Second 40
FĂRelated parameter
AT execute/cancel" (adjustment level) (p. 5Ć12)
5–16
Adjustment Level
Cooling coefficient
The control must be either heating and cool­ing control and 2-PID control.
If the heating and cooling characteristics of the control target greatly differ, preventing satisfacĆ tory control characteristics from being obtained by the same PID parameters, adjust the proporĆ tional band (P) at the control output 2 side by adding the cooling coefficient to balance control between the control output 1 and control output 2 sides.
In heating and cooling control, control output 2 side P is calculated by the following
formula to set the cooling coefficient:
Function
Setting
Control output 2 side P = Cooling coefficient P (proportional bounds)
Setting Range Unit Default
0.01 to 99.99 None 1.00
FĂRelated parameter
Proportional band" (adjustment level) (p. 5Ć16)
See
Dead band
The control system must be heating and cool­ing control.
This parameter sets the output dead band width in a heating and cooling control system. A negaĆ tive setting sets an overlap band.
ĂThis parameter sets an area in which the control output is 0" centering around the
set point in a heating and cooling control system.
Function
ĂThe decimal point setting follows the currently set sensor. During analog input, the
decimal point setting follows the decimal point position" setting.
Setting Range Unit Default
-199.9 to 999.9 EU 0.0
Setting
5–17
CHAPTER 5 PARAMETERS
Adjustment Level
Function
Setting
See
Manual reset value
The control must be standard control and 2-PID control. The “integral time” parameter must be set to “0”.
ĂThis parameter sets the required manipulated variable to remove offset during stabiĆ
lization of P or PD control.
Setting Range Unit Default
0.0 to 100.0 % 50.0
FĂRelated parameters
PID / ON/OFF" (initial setting level) (p. 5Ć23)
Integral time" (adjustment level) (p. 5Ć16)
Hysteresis (OUT1)
The control must be ON/OFF control.
Hysteresis (OUT2)
This parameter sets the hysteresis for ensuring stable operation at ON/OFF switching.
ĂIn a standard control, use the hysteresis (OUT1)" parameter. The hysteresis
(OUT2)" parameter cannot be used.
Function
ĂIn a heating and cooling control, the hysteresis can be set independently for heating
and cooling. Use the hysteresis (OUT1)" parameter to set the control output 1 side
hysteresis, and use the hysteresis (OUT2)" parameter to set the control output 2 side
hysteresis.
The decimal point setting follows the currently set sensor. During analog input, the
decimal point setting follows the decimal point position" setting.
Setting Range Unit Default
0.1 to 999.9 EU 1.0
5–18
Setting
FĂRelated parameter
PID / ON/OFF" (initial setting level) (p. 5Ć23)
See
Initial Setting Level
This level is for setting up the basic specifications of the E5AN. In this level, you can set the input type" parameter for selecting the sensor input to be connected to the E5AN, limit the setĆ ting range of set points or set the alarm mode.
Power ON
Operation level
key
1 second
min.
key
3 seconds
min.
Initial setting level
No.1 display flashes.key
Control stops
Control in progress
Control stopped
To move from the operation level to the initial setting level, press key for three seconds or more.
ĂThe initial setting level is not displayed when initial/communications protection" is set to
2". This initial setting level can be used when initial setting/communications protection" is set to 0" or 1".
ĂThe scaling upper limit", scaling lower limit" and decimal point" parameters are displayed
when analog input is selected as the input type.
Initial setting level
Input type
Scaling upper limit
Page
5-20
5-21
ST
Control period (OUT1)
Page
5-24
5-24
Scaling lower limit
Decimal point
_C/_F selection
Set point upper limit
Set point lower limit
PID / ON/OFF
Standard/heating and cooling
5-21
5-21
5-22
5-22
5-22
5-23
5-23
Control period (OUT2)
Direct/reverse operation
Alarm 1 type
Alarm 2 type
Alarm 3 type
Move to advanced function setting level
5-24
5-25
5-25
5-25
5-25
5-26
5–19
CHAPTER 5 PARAMETERS
thermometer
Thermocouple
p
sensor
Initial Setting Level
Input type
ĂThis parameter sets the sensor type by a corrensponding code.
ĂWhen this parameter is changed, the set point upper limit is changed to the default.
Function
Setting
If the set point limits must be changed, set the set point upper limit" and set point
lower limit" parameters (initial setting level).
ĂSet the code according to the following table. Shaded ranges indicate default settings.
The defaults are as follows.
Platinum resistance thermometer : 
Thermocouple : 
": platinum resistance thermometer Pt100
": K thermocouple
Input type Name
Platinum resistance thermometer resistance
Thermocouple
Platinum thermometer
Input type Name
Thermocouple K 0 -200 to 1300 (_C) / -300 to 2300 (_F)
input type
Non-contact temperature sensor ES1A
Analog input 0 to 50mV 16 One of following ranges depending on the
Set
Value
Pt100 0 -200 to 850 (_C) / -300 to 1500 (_F)
1 -199.9 t o 500.0 (_C)/ -199.9 to 900.0 (_F) 2 0.0 to 100.0 (_C) / 0.0 to 210.0 (_F)
JPt100 3 -199.9 to 500.0 (_C) / -199.9 to 900.0 (_F)
4 0.0 to 100.0 (_C) / 0.0 to 210.0 (_F)
Set
Value
1 -20.0 to 500.0 (_C) / 0.0 to 900.0 (_F)
J 2 -100 to 850 (_C) / -100 to 1500 (_F)
3 -20 to 400.0 (_C) / 0.0 to 750.0 (_F)
T 4 -200 to 400 (_C) / -300 to 700 (_F)
17 -199.9 to 400.0 (_C) / -199.9 to 700.0 (_F) E 5 0 to 600 (_C) / 0 to 1100 (_F) L 6 -100 to 850 (_C) / -100 to 1500 (_F)
U 7 -200 to 400 (_C) / -300 to 700 (_F)
18 -199.9 to 400.0 (_C) / -199.9 to 700.0 (_F)
N 8 -200 t o 1300 (_C) / -300 to 2300 (_F) R 9 0 to 1700 (_C) / 0 to 3000 (_F)
S 10 0 to 1700 (_C) / 0 to 3000 (_F) B 11 100 to 1800 (_C) / 300 to 3200 (_F)
K10 to 70_C 12 0 to 90 (_C) / 0 to 190 (_F)
K60 to 120_C 13 0 to 120 (_C) / 0 to 240 (_F) K115 to 165_C 14 0 to 165 (_C) / 0 to 320 (_F) K160 to 260_C 15 0 to 260 (_C) / 0 to 500 (_F)
Input Temperature Range
Input Temperature Range
results of scaling:
-1999 to 9999, -199.9 to 999.9,
5–20
See
FĂRelated parameters
_C/_F selection" Set point upper limit" Set point lower limit" (initial setting
level) (p. 5Ć22)
Initial Setting Level
Function
Setting
Scaling upper limit
The input type must be set to analog input.
Scaling lower limit
Decimal point
ĂThese parameters can be used when voltage input is selected as the input type.
ĂWhen voltage input is selected as the input type, scaling is carried out. Set the upper
limit in the scaling upper limit" parameter and the lower limit in the scaling lower
limit" parameter.
ĂThe decimal point" parameter specifies the decimal point position of parameters
(set point, etc.) whose unit is set to EU.
ĂScaling upper limit, Scaling lower limit
Parameter Setting Range Unit Default
Scaling upper limit Scaling lower limit +1 to 9999 None 100
Scaling lower limit -1999 to scaling upper limit -1 None 0
See
ĂDecimal point: Default is 0: 0 digits past decimal point"
Set value Setting Example
0 0 digits past decimal point 1234 1 1 digit past decimal point 123.4
FĂRelated parameter
Input type" (initial setting level) (p. 5Ć20)
5–21
CHAPTER 5 PARAMETERS
ppp
Initial Setting Level
Function
Setting
See
_C/_F selection
The input type must be set to temperature input.
ĂSet the temperature input unit to either of _C" or _F".
Setting Range Default
: _C / : _F
FĂRelated parameter
Input type" (initial setting level) (p. 5Ć20)
Set point upper limit Set point lower limit
Function
Setting
See
ĂThis parameter limits the upper and lower limits when the SP is set. The SP can be
set within the range defined by the upper and lower limit set values in the set point upper limit" and set point lower limit" parameters. The existing SP settings that are out of the range are forcibly changed to one of the upper or lower limit values (whichĆ ever is closest).
ĂWhen the temperature input type and temperature unit have been changed, the set
point upper limit and set point lower limit are forcibly changed to the upper and lower limits of the sensor.
ĂDuring temperature input, the decimal point position is dependent on the currently
selected sensor. During analog input, it is dependent on the decimal point" parameĆ ter setting.
Parameter Setting Range Unit Default
Set point upper limit Set point lower limit +1 to sensor range upper limit EU 1300
Platinum resistance thermometer EU 850
Set point lower limit Sensor range lower limit to set point upper limit -1 EU -200
FĂRelated parameters
Input type" (p. 5Ć20) _C/_F selection" (initial setting level) (p. 5Ć22)
5–22
Function
Setting
See
Initial Setting Level
PID / ON/OFF
ĂThis parameter selects 2ĆPID control or ON/OFF control.
ĂThe AT and ST tuning functions can be used in 2ĆPID control.
Setting Range Default
: 2-PID / : ON/OFF
FĂRelated parameters
AT execute/cancel" (p. 5Ć12) Manual reset" Hysteresis (OUT1)" Hysteresis
(OUT2)" (adjustment level) (p. 5Ć18)
ST stable range" (advanced function setting level) (p. 5Ć36)
Function
Setting
See
Standard/heating and
The E5AN must support alarm 3 output.
cooling
ĂThis parameter selects standard control or heating and cooling control as control
output 2.
ĂWhen heating and cooling control is selected, the alarm 3 output terminal ALM3"
is used for cooling side output. Therefore, alarm 3 cannot be used.
Setting Range Default
: Standard / : Heating and cooling
FĂRelated parameters
MV monitor (OUT1)" MV monitor (OUT2)" (operation level) (p. 5Ć9, 10)
Alarm value" (p. 5Ć7) UpperĆlimit alarm value 3" LowerĆlimit alarm value 3"
(operation level) (p. 5Ć9)
Hysteresis (OUT2)" (p.Ă5Ć18) Cooling coefficient" Dead band" (p.Ă5Ć17) (adjustĆ
ment level)
Control period (OUT2)" (initial setting level) (p. 5Ć24)
Alarm 3 type" (initial setting level) (p. 5Ć25)
Alarm 3 hysteresis" (p.Ă5Ć34) Alarm 3 open in alarm" (p.Ă5Ć34) (advanced function
setting level)
5–23
CHAPTER 5 PARAMETERS
Initial Setting Level
Function
Setting
See
ST self-tuning
The control must be set to temperature input, standard control and 2-PID control.
ĂThe ST (selfĆtuning) function executes tuning from the start of program execution
to calculate PID constants matched to the control target. When the ST function is in
operation, be sure to turn the power supply of the load connected to the control outĆ
put ON simultaneously with or before starting operation of the E5AN.
Parameter Setting Range Unit Default
ST
: ST function OFF / : ST function ON
None
FĂRelated parameters
ST stable range" (advanced function setting level) (p. 5Ć36)
Input type" (p. 5Ć20) PID / ON/OFF" (p. 5Ć23) (initial setting level)
Control period (OUT1)
The control must be set to 2-PID control.
Function
Setting
Control period (OUT2)
ĂThis parameter sets the output period. Set the control period taking the control charĆ
acteristics and the electrical life expectancy of the relay into consideration.
ĂIn a standard control system, use the control period (OUT1)" parameter. The conĆ
trol period (OUT2)" parameter cannot be used.
ĂWhenever control output 1 is the current output, control period (OUT1)" cannot be
used.
ĂIn a heating and cooling control system, the control period can be set independently
for heating and cooling. Use the control period (OUT1)" parameter to set the heatĆ
ing side control period, and use the control period (OUT2)" parameter to set the
cooling side control period.
Parameter Setting Range Unit Default
Control period (OUT1) 1 to 99 Second 20 Control period (OUT2) 1 to 99 Second 20
FĂRelated parameter
PID / ON/OFF" (initial setting level) (p. 5Ć23)
5–24
See
Function
Setting
Initial Setting Level
Direct/reverse operation
ĂDirect operation" refers to control where the manipulated variable is increased
according to the increase in the process value. Alternatively, reverse operation"
refers to control where the manipulated variable is increased according to the
decrease in the process value.
Setting Range Default
: Reverse operation/ : Direct operation
Function
Setting
See
Alarm 1 type
ĂSelect one of the following alarm 1 types:
Deviation/Deviation range/Absolute value
Refer to the alarm 2, 3 type list on the following page.
FĂRelated parameters
Alarm value 1" (operation level) (p. 5Ć7)
UpperĆlimit alarm value 1" LowerĆlimit alarm value 1" (operation level) (p. 5Ć8)
Standby sequence reset method" (p.Ă5Ć31) Alarm 1 open in alarm" Alarm 1 hysterĆ
esis" (p. 5Ć32) (advanced function setting level)
The alarm 1 type must be supported.
Function
Alarm 2 type
The alarm 2, 3 type must be supported. The control must be set to standard control.
Alarm 3 type
ĂSelect one of the following alarm 2, 3 types:
Deviation/Deviation range/Absolute value
5–25
CHAPTER 5 PARAMETERS
Set
Al
Initial Setting Level
Setting
See
Set
Value
arm Type
When X is positive When X is negative
0 Alarm function OFF
*1
1 Upper- and lower-limit (deviation)
2 Upper-limit (deviation)
3 Lower-limit (deviation)
*1
*1
Upper- and lower-limit range
4
(deviation) Upper- and lower-limit with
5
standby sequence (deviation) Upper-limit with standby
6
sequence (deviation) Lower-limit with standby
7
sequence (deviation)
8 Absolute-value upper-limit
9 Absolute-value lower-limit
Absolute-value upper-limit with
10
standby sequence Absolute-value lower-limit with
11
standby sequence
*1 : The upperĆ and lowerĆlimit values, expressed as L" and H", can be set independently for each alarm point with
set values 1, 4 and 5.
*2 : Set value : 1 UpperĆ and lowerĆlimit alarm
Case 1 Case 2 Case 3 (Normally ON)
LHSP LHSP
H < 0, L > 0
|H| < |L|
*3 : Set value : 4 UpperĆ and lowerĆlimit range
Case 1 Case 2 Case 3 (Normally OFF)
LHSP LHSP
H < 0, L > 0
|H| < |L|
*4 : Set value : 5 UpperĆ and lowerĆlimit alarm with standby sequence
*For the above upperĆ and lowerĆlimit alarm Ć In cases 1 and 2, the alarm is normally OFF if upperĆ and lowerĆlimit values of hysteresis overlap.
*5 : Set value : 5 UpperĆ and lowerĆlimit alarm with standby sequence
The alarm is normally OFF if upperĆ and lowerĆlimit values of hysteresis overlap.
H > 0, L < 0
|H| > |L|
H > 0, L < 0
|H| > |L|
LHSP
LHSP
LHSP
LHSP
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
*5
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
LHSP
LHSP
Ć In case 3, the alarm is normally OFF.
Alarm Output Operation
LH
SP
X
SP
X
SP
LH SP
LH
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
H < 0, L < 0
H < 0, L > 0
|H| y |L|
H > 0, L < 0
|H| x |L|
H < 0, L < 0 H < 0, L > 0
|H| y |L|
H > 0, L < 0
|H| x |L|
Output OFF
*2
ON OFF
ON OFF
*3
*4
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
X
SP
X
SP
X
SP
X
SP
X
0
X
0
X
0
X
0
ĂAlarm types are set independently for each alarm in the alarm 1 to 3 type" parameĆ
ters (initial setting level). Default is 2: UpperĆlimit alarm".
FĂRelated parameters
Alarm value 2, 3" (operation level) (p. 5Ć7) UpperĆlimit alarm value 2, 3" LowerĆlimit alarm value 2, 3" (operation level) (p. 5Ć8, 9) Standby sequence reset method" (p.Ă5Ć31) Alarm 2, 3 open in alarm" Alarm 2, 3 hysteresis" (p. 5Ć33, 34) "alarm 2, 3 latch" (p.5Ć40) (advanced function setting level)
5–26
Loading...