Omron E5AK - PROGRAMMABLE TYPE, E5AK-T User Manual

E5AK
Digital Controller
Digital Controller (Programmable Type)
User's Manual
(Programmable Type)
User's Manual
Cat. No. H088-E1-01A
Preface
The E5AKĆT is a highĆperformance programmable digital controller. The E5AKĆT alĆ lows the user to carry out the following:
Set program patterns to each step by time or ramp rise rate
Execute advance, hold and reset step operations
Execute continuous operation of all patterns and repeated operation of same patterns
Check the start of each step or program end time by signals.
Count time from the beginning of each step (time signal)
Select from many types of temperature and analog input (multiĆinput)
Support positionĆproportional control (positionĆproportional type controllers only)
Select output functions such as control output or alarm output (output assignment)
Use the HBA (heater burnout alarm) function (standard type controllers only)
Monitor the control loop by LBA (Loop Break Alarm)
Use the communications function
Calibrate input or transfer output
The E5AKĆT also features a watertight construction (NEMA4: equivalent to IP66).
This User's Manual describes how to use the E5AKĆT. Before using your E5AKĆT thoroughly read and understand this manual in order to ensure correct use. Also, store this manual in a safe place so that it can be retrieved whenever necessary.
PRECAUTIONS IN USING THE PRODUCT
When the product is used under the circumstances or environment below, ensure adĆ herence to limitations of the ratings and functions. Also, take countermeasures for safety precautions such as failĆsafe installations.
(1) Use under circumstances or environments which are not described in this user's manual.
(2) Use for nuclear power control, railway, air craft, vehicle, incinerator, medical equipment, enterĆ
tainment equipment, safety device, etc.
(3) Use for applications where death or serious property damage is possible and extensive safety preĆ
cautions are required.
About this manual
(1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system or transmitted,
in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
(2) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in this
manual is subject to change without notice.
(3) Every precaution has been taken in the preparation of this manual. Nevertheless, if you find any errors or omis-
sions, please contact the branch of OMRON or sales office listed at the end of this manual, and inform them of the catalog No. on the front cover.
I
Conventions Used in This Manual
JMeanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text exĆ planations. These abbreviations mean the following:
Symbol Term
PV Process value
SP (Present) set point *1
LBA Loop break alarm
HB Heater burnout
AT AutoĆtuning
EU Engineering unit *2
*1 In program pattern diagrams, the present SP is indicated.
*2 C, m, g and other units are indicated for scaled data. However, EU" is used as the minimum
unit for the data. For example, for 50.02 (m)", 1EU is taken as the minimum unit 0.01 (m).
JHow to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays and alphabet characters.
ABCDEFGHI J KLM
NOPQRSTUVWXYZ
J“Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explanations and how to apply functions.
II
JHow This Manual is Organized
Purpose Title Description
Learning about the gener-
al features of the E5AK-T
Chapteră1ăăINTRODUCĆ TION
This chapter describes the feaĆ tures of the E5AKĆT, names of parts, and typical functions.
Setting up
Basic E5AK-T operations
Applied E5AK-T opera-
tions
Using a Position-propor-
tional type controller
Communications with a
host computer
Chapteră2ăăPREPARAĆ TIONS
Chapteră3ăăBASIC OPERAĆ TION Chapteră5ăăPARAMETERS
Chapteră4ăăAPPLIED OPĆ ERATION Chapteră5ăăPARAMETERS
Chapteră4ăăAPPLIED OPĆ ERATION /4.1ăăSelecting the Control Method
Chapteră6ăăUSING THE COMMUNICATIONS FUNCTION
This chapter describes the operaĆ tions that you must carry out (e.g. installation, wiring and switch settings) before you can use the E5AKĆT.
These chapters describe using basic control examples how to use the front panel keys and how to view the display when setting the parameters of the major funcĆ tions for the E5AKĆT.
These chapters describes the imĆ portant functions of the E5AKĆT and how to use the parameters for making full use of the E5AKĆT.
This chapter describes how to use the functions related specifically to positionĆproportional type controllers.
This chapter mainly describes how to use the communications commands, and gives program examples.
Calibration
Troubleshooting
Chapteră7ăăCALIBRATION This chapter describes how the
user should calibrate the E5AKĆT.
Chapteră8ăăTROUBLEĆ SHOOTING
This chapter describes what to do if any problems occur.
III
PRECAUTIONS ON SAFETY
Marks For Ensuring Safe Use and Their Meanings
This manual uses the following marks to indicate precautions for ensuring that the E5AKĆT is used safely. The precautions indicated below describe important information regarding safety. Be sure to follow the instructions described in these precautions.
WARNING
Incorrect handling may cause death or injury.
WARNING
Do not touch the terminals while the power is ON. This may cause an electric shock.
IV
NOTICE
Be sure to observe these precautions to ensure safe use.
Do not use the product in places where explosive or flammable gases may be present.
Never disassemble, repair or modify the product.
Tighten the terminal screws properly.
Use the specified size of solderless terminals for wiring.
Use the product within the rated supply voltage.
Use the product within the rated load.
The life expectancy of the output relay varies considerably according to its switching capacity and
operating conditions. Be sure to use the output relay within its rated load and electrical life expecĆ tancy. If the output relay is used beyond its life expectancy, its contacts may become fused or burned.
If you remove the controller from its case, never touch nor apply shock to the electronic parts inside.
Do not cover the E5AKĆT. (Ensure sufficient space around the controller to allow heat radiation.)
Do not use the controller in the following places:
ĂPlaces subject to icing, condensation, dust, corrosive gas (especially sulfide gas or ammonia gas).
ĂPlaces subject vibration and large shocks.
ĂPlaces subject to splashing liquid or oil atmosphere.
ĂPlaces subject to intense temperature changes.
ĂPlaces subject to heat radiation from a furnace.
Be sure to wire properly with correct polarity of terminals.
When wiring input or output lines to your controller, keep the following points in mind to reduce the
influence from inductive noise:
ĂAllow adequate space between the high voltage/current power lines and the input/output lines.
ĂAvoid parallel or common wiring with high voltage sources and power lines carrying large currents.
ĂUsing separating pipes, ducts, and shielded line is also useful in protecting the controller, and its
lines from inductive noise.
Cleaning: Do not use paint thinner or organic solvents. Use standard grade alcohol to clean the prodĆ
uct.
Use a voltage (100 to 240 VAC at 50 to 60 Hz). At power ON, the prescribed voltage level must be
attained within two seconds.
Allow as much space as possible between the controller and devices that generate a powerful high
frequency (highĆfrequency welders, highĆfrequency sewing machines, etc.) or surge. These devices may cause malfunctions.
If there is a large powerĆgenerating peripheral device and any of its lines near the controller, attach
a surge suppressor or noise filter to the device to stop the noise affecting the controller system. In particular, motors, transformers, solenoids and magnetic coils have an inductance component, and therefore can generate very strong noise.
When mounting a noise filter on the power supply to the controller, be sure to first check the filter's
voltage and current capacity, and then mount the filter as close as possible to the controller.
V
Use within the following temperature and humidity ranges:
ĂTemperature: Ć10C to 55C, humidity: 35%RH to 85%RH (with no icing or condensation)
If the controller is installed inside a control board, the ambient temperature must be kept to under 55C, including the temperature around the controller. If the controller is subjected to heat radiation, use a fan to cool the surface of the controller to under 55C.
Store within the following temperature and humidity ranges:
ĂTemperature: Ć25C to 65C, humidity: 35%RH to 85%RH (with no icing or condensation)
Never place heavy objects on, or apply pressure to the controller that may cause it to deform and deteĆ
riorate during use or storage.
Avoid using the controller in places near a radio, television set, or wireless installation. These devices
can cause radio disturbances which adversely affect the performance of the controller.
VI
Table of Contents
Preface I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conventions Used in This Manual II. . . . . . . . . . . . . . .
Precautions on Safety V. . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 1 INTRODUCTION 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . .
This chapter introduces the names of parts on the E5AK-T and their functions. For details on how to use the controller and parameter settings, see Chapter 2 onwards.
1.1 Names of parts 1–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Input and Output 1–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Program 1–8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Parameters and Menus 1–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 About the Communications Function 1–12. . . . . . . . . . . . . . . . . . . . . . .
1.6 About Calibration 1–13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 2 PREPARATIONS 2–1. . . . . . . . . . . . . . . . . . . . . . . . . . .
This chapter describes the operations (e.g. setup, installation and wiring) you should carry out before turning the E5AK-T ON.
2.1 Setup 2–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Installation 2–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Wiring Terminals 2–8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 3 BASIC OPERATION 3–1. . . . . . . . . . . . . . . . . . . . . . . .
This chapter describes actual examples for understanding the basic operation of the E5AK-T.
3.1 Convention Used in this Chapter 3–2. . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Setting Input Specifications 3–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Setting Output Specifications 3–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Setting Alarm Type 3–10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Setting Patterns 3–14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 Protect Mode 3–19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7 Starting and Stopping Operation 3–21. . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 Adjusting Control Operation 3–22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 4 APPLIED OPERATION 4–1. . . . . . . . . . . . . . . . . . . . . .
This chapter describes each of the parameters required for making full use of the features of the E5AK-T. Read this chapter while referring to the parameter descriptions in chapter 5.
4.1 Selecting the Control Method 4–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Operating Condition Restrictions 4–7. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Ramp Rise Rate Setup Program 4–9. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Program Operation 4–13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 Wait Operation 4–16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6 Program output 4–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7 Setting Running Conditions 4–19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8 How to Use Event Input 4–21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.9 How to Use the Heater Burnout Alarm 4–23. . . . . . . . . . . . . . . . . . . . . .
4.10 LBA 4–26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.11 How to Use Transfer Output 4–28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 5 PARAMETERS 5–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
This chapter describes the parameters of the E5AK-T. Use this chapter as a reference guide.
Conventions Used in this Chapter 5–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protect Mode 5–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual Mode 5–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Level 0 Mode 5–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Program Mode 5–11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Level 1 Mode 5–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Level 2 Mode 5–24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setup Mode 5–30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Expansion Mode 5–38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Option Mode 5–46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration Mode 5–52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6–1. .
This chapter mainly describes communications with a host computer and com­munications commands.
6.1 Outline of the Communications Function 6–2. . . . . . . . . . . . . . . . . . . .
6.2 Preparing for Communications 6–3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Command Structure 6–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Commands and Responses 6–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 How to Read Communications Error Information 6–15. . . . . . . . . . . . .
6.6 Program Example 6–17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 7 CALIBRATION 7–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
This chapter describes procedures for each calibration operation. Read this chapter only when the controller must be calibrated.
7.1 Parameter Structure 7–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Calibrating Thermocouples 7–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 Calibrating Platinum Resistance Thermometers 7–7. . . . . . . . . . . . .
7.4 Calibrating Current Input 7–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.5 Calibrating Voltage Input 7–10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.6 Checking Indication Accuracy 7–12. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHAPTER 8 TROUBLESHOOTING 8–1. . . . . . . . . . . . . . . . . . . . . .
This chapter describes how to find out and remedy the cause if the E5AK-T does not function properly . Remedy E5AK-T trouble in the order of the descriptions in this chapter
8.1 Initial Checks 8–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.2 How to Use the Error Display 8–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.3 How to Use the Error Output 8–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.4 Checking Operation Restrictions 8–6. . . . . . . . . . . . . . . . . . . . . . . . . . .
APPENDIX
SPECIFICATIONS A–2. . . . . . . . . . . . . . . . . . . . . . . .
ABOUT CURRENT TRANSFORMER (CT) A–5. . .
CONTROL BLOCK DIAGRAM A–6. . . . . . . . . . . . . .
SETTING LIST A–8. . . . . . . . . . . . . . . . . . . . . . . . . . .
MODEL LIST A–12. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PARAMETER OPERATIONS LIST A–13. . . . . . . . . .
ASCII CODE LIST A–15. . . . . . . . . . . . . . . . . . . . . . . .
INDEX
REVISION HISTORY
CHAPTER1
CHAPTER 1
INTRODUCTION
This chapter introduces the names of parts on the E5AKĆT and their functions. For details on how to use the controller and parameter settings, see Chapter 2 onwards.
CHAPTER 1 INTRODUCTION
1.1 Names of parts 1Ć2. . . . . . . . . . . . . . . . . . . . . . . .
Main parts 1Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Front panel 1Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . .
About the displays 1Ć3. . . . . . . . . . . . . . . . . . . . .
How to use keys 1Ć4. . . . . . . . . . . . . . . . . . . . . . .
1.2 Input and Output 1Ć5. . . . . . . . . . . . . . . . . . . . . .
Input 1Ć5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Output 1Ć6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Program 1Ć8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
How programs are structured 1Ć8. . . . . . . . . . .
Program operation 1Ć8. . . . . . . . . . . . . . . . . . . . .
Alarm output 1Ć8. . . . . . . . . . . . . . . . . . . . . . . . . .
Program output 1Ć8. . . . . . . . . . . . . . . . . . . . . . . .
1.4 Parameters and Menus 1Ć9. . . . . . . . . . . . . . . . .
Parameter types 1Ć9. . . . . . . . . . . . . . . . . . . . . . .
Selecting modes 1Ć10. . . . . . . . . . . . . . . . . . . . . . . .
Selecting parameters 1Ć11. . . . . . . . . . . . . . . . . . .
Fixing settings 1Ć11. . . . . . . . . . . . . . . . . . . . . . . . .
1.5 About the Communications Function 1Ć12. . . .
1.6 About Calibration 1Ć13. . . . . . . . . . . . . . . . . . . . . .
1–1
CHAPTER 1 INTRODUCTION
1.1 Names of parts
JMain parts
Terminals
P 2-6
Rear case
JFront panel
Program state indica­tors
Bar graph
Operation st atus indicators
OUT1 SUB1 MANU HOLD WAIT
Run/Reset key Display key Down key Up key
RUN/RST
OUT2 SUB2 RMT RST AT
Front panel
This page
No.1 display
Pattern No.
No.2 display
E5AK
1–2
JAbout the displays
1.1 Names of parts
F No.1 display
F No.2 display
F Pattern No.
F Program status
indicators
F Operation status
indicators
Displays the process value or parameter symbols.
Displays the set point, manipulated variable or parameter settings.
Displays pattern No..
Indicate how the presentĆSP of the operating step changes.
ĂOUT1
Lights when the pulse output function assigned to control output 1" is ON.
ĂOUT2
Lights when the pulse output function assigned to control output 2" is ON.
ĂSUB1
Lights when the pulse output function assigned to auxiliary output 1" is ON.
ĂSUB2
Lights when the pulse output function assigned to auxiliary output 2" is ON.
ĂMANU
Lights in the manual operation mode.
ĂRST
Lights when the control is in reset status.
ĂRMT
Lights during remote operation.
ĂHOLD
Lights when the program is in hold status.
ĂWAIT
Lights when the program is in wait status.
ĂAT
Flashes during autoĆtuning.
F Bar graph
ĂThis bar graph indicates how much of the pattern has elapsed in 20% inĆ
crements (five stages) per single segment.
1–3
CHAPTER 1 INTRODUCTION
JHow to use keys
RUN/RST
F key
F key
F key
The following describes basic key operations.
To change to run operation from the reset status, press this key for one seĆ
cond minimum.
To change to the reset status from run operation, press this key for two seĆ
conds minimum.
The functions of this key change according to how long it is pressed. If the
key is pressed for less than one second, the parameters are switched. If the
key is pressed for one second minimum, the menu display appears. In key
operations from here on, press the key" refers to pressing the key for less
than one second.
For details on switching of parameters and menu display items, see page
1Ć10.
Each press of key increments or advances the values or settings on the
No.2 display, while each press of the key decrements or returns the
values or settings on the No.2 display.
Functions vary, for example, when the
RUN/RST
key is held down simultaĆ
neously with the key, or a key is held down continuously. For details,
see page 1Ć10. Also, chapters 3 and 4 describe examples using various key
combinations.
1–4
1.2 Input and Output
1.2 Input and Output
Temperature input Voltage input Current input
CT input Potentiometer
Event input
Controller
Control output (heat)
Control output (cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Time signal 1
Time signal 2
Program end
Stage output
Error 1
Error 2
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
Transfer output
JInput
The E5AKĆT supports the following inputs:
Temperature input, Current input, Voltage input, CT input/potentiomeĆ
ter, and Event input.
F Temperature input/Voltage input/Current input
ĂOnly one of temperature input, current input and voltage input can be
selected and connected to the controller.
ĂThe following input sensors can be connected for temperature input:
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII Platinum resistance thermometer: JPt100, Pt100
ĂThe following currents can be connected for current input:
4 to 20 mA, 0 to 20 mA
ĂThe following voltages can be connected for voltage input:
1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC
F CT input/Poten-
tiometer
ĂConnect CT input when using the HBA (heater burnout alarm) function
on a standard type controller (E5AKĆTAA2). Note that CT input cannot be used when the linear output unit is mounted.
ĂConnect the potentiometer when monitoring the valve opening on a
positionĆproportional type controller (E5AKĆTPRR2).
1–5
CHAPTER 1 INTRODUCTION
F Event input
JOutput
F Output assign-
ments
Add on the input unit (E53ĆCKB) when using event input. You can select
from the following six event inputs:
Run/Reset, Remote/Local, Auto/Manual, Hold/Hold Cancel, Advance, Pattern
The output functions of the E5AKĆT do not operate for five seconds after the E5AKĆT is turned ON.
The E5AKĆT supports the following five outputs:
Control output 1 Control output 2 Auxiliary output 1 Auxiliary output 2 Transfer output
When using control output 1 and 2, set the output unit (sold separately).
Nine output units are available to suit the output circuit configration.
When using transfer output, add on the communication unit (E53ĆAKF).
ĂThe E5AKĆT supports the following thirteen output functions:
Control output (heat), Control output (cool), Alarms 1 to 3, HBA, LBA, Time Signals 1 and 2, Program End, Stage Output, Error 1 (input error), Error 2 (A/D converter error)
ĂAssign these output functions to control output 1, control output 2, auxĆ
iliary output 1, and auxiliary output 2. However, note that as control output 1 is used as the open output and control output 2 is used as close output on a positionĆproportional type controller (E5AKĆTPRR2), control outputs 1 and 2 cannot be used as asĆ signment destinations. Also, of the output functions, control output (heat), control output (cool), HBA and LBA are disabled.
ĂOn a standard type controller, there are restrictions on how assignment
destinations (control output 1, control output 2, auxiliary output 1, and auxiliary output 2) can be used. For details, see Chapter 3 Basic OperaĆ tion/3.3 Setting Output Specifications (page 3Ć7).
ĂIn the example on the previous page, control output (heat)" is assigned
to control output 1", alarm 1" is assigned to control output 2", and alarm 2" is assigned to auxiliary output 1". Accordingly, the configuĆ ration is such that heating control output is connected to control output 1, and alarm output is connected to control output 2 and auxiliary outĆ put 1.
ĂControl outputs 1 and 2 are used depending on the differences in control
method as follows:
1–6
1.2 Input and Output
F Transfer output
Control Method Model
Standard control E5AK-TAA2 AC100-240
E5AK-TAA2 AC/DC24
Heating and cooling control
Position-propor­tional control
ĂThe E5AKĆT supports the following five transfer outputs:
Set point, Process value, Heating side manipulated variable,
Cooling side manipulated variable, Valve opening
However, note that heating/cooling side manipulated variables can be outĆ
put only on standard type controllers, and valve opening can be output
only on positionĆproportional type controllers.
ĂThese transfer outputs can be output after being scaled. Setting of an upĆ
per limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out.
E5AK-TAA2 AC100-240 E5AK-TAA2 AC/DC24
E5AK-TPRR2 AC100-240 E5AK-TPRR2 AC/DC24
Control Output 1/
Control Output 2
Control output (heat) / Alarm, etc.
Control output (heat) / Control output (cool)
Open/Close
1–7
CHAPTER 1 INTRODUCTION
1.3 Program
JHow programs
are structured
E5AKĆT allows you to configure programs made up of a maximum of eight
patterns (pattern 0 to 7).
The number of steps (16 maximum) in each pattern can be specified in paĆ
rameters.
Pattern 7
Pattern 1
Pattern 0
Step 0 Step 1 Step 2 Step 15
ĂGenerally, the time setup method" is used to configure programs. By
this method, set points at each step and time are used as program eleĆ ments. However, the ramp rise rate setup method" can also be used. By this method, the set point, ramp time and soak times are used as program elements.
JProgram opera-
tion
F Step operation
F Wait operation
JAlarm output
JProgram output
1–8
ĂGenerally, the target patterns are specified before the program is
executed.
ĂIn parameter setup, you can specify repeated execution of the same patĆ
tern (Repeat) or consecutive execution of all patterns 0 to 7 (Run all).
ĂDuring program operation, steps can be skipped (Advance) and the conĆ
trol monitoring can be paused (Hold).
ĂWhen the wait width is specified in parameter setup, the program does
not go to the next step and waits until the PV reaches the specified time (wait width) at the end of each step.
ĂAlarms that are assigned as outputs operate referenced to the alarm valĆ
ues preset to each pattern.
ĂTime signals, program end and stage output can be output according to
output assignment.
ĂON/OFF signals are output as time signals according to the timer that
takes a specified step as its start point.
1.4 Parameters and Menus
1.4 Parameters and Menus
JParameter types
F Protect mode
F Manual mode
E5AKĆT parameters are distributed between the following ten modes:
Protect mode Manual mode Level 0 mode Program mode Level 1 mode Level 2 mode Setup mode Expansion mode Option mode Calibration mode
The settings of parameters in each of eight modes (excluding the protect
mode and manual mode) can be checked and modified by selection on the
menu display.
The protect function is for preventing unwanted modification of parameĆ
ters, and switching between run and reset operation or auto and manual
operation.
In this mode, the controller can be switched to manual operation. The maĆ
nipulated variable can be manipulated manually only in this mode.
F Level 0 mode
F Program mode
F Level 1 mode
F Level 2 mode
F Setup mode
Set the controller to this mode during normal operation. In this mode, you
can change the set point and pattern during operation, and execute step
operation (e.g. advance). You can only monitor (not change) the process
value, step No., standby time, pattern elapsing time, pattern execution
count and manipulated variable.
This is the programming mode. In this mode, you can set the number of
steps used in each pattern, pattern execution count, alarm values, set
points for each step, step time, and time signals for two steps.
This is the main mode for adjusting control. In this mode, you can execute
AT (autoĆtuning), and set up the control period, PID parameters and heatĆ
er burnout alarm (HBA) conditions.
This is the auxiliary mode for adjusting control. In this mode, you can set
the parameters for limiting the manipulated variable, switch between the
remote and local modes, and set the loop break alarm (LBA), alarm hysterĆ
esis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you can set parameters that must be checked or set before operation such as the input type, scaling, output assignments and direct/reverse operation.
1–9
CHAPTER 1 INTRODUCTION
F Expansion mode
F Option mode
F Calibration mode
JSelecting modes
This is the mode for setting expanded functions. In this mode, you can set SP setting limitter, switching between advanced PID control or ON/OFF control, program time unit, selection of step time/rate of rise programĆ ming, time unit of ramp rise rate, and the time for automatic return to the monitoring display.
This is the mode for setting optional functions. You can select this mode
only when an option unit is mounted in the controller. In this mode, you
can set the communications conditions, transfer output and event input
parameters to match the type of option unit mount in the controller. HeatĆ
er burnout alarm function and positionĆproportional travel time are also
located in this mode.
This mode is provided so that the user can calibrate inputs and output.
When calibrating input, the selected input type is calibrated. Whereas,
transfer output can be calibrated only when the communication unit
(E53ĆAKF) is set in the controller.
The following diagram shows the order in which modes are selected.
Power ON
+
1 second min.
Level 0 mode
1 second min.
Manual mode
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
Program mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
RUN/RST
1 second min.
RUN/RST
1 second min.
+
Protect mode
+
+
1 second min.
RUN/RST
1 second min.
+
ĂTo select the menu display in any of the above modes (excluding the proĆ
tect mode and manual mode), press the key for 1 second minimum. When you have selected the menu display, the previous mode is selected. For example, if you selected the menu display while in the level 0 mode, the No.2 display changes to [ ] as shown on the left.
ĂTo move to the desired mode after you have entered the menu display,
select the desired mode using the keys and hold down the key for one second minimum. The display switches to the first parameter of the mode that you specified.
1–10
1.4 Parameters and Menus
ĂProtected modes cannot be selected. Also, the menu display does not apĆ
pear when modes are protected up to the program mode.
ĂIf you select [ ], [ ], [ ] or [ ] in the menu display, the
level 0, program, level 1 and level 2 modes, respectively, are selected. These modes are selected with control still continuing.
ĂIf you select[ĂĂ ] [ĂĂ ] [ĂĂ ] or [ĂĂ ] in the menu display, the
setup, expansion, option and calibration modes, respectively, are seĆ lected. When these modes are selected, the control is reset. So, control outputs and auxiliary output are turned OFF. When another mode is selected while in these modes control, reset is canceled.
ĂTo set the controller to the protect mode or to return to the level 0 mode
from the protect mode, press the
neously for 1 second minimum.
ĂTo set the controller to the manual mode, press the key for one seĆ
cond minimum with the key held down in the level 0 to 2 modes. To return to the level 0 mode in the manual mode, press the key for one second minimum with the key pressed. Be sure to press the key first in this operation.
RUN/RST
key and the key simultaĆ
JSelecting
parameters
JFixing settings
ĂWhen the controller is not in the manual mode, each press of the key
switches the parameter in the respective mode.
Parameter
1
ĂIf you press the key when at the final parameter, the display returns
to the top parameter for the current mode.
ĂWhen you change parameter settings or contents, specify the parameter
using the or keys, and either leave the setting for at least two seconds or press the key. This fixes the setting.
ĂWhen another mode is selected, the content of the parameters before the
mode was selected is fixed.
ĂWhen you turn the power OFF, you must first fix the settings and paramĆ
eter contents (by pressing the key or selecting another mode). The settings and parameter contents are sometimes not changed by merely pressing the or keys.
Parameter
2
Parameter
3
Parameter
n
1–11
CHAPTER 1 INTRODUCTION
1.5 About the Communications Function
The E5AKĆT can be provided with a communications function that allows
you to check and set controller parameters from a host computer. If the
communications function is required, add on the communications unit.
For details on the communications function, refer to Chapter 6.
F RS-232C
F RS-422
F RS-485
When using the communications function on the RSĆ232C interface, add
on the communications unit (E53ĆAK01).
When using the communications function on the RSĆ422 interface, add on
the communications unit (E53ĆAK02).
When using the communications function on the RSĆ485 interface, add on
the communications unit (E53ĆAK03).
1–12
1.6 About Calibration
The E5AKĆT controller is calibrated before shipment from the factory. So,
the user need not calibrate the E5AKĆT controller during regular use.
However, if the E5AKĆT controller must be calibrated by the user, use the
parameters provided for the user to calibrate temperature input, analog
input (voltage, current) and transfer output. In this case, note that the reĆ
sults of calibration will not be assured.
Also, note that calibration data is updated to the latest value each time
that the E5AKĆT controller is calibrated. Calibration data set before shipĆ
ment from the factory cannot be returned to after calibration by the user.
1.6 About Calibration
F Calibrating
inputs
F Calibrating trans-
fer output
F Registering cal-
ibration data
The input type selected in parameters is the item to be calibrated. The
E5AKĆT is provided with the following four calibration parameters:
ĂThermocouple
ĂPlatinum resistance thermometer
ĂCurrent input
ĂVoltage input
Two parameters are provided for thermocouple and voltage input.
Transfer output also can be calibrated when the communications unit
(E53ĆAKF) is added on.
When calibrating each item, the calibration data is temporarily regisĆ
tered. This data can be registered as final calibration data only when all
items have been newly calibrated. So, all items must be temporarily regisĆ
tered when the E5AKĆT controller is calibrated.
When registering data, information regarding whether or not calibration
has been carried out is also registered.
To calibrate these items, the user must prepare separate measuring deĆ
vices and equipment. For details on handling these measuring devices and
equipment, refer to the respective manuals.
For details, see Chapter 7 Calibration.
1–13
CHAPTER 1 INTRODUCTION
1–14
CHAPTER2
CHAPTER 2
PREPARATIONS
This chapter describes the operations (e.g. setup, installation and wirĆ ing) you should carry out before turning the E5AKĆT ON.
CHAPTER 2 PREPARATIONS
2.1 Setup 2Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DrawĆout 2Ć2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up the output unit 2Ć3. . . . . . . . . . . . . .
Setting up the option unit 2Ć4. . . . . . . . . . . . . . .
2.2 Installation 2Ć5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions 2Ć5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Panel cutout 2Ć5. . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 2Ć6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Wiring Terminals 2Ć8. . . . . . . . . . . . . . . . . . . . . .
Terminal arrangement 2Ć8. . . . . . . . . . . . . . . . .
Precautions when wiring 2Ć8. . . . . . . . . . . . . . .
Wiring 2Ć8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2–1
CHAPTER 2 PREPARATIONS
2.1 Setup
ĂOn a standard type controller, set up the output units for control outputs
1 and 2 before mounting the controller.
ĂOn a positionĆproportional type controller, the relay output unit is alĆ
ready mounted. So, this setup operation is unnecessary. (That is, do not replace the currently mounted unit with other output units.)
ĂWhen setting up the output units, draw out the internal mechanism
from the housing, and insert the output units into the sockets for control outputs 1 and 2.
JDraw-out
When drawing out the internal mechanism from the housing, prepare a
Phillips screwdriver matched to the size of the screw on the lower part of
the front panel.
(1) Press down on the hook on the top of the front panel, and turn the
Phillips screwdriver to the left to loosen the screw on the lower part
of the front panel.
Fixing Screw for Front Panel
2–2
(2) Draw out the internal mechanism towards you holding both sides of
the front panel.
Tighten this screw by a torque of 0.3 to 0.5 Nm (approx. 3 to 5 kgf⋅cm).
JSetting up the output unit
2.1 Setup
F Before setup
F Procedure
ĂCheck the type of the output unit you are about to set up.
ĂFor details on types of output unit and main specifications, see page 2Ć7.
(1) Check the positions of the sockets you are about to insert the output
units into as shown in the following diagram.
OUT1 OUT2
Bracket
(2) Insert the output unit for control output 1 into the socket OUT1"
and the output unit for control output 2 into the socket OUT2".
(3) Fasten the output units with the bracket (accessory).
2–3
CHAPTER 2 PREPARATIONS
JSetting up the option unit
F Before setup
F Procedure
ĂCheck the type of the option unit you are about to set up.
ĂFor details on types of option unit and main specifications, see Appendix,
Model List (page AĆ12) and Appendix, Option Unit Ratings and CharacĆ teristics (page AĆ4).
ĂFor details on the relationship between units and terminals, see page
2Ć8.
(1) Remove the power board and option boards in the order shown in the
following diagram.
2
1
(2) Insert the option units into the sockets for options 1 to 3. The followĆ
ing diagram shows the relationship between option units and mountĆ
ing positions.
Option 1 E53–AKB: Event inputs 1/2 E53–AK01: RS–232C
Option 2 E53–AKF: Transfer output
E53–AK02: RS–422 E53–AK03: RS–485
Option 3 E53–AKB: Event inputs 3/4
(3) Mount the option boards and the power board in the order shown.
2–4
2.2 Installation
JDimensions
96 13.5 100
2.2 Installation
91
112
JPanel cutout
Unit (mm)
120 min.
92
+0.8
0
110 min.
+0.8
92
ĂRecommended panel thickness is 1 to 8
mm.
ĂMaintain the specified vertical and horiĆ
zontal mounting space between each conĆ
0
troller. Controllers must not be closely mounted vertically or horizontally.
2–5
CHAPTER 2 PREPARATIONS
JMounting
(1) Insert the E5AKĆT controller into the mounting hole in the panel.
(2) Fit the mounting bracket (accessory) into the fixing slots on the top
and bottom of the rear case.
(3) Tighten the mounting bracket screws alternately a little at a time unĆ
til the ratchet starts to slide.
2–6
Loading...
+ 173 hidden pages