Omron E5AK User Manual

E5AK
Digital Controller
User's Manual
Cat. No. H083-E1-03
Preface
Select from many types of temperature and analog input (multiple input)
Support position-proportional control (position-proportional type controllers
only).
Select output functions such as control output or alarm (output assignment)
Use the HBA (heater burnout alarm) function (standard type controllers only).
Use four setpoints (multi-SP function)
UseremoteSPinput.
Monitor the control loop by LBA (Loop Break Alarm)
Use the communications function
Calibrate input or transfer output
It also features a watertight construction (NEMA4: equivalent to IP66)
This User’s Manual describes how to use the E5AK compact, high-function digital controller. Before using your E5AK, thoroughly read and understand this manual in order to ensure correct use.
About this manual
E OMRON, 1996 (1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or trans-
mitted, in any form, or by any means, mechanical, electronic, photocopying, recording, recording, or other-
wise, without the prior written permission of OMRON. (2) No patent liability is assumed with respect to the use of the information contained herein. (3) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in
this manual is subject to change without notice. Every precaution has been taken in the preparation of this
manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability
assumed for damages resulting from the use of the information contained in this publication.
I
Conventions Used in This Manual
JMeanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text explanations. These abbreviations mean the following.
Abbreviation Term
PV Process value
SP Set point
RSP Remote set point
LSP Local set point
LBA Loop break alarm
HB Heater burnout
AT Auto -tuning
ST Self-tuning
JHow to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays and alphabet characters.
ABCDEFGH I JKLM
NOPQRS TUVWXYZ
J“Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explana­tions and how to apply functions.
II
JNotice:
OMRON p roducts are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Al­ways heed the information provided with them. Failure to heed precautions can result in inju­ry to people or damage to the product.
DANGER
!
! WARNING
!Caution
Indicates information that, if not heeded, is likely to result in loss of life or serious injury.
Indicates information that, if not heeded, could possibly result in loss of life or serious injury.
Indicates information that, if not heeded, could result in relatively serious or minor injury, damage to the product, or faulty operation.
III
JHow this Manual is Organized
Purpose Title Description
D Learning about the gen-
eral features of the E5AK
Chapter 1 Introduction This chapter describes the fea-
tures of the E5AK, names of parts, and typical functions.
D Setting up the E5AK
D Basic E5AK operations
D Applied E5AK operations
D Using a Position-propor-
tional Type Controller
D Communications with a
host computer
Chapter 2 Preparations This chapter describes the
operations that you must carry out (e.g. installation, wiring and switch settings) before you can use the E5AK.
Chapter 3 Basic Operation Chapter 5 Parameters
Chapter 4 Applied Opera­tion Chapter 5 Parameters
Chapter 4 Applied Opera­tion/4.1 Selecting the Con­trol Method
Chapter 6 Using the Com­munications Function
These chapters describe how to use the front panel keys and how to view the display when setting the parameters of the major functions for the E5AK.
These chapters describe the important functions of the E5AK and how to use the parameters for making full use of the E5AK.
This chapter describes the func­tions related specifically to posi­tion-proportional type control­lers.
This chapter mainly describes the communications commands, and gives program examples.
D Calibration
D Troubleshooting
IV
Chapter 7 Calibration This chapter describes how the
user should calibrate the E5AK.
Chapter 8 Troubleshooting This chapter describes what to
do if any problems occur.
PayAttention to the Following when Installing this Controller
F If you remove the controller from its case, never touch nor apply shock to the elec-
tronic parts inside.
F Do not cover the area around the E5AK. (Ensure sufficient space around the control-
ler to allow heat radiation.)
F Use a voltage (AC100-240V
scribed voltage level must be attained within two seconds.
F When wiring input or output lines to your controller, keep the following points in
mind to reduce the influence from inductive noise:
Allow adequate space between the high voltage/current power lines and the input/ output lines.
Avoid parallel or common wiring with high voltage sources and power lines carrying large currents.
Using separating p ipes, duct, and shielded line is also useful in protecting the con­troller, and its lines form inductive noise.
F Allow as much space as possible between the controller and devices that generate a
powerful, high frequency (high-frequency welders, high-frequency sewing machines, and so forth) or surge. These devices may cause malfunctions.
F If there is a large power-generating peripheral device and any of its lines, attach a
surge suppressor or noise filter to the device to stop the noise affecting the controller system. In particular, motors, transformers, solenoids and magnetic coils have an inductance component, and therefore can generate very strong noises.
F When mounting a noise filter, be sure to first check the filter’s voltage and current
capacity, then mount the filter as close as possible to the controller.
F Do not use the controller in places where icing, condensation, dust, corrosive gas
(especially sulfurized gas or ammonia gas), shock, vibration, splashing liquid, or oil atmosphere occur. Also, avoid places where the controller can be subjected to intense heat radiation (like from a furnace) or sudden temperature changes.
or AC/DC24V at 50 to 60 Hz). At power ON, the pre-
F Ambient temperature must be kept between -10_Cto55_C. Ambient humidity must
be kept between 35%RH to 85%RH (with no icing or condensation). If the controller is installed inside a control board, the ambient temperature must be kept under 55_C, including the temperature around the controller. If the controller is subjected to heat radiation, use a fan to cool the surface of the controller to under 55_C.
F Store the controller at an ambient temperature between -25_Cto65_C. T he amb ient
humidity must be between 35%RH to 85%RH (with no icing or condensation).
F Never place heavy objects on, or apply pressure to the controller that may cause it to
deform and deterioration during use or storage.
F Avoid using the controller in places near a radio, television set, or wireless installa-
tion. These devices can cause radio disturbances which adversely affect the perfor­mance of the controller.
V
Table of Contents
Preface I......................................
Conventions Used in This Manual II...............
Pay Attention to the Following when Installing
this Controller V.................................
CHAPTER 1 INTRODUCTION 1--1...........................
This chapter introduces the E5AK. First-time users should read this chapter with­out fail. For details on how to use the controller and parameter settings, see Chapters 2 onwards.
1.1 Names of parts 1--2..........................................
1.2 Input and Output 1--4.........................................
1.3 Parameters and Menus 1--7...................................
1.4 About the Communications Function 1--10.......................
1.5 About Calibration 1--11........................................
CHAPTER 2 PREPARATIONS 2--1...........................
This chapter describes the operations you should carry out before turning the E5AK ON.
2.1 Setting up 2--2...............................................
2.2 Installation 2--5..............................................
2.3 Wiring Terminals 2--8.........................................
CHAPTER 3 BASIC OPERATION 3--1........................
This chapter describes an actual example for understanding the basic operation of the E5AK.
3.1 Convention Used in this Chapter 3--2...........................
3.2 Setting Input Specifications 3--4...............................
3.3 Setting Output Specifications 3--6..............................
3.4 Setting Alarm Type 3--9.......................................
3.5 Protect Mode 3--12............................................
3.6 Starting and Stopping Operation 3--13...........................
3.7 Adjusting Control Operation 3--14...............................
CHAPTER 4 APPLIED OPERATION 4--1......................
This chapter describes each of the parameters required for making full use of the features of the E5AK. Read this chapter while referring to the parameter descrip­tions in chapter 5.
4.1 Selecting the Control Method 4--2..............................
4.2 Operating Condition Restrictions 4--5...........................
4.3 How to Use Event Input 4--8..................................
4.4 How to Use the Remote SP 4--11...............................
4.5 How to Use the Heater Burnout Alarm 4--13......................
4.6 LBA 4--15....................................................
4.7 How to Use Transfer Output 4--17...............................
CHAPTER 5 PARAMETERS 5--1.............................
This chapter describes the parameters of the E5AK. Use this chapter as a refer­ence guide.
Protect Mode 5--3................................................
Manual Mode 5--5................................................
Level 0 Mode 5--6................................................
Level 1 Mode 5--10................................................
Level 2 Mode 5--18................................................
Setup Mode 5--25.................................................
Expansion Mode 5--32.............................................
Option Mode 5--37.................................................
Calibration Mode 5--46.............................................
CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6--1..
This chapter mainly describes communications with a host computer and com­munications commands.
6.1 Outline of the Communications Function 6--2....................
6.2 Preparing for Communications 6--3............................
6.3 Command Configuration 6--5..................................
6.4 Commands and Responses 6--6...............................
6.5 How to Read Communications Error Information 6--12.............
6.6 Program Example 6--14.......................................
CHAPTER 7 CALIBRATION 7--1.............................
This chapter describes procedures for each calibration operation. Read this chapter only when the controller must be calibrated.
7.1 Structure of Parameters 7--2..................................
7.2 Calibrating Thermocouple 7--4.................................
7.3 Calibrating Platinum Resistance Thermometer 7--7..............
7.4 Calibrating Current Input 7--9..................................
7.5 Calibrating Voltage Input 7--10..................................
7.6 Checking Indication Accuracy 7--12.............................
CHAPTER 8 TROUBLESHOOTING 8--1......................
This chapter describes how to find out and remedy the cause if the E5AK does not function properly.
8.1 Initial Checks 8--2............................................
8.2 How to Use the Error Display 8--3..............................
8.3 How to Use Error Output 8--5..................................
8.4 Checking Operation Restrictions 8--6...........................
APPENDIX
SPECIFICATIONS A--2........................
ABOUT CURRENT TRANSFORMER (CT) A--5...
CONTROL BLOCK DIAGRAM A--6..............
SETTING LIST A--8...........................
MODEL LIST A--11.............................
PARAMETER OPERATIONS LIST A--12..........
FUZZY SELF-TUNING A--14....................
XFORMAT A--17...............................
ASCII CODE LIST A--20........................
INDEX
REVISION HISTORY
CHAPTER1
CHAPTER 1
INTRODUCTION
This chapter introduces the E5AK. First-time users should read this chapter without fail. For details on how to use the controller and parameter settings, see Chapters 2 onwards.
CHAPTER 1 INTRODUCTION
1.1 Names of parts 1-2........................
Main parts 1-2............................
Front panel 1-2...........................
About the displays 1-3.....................
How to use keys 1-3.......................
1.2 Input and Output 1-4......................
Input 1-4.................................
Output 1-5................................
1.3 P arameters and Menus 1-7.................
Parameter types 1-7.......................
Selecting modes 1-8........................
Selecting parameters 1-9...................
Fixing settings 1-9.........................
1.4 About the Communications Function 1-10....
1.5 About Calibration 1-11......................
1--1
CHAPTER 1 INTRODUCTION
1.1 Names of parts
JMain parts
Terminals
P2-8
Rear case
JFront panel
Bar graph
Operation indicators
OUT1 SUB1 MANU STOP RMT RST AT
A/M key Display key Down ke y Up key
A/M
OUT2 SUB2
RMT
RSP SUB1
OUT1 OUT2
MANU
STOP
PV
Front panel
This page
No.1 display
SV
No.2 display
SUB2
AT
E5AK
1--2
JAbout the displays
1.1 Names of parts
F No.1 display
F No.2 display
F Operation indica-
tors
F Bar graph
Displays the process value or parameter symbols.
Displays the set point, manipulated variable or parameter settings.
OUT1 : Lit when the pulse output function assigned to control output 1” is ON.
OUT2 : Lit when the pulse output function assigned to “control
output 2” is ON.
SUB1 : Lit when the output function assigned to auxiliary output 1” is ON.
SUB2 : Lit when the output function assigned to “auxiliary output 2” is ON.
MANU : Lit in the manual operation mode.
STOP : Lit when operation has stopped.
RMT : Lit during remote operation.
RSP : Lit during remote SP operation.
AT : Flashes during auto-tuning.
On a standard type controller (E5AK-AA2), this bar graph indicates the manipulated variable (heat) in 10% increments per single segment. On
a position-proportional type controller (E5AK-PRR2), this bar graph indicates the valve opening in 10% increments per single segment.
JHow to use keys
A/M
F key
F key
F key
The following describes basic key operations.
Each press of this key switches between the auto and manual opera­tions.
The functions of this key change according to how long it is pressed. If the key is pressed for less than one second, the parameters are switched. If the key is pressed for one second or more, the menu display appears.
In key operations from here on, press the key” refers to pressing the key for less than one second. For details on parameter switching and menu display items, see page 1-8.
Each press of the
on the No.2 display, while each press of the key decrements or returns the values or settings on the No.2 display.
Functions vary, for example, when the neously with the display key, or a key is held down continuously. For
details, see page 1-8. Also, chapters 3 and 4 describe examples using various key combinations.
key increments or advances the values or settings
A/M
key is held down simulta-
1--3
CHAPTER 1 INTRODUCTION
1.2 Input and Output
JInput
Temperature input Voltage input Current input
CT input Potentiometer
Remote SP input
Event input
Controller
Control output (heat)
Control output (cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Error 1
Error 2
Error 3
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output 2
Transfer output
The E5AK supports following inputs: temperature input, current input,
voltage input, CT input/Potentiometer, remote SP input and event input.
F Temperature input/Voltage input/Current input
Only one of temperature input, voltage input and current input can
be selected and connected to the controller. The above figure shows temperature input connected to the controller.
The following input sensors can be connected for temperature input:
Thermocouple:K,J,T,E,L,U,N,R,S,B,W,PLII Platinum resistance thermometer: JPt100, Pt100
The following currents can be connected for current input:
4to20mA,0to20mA
The following voltages can be connected for voltage input:
1to5VDC,0to5VDC,0to10VDC
F CT input/Poten-
tiometer
F Remote SP input
Connect CT input when using the HBA (heater b urnout alarm) func-
tion on a standard type controller (E5AK-AA2).
Connect the potentiometer when monitoring the valve opening on a
position-proportional type controller (E5AK-PRR2).
When the remote SP function is enabled, inputs within the range 4 to
20 mA are used as the remote SP.
1--4
1.1 Names of parts
F Event input
JOutput
When using event input, add on the input unit (E53-CKB). You can select from the following five event inputs:
Multi-SP Run/Stop Remote/Local Auto/Manual SP mode
The E5AK supports the following five outputs.
Control output 1 Control output 2 Auxiliary output 1 Auxiliary output2 Transfer output
When using control outputs 1 and 2, set the output unit (sold sepa­rately). Nine output units are available to suit the output circuit config­uration.
When using transfer output, add on the communication unit (E53-AKF).
Note: The output functions of the E5AK do not operate for five seconds
after the E5AK is turned ON.
F Output assign-
ments
The E5AK supports the following ten output functions.
Control output (heat) Control output (cool) Alarms 1 to 3 HBA LBA Error 1 (input error) Error 2 (A/D converter error) Error 3 (RSP input error)
Assign these output functions to control output 1, control output 2, auxiliary output1, and auxiliary output2. However, note that as control output 1 is used as the open output and control output 2 is used as close output on a position-proportional type controller (E5AK-PRR2), control outputs 1 and 2 cannot be used as assignment destinations. Also, of the output functions, control output (heat), control output (cool), HBA and LBA are disabled.
On a standard type controller, there are restrictions on how assignment destinations (control output 1, control output2, auxiliary output1, and auxiliary output2) can be used. For details, see 3.3 Setting Output Spec­ifications.
In the example on the previous page, “control output (heat)” is assigned to “control output 1”, “alarm 1” is assigned to “control output 2”, and “alarm 2” is assigned to “auxiliary output 1”. Accordingly, the configu­ration is such that heating control output is connected to control output 1, and alarm output is connected to control output 2 and auxiliary out­put 1.
1--5
CHAPTER 1 INTRODUCTION
Control outputs 1 and 2 are used depending on the differences in con ­trol method as follows.
F Transfer output
Control Method
Standard control E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Heating and cooling control
Position-proportional control
The E5AK supports the following six transfer outputs.
Set point
Set point during SP ramp Process value Heating side manipulated variable Cooling side manipulated variable
Valve opening
However, note that heating/cooling side manipulated variables can be output only standard type controllers, and valve opening can be output
on position-proportional type controllers
These transfer outputs can be output after being scaled. Setting of an upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out.
E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24
E5AK-PRR2 AC100-240 E5AK-PRR2 AC/DC24
Model
Control Output 1/
Control Output 2
Control output (heat) / Alarm, etc.,
Control output (heat) / Control output (cool)
Open/Close
1--6
1.3 Parameters and Menus
1.1 Names of parts
JParameter types
F Protect mode
F Manual mode
F Level 0 mode
E5AK parameters are distributed between the following nine modes.
Protect mode Manual mode Level 0 mode Level 1 mode Level 2 mode Setup mode Expansion mode Option mode Calibration mode
The settings of parameters in each of seven modes (excluding the pro­tect mode and manual mode) can be checked and modified by selection on the menu display.
This mode is used to limit use of the menu and function is for preventing unwanted modification of parameters and switching between the auto and manual operation.
In this mode, the controller can be switched manual operation. The manipulated variable can be manipulated manually only in this mode.
Set the controller to this mode during normal operation. In this mode, you may change the set point during operation, and stop and start op­eration. You can also monitor (not change) the process value, ramp SP and manipulated variable.
A/M
keys. The protect
F Level 1 mode
F Level 2 mode
F Setup mode
F Expansion mode
F Option mode
This is the main mode for adjusting control. In this mode, you can execute AT (auto-tuning), and set alarm values, the control period and PID parameters.
This is the auxiliary mode for adjusting control. In this mode, you can set the parameters for limiting the manipulated variable, switch between the remote and local modes, switch between the SP modes, and set the loop break alarm (LBA), alarm hysteresis and the digital filter value of inputs.
This is the mode for setting the basic specifications. In this mode, you can set parameters that must be checked or set before operation such as the input type, scaling, output assignments and direct/reverse opera­tion.
This is the mode for setting expanded functions. In this mode, you can set ST (self-tuning), SP setting limiter, selection of advanced PID or ON/OFF control, specification of the standby sequence resetting method, time for automatic return to the monitoring display.
This is the mode for setting option functions. You can select this mode only when the option unit is set in the controller. In this mode, you can
1--7
CHAPTER 1 INTRODUCTION
set the communications conditions, transfer output and event input parameters to match the type of option unit set in the controller. Heater burnout latch function, position-proportional travel time and remote SP scaling parameters are also located in this mode.
F Calibration mode
JSelecting modes
This mode is provided so that the user can calibrate inputs and transfer
output. When calibrating input, the selected input type is calibrated. Whereas, transfer output can be calibrated only when the communications unit (E53-AKF) is set in the controller.
The following diagram shows the order in which modes are selected.
Power ON
1 second min.
Level 0 mode
1 second min.
Level 1 mode
1 second min.
Level 2 mode
1 second min.
Setup mode
1 second min.
Expansion mode
1 second min.
Option mode
A/M
1secondmin.
Manual mode
A/M
++
1 second min. 1 second min.
Protect mode
A/M
1secondmin.
A/M
A/M
+
1secondmin.
F Menu display
F Level 0 to 2
modes
1 second min.
Calibration mode
To select the menu display in any of the above modes (excluding the
protect mode and manual mode), press the mum. If you select the desired mode using the press the
key, the top parameter in the specified mode is dis-
key for 1 second mini-
or keys and
played.
When you have selected the menu display, the previous mode is
selected. For example, if you selected the menu display while in the level 0 mode, the No.2 display changes to [
] as shown on the left.
Protected modes cannot be selected. Also, the menu display does not
appear when modes are protected up to the level 1 mode.
If you select [
][ ]or[ ] in the menu display, the level 0,
level 1 and level 2 modes, respectively, are selected.
These modes are selected with control still continuing.
1--8
1.1 Names of parts
F Setup mode F Expansion mode F Option mode F Calibration mode
F Protect mode
F Manual mode
JSelecting
parameters
If you select [
the setup, expansion, option and calibration modes, respectively, are selected.
When these modes are selected, the control is reset. So, control out-
puts and auxiliary output are turned OFF. When another mode is selected while in these modes, reset is canceled.
To set the controller to the protect mode or to return to the level 0
mode from the protect mode, press the cond minimum simultaneously.
To set the controller to the manual mode, press the
cond minimum in the level 0 to 2 mode. To return to the level 0 mode from the manual mode, press the
When not in the manual mode, each press of the
parameter.
If you press the
turns to the first parameter.
Parameter
1
][ ][ ]or[ ]inthe menudisplay,
A/M
key and key for 1 se-
A/M key for 1 se-
A/M key for 1 second minimum.
key switches the
key when at the final parameter , the display re-
Parameter
2
Parameter
3
Parameter
n
JFixing settings
When you have changed a parameter setting, specify the parameter
using the seconds or press the
When another mode is selected, the content of the parameters before
the mode was selected is fixed.
When turning the power OFF, you must first fix the settings and
parameter contents (by pressing the mode). The settings and parameter contents are sometimes not changed by merely pressing the
or keys, and either leave the setting for at least two
key. This fixes the setting.
key or selecting another
or keys.
1--9
CHAPTER 1 INTRODUCTION
1.4 About the Communications Function
The E5AK can be provided with a communications function that allows you to check and set controller parameters from a host computer. If the
communications function is required, add on the communications unit. For details on the communications function, refer to Chapter 6.
F RS-232C
F RS-422
F RS-485
When using the communications function on the RS-232C interface, add on the communications unit (E53-AK01).
When using the communications function on the RS-422 interface, add on the communications unit (E53-AK02).
When using the communications function on the RS-485 interface, add on the communications unit (E53-AK03).
1--10
1.5 About Calibration
The E5AK controller is calibrated before shipment from the factory. So, the user need not calibrate the E5AK controller during regular use.
However, if the E5AK controller must be calibrated by the user, use the parameters provided for user to calibrate temperature input, analog input (voltage, current) and transfer output. Also, note that calibration data is updated to the latest value each time
the E5AK controller is calibrated. Calibration data set before shipment from the factory cannot be returned to after calibration by the user.
1.1 Names of parts
F Calibrating
inputs
F Calibrating trans-
fer output
F Registering cal-
ibration data
The input type selected in the parameter is the item to be calibrated. The E5AK is provided with the following four calibration parameters.
Thermocouple
Platinum resistance thermometer
Current input
Voltage input
Two parameters are provided for thermocouple and voltage input.
Transfer output can be calibrated when the communications unit (E53-AKF) is added on.
When calibrating each item, the calibration data is temporarily regis­tered. This data can be registered as final calibration data only when all items have been newly calibrated. So, all items must be temporarily
registered when calibrating the E5AK controller. When registering data, information regarding whether or not calibra­tion has been carried out is also registered.
To calibrate these items, the user must prepare separate measuring
devices and equipment. For details on handling these measuring devices and equipment, refer to the respective manuals.
For details, see Chapter 7 Calibration.
1--11
CHAPTER 1 INTRODUCTION
1--12
CHAPTER2
CHAPTER 2
PREPARATIONS
This chapter describes the operations you should carry out before turning the E5AK ON.
CHAPTER 2 PREPARATIONS
2.1 Setting up 2-2.............................
Draw-out 2-2..............................
Setting up the output unit 2-3..............
Setting up the option unit 2-4...............
2.2 Installation 2-5............................
Dimensions 2-5............................
Panel cutout 2-5...........................
Mounting 2-6.............................
2.3 Wiring Terminals 2-8......................
Terminal arrangement 2-8.................
Precautions when wiring 2-8...............
Wiring 2-8................................
2--1
CHAPTER 2 PREPARATIONS
2.1 Setting up
On a standard type controller, set up the output units for control out­puts 1 and 2 before mounting the controller.
On a position-proportional type controller, the relay output unit is already set. So, this setup operation unnecessary. (Do not replace with other output units.)
When setting up the output units, draw out the internal mechanism from the housing and insert the output units into the sockets for con­trol outputs 1 and 2.
JDraw-out
When drawing out the internal mechanism from the housing, p repare a
phillips screwdriver matched to the size of the screw on the lower part of the front panel.
(1) Press down on the hook on the top of the front panel and turn the
phillips screwdriver to the left to loosen the screw on the lower part
of the front panel.
2--2
Fixing Screw for Front Panel
(2) Draw out the internal mechanism towards you holding both sides
of the front panel.
Tighten this screw by a torque of 0.3 to 0.5 Nm, or approx. 3 to 5 kgfcm.
JSetting up the output unit
2.1 Setting up
F Before setup
F Procedure
Check the type of the output unit you are about to set up.
For details on types of output unit and main specifications, see page
2-9.
(1) Check the positions of the sockets you are about to insert the out-
put units into as shown in the following diagram.
OUT1
OUT2
Bracket
(2) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(3) Fasten the output units with the bracket (accessory).
2--3
CHAPTER 2 PREPARATIONS
JSetting up the option unit
F Before setup
F Procedure
Check the type of the option unit you are about to set up.
For details on types of option unit and main specifications, see Appen-
dix, Model List (page A-11) and Appendix, Option Unit Ratings and Characteristics (page A-4).
For details on the relationship between units and terminals, see page 2-8.
(1) Remove the power board and option boards in the order shown in
the following diagram.
2
1
(2) Insert the option units into the sockets for options 1 to 3. The fol-
lowing diagram shows the relationship between option units and mounting positions.
Option 1 E53--AKB: Event inputs 1/2 E53--AK01: RS--232C
Option 2 E53--AKF: Transfer output
E53--AK02: RS--422 E53--AK03: RS--485
Option 3 E53--AKB: Event inputs 3/4
2--4
(3) Mount the option boards and the power board in the order shown.
2.2 Installation
JDimensions
96j 13.5 100
PV
SV
RMT
OUT1 OUT2
MANU
STOP
2.2 Installation
j
91
SUB2RSP SUB1
AT
112
JPanel cutout
Unit (mm)
120 mm min
92
+0.8
0
E5AK
110 mm m in
92
+0.8
0
R ecommended panel thickness is 1 to 8 mm.
Maintain the specified vertical and hori­zontal mounting space between each controller. Controllers must not be closely mounted vertically or horizontally.
2--5
CHAPTER 2 PREPARATIONS
JMounting
(1) Insert the E5AK controller into the mounting hole in the panel.
(2) Fit the mounting bracket (accessory) into the fixing slots on the top
and bottom of the rear case.
(3) Tighten the mounting bracket screws alternately a little at a time
until the ratchet start to slide.
2--6
F Setting up the terminal covers
Fasten the terminal covers (E53-COV0809) to protect terminals.
E5AK-VV2-500 controller is provided with terminal covers.
Use E53-COV09 for terminals 1 to 10, and E53-COV08 for terminals
11 to 33.
Fasten the terminal covers as follows by using the snap pins.
2.2 Installation
E5AK
E53-COV0809
To remove the terminal covers, pull the edges of the snap pins.
2--7
CHAPTER 2 PREPARATIONS
2.3 Wiring Terminals
JTerminal arrangement
AC100-240V (AC/DC24V )
OUT1
OUT2
SUB1
SUB2
SOURCE
~
10
30
29
28
27
26
25
24
23
22 21
31 32
33
TRSF
9
8
7
6
EV3/4
5
4
3
2
RSP
1
20
19
18
17
16
15
14
13
12
11
EV1/2
RS232C
RS422 RS485
CT
PTMR
TC
Pt
I
V
JPrecautions
when wiring
JWiring
F Power supply
10
9
8 7 6 5
4 3 2
1
30
29
28
27
26
25
24
23
22
21
31 32
33
TRSF : Transfer output EV1 to 4 : Event inputs PTMR : Potentiometer
Use ducts to separate input leads and power lines in order to protect the controller and its lines from external noise.
We recommend using solderless terminals when wiring the controller.
Ti ghten the terminal screws using a torque no greater than 0.78 N·m,
or 8 kgf·cm max. Take care not to tighten the terminal screws too tightly.
Use the following type of solderless terminals for M3.5 screws.
7.2mm max.
7.2mm max.
In the following wiring diagrams, the left side of the terminal Nos. indi­cates the inside of the controller
Input power to terminal Nos. 9 and 10. Power specif ications are as fol­lows:
20 19
18 17 16 15
14 13 12
11
AC100-240V
(AC/DC24V
, 50/60Hz, 16VA
, 50/60Hz, 12VA, 8W)
2--8
2.3 Wiring Terminals
F Sensor input
10
9 8 7 6 5 4 3 2 1
30 29 28 27 26 25 24 23 22
21
31 32
33
F Control output
10
9
8 7 6 5
4 3 2
1
30 29
28 27 26 25
24 23 22
21
31 32
33
Connect the sensor input to terminal Nos. 11 to 14 and 33 as follows
20 19 18 17 16 15
14 13 12
11
according to the input type.
14
13
12
11
33
Thermocouple Platinum
--
+
resistance
thermometer
14
13
12
11
33
+
14
V
13
12
--
11
33
Voltage input Current input
14
13
12
11
33
--
mA
+
Terminal Nos. 7 and 8 are for control output 1 (OUT1), and terminal
20 19
18 17 16 15
14 13 12
11
Nos. 5 and 6 are for control outpu t 2 (OUT2). The following diagrams show the available outpu t units and their internal eq u alizing circuits.
With E53-VVV output units, about 2 V is output for one second after the power is interrupted.
The following table shows the specifications for each output unit.
Model Output Type Specifications
E53-R Relay 250 VAC, 5 A
E53-S SSR 75 to 250 VAC, 1 A
E53-Q E53-Q3 E53-Q4
E53-C3 E53-C3D
E53-V34 E53-V35
Voltage (NPN) Voltage (NPN) Voltage (PNP)
4to20mA 0to20mA
0to10V 0to5V
NPN : 12 VDC, 40 mA (with short-circuit protection) NPN : 24 VDC, 20 mA (with short-circuit protection) PNP : 24 VDC, 20 mA (with short-circuit protection)
4 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600 0 to 20 mA, Permissible load impedance: 600 max., Resolution: Approx. 2600
0 to 10 VDC, Permissible load impedance: 1 kmin., Resolution: Approx. 2600 0 to 5 VDC, Permissible load impedance: 1 kmin., Resolution: Approx. 2600
With E5AK-PRR2 controllers, relay output (250 VAC, 1 A) is fix­ed.When replacing the output unit, use the E53-R. The following dia­grams show the relationship between terminals and open/close relay settings.
8
7
Open
6
5
Close
2--9
CHAPTER 2 PREPARATIONS
F Auxiliary output
10
9 8 7 6 5
4 3 2 1
30 29 28 27 26 25
24 23 22 21
31 32
33
F CT input/
Potentiometer
10
9 8 7 6 5 4 3 2 1
30 29 28 27 26 25
24 23 22 21
31 32
33
Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal
20 19 18 17 16 15
14 13 12 11
Nos.1 and 2 are for auxiliary output 2 (SUB2).
The internal equalizing circuits for the auxiliary outputs are as fol­lows:
4
3
Auxiliary
output 1
2
1
Auxiliary
output 2
Output specifications are as follows:
SPST-NO, AC250V, 3A
When using the HBA function on the E5AK-AA2 controller, connect CT input (CT) to terminal Nos.15 to 17. When monitoring the valve
20 19 18
17 16 15
14 13 12 11
opening on the E5AK-PRR2 controller, connect the potentiometer (PTMR) to terminal Nos.15 to 17. Connect each of these inputs as fol­lows:
17
16
15
CT input Potentiometer
CT
17
16
15
O
W
C
For details on CT inputs, see Appendix, About Current transformer.
For details on the potentiometer, see the Instruction Manual for the
valve connected to the controller. The variable resistance range is 100 to 2.5 k.
F Remote SP input
10
9 8 7 6 5 4 3 2 1
About the power blocks
30 29 28 27 26 25 24 23
22 21
31 32
33
20 19 18 17 16 15 14 13 12
11
Connect an input (RSP) to be used as the remote SP to terminal Nos.21 and 22.
Only 4 to 20 mA inputs can be connected. Connect the input as fol­lows:
+
22
4to20mA
21
--
The E5AK has independent power supplies for each of the terminal blocks shown on the right.
AB C
31 32
33
20 19
18 17 16 15 14 13 12 11
10
9 8
7
B
6 5 4
E
3 2 1
FD
30 29
28 27 26
C
25 24 23 22 21
2--10
Loading...
+ 146 hidden pages