Omron E5 GETTING STARTED GUIDE

Cat. No. H08E-EN-01
E5CN E5AN E5EN E5GN
ZX-T Series
Digital Temperature Controllers
Getting Started Manual
E5CN/E5AN/E5EN/E5GN
This manual needs the H04E+E5CN(-U) and H03E+E5EN/AN datasheet for selection and installation. (This manual is a selection from the full manual H156)
Digital Temperature Controllers
Getting Started Manual
Basic Type
Revised August 2010
iv
Preface
The E5CN, E5CN-U, E5AN, E5EN, and E5GN are Digital Temperature Controllers. The E5CN and E5CN-U are both compact temperature controllers, with the E5CN featuring screw terminal connec­tions, and the E5CN-U featuring socket pin connections. The E5GN can be connected using screw ter­minals or screwless clamp terminals. The main functions and characteristics of these Digital Temperature Controllers are as follows:
This manual describes the E5CN, E5CN-U, E5AN, E5EN, and E5GN for basic functions. Read this manual thoroughly and be sure you understand it before attempting to use the Digital Temperature Controller and use the Digital Temperature Controller correctly according to the information provided. Keep this manual in a safe place for easy reference. Refer to the full manual for advanced settings:
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User’s Manual (Cat. No. H156). Refer to the following manual for further information on communications: E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158). Refer to the following manual for information on the Advanced Type Controllers: E5CN/E5AN/E5EN-H Digital Temperature Controllers User's Manual Advanced Type (Cat. No. H157).
• Any of the following types of input can be used: thermocouple, platinum resistance thermometer, infrared sensor, analog voltage, or analog cur­rent.
• Either standard or heating/cooling control can be performed.
• Both auto-tuning and self-tuning are supported.
• Event inputs can be used to switch set points (multi-SP function), switch between RUN and STOP status, switch between automatic and manual operation, start/reset the simple program function, and perform other operations. (Event inputs are not applicable to the E5CN-U.)
• Heater burnout detection, heater short (HS) alarms, and heater overcur­rent (OC) functions are supported. (Applicable to E5CN, E5AN, E5EN, and E5GN models with heater burnout detection function.)
• Communications are supported. (Applicable to E5CN, E5AN, E5EN, and E5GN models with communications.)
• User calibration of the sensor input is supported.
• The structure is waterproof (IP66). (Not applicable to the E5CN-U.)
• Conforms to UL, CSA, and IEC safety standards and EMC Directive.
• The PV display color can be switched to make process status easy to understand at a glance.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient opera-
tion of the product.
1,2,3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc.
v
© OMRON, 2010
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con­stantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
vi
Precautions for Operation
1) It takes approximately two seconds for the outputs to turn ON from after the power supply is turned ON. Due consideration must be given to this time when incorporating Temperature Controllers into a control panel or similar device.
2) Make sure that the Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display.
3) When executing self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Temperature Controller. If power is turned ON for the Temperature Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved. When starting operation after the Temperature Controller has warmed up, turn OFF the power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the Temperature Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.)
4) Avoid using the Controller in places near a radio, television set, or wireless installing. The Controller may cause radio disturbance for these devices.
Shipping Standards
The E5CN, E5CN-H, E5AN, E5AN-H, E5EN, and E5EN-H comply with Lloyd's standards. When applying the standards, the following installation and wiring requirements must be met in the application.
Application Conditions
1) Installation Location
The E5CN, E5CN-H, E5AN, E5AN-H, E5EN, and E5EN-H comply with installation category ENV1 and ENV2 of Lloyd's standards. Therefore, they must be installed in a location equipped with air condition­ing. They must therefore be installed in a location equipped with air conditioning. They cannot be used on the bridge or decks, or in a location subject to strong vibration.
2) Wiring Conditions
Install the recommended ferrite core and wrap the line around it three turns for the applicable lines (e.g., power supply cable line and signal lines) of the models listed in the following table. (See illustra­tions.) Install the ferrite cores as close to the terminal block of the E5@N as possible. (As a guideline, the ferrite core should be within 10 cm of the terminal block.)
Lines Requiring Ferrite Cores
Model Signal and power lines provided with ferrite cores
E5CN, E5CN-U, or E5CN-H Input power supply
E5EN, E5AN, E5EN-H, or E5AN-H
Recommended Ferrite Core
Manufacturer Seiwa Electric Mfg. Co., Ltd.
Model E04RA310190100
Note This part is available from Omron stock.
Input power supply and I/O lines (control outputs (1 and 2), communications, event inputs (1 to 4), transfer output, and external power supply (Advanced Type models do not have an external power supply.)
vii
Ferrite Core Connection Examples
y
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
21
22
23
24
25
26
27
28
29
30
21
22
23
24
25
26
27
28
29
30
11
12
13
14
15
16
17
18
19
20
EV4
EV3
+
+
+
+
+
+
+
DO NOT USE
DO NOT USE
DO NOT USE
B
V
CT2
CT1
EV1
EV2
CT1/CT2
DO NOT USE
DO NOT USE
DO NOT USE
B
A
DO NOT USE
DO NOT USE
DO NOT USE
B (+)
A ()
DO NOT USE
B (+)
A ()
11
12
13
21
22
11
12
13
21
22
RS-485RS-232C
SD
RD
SG
DO NOT USE
DO NOT USE
mA
Input power supply
Control output 1
Auxiliary output 3
Auxiliary output 2
Auxiliary output 1
Transfer output
4 to 20 mA DC (Load: 600 Ω max.)
Communications
Event Inputs
Control Output 2
Control Output 2
External Power Supply
External power supply 12 VDC, 20 mA
Connected to communications or event inputs 1 and 2.
Connected to control output 2 or external power supply.
Power supply
Connected to control output 1.
Connected to event inputs 3 and 4.
Connected to transfer output.
Analog input
TC/Pt universal input
AC/DC
3 turns
3 turns
3 turns
3 turns
3 turns
3 turns
1. E5CN/E5CN-H
mA
+
DO NOT USE
DO NOT USE
V
+
+
Control output 1
DO NOT USE
+
1
2
A
3
B
4
B
5
11
12
13
14
15
Auxiliary outputs (relay outputs)
6
7
Auxiliary output 1
8
9
Input power supply
10
Auxiliary output 2
Power suppl
AC/DC
3 turns
Analog input
TC/Pt universal input
2. E5AN/E5EN/E5AN-H/E5EN-H
viii
Preparations for Use
Be sure to thoroughly read and understand the manual provided with the product, and check the fol­lowing points.
Timing Check point Details
Purchasing the prod­uct
Setting the Unit Product installation loca-
Wiring Terminal wiring Do not subject the terminal screws to excessive stress (force) when
Operating environ­ment
Product appearance After purchase, check that the product and packaging are not dented or
otherwise damaged. Damaged internal parts may prevent optimum control.
Product model and speci­fications
tion
Power supply inputs Wire the power supply inputs correctly. Incorrect wiring will result in
Ambient temperature The ambient operating temperature for the product is 10 to 55°C (with
Vibration and shock Check whether the standards related to shock and vibration are satis-
Foreign particles Install the product in a location that is not subject to liquid or foreign
Make sure that the purchased product meets the required specifica­tions.
Provide sufficient space around the product for heat dissipation. Do not block the vents on the product.
tightening them. Make sure that there are no loose screws after tightening terminal screws to the specified torque of 0.74 to 0.90 N·m (see note).
Be sure to confirm the polarity for each terminal before wiring the termi­nal block and connectors.
damage to the internal circuits.
no condensation or icing). To extend the service life of the product, install it in a location with an ambient temperature as low as possible. In locations exposed to high temperatures, if necessary, cool the products using a fan or other cooling method.
fied at the installation environment. (Install the product in locations where the conductors will not be subject to vibration or shock.)
particles entering the product.
Note The tightening torque is 0.5 N·m for the E5CN-U and 0.43 to 0.58 N·m for the
E5GN. The terminal torque is 0.5 to 0.6 N·m for auxiliary output 2 on the E5GN.
ix
Conventions Used in This Manual
Model Notation
The E5CN-@@@, E5CN-@@@U, E5AN-@@@, E5EN-@@@, and E5GN-@@@ are given as the E5CN, E5CN-U, E5AN, E5EN, and E5GN when they share functionality. The following notation is used when specifying differences in functionality.
Notation Options
E5@N-@@@B Two event inputs E5@N-@@@03 RS-485 communications E5@N-@@H One of HB, HS, and heater overcurrent detection E5@N-@@HH Two of HB, HS, and heater overcurrent detection (See note 1.) E5@N-@Q Control output 2 (voltage output) (See note 1.) E5@N-@@P External power supply to ES1B (See note 1.) E5@N-@@@01 RS-232C communications (See note 2.) E5@N-@@F Transfer output (See note 3.)
Note: (1) Excluding the E5GN.
(2) Excluding the E5CN.
(3) The E5AN and E5EN only.
Meanings of Abbreviations
The following abbreviations are used in parameter names, figures and in text explanations. These abbreviations mean the following:
Symbol Term
PV Process value
SP Set point
SV Set value
AT A ut o - tu n i ng
ST Self-tuning
HB Heater burnout
HS Heater short (See note 1.)
OC Heater overcurrent
LBA Loop burnout alarm
EU Engineering unit (See note 2.)
Note: (1) A heater short indicates that the heater remains ON even when the control output from the Tempera-
ture Controller is OFF because the SSR has failed or for any other reason.
(2) “EU” stands for Engineering Unit. EU is used as the minimum unit for engineering units such as °C,
m, and g. The size of EU varies according to the input type. For example, when the input temperature setting range is –200 to +1300°C, 1 EU is 1°C, and when the input temperature setting range is –20.0 to +500.0°C, 1 EU is 0.1°C. For analog inputs, the size of EU varies according to the decimal point position of the scaling setting, and 1 EU becomes the minimum scaling unit.
x

TABLE OF CONTENTS

SECTION 1
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1-1 Names of Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-2 I/O Configuration and Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1-3 Setting Level Configuration and Key Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
1-4 Communications Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1-5 Insulation Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
SECTION 2
Preparations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2-1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2-2 Using the Support Software Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
SECTION 3
Basic Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3-1 Initial Setting Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3-2 Setting the Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3-3 Selecting the Temperature Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-4 Selecting PID Control or ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-5 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
3-6 Setting the Set Point (SP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3-7 Using ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
3-8 Determining PID Constants (AT, ST, Manual Setup) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3-9 Alarm Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-10 Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms . . . . . . . . . . . . . . . . . 53
3-11 Setting the No. 3 Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
SECTION 4
Applications Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
4-1 Shifting Input Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4-2 Alarm Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4-3 Setting Scaling Upper and Lower Limits for Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 69
4-4 Executing Heating/Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4-5 Using Event Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4-6 Setting the SP Upper and Lower Limit Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
4-7 Using the SP Ramp Function to Limit the SP Change Rate . . . . . . . . . . . . . . . . . . . . . . . . . 81
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
xi

About this Manual:

!WARNING Failure to read and understand the information provided in this manual may result in per-
sonal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
This manual describes the E5CN/CN-U/AN/EN Digital Temperature Controllers and includes the sec­tions described below.
Please read this manual carefully and be sure you understand the information provided before attempting to set up or operate an E5CN/CN-U/AN/EN Digital Temperature Controller.
• Overview
Section 1 introduces the features, components, and main specifications of the E5CN/CN-U/AN/EN/ GN Digital Temperature Controllers.
•Setup
Section 2 describes the work required to prepare the E5CN/CN-U/AN/EN/GN Digital Temperature Controllers for operation, including installation and wiring.
• Basic Operations
Section 3 describes the basic operation of the E5CN/CN-U/AN/EN/GN Digital Temperature Control­lers, including key operations to set parameters and descriptions of display elements based on specific control examples.
Section 5 describes the individual parameters used to setup, control, and monitor operation.
• Operations for Applications
Section 4 describes scaling, the SP ramp function, and other special functions that can be used to make the most of the basic functionality of the E5CN/CN-U/AN/EN/GN Digital Temperature Control­lers.
xii
SECTION 1
Introduction
This section introduces the features, components, and main specifications of the E5GN, E5CN, E5EN and E5AN digital temperature controllers.
1-1 Names of Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1-1-2 Explanation of Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1-1-3 Using the Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1-2 I/O Configuration and Main Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1-2-1 I/O Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1-2-2 Main Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1-3 Setting Level Configuration and Key Operations . . . . . . . . . . . . . . . . . . . . . . 12
1-3-1 Selecting Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1-3-2 Saving Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1-4 Communications Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1-5 Insulation Block Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
1
Names of Parts Section 1-1

1-1 Names of Parts

1-1-1 Front Panel

E5CN/CN-U The front panel is the same for the E5CN and E5CN-U.
Temperature unit
No. 1 display
Operation indicators
No. 2 display
E5AN
Operation indicators
Level Key
Temperature unit
SUB1
SUB2
SUB3
HA
OUT1
OUT2
STOP
CMW
MANU
Mode Key
Down Key
PV
SV
MV
Up Key
No.1 display
No. 2 display
No. 3 display
Function Key/ Auto/Manual Key
E5AN
PF
A/M
Level Key
Up Key
Down Key
Mode Key
2
Names of Parts Section 1-1
E5EN
E5GN
Operation indicators
Temperature unit
Operation indicators
Mode Key
Level Key
SUB1
HA
E5EN
SUB2
SUB3
STOPOUT1
CMWOUT2
MANU
PF
A/M
Down Key
PV
SV
MV
No. 1 display
No.1 display
No.2 display
No.3 display
Up Key
Function Key/ Auto/Manual Key
Temperature unit
Operation indicators
Level Key
Mode Key
Down Key
Operation indicators
No. 2 display
Up Key
3
Names of Parts Section 1-1

1-1-2 Explanation of Indicators

No. 1 Display Displays the process value or parameter name.
Lights for approximately one second during startup.
No. 2 Display Displays the set point, parameter operation read value, or the variable input
value.
Lights for approximately one second during startup.
The set point will flash during autotuning.
No. 3 Display (E5AN/EN Only)
Operation Indicators
Displays MV, soak time remaining, or multi SP.
Lights for approximately one second during startup.
A 2-level display is set when shipped from the factory. A 3-level display is activated if parameters are initialized.
1,2,3... 1. SUB1 (Sub 1)
Lights when the function set for the Auxiliary Output 1 Assignment param­eter is ON.
SUB2 (Sub 2) Lights when the function set for the Auxiliary Output 2 Assignment param­eter is ON.
SUB3 (Sub 3) (E5AN/EN Only) Lights when the function set for the Auxiliary Output 3 Assignment param­eter is ON.
2. HA (Heater Burnout, Heater Short Alarm, Heater Overcurrent Detection Output Display) Lights when a heater burnout, heater short alarm, or heater overcurrent occurs.
3. OUT1 (Control Output 1) Lights when the control output function assigned to control output 1 turns ON. For a current output, however, OFF for a 0% output only.
OUT2 (Control Output 2) (Excluding the E5GN) Lights when the control output function assigned to control output 2 turns ON. For a current output, however, OFF for a 0% output only.
4. STOP Lights when operation is stopped.
During operation, this indicator lights when operation is stopped by an event or by key input using the RUN/STOP function.
5. CMW (Communications Writing) Lights when communications writing is enabled and is not lit when it is dis­abled.
6. MANU (Manual Mode) Lights when the auto/manual mode is set to manual mode.
7. (Key) Lights when settings change protect is ON (i.e., when the U and D Keys are disabled by protected status.)
Temperature Unit The temperature unit is displayed when parameters are set to display a tem-
perature. The display is determined by the currently set value of the Tempera­ture Unit parameter. °c indicates °C and °f indicates °F.
This indicator flashes during ST operation. It is OFF on models with linear inputs.
4
Names of Parts Section 1-1

1-1-3 Using the Keys

This section describes the basic functions of the front panel keys.
PF (Function (Auto/ Manual)) Key (E5AN/EN Only)
O Key Press this key to move between setting levels. The setting level is selected in
M Key Press this key to change parameters within a setting level.
U Key Each press of this key increments the value displayed on the No. 2 display or
D Key Each press of this key decrements values displayed on the No. 2 display or
O + M Keys Press these keys to change to the protect level. For details on operations
O + U Keys O + D Keys
This is a function key. When it is pressed for at least 1 second, the function set in the PF Setting parameter will operate.
Example: When A-M (auto/manual) is selected in the PF Setting parameter (initial value: A-M), the key operates as an auto/manual switch, switching between Auto Mode and Manual Mode. If the key is pressed for more than 1 second (regardless of key release timing), the mode will switch.
the following order: operation level: adjustment level, initial setting level, com­munications setting level.
The parameters can be reversed by holding down the key (moving one per second in reverse order).
advances the setting. Holding the key down speeds up the incrementation.
reverses the setting. Holding the key down speeds up the incrementation.
involving holding these keys down simultaneously, refer to 1-3 Setting Level Configuration and Key Operations.
To restrict set value changes (in order to prevent accidental or incorrect oper­ations), these key operations require simultaneously pressing the O key along with U or D key. This applies only to the parameter for the password to move to protect level.
5
I/O Configuration and Main Functions Section 1-2

1-2 I/O Configuration and Main Functions

1-2-1 I/O Configuration

E5CN
Temperature input or analog input
CT1 input
CT2 input
Event inputs 2 channels
Control section
Control output (heating)
Control output (cooling)
Alarm 3
Alarm 2
Alarm 1
HB alarm
HS alarm
OC alarm
Input error
Program end output
Communications function
Heating/cooling
Control output 1
Control output 2
External power supply for ES1B
Auxiliary output 2
Auxiliary output 1
Note:
Press one of these keys, depending on the model.
(See note.)
(See note.)
Note Functions can be assigned individually for each output by changing the set
values for the Control Output 1 Assignment, the Control Output 2 Assignment, the Auxiliary Output 1 Assignment, and the Auxiliary Output 2 Assignment parameters in the advanced function setting level.
6
I/O Configuration and Main Functions Section 1-2
E5CN-U
Temperature input or analog input
Control section
Control output (heating)
Control output (cooling)
Alarm 3
Alarm 2
Alarm 1
Input error
Program end output
Control output 1
Heating/ cooling
Auxiliary output 2
Standard
Auxiliary output 1
Note Functions can be assigned individually for each output by changing the set
values for the Control Output 1 Assignment, the Auxiliary Output 1 Assign­ment, and the Auxiliary Output 2 Assignment parameters in the advanced function setting level.
7
I/O Configuration and Main Functions Section 1-2
Temperature input or analog input
Control section
CT1 input
CT2 input
Event inputs 1 and 2 (2 channels)
Control output (heating)
Control output (cooling)
Alarm 3
Alarm 1
Alarm 2
HB alarm
HS alarm
Input error
Program end output
Communications function
Heating/cooling
Control output 1
Control output 2
Alarm output 1
Alarm output 2
Alarm output 3
External power supply for ES1B
OC alarm
(See note.)
(See note.)
Note:
Press one of these keys, depending on the model.
E5AN/EN
Note Functions can be assigned individually to each output by changing the set val-
ues for the Control Output 1 Assignment, Control Output 2 Assignment, Auxil­iary Output 1 Assignment, Auxiliary Output 2 Assignment, and Auxiliary Output 3 Assignment parameters in the advanced function setting level.
8
I/O Configuration and Main Functions Section 1-2
E5GN
Temperature input or analog input
CT1 input
Event inputs 2 channels
Control section
Control output (heating)
Control output (cooling)
Alarm 1
HB alarm
HS alarm
OC alarm
Input error
Alarm 2
Alarm 3
Program end output
Communications function
Control output 1
Heating/ cooling
Auxiliary output 1
Standard
Auxiliary output 2
Note Functions can be assigned individually for each output by changing the set
values for the Control Output 1 Assignment, the Auxiliary Output 1 Assign­ment, and the Auxiliary Output 2 Assignment parameters in the advanced function setting level.
9
I/O Configuration and Main Functions Section 1-2

1-2-2 Main Functions

This section introduces the main E5CN/CN-U/AN/EN/GN functions. For
details on particular functions and how to use them, refer to SECTION 3 Basic Operation and following sections.
Input Sensor Types • The following input sensors can be connected for temperature input
(i.e., E5_N-@@@@T): Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII Infrared temperature sensor: ES1B
10 to 70°C, 60 to 120°C, 115 to 165°C,
140 to 260°C Platinum resistance thermometer: Pt100, JPt100 Analog input: 0 to 50 mV
• Inputs with the following specifications can be connected for analog input
(i.e., E5_N-@@@@L): Current input: 4 to 20 mA DC, 0 to 20 mA DC Voltage input: 1 to 5 VDC, 0 to 5 V DC, 0 to 10 V DC
Control Outputs • A control output can be a relay, voltage (for driving SSR), or current out-
put, depending on the model.
• Long-life relay outputs (see note) use semiconductors for switching when closing and opening the circuit, thereby reducing chattering and arcing and improving durability. However, if high levels of noise or surge are imposed between the output terminals, short-circuit faults may occasion­ally occur. If the output becomes permanently shorted, there is the danger of fire due to overheating of the heater. Design safety into the system, including measures to prevent excessive temperature rise and spreading of fire. Take countermeasures such as installing a surge absorber. As an additional safety measure, provide error detection in the control loop. (Use the Loop Burnout Alarm (LBA) and HS alarm that are provided for the E5@N.)
Long-life relay output
1
Varistor
2
Varistor
Inductive load
Select a surge absorber that satisfies the following conditions.
Voltage used Varistor voltage Surge resistance
100 to 120 VAC 240 to 270 V 1,000 A min.
200 to 240 VAC 440 to 470 V
• Always connect an AC load to a long-life relay output (see note). The out­put will not turn OFF if a DC load is connected.
Note Long-life relay outputs are not supported for the E5GN.
Alarms • Set the alarm type and alarm value or the alarm value upper and lower
limits.
• If necessary, a more comprehensive alarm function can be achieved by setting a standby sequence, alarm hysteresis, auxiliary output close in alarm/open in alarm, alarm latch, alarm ON delay, and alarm OFF delay.
• If the Input Error Output parameter is set to ON, the output assigned to alarm 1 function will turn ON when an input error occurs.
10
I/O Configuration and Main Functions Section 1-2
Control Adjustment • Optimum PID constants can be set easily by performing AT (auto-tuning)
or ST (self-tuning).
Event Inputs • With the E53-CN@B@N2 for the E5CN or the E5AN/EN-@M@-500-N with
the E53-AKB for the E5AN/EN, the following functions can be executed using event inputs: switching set points (multi-SP, 4 points max.), switch­ing RUN/STOP, switching between automatic and manual operation, start­ing/resetting the program, inverting direct/reverse operation, 100% AT execute/cancel, 40% AT execute/cancel, setting change enable/disable, and canceling the alarm latch.
Heater Burnout, HS Alarm, and Heater Overcurrent
Communications Functions
Note (1) CompoWay/F is an integrated general-purpose serial communications
• With the E53-CN@H@N2 or E53-CN@HH@N2 for the E5CN, or the E5AN/EN-@@H@-500-N or E5AN/EN-@@HH@-500-N, the heater burnout detection function, HS alarm function, and heater overcurrent detection function can be used.
• Communications functions utilizing CompoWay/F (See note 1.), SYSWAY (See note 2.), or Modbus (See note 3.) can be used.
RS-485 Interface
Use the E53-CN@03N2 for the E5CN or the E53-EN03 for the E5AN/ EN.
RS-232C Interface
Use the E53-EN01 for the E5AN/EN.
protocol developed by OMRON. It uses commands compliant with the well-established FINS, together with a consistent frame format on OMRON Programmable Controllers to facilitate communications be­tween personal computers and components.
(2) SYSWAY communications do not support alarm 3.
(3) Modbus is a communications control method conforming to the RTU
Mode of Modbus Protocol. Modbus is a registered trademark of Schneider Electric.
(4) The E5CN and E5CN-U do not support the RS-232C interface.
External Power Supply for ES1B
Note The E5GN does not provide a power supply for an ES1B Infrared Tempera-
Transfer Output A transfer output for 4 to 20 mA can be used with the E5AN/E5EN-@@F.
The E5AN-@P@-N or E5EN-@P@-N with the E53-CN@P@N2 can be used as the power supply for ES1B Infrared Temperature Sensors.
ture Sensor.
For E5@N-C@@ models (models without “F” in the model number), the cur­rent output can be used as a simple transfer output.
11
Setting Level Configuration and Key Operations Section 1-3
Note: Not described in this manual.
Please refer to H156
Start in manual mode.
25
100
c
25
100
c
a-m
Power ON
(See note
3.)
(See note 1.)
(See note 2.)
Manual mode
Press the O Key or the PF Key for at least 1 s. (See note 4.)
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)
Operation Level
Press the O Key for at least 1 s.
Press the O Key for at least 1 s.
Input password.
Input password while amoV is displayed. (Set value 169)
Press the O Key less than 1 s.
Press the O Key for at least 3 s. (Display will flash after 1st second.)
Control stops.
Press the O Key for less than 1 s.
Press the O+ M Keys for at least 3 s. (Display will flash
after 1st second.)
Protect Level
Control in progress
Level change
Not displayed for some models
Control stopped
Start in automatic mode.
Adjustment Level
(See note 4.)
PF Key (See note 5.)
PF Key (See note 5.)
Initial Setting Level
Manual Control Level
Monitor/Setting Item Level
Advanced Function Setting Level
Calibration Level
Press the PF Key for at least 1 s.
Communica­tions Setting Level
Press the O+ M Keys for at least 1 s.
Note The time taken to move
to the protect level can be adjusted by chang­ing the "Move to pro­tect level time" setting.

1-3 Setting Level Configuration and Key Operations

Parameters are divided into groups, each called a level. Each of the set val­ues (setting items) in these levels is called a parameter. The parameters on the E5CN/CN-U/AN/EN/GN are divided into the following 9 levels.
When the power is turned ON, all of the display lights for approximately one second.
12
Note (1) You can return to the operation level by executing a software reset.
(2) You cannot move to other levels by operating the keys on the front panel
from the calibration level. You must turn OFF the power supply.
(3) From the manual control level, key operations can be used to move to the
operation level only.
Protect level Can be set. ---
Operation level Can be set. ---
Adjustment level Can be set. ---
Manual control level Can be set. ---
Level Control in progress Control stopped
Monitor/setting item level Can be set. ---
Initial setting level --- Can be set.
Setting Level Configuration and Key Operations Section 1-3
Level Control in progress Control stopped
Advanced function setting level --- Can be set.
Calibration level --- Can be set.
Communications setting level --- Can be set.
Of these levels, the initial setting level, communications setting level, advanced function setting level, and calibration level can be used only when control is stopped. Control outputs are stopped when any of these four levels is selected.
(4) When the PF Setting is set to A-M in models with a PF Key (E5AN/EN)
(5) When the PF Setting is set to PFDP in models with a PF Key (E5AN/EN)
Protect Level • To switch to the protect level from the operation level, the adjustment
level, or the monitor/setting item level, simultaneously hold down the O and M Keys for at least 3 seconds. (See note.) This level is for preventing unwanted or accidental modification of parameters. Protected levels will not be displayed, and so the parameters in that level cannot be modified.
Note The key pressing time can be changed in Move to Protect Level pa-
rameter (advanced function setting level).
Operation Level • The operation level is displayed when the power is turned ON. You can
move to the protect level, initial setting level, or adjustment level from this level.
• Normally, select this level during operation. While operation is in progress, items such as the PV and manipulated variable (MV) can be monitored, and the set points, alarm values, and alarm upper and lower limits can be monitored and changed.
Adjustment Level • To move to the adjustment level, press the O Key once (for less than 1 s).
• This level is for entering set values and offset values for control. In addi­tion to AT (auto-tuning), communications write enable/disable switching, hysteresis settings, multi-SP settings, and input offset parameters, it includes HB alarm, HS alarm, OC alarm, and PID constants. From the adjustment level, it is possible to move to the top parameter of the initial setting level, protect level, or operation level.
Monitor/Setting Item Level • To switch to the monitor/setting item level, press the PF Key from the
operation level or adjustment level. The contents set for monitor/setting items 1 to 5 can be displayed. You can move from the monitor/setting item level to the operation level or initial setting level. (This level is supported by the E5AN and E5EN only.)
Manual Control Level • When the O Key is pressed for at least 3 seconds from the operation
level's auto/manual switching display, the manual control level will be dis­played. (The MANU indicator will light.)
• When the PF Setting is set to A-M (auto/manual) and the PF Key is pressed for more than one second from the operation level or adjustment level, the manual control level will be displayed (E5AN and E5EN only.)
• This is the level for changing the MV in manual mode.
• To return to the operation level, press the O Key for at least one second. It is also possible to return to the operation level by pressing the PF Key for more than one second when the PF Setting is set to A-M.
13
Setting Level Configuration and Key Operations Section 1-3
Initial Setting Level • To move to the initial setting level from the operation level or the adjust-
ment level, press the O Key for at least 3 seconds. The PV display flashes after one second. This level is for specifying the input type and selecting the control method, control period, setting direct/reverse opera­tion, setting the alarm types, etc. You can move to the advanced function setting level or communications setting level from this level. To return to the operation level, press the O Key for at least one second. To move to the communications setting level, press the O Key for less than one sec­ond. (When moving from the initial setting level to the operation level, all the indicators will light.)
Note Pressing the O Key for at least 3 seconds in the operation level's
auto/manual switching display will move to the manual control level, and not the initial setting level.
Advanced Function Setting Level
Communications Setting Level
• To move to the advanced function setting level, set the Initial Setting/Com­munications Protect parameter in the protect level to 0 and then, in the ini­tial setting level, input the password (−169).
• From the advanced function setting level, it is possible to move to the cali­bration level or to the initial setting level.
• This level is for setting the automatic display return time and standby sequence, and it is the level for moving to the user calibration and other functions.
• To move to the communications setting level from the initial setting level, press the O Key once (for less than 1 s). When using the communica­tions function, set the communications conditions in this level. Communi­cating with a personal computer (host computer) allows set points to be read and written, and manipulated variables (MV) to be monitored.

1-3-1 Selecting Parameters

• Within each level, the parameter is changed in order (or in reverse order) each time the M Key is pressed. (In the calibration level, however, param­eters cannot be changed in reverse order.)
14
Communications Function Section 1-4

1-3-2 Saving Settings

Moves in order after M key is pressed (if key is released within 1 s).
Parameter 1
While the M key is being held down, the parameter will move each second in reverse order.
M
Parameter 2
M
Parameter 3
Hold down the M key
After M key is pressed
Parameter 4
• If you press the M Key at the final parameter, the display returns to the top parameter for the current level.
• To change parameter settings, specify the setting using the U or D Key, and either leave the setting for at least two seconds or press the M Key. This saves the setting.
• When another level is selected after a setting has been changed, the con­tents of the parameter prior to the change is saved.
• When you turn the power OFF, you must first save the settings (by press­ing the M Key). The settings are sometimes not changed by merely pressing the U or D Keys.
during this interval.
Parameter 2
After M key has been held down for 2 s.
Parameter 3
After M key has been held down for 1 s.

1-4 Communications Function

The E5CN/AN/EN/GN are provided with a communications function that enables parameters to be checked and set from a host computer. If the com­munications function is required, use the E53-CN@03N2 with the E5CN, or the E53-EN03 or E53-EN01 with the E5AN/EN/GN. For details on the com-
munications function, see the separate Communications Manual Basic Type.
Use the following procedure to move to the communications setting level.
1,2,3... 1. Press the O Key for at least three seconds to move from the operation lev-
el to the initial setting level.
2. Press the O Key for less than one second to move from the initial setting
level to the communications setting level.
3. Select the parameters as shown below by pressing the M Key.
4. Press the U or D Key to change the parameter setting.
15
Communications Function Section 1-4
M
M
M
M
M
M
M
psel
cwf
u-no
1
bps
9.6
len
7
sbit
2
prty
even
sdwt
20
Protocol Setting
Communications Unit No.
Communications Baud Rate
Communications Parity
Send Data Wait Time
Communications Data Length (See note.)
Communications Stop Bits (See note.)
Note The Protocol Setting parameter is displayed only when CompoWay/F commu-
nications are being used.
Setting Communications Data
Parameter name Symbol Setting (monitor) value Selection symbols Default Unit
Protocol Setting psel CompoWay/F (SYSWAY),
Communications Unit No.
Communications Baud Rate
Communications Data Length
Communications Stop Bits
Communications Parity
Send Data Wait Time
16
Match the communications specifications of the E5CN/AN/EN/GN and the host computer. If a 1:N connection is being used, ensure that the communica­tions specifications for all devices in the system (except the communications Unit No.) are the same.
Modbus
(SYSWAY)
u-no 0 to 99 1 None
cwf, mod CompoWay/F
bps 1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6
1.2, 2.4, 4.8, 9.6, 19.2, 38.4.
57.6
9.6 kbps
len 7, 8 7 Bits
sbit 1, 2 2 Bits
prty None, Even, Odd none, even, odd Even None
sdwe 0 to 99 20 ms
None
Insulation Block Diagrams Section 1-5

1-5 Insulation Block Diagrams

The insulation block diagrams for the E5CN, E5AN, E5EN, and E5GN are pro­vided in this section.
E5CN
Input, CT input, Q outputs (outputs 1 and 2)
Communications and events
Power supply
: Reinforced insulation : Functional insulation
E5CN-U
Power supply
External power supply
C output
R output
Y output
Auxiliary outputs 1 and 2
Input and Q output (output 1)
C output
R output
Y output
Auxiliary outputs 1 and 2
E5AN/EN
E5GN
Power supply
Power supply
: Reinforced insulation : Functional insulation
Input, CT input, and Q output (output 1)
Communications and events
External power supply and Q output (output 2)
C output and transfer output
R output
Y output
Auxiliary output 1
Auxiliary output 2
Auxiliary output 3
: Reinforced insulation : Functional insulation
Input, CT input, Q output (output 1)
Communications and events
C output
R output
Auxiliary output 1
Auxiliary output 2
: Reinforced insulation : Functional insulation
17
Insulation Block Diagrams Section 1-5
18
SECTION 2
Preparations
This section describes the work required to prepare the E5GN, E5CN, E5EN and E5AN Digital Temperature Controllers for installation. For operation and wiring details refer to the datasheet (H03E and H04E).
2-1 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2-1-1 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2-1-2 Removing the Temperature Controller from the Case . . . . . . . . . . . 22
2-2 Using the Support Software Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
19
Installation Section 2-1
Adapter
Waterproof packing
Panel
E53-COV17 Terminal Cover
E5CN E5CN-U

2-1 Installation

2-1-1 Mounting

E5CN/CN-U
For the Wiring Socket for the E5CN-U, order the P2CF-11 or P3GA-11 sepa­rately.
Mounting to the Panel
1,2,3... 1. For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. There is no waterproof packing included with the E5CN-U.
2. Insert the E5CN/E5CN-U into the mounting hole in the panel.
3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CN/E5CN-U.
4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m.
Mounting the Terminal Cover
For the E5CN, make sure that the “UP” mark is facing up, and then attach the E53-COV17 Terminal Cover to the holes on the top and bottom of the Temper­ature Controller.
20
Installation Section 2-1
E5AN
Waterproof packing
Panel
Terminal Cover (E53-COV16)
Mounting Bracket
E5EN
Terminal Cover (E53-COV16)
Waterproof packing
Mounting Bracket
Panel
g
E5AN/EN
Mounting to the Panel
1,2,3... 1. For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function.
2. Insert the E5AN/E5EN into the square mounting hole in the panel (thick­ness: 1 to 8 mm). Attach the Mounting Brackets provided with the product to the mounting grooves on the top and bottom surfaces of the rear case.
3. Use a ratchet to alternately tighten the screws on the top and bottom Mounting Brackets little by little to maintain balance, until the ratchet turns freely.
Mounting the Terminal Cover
Slightly bend the E53-COV16 Terminal Cover to attach it to the terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction.
Slightly bend the E53-COV16 Terminal Cover in the direction shown by the arrows to attach it to the terminal block.
Enlar
ed Illustration of Terminal Section
21
Installation Section 2-1
(1)
E5GN Mounting to the Panel
1,2,3... 1. For waterproof mounting, waterproof packing must be installed on the
Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the water­proofing function.
2. Insert the E5GN into the mounting hole in the panel.
3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5GN.
4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance.Tighten the screws to a torque of 0.29 to 0.39 N·m.
Pane l
Adapter
Waterproof packing

2-1-2 Removing the Temperature Controller from the Case

The Temperature Controller can be removed from the case to perform mainte­nance without removing the terminal leads. This is possible for only the E5CN, E5AN, and E5EN, and not for the E5CN-U or E5GN. Check the specifications of the case and Temperature Controller before removing the Temperature Controller from the case.
E5CN
Tool insertion hole
Flat-blade screwdriver
(1)
(2)
(3)
1,2,3... 1. Insert a flat-blade screwdriver into the two tool insertion holes (one on the
top and one on the bottom) to release the hooks.
2. Insert the flat-blade screwdriver in the gap between the front panel and rear case, and pull out the front panel slightly. Hold the top and bottom of the front panel and carefully pull it out toward you, without applying unnec­essary force.
(Unit: mm)
E5GN
20 min.
2.00.4
22
Installation Section 2-1
3. When inserting the body of the Temperature Controller into the case, make sure the PCBs are parallel to each other, make sure that the sealing rubber is in place, and press the E5CN toward the rear case into position. While pushing the E5CN into place, push down on the hooks on the top and bot­tom surfaces of the rear case so that the hooks are securely locked in place. Be sure that electronic components do not come into contact with the case.
Make sure the PCBs are parallel to each other, and then press the body of the Temperature Controller toward the rear case into position.
Bottom View of the E5CN
E5AN/EN
Tool insertion hole
(1)
Tool insertion hole
(1)
(2)
(3)
(1)
(2)
(3)
(1)
E5AN E5EN
Flat-blade screwdriver (Unit: mm)
2.00.4 5. 0
1,2,3... 1. Insert a flat-blade screwdriver into the two tool insertion holes (one on the
top and one on the bottom) to release the hooks.
2. Insert the flat-blade screwdriver in the gap between the front panel and rear case (two on the top and two on the bottom), and use it to pry and pull out the front panel slightly. Then, pull out on the front panel gripping both sides. Be sure not to impose excessive force on the panel.
23
Installation Section 2-1
p
p
Gap between the Front Panel and Rear Case Four gaps, two on the top and two on the bottom
View of E5AN
To
Gap between the Front Panel and Rear Case Four gaps, two on the top and two on the bottom
To
View of E5EN
3. When inserting the body of the Temperature Controller into the case, make sure the PCBs are parallel to each other, make sure that the sealing rubber is in place, and press the E5AN/EN toward the rear case until it snaps into position. While pressing the E5AN/EN into place, press down on the hooks on the top and bottom surfaces of the rear case so that the hooks securely lock in place. Make sure that electronic components do not come into con­tact with the case.
Make sure the PCBs are parallel to each other, and then press the body of the Temperature Controller toward the rear case until it snaps into position.
Bottom View of the E5EN
Make sure the PCBs are parallel to each other, and then press the body of the Temperature Controller toward the rear case until it snaps into position.
Bottom View of the E5AN
Removing the Terminal Block
The terminal block can be removed from the E5GN. It is not possible for the E5CN, E5AN, E5EN, and E5CN-U.
E5GN The body of the Controller can be replaced by removing the terminal block
from the E5GN.
1,2,3... 1. Insert a flat-blade screwdriver into the tool holes (one on the top and one
on the bottom) to release the hooks. Do not apply excessive force.
Terminal hole
Flat-blade screwdriver (Unit: mm)
20 min.
200.4
2. Pull the terminal block out while the hooks are released.
24
Installation Section 2-1
Note The method for removing the terminal block is the same for both screw termi-
nal blocks and screwless clamp terminal blocks. Do not connect a different type of terminal block to a Controller. For example, do not replace a screw terminal block with a screwless clamp terminal block. The temperature indication accuracy will decrease.
25
Using the Support Software Port Section 2-2

2-2 Using the Support Software Port

Use the communications port for Support Software to connect the personal computer to the Temperature Controller when using EST2-2C-MV4 CX­Thermo or a version of CX-Thermo higher than 4.00, or other Support Soft­ware. The E5GN is supported from CX-Thermo version 4.2. The E58-CIFQ1 USB-Serial Conversion Cable is required to make the connection.
For information concerning the models that can be used with CX-Thermo, contact your OMRON sales representative.
Procedure Use the following procedure to connect the Temperature Controller to the per-
sonal computer using the USB-Serial Conversion Cable. The USB-Serial Conversion Cable is used to communicate with the COM port of the personal computer. To perform communications using USB-Serial Conversion Cable, set the communications port (COM port) number to be used for the software to the COM port assigned to the Cable.
1,2,3... 1. Turn ON the power to the Temperature Controller.
Note If the Cable is connected when the power to the Temperature Con-
troller is OFF, power will be supplied from the personal computer and impose a load on the internal circuits of the Temperature Con­troller.
2. Connect the Cable. Connect the personal computer’s USB port with the Support Software port on the Temperature Controller using the Cable.
• Temperature Controller Connection Method
Personal computer's USB port
Communications port for Support Software
Bottom view of E5EN
E5CN/CN-U
Communications port for Support Software
E58-CIFQ1
Bottom view of E5CN
E5ANE5EN
Communications port for Support Software
Bottom view of E5AN
26
Using the Support Software Port Section 2-2
E5GN
Side View of the E5GN
Setup Tool port
Note Hold the connector when inserting or disconnecting the Cable.
3. Install the driver. Install the driver to enable the Cable to be used with the personal comput­er.
• Installation When the Cable is connected with the personal computer, the OS detects the product as a new device. At this time, install the driver using the instal­lation wizard. For details on installation methods, refer to the user’s man­ual for the E58-CIFQ1 USB-Serial Conversion Cable.
4. Setting Setup Tool Communications Conditions Set the communications port (COM port) number to be used for the CX­Thermo Setup Tool to the COM port number assigned to the USB-Serial Conversion Cable.
Refer to the E58-CIFQ1 USB-Serial Conversion Cable Instruction Manual and Setup Manual for details on how to check the COM port assigned to
the USB-Serial Conversion Cable. The communications conditions for Setup Tool COM ports are fixed as shown in the table below. Set the communications conditions for the CX­Thermo Setup Tool according to the following table.
Parameter Set value
Communications Unit No. 01
Communications baud rate 38.4 (kbps)
Communications data length 7 (bits)
Communications stop bits 2 (bits)
Communications parity Even
27
Using the Support Software Port Section 2-2
28
SECTION 3
Basic Operation
This section describes the basic operation of the E5GN, E5CN, E5EN and E5AN Digital Temperature Controllers, including key operations to set parameters and descriptions of display elements based on specific control examples.
3-1 Initial Setting Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3-2 Setting the Input Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3-2-1 Input Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3-3 Selecting the Temperature Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-3-1 Temperature Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-4 Selecting PID Control or ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-5 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-5-1 Control Periods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3-5-2 Direct and Reverse Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3-5-3 Assigned Output Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3-6 Setting the Set Point (SP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3-6-1 Changing the SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3-7 Using ON/OFF Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-7-1 ON/OFF Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3-7-2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3-8 Determining PID Constants (AT, ST, Manual Setup) . . . . . . . . . . . . . . . . . . . 42
3-8-1 AT (Auto-tuning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3-8-2 ST (Self-tuning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3-8-3 RT (Robust Tuning) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3-8-4 Manual Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3-9 Alarm Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-9-1 Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3-9-2 Alarm Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3-10 Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms. . . . . . 53
3-10-1 Heater Burnout, Heater Short, and Heater Overcurrent Alarm Operations 53
3-10-2 Installing Current Transformers (CT). . . . . . . . . . . . . . . . . . . . . . . . 54
3-10-3 Calculating Detection Current Values . . . . . . . . . . . . . . . . . . . . . . . 55
3-10-4 Settings: HB Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
3-10-5 Settings: Heater Short Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
3-10-6 Settings: Heater Overcurrent Alarm. . . . . . . . . . . . . . . . . . . . . . . . . 59
3-11 Setting the No. 3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
3-11-1 PV/SP Display Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
29
Initial Setting Examples Section 3-1

3-1 Initial Setting Examples

Initial hardware setup, including the sensor input type, alarm types, control periods, and other settings, is done using parameter displays. The O and M Keys are used to switch between parameters, and the amount of time that you press the keys determines which parameter you move to.
This section describes two typical examples.
Explanation of Examples
Example 1
Changing Parameters
in-t
0
in-h
100
in-l
cntl
onof
M
0
M
M
cntl
onof
A image means that there are parameters. Continue pressing the M key to change parameters until you reach the intended parameter.
Changing Numbers
C
25
Numeric data and selections in each
0
screen can be changed by using the U and D keys.
Input type: 5 (K thermocouple,
200°C to 1,300°C) Control method: ON/OFF control Alarm type: 2 (upper limit) Alarm value 1: 20°C (deviation) Set point: 100°C
Initial Setting Level
Operation Level
Setup Procedure
Power ON
An s.err error will be displayed if the power supply is turned ON before the sensor is connected.
Set input specifications
Set control specifications
Set alarm type
Set alarm values
Operation Level
Initial Setting Level
Check input type.
Check that control method is ON/OFF control.
Check alarm type.
Operation Level
Use the U and D keys to set the SP to 100°C.
Confirm that control is running.
Use the U and D keys to set the alarm value to 20°C.
Power ON
C
25
0
Press the O key for at least 3 s.
in-t
5
M
cntl
onof
M
alt1
2
M
Press the O key for at least 1 s.
C
25
100
M
r-s
run
M
C
al-1
20
M
PV/SP
Control stops.
Input Type: 5
ON/OFF control:
PID control:
Alarm 1 Type: 2
onof
pid
Control starts.
PV/SP:
Running
Stopped:
Alarm Value 1:
run stop
100
20
30
Start operation
Start operation.
Initial Setting Examples Section 3-1
9
20
30
2
150
onof
pid
on
off
off
run stop
Input type: 9 (T thermocouple,
200°C to 400°C) Control method: PID control PID constants found using auto­tuning (AT). Alarm type: 2 upper limit Alarm value 1: 30°C Set point: 150°C
Setup Procedure
Power ON
Initial Setting Level
Set input specifications
Set control specifications
Set alarm type
Adjustment Level
AT execution
(When PID control is selected)
Operation Level
Set alarm value
Start operation
Power ON
25
0
C
in-t
9
cntl
pid
st
off
cp
20
alt1
2
25
150
C
at
off
25
150
C
r-s
run
al-1
30
C
at
at-1
at
off
26
150
C
25
150
C
M
M
M
M
M
M
M
M
Operation Level
PV/SP
Press the O key for at least 3 s.
Control stops.
Initial Setting Level
Use the U and D keys to select the input type.
Input Type:
Use the U and D keys to select PID control.
ON/OFF control:
Use the U and D keys to set ST to OFF.
To execute ST:
PID control:
To cancel ST:
Check the control period.
Control Period (Heat) (Unit: Seconds)
Check the alarm type.
Alarm 1 Type:
For PID, set pid.
When ON, self-tuning operates.
It is recommended that 20 seconds be set for a relay output and 2 seconds for an SSR voltage output.
Press the O key for at least 1 s.
Operation Level
Use the U and D keys to set the SP to 150°C.
PV/SP:
Adjustment Level
Execute AT.
To execute 100%AT:
To cancel AT:
To execute 100% AT (auto-tuning), select at-2. To execute 40% AT, select at-1. To cancel AT, select off: (AT cancel).
Press the O key (for less than 1 s).
Press the O key (for less than 1 s).
Control starts.
Operation Level
Confirm that the set point is 150°C.
PV/SP
Confirm that control is running.
Running Stopped
Use the U and D keys to set the alarm value to 30°C.
Alarm Value 1
Start operation.
PV/SP after AT is stopped
The set point flashes during auto-tuning (AT) execution.
After AT is stopped
During AT execution
at-1
To execute 40%AT:
at-2
Example 2
31
Setting the Input Type Section 3-2
C
25
0
in-t
5
Input Type
in-t
6

3-2 Setting the Input Type

The Controller supports four input types: platinum resistance thermometer, thermocouple, infrared temperature sensor, and analog inputs. Set the input type that matches the sensor that is used. In the product specifications, there are models with thermocouple/resistance thermometer inputs (universal inputs) and models with analog input. The settings differ depending on the model. Check to make sure which model you are using.

3-2-1 Input Type

The following example shows how to set a K thermocouple for 20.0 to
500.0°C.
Operating Procedure
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
Initial Setting Level
2. Press the U Key to enter the set value of the desired sensor.
When you use a K thermocouple (20.0 to 500.0°C), enter 6 as the set value.
Hint: The key operation is saved two seconds after the change, or by press-
ing the O or M Key.
32
Setting the Input Type Section 3-2
List of Input Types
Input type Specifications Set value Input temperature setting range
Controllers with Ther­mocouple/ Resistance Thermome­ter Multi­input
Platinum resistance thermometer
Thermocouple K
Infrared temperature sensor ES1B
Analog input 0 to 50 mV 23 Either of the following ranges, by scaling:
Thermocouple W 24 0 to 2,300 (°C)/0 to 3,200 (°F)
Pt100 0 200 to 850 (°C)/300 to 1,500 (°F)
1 199.9 to 500.0 (°C)/199.9 to 900.0 (°F)
2 0.0 to 100.0 (°C)/0.0 to 210.0 (°F)
JPt100 3 199.9 to 500.0 (°C)/199.9 to 900.0 (°F)
4 0.0 to 100.0 (°C)/0.0 to 210.0 (°F)
5 200 to 1,300 (°C)/300 to 2,300 (°F)
6 20.0 to 500.0 (°C)/0.0 to 900.0 (°F)
J7−100 to 850 (°C)/−100 to 1,500 (°F)
8 20.0 to 400.0 (°C)/0.0 to 750.0 (°F)
T9−200 to 400 (°C)/−300 to 700 (°F)
10 199.9 to 400.0 (°C)/199.9 to 700.0 (°F)
E11−200 to 600 (°C)/−300 to 1,100 (°F)
L12−100 to 850 (°C)/−100 to 1,500 (°F)
U13−200 to 400 (°C)/−300 to 700 (°F)
14 199.9 to 400.0 (°C)/199.9 to 700.0 (°F)
N15−200 to 1,300 (°C)/−300 to 2,300 (°F)
R 16 0 to 1,700 (°C)/0 to 3,000 (°F)
S 17 0 to 1,700 (°C)/0 to 3,000 (°F)
B 18 100 to 1,800 (°C)/300 to 3,200 (°F)
10 to 70°C 19 0 to 90 (°C)/0 to 190 (°F)
60 to 120°C 20 0 to 120 (°C)/0 to 240 (°F)
115 to 165°C 21 0 to 165 (°C)/0 to 320 (°F)
140 to 260°C 22 0 to 260 (°C)/0 to 500 (°F)
1,999 to 9,999
199.9 to 999.9
PLII 25 0 to 1,300 (°C)/0 to 2,300 (°F)
Models with analog input
• The default is 5.
• If a platinum resistance thermometer is mistakenly connected while a set­ting for other than a platinum resistance thermometer is in effect, S.ERR will be displayed. To clear the S.ERR display, check the wiring and then turn the power OFF and back ON. Make sure that the setting of the input
type parameter agrees with the sensor that is connected.
Input type Specifications Set value Input temperature setting range
Current input 4 to 20 mA
0 to 20 mA 1
Voltage input 1 to 5 V 2
0 to 5 V 3
0 to 10 V 4
0 Either of the following ranges, by scaling:
1,999 to 9,999
199.9 to 999.9
19.99 to 99.99
1.999 to 9.999
• The default is 0.
33
Selecting the Temperature Unit Section 3-3
C
30
0
in-t
5
Input Type
d-u
c
Temperature Unit
cp
c-cp
Control Period (Heating)
Control Period (Cooling)

3-3 Selecting the Temperature Unit

3-3-1 Temperature Unit

• Either °C or °F can be selected as the temperature unit.
• Set the temperature unit in the Temperature Unit parameter of the initial setting level. The default is c (°C).
Operating Procedure The following example shows how to select °C as the temperature unit.
Operation Level
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Temperature Unit parameter by pressing the M Key. Press the U or D Key to select either °C or °F.
c: °C f: °F
3. To return to the operation level, press the O Key for at least one second.

3-4 Selecting PID Control or ON/OFF Control

Two control methods are supported: 2-PID control and ON/OFF control. Switching between 2-PID control and ON/OFF control is executed by means of the PID ON/OFF parameter in the initial setting level. When this parameter is set to pid, 2-PID control is selected, and when set to onof, ON/OFF con­trol, is selected. The default is onof.
2-PID Control PID control is set by AT (auto-tuning), ST (self-tuning), or manual setting.
For PID control, set the PID constants in the Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters.
ON/OFF Control In ON/OFF control, the control output is turned ON when the process value is
lower than the current set point, and the control output is turned OFF when the process value is higher than the current set point (reverse operation).

3-5 Setting Output Specifications

3-5-1 Control Periods

• Set the output periods (control periods). Though a shorter period provides better control performance, it is recommended that the control period be set to 20 seconds or longer for a relay output to preserve the service life of the relay. After the settings have been made in the initial setup, readjust the control period, as required, by means such as trial operation.
• Set the control periods in the Control Period (Heating) and Control Period (Cooling) parameters in the initial setting level. The default is 20 seconds.
• The Control Period (Cooling) parameter is used only for heating/cooling control.
• When control output 1 is used as a current output, Control Period (Heat­ing) cannot be used.
34
Setting Output Specifications Section 3-5
100%
0%
100%
0%
Manipulated variable Manipulated variable
Low temperature
Set Value High
temperature
Low temperature
Set Value High
temperature
Direct operation Reverse operation
C
30
0
in-t
5
Input Type
d-u
c
Temperature Unit
cp
20
Control Period (Heating)

3-5-2 Direct and Reverse Operation

• Direct operation increases the manipulated variable whenever the pro­cess value increases. Reverse operation decreases the manipulated vari­able whenever the process value increases.
For example, when the process value (PV) is lower than the set point (SP) in a heating control system, the manipulated variable increases according to the difference between the PV and SP. Accordingly, reverse operation is used in a heating control system. Direct operation is used in a cooling con­trol system, in which the operation is the opposite of a heating control sys­tem. The Control Output 1 Assignment is set to o (control output (heating)) for either direct or reverse operation.
• Direct/reverse operation is set in the Direct/Reverse Operation parameter in the initial setting level. The default is or-r (reverse operation).
Operating Procedure In this example, the input type, temperature unit, direct/reverse operation, and
control period (heat) parameters are checked.
Operation Level
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
2. The input type is displayed. When the input type is being set for the first
3. Select the Temperature Unit parameter by pressing the M Key. The de-
4. Select the Control Period (Heating) parameter by pressing the M Key.
Input type = s (K thermocouple) Temperature unit = c (°C) Direct/reverse operation = or-r (reverse operation) Control period (heat) = 20 (seconds)
level to the initial setting level.
time, s (K thermocouple) is set. To select a different sensor, press the U or D Key.
fault is c (°C). To select f (°F), press the U Key.
The default is 20.
35
Setting Output Specifications Section 3-5
orev
or-r
Direct/Reverse Operation
C
30
0
PV/SP
amov
0
Move to Ad­vanced Function Setting Level
5. Select the Direct/Reverse Operation parameter by pressing the M Key. The default is or-r (reverse operation). To select or-d (direct opera­tion), press the U Key.
Operation Level
6. To return to the operation level, press the O Key for at least one second.
7. Select the Move to Advanced Function Setting Level parameter by press­ing the M Key.

3-5-3 Assigned Output Functions

• Function assignments can be changed by changing the settings for con­trol and auxiliary output assignments.
• The default function assignments for each output are shown below.
Parameter name Symbol Initial status
Control Output 1 Assignment out1 Control output (heating) Control Output 2 Assignment out2 Not assigned. Auxiliary Output 1 Assignment sub1 Alarm 1 Auxiliary Output 2 Assignment sub2 Alarm 2
Auxiliary Output 3 Assignment (E5AN/EN only)
• Refer to pages 240 to 242 of H156 for the functions that can be assigned to the outputs.
• Each output is automatically initialized as shown below by changing the control mode.
sub3 Alarm 3
Example: E5CN
Parameter name Symbol Without control output 2 With control output 2
Standard Heating/cooling Standard Heating/cooling
Control Output 1 Assignment
Control Output 2 Assignment
Auxiliary Output 1 Assignment
Auxiliary Output 2 Assignment
out1 Control output
(heating)
out2 Not assigned.
(See note 1.)
sub1 Alarm 1
(See note 2.)
sub2 Alarm 2
(See note 3.)
Control output (heating)
Not assigned. (See note 1.)
Alarm 1 (See note 2.)
Control output (cooling) (See note 3.)
Control output (heating)
Not assigned. Control output
Alarm 1 (See note 2.)
Alarm 2 Alarm 2
Control output (heating)
(cooling)
Alarm 1 (See note 2.)
Example: E5GN
Parameter name Symbol Standard Heating/cooling
Control Output 1 Assignment
Auxiliary Output 1 Assignment
Auxiliary Output 2 Assignment
out1 Control output
(heating)
sub1 Alarm 1
(See note 2.)
sub2 Alarm 2 Alarm 2
Control output (heating)
Control output (cooling)
36
Setting Output Specifications Section 3-5
C
25
100
PV/SP
in-t
5
Input Type
5-hc
stnd
Standard or Heating/Cooling
5-hc
h-c
amov
0
Move to Ad­vanced Function Setting Level
init
off
Parameter Initialization
Note (1) There is no control output 2 and no parameter assignment is displayed
for that output.
(2) The Auxiliary Output 1 Assignment parameter becomes the program end
output unless the Program Pattern parameter is set to OFF.
(3) For the E5AN/EN, the Auxiliary Output 3 Assignment parameter is set as
the control output for cooling. (The Auxiliary Output 2 Assignment param­eter is set for alarm 2).
Alarms
It will be specified in this section when an alarm must be assigned, i.e., when an alarm must be set for the Control Output 1 or 2 Assignment parameters, or for the Auxiliary Output 1 to 3 Assignment parameters. For example, if alarm 1 is set for the Control Output 1 Assignment parameter, then alarm 1 has been assigned.
Assigning a work bit to either control output 1 or 2 or to auxiliary output 1 to 3 is also considered to be the same as assigning an alarm. For example, if work bit 1 is set for the Auxiliary Output 1 Assignment parameter, then alarms 1 to 3 have been assigned.
Operating Procedure This procedure sets the following control and auxiliary output assignments.
Control output 1: Control output (heating); Control output 2: Control output (cooling); Auxiliary output 1: Alarm 1; Auxiliary output 2: Alarm 2
Operation Level
Initial Setting Level
Initial Setting Level
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Standard or Heating/Cooling parameter by pressing the M
Key.
3. Press the U Key to set the parameter to h-c.
Note The following output assignments do not need to be set because they
are set automatically by changing the control mode, but they are shown here as a reference for checking the assignments for each out­put.
4. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 1-3 (page
14) Moving to the Advanced Fu nction Setting Level.)
Advanced Function Setting Level
5. Press the D Key to enter the password (“169”), and move from the initial
setting level to the advanced function setting level.
37
Setting Output Specifications Section 3-5
out1
o
Control Output 1 Assignment
out1
o
out2
c-o
Control Output 2 Assignment
out2
c-o
sub1
alm1
Auxiliary Output 1 Assignment
sub1
alm1
sub2
alm2
Auxiliary Output 2 Assignment
sub2
alm2
in-t
5
Input Type
C
25
100
PV/SP
Advanced Function Setting Level
Advanced Function Setting Level
Advanced Function Setting Level
6. Select the Control Output 1 Assignment parameter by pressing the M
Key.
7. Press the U or D Key to set o. (The default is o.)
8. Select the Control Output 2 Assignment parameter by pressing the M Key.
9. Press the U or D Key to set c-o. (When h-c is selected for the Standard or Heating/Cooling parameter, the setting will be c-o.)
10. Select the Auxiliary Output 1 Assignment parameter by pressing the M Key.
11. Press the U or D Key to set alm1. (The default is alm1.)
Advanced Function Setting Level
Initial Setting Level
Operation Level
Auxiliary Output Opening or Closing in Alarm
12. Select the Auxiliary Output 2 Assignment parameter by pressing the M Key.
13. Press the U or D Key to set alm2. (The default is alm2.)
14. Press the O Key for at least one second to move from the advanced function setting level to the initial setting level.
15. Press the O Key for at least one second to move from the initial setting level to the operation level.
• When “close in alarm” is set, the status of the auxiliary output is output unchanged. When “open in alarm” is set, the status of the auxiliary output function is reversed before being output.
• Each auxiliary output can be set independently.
• These settings are made in the Auxiliary Output 1 to 3 Open in Alarm parameters (advanced function setting level).
• The default is n-o: Close in Alarm.
38
Setting the Set Point (SP) Section 3-6
C
20
0
20
0
50.0
C
C
30
0
C
30
200
• When “open in alarm” is set for the alarm 1 output, the open in alarm sta­tus is also applied to heater burnout, HS alarm, heater overcurrent, and input error outputs.
Auxiliary output functions 1 to 3
Close in Alarm ON ON Lit
OFF OFF Not lit
Open in Alarm ON OFF Lit
OFF ON Not lit
• The alarm output will turn OFF (i.e., the relay contacts will open) when power is interrupted and for about two seconds after the power is turned ON regardless of the setting of the Auxiliary Output 1 to 3 Open in Alarm parameter.
Auxiliary
output
Indicators
(SUB1 to SUB3)

3-6 Setting the Set Point (SP)

Operation Level
Operation Level
The operation level is displayed when the power is turned ON. The process value (PV) is at the top of the display, and the set point (SP) is at the bottom.
For Controllers that support a No. 3 display (E5AN/E5EN), the contents set in the PV/SP Display Screen Selection parameter (advanced function setting level) are displayed below the PV and SP.
The MV is displayed as the default. For details, refer to 3-11 Setting the No. 3 Display.

3-6-1 Changing the SP

• The set point cannot be changed when the Operation/Adjustment Protect
parameter is set to 3. For details, refer to 4-9 of H156 Using the Key Pro- tect Level.
• To change the set point, press the U or D Key in the Process Value/Set Point parameter (in the operation level), and set the desired set value. The new set point is selected two seconds after you have specified the new value.
• Multi-SP is used to switch between two or four set points. For details, refer
to 4-5 of H156 Using Event Inputs for details.
Operating Procedure In this example, the set point is changed from 0°C to 200°C.
Operation Level
1. Normally, the Process Value/Set Point parameter is displayed. The set point is 0°C.
2. Use the U and D Keys to set the set point to 200°C.
39
Using ON/OFF Control Section 3-7
PV
ON
OFF
Reverse operation
Hysteresis (heating)
Set point

3-7 Using ON/OFF Control

In ON/OFF control, the control output turns OFF when the temperature being controlled reaches the preset set point. When the manipulated variable turns OFF, the temperature begins to fall and the control turns ON again. This oper­ation is repeated over a certain temperature range. At this time, how much the temperature must fall before control turns ON again is determined by the Hys­teresis (Heating) parameter. Also, what direction the manipulated variable must be adjusted in response to an increase or decrease in the process value is determined by the Direct/Reverse Operation parameter.

3-7-1 ON/OFF Control

• Switching between 2-PID control and ON/OFF control is performed using the PID ON/OFF parameter in the initial setting level. When this parame­ter is set to pid, 2-PID control is selected, and when it is set to onof, ON/ OFF control is selected. The default is onof.
Hysteresis • With ON/OFF control, hysteresis is used to stabilize operation when
switching between ON and OFF. The control output (heating) and control output (cooling) functions are set in the Hysteresis (Heating) and Hystere­sis (Cooling) parameters, respectively.
• In standard control (heating or cooling control), the setting of the Hystere­sis (Heating) parameter in the adjustment level is used as the hysteresis regardless of whether the control type is heating control or cooling con­trol.
Three-position Control
40
• In heating/cooling control, a dead band (an area where both control out­puts are 0) can be set to either the heating or cooling side. This makes it possible to use 3-position control.
Reverse operation
Dead band
Hysteresis (heating) Hysteresis (cooling)
ON
Heating side
OFF
Set point
Cooling side
PV
Using ON/OFF Control Section 3-7
C
25
100
PV
in-t
5
Input Type
cntl
onof
PID ON/OFF
C
25
100
PV/SP
C
25
200
Parameters
Symbol Parameter: level Application
s-hc cntl orev c-db hys chys
Standard or Heating/Cooling: Initial setting level PID ON/OFF: Initial setting level Direct/Reverse Operation: Initial setting level Dead Band: Adjustment level Hysteresis (Heating): Adjustment level Hysteresis (Cooling): Adjustment level
Specifying control method Specifying control method Specifying control method Heating/cooling control ON/OFF control ON/OFF control

3-7-2 Settings

To execute ON/OFF control, set the Set Point, PID ON/OFF, and Hysteresis parameters.
Setting the PID ON/OFF Parameter
Operating Procedure Confirm that the PID ON/OFF parameter is set to onof in the initial setting
level.
Operation Level
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. The Input Type parameter is displayed in the initial setting level.
3. Select the PID ON/OFF parameter by pressing the M Key.
4. Check that the set value is onof (i.e., the default).
5. To return to the operation level, press the O Key for at least one second.
Next, set the set point value.
Setting the SP
Operating Procedure In this example, the set point is set to 200. The set value (i.e., the SP) is
shown at the bottom of the display.
Operation Level
1. Select the Process Value/Set Point parameter in the operation level.
2. Use the U and D Keys to set the SP. (In this example, it is set to 200.) The new set value can be saved by pressing the M Key, or it will go into effect after two seconds have elapsed.
Next, set the hysteresis.
41
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
C
25
200
PV
1.adj
Adjustment Level Display
hys
1.0
Hysteresis (Heating)
C
hys
2.0
C
Setting the Hysteresis
Operating Procedure Set the hysteresis to 2.0°C.
Operation Level
Adjustment Level
1. Press the O Key to move from the operation level to the adjustment level.
2. The Adjustment Level Display parameter will be displayed in the adjust­ment level.
3. Select the Hysteresis (Heating) parameter by pressing the M Key.
4. Press the U and D Keys to set the hysteresis (2.0 in this example). Ei­ther press the M Key or wait for at least two seconds after setting the hys­teresis value to confirm the setting.
5. To return to the operation level, press the O Key.

3-8 Determining PID Constants (AT, ST, Manual Setup)

3-8-1 AT (Auto-tuning)

at
• When AT is executed, the optimum PID constants for the set point at that time are set automatically. A method (called the limit cycle method) for forcibly changing the manipulated variable and finding the characteristics of the control object is employed.
• Either 40% AT or 100% AT can be selected depending on the width of MV variation in the limit cycle. In the AT Execute/Cancel parameter, specify at-2 (100% AT) or at-1 (40% AT). To cancel AT, specify off (AT can- cel).
• Only 100% AT can be executed for heating and cooling control.
• AT cannot be executed when control has stopped or during ON/OFF con­trol.
• The results of AT are reflected in the Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters in the adjustment level.
Adjustment Level
C
Proportional Band
p
(0
Integral Time
i
233
Derivative Time
d
40
42
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
y
C
25
100
C
25
100
PV/SP
AT execution in progress
No. 2 display
AT Operations AT is started when either at-2 (100% AT) or at-1 (40% AT) is specified for
the AT Execute/Cancel parameter. During execution, the AT Execute/Cancel parameter on the No. 1 display flashes. When AT ends, the AT Execute/Can­cel parameter turns OFF, and the No. 1 display stops flashing.
AT Execute/Cancel
at
off
100% AT execution in progress
If you move to the operation level during AT execution, the No. 2 display flashes to indicate that AT is being executed.
Only the Communications Writing, RUN/STOP, AT Execution/Cancel, and Pro­gram Start parameters can be changed during AT execution. Other parame­ters cannot be changed.
AT Calculated Gain
The AT Calculated Gain parameter sets the gain for when PID values are cal­culated using AT. When emphasizing response, decrease the set value. When emphasizing stability, increase the set value.
AT Hysteresis
The AT Hysteresis parameter sets the hysteresis when switching ON and OFF for the limit cycle operation during auto-tuning.
at
at-2
No. 1 displa
Limit Cycle MV Amplitude
The Limit Cycle MV Amplitude parameter sets the MV amplitude for limit cycle operation during auto-tuning.
Note This setting is disabled for 100% AT.
40% AT
The width of MV variation in the limit cycle can be changed in the Limit Cycle MV Amplitude parameter, but the AT execution time may be longer than for 100% AT. The limit cycle timing varies according to whether the deviation (DV) at the start of auto-tuning execution is less than 10% FS.
PV
SP
Deviation 10% FS
AT started
Limit Cycle MV Amplitude 40%
Deviation: 10% FS
PV
SP
Time
AT ended
Deviation < 10% FS
Limit Cycle MV Amplitude 40%
Deviation: 10% FS
AT started AT ended
Time
43
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
at
off
AT Execute/ Cancel
at
at-1
at
off
C
25
0
PV
100% AT
Operation will be as shown in the following diagram, regardless of the devia­tion (DV) at the start of AT execution. To shorten the AT execution time, select 100% AT.
PV
SP
AT started AT ended
Note The Limit Cycle MV Amplitude parameter is disabled.
Operating Procedure This procedure executes 40%AT.
Adjustment Level
1. Press the O Key to move from the operation level to the adjustment level.
2. Press the U Key to select at-1. The No. 1 display for AT Execute/Cancel
will flash during AT execution.
3. off will be displayed when AT ends.
Limit Cycle MV Amplitude 100%
Time
Operation Level

3-8-2 ST (Self-tuning)

ST (self-tuning) is a function that finds PID constants by using step response
st
tuning (SRT) when Controller operation begins or when the set point is changed.
Once the PID constants have been calculated, ST is not executed when the next control operation is started as long as the set point remains unchanged.
ST (self-tuning) is enabled when the ST parameter is set to ON in the initial setting level.
When the ST function is in operation, be sure to turn the power supply of the load connected to the control output ON simultaneously with or before starting Controller operation.
When executing self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Digital Temperature Controller. If power is turned ON for the Digital Temperature Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved.
4. To return to the operation level, press the O Key.
44
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
in-t
5
Input Type
st
on
ST
C
25
100
PV
Note PID Constants
When control characteristics are already known, PID constants can be set directly to adjust control. PID constants are set in the Proportional Band (P), Integral Time (I), and Derivative Time (D) parameters in the adjustment level.
Operating Procedure This procedure executes self-tuning (ST).
Initial Setting Level
Operation Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the ST parameter by pressing the M Key.
3. Press the U Key to select on. ON is the default.
4. To return to the operation level, press the O Key for at least one second.
The temperature display flashes during self-tuning (ST) execution.
Startup Conditions Self-tuning by step response tuning (SRT) is started when the following condi-
tions are met after program execution is started and the set point is changed.
At start of operation When set point is changed
1. The set point at the start of operation differs from the set point when the pre­vious SRT was executed. (See note 1.)
2. The difference between the tempera­ture at the start of operation and the set point is greater both of the following: (Present proportional band × 1.27 + 4°C) and the ST stable range.
3. The temperature at the start of opera­tion is lower than the set point during reverse operation, and is larger than the set point during direct operation.
4. There is no reset from input errors.
1. The new set point differs from the set point used when the previous SRT was executed. (See note 1.)
2. The set point change width is greater both of the following: (Present propor­tional band × 1.27 + 4°C) and the ST stable range.
3. During reverse operation, the new set point is larger than the set point before the change; and during direct opera­tion, the new set point is smaller than the set point before the change.
4. The temperature is stable. (See note
2.) (Equilibrium with the output amount at 0% when the power is turned ON is also all right.) (See note 3.)
Note (1) The previous SRT-implemented set point is the set point that was used for
calculating the PID constants for the previous SRT.
(2) In this state, the measurement point is within the ST stable range.
(3) In this state, the change width of the PV every 60 seconds is within the
ST stable range or less.
In the following instances, PID constants are not changed by self-tuning (ST) for the present set point.
1,2,3... 1. When the PID constants have been changed manually with ST set to ON.
2. When auto-tuning (AT) has been executed.
ST Stable Range
Operating Procedure The ST stable range determines the condition under which ST (self-tuning)
functions.
45
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
C
st-b
1%0
ST Stable Range
C
st-b
2*0
Temperature Temperature
Much hunting occurs.
Set value Set value
Start of control Start of control
Time Time
Hunting is reduced.
This procedure sets the ST stable range to 20.0°C.
Advanced Function Setting Level
1. Select the ST Stable Range parameter by pressing the M Key in the ad-
vanced function setting level.
2. Use the U Key to set the parameter to 20.0°C.

3-8-3 RT (Robust Tuning)

• When AT or ST is executed with RT selected, PID constants are automat-
rt
ically set that make it hard for control performance to degenerate even when the characteristics of the controlled object are changed.
• RT can be set in the advanced function setting level when PID control has been set.
• The RT mode cannot be selected while an analog input is set.
• Selecting the RT mode in the following cases will help to prevent hunting from occurring.
• When the set temperature is not constant and is changed in a wide range
• When there are large variations in ambient temperatures due to factors such as seasonal changes or differences between day and night tem­peratures
• When there are large variations in ambient wind conditions and air flow
• When heater characteristics change depending on the temperature
• When an actuator with disproportional I/O, such as a phase-control­type power regulator, is used
• When a rapidly heating heater is used
• When the control object or sensor has much loss time
• When hunting occurs in normal mode for any reason
• PID constants are initialized to the factory settings by switching to RT mode.
• When the RT mode is selected, the derivative time setting unit be­comes the second.
RT Features • Even when hunting occurs for PID constants when AT or ST is executed
46
in normal mode, it is less likely to occur when AT or ST is executed in RT mode.
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
Temperature Temperature
Set value
Set value
Start of control Start of control
Time Time
C
25
100
PV/SP
in-t
5
Input Type
amov
0
Move to Ad­vanced Function Setting Level
init
off
Parameter Initialization
rt
off
RT
rt
on
in-t
5
Input Type
• When the temperature (PV) falls short of the set point for the PID con­stants when using AT or ST in normal mode, executing AT or ST in RT mode tends to improve performance.
• When the manipulated variable (MV) is saturated, the amount of over­shooting may be somewhat higher in comparison to PID control based on AT or ST in normal mode.
Operating Procedure This procedure selects RT mode.
Operation Level
Initial Setting Level
Initial Setting Level
Advanced Function Setting Level
Advanced Function Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key.
3. Use the D Key to enter “169” (the password).
It is possible to move to the advanced function setting level by pressing the M Key or leaving the setting for at least two seconds.
4. Press the M Key to select rt.
Initial Setting Level
5. Press the U Key to select on. off is the default.
6. To return to the initial setting level, press the O Key for at least one sec-
ond.
47
Determining PID Constants (AT, ST, Manual Setup) Section 3-8
C
25
100
PV/SP
l.adj
Adjustment Level Display
C
p
8.0
Proportional Band
C
p
10.0
i
233
Integral Time
i
250
d
40
Derivative Time
d
45
Operation Level
7. To return to the operation level, press the O Key for at least one second.

3-8-4 Manual Setup

Individual PID constants can be manually set in the Proportional Band, Inte­gral Time, and Derivative Time parameters in the adjustment level.
Operating Procedure In this example, the Proportional Band parameter is set to 10.0, the Integral
Time parameter to 250, and the Derivative Time parameter to 45.
Adjustment Level
1. Press the O Key to move from the operation level to the adjustment level.
2. Press the M Key to select the proportional band” parameter.
3. Use the U and D Keys to set 10.0.
4. Press the M Key to select the Integral Time parameter.
5. Use the U and D Keys to set 250.
6. Select the Derivative Time operation by pressing the M Key.
7. Use the U and D Keys to set 45.
8. To return to the operation level, press the O Key.
Note Proportional Action
When PID constants I (integral time) and D (derivative time) are set to 0, con­trol is executed according to proportional action. As the default, the center value of the proportional band becomes the set point. Related parameter: Manual reset value (adjustment level)
48
Alarm Outputs Section 3-9
When P (Proportional Band) Is Adjusted
Increased The curve rises gradually, and a long
Set value
stabilization time is created, but over­shooting is prevented.
Decreased Overshooting and hunting occur, but
Set value
the set value is quickly reached and the temperature stabilizes.
When I (Integral Time) Is Adjusted
Increased It takes a long time to reach the set
Decreased Overshooting and undershooting occur.
Set value
Set value
point. It takes time to achieve a stable state, but overshooting, undershooting, and hunting are reduced.
Hunting occurs. The Controller starts up faster.
When D (Derivative Time) Is Adjusted
Increased Overshooting, undershooting, and sta-
Decreased Overshooting and undershooting
Set value
Set value
bilization times are reduced, but fine hunting occurs on changes in the curve itself.
increase, and it takes time to return to the set point.

3-9 Alarm Outputs

• Alarms can be used by the E5CN-@2@@@ (2 auxiliary outputs), E5AN/ E5EN-@1@@@ (1 auxiliary output), E5AN/E5EN-@3@@@ (3 auxiliary out­puts), the E5CN-@1@@@U (1 auxiliary output), the E5CN-@2@@@U (2 auxiliary outputs), E5GN-@1@@@ (1 auxiliary output), and E5GN­@2@@@ (2 auxiliary outputs). Alarms can also be used by setting the Control Output 1 Assignment or Control Output 2 Assignment parameter to any of the alarms from alarm 1 to 3. The alarm output condition is determined by a combination of the alarm type, alarm value, alarm hysteresis, and the standby sequence. For details, refer to 4-2 Alarm Hysteresis.
• This section describes the Alarm Type, Alarm Value, Upper-limit Alarm and Lower-limit Alarm parameters.

3-9-1 Alarm Types

Set value Alarm type Alarm output operation Description of function
When alarm value X
is positive
0 Alarm function OFF Output OFF No alarm
1 (See note
1.)
2 Upper-limit Set the upward deviation in the set
Upper- and lower-limit See note 2. Set the deviation in the set point by
ON OFF
ON OFF
LH
SP
X
SP
When alarm value X
is negative
X
ON OFF
SP
setting the alarm upper limit (H) and alarm lower limit (L).
point by setting the alarm value (X).
49
Alarm Outputs Section 3-9
ON OFF
X
0
X
ON OFF
0
ON OFF
X
0
0
Set value Alarm type Alarm output operation Description of function
When alarm value X
is positive
3 Lower-limit Set the downward deviation in the
4 (See note
1.)
5 (See note
1.)
Upper- and lower-limit range
Upper- and lower-limit with standby sequence
ON OFF
ON OFF
ON OFF
X
SP
LH
SP
LH
SP
See note 5.
When alarm value X
is negative
ON OFF
SP
X
set point by setting the alarm value (X).
See note 3. Set the deviation in the set point by
setting the alarm upper limit (H) and alarm lower limit (L).
See note 4. A standby sequence is added to
the upper- and lower-limit alarm (1). (See note 6.)
6 Upper-limit with standby
sequence
7 Lower-limit with standby
sequence
8 Absolute-value upper-
limit
ON OFF
ON OFF
ON OFF
X
SP
X
SP
X
0
ON OFF
ON OFF
ON OFF
X
SP
X
SP
X
0
A standby sequence is added to the upper-limit alarm (2). (See note
6.)
A standby sequence is added to the lower-limit alarm (3). (See note
6.)
The alarm will turn ON if the pro­cess value is larger than the alarm value (X) regardless of the set point.
9 Absolute-value lower-limit The alarm will turn ON if the pro-
ON OFF
X
0
cess value is smaller than the alarm value (X) regardless of the set point.
10 Absolute-value upper-
limit with standby sequence
11 Absolute-value lower-limit
with standby sequence
ON OFF
ON OFF
X
0
X
0
A standby sequence is added to the absolute-value upper-limit alarm (8). (See note 6.)
A standby sequence is added to the absolute-value lower-limit alarm (9). (See note 6.)
12 LBA (alarm 1 type only) --- (See note 7.)
13 PV change rate alarm --- Refer to page 52. (See note 8.)
Note (1) With set values 1, 4, and 5, the upper- and lower-limit values can be set
independently for each alarm type, and are expressed as “L” and “H.”
(2) Set value: 1 (Upper- and lower-limit alarm)
50
Case 1 Case 2 Case 3 (Always ON)
LH
H < 0, L > 0
|H| < |L|
SP
LH
SP
H > 0, L < 0
|H| > |L|
SP
LH
SP
SP
LH
H < 0, L > 0
|H| |L|
H > 0, L < 0
|H| |L|
H < 0, L < 0
LH
(3) Set value: 4 (Lower limit range)
Case 1
LH
H < 0, L > 0
|H| < |L|
Case 2 Case 3 (Always OFF)
SP
HL
SP
H > 0, L < 0
|H| > |L|
LLH
SP
SP
SP
H < 0, L <
LH
H < 0, L > 0
|H| |L|
H > 0, L < 0
H
|H| |L|
(4) Set value: 5 (Upper- and lower-limit with standby sequence)
• For the lower-limit alarms in cases 1 and 2 above, the alarm is always OFF if upper- and lower-limit hysteresis overlaps.
• In case 3, the alarm is always OFF.
Alarm Outputs Section 3-9
al1l
al1h
al2l
al2h
al-1
al-2
al3l
al3h
al-3
Alarm Lower Limit Value
Alarm Upper Limit Value
Alarm Value
in-t
5
Input Type
alt1
2
Alarm 1 Type
C
25
100
PV/SP
(5) Set value: 5 (Upper- and lower-limit with standby sequence)
• The alarm is always OFF if upper- and lower-limit hysteresis overlaps.
(6) Refer to 4-2-1 Standby Sequence for information on the operation of the
standby sequence.
(7) Refer to 4-12 of H156: Loop Burnout Alarm (LBA). (8) Refer to PV Change Rate Alarm on page 52.
• Set the alarm type independently for each alarm in the Alarm 1 to 3 Type parameters in the initial setting level. The default is 2 (Upper-limit alarm).

3-9-2 Alarm Values

• Alarm values are indicated by “X” in the table on the previous page. When the upper and lower limits are set independently, “H” is displayed for upper limit values, and “L” is displayed for lower limit values.
• To set the alarm value upper and lower limits for deviation, set the upper and lower limits in each of the Alarm 1 to 3 Upper Limit, and Alarm 1 to 3 Lower Limit parameters in the operation level.
Operating Procedure This procedure sets alarm 1 as an upper-limit alarm. The related parameters
and settings are shown below. The alarm is output when the set point exceeds 10°C. (In this example, the temperature unit is °C.)
Alarm 1 type = 2 (Upper-limit alarm) Alarm value 1= 10
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Alarm 1 Type parameter by pressing the M Key. Confirm that
the set value is 2. The default value is 2 (Upper-limit alarm).
3. To return to the operation level, press the O Key for at least one second.
51
Alarm Outputs Section 3-9
C
al-1
0
Alarm Value 1
C
al-1
10
4. Select the Alarm Value 1 parameter by pressing the M Key.
5. Use the U Key to set the parameter to 10.
PV Change Rate Alarm The change width can be found for PV input values in any set period. Differ-
ences with previous values in each set period are calculated, and an alarm is output if the result exceeds the alarm value. The PV rate of change calculation period can be set in units of 250 ms.
If a positive value is set for the alarm value, the PV will operate as a change rate alarm in the rising direction. If a negative value is set, the PV will operate as a change rate alarm in the falling direction.
Precaution
If a shorter PV rate of change calculation period is set, outputs set for the PV change rate alarm function may repeatedly turn ON and OFF for a short period of time. It is therefore recommended that the PV change rate alarm be used with the alarm latch turned ON.
PV
Alarm value
0
ON
Alarm function
Parameter name Setting range Unit Default
PV Rate of Change Calcu­lation Period
OFF
1 to 999 Sampling cycle 4 (1 s)
OFF
PV change width for PV rate of change calculation period
ON
Time
52

Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10

3-10 Using Heater Burnout, Heater Short, and Heater
Overcurrent Alarms
3-10-1 Heater Burnout, Heater Short, and Heater Overcurrent Alarm
Operations
• Heater burnout detection and heater overcurrent detection are executed by measuring heater current while the control output (heating) is ON, and heater short detection is executed by measuring heater current while it is OFF. For details, refer to the following table. (Heater burnout detection, heater short detection, and heater overcurrent detection cannot be used with the control output for cooling.)
Control output (heating) status Power to heater HB alarm
Control output
(heating)
ON Lit Yes (Normal) (See note 1.) OFF --- ---
OFF Not lit Yes (HS alarm) --- ON ---
ON Lit Normal --- --- OFF
Operation
indicator
No (Heater burnout) ON --- ---
No (Normal) (See note 2.) --- OFF ---
Heater overcurrent status (See note 3.)
ON
Control output (heating)
OFF
output
--- --- ON
Ton
(See note 4.)
HS alarm
output
Tof f
(See note 5.)
Heater overcurrent
Note (1) In the above diagram, power is considered to be ON (normal) if the heater
current is greater than the heater burnout detection current during the Ton interval. If the heater is burned out, the measured current decreases and falls below the heater burnout detection value. The output is then activat­ed as the heater burnout alarm.
(2) In the above diagram, power is considered to be OFF (normal) if the leak-
age current is less than the HS alarm current during the Toff interval. If the SSR output is short-circuited, the measured current increases be­yond the HS alarm value. The output is then activated as the HS alarm.
(3) In the above diagram, it is regarded as normal when the heater current is
less than the heater overcurrent detection current during the Ton period. Current is increased when excessive current flows to the heater, causing the heater overcurrent detection value to be exceeded and an OC (heater overcurrent) alarm to be output.
(4) Heater burnout and heater overcurrent are not detected if the control out-
put (heating) ON time (Ton) is 100 ms or less.
(5) HS alarms are not detected if the control output (heating) OFF time (Toff)
is 100 ms or less.
alarm output
53
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
CT
Load Load (such as a heater)
AC line
Product To CT input
• For Controllers with heater burnout, HS, and heater overcurrent alarms, an OR output is established between the ALM 1 function and the alarms. If the ALM1 function is to be used for the heater burnout, HS, and heater overcurrent alarms only, set 0 as the alarm 1 type (i.e., do not use ALM1).
• Turn the heater power ON simultaneously or before turning ON the E5@N power. If the heater power is turned ON after turning ON the E5AN power, the HB alarm will be activated.
• Control is continued even when the heater burnout, HS, or heater over­current alarm is active.
• The rated current value may sometimes differ slightly from the actual cur­rent flowing to the heater. Use the Heater Current 1 Value Monitor, Heater Current 2 Value Monitor, Leakage Current 1 Monitor, and Leakage Current 2 Monitor parameters to check the actual current being used.
• If there is little difference between the current in normal and abnormal states, detection may become unstable. To stabilize detection, set a cur­rent value difference of at least 1.0 A for heaters of less than 10.0 A, and at least 2.5 A for heaters of 10.0 A or more. If the heater current is too low, loop the load line several times through a CT, as shown in the diagram below. Looping it through once will double the detection current.
Load line
CT

3-10-2 Installing Current Transformers (CT)

• This function can be used with E5@N models that have the HB alarm, HS alarm, and OC alarm. For the E5CN, connect the CT in advance to terminals 14 and 15 (CT1), or 13 and 15 (CT2). For the E5AN/E5EN, connect the CT in advance to terminals 14 and 15 (CT1) or 15 and 16 (CT2). For the E5GN, connect the CT in advance to terminals 7 and 8 (CT1). Then pass the heater power line through the CT's hole. For specifications, models and dimensions of current transformers that can be used with this Controller, refer to Appen­dix Current Transformer (CT) on page 279 of H156 .
Single-phase Heaters For single-phase heaters, install the CT in the position shown in the following
diagram.
Three-phase Heaters (E5AN-@@HH@-N, E5EN-@@HH@-N, and E53-CN@@HHN2 (for E5CN) 3-phase Heater Detection Models)
When a 3-phase power supply is used, regardless of the types of connecting lines, two current transformers (CTs) are required to detect heater burnout, HS, and OC.
1,2,3... 1. Delta connecting lines: Refer to the following diagram for CT installation
positions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
54
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
Heater Burnout Detection 1/2 set value =
Normal current value + Burnout current value
2
HS Alarm 1/2 set value =
Leakage current value (output OFF) + HS current value
2
Heater overcurrent 1/2 set value =
Normal current value + Overcurrent value
2
Load
Load
AC line
AC line
Product To CT input
Product To CT input
Load
2. Star connecting lines: Refer to the following diagram for CT installation po­sitions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
Load
Load (such as a heater)
Load
AC line
Product To CT input
Load
CT
Load (such as a heater)
CT
Product To CT input
CT
3. V connecting lines: Refer to the following diagram for CT installation posi­tions.
Note Heater voltage fluctuations are not considered here, so be take that
into account when setting the detection current.
Product To CT input
AC line
Product To CT input
CT
Load
Load (such as a heater)
Load
CT

3-10-3 Calculating Detection Current Values

• Calculate the set value using the following equation:
• To set the current for heater burnout when two or more heaters are con­nected through the CT, use the value from when the heater with the small­est current burns out. If all of the heaters have the same current, use the value from when any one of them burns out.
55
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
• Make sure that the following conditions are satisfied: Heater with a current of less than 10.0 A: (Current value at normal operation) (Current value at heater burnout) 1A When the difference is less than 1 A, detection is unstable. Heater with a current of 10.0 A or more: (Current value at normal operation) (Current value at heater burnout)
2.5 A When the difference is less than 2.5 A, detection is unstable.
• The setting range is 0.1 to 49.9 A. Heater burnout, HS, and heater over­current are not detected when the set value is 0.0 or 50.0. When the set value is 0.0, the heater burnout alarm is always OFF, the HS alarm is always ON, and the heater overcurrent alarm is always ON. When the set value is 50.0, the heater burnout alarm is always ON, the HS alarm is always OFF, and the heater overcurrent alarm is always OFF.
• Set the total current value for normal heater operation to 50 A or less. When a current value of 55.0 A is exceeded, ffff is displayed in the Heater Current 1 (or 2) Value Monitor and Leakage Current 1 (or 2) Moni­tor parameters.
Note For application examples see H156 section 3-10-4
56
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
C
25
100
PV/SP
in-t
5
Input Type
amov
-169
init
off
Moves to Ad­vanced Function Setting Level
hbu
on
Heater Burnout Detection
C
25
100
PV/SP
l.adj
Adjustment Level Display
ct1
0.0
Heater Current 1 Value Monitor
hb1
0.0
Heater Burnout Detection 1

3-10-4 Settings: HB Alarm

To activate the heater burnout alarm, set the HB ON/OFF parameter to ON in the advanced function setting level and set the Heater Burnout Detection 1 and Heater Burnout Detection 2 parameters in the adjustment level.
Operating Procedure This procedure sets the Heater Burnout Detection 1 parameter to 2.5.
Moving to the Advanced Function Setting Level
The Heater Burnout Detection parameter setting is already ON by default, so set the Heater Burnout Detection 1 parameter.
Operation Level
Initial Setting Level
Initial Setting Level
Advanced Function Setting Level
1. Move to the advanced function setting level.
Press the O Key for at least three seconds to move from the operation level to the initial setting level.
2. Select Move to Advanced Function Setting Level by pressing the M Key.
(For details on moving between levels, refer to 4-8 of H156 Moving to the Advanced Function Setting Level.)
3. Press the D Key to enter the password (169), and move from the initial
setting level to the advanced function setting level.
The top parameter in the advanced function setting level is displayed.
4. Select the Heater Burnout Detection parameter by pressing the M Key.
Check that this parameter is set to ON (the default). Next, set the Heater Burnout Detection 1 parameter.
Operation Level
Adjustment Level
Setting Heater Burnout Detection
5. Press the O Key for at least one second to move from the advanced function setting level to the initial setting level. Press the O key again for at least one second to move to the operation level.
6. Press the O Key for less than one second to move from the operation level to the adjustment level.
7. Select the Heater Current 1 Value Monitor parameter by pressing the M Key. Check the current value. Next, set the Heater Burnout Detection 1 parameter.
8. Select the Heater Burnout Detection 1 parameter by pressing the M Key.
Refer to Calculating Detection Current Values on page 55 on when mak-
ing the settings.
57
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
hb1
2.5
C
25
100
PV/SP
in-t
5
Input Type
amov
-169
init
off
Move to the Advanced Function Setting Level
hsu
on
HS Alarm Use
9. For this example, set 2.5. To return to the operation level, press the O Key for less than one second.

3-10-5 Settings: Heater Short Alarm

To activate the HS alarm, set the HS Alarm Use parameter to ON in the advanced function setting level and set the HS Alarm 1 and HS Alarm 2 parameters in the adjustment level.
Operating Procedure This procedure sets the HS Alarm 1 parameter to 2.5.
Moving to the Advanced Function Setting Level
The HS Alarm Use parameter setting is already ON by default, so set the HS Alarm 1 parameter.
Operation Level
Initial Setting Level
Initial Setting Level
Advanced Function Setting Level
1. Move to the advanced function setting level. Press the O Key for at least three seconds to move from the operation level to the initial setting level.
2. Select Move to Advanced Function Setting Level by pressing the M Key.
(For details on moving between levels, refer to 4-8 of H156 Moving to the Advanced Function Setting Level.)
3. Press the D Key to enter the password (169), and move from the initial setting level to the advanced function setting level.
The top parameter in the advanced function setting level is displayed.
4. Select the HS Alarm Use parameter by pressing the M Key. Check that this parameter is set to ON (the default). Next, set the HS Alarm 1 parameter.
58
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
C
25
100
PV/SP
l.adj
Adjustment Level Display
lcr1
0.0
Leakage Current 1 Monitor
hs1
50.0
HS Alarm 1
hs1
2.5
C
25
100
PV/SP
in-t
5
Input Type
amov
-169
HS Alarm Settings
Operation Level
5. Press the O Key for at least one second to move from the advanced function setting level to the initial setting level. Press the O key again for at least one second to move to the operation level.
Adjustment Level
6. Press the O Key for less than one second to move from the operation level to the adjustment level.
7. Select the Leakage Current 1 Monitor parameter by pressing the M Key. Check the current value. Next, set the HS Alarm 1 parameter.
8. Select the HS Alarm 1 parameter by pressing the M Key. Refer to Calcu- lating Detection Current Values on page 55 when setting the values.
9. For this example, set 2.5. To return to the operation level, press the O Key for less than one second.

3-10-6 Settings: Heater Overcurrent Alarm

To activate heater overcurrent alarm, set the Heater Overcurrent Use parame­ter to ON in the advanced function setting level and set the Heater Overcur­rent Detection 1 and Heater Overcurrent Detection 2 parameters in the adjustment level.
Operating Procedure This procedure sets the Heater Overcurrent Detection 1 parameter to 20.0.
Moving to the Advanced Function Setting Level
The default setting for the Heater Overcurrent Use parameter is ON, so set the Heater Overcurrent Detection 1 parameter.
Operation Level
Initial Setting Level
Initial Setting Level
1. Move to the advanced function setting level. Press the O Key for at least three seconds to move from the operation level to the initial setting level.
2. Press the M Key to select the Move to Advanced Function Setting Level
parameter. (For details on moving between levels, refer to 4-8 of H156 Moving to the Advanced Function Setting Level.)
3. Press the D Key to enter the password (169), and move from the initial setting level to the advanced function setting level.
59
Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms Section 3-10
init
off
Move to the Advanced Function Setting Level
ocu
on
Heater Overcurrent Use
C
25
100
PV/SP
l.adj
Adjustment Level Display
ct1
0.0
Heater Current 1 Value Monitor
oc1
50.0
Heater Overcurrent Detection 1
oc1
20.0
Advanced Function Setting Level
Operation Level
Adjustment Level
The top parameter in the advanced function setting level is displayed.
4. Press the M Key to select the Heater Overcurrent Use parameter. Check that this parameter is set to ON (the default), and then set the Heater Overcurrent Detection 1 parameter.
Setting Heater Overcurrent Detection
5. Press the O Key for at least one second to move from the advanced function setting level to the initial setting level. Press the O key again for at least one second to move to the operation level.
6. Press the O Key for less than one second to move from the operation level to the adjustment level.
7. Press the M Key to select the Heater Current 1 Value Monitor parameter. Check the current value, and then set the Heater Overcurrent Detection parameter.
8. Press the M Key to select the Heater Overcurrent Detection 1 parameter.
Refer to Calculating Detection Current Values on page 55 when setting
the values.
9. For this example, set 20.0. To return to the operation level, press the O Key for less than one second.
60
Setting the No. 3 Display Section 3-11

3-11 Setting the No. 3 Display

This section describes how to set the No. 3 Display (E5AN/EN). The Multi-SP, MV, or soak time remain can be displayed on the No. 3 display.

3-11-1 PV/SP Display Selection

The following table shows the set values and display contents for the PV/SP Display selection.
Set value Display contents
0 Only PV/SP is displayed (with no No. 3 display.)
1 PV/SP/Multi-SP and PV/SP/MV are displayed in order. (See note.)
2 PV/SP/MV and PV/SP/Multi-SP are displayed in order. (See note.)
3 Only PV/SP/Multi-SP is displayed.
4 Only PV/SP/MV is displayed. (See note.)
5 PV/SP/Multi-SP and PV/SP/Soak time remain are displayed in order.
6 PV/SP/MV and PV/SP/Soak time remain are displayed in order. (See
note.)
7 Only PV/SP/Soak time remain is displayed.
• A 2-level display is set when shipped from the factory. (set value: 0) A 3-level display is activated if parameters are initialized. (set value: 4)
Note For details on setting the MV for heating and cooling control, refer to MV Dis-
MV Display for Heating and Cooling Control
play for Heating and Cooling Control below.
When 1, 2, 5, or 6 is selected, press the M Key to display the next value set for the PV/SP display (display 2).
Example: When the PV/SP Display Screen Parameter Is Set to 2
Operation Level PV/SP (Display 1)
C
25
Press the
M key
100
50.0
PV/SP/MV PV/SP/Multi-SP
Select either the manipulated variable (heating) or manipulated variable (cool­ing) as the MV to be displayed for PV/SP/MV during heating and cooling con­trol. The MV Display Selection parameter is displayed only when heating/ cooling control is being performed and PV/SP/MV is selected in the PV/SP Display Screen parameter or a Monitor/Setting Item Display parameter.
Parameter name Set value Symbol Display contents
MV Display Selection O o Manipulated variable
PV/SP (Display 2)
C
25
100
sp0
(heating)
C-O c-o Manipulated variable
(cooling)
61
Setting the No. 3 Display Section 3-11
PV/SP
25
100
C
Input Type
in-t
5
amov
-169
Move to Advanced Function Setting Level
Parameter Initialization
init
off
spdp
4
PV/SP Display Screen Selection
spdp
2
in-t
5
Input Type
25
100
50.0
PV/SP
C
PV/SP
25
100
sp0
C
Operating Procedure This procedure displays PV/SP/MV and PV/SP/Multi-SP on the Process
Value/Set Point display. The PV/SP Display Screen Selection parameter is set to 2.
Operation Level
Initial Setting Level
Initial Setting Level
Advanced Function Setting Level
Advanced Function Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Press the M Key to select the Move to Advanced Function Setting Level
parameter.
3. Use the D Key to enter the password (“−169”).
It is possible to move to the advanced function setting level by either pressing the M Key or waiting two seconds without pressing any key.
4. Press the M Key to select the PV/SP Display Screen Selection parame-
ter.
5. Use the U and D Keys to set 2.
Initial Setting Level
Operation Level
Operation Level
6. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
7. Press the O Key for at least one second to move from the initial setting
level to the operation level.
The MV will be displayed on the No. 3 display.
8. Press the M Key to confirm that the Multi-SP is displayed on the No. 3
display.
62
SECTION 4
Applications Operations
This section describes scaling, the SP ramp function, and other special functions that can be used to make the most of the functionality of the E5GN, E5CN, E5AN, and E5EN Digital Temperature Controllers.
4-1 Shifting Input Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4-1-1 Shifting Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4-1-2 How to Calculate Input Shift Values for a 2-point Shift. . . . . . . . . . 65
4-2 Alarm Hysteresis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4-2-1 Standby Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4-2-2 Alarm Latch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
4-3 Setting Scaling Upper and Lower Limits for Analog Inputs . . . . . . . . . . . . . 69
4-3-1 Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
4-4 Executing Heating/Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4-4-1 Heating/Cooling Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
4-4-2 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
4-5 Using Event Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4-5-1 Event Input Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
4-5-2 How to Use the Multi-SP Function . . . . . . . . . . . . . . . . . . . . . . . . . 76
4-5-3 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
4-5-4 Operation Commands Other than Multi-SP . . . . . . . . . . . . . . . . . . . 77
4-6 Setting the SP Upper and Lower Limit Values . . . . . . . . . . . . . . . . . . . . . . . . 79
4-6-1 Set Point Limiter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
4-6-2 Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
4-7 Using the SP Ramp Function to Limit the SP Change Rate . . . . . . . . . . . . . . 81
4-7-1 SP Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
63

4-1 Shifting Input Values

ins
Temperature Input Shift
C
30
200
l.adj
Adjustment Level Display
C
ins
0.0
Temperature Input Shift
C
ins
1.0
C
31
200

4-1-1 Shifting Inputs

The input shift matched to the sensor currently selected in the Input Type parameter is displayed.
• A 2-point shift is applied for infrared temperature sensors. A 2-point shift can also be used if the Input Shift Type parameter (advanced function set­ting level) is set to INS2 for a thermocouple or platinum resistance ther­mometer.
• There is no shift for analog inputs. Use scaling for fine adjustments.
One-point shift
• With a 1-point shift, the value set for the Temperature Input Shift parame­ter (adjustment level) is applied to each point in the entire temperature input range. For example, if the input shift value is set to 1.2°C, the pro­cess value is treated as 201.2°C after the input shift is applied when the measured process value is 200°C.
Upper limit
Lower limit
Temperature
After shifting
0
Input shift value
Before shifting
Input
100
Operating Procedure In this example, the input from a K sensor is shifted by 1°C using a 1-point
input shift.
Operation Level
Adjustment Level
Operation Level
Operation Level
1. Press the O Key to move from the operation level to the adjustment level.
2. Select the Temperature Input Shift parameter by pressing the M Key.
3. Press the U or D Key to set 1.0.
4. To return to the operation level, press the O Key. The process value is
1°C larger than before the shift was applied.
64
Shifting Input Values Section 4-1
Two-point shift
• Separate shift values can be set for the upper limit and lower limit of the sensor input range for an infrared sensor as well as for a thermocouple or platinum resistance thermometer with the Input Shift Type parameter set to INS2. If different shift values are set for the upper limit and lower limit, then the slope of the line will be different before and after applying the input shift. For example, if the upper-limit value is set to 2°C and the lower-limit value is set to 1°C, the input temperature will be shifted by
1.5°C for a 50% input, i.e., by the average of the upper-limit and lower­limit values.
• Set the upper-limit value in the Upper-limit Temperature Input Shift Value parameter and the lower-limit value in the Lower-limit Temperature Input Shift Value parameter.
Upper-limit temperature
Temperature
Upper limit
After shifting
input shift value
Before shifting
insh
insl
Upper-limit Temperature Input Shift Value
Lower-limit Temperature Input Shift Value
Lower limit
0
Lower-limit temperature input shift value
100
Input

4-1-2 How to Calculate Input Shift Values for a 2-point Shift

When an ES1B Infrared Temperature Sensor is connected to the E5CN, an offset of several degrees to several tens of a degree can occur.
For this reason, offset the readout value using a 1-point or 2-point shift as described in this section. This offset occurs because a bias current for detect­ing a Controller sensor error flows to the output impedance of the infrared temperature sensor.
Preparations
1,2,3... 1. Set a temperature range matching the input specifications of the infrared
temperature sensor. (The ES1B can be used with the E5@N only for a ther­mocouple/resistance thermometer universal input.)
2. Prepare a thermometer capable of measuring the temperature of the con-
trol target as shown in Figure 1 so that a 1-point shift or 2-point shift can
be carried out.
3. The E53-CN@@P@N2 (for E5CN), E5AN-@@P@-N, or E5EN-@@P@-N
has a built-in external power supply for ES1B Infrared Temperature Sen­sors. These E5CN models can be used as the power supply when using ES1B. When ES1B are used with other E5CN models, provide a separate power supply for the Infrared Temperature Sensors.
65
Shifting Input Values Section 4-1
Infrared Temperature Sensor
(C) Control target
(B) Thermometer
(A) E5CN/AN/EN Temperature Controller
Power supply
Output
Method for a 1-point Shift
C
C
insh
10.0
insl
10.0
Figure 1 Offset Configuration for an Infrared Temperature Sensor
1,2,3... 1. In the configuration shown in Figure 1 , bring the set point to near the value
at which the temperature of the control target is to be controlled. Assume that the control target temperature (C) and the thermometer temperature (B) are the same.
Upper-limit Temperature Input Shift Value
Lower-limit Temperature Input Shift Value
2. Check the thermometer temperature (B) and the Controller readout (A). Subtract the Controller readout temperature (A) from the thermometer temperature (B), and set insl and insh to the result as the input shift val-
ue. The shift is illustrated in Figure 2.
3. After setting the input shift values, check the Controller readout (A) and the thermometer temperature (B). If they are almost the same, this completes shifting the temperature input.
Controller readout (A)
Controller readout after shifting (e.g., 120°C)
Controller readout before shifting (e.g., 110°C)
0
Figure 2 Illustration of 1-Point Shift
After shifting
Input shift value (e.g., 10°C)
Before shifting
Near set point (e.g., 120°C)
Control target temperature (B)
66
Shifting Input Values Section 4-1
Method for a 2-point Shift
1,2,3... 1. Shift the Controller readout at two points, near room temperature and near
YH: Set temperature upper limit (e.g., 260°C)
Use a 2-point input shift if you want to increase the accuracy of the readout values across the range of the Sensor.
the value at which the temperature of the control target is to be controlled. For this reason, check the thermometer temperature (B) and Controller readout (A) with the thermometer temperature near room temperature and near the set point.
2.
• Y1 is the Controller readout at room temperature before shifting and X1 is the Controller readout at room temperature after shifting.
• Y2 is the Controller readout at the set temperature before shifting and X2 is the Controller readout at the set temperature after shifting.
• Set the upper-limit temperature input shift and the lower-limit temper­ature input shift using the following formulas based on the tempera­tures before shifting (Y1 and Y2), the temperatures after shifting (X1 and X2), the set temperature upper limit (YH), and the set temperature
lower limit (YL). The shift is illustrated in Figure 3.
Controller readout (A)
After shifting
Upper-limit temperature input shift value (e.g., 52.7°C) insh
Before shifting
X2: Controller readout after shifting (e.g., 110°C)
Y2: Controller readout before shifting (e.g., 105°C)
Y1: Controller readout before shifting (e.g., 40°C)
X1: Controller readout after shifting (e.g., 25°C)
Lower-limit temperature input shift value (e.g., 27.3°C) insl
Figure 3 Illustration of 2-Point Shift
a. Lower-limit temperature input shift value
insl =
b. Upper-limit temperature input shift value
insh =
3. After setting the calculated values to insl and insh, check the Controller
readout (A) and thermometer temperature (B).
4. Here, offsets are set at two points, near room temperature and near the set point. To improve accuracy within the measurement temperature range, another point in the measurement temperature range other than the set point should be set instead of room temperature.
X1: Room temper-
0
ature (e.g., 25°C)
YL: Set temperature lower limit (e.g., 0°C)
YL Y1 Y2 Y1
YH Y1 Y2 Y1
× {(X2 Y2) (X1 Y1)} + (X1 Y1)
× {(X2 Y2) (X1 Y1)} + (X1 Y1)
X2: Near set point (e.g., 110°C)
260°C
Control target temperature (B)
67
Alarm Hysteresis Section 4-2
C
insh
52.7
Upper-limit Temperature Input Shift Value
s
Example of a 2-point Temperature Input Shift
C
insl
-27.3
Lower-limit Temperature Input Shift Val ue
In this example, we use the ES1B K 0 to 260°C specification. In equations 1 and 2, the set temperature lower limit YL is 0°C and the set temperature upper limit YH is 260°C. Check the temperature of the control target.
The temperature input offset values can be calculated as shown below when the Controller readout Y1 is 40°C for a room temperature X1 of 25°C and when the Controller readout Y2 is 105°C for a set point temperature X2 of 110°C.
Lower-limit Temperature Input Shift Value
insl =
Upper-limit Temperature Input Shift Value
insh =

4-2 Alarm Hysteresis

• The hysteresis of alarm outputs when alarms are switched ON/OFF can be set as follows:
Upper-limit alarm
0 40
105 40
260 40 105 40
ON
× {(110 105) (25 40)} + (25 40) = 27.3 (°C)
× {(110 105) (25 40)} + (25 40) = 52.7 (°C)
Alarm hysteresis
Lower-limit alarm
ON
Alarm hysteresi
OFF
Alarm value
• Alarm hysteresis is set independently for each alarm in the Alarm Hyster­esis 1 to Alarm Hysteresis 3 parameters (initial setting level).
• The default is 0.2 (°C/°F) for Controllers with Thermocouple/Resistance Thermometer Universal Inputs and 0.02% FS for Controllers with Analog Inputs.
OFF
Alarm value

4-2-1 Standby Sequence

• The standby sequence can be used so that an alarm will not be output until the process value leaves the alarm range once and then enters it again.
• For example, with a lower limit alarm, the process value will normally be below the set point, i.e., within the alarm range, when the power supply is turned ON, causing an alarm to be output. If the lower limit alarm with a standby sequence is selected, an alarm will not be output until the process value increases above the alarm set value, i.e., until it leaves the alarm range, and then falls back below the alarm set value.
Restart • The standby sequence is canceled when an alarm is output. It is, how-
ever, restarted later by the Standby Sequence Reset parameter (advanced function setting level). For details, refer to the Standby
Sequence Reset parameter in SECTION 5 of H156 Parameters.
68
Setting Scaling Upper and Lower Limits for Analog Inputs Section 4-3
(open)

4-2-2 Alarm Latch

• The alarm latch can be used to keep the alarm output ON until the latch is canceled regardless of the temperature once the alarm output has turned ON.
Any of the following methods can be used to clear the alarm latch.
• Turn OFF the power supply. (The alarm latch is also cleared by switching to the initial setting level, communications setting level, advanced function setting level, or calibration level.)
•Use the PF Key.
• Use an event input.
For details on setting the PF Key, refer to 4-19 of H156: Setting the PF Key. For details on setting events, refer to 4-5 Using Event Inputs.
Summary of Alarm Operation
Parameters
The following figure summarizes the operation of alarms when the Alarm Type parameter is set to “lower-limit alarm with standby sequence” and “close in alarm” is set.
Alarm value
Alarm
Output
Symbol Parameter: level Description
alh* rest
Note * = 1 to 3
Alarm type: Lower-limit alarm with standby sequence
PV
Alarm hysteresis
Time
Standby sequence canceled
Alarm 1 to 3 Hysteresis: Initial setting level Standby Sequence: Advanced function setting level
ON OFF
ON (closed)
OFF
Alarm Alarm

4-3 Setting Scaling Upper and Lower Limits for Analog Inputs

4-3-1 Analog Input

• When an analog input is selected, scaling can be performed as needed by the control application.
• Scaling is set in the Scaling Upper Limit, Scaling Lower Limit, and Deci­mal Point parameters (initial setting level). These parameters cannot be used when a temperature input is selected.
• The Scaling Upper Limit parameter sets the physical quantity to be expressed by the upper limit value of input, and the Scaling Lower Limit parameter sets the physical quantity to be expressed by the lower-limit value of input. The Decimal Point parameter specifies the number of digits below the decimal point.
in-h
in-l
dp
Scaling Upper Limit
Scaling Lower Limit
Decimal Point
69
Executing Heating/Cooling Control Section 4-4
4
20
Display (humidity)
Upper limit (95.0%)
Lower limit (10.0%)
Input (mA)
in-t
0
Input Type
in-h
100
Scaling Upper Limit
in-h
950
in-l
0
Scaling Lower Limit
in-l
100
dp
0
Decimal Point
dp
1
• The following figure shows a scaling example for a 4 to 20 mV input. After scaling, the humidity can be directly read. Here, one place below the decimal point is set.
Operating Procedure In this example scaling is set to display 4 to 20 mA as 10.0% to 95.0%.
Initial Setting Level
1. Press the O Key for three seconds to move from the operation level to
the initial setting level.
2. Select Scaling Upper Limit parameter by pressing the M Key.
3. Use the U and D Keys to set the parameter to 950.
4. Select the Scaling Lower Limit parameter by pressing the M Key.
5. Press the U and D Keys to set 100.
6. Select the Decimal Point parameter by pressing the M Key.

4-4 Executing Heating/Cooling Control

4-4-1 Heating/Cooling Control

70
7. Press the U and D Keys to set 1.
8. To return to the operation level, press the O Key for one second.
Heating/cooling control can be used on the E5CN-@M@-500 (with an E53­CNQ@@N2), E5CN-@2M@-500, E5AN-@3@M@-500-N or E5EN-@3@M@- 500-N. Heating/cooling control operates when h-c (heating/cooling) is selected for the Standard or Heating/Cooling parameter.
Executing Heating/Cooling Control Section 4-4
The following functions are assigned to outputs in the initial status.
Parameter name Symbol Initial status
Control Output 1 Assignment out1 Control output for heating Control Output 2 Assignment out2 Not assigned. Auxiliary Output 1 Assignment sub1 Alarm 1 Auxiliary Output 2 Assignment sub2 Alarm 2
Auxiliary Output 3 Assignment (E5AN/EN only)
Each output assignment is automatically initialized as shown below when the control mode is changed.
Example: E5CN
Parameter name Symbol Without control output 2 With control output 2
Standard Heating/cooling Standard Heating/cooling
Control Output 1 Assignment
Control Output 2 Assignment
Auxiliary Output 1 Assignment
Auxiliary Output 2 Assignment
out1 Control output
(heating)
out2 Not assigned. (See
note 1.)
sub1 Alarm 1 (See note
2.)
sub2 Alarm 2 (See note
3.)
Control output (heating)
Not assigned. (See note 1.)
Alarm 1 (See note
2.)
Control output (coo­ing) (See note 3.)
sub3 Alarm 3
Control output (heating)
Not assigned. Control output (coo-
Alarm 1 (See note
2.)
Alarm 2 Alarm 2
Control output (heating)
ing)
Alarm 1 (See note
2.)
Example: E5GN
Parameter name Symbol Standard Heating/cooling
Control Output 1 Assignment
Auxiliary Output 1 Assignment
Auxiliary Output 2 Assignment
out1 Control output
(heating)
sub1 Alarm 1 (See note
2.)
sub2 Alarm 2 Alarm 2
Control output (heating)
Control output (coo­ing)
Note (1) No parameter assignment is displayed because there is no control output
2.
(2) The output set for the Auxiliary Output 1 Assignment parameter becomes
the program END output unless the program pattern is OFF.
(3) For the E5AN/EN, the Auxiliary Output 3 Assignment parameter is set for
control output (cooling) (the Auxiliary Output 2 Assignment parameter is set for alarm 2).
• The heating/cooling operation of the control outputs will switch when the Direct/Reverse Operation parameter is set to “direct.”
• When DRS (Invert Direct/Reverse Operation) is assigned for an Event Input Assignment (1 or 2), control will start with the contents set for the Direct/Reverse Operation parameter inverted when the event input turns ON, and with the contents left according to the setting when the event input turns OFF. For details on event inputs and control combined with the
Direct/Reverse Operation parameter, refer to Control by Inver ting Direct/ Reverse Operation on page 78.
• When heating/cooling control is selected, the Dead Band and Cooling Coefficient parameters can be used.
71
Executing Heating/Cooling Control Section 4-4
PV
0
PV
0
Output
Dead band: Dead band width = A positive value
Output
Heating side
Cooling side
Set point
Overlapping dead band: Dead band width = A negative value
Heating side
Cooling side
Set point
PV
0
PV
0
Output Output
P for control output assigned to heating side
P for control output assigned to heat­ing side
× 1.0
P for control output assigned to cooling side
Set point Set point
P for control output assigned to heating side × 0.8
P for control output assigned to heating side
P for control output assigned to heat­ing side × 1.0
P for control output assigned to cooling side
P for control output assigned to heating side × 1.5
Dead Band • For heating/cooling control, the dead band is set with the set point as its
center. The dead band width is the set value of the Dead Band parameter (adjustment level). Setting a negative value produces an overlapping band.
• If an overlapping band is set, the bumpless function may not operate when switching between manual operation and automatic operation.
• The default is 0.0 EU for Controllers with Thermocouple/Resistance Ther­mometer Universal Inputs and 0.00% FS for Controllers with Analog Inputs.
Cooling Coefficient If the heating characteristics and cooling characteristics of the control object
are very different and good control characteristics cannot be achieved with the same PID constants, the cooling coefficient can be used to adjust the propor­tional band (P) for the control output assigned to the cooling side. Use this to achieve balanced control between the heating side and cooling side. The pro­portional bands (P) for the control outputs assigned to the heating/cooling sides can be calculated using the following equations.
P for control output assigned to heating side = P
P for control output assigned to cooling side = P for control output assigned to heating side × cooling coefficient
The cooling coefficient is multiplied by the P for the control output assigned to the heating side to obtain control with characteristics that differ from those of the control output assigned to the heating side.
Automatic Cooling Coefficient Adjustment
72
By executing AT during heating/cooling control, the cooling coefficient can be automatically calculated along with the PID parameters.
Parameter name Setting rage Default
Automatic Cooling
OFF: Disabled, ON: Enabled OFF Coefficient Adjust­ment
Note If there is strong non-linear gain for the cooling characteristics, such as when
cooling water boils for cooling control, it may not be possible to obtain the opti­mum cooling coefficient at the Controller, and control may take the form of
Executing Heating/Cooling Control Section 4-4
s-hc
stnd
Standard or Heating/ Cooling
c-sc
1.00
Cooling Coefficient
c-sc
10.00
C
c-db
0.0
Dead Band
C
c-db
5.0
oscillating waves. If that occurs, increase the proportional band or the cooling coefficient to improve control.

4-4-2 Settings

To set heating/cooling control, set the Standard or Heating/Cooling, Dead Band, and Cooling Coefficient parameters.
Setting Heating/Cooling Control
Operating Procedure Standard or heating/cooling = Heating/cooling
Initial Setting Level
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select “heating/cooling control” in the initial setting level.
stnd: Standard control h-c: Heating/cooling control
Setting the Cooling Coefficient
Operating Procedure Cooling Coefficient = 10
Adjustment Level
1. Select the Cooling Coefficient parameter in the adjustment level.
2. Use the U Key to set the parameter to 10.00.
Setting the Dead Band
Operating Procedure Dead Band = 5
Adjustment Level
1. Select the Dead Band parameter in the adjustment level.
2. Use the U Key to set the parameter to 5.0.
73
Using Event Inputs Section 4-5

4-5 Using Event Inputs

4-5-1 Event Input Settings

• Event inputs can be used for Multi-SP, RUN/STOP, Auto/Manual Switch, Program Start, Invert Direct/Reverse Operation, 100% AT Execute/Can­cel, 40% AT Execute/Cancel, Setting Change Enable/Disable, and Alarm Latch Cancel.
• Of these, only the number of event inputs (0 to 2) set in the Number of Multi-SP Uses parameter (initial setting level) are used for the multi-SP function.
• Of these, only the number of event inputs (0 to 2) set in the Number of Multi-SP Uses parameter (initial setting level) are automatically assigned by the multi-SP function. Displays for event input assignments will not be displayed for inputs that are automatically assigned by the multi-SP func­tion. Event inputs 1 and 2 are used for the multi-SP function by models with four event inputs.
• Event inputs can be used on the following models: E5CN-@M@-500 with the E53-CN@B@N2 for the E5CN E5AN/EN-@M@-500-N with the E53-AKB for the E5AN/EN
• When using event inputs to switch the multi-SP, the event input assign­ment display will not appear. Whether the set value and event input assignments 1 and 2 will be displayed or hidden is shown in the tables below.
• Do not connect the contacts from the same switch to more than one E5@N Controllers.
Number of Multi­SP Uses
Models with Two Event Inputs, 1 and 2
Event input assignment 1 Event input assignment 2 Description of EV1 and EV2
0 Displayed (Multi-SP not used). EV1 and EV2 will perform the
operation command assigned using the Event Input Assign­ment 1 and 2 parameters.
1 Not displayed (Operation per-
formed with two Multi-SP points.)
2 Not displayed (Operation performed with four Multi-SP points.) EV1 and EV2 will be used for
Displayed (Event input 2 not used as multi-SP switch).
EV1 will be used for the Multi­SP function to switch between set points 0 and 1. EV2 will perform the operation com­mand assigned using the Event Input Assignment 2 parameter.
the Multi-SP function to switch between set points 0, 1, 2, and 3.
operation
74
Using Event Inputs Section 4-5
Models with Two Event Inputs, 3 and 4
Event input assignment 3 Event input assignment 4 Description of EV3 and EV4
operation
Number of Multi­SP Uses
0 Displayed (Multi-SP not used). EV3 and EV4 will perform the
1 Not displayed (Operation per-
formed with two Multi-SP points.)
2 Not displayed (Operation performed with four Multi-SP points.) EV3 and EV4 will be used for
Displayed (Event input 4 not used as multi-SP switch).
operation command assigned using the Event Input Assign­ment 3 and 4 parameters.
EV3 will be used for the Multi­SP function to switch between set points 0 and 1. EV4 will perform the operation com­mand assigned using the Event Input Assignment 2 parameter.
the Multi-SP function to switch between set points 0, 1, 2, and 3.
Models with Four Event Inputs, 1 to 4
Number of Multi­SP Uses
Event input
assignment 1
0 Displayed (Multi-SP not used). EV1, EV2, EV3, and EV4 will
1 Not displayed
(Operation performed with two Multi­SP points.)
2 Not displayed (Operation per-
formed with four Multi-SP points.)
Event input
assignment 2
Displayed (Event inputs 2, 3, and 4 cannot be used for multi-SP switching.)
Event input
assignment 3
Displayed (Event inputs 3 and 4 cannot be used for multi-SP switching.)
Event input
assignment 4
Description of EV1, EV2,
EV3, and EV4 operation
perform the operation com­mand assigned using the Event Input Assignment 1, 2, 3, and 4 parameters.
EV1 will be used for the Multi­SP function to switch between set points 0 and 1. EV2, EV3, and EV4 will perform the operation command assigned using the Event Input Assign­ment 2, 3, and parameters.
EV1 and EV2 will be used for the Multi-SP function to switch between set points 0, 1, 2, and 3. EV3 and EV4 will per­form the operation command assigned using the Event Input Assignment 3 and 4 parameters.
75
Using Event Inputs Section 4-5
Two set points are set externally by using the Number of Multi-SP Uses parameter.
• Switching is possible between two set points (0 and 1) by setting the Number of Multi-SP Uses parameter to 1. The default setting is 1 and does not need to be changed to switch between two set points. Set points 0 and 1 are specified by the status of event input 1.
E5CN
E5AN/EN
11
12
13
E53-CN@B@N2 in the E5CN-@M@-500 (for E5CN)
E5GN
7
8
9
EV1
EV2
EV1
EV2
+
+
+
+
EV1
EV2
EV1
EV2

4-5-2 How to Use the Multi-SP Function

The multi-SP function allows you to set up to four set points (SP 0 to 3) in the adjustment level. The set point can be switched by operating the keys on the front panel or by using external input signals (event inputs).
Using Event Inputs
Two Event Inputs: Event Inputs 1 and 2
The following tables show the relationship between the ON/OFF combinations of event inputs 1 and 2 and the selected set points.
11
12
13
E53-AKB in the E5AN/EN-@M@-500-N (for E5AN/EN)
EV1
EV2
+
+
EV1
EV2
Number of Multi-SP Uses = 1
Event input 1 Selected set point
OFF Set point 0
ON Set point 1
Number of Multi-SP Uses = 2
Event input 1 Event input 2 Selected set point
OFF OFF Set point 0
ON OFF Set point 1
OFF ON Set point 2
ON ON Set point 3
Using Key Operations You can select any of the set points 0 to 3 by changing the set value of the
Multi-SP Uses parameter. The Multi-SP Uses parameter display conditions are as follows:
• If the Controller does not support event inputs, the Multi-SP Uses param­eter must be set to ON.
• If the Controller supports event inputs, the Number of Multi-SP Uses parameter must be set to 0 and the Multi-SP Uses parameter must be set to ON.
76
Using Event Inputs Section 4-5
C
25
100
PV/SP
ev-m
1
Number of Multi-SP Uses
ev-m
2
The following table shows the relationship between the Multi-SP Uses param­eter set value and the selected set point.
Multi-SP Selected set point
0 Set point 0
1 Set point 1
2 Set point 2
3 Set point 3
Note The set point can also be switched using communications.

4-5-3 Settings

Switching between Set Points 0, 1, 2, and 3
Operating Procedure The following example sets the Number of Multi-SP Uses parameter to 2.
Operation Level
Number of Multi-SP Uses Setting
E5CN
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Number of Multi-SP Uses parameter by pressing the M Key.
3. Use the U Key to set the parameter to 2.
Set points 0, 1, 2 and 3 will be set according to the ON/OFF states of event inputs 1 and 2.
E5AN/EN E5GN
11
12
13
EV1
EV2
+
+
EV1
EV2
11
12
13
EV1
EV2
+
+
EV1
EV2
7
8
9
EV1
EV2
+
+
EV1
EV2

4-5-4 Operation Commands Other than Multi-SP

The following table shows the functions assigned when an Event Input Assignment (1 or 2) is displayed.
Setting Function
none None stop RUN/STOP manu Auto/Manual prst Program Start (See note 1.) drs Invert Direct/Reverse Operation at-2 100% AT Execute/Cancel at-1 40% AT Execute/Cancel (See note 2.) wtpt Setting Change Enable/Disable lat Alarm Latch Cancel
77
Using Event Inputs Section 4-5
Note (1) PRST (Program Start) can be set even when the Program Pattern param-
eter is set to OFF, but the function will be disabled.
(2) This function can be set for heating/cooling control, but the function will
be disabled.
When any of the following functions is set for an Event Input Assignment parameter, the same function cannot be set for another Event Input Assign­ment parameter: STOP (RUN/STOP), MANU (Auto/Manual Switch), PRST (Program Start), DRS (Invert Direct/Reverse Operation), AT-2 (100% AT Exe­cute/Cancel), AT-1 (40% AT Execute/Cancel), WTPT (Setting Change Enable/ Disable), or LAT (Alarm Latch Cancel). Turn event inputs ON and OFF while the power is being supplied. Event input ON/OFF changes are detected for inputs of 50 ms or longer. (However, inputs of 250 ms or longer is determined using logic operations.)
The functions are described in detail below. Event inputs 1 and 2 are taken as examples.
Executing Run/Stop Control
Switching between Auto and Manual Control
Controlling the Start of the Simple Program Function
When the Event Input Assignment 1 or Event Input Assignment 2 parameter is set to STOP (RUN/STOP), control is started when event input 1 or 2 turns OFF. Control is stopped when the input turns ON. Alarm outputs, however, will be according to the process value.
The STOP indicator will light while control is stopped.
Setting Input contact Status
Event input 1 or 2 ON STOP
Event input 1 or 2 OFF RUN
When the Event Input Assignment 1 or Event Input Assignment 2 parameter is set to MANU (auto/manual), manual control will start when event input 1 or 2 turns ON. Auto control will start when the input turns OFF.
The MANU indicator will light during manual control.
Setting Input contact Status
Event input 1 or 2 OFF Automatic
Event input 1 or 2 ON Manual
When the Event Input Assignment 1 or Event Input Assignment 2 parameter is set to PRST (program start), the program will start when event input 1 or 2 turns ON. The program will be reset when the input turns OFF and the RUN/ STOP status will automatically switch to STOP mode. If the program END out­put is ON, the program END output will turn OFF.
Setting Input contact Status
Event input 1 or 2 OFF Reset
Event input 1 or 2 ON Start
Control by Inverting Direct/Reverse Operation
78
When DRS (Invert Direct/Reverse Operation) is set for the Event Input Assignment 1 or Event Input Assignment 2 parameter and the Direct/Reverse Operation parameter is set for reverse operation, control starts with direct operation (cooling control) when event input 1 or 2 turns ON and control starts with reverse operation (heating control) when the event input turns OFF.
Setting Input
Event input 1 or 2
contact
OFF Direct operation (cooling) Direct operation (cooling)
Direct/Reverse Operation
parameter
Reverse operation (heating) Reverse operation (heating)
Status
Setting the SP Upper and Lower Limit Values Section 4-6
Switching 100% AT Execute/Cancel
Switching 40% AT Execute/Cancel
Switching Setting Change Enable/ Disable
Setting Input
contact
Event input 1 or 2
When AT-2 (100% AT Execute/Cancel) is set for either the Event Input Assign­ment 1 or Event Input Assignment 2 parameter, 100% AT will be executed when event input 1 or 2 turns ON and will be cancelled when the input turns
OFF.
Event input 1 or 2 OFF 100% AT cancelled
Event input 1 or 2 ON 100% AT executed
When AT-1 (40% AT Execute/Cancel) is set for either the Event Input Assign­ment 1 or Event Input Assignment 2 parameter, 40% AT will be executed when event input 1 or 2 turns ON and will be cancelled when the input turns OFF.
Event input 1 or 2 OFF 40% AT cancelled
Event input 1 or 2 ON 40% AT executed
When WTPT (Setting Change Enable/Disable) is set for either the Event Input Assignment 1 or Event Input Assignment 2 parameter, the setting change will be disabled when event input 1 or 2 turns ON and will be enabled when the input turns OFF.
Event input 1 or 2 OFF Enabled
Event input 1 or 2 ON Disabled
ON Direct operation (cooling) Reverse operation (heating)
Setting Input contact Status
Setting Input contact Status
Setting Input contact Status
Direct/Reverse Operation
parameter
Reverse operation (heating) Direct operation (cooling)
Status
Switching Alarm Latch Cancel
Parameters
When LAT (Alarm Latch Cancel) is set for either the Event Input Assignment 1 or Event Input Assignment 2 parameter, all alarm latches (alarms 1 to 3, heater burnout, HS alarm, and heater overcurrent latch) will be cancelled when event input 1 or 2 turns ON.
Setting Input contact Status
Event input 1 or 2 OFF ---
Event input 1 or 2 ON Cancelled
Symbol Parameter: level Description
ev-1 Event Input Assignment 1: Initial setting level Function of ev-2 Event Input Assignment 2: Initial setting level ev-m Number of Multi-SP Uses: Initial setting level

4-6 Setting the SP Upper and Lower Limit Values

4-6-1 Set Point Limiter

The setting range of the set point is limited by the set point limiter. This func­tion can be used to prevent setting incorrect process values. The set point lim­iter is used to prevent the control target from reaching abnormal temperatures. If the set point is not within the range set for the set point limiter as the result of changes to the Set Point Upper Limit or Set Point Lower Limit parameter, the set point will automatically be change to a value within the set
event input func­tion
79
Setting the SP Upper and Lower Limit Values Section 4-6
t
t
t
in-t
5
Input Type
C
sl-h
1300
Set Point Upper-limit
range. The upper- and lower-limit values of the set point limiter are set using the Set Point Upper Limit and Set Point Lower Limit parameters in the initial setting level. When the set point limiter is reset, the set point is forcibly changed to the upper- or lower-limit value of the set point limiter if the set point is out of the limiter range. Also, when the input type and the temperature unit, scaling upper-limit value, or lower-limit value are changed, the set point limiter is forcibly reset to the input setting range or the scaling upper- or lower-limit value.
Input setting range
Set point limiter
Parameters
Setting range
B
Upper limit value changed
Upper limit value changed
Input type changed
Set value Upper/lower limit values Sensor upper/lower limit values
Symbol Parameter: level Description
sl-h sl-l
Set Point Upper Limit: Initial setting level Set Point Lower Limit: Initial setting level
A
C
(Cannot be set.)
B
(Can be set.)
To limit the SP setting To limit the SP setting
Set poin
Set poin
Set poin

4-6-2 Setting

Set the set point upper and lower limits in the Set Point Upper Limit and Set Point Lower Limit parameters in the initial setting level. In this example, it is assumed that the input type is set to a K thermocouple with a temperature range of 200 to 1300°C.
200 1300
Input setting range
Set point limiter
100 1000
Setting the Set Point Upper-limit Value
Operating Procedure Set Point Upper Limit = 1000
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Set Point Upper Limit parameter.
80
Using the SP Ramp Function to Limit the SP Change Rate Section 4-7
C
sl-h
1000
C
sl-l
-200
Set Point Lower Limit
C
sl-l
-100
g
3. Use the U and D Keys to set the parameter to 1000.
Setting the Set Point Lower-limit Value
Operating Procedure Set Point Lower Limit = 100
1. Select the Set Point Lower Limit parameter in the initial setting level.
2. Use the U and D Keys to set the parameter to 100.

4-7 Using the SP Ramp Function to Limit the SP Change Rate

4-7-1 SP Ramp

The SP ramp function is used to restrict the width of changes in the set point as a rate of change. When the SP ramp function is enabled and the change width exceeds the specified rate of change, an area where the set point is restricted will be created, as shown in the following diagram.
During the SP ramp, control will be performed not for the specified set point but rather for the set point restricted by the rate of change set for the SP ramp function.
SP
SP after change
SP before change
Point of chan
The rate of change during SP ramp is specified using the SP Ramp Set Value and SP Ramp Time Unit parameters. The SP Ramp Set Value parameter is set to OFF by default, i.e., the SP ramp function is disabled.
Changes in the ramp set point can be monitored in the Set Point During SP Ramp parameter (operation level). Use this parameter when monitoring SP ramp operation.
The SP ramp function operates in the same way when switching the set point using the multi-SP function.
SP ramp
SP ramp set value
SP ramp time unit (s/min)
Time
e
81
Using the SP Ramp Function to Limit the SP Change Rate Section 4-7
Parameters
Symbol Parameter: level Description
ol-h ol-l sl-h sl-l sprt spru alsp
MV Upper Limit: Adjustment level MV Lower Limit: Adjustment level Set Point Upper Limit: Initial setting level Set Point Lower Limit: Initial setting level SP Ramp Set Value: Adjustment level SP Ramp Time Unit: Advanced function setting level Alarm SP Selection: Advanced function setting level
To limit the manipulated variable To limit the manipulated variable To limit the SP setting To limit the SP setting To limit the SP rate of change Unit for setting the SP Alarm SP selection
Operation at Startup If the SP ramp function is enabled when the Controller is turned ON or when
switching from STOP to RUN mode, the process value reaches the set point using the SP ramp function in the same way as when the set point is changed. In this case, operation is carried out with the process value treated as the set point before the change was made. The direction of the SP ramp changes according to the relationship between the process value and the set point.
Restrictions during SP Ramp Operation
Set point
PV
PV < SP
SP
SP ramp
Set point
Time Time
Power ON Power ON
SP
PV
PV > SP
SP ramp
Same rate of change
• Execution of auto-tuning starts after the end of the SP ramp.
• When control is stopped or an error occurs, the SP ramp function is dis­abled.
82
Using the SP Ramp Function to Limit the SP Change Rate Section 4-7
Alarms during SP Ramp Operation
The operation of alarms during SP ramp operation depends on whether alarms are set to be based on the ramp set point or the target set point (refer to the following diagrams). The set point to be used is set in the Alarm SP
Selection parameter. (Refer to page 244 of H156.)
Alarm SP Selection = Ramp SP (Alarm Type: 1 (Upper/Lower Limits))
Temperature
Alarm output ON
Alarm output ON
Time
Alarm SP Selection = Target SP (Alarm Type: 1 (Upper/Lower Limits))
Temperature
Alarm output ON
Alarm output ON
Time
83
Using the SP Ramp Function to Limit the SP Change Rate Section 4-7
84

Index

Numerics
2-PID control . . . . . . . . . . . . . . . . . . . . . . . . . 34
A
adjustment level . . . . . . . . . . . . . . . . . . . . . . . 13
advanced function setting level . . . . . . . . . . . 14
alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
alarm hysteresis . . . . . . . . . . . . . . . . . . . . 68
alarm latch . . . . . . . . . . . . . . . . . . . . . . . . 69
alarm outputs . . . . . . . . . . . . . . . . . . . . . . 49
alarm types . . . . . . . . . . . . . . . . . . . . . . . . 49
alarm values . . . . . . . . . . . . . . . . . . . . . . . 51
operation . . . . . . . . . . . . . . . . . . . . . . . . . 69
analog input . . . . . . . . . . . . . . . . . . . . . . . . . . 69
AT (auto-tuning) . . . . . . . . . . . . . . . . . . . . . . 42
auto control . . . . . . . . . . . . . . . . . . . . . . . . . . 78
B
basic model
E5AN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
E5CN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
E5CN-U . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
E5EN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
E5GN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
C
communications function . . . . . . . . . . . . . . . . 11
communications setting level . . . . . . . . . . . . . 14
control outputs . . . . . . . . . . . . . . . . . . . . . . . . 10
control periods . . . . . . . . . . . . . . . . . . . . . . . . 34
cooling coefficient
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
current transformer
calculating detection current . . . . . . . . . . 55
Current Transformers (CT) . . . . . . . . . . . . . . 54
D
dead band . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
derivative time . . . . . . . . . . . . . . . . . . . . . . . . 48
detection current . . . . . . . . . . . . . . . . . . . . . . 55
direct operation . . . . . . . . . . . . . . . . . . . . . . . 35
down key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
E
event inputs . . . . . . . . . . . . . . . . . . . . 11, 74, 76
external power supply for ES1B . . . . . . . 11, 65
F
front panel
E5AN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
E5CN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
E5CN-U . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
E5EN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
E5GN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
H
HB alarm (heater burnout alarm) . . . . . . . . . . 53
settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
heater burnout alarm . . . . . . . . . . . . . . . . . . . 11
heating/cooling control . . . . . . . . . . . . . . . . . 70
cooling coefficient . . . . . . . . . . . . . . . . . . 72
dead band . . . . . . . . . . . . . . . . . . . . . . . . . 72
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
HS alarm . . . . . . . . . . . . . . . . . . . . . . . . . 11, 53
settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . 40, 42
I
I/O configuration . . . . . . . . . . . . . . . . . . . . . . . 6
basic model
E5AN . . . . . . . . . . . . . . . . . . . . . . . . . . 8
E5CN . . . . . . . . . . . . . . . . . . . . . . . . . . 6
E5CN-U . . . . . . . . . . . . . . . . . . . . . . . . 7
E5EN . . . . . . . . . . . . . . . . . . . . . . . . . . 8
E5GN . . . . . . . . . . . . . . . . . . . . . . . . . . 9
main functions . . . . . . . . . . . . . . . . . . . . . 10
indicators
explanation . . . . . . . . . . . . . . . . . . . . . . . . . 4
operation . . . . . . . . . . . . . . . . . . . . . . . . . . 4
initial setting level . . . . . . . . . . . . . . . . . . . . . 14
initial settings . . . . . . . . . . . . . . . . . . . . . . . . . 30
examples . . . . . . . . . . . . . . . . . . . . . . 30, 31
input sensor types . . . . . . . . . . . . . . . . . . . . . . 10
input shift . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
one-point shift . . . . . . . . . . . . . . . . . . . . . 64
two-point shift . . . . . . . . . . . . . . . . . . . . . 65
calculating . . . . . . . . . . . . . . . . . . . . . 65
input types . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
E5AN/E5EN
mounting the terminal cover . . . . . . . 21
mounting to the panel . . . . . . . . . . . . 21
E5CN/E5CN-U
85
Index
mounting the terminal cover . . . . . . . 20
mounting to the panel . . . . . . . . . . . . 20
E5GN
mounting to the panel . . . . . . . . . . . . 22
removing from case
E5AN . . . . . . . . . . . . . . . . . . . . . . . . . 23
E5CN . . . . . . . . . . . . . . . . . . . . . . . . . 22
E5EN . . . . . . . . . . . . . . . . . . . . . . . . . 23
removing the terminal block
E5GN . . . . . . . . . . . . . . . . . . . . . . . . . 24
integral time . . . . . . . . . . . . . . . . . . . . . . . . . . 48
K
keys
down key . . . . . . . . . . . . . . . . . . . . . . . . . . 5
key operations . . . . . . . . . . . . . . . . . . . . . 12
level key . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
mode key . . . . . . . . . . . . . . . . . . . . . . . . . . 5
operations . . . . . . . . . . . . . . . . . . . . . . . . . . 5
up key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
L
level key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
M
main functions . . . . . . . . . . . . . . . . . . . . . . . . 10
manual control . . . . . . . . . . . . . . . . . . . . . . . . 78
manual control level . . . . . . . . . . . . . . . . . . . . 13
manual setup . . . . . . . . . . . . . . . . . . . . . . . . . 48
mode key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
terminal cover
E5AN/E5EN . . . . . . . . . . . . . . . . . . . 21
E5CN/E5CN-U . . . . . . . . . . . . . . . . . 20
to panel
E5AN/E5EN . . . . . . . . . . . . . . . . . . . 21
E5CN/E5CN-U . . . . . . . . . . . . . . . . . 20
E5GN . . . . . . . . . . . . . . . . . . . . . . . . . 22
multi-SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
N
No. 1 display . . . . . . . . . . . . . . . . . . . . . . . . . . 4
No. 2 display . . . . . . . . . . . . . . . . . . . . . . . . . . 4
O
ON/OFF control . . . . . . . . . . . . . . . . . . . . . . . 34
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
one-point shift . . . . . . . . . . . . . . . . . . . . . . . . 66
operation level . . . . . . . . . . . . . . . . . . . . . . . . 13
output functions
assignments . . . . . . . . . . . . . . . . . . . . . . . 36
output specifications
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
P
parameters
selecting . . . . . . . . . . . . . . . . . . . . . . . . . . 14
part names . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
PID constants . . . . . . . . . . . . . . . . . . . . . . 42, 45
setting manually . . . . . . . . . . . . . . . . . . . . 48
PID control
setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
proportional action . . . . . . . . . . . . . . . . . . . . . 48
proportional band . . . . . . . . . . . . . . . . . . . . . . 48
protect level . . . . . . . . . . . . . . . . . . . . . . . . . . 13
R
removing from case
E5AN/E5EN . . . . . . . . . . . . . . . . . . . . . . 23
E5CN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
removing the terminal block
E5GN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
reverse operation . . . . . . . . . . . . . . . . . . . . . . 35
RT (robust tuning) . . . . . . . . . . . . . . . . . . . . . 46
run/stop control . . . . . . . . . . . . . . . . . . . . . . . 78
S
scaling
upper and lower limits for analog inputs . 69
self-tuning (ST) . . . . . . . . . . . . . . . . . . . . . . . 44
set point (SP) . . . . . . . . . . . . . . . . . . . . . . . . . 39
limiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
limiting change rate . . . . . . . . . . . . . . . . . 81
lower limit . . . . . . . . . . . . . . . . . . . . . . . . 81
ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
setting . . . . . . . . . . . . . . . . . . . . . . . . . 39, 41
setting upper and lower limits . . . . . . . . . 79
switching between SPs . . . . . . . . . . . . . . . 77
upper limit . . . . . . . . . . . . . . . . . . . . . . . . 80
setting level configuration . . . . . . . . . . . . . . . 12
settings
cooling coefficient . . . . . . . . . . . . . . . . . . 73
dead band . . . . . . . . . . . . . . . . . . . . . . . . . 73
event input . . . . . . . . . . . . . . . . . . . . . . . . 74
HB alarm (heater burnout alarm) . . . . . . . 57
moving to advanced function setting level
86
. . . . . . . . . . . . . . . . . . . . . . . . 57
heating/cooling control . . . . . . . . . . . . . . 73
HS alarm . . . . . . . . . . . . . . . . . . . . . . . . . 59
moving to advanced function setting level
. . . . . . . . . . . . . . . . . . . . . 58, 59
hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . 42
PID ON/OFF . . . . . . . . . . . . . . . . . . . . . . 41
saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
SP lower limit . . . . . . . . . . . . . . . . . . . . . 81
SP upper limit . . . . . . . . . . . . . . . . . . . . . 80
switching between SPs . . . . . . . . . . . . . . 77
shifting input values . . . . . . . . . . . . . . . . . . . 64
simple program function
controlling start . . . . . . . . . . . . . . . . . . . . 78
SP ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
alarm operations . . . . . . . . . . . . . . . . . . . 83
operation at startup . . . . . . . . . . . . . . . . . 82
restrictions . . . . . . . . . . . . . . . . . . . . . . . . 82
specifications
output . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
ST (self-tuning) . . . . . . . . . . . . . . . . . . . . . . . 44
ST stable range . . . . . . . . . . . . . . . . . . . . 45
startup conditions . . . . . . . . . . . . . . . . . . 45
standby sequence . . . . . . . . . . . . . . . . . . . . . . 68
startup
conditions . . . . . . . . . . . . . . . . . . . . . . . . 45
operation . . . . . . . . . . . . . . . . . . . . . . . . . 82
support software port . . . . . . . . . . . . . . . . . . . 26
Index
T
temperature input . . . . . . . . . . . . . . . . . . . . . . 10
shift values . . . . . . . . . . . . . . . . . . . . . . . . 68
temperature unit . . . . . . . . . . . . . . . . . . . . . 4, 34
three-position control . . . . . . . . . . . . . . . . . . 40
two-point shift . . . . . . . . . . . . . . . . . . 65, 67, 68
calculating . . . . . . . . . . . . . . . . . . . . . . . . 65
U
up key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
87

Revision History

Cat. No. H08E-EN-01
Revision code
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code Date Revised content
01 August 2010 Original production
88
Loading...