Italiano .........................................................18
Français .......................................................23
E N G L I S H
IMPORTANT NOTICE
Use FTB690 Series meters with water and other
chemicals compatible with wetted components
(see Specifications Section). Do not use to
meter fuel or incompatible chemicals. FTB690
Series meters are available with either a local
electronic display, or a conditioned signal
output module to provide a digital signal to
customer interfacing equipment. FTB690
Series meters with computer display measure
in gallons or liters. Refer to the Calibration
Section for details.
These meters are not legal for trade applications.
FTB690 Series meters are very sensitive to
electric noise if operated within one to two
inches of some electric motors or other sources
of electronic noise.
INSTALLATION
Install your meter in-line either horizontally or
vertically or at the end of the hose adjacent to
the nozzle. Installation to metal connections is
not recommended. Install as follows:
1. Plan to install turbine with a minimum
straight pipe length as follows:
– Upstream from the turbine, allow a mini-
mum straight pipe length of 10 times
the internal diameter of the turbine.
– Downstream from the turbine, allow a
minimum straight pipe length of 5 times
the internal diameter of the turbine.
2. For NPT Fittings wrap all connections with
3 to 4 wraps of thread tape. Make sure the
tape does not intrude into the flow path.
3. Attach meter with arrow pointed in the
direction of flow.
4. For NPT Fittings - Hand tighten the meter
at the housing ends. Do not use a wrench
or similar tool to tighten. This can damage
the housing.
Conditioned Signal Output
Module Wiring
This conditioned signal output module can be
wired to provide an open collector signal output
or 6-volt square wave output.
When installing an FTB690 Series meter, the
correct K-factor must be entered into the readout
device. You can find the K-factor printed on the
turbine body. All K-factors on Omega flowmeters
are calculated in pulses per gallon (PPG).
Open Collector Signal Output
To achieve an open collector signal output,
reference Wiring Diagram 1. The terminal block
is located on the back side of the module. The
module is factory assembled for open collector signal output. Please provide the (820 ohm
minimum) resistor, if not supplied by receiving
equipment.
Ten feet (3 m) of cable is provided with the
module. Trim it to desired length or extend it as
necessary. Distances up to 5,000 feet (1,524 m)
can be achieved for open collector signal output.
Square Wave Output
To achieve square wave output, reference Wiring Diagram 2 and use an FLSC790-BATT (sold
separately) for battery power. The terminal block
and battery location are located on the back
side of the module. Access as follows:
1. Remove the four Phillips-head screws from
the front of the module and lift the module
from the turbine.
2. To change terminal block connections,
loosen the appropriate screws. Reconnect
the wires in the proper positions and tighten
the screws.
1
Wiring Diagram 1
+9 to 35 volt DC
Open Collector
Signal
3
2
1
4
Red
White
Black
Common
(Ground)
Terminal
Block
Customer
Interfacing
Equipment
The terminal block is identified as follows:
Pin #1 6 volt square wave (not used)
Pin #2 +9 to 35 volt DC Input
Pin #3 Common Ground
Pin #4 Open Collector signal Output
3
2
1
4
White
Black
Common
(Ground)
Terminal
Block
Customer
Interfacing
Equipment
6 volt Square
Wave Signal
The terminal block is identified as follows:
Pin #1 6 volt square wave
Pin #2 +9 to 35 volt DC Input (not used)
Pin #3 Common Ground
Pin #4 Open Collector signal Output (not used)
OPEN COLLECTOR SIGNAL OUTPUT
Resistor
(820 ohm min.)
Wiring Diagram 2
2
SQUARE WAVE OUTPUT
3. Install the batteries. Make sure the positive
post is in the correct position.
4. Position the module on the turbine housing.
To avoid moisture damage, make sure the
seal is fully seated. Tighten the four screws
on the front of the module.
Ten feet (3 m) of cable is provided with the
module. Trim the cable to desired length or
extend it as necessary.
Verify Meter Accuracy
Before using, check the meter’s accuracy and
verify calibration.
1. Make sure there is no air in the system
by starting the flow until it runs steadily.
Then, stop or divert the flow using a valve
or nozzle.
2. Hold down DISPLAY for 3 seconds to zero
the meter’s Batch Total. When zeros appear,
release the button.
3. Meter an exact known volume into an
accurate container. For best results, meter
with one continuous full stream.
4. Check the volume against the display
or recording equipment. If the amount
metered is accurate, field calibration is not
necessary. If not, refer to the Calibration
Section for further instructions.
Batch and Cumulative Totals
The computer maintains two totals. The Cumulative Total provides continuous measurement
and cannot be manually reset. The Batch Total
can be reset to measure flow during a single
use. The Cumulative Total is labeled TOTAL 1,
Batch Total is labeled TOTAL 2 BATCH.
When the Cumulative Total reaches a display
reading of 999,999 the computer will highlight
an X10 icon. This indicates to the operator that
a zero must be added to the 6 digits shown.
When the next rollover occurs, the computer
will highlight an X100 icon. This indicates to
the operator that two zeros must be added to
the 6 digits shown.
Press the DISPLAY button briefly to switch
between the TOTAL 1, TOTAL 2 BATCH and
FLOWRATE. Press DISPLAY briefly to display
the TOTAL 2 BATCH. Hold the DISPLAY button
for 3 seconds to reset the Batch Total to zero.
When fluid is flowing through the meter, a small
propeller icon is highlighted.
Flowrate Feature
To use this feature, press and release DISPLAY
button until FLOWRATE icon appears. The
factory set time base will be highlighted to the
right of FLOWRATE (M = minutes, H = hours,
D = days). When FLOWRATE is invoked, the
display will be indicating rate of flow.
OPERATION
Computer Display
All operations are reflected in the LCD readout.
The large center digits indicate amounts, where
smaller words or “icons” located above and
below indicate specific information regarding
totals, flow, calibration and units of measure.
Activate the Meter
Computer is on continuously and always ready
to perform. The computer is powered by field
replaceable batteries. When display becomes
dim, faded or the low battery message appears
(see below), the batteries need to be replaced.
Reference the Maintenance Section for details.
Factory and Field Calibration
All calibration information is visible to the user
as icons on the top line of the display, above
the numeric digits.
All units are configured with a “factory” calibration. Both gallons and liters are available (“GL” or
“LT” will be displayed). While holding the CALIBRATE button, briefly press DISPLAY to toggle
between gallons and litres. This factory calibration (indicated with FAC) is permanently programmed into the computer and is not user adjustable.
NOTE: Your computer may have other units of
measure programmed into it. If so, holding
the CALIBRATE button and momentarily
pressing the DISPLAY button will toggle
through all factory set units. Other possible units are: IGL (imperial gallon), QT
(quart), CF (cubic feet), CM (cubic meter),
BL (42 gal. barrel), CC (cubic centimeter)
or OZ (ounce).
3
Switching between different units will not corrupt
the Total’s contents. For example, in GL mode,
the computer totalizes 10.00 gallons, if the user
switches to LT mode, the display will read 37.85
litres (the same volume, different unit).
The “field” calibration may be set by the user,
and can be changed or modified at any time
using the calibration procedure described below
in the Calibration Section. Totals or flowrate
derived from the field calibration are invoked
when the FAC icon is no longer visible on the
top line of the display.
CALIBRATION
Verify Accuracy Before
Beginning Field Calibration
For the most accurate results, dispense at
a flowrate which best simulates your actual
operating conditions. Avoid “dribbling” more
fluid or repeatedly starting and stopping the
flow. This can result in less accurate calibrations.
Make sure you meet the meter’s minimum
flowrate requirements:
FTB690A Series Meters
1/2 inch meter 1 GPM (3.8 LPM)
3/4 inch meter 2 GPM (7.5 LPM)
1 inch meter 5 GPM (18.9 LPM)
1-1/2 inch meter 10 GPM (37.9 LPM)
2 inch meter 20 GPM (75 LPM)
The use of a uniformly dependable, accurate
calibration container is recommended for the
most accurate results. Due to high flowrate, it
is strongly recommended that calibration be
completed with a combination of volume and
weight using fine resolution scales. For best
results, the meter should be installed and purged
of air before field calibration.
Field Calibration Procedures
(Dispense/Display Method)
1. To field calibrate, press and hold CALIBRATE and DISPLAY buttons for about 3
seconds until you see FLdCAL. Release
both buttons and you will see dd000.0.
You are now in the field calibration mode.
2. Dispense a known amount of fluid at a
flowrate representative of the application.
Any amount between .1 and 999.9 units
can be used. Display will count up while
fluid is flowing through the meter.
3. The DISPLAY button can then be pushed
to select the digit location and the CALIBRATE button can be pushed to scroll the
desired value at the blinking position. Edit
the amount shown with the value that was
dispensed above. Values from 000.1 to
999.9 can be entered.
4. When satisfied with the value, press both
CALIBRATE and DISPLAY buttons simultaneously. CALEnd will be displayed and
unit will go back to normal operation, less
the FAC (factory calibration) icon.
5. The meter will now be operating with a custom calibration number unique to the above
dispense procedure. No unit of measure
(gallon, litre, etc.) icon will be highlighted.
NOTE: To return to factory calibration (FAC),
press and hold both CALIBRATION and
DISPLAY buttons for about 3 seconds, until
FAcCAL is displayed. Then release buttons.
Unit should return to normal operation and
FAC icon visible.
NOTE: If the field calibration mode is entered
and NO fluid is dispensed, then upon leaving, the computer will use data from the last
successful field calibration.
Field Calibration with
Computer Display
Field Calibration and Factory Calibration are
defined in the Operation Section. Factory
calibration settings are programmed into each
computer during manufacturing, using water
at 70° F (21° C). Readings using the Factory
Calibration (FAC) may not be accurate in some
situations, for example, under extreme temperature conditions, non-standard plumbing
configurations or with fluids other than water.
4
MAINTENANCE
SPECIFICATIONS
Proper handling and care will extend the life
and service of the meter.
Turbine Rotor
The meter is virtually maintenance-free.
However, it is important the rotor moves freely.
Keep the meter clean and free of contaminants.
If the rotor does not turn freely, apply a penetrating lubricant on the rotor, shaft, and bearings.
Remove any debris or deposits from the rotor
using a soft brush or small probe. Be careful not
to damage the turbine rotor or supports.
CAUTION
Blowing compressed air through the turbine
assembly could damage the rotor.
Battery Replacement
The computer display is powered by two 3-volt
lithium batteries which may be replaced while
the meter is installed. When batteries are
removed or lose power, the batch and cumulative totals and the field and factory calibrations
are re tained.
If the display becomes dim, blankor the low
battery message appears (see below), replace
the batteries as follows:
1. Remove the four Phillips-head screws from
the face of the meter and lift the faceplate
from the turbine.
2. Remove the old batteries and clean any
corrosion from the terminals.
3. Install new batteries. Make sure the positive
post is in the correct position.
4. When the batteries are replaced, the faceplate will power ON. Check the display to
ensure normal functions have resumed
before assembling again.
5. Reseat batteries, if necessary, and position
the faceplate on the turbine housing.
To avoid moisture damage, make sure the
seal is fully seated. Tighten the four screws
Utilizar los metros de los Series del FTB690
con agua y otros productos químicos que son
compatibles con les componentes que se exponen
al líquido (véase la sección de especificaciones). No utilizar para medir el incompatible
combustible o los productos químicos. Los
metros de la serie del FTB690 están disponibles
con una visualización electrónica local, o un
módulo de salida condicionado de la señal
para proporcionar una señal numérica al
equipo de interconexión del cliente. Los
medidores Series FTB690 miden en galones
o litros. Referirse a la sección de la calibración
para mayores pantalla de ordenador detalles.
Estos medidores no son legales para las
aplicaciones comerciales.
Los medidores de las Series FTB690 son muy
sensibles a interferencia electrónica si funcionan
a 1 o 2 pulgadas de algunos motores eléctricos
o de otras fuentes del uso electrónico.
Instalar su medidor en línea, u horizontalmente,
o verticalmente, o en el extremo de la manguera
adyacente al inyector. No se recomienda la
instalación a las conexiones de metal. Siga
estos pasos para instalar:
1. Planee instalar la turbina con una longitud
mínima de la pipa recta de esta manera:
– Contra la corriente de la turbina,
permita a una longitud mínima de la
– Con la corriente de la turbina, permita
una longitud mínima de la pipa recta de 5
veces el diámetro interno de la turbina.
2. Para las Conexiones del NPT cubrir las con
exiones de pipa con la vueltas de cinta del
3 a 4 veces. Cerciorarse de que la cinta no
imponga en la trayectoria del flujo.
3. Unir el metro con la flecha señalada en la
dirección del flujo.
INSTALACIÓN
pipa recta de 10 veces el diámetro
interno de la turbina.
4. Para las Conexiones del NPT utilizar
solamente sus manos para apretar las
conexiones del metro. No utilizar una llave
inglesa o una herramienta similar para
apretar. Esto puede dañar la cubierta.
Señal de Salida Condicionada
Cableado de Módulo
Este módulo de Señal de salida condicionada
se puede conectar para proporcionar una
salida de colector abierta o de señal de onda
cuadra da de 6-voltios.
Al instalar un flujómetro de la turbina de la serie
del FTB690, el factor K correcto se debe incorporar en el dispositivo de la lectura. Usted puede
encontrar el factor K impreso en el cuerpo de la
turbina. Todos los factores K en flujómetros del
Omega se calculan en pulsos por galón (PPG).
Señal de Salida de Colector Abierto
Para alcanzar una señal de salida de colector
abierto, refierase por favor al digrama eléctrico
1. El bloque de terminales está situado en
el lado trasero del módulo. El módulo viene
montado de fábrica para señal de colector
abierta. Por favor proporcionar (el resistor de
un minimo de 820 ohmios), si no es provisto
por el equipo de recepción.
Diez pies (3 m) de cable se proporcionan con el
módulo. Ajustar el cable a la longitud deseada
o extender el cable cuanto le sea necesario.
Se puede alcanzar una señal de salida de
colector abierto hasta distancias de 5.000
pies (1,524 m).
Salida de corrente de
Onda Cuadrada
Para lograr una salida de corriente de onda
cuadrada, refierase por favor al digrama eléctrico 2 y utilize un FLSC790-BATT (vendido
por separado) para la fuente de energia de la
bateria. El bloque de terminales y la localización
de la bateria están situados en el lado trasero
del modulo. Acceda al módulo de la siguiente
manera:
1. Quitar los cuatro tornillos de cabeza
Phillips del frente del módulo. Levantar el
módulo de la turbina.
7
2. Para cambiar las conexiones del bloque
de terminales, aflojar los tornillos apropiados. Volver a conectar los alambres
en las posiciones apropiadas y apretar
los tornillos.
3. Instalar las baterias. Cerciorarse de que el
poste positivo esté en la posición correcta.
4. Colocar el módulo en la cubierta de la
turbina. Para evitar daños causados por
la humedad, cerciorarse de que el anillo
esté asentado completamente. Apretar los
cuatro tornillos en el frente del módulo.
Diez pies (3 m) de cable se proporcionan con el
módulo. Ajustar el cable a la longitud deseada
o extender el cable cuanto le sea necesario.
Verificar la Exactitud del Metro
Antes de usar, comprobar la exactitud del metro
y verificar la calibración.
1. Cerciorarse de que no haya aire en el sistema
comenzando el flujo hasta que funciona
constantemente. Entonces, detener o des-
viar el flujo mediante una válvula o la boquilla.
2. Mantenga el botón de la DISPLAY durante
3 segundos para llevar a cero el total de
medidor. Cuando aparezcan los ceros,
suelte el botón.
3. Con el medidor, mida un volumen exacto en
un envase exacto. Para mejores resultados,
medir con una corriente complete y continua.
4. Comprobar el volumen contra la pantalla o
el equipo de grabacion. Si la cantidad medi-
da es exacta, la calibración de campo no
es necesaria. Si no, refeierase a la sección
de la calibración.
OPERACIÓN
Ordenador de Pantalla
Todas las operaciones se reflejan en la lectura
del LCD. Los dígitos grandes del centro indican
cantidades, donde las palabras más pequeñas
o “iconos” que se encuentran por encima y por
debajo indican la información específica sobre
los totales, el flujo, la calibración y unidades de
medida.
Para Activar el Contador
El ordenador está encendido continuamente
y siempre dispuesto a operar. El equipo es alimentado por baterías reemplazables de campo.
Cuando la pantalla se vuelve opaco, desteñido
o el mensaje de batería baja (vea más abajo),
las baterías necesitan ser reemplazadas. Referencia de la sección de mantenimiento para
más detalles.
Lote y los Totales Acumulados
El computadora mantiene dos totales. El total
acumulativo proporciona la medida continua y
no puede ser reajustado manualmente. El total
de hornada se puede reajustar para medir el
flujo durante una sola vez. El total acumulativo
se etiqueta con el TOTAL 1 LOCKED. Esto indica que el total esta bloqueado y no puede ser
puesto a cero manualmente. l total acumulado
es etiquetado con TOTAL 1, lote total se etiqueta
TOTAL 2 BATCH.
Cuando el total acumulado llega a una lectura de
la pantalla de la computadora 999.999 resaltar
un icono de X10. Esto indica al operador que
un cero se debe agregar a los 6 dígitos que se
muestran. Cuando el traspaso se produzca la
próxima vez, el equipo se hará hincapié en un
icono X100. Esto indica al operador que dos
ceros se debe agregar a los 6 dígitos que se
muestran.
Pulse brevemente el botón DISPLAY para
cambiar entre el TOTAL 1, TOTAL 2 BATCH y la
configuración FLOWRATE. Pulse brevemente
DISPLAY para mostrar un total de TOTAL 2
BATCH. Mantenga pulsado el botón DISPLAY
durante 3 segundos para restablecer el lote
total a cero.
Cuando el líquido fluye a través del medidor, un
icono de hélice está resaltado.
Atributo del Indice de Flujo
Para utilizar esta función, pulse el botón DISPLAY y la FLOWRATE hasta que el icono aparece. La fábrica del conjunto de base de tiempo
se pondrá de relieve a la derecha del caudal de
agua (M = minutos, h = horas, D = días). Cuando
el cuadal de agua fluye, en la pantalla se indica
la velocidad de flujo.
8
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.