Omega Products DPG1000DAR Installation Manual

Digital Pressure Gauges
DPG1000DAR Series, Low Voltage AC/DC Powered with Dual Alarm Relays and 4 to 20 mA Output
INSTRUCTION
MANUAL
M3363/1001
Installation Precautions
Tighten/remove with wrench on hex fitting only. Do not attempt to rotate gauge by turning housing. Use fittings appropriate for the pressure range of the gauge. Do not apply vacuum to gauges not designed for vacuum operation. NEVER insert objects into the gauge port or blow out with compressed air.Permanent damage not covered by warranty will result.
Electrical Connection
NEVER connect the gauge power wires directly to 115 VAC or permanent
damage not covered by warranty will result. The two-conductor cable at the gauge rear with the RED and BLACK leads
is for the gauge power supply. Connect to 8 to 24 VAC, 50/60Hz or 9 to 32 VDC.The gauge will operate on either AC or DC power and there is no need to observe polarity. An unregulated power supply can be used. The supply voltage, when within the stated ranges, has negligible effect on the gauge calibration. Operation below 9 VDC or 8 VAC RMS may cause erratic or erroneous readings or output.
The gauge is powered on whenever a supply voltage is applied. Warm-up time is negligible.In normal operation the system pressure is displayed.
The color code for the 6-conductor alarm relay output cable is as follows.
SETPOINT 1 SETPOINT 2
Normally Closed (NC) BLACK Normally Closed (NC) GREEN Common (C) RED Common (C) BROWN Normally Open (NO) WHITE Normally Open (NO) BLUE
The shield (drain) wire is generally not needed for 4-20 mA current loops unless long cable lengths are used in electrically noisy environments.
Operation
The gauge is on whenever a supply voltage is applied.Warm-up time for full accuracy is negligible.In normal operation, the system pressure is displayed on the gauge LCD.The circuitr y also compares the system pressure to two independent setpoint levels;Setpoint 1 and Setpoint 2. These setpoint levels may be viewed by pressing either the SP1 or SP2 buttons. Operation of the alarm outputs is not affected by pressing SP1 or SP2.
Alarm status is easily seen on the two alarm indicator LEDs in the corner of the SP1 and SP2 buttons. A GREEN indication is a normal or non-alar m condition; RED is an abnormal or alarm condition.
In the standard HI/LO configuration, SP1 is configured as a HI alarm and will provide a RED alarm indication when the system pressure exceeds the setpoint. SP2, the LO alarm will provide a RED alar m indication when the system pressure falls below the setpoint.
Test Button
For system setup, testing, and troubleshooting, the TEST button is provided. The alarm outputs and the current loop may be “exercised” on demand without the need to vary the system pressure to test devices, annunciators, etc. connected to these outputs.
When the TEST button is pressed, the alarm relays are toggled to the opposite state, and the 4-20 mA output is set to the “test” level, which is indicated on the display.
The test level of the 4-20 mA output is determined by the setting of the top­accessible TEST potentiometer. To set the “test calibration” level, lift the top calibration label and locate the “TEST” potentiometer. While pressing the TEST button, adjust the display to the desired pressure reading that will be output as a 4-20 mA signal. For example, on a 0 to 100 psi gauge, setting the test level to 50.0 will give a 12 mA output whenever the TEST button is depressed.
Setting Alarms
To access alarm SP1 and SP2 controls, lift the calibration label on the top of unit and locate the proper potentiometer as indicated by the gauge rear label.This label can be reused many times.
Pressing SP1 or SP2 will switch the display to show and allow adjusting of the corresponding alarm setpoint.
To adjust alarm Setpoint 1, press and hold the SP1 button.When holding the SP1 button, the display will show the current setting for Setpoint 1. Turn the top-accessible Setpoint 1 control. Repeat the procedure by pressing and holding the SP2 button to adjust Setpoint 2.
It is allowable to set the LO alarm to a higher pressure than the HI alarm. Normal (Failsafe) vs. Reverse Action - Alarm configuration is set at the
factory at time of manufacture. Standard is a Normal (Failsafe) action HI/LO configuration where SP1 is the HI alarm and SP2 is the LO alarm. Gauges with HI/HI, LO/LO and reverse action relay configurations are also available.
With the Normal or Failsafe configuration, the alarm output relays will be CLOSED (relay energized) for a clear or non-alarm condition and OPEN (relay not energized) for an alarm condition. This is primarily for users who desire an alarm condition should the gauge lose power. “Normally closed” and “normally open” designations refer to standard relay terminology; i.e., the relay contact status with the relay coil not energized.
With the Normal (Failsafe) configuration, when in a green or non-alarm condition, the relay will be energized so that continuity can be expected between the common and normally open leads. In a red or alarm condition, the relay will be open (not energized), so that continuity can be expected between the common and normally closed leads.
With the Reverse acting alarm configuration, the relays will be open (not energized) in the non-alarm condition and closed for the alarm condition. In this case, continuity can be expected from common to normally closed in the green (non-alarm) condition and from common to normally open in the red (alarm) condition. This configuration can be used if a non-alarm condition is desired when the gauge power is shut off.
Alarm Deadband - The alar m circuit setpoints have built-in deadbands, also known as hysteresis, of 1% of span as standard.This means, for example, the deadband is approximately 1 psi in a 0 to 100 psi gauge.
This deadband serves to eliminate output oscillation or “chatter” of the alarms due to minor fluctuations in pressure. If, for example, the system pressure in a 0-100 psi system is 40.0 psi, and Setpoint 1 is set to 50.0 psi (HI alarm), the alarm indication will trip if the pressure exceeds 50.0 psi. After the HI alarm has tripped, pressing the SP1 button will show that the alarm indication will “release” at 1 psi lower (approximately 49 psi). Deadband is set at the factory to 1% but other deadbands can be configured at the factory where the application requires.
Contact Rating and Protection - The contacts of the alarm relays are rated at 1A/24VDC or 0.5A/115VAC maximum with non-inductive loads. Using mechanical relay contacts above their rating, or with large inductive loads, will shorten their useful life. In circuits other than low-level switching or pilot duty, the user should consider whether external contact protection such as snubber networks or arc suppression networks are required to protect the contacts. When switching higher electrical loads, the alarm relay should be used to drive an external contactor or solid state relay of sufficient capacity.
In addition, no internal fusing is included in the gauges. The circuit external to the gauge alarm outputs should be fused by the user in applications where good design practice dictates.
1
/4" NPT
2.88"
3.38"
0.75"
1.65"
Turn at
hex
fitting
only!
0.75"
Two 3 ft long, 4­conductor & 6 conductor 22 AWG shielded cables
SPECIFICATIONS
Ranges & Resolution
30.0 inHg vacuum, ±15.00, 3.00, 5.00, 15.00 psig
30.0, 100.0, 199.9, 300, 500, 1000, 3000, 5000 psig Absolute reference:15.00, 100.0 psia
Optional Units
Most engineering units such as kPa, atm, bar, mbar, inHg, mmHg, inH2O, ftH2O, torr, kg/cm2, cmH
2
O, oz/in
2
Display (type, size, update rate)
Ranges up to 1999: 3
1
/
2 digit LCD,
1
/
2" digit height
3000 & 5000 psi ranges: 4 digit LCD, 0.4" H digits 3 readings per second nominal display update
Accuracy (linearity, hysteresis, repeatability)
±0.25% of full scale or better, ±1 least significant digit
Temperature Stability(rel. to 77°F or 25°C)
±1% FS for offset & span, 32 to 158°F (0 to 70°C) typical ±2% FS for offset & span, 32 to 158°F (0 to 70°C) typical for 3 and 5 psi ranges
Alarm Deadbands (hysteresis)
1% of of full scale
Alarm Outputs
Dual form C (SPDT) relay contacts Individual Setpoint 1 and Setpoint 2 settings via top-accessible multiturn potentiometers HI/LO alarm configuration standard Relay contacts rated 1A/24VDC, 0.5A/115VAC maximum, non-inductive
Alarm Indicators
Bicolor (red/green) LEDs on front panel
Alarm Response Time
100 milliseconds typical
Test Function
Front panel TEST button toggles SP1 and SP2 alarm status and 4-20 mA output to test level, independent of pressure input to allow testing of system operation.
Retransmission Output
4-20 mA DC true analog output, 50 milliseconds typical response time.Output drive (compliance) determined by power source.
Power
DC 9 to 32 VDC, or AC 8 to 24VAC 50-60Hz
1.0 watt max.power consumption
Storage Temp:–40 to 203°F (–40 to 95°C) Operating Temp:–4 to 185°F (–20 to 85°C) Compensated Temp:32 to 158°F (0 to 70°C) Weight (approximate)
Gauge: 9 ounces, shipping weight: 1 pound
Housing
Extruded aluminum case, light gray epo xy powder coated Black polycarbonate cover, front and rear gaskets
Electrical Connection
3 ft long, 4-conductor 22AWG cable for power and 4-20 mA output. 3 ft long, 6-conductor 22AWG alarm relay cable
Pressure/Vacuum Connection & Material
1
/
4
" NPT male.All wetted parts are 316SS
Overpressure & Burst
5000 psig for 3000 psig range 7500 psig for 5000 psig range All others 2x rated pressure minimum Burst: 4x rated pressure minimum or 10,000 psi, whichever is less
Using the 4-20 mA Output
The 4-20 mA output is driven by the transducer rather than the display and thus is a true analog output.The output is filtered to improve noise immunity and thus has a response time of about 50 msec.
The power supply (–) lead is tied to the 4-20 mA output ground. Therefore the DC supply (–) lead should be considered common with regard to the 4­20 mA output (–) or ground connection.
Be sure to observe the output compliance (voltage drive) capabilities of the gauge. The compliance, and therefore the maximum loop resistance the output can drive, is a function of the supply voltage to the gauge. Consult the graph below for maximum loop resistance vs. supply voltage.Too large a loop resistance will cause the gauge output to “limit” or saturate before reaching its full 20 mA output.
Calibration
These gauges are factory calibrated and normally do not require recalibration before being put into service. If calibration is required, lift calibration label on the top of unit to access the Zero and Span controls.this label is designed to be reused many times.
For GAUGE reference units the setting of the Zero control is correct when the gauge reads zero, with the “–” sign occasionally flashing, when the pressure port is open to the ambient. Zero calibration must be done before span calibration is attempted. Since the calibration potentiometers are non-
interactive, gauge reference units may be rezeroed without affecting the span.
Span calibration should only be done when a pressure reference of known accuracy is available. The calibration equipment accuracy should be better than 4 times the accuracy of the gauge. Zero calibration must be done before span calibration. Record readings at three to five points over the range of gauge and adjust span control to minimize error and meet specifications.
Calibration of ABSOLUTE reference units is more difficult and is not recommended in the field, unless the user has access to equipment required to calibrate absolute-reference units, such as vacuum generation and atmospheric pressure measurement equipment.
Gauges can be returned to Omega Engineering for recalibration. NIST traceability is available.
The DPG1000DAR has internal controls that adjust the “agreement” between the displayed value and the 4-20 mA loop current. These are carefully set at the factory and should not normally be adjusted. Should the user feel this adjustment is necessary, the display zero/span must be accurately set first. Then, after removing the rear cover, the “loop zero” and “loop span” controls may be trimmed for 4.00 mA of loop current at the low end of the range, and 20.00 mA at the high end of the range, respectively. Accurate pressure generation and measurement, and current measurement equipment are required to successfully complete this calibration.
OMEGA Engineering Inc./Made in USA
TEST
SP1 SP2
1400
1200
1000
800
600
400
200
0
Max Loop Resistance (Ohms)
8 121620242832
Supply V oltage
Voltage Compliance for 4-20 mA Output
PSIG
DC
AC
Gauge power supply
9-32 VDC
or
8-24 VAC 50/60 Hz
(–)BLACK
(+)RED
(+)WHITE
(–)GREEN
Remote device
Optional
shield
connection
Zero SP2
Span
Test
SP1
See "Electrical Connections"
for relay wiring
Loading...
+ 2 hidden pages