Omega Products DPG1000DAR Installation Manual

Page 1
Digital Pressure Gauges
DPG1000DAR Series, Low Voltage AC/DC Powered with Dual Alarm Relays and 4 to 20 mA Output
INSTRUCTION
MANUAL
M3363/1001
Installation Precautions
Tighten/remove with wrench on hex fitting only. Do not attempt to rotate gauge by turning housing. Use fittings appropriate for the pressure range of the gauge. Do not apply vacuum to gauges not designed for vacuum operation. NEVER insert objects into the gauge port or blow out with compressed air.Permanent damage not covered by warranty will result.
Electrical Connection
NEVER connect the gauge power wires directly to 115 VAC or permanent
damage not covered by warranty will result. The two-conductor cable at the gauge rear with the RED and BLACK leads
is for the gauge power supply. Connect to 8 to 24 VAC, 50/60Hz or 9 to 32 VDC.The gauge will operate on either AC or DC power and there is no need to observe polarity. An unregulated power supply can be used. The supply voltage, when within the stated ranges, has negligible effect on the gauge calibration. Operation below 9 VDC or 8 VAC RMS may cause erratic or erroneous readings or output.
The gauge is powered on whenever a supply voltage is applied. Warm-up time is negligible.In normal operation the system pressure is displayed.
The color code for the 6-conductor alarm relay output cable is as follows.
SETPOINT 1 SETPOINT 2
Normally Closed (NC) BLACK Normally Closed (NC) GREEN Common (C) RED Common (C) BROWN Normally Open (NO) WHITE Normally Open (NO) BLUE
The shield (drain) wire is generally not needed for 4-20 mA current loops unless long cable lengths are used in electrically noisy environments.
Operation
The gauge is on whenever a supply voltage is applied.Warm-up time for full accuracy is negligible.In normal operation, the system pressure is displayed on the gauge LCD.The circuitr y also compares the system pressure to two independent setpoint levels;Setpoint 1 and Setpoint 2. These setpoint levels may be viewed by pressing either the SP1 or SP2 buttons. Operation of the alarm outputs is not affected by pressing SP1 or SP2.
Alarm status is easily seen on the two alarm indicator LEDs in the corner of the SP1 and SP2 buttons. A GREEN indication is a normal or non-alar m condition; RED is an abnormal or alarm condition.
In the standard HI/LO configuration, SP1 is configured as a HI alarm and will provide a RED alarm indication when the system pressure exceeds the setpoint. SP2, the LO alarm will provide a RED alar m indication when the system pressure falls below the setpoint.
Test Button
For system setup, testing, and troubleshooting, the TEST button is provided. The alarm outputs and the current loop may be “exercised” on demand without the need to vary the system pressure to test devices, annunciators, etc. connected to these outputs.
When the TEST button is pressed, the alarm relays are toggled to the opposite state, and the 4-20 mA output is set to the “test” level, which is indicated on the display.
The test level of the 4-20 mA output is determined by the setting of the top­accessible TEST potentiometer. To set the “test calibration” level, lift the top calibration label and locate the “TEST” potentiometer. While pressing the TEST button, adjust the display to the desired pressure reading that will be output as a 4-20 mA signal. For example, on a 0 to 100 psi gauge, setting the test level to 50.0 will give a 12 mA output whenever the TEST button is depressed.
Setting Alarms
To access alarm SP1 and SP2 controls, lift the calibration label on the top of unit and locate the proper potentiometer as indicated by the gauge rear label.This label can be reused many times.
Pressing SP1 or SP2 will switch the display to show and allow adjusting of the corresponding alarm setpoint.
To adjust alarm Setpoint 1, press and hold the SP1 button.When holding the SP1 button, the display will show the current setting for Setpoint 1. Turn the top-accessible Setpoint 1 control. Repeat the procedure by pressing and holding the SP2 button to adjust Setpoint 2.
It is allowable to set the LO alarm to a higher pressure than the HI alarm. Normal (Failsafe) vs. Reverse Action - Alarm configuration is set at the
factory at time of manufacture. Standard is a Normal (Failsafe) action HI/LO configuration where SP1 is the HI alarm and SP2 is the LO alarm. Gauges with HI/HI, LO/LO and reverse action relay configurations are also available.
With the Normal or Failsafe configuration, the alarm output relays will be CLOSED (relay energized) for a clear or non-alarm condition and OPEN (relay not energized) for an alarm condition. This is primarily for users who desire an alarm condition should the gauge lose power. “Normally closed” and “normally open” designations refer to standard relay terminology; i.e., the relay contact status with the relay coil not energized.
With the Normal (Failsafe) configuration, when in a green or non-alarm condition, the relay will be energized so that continuity can be expected between the common and normally open leads. In a red or alarm condition, the relay will be open (not energized), so that continuity can be expected between the common and normally closed leads.
With the Reverse acting alarm configuration, the relays will be open (not energized) in the non-alarm condition and closed for the alarm condition. In this case, continuity can be expected from common to normally closed in the green (non-alarm) condition and from common to normally open in the red (alarm) condition. This configuration can be used if a non-alarm condition is desired when the gauge power is shut off.
Alarm Deadband - The alar m circuit setpoints have built-in deadbands, also known as hysteresis, of 1% of span as standard.This means, for example, the deadband is approximately 1 psi in a 0 to 100 psi gauge.
This deadband serves to eliminate output oscillation or “chatter” of the alarms due to minor fluctuations in pressure. If, for example, the system pressure in a 0-100 psi system is 40.0 psi, and Setpoint 1 is set to 50.0 psi (HI alarm), the alarm indication will trip if the pressure exceeds 50.0 psi. After the HI alarm has tripped, pressing the SP1 button will show that the alarm indication will “release” at 1 psi lower (approximately 49 psi). Deadband is set at the factory to 1% but other deadbands can be configured at the factory where the application requires.
Contact Rating and Protection - The contacts of the alarm relays are rated at 1A/24VDC or 0.5A/115VAC maximum with non-inductive loads. Using mechanical relay contacts above their rating, or with large inductive loads, will shorten their useful life. In circuits other than low-level switching or pilot duty, the user should consider whether external contact protection such as snubber networks or arc suppression networks are required to protect the contacts. When switching higher electrical loads, the alarm relay should be used to drive an external contactor or solid state relay of sufficient capacity.
In addition, no internal fusing is included in the gauges. The circuit external to the gauge alarm outputs should be fused by the user in applications where good design practice dictates.
Page 2
1
/4" NPT
2.88"
3.38"
0.75"
1.65"
Turn at
hex
fitting
only!
0.75"
Two 3 ft long, 4­conductor & 6 conductor 22 AWG shielded cables
SPECIFICATIONS
Ranges & Resolution
30.0 inHg vacuum, ±15.00, 3.00, 5.00, 15.00 psig
30.0, 100.0, 199.9, 300, 500, 1000, 3000, 5000 psig Absolute reference:15.00, 100.0 psia
Optional Units
Most engineering units such as kPa, atm, bar, mbar, inHg, mmHg, inH2O, ftH2O, torr, kg/cm2, cmH
2
O, oz/in
2
Display (type, size, update rate)
Ranges up to 1999: 3
1
/
2 digit LCD,
1
/
2" digit height
3000 & 5000 psi ranges: 4 digit LCD, 0.4" H digits 3 readings per second nominal display update
Accuracy (linearity, hysteresis, repeatability)
±0.25% of full scale or better, ±1 least significant digit
Temperature Stability(rel. to 77°F or 25°C)
±1% FS for offset & span, 32 to 158°F (0 to 70°C) typical ±2% FS for offset & span, 32 to 158°F (0 to 70°C) typical for 3 and 5 psi ranges
Alarm Deadbands (hysteresis)
1% of of full scale
Alarm Outputs
Dual form C (SPDT) relay contacts Individual Setpoint 1 and Setpoint 2 settings via top-accessible multiturn potentiometers HI/LO alarm configuration standard Relay contacts rated 1A/24VDC, 0.5A/115VAC maximum, non-inductive
Alarm Indicators
Bicolor (red/green) LEDs on front panel
Alarm Response Time
100 milliseconds typical
Test Function
Front panel TEST button toggles SP1 and SP2 alarm status and 4-20 mA output to test level, independent of pressure input to allow testing of system operation.
Retransmission Output
4-20 mA DC true analog output, 50 milliseconds typical response time.Output drive (compliance) determined by power source.
Power
DC 9 to 32 VDC, or AC 8 to 24VAC 50-60Hz
1.0 watt max.power consumption
Storage Temp:–40 to 203°F (–40 to 95°C) Operating Temp:–4 to 185°F (–20 to 85°C) Compensated Temp:32 to 158°F (0 to 70°C) Weight (approximate)
Gauge: 9 ounces, shipping weight: 1 pound
Housing
Extruded aluminum case, light gray epo xy powder coated Black polycarbonate cover, front and rear gaskets
Electrical Connection
3 ft long, 4-conductor 22AWG cable for power and 4-20 mA output. 3 ft long, 6-conductor 22AWG alarm relay cable
Pressure/Vacuum Connection & Material
1
/
4
" NPT male.All wetted parts are 316SS
Overpressure & Burst
5000 psig for 3000 psig range 7500 psig for 5000 psig range All others 2x rated pressure minimum Burst: 4x rated pressure minimum or 10,000 psi, whichever is less
Using the 4-20 mA Output
The 4-20 mA output is driven by the transducer rather than the display and thus is a true analog output.The output is filtered to improve noise immunity and thus has a response time of about 50 msec.
The power supply (–) lead is tied to the 4-20 mA output ground. Therefore the DC supply (–) lead should be considered common with regard to the 4­20 mA output (–) or ground connection.
Be sure to observe the output compliance (voltage drive) capabilities of the gauge. The compliance, and therefore the maximum loop resistance the output can drive, is a function of the supply voltage to the gauge. Consult the graph below for maximum loop resistance vs. supply voltage.Too large a loop resistance will cause the gauge output to “limit” or saturate before reaching its full 20 mA output.
Calibration
These gauges are factory calibrated and normally do not require recalibration before being put into service. If calibration is required, lift calibration label on the top of unit to access the Zero and Span controls.this label is designed to be reused many times.
For GAUGE reference units the setting of the Zero control is correct when the gauge reads zero, with the “–” sign occasionally flashing, when the pressure port is open to the ambient. Zero calibration must be done before span calibration is attempted. Since the calibration potentiometers are non-
interactive, gauge reference units may be rezeroed without affecting the span.
Span calibration should only be done when a pressure reference of known accuracy is available. The calibration equipment accuracy should be better than 4 times the accuracy of the gauge. Zero calibration must be done before span calibration. Record readings at three to five points over the range of gauge and adjust span control to minimize error and meet specifications.
Calibration of ABSOLUTE reference units is more difficult and is not recommended in the field, unless the user has access to equipment required to calibrate absolute-reference units, such as vacuum generation and atmospheric pressure measurement equipment.
Gauges can be returned to Omega Engineering for recalibration. NIST traceability is available.
The DPG1000DAR has internal controls that adjust the “agreement” between the displayed value and the 4-20 mA loop current. These are carefully set at the factory and should not normally be adjusted. Should the user feel this adjustment is necessary, the display zero/span must be accurately set first. Then, after removing the rear cover, the “loop zero” and “loop span” controls may be trimmed for 4.00 mA of loop current at the low end of the range, and 20.00 mA at the high end of the range, respectively. Accurate pressure generation and measurement, and current measurement equipment are required to successfully complete this calibration.
OMEGA Engineering Inc./Made in USA
TEST
SP1 SP2
1400
1200
1000
800
600
400
200
0
Max Loop Resistance (Ohms)
8 121620242832
Supply V oltage
Voltage Compliance for 4-20 mA Output
PSIG
DC
AC
Gauge power supply
9-32 VDC
or
8-24 VAC 50/60 Hz
(–)BLACK
(+)RED
(+)WHITE
(–)GREEN
Remote device
Optional
shield
connection
Zero SP2
Span
Test
SP1
See "Electrical Connections"
for relay wiring
Page 3
DPG1000-PS Optional Power Supply Kit
The optional power supply kit includes a UL and CSA listed 115 VAC (50/60 Hz) wall-mount power supply with U.S. style 2-prong plug. Output is 12 VDC at 200 mA and is intended for gauges that accept DC power. The power supply’s two­conductor wire is approximately 6 feet long and has plain wire ends. Also included is a moisture resistant connector to allow easy hookup without having to strip wires.Use a pair of pliers to snap connector onto wires.
Note: A higher voltage power supply may be required for your current loop. See instructions for loop resistance and compliance voltage
1N Alarms, Hi/Lo Normal (Failsafe) Action
TEST
SP1
SP2
Span
Zero
Top View of Gauge
Potentiometers
Front
Condition Below SP Above SP Power Failure Relay coil Energized Not energized Not energized NC to Common Open Continuity Continuity NO to Common Continuity Open Open Alarm LED Green Red off
SP1, High Alarm
Condition Above SP Below SP Power Failure Relay coil Energized Not energized Not energized NC to Common Open Continuity Continuity NO to Common Continuity Open Open Alarm LED Green Red off
SP2, Low Alarm
2N Alarms, Hi/Hi Normal (Failsafe) Action
Condition Below SP Above SP Power Failure Relay coil Energized Not energized Not energized NC to Common Open Continuity Continuity NO to Common Continuity Open Open Alarm LED Green Red off
SP1, High Alarm
Condition Below SP Above SP Power Failure Relay coil Energized Not energized Not energized NC to Common Open Continuity Continuity NO to Common Continuity Open Open Alarm LED Green Red off
SP2, High Alarm
3N Alarms, Lo/Lo Normal (Failsafe) Action
Condition Above SP Below SP Power Failure Relay coil Energized Not energized Not energized NC to Common Open Continuity Continuity NO to Common Continuity Open Open Alarm LED Green Red off
SP2, Low Alarm
Condition Above SP Below SP Power Failure Relay coil Energized Not energized Not energized NC to Common Open Continuity Continuity NO to Common Continuity Open Open Alarm LED Green Red off
SP1, Low Alarm
1R Alarms, Hi/Lo Reverse Action
SP1, High Alarm
SP2, Low Alarm
2R Alarms, Hi/Hi Reverse Action
SP1, High Alarm
SP2, High Alarm
3R Alarms, Lo/Lo Reverse Action
SP2, Low Alarm
SP1, Low Alarm
Condition Below SP Above SP Power Failure Relay coil Not energized Energized Not energized NC to Common Continuity Open Continuity NO to Common Open Continuity Open Alarm LED Green Red off
Condition Above SP Below SP Power Failure Relay coil Not energized Energized Not energized NC to Common Continuity Open Continuity NO to Common Open Continuity Open Alarm LED Green Red off
Condition Below SP Above SP Power Failure Relay coil Not energized Energized Not energized NC to Common Continuity Open Continuity NO to Common Open Continuity Open Alarm LED Green Red off
Condition Below SP Above SP Power Failure Relay coil Not energized Energized Not energized NC to Common Continuity Open Continuity NO to Common Open Continuity Open Alarm LED Green Red off
Condition Above SP Below SP Power Failure Relay coil Not energized Energized Not energized NC to Common Continuity Open Continuity NO to Common Open Continuity Open Alarm LED Green Red off
Condition Above SP Below SP Power Failure Relay coil Not energized Energized Not energized NC to Common Continuity Open Continuity NO to Common Open Continuity Open Alarm LED Green Red off
Alarm Configuration Options
Model number: DPG1000DAR_____________________ Serial number: Location: Date recieved: Date put in service: Next calibration due:
Wiring Summary Potentiometers
4 Conductor Cable
Power Connection,DC 9 to 32 VDC,or AC 8 to 24 VAC 50-60Hz
RED (+) BLACK (–)
Current Loop Connection, 4-20 mA Output
WHITE (+) GREEN (–)
6 Conductor Cable
SETPOINT 1 Connections SETPOINT 2 Connections
Normally Closed(NC) BLACK Normally Closed(NC) GREEN Common (C) RED Common (C) BROWN Normally Open (NO) WHITE Normally Open (NO) BLUE
Page 4
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc.accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARNING:These products are not designed for use in, and should not be used for, patient connected applications.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC.warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase.OMEGA’s Warranty adds an additional one (1) month grace period to the normal one (1) year product warranty to cover handling and shipping time.This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer Service Depar tment will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will be repaired or replaced at no charge.OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of being damaged as a result of excessive corrosion;or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products.However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects.OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.LIMITATION OF LIABILITY:The remedies of purchaser set forth herein are exclusive and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based.In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component”under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/ DISCLAIMER language, and additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit. FOR W
ARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
1. P.O. number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-W
ARRANTY REPAIRS,
consult OMEGA for current repair charges.Have the following information available BEFORE contacting OMEGA:
1. P.O.number to cover the COST of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems relative to
the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC. © Copyright 2001 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any
electronic medium or machine-readable form, in whole or in part, without prior written consent of OMEGA ENGINEERING, INC.
Servicing North America:
USA: One Omega Drive, P.O. Box 4047
ISO 9001 Certified Stamford CT 06907-0047
TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com
Canada: 976 Bergar
Laval (Quebec) H7L 5A1 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: canada@omega.com
For immediate technical or application assistance:
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
®
Customer Service: 1-800-622-2378 / 1-800-622-BEST
®
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
®
TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
Mexico: Tel: (001) 800-826-6342 FAX: (001) 203-359-7807
En Espan˜ol: (001) 203-359-7803 e-mail: espanol@omega.com
info@omega.com.mx
OMEGAnet®On-Line Service Internet e-mail
www.omega.com info@omega.com
Servicing Europe:
Benelux: Postbus 8034, 1180 LAAmstelveen, The Netherlands
Tel: +31 (0)20 6418405 FAX: +31 (0)20 6434643 Toll Free in Benelux: 06 0993344 e-mail: nl@omega.com
Czech Republic: Rudé armády 1868,73301 Karviná
TEL: +420 (0)69 6311899 FAX: +420 (0)69 6311114 Toll Free in Czech Rep.: 0800-1-66342 e-mail: czech@omega.com
France: 9, rue Denis Papin, 78190 Trappes
TEL: +33 (0)130 621 400 FAX: +33 (0)130 699 120 Toll Free in France: 0800-4-06342 e-mail: france@omega.com
Germany/Austria: Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 (0)7056 3017 FAX: +49 (0)7056 8540 Toll Free in Germany: 0800 TC OMEGA
SM
e-mail: germany@omega.com
United Kingdom: P.O. Box 7, Omega Drive,
ISO 9002 Certified Irlam, Manchester,
M44 5EX, United Kingdom TEL: +44 (0)161 777 6611 FAX: +44 (0)161 777 6622 Toll Free in England: 0800 488 488 e-mail: sales@omega.co.uk
Loading...