Omega Products DPF9101 User Manual

DIGITAL INPUT PANEL METERS
DPF9100
Starts at
$
211
Count, Dual Count,
Rate and Slave Display
6-Digit, 14 mm
(0.56") LED
Variable Intensity Display10-Point Scaling for
Non-Linear Inputs (DPF9300 Series)
NEMA 4X (IP65) Sealed
Front Bezel
The DPF9000 Series digital input panel meters offer many features and performance capabilities to suit a wide range of industrial applications. Available in three different models, DPF9100 Series rate meter, DPF9200 Series counter/dual counter, and the DPF9300 Series which offers both counting and rate in the same package. The DPF9100 Series and DPF9200 Series offer only the set point option, while the DPF9300 Series is the fully featured version offering all the capabilities as outlined in this bulletin as well as a slave display feature. The optional plug in output cards allow the opportunity to configure the meter for present applications, while providing easy upgrades for future needs. The meters employ a bright 14 mm (0.56") LED display. The intensity of the red LED display can be adjusted from dark room applications up to sunlight readable, making it ideal for viewing in bright light applications. The meters accept digital inputs from a variety of sources including switch contacts, outputs from CMOS or TTL circuits, magnetic pickups and
all standard RLC sensors. The meter can accept directional, uni­directional or quadrature signals simultaneously. The maximum input signal varies up to 34 KHz depending on the count mode and function configurations programmed. Each input signal can be independently scaled to various process values. The rate meters provide a MAX and MIN reading memory with programmable capture time. The capture time is used to prevent detection of false max or min readings which may occur during start-up or unusual process events. The meters have four set point outputs, implemented on plug-in option cards. The plug-in cards provide dual FORM-C relays (5A), quad FORM-A (3A), or either quad sinking or quad sourcing open collector logic outputs. The set point alarms can be configured to suit a variety of control and alarm requirements. Communication and Bus capabilities are also available as option car through the bus. Additionally, the meters have a feature that allows a remote computer to directly control the outputs of the meter.
M-X
DPF9100, $211, shown actual size.
With an RS232 or RS485 card installed (on DPF9300 Series only), it is possible to configure the meter using free
omega.com/ftp.
data can be saved to a file for later recall. A linear DC output signal is available as an optional Plug-in card for the DPF9300 series only. The card provides either 20 mA or 10V signals. The output can be scaled independent of the input range and can track any of the counter or rate displays.
Once the meters have been initially configured, the parameter list may be locked out from further modification in its entirety or only the set point values can be made accessible. The meters have been specifically designed for harsh industrial environments. With NEMA 4X(IP65) sealed bezel and extensive testing of noise effects to CE requirements, the meter provides a tough yet reliable application solution.
software available at The configuration
M
DPF9100, $211,
SPECIFICATIONS
Display: 6-digit, 14.2 mm (0.56")
red LED, (-99999 to 999999)
POWER
AC Powered Units: 85 to 250 Vac,
50/60 Hz, 18 VA Isolation: 2300 Vrms for 1 min. to all
inputs and outputs (300V working) Low Voltage Power: 11 to 36 Vdc,
14 W (derated operating temperature to 40°C (104°F) if operating <15 Vdc and three plug in option cards are installed); 24 Vac, ±10%, 50/60 Hz, 15 VA, 500 Vrms isolation for 1 min to all inputs and outputs (50V working)
Sensor Power: 12 Vdc, ±10%, 100 mA max short circuit protected Keypad: 3 programmable function keys, 5 keys total
User Inputs: Three programmable user inputs
Max Continuous Input: 30 Vdc Isolation to Sensor Input Commons:
Not isolated Logic State: Jumper selectable for
sink/source logic
INPUT STATE
Sinking Inputs: 5.1 k pull-up to +12V
Active: Vin<0.9 Vdc Inactive: Vin>3.6 Vdc
Sourcing Inputs
Active: Vin>3.6 Vdc Inactive: Vin<0.9 Vdc
Response Time: 6 msec. typical;
function dependent. Certain resets, stores and inhibits respond within 25 µsec if an edge occurs with the associated counter or within 6 msec if no count edge occurs with the associated counter. These functions include CtrStL, CtrStE, HLrStL, HLrStE, INHlbt, StOrE, and PrNsSt. Once activated, all functions are latched for 50 msec min. to 100 msec max. After that period, another edge/level may be recognized
: 5.1 k pull-down
Memory: Nonvolatile EEPROM retains
all programmable parameters and display values.
ENVIRONMENTAL CONDITIONS
Operating Temperature Range:
0 to 50°C (32 to 122°F) [0 to 45°C (32 to 113°F) with all three plug-in cards installed]
Storage Temperature Range:
-40 to 60°C (-40 to 140°F)
Operating and Storage Humidity:
0 to 85% max relative humidity non-condensing
Altitude: Up to 2000 m (1.24 mi) Connections: High compression cage-
clamp terminal block
Wire Strip Length: 7.5 mm (0.3") Wire Gage: 30-14 AWG copper wire Torque: 4.5 inch-lbs (0.51 Nm) max Construction: This unit is rated for
NEMA 4X/IP65 outdoor use. IP20 Touch safe. Installation Category II, Pollution Degree 2. One piece bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and mounting clip included.
Weight: 10.1 oz (286 g)
COUNTER DISPLAYS (DPF9200 and DPF9300 only)
Maximum Display: 8-digits:
±99999999 (greater than 6-digits display alternates between high order and low order)
RATE DISPLAY (DPF9100 and DPF9300 only)
Accuracy: ±0.01% Minimum Frequency: 0.01 Hz Maximum Frequency: 34 kHz
(depending on set-up)
Maximum Display: 5-Digits: 99999 Adjustable Display (low) Update:
0.1 to 99.9 seconds
Over Range Display: “rOLOL”
M-X
FTB-1302, liquid turbine flowmeter, $620, shown smaller than actual size. See page F-47.
INPUTS A or B:
DIP switch selectable to accept pulses from a variety of sources including switch contacts, TTL outputs, magnetic pickups and all standard RLC sensors.
Logic: Input trigger levels VIL=1.5V max; VIH=3.75V min.
Current Sinking: Internal 7.8 k pull-up to +12 Vdc, IMAX=1.9 mA.
Current Sourcing: Internal 3.9 k pull-down, 7.3 mA max @ 28 Vdc, VMAX=30 Vdc.
Filter: Damping capacitor provided for switch contact bounce. Limits input frequency to 50 Hz and input pulse widths to 10 msec minimum.
MAGNETIC PICKUP (DPF9100 and DPF9300 only)
Sensitivity: 200 mV peak Hysteresis: 100 mV
Input Impedance: 3.9 k @ 60 Hz Maximum Input Voltage: ±40V peak,
30 Vrms
DUAL COUNT MODES (DPF9200 or DPF9300 only)
When any dual count mode is used, then User Inputs 1 and/or 2 will accept the second signal of each signal pair. The user inputs do not have the Logic/Mag, High/Low Freq, and Sink/Source input setup switches. The user inputs are inherently a logic input with no low frequency filtering. Any mechanical contacts used for these inputs in a dual count mode must be debounced externally. The user input may only be selected for sink/source by the User Jumper placement.