PROCESS RECEIVER INDICATOR/
CONTROLLER
1
⁄8 DIN
DP2000-PE Series
U 10 or 15 Vdc Excitation Output
(DP2/9000E)
U ±1999 or ±9999 Count Display Span
U Selectable Current Ranges From
±1 to ±50 mA
U Selectable Voltage Ranges From
±0.5 to ±20 V
U Built-In Shunts and Attenuators
U
Zero Adjustment to ±100% of Readout
U Standard Signal Ranges of 4 to 20 mA,
10 to 50 mA, 1 to 5V or 0 to 10V
U Front-Panel Accessible Zero and
Span Adjust
U 1 mV/Count Analog Output
U LED or LCD Display
U Automatic Polarity
U Display Hold and Test
U Screw-Terminal Barrier Strip
The DP2000/9000-P is a process receiver with
extensive zero and span adjustment capability for
readout in engineering units. The more popular process
signals are 4 to 20 mA, 10 to 50 mA, 1 to 5V and 0 to
10V. The DP2000/9000-P can also be scaled for other
signal levels. Full-scale input ranges are selectable from
±1 to ±50 mA (current signal) or ±0.5 to ±20 V (voltage
signal). Zero is adjustable up to ±100% of full-scale
readout for every input range. A universal
houses each meter. Choose any combination of display
type (LED or LCD), operating power, input type and
range, analog output, and digital or control outputs.
1
⁄
8 DIN case
The DP2000/9000-E is an enhanced version of
the DP2000/9000-P with an excitation output for
powering transmitters and active transducers. In
many cases, this output can eliminate the need for a
more expensive external supply. The output shares
the ground of the signal input. Two output levels are
jumper-selectable: 10 Vdc at up to 50 mA and
15 Vdc at up to 25mA.
CONFIGURATION AND CALIBRATION
The DP2000/9000-P and DP2000/9000-E includes
configuration and calibration. Models can also be
configured and scaled in the field. Full-scale signal,
coarse-span and coarse-zero ranges are selected
by plug-in jumpers. A complete set of internal shunts
and attenuators are already on board. Fine-zero and
fine-span potentiometers are accessible behind the
lens to allow final calibration or field recalibration
without removal of the panel meter.
DP2401-P1 shown
actual size.
INSTRUMENTATION
D
PROCESS SIGNAL INPUT
15 Vdc INTERNAL EXCITATION
CODE*
E10
E11
MAX INPUT
SPAN
E1
0.5 V 0.08 counts/mV 2.85 counts/mV
E2
0.5 V 2.84 counts/mV 5.55 counts/mV
E3
0.5 V 5.49 counts/mV 8.17 counts/mV
E4
5.0 V 8.0 counts/mV 231.0 counts/mV
E5
5.0 V
E6
10.0 V 4.0 counts/mV 114.5 counts/mV
E7
10.0 V
E8
4 to 20 mA 2.5 counts/mA 70.4 counts/mA
E9
4 to 20 mA 70.5 counts/mA 137.0 counts/mA
10 to 50 mA 1.0 counts/mA 28.2 counts/mA
10 to 50 mA 28.1 counts/mA 55.0 counts/mA
WITH
MIN GAIN MAX GAIN
230.0 counts/mV
114.0 counts/mV
E SERIES
449.0 counts/mV
223.0 counts/mV
PROCESS SIGNAL INPUTS P SERIES
CODE*
P1
P2
P3
P4
P5
P6
P7
P8
P9
P10
P11
D-1
MAX INPUT
SPAN
0.5V
0.5V
0.5V
5.0V 8.0 counts/V 231.0 counts/V
5.0V 230.0 counts/V 449.0 counts/V
10.0V 4.0 counts/V 114.5 counts/V
10.0V 114.0 counts/V 223.0 counts/V
4 to 20 mA 2.5 counts/mA 70.4 counts/mA
4 to 20 mA
10 to 50 mA
10 to 50 mA
MIN GAIN MAX GAIN
0.08 counts/mV
2.84 counts/mV
5.49 counts/mV
70.5 counts/mA 137.0 counts/mA
1.0 counts/mA
28.1 counts/mA
2.85 counts/mV
5.55 counts/mV
8.17 counts/mV
28.2 counts/mA
55.0 counts/mA
SPECIFICATIONS
Conversion
Technique: Dual slope, average value
Signal Integration Period: 100 ms,
nominal
Reading Rate: 2.5/s, nominal
Display
LED: Red, 14.2 mm (0.56"), 7-segment
LCD: 12.7 mm (0.50"), 7-segment
Power
AC Models: 120, 240 or 24 Vac 10%/
-15%, 49 to 440 Hz
DC Models: 9 to 32 Vdc, isolated to
300 Vp; 26 to 56 Vdc, isolated to 300 Vp;
5 Vdc ±5%, non-isolated
Common Mode
Voltage: 1500 Vp test (354 Vp per IEC
spacing)
Rejection: 120 dB
Accuracy at 25°C
Error, Maximum: ±0.05% of reading ±1
count (DP2000); ±2 counts (DP9000)
Span Tempco: ±0.01% of reading/°C
Zero Drift, Maximum: ±0.01% of
reading/°C
Offset Drift, Maximum: ±(0.01% offset
V ±0.01% full scale V)/°C
Step Response: 1 s to 99.9% of span
Warmup to Rated Accuracy:
10 minutes (DP2000); 30 minutes
(DP9000)
Environmental
Operating Temperature: 0 to 60°C
(32 to 140°F)
Storage Temperature: -40 to 85°C
(-40 to 185°F)
Humidity: To 95% RH, non-condensing
@ 40°C (104°F)
Mechanical
Bezel: 96 W x 48 H x 8 mm D
(3.78 x 1.89 x 0.31")
Depth Behind Bezel: 139.8 mm (5.50")
Panel Cutout: 92 W x 45 mm H
(3.62 x 1.77")
Weight: 17 oz (480 g)
Case Material: 94V-0 UL-rated
polycarbonate
To Order Visit omega.com/dp2000-pe for Pricing and Details
MODEL NO. DESCRIPTION
DP2
DP9
* Refer to chart on previous page for input code options.
Accessory
MODEL NO. DESCRIPTION
DPP-5
Comes complete with operator’s manual.
Ordering Examples: DP2000-P4, 3½ digit process receiver, red LED, 120 Vac power, 1 to 5V, and 8 to 230 counts/V.
DP2001-E4, 3½ digit process receiver with excitation, red LED, 120 Vac power, 1 to 5V, with dual setpoint 10A relay, and 8 to 230 counts/mV.
3½-DIGIT FOR ±1999 COUNT
4-DIGIT FOR ±9999 COUNT
0 0 0 -X A. POWER AND DISPLAY
0
1
2
3
4
5
6
7
8
9
A
B
1
DIN panel punch
⁄
8
0
1
2
3
4
5
6
0
1
2
3
4
5
(*)
-E
(*)
-P
-G
LED; 120 Vac (50/60 Hz)
LCD; 120 Vac (50/60 Hz) (DP2000 only)
LED; 240 Vac (50/60 Hz)
LCD; 240 Vac (50/60 Hz) (DP2000 only)
LED; 9 to 32 Vdc, isolated
LCD; 9 to 32 Vdc, isolated (DP2000 only)
LED; 5 Vdc
LCD; 5 Vdc (DP2000 only)
LED; 24 Vac
LCD; 24 Vac (DP2000 only)
LED; 26 to 56 Vdc, isolated
LCD; 26 to 56 Vdc, isolated (DP2000 only)
B. ANALOG OUTPUTS
1 mV/count (supplied on all units)
0 to 5 Vdc
0 to 10 Vdc
0 to 1 mA (internally driven)
4 to 20 mA (internally driven)
4 to 20 mA (externally driven)
4 to 20 mA (isolated)
C. CONTROL OUTPUTS
None
Dual setpoint, 10 A relay (SPDT)
Proportional 4 to 20 mA
Proportional/time proportioning, 2 A relay
Parallel BCD, isolated
Single setpoint, 10 A relay (SPDT)
D. SIGNAL CONDITIONER INPUTS
Process signal with 15 Vdc excitation
Process signal
ADDITIONAL OPTIONS
Geen LED display
D-2