Omega Products CNiTH User Manual

Humidity and Temperature Controllers
CNiTH-i8DV33-5
DPiTH Series CNiTH Series
All models shown
smaller than actual size.
CNiTH-i16D33-2
U Dual Loop
Control
U Humidity and
Temperature
U High Accuracy
±0.5°C and ±2% RH
U 4 Popular DIN Sizes U Ethernet and Serial
Communications (Optional)
U 2 Control or Alarm
Outputs (Optional)
U Choice of Relays,
SSR, DC Pulse, Analog Voltage and Current
U User-Friendly, Simple
to Configure
U Full Autotune PID Control U Programmable Ramp and
Soak for Humidity and/or Temperature
U Includes Temp/RH Sensor
The OMEGA® iTH Series instruments monitor and control both temperature and relative humidity. All meters and controllers in the series are high quality, highly accurate instruments featuring Omega’s award-winning iSeries technology, uncompromising accuracy, backed by an extended 5-year warranty.
The instruments are simple to configure and use, while providing tremendous versatility and a wealth of powerful features.
The OMEGA iTH Series instruments are available either as monitors or controllers. The monitors are extremely accurate programmable digital panel meters displaying humidity, temperature, or dew point. The controllers also provide dual loop control for both humidity
and temperature and are easily programmed for any control or alarming requirement from simple on/off to full autotune PID control.
The iTH family of meters and controllers are available in 4 DIN sizes with NEMA 4X (IP65) splash resistant bezels: the ultra compact
1
32 DIN (the world’s smallest dual loop humidity and temperature controller); the popular midsize
1
16 DIN square bezel with dual display; the 1⁄8 DIN vertical, and the
1
8 DIN horizontal with the big, bright 21 mm (0.83") digits.
The OMEGA iTH Series LED displays can be programmed to change color between GREEN, AMBER, and RED at any setpoint or alarm point.
The iTH controller models offer a choice of 2 control or alarm outputs in almost any combination: solid state relays (SSR); form “C” SPDT (single pole double throw) relays; pulsed 10 Vdc output for use with an external SSR; or analog output selectable for control or retransmission of the process value.
The networking and communications options (highly recommended) include direct Ethernet LAN connectivity with an embedded Web server, and serial communications. The C24 serial communications option includes both RS232 and RS485. Protocols include both MODBUS® and a straightforward ASCII protocol. The C4EI option includes both Ethernet and RS485 ASCII/MODBUS on one device.
CNiTH-i8DH33-2
Hu-29
SenSor
included!
The iTH Series meters and controllers are designed for easy integration with popular industrial automation, data acquisition and control programs as well as Microsoft Visual Basic and Excel. OMEGA provides free configuration software which makes it fast and easy to get up and running. Available on CD ROM and for download on the Web.
Specifications
Control
Action: Reverse (heat) or direct (cool) Modes: Time and amplitude proportional
control modes; selectable manual or auto PID, proportional, proportional with integral, proportional with derivative with anti-reset windup and ON/OFF
Rate: 0 to 399.9 seconds Reset: 0 to 3999 seconds Cycle Time: 1 to 199 seconds; set to
0 for ON/OFF operation
Gain: 0.5 to 100% of span; setpoints 1 or 2 Damping: 0000 to 0008 Soak: 00.00 to 99.59 (HH:MM), or OFF Ramp to Setpoint:
00.00 to 99.59 (HH:MM), or OFF Autotune: Operator initiated from front
panel for 1 input at a time only
Control Output 1 and 2
Relay: 250 Vac or 30 Vdc @ 3 A
(resistive load); configurable for on/off, PID, Ramp and Soak
Output 1: SPDT type, can be configured as alarm 1 output
Output 2: SPDT type, can be configured as alarm 2 output
SSR: 20 to 265 Vac @ 0.05 to 0.5 A (resistive load); continuous
DC Pulse: Non-Isolated; 10 Vdc @ 20 mA
CNiTH-i3233-5
(1.89 x 3.78 x 5)
POWER
OUTPUT2 OUTPUT1
BLACK
WHITE
GREEN
RED
SHIELD
N/C
Analog Output (Output 1 Only): Non-Isolated, Proportional 0 to 10 Vdc or 0 to 20 mA; 500 Ω maximum
Alarm 1 and 2 (Programmable)
Type: Same as output 1 and 2 Operation: High/low, above/below, band,
latch/unlatch, normally open/normally closed and process/deviation; front panel configurations
Analog Output (Programmable):
Non-Isolated, retransmission 0 to 10 Vdc or 0 to 20 mA, 500 Ω maximum (output 1 only) (accuracy is ± 1% of FS when following conditions are satisfied):
1) Input is not scaled below 1% of Input FS
2) Analog out is not scaled below 3% of Output FS
Input
Accuracy/Range:
±2% for 10 to 90%; ±3% for 5 to 10% and 90 to 95% ±4% for 0 to 5% and 95 to 100%
Hysteresis: ±1% RH Non-linearity: ±3% Temperature Accuracy/Range*
±0.5°C for 5° to 45°C (±1°F for 41 to 113°F); up to ±1.5°C for -40° to 5°C and 45° to 124°C (up to ±2.7°F for -40° to 41°F and 113° to 255°F) Resolution: 0.1%, 12bit for RH; 0.1°C, 14 bit for temperature Response Time: 8 seconds, tau 63% for RH; 5 to 30 seconds, tau 63% for temperature
* Note: Extended temperature range is for industrial probe only, the controller’s operating temperature is 0 to 50°C.
Network and Serial Communications (For Options -C24, -C4EI, -EI)
Ethernet: Standards compliance
IEEE 802.3 10Base-T Supported Protocols: TCP/IP, ARP,
HTTPGET RS232/RS422/RS485: Selectable from
menu; both ASCII and MODBUS protocol selectable from menu; programmable 300 to 19.2 K baud; complete programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status
RS485: Addressable from 0 to 199 Connection: Screw terminals
General
A/D Conversion: 12-bit RH and 14-bit temp Reading Rate: 2 samples per sec max Digital Filter: Programmable
Display: 4-digit, 9-segment LED
i32, i16D, i8DV: 10.2 mm (0.40") i8: 21 mm (0.83") i8DH: 10.2 mm (0.40") and 21 mm (0.83")
RED, GREEN and AMBER
programmable colors for process variable, setpoint and temp units
Operating Temperature: 0 to 50°C (32 to 122°F), 90% RH non-condensing
Protection: i32, i16D: NEMA 4X (IP65) front bezel
i8DH, i8DV: NEMA 1 (IP23) front beze
Power: Refer to ordering guide below
No CE compliance above 60 Hz.
l
CNiTH-i8DH shown with -2 Probe
16 (0.63) DIA
1 m (3') CABLE
51 (2)
21.1 (0.83) SQ
48 H x 96 W x 127 D
CUTOUT: 45 H x 92 W (1.77 x 3.62)
For other mechanical drawings please visit
omega.com/ith for more information.
CNiTH-i8DV shown with -5 Probe
16 (0.63) DIA
3 m
(10')
CABLE
137 (5.4)
0.83 (21.1) SQ
96 H x 48 W x 127 D (3.78 x 1.89 x 5)
CUTOUT: 92 H x 45 W (3.62 x 1.77)
To Order Visit omega.com/ith for Pricing and Details
Model No. Description
DPiTH- (****) Monitor version, no control outputs CNiTH- (****) ( * * ) Controller version, select 2 control outputs i8DH Temperature and RH Input i8DV Temperature and RH Input i16D Temperature and RH Input i32 Temperature and RH Input
Control Outputs 2 2 2 solid state relays (SSR’s): 0.5 A @ 120/240 Vac continuous 2 3 SSR and relay: Form “C” SPDT 3A @ 120Vac, 3A @ 240Vac 2 4 SSR and pulsed 10 Vdc @ 20 mA (for use with external SSR) 3 3 2 Relays: Form “C” SPDT 3 A @ 120 Vac, 3 A @ 240 Vac 4 2 Pulsed 10 Vdc @ 20 mA (for use with external SSR) and SSR 4 3 Pulsed 10 Vdc @ 20 mA (for use with external SSR) and relay 4 4 2 pulsed 10 Vdc @ 20 mA (for use with external SSR) 5 2 Analog output selectable as either control or retransmission of process
value; 0 to 10 Vdc or 0 to 20 mA @ 500 Ω max & SSR
5 3 Analog output 0 to 10 Vdc or 0 to 20 mA @ 500 Ω max & relay
5 4 Analog out 0 to 10 Vdc or 0 to 20 mA @ 500 Ω max & pulse 10 V
-AL limit alarm version (simplified menu; no PID control)* RH/Temperature Probe (Must Select One)
-2 51 mm (2") probe for iTH with 1 m (3') cable
-5 127 mm (5") probe for iTH with 3 m (10') cable Power Supply * Standard power input: 90 to 240 Vac ±10%, 50 to 400 Hz, 110 to 375 Vdc,
equivalent voltage (*no entry required)
-DC Low voltage power option: 20 to 36 Vdc, 24 Vac ±10%; 12 to 36 Vdc, 24 Vac ±10% for iTH-32
Network Options
-EI Ethernet with Embedded Web Server*
-C24 Isolated RS232 and RS485/422. 300 to 19.2k Baud
-C4EI Ethernet with Embedded Web Server + Isolated RS485/422 hub for up to 31 devices*
2
Accessories
Software
OPC-SERVER LICENSE OPC server/driver software license (requires network option) iTHP-2
iTHP-5
*1 Analog output (Option 5) is not available with “-AL” units. *2 -C4EI or -EI option is not available on the
that can connect to a CNiTH-i32xx-x-C24. Units can be powered safely with 24 Vac power, but no certification for CE/UL are claimed.
Ordering Examples: CNiTH-i8DH43-5-C4EI is a horizontal a 5" probe and Ethernet with embedded Web server.
DPiTH-i16D-2-EI,
1
16 DIN dual display with a 2" probe and Ethernet with embedded Web server.
51 mm (2") replacement probe for iTH with 1 m (3') cable 127 mm (5") replacement probe for iTH with 3 m (10') cable
1
32 DIN. Refer to the iServer section for other Ethernet devices
1
8 DIN dual display horizontal
1
8 DIN dual display vertical
1
16 DIN dual display
1
32 DIN single display*
2
1
8 DIN dual display with pulse and relay outputs,
2
1
H
u
Hu-30