Disassembly Instruction:
If necessary, the unit may be removed from the panel and
opened.
Warning: Disconnect all ac power from the unit
before proceeding.
1. Remove all wiring connections from the rear of the
instrument, by unplugging the power and input connectors.
2. Remove both thumbnuts and set aside.
3. Remove the sleeve and set aside.
4. Remove the meter from the panel and bend the side
panel detents on the case outward to release the board.
Pull the board assembly out of the case.
WIRING
Wire the instrument according to the figure shown below
Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow all
instructions and warnings may result in injury!
This Quick Start Reference provides information
on setting up your instrument for basic operation.
The latest complete Communication and Operational
Manual as well as free Software and ActiveX Controls
are available at www.omega.com/specs/iseries or
on the CD-ROM enclosed with your shipment
..
SAFETY CONSIDERATION
This device is marked with the international
Caution symbol.
The instrument is a panel mount device protected in
accordance with EN 61010-1:2001, electrical safety
requirements for electrical equipment for measurement, control
and laboratory. Remember that the unit has no power-on
switch. Building installation should include a switch or circuitbreaker that must be compliant to IEC 947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on
the top of the instrument housing.
• Always disconnect power before changing signal and
power connections.
• Do not use this instrument on a work bench without
its case for safety reasons.
• Do not operate this instrument in flammable or
explosive atmospheres.
• Do not expose this instrument to rain or moisture.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the
instrument if EMC problems persist.
MOUNTING
Panel Mounting Instruction:
1. Using the dimensions from the panel cutout diagram
shown above, cut an opening in the panel.
2. Remove sleeve from the rear of the case by removing
thumbnuts.
3. Insert the unit into the opening from the front of the panel,
so the gasket seals between the bezel and the front of the
panel.
4. Slip the sleeve over the rear of the case.
5. Tighten the thumbnuts to hold the unit firmly in the panel.
START HERE
Connect the main power connections in the figure shown below.
FUSE Connector Output Type For 115Vac For 230Vac DC
FUSE 1 Output 1 Relay 3 A(T) 3 A(T) -
FUSE 2 Output 2 Relay 3 A(T) 3 A(T) FUSE 3 Power N/A 100 mA(T) 100 mA(T) 100 mA(T)
FUSE 4 Power N/A N/A N/A 400 mA(T)
CONFIGURATION
Button Functions in Configuration Mode
• To enter the Menu, the user must first press
a
button.
• Use this button to advance/navigate to the next
menu item. The user can navigate through all the
top level menus by pressing a.
• While a parameter is being modified, press ato
escape without saving the parameter.
• Press the up bbutton to scroll through “flashing”
selections. When a numerical value is displayed
press this key to increase value of a parameter
that is currently being modified.
• Holding the bbutton down for approximately
3 seconds will speed up the rate at which the
setpoint value is incremented.
• In the Run Mode pressing bcauses the display
to flash the PEAK or GROSS value – press again
to return to the Run Mode.
• Press the down cbutton to go back to a previous
Top Level Menu item.
• Press this button twice to reset the controller to
the Run Mode.
• When a numerical value is flashing (except
setpoint value) press cto scroll digits from left to
right allowing the user to select the desired digit to
modify.
• When a setpoint value is displayed press cto
decrease value of a setpoint that is currently being
modified. Holding the cbutton down for
approximately 3 seconds will speed up the rate at
which the setpoint value is decremented.
• In the Run Mode pressing ccauses the display
to flash TARE value to tare your reading (zeroing).
• Press the enter dbutton to access the submenus
from a Top Level Menu item.
• Press dto store a submenu selection or after
entering a value — the display will flash a
STRD
message to confirm your selection.
• To reset flashing PEAK or GROSS press d.
• In the Run Mode, press dtwice to enable
Standby Mode with flashing
STBY
.
a
d
c
b
PK/GRS
(UP)
MENU
TARE
(DOWN)
ENTER
Reset: Except for Alarms, modifying any settings of
the menu configuration will reset the controller prior
to resuming Run Mode.
DISPLAY ABBREVIATIONS
SP1 Set Point 1 Value SP2 Set Point 2 Value
CNFG Configuration Menu INPt
INPt Input Type (range) 0 - 0.1 100 mV Input
Voltage
0 - 1.0 1 V Input Voltage 0 - 10 10 V Input Voltage
0 - 20 20 mA Input Current
Rtio Ratiometric Operation RESO Display Resolution
bUtN Button Peak/Gross PEAk Peak Value
GROS Gross Value
RdG Reading Configuration
dEC Decimal Point F.FFF Decimal Point
..FFFF Position
LOAd Input Load EnbL Scaling with Known
Loads (Actual Value)
DSbL Scaling without Known L.PNt
Linearization Points
Loads (Calculated Value)
0002..
Number of Linearization
FLtR Filter Constant
..0010 Points
0001.. Filter Constant Value IN.Rd
Input/Reading Scale
..0128 and Offset Menu
IN 1 Input 1 Rd 1 Reading 1
IN 2 Input 2 Rd 2 Reading 2
. . . . . . . . . . . . . . . . . . . .
IN 10 Input 10 Rd 10 Reading 10
ALR1 Alarm 1 Menu AbSo Absolute Mode
_dEV Deviation Mode LtcH Latched Mode
UNLt Unlatched Mode Ct.CL Contact Closure
N.o. Normally Open N.c. Normally Closed
ActV Active Type AboV Active Above
bELo Active Below Hi.Lo Above High/Below
Low
bANd Above or Below Band A.P.oN
Alarm
Enable/Disable
at Power On
ALR.L Alarm Low Value ALR.H Alarm High Value
ALR.2 Alarm 2 Menu
SP.dN Set Point Deviation
Id ID Code Menu CH.Id Change ID Code
FULL Full ID SP.Id Set Point ID
COMM Communication Option* NONE Communication is
Not Installed
C.PAR Communication bAUd Baud Rate
Parameters
PRtY Parity odd_ Odd
EVEN Even _No_ No
dAtA Data Bit 7.bit 7 Data Bit
8.bit 8 Data Bit StOP Stop Bit
1.bit 1 Data Bit 2.bit 2 Stop Bit
bus.F Bus Format M.bus Modbus Protocol
_LF_ Line Feed ECHO Echo
StNd Communication 232C RS-232
Standard
485_ RS-485 ModE Data Flow Mode
CMd_ Command Mode CoNt Continuous Mode
SEPR Data Separation SPCE Space
Character
_cR_ Carriage Return dAt.F Data Format
stAt Alarm Status RdNG Transmit Reading
Value
PEAk Transmit Peak Value GROS Transmit Gross
Value
UNit Units of Measurement AddR Multipoint Address
tR.tM
Transmit Color Selection
COLR Display Color Selection N.CLR
Normal Color Display
1.CLR Alarm 1 Color Display 2.CLR
Alarm 2 Color Display
REd Display Color is Red AMbR Display Color is
Amber
GRN Display Color is Green
dSbL Disable ENbL Enable
ERRO Error + OL Input (+) Overload