¼ DIN Temperature/Process
Limit Controllers
CN2504 Series
FM
APPROVED
U Dual Display
U Universal Input
U High/Low Limit
U Limit Relay Output (Fixed)
U Additional Modular Outputs (Optional)
U RS485 (Optional)
U Remote Reset (Optional)
The CN2504 Series is part of a range of new
generation series of limit controllers that incorporate
numerous product specification, communication,
display interface and software improvements that
surpass competitive limit device offerings in ease of
use and programming.
By adding more versatile features and user-friendly
functionality like digital inputs, an easy-to-use
HMI, jumperless and auto-hardware configuration,
24 Vdc transmitter power supply and MODBUS
communication across the range, the CN2504 limit
controller transform the complicated into the simple
while saving you time (as much as 50% on product
set-up), reducing inventory stock and virtually
eliminating the likelihood of operator errors.
The CN2504 limit controllers are affordable, wellfeatured, easy to use and adaptable with performance
features that work for you to make limit control simple.
The CN2504 is a fail-safe protection device to prevent
damage toequipment or products. It will shut down a
process when a preset temperature is reached and
cannot be reset by the operator until the process has
returned to a safe condition.
®
SPECIFICATIONS
Environmental Characteristics
Operating Temp: 0 to 55°C (32 to 131°F)
Storage Temp: -20 to 80°C (-4 to 176°F)
Humidity: 20 to 95% non-condensing RH
Electrical
Supply Voltage: 100 to 240V, 50/60 Hz, optional 20 to
48 Vac 50/60 Hz or 22 to 65 Vdc
Power Consumption: 5 W/7.5 VA maximum
Inputs
Thermocouples: J, T, K, L, N, B, R, S, C; Pt Rh 20%
vs. Pt 40% Rh
RTD: 3-wire, PT100 DC linear (scalable -1999 to +9999)
Volts: 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V
DC milliamps: 0 to 20 mA or 4 to 20 mA
DC millivolts: 0 to 50 mV, 10 to 50 mV
CN2504 shown smaller
than actual size.
Outputs
Output 1: (Limit relay) fixed
Outputs 2 and 3: (Alarm relay) are user-selectable and
customized based on desired application
Choose From the Following Output Types:
Max # of Outputs: 3 for alarm, 24 Vdc transmitter power
supply or retransmit of process value/limit trip setpoint
Limit Relay: SPDT; 240 Vac 5 A resistive; lifetime
>100,000 operations at rated voltage/current
Alarm Relay: Optional SPDT; 240 Vac 2A resistive;
lifetime >500,000 operations at rated voltage/current
SSR Drive (Optional Drive Capability): >10 Vdc nominal
into 500Ω minimum
DC Linear: Optional 0 to 20 mA, 4 to 20 mA into 500 Ω
maximum; 0 to 10V, 1 to 5V, 2 to 10V, 0 to 5V into 500Ω
minimum; outputs have 2% over/under drive applied;
accuracy ±0.25% (mA into 250 Ω load, V into 2k Ω load);
degrading linearity to ±0.5% for increasing burden to
specified limits
Triac: Optional 0.01 to 1A AC, 20 to 280 Vrms,
47 to 63 Hz (limit 2)
Transmitter Power Supply: Optional 24 Vdc (limit 1)
Output Functions
Process Alarm: (Reverse or direct)
Modes (Alarm 1 and 2): High/low, band, deviation, logical
OR/AND
P
P-1
Retransmit: Process value or limit setpoint
Electrical Performance
Accuracy: ±0.1% of input range ±1 LSD
(thermocouple CJC better than 1°C)
Input Sample Rate: 4 per second, 14-bit resolution
Impedance: >10M Ω for the thermocouple and mV ranges,
47k Ω for V ranges and 5 Ω for mA ranges
Sensor Break Detection: <2 seconds (except zero based
DC ranges), limit output opens, low alarms activate for RTD,
mA or V ranges
Communications Interface
User-Selectable: 2-wire, RS485 serial communications
option with choice of MODBUS RTU or ASCII protocol;
1200 to 19200 baud
PC Configuration: Offline configuration from serial port to
dedicated configuration socket (comms option not required)
Protection
IEC IP66 (NEMA 4X): Front panel
IEC IP20: Behind the panel protection
Dimensions
Panel Cutout: 92 W x 92 mm H (3.62 x 3.62")
Height: 96 mm (3.77")
Width: 96 mm (3.77")
Depth: 100 mm (3.94")
Weight: 0.21 kg (0.46 lb)
Mounting: Plug in panel with fixing strap
Input Type Range
-200 to 1373°C
(-328 to 1399°F)
0 to 761°C
(32 to 1401°F)
-200 to 262°C
(-328 to 503°F)
0 to 1399°C
(32 to 2550°F)
0 to 1650°C
(32 to 3002°F)
0 to 1649°C
(32 to 3000°F)
100 to 1824°C
(211 to 3315°F)
0 to 762°C
(32 to 1403°F)
0 to 2320°C
(32 to 4208°F)
Pt 100 RTD (0.00385)
(-328 to 1472°F)
-199 to 800°C
0 to 20 mA, 4 to 20 mA -1999 to 9999
0 to 10 Vdc, 0 to 5 Vdc,
0 to 50 mVdc
SM
OMEGACARESM extended warranty program is
available for models shown on this page. Ask
your sales representative for full details when
Extended Warranty
Program
placing an order. OMEGACARE
labor and equivalent loaners.
-1999 to 9999
SM
covers parts,
To Order Visit omega.com/cn2504 for Pricing and Details
Model No Description
CN2504-R1 Single output, relay
CN2516-R1-LV Single output, relay, low voltage
Output and Communications Options (Field Installable Modules)
Model No Description
Output 2 and 3 Slot
2500X-R Relay module
2500X-DC DC pulse module
2300X-F2 Linear DC module
2500X-T Triac module (output 2 only)
2300X-TPS Transmitter power supply (output 3 only)
Option A Slot
2300X-485 RS485 communications
2300X-DI Digital input
Accessories (Field Installable)
Model Number Description
CN2500-SOFT Configuration software
CNQUENCHARC Noise suppression kit, 110 to 230 Vac
Comes complete with mounting bracket and operator’s manual.
Ordering Example: CN2504-R1, single output controller.
OCW-2, OMEGACARESM extends standard 3-year warranty to a total of 5 years.
P