Nortel Networks BM450 User Manual

BCM450 Troubleshooting Guide
BCM450
Business Communications Manager
Document Status:Standard Document Number: NN40160-700 Document Version: 01.01 Date: August 2008
Copyright © 2008 Nortel Networks, All Rights Reserved
recommendations in this document are believed to be accurate and reliable, but are presented without express or implied warranty. Users must take full responsibility for their applications of any products specified in this document. The information in this document is proprietary to Nortel Networks.
Trademarks
Nortel, the Nortel logo, and the Globemark are trademarks of Nortel Networks. Microsoft, MS, MS-DOS, Windows, and Windows NT are trademarks of Microsoft Corporation. All other trademarks and registered trademarks are the property of their respective owners.

Task List

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Initial Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Hardware Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
To verify the keycodes using Element Manager..................... .......................................24
To verify the keycodes using Telset . ... ... .......................................................................25
To restart the system........... ... ... ... .... .............................................................................26
Viewing the POST log file..............................................................................................27
To test the main unit......................................................................................................29
To troubleshoot the main unit.................................... .... ... ... ... .... ...................................29
To test the expansion unit .............................................................................................29
To troubleshoot the expansion unit ........................................ .... ... ................................30
Testing an MBM ............................................................................................................30
Troubleshooting the FEM .................................................... ..........................................31
To determine why the ATA 2 does not function.............................................................31
To determine why there is no dial tone at the ATA2......................................................32
To check the ATA2 wiring..............................................................................................32
To perform a Level 1 reset (configuration reset) ........................... ... ... ... .... ...................34
To perform a Level 2 reset (software reset) .................................. ................................34
3
Software Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
To check line programming ...........................................................................................38
To restore data from an archive ............................................. .... ... ................................46
To restore the factory configuration...............................................................................47
To view the BCM450 software inventory.......................................................................48
To obtain updates from the Nortel Technical Supp or t Web pag e.................. ... ... .... ... ...49
Advanced Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Troubleshooting example 1 . ... ... ....................................................................................51
Troubleshooting example 2 . ... ... ....................................................................................53
Troubleshooting example 3a .. ... ... .... .............................................................................59
Troubleshooting example 3b .. ... ... .... .............................................................................59
Troubleshooting example 4 . ... ... ....................................................................................61
Troubleshooting example 5 . ... ... ....................................................................................62
Troubleshooting example 6 . ... ... ....................................................................................67
Troubleshooting example 7 . ... ... ....................................................................................67
Recovery trees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Downloading Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
To download software from the BCM450 webpage.......................................................76
Troubleshooting Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Accessing the CLI through a serial connection ............................. ... ... ... .... ... ................81
Accessing the CLI through the OAM port............................ ... .... ... ... .............................81
BCM450 Troubleshooting Guide
4 Task List
Understanding system messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
To set Release Reasons ...............................................................................................83
Useful Troubleshooting Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
To use the Knowledge and Solution Engine............................... ... ... ... ..........................86
Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
To perform a backup ................................................. .... ... ... ... .... ...................................87
To restore data from the BCM450 .................................................................................88
Completing a warm or cold reset...................................................................................89
Recovering a lost password ..........................................................................................89
To view an alarm .................... ... ... .... .............................................................................90
To acknowledge an alarm ................................................ ... ... .... ...................................91
Using the Element Manager to transfer log files............................................................91
Capturing the current configuration...............................................................................93
Viewing the system health.............................................................................................94
Viewing specific process states.....................................................................................94
Verify the current software revision...............................................................................95
Viewing the system ID and serial number .....................................................................95
Contacting Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
NN40160-700

Contents

Chapter 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Symbols and conventions used in this guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Related publications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2
Initial Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Proper installation and routine maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Network configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Site network map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Logical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Device configuration information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Other important data about your network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Normal behavior on your network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5
Chapter 3
Hardware Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Troubleshooting the BCM450 hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Check the power source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Check LED indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Check the wiring connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Verify the keycodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Restart or shut down the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Power on self test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Testing basic hardware functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Reset to factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Monitoring the boot process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Chapter 4
Software Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Verify the software version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Verify the keycodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
BCM450 Troubleshooting Guide
6 Contents
Check the programming of lines and phones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Restoring system data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Verify the software inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Chapter 5
Advanced Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Example 1: Cannot dial out from an analog trunk . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Example 2: Cannot dial out from a SIP or H323 VoIP trunk . . . . . . . . . . . . . . . . . . . . 53
Example 3: IP set is not registering with the BCM450 . . . . . . . . . . . . . . . . . . . . . . . . . 58
Example 4: Cannot install keycode or invalid keycode application . . . . . . . . . . . . . . . 60
Example 5: Cannot dial out from digital trunk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Example 6: MeetMe Conferencing commands do not work, or conferencing is busy . 66
Example 7: Unable to apply a software update from a USB storage device . . . . . . . . 67
Example 8: Element Manager incorrectly shows expansion cabinet as empty . . . . . . 68
Check line programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Trunk/Line data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Preferences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Assigned DNs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Viewing the inventory of BCM450 software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Obtaining software updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Chapter 6
Recovery trees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
System is not processing calls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Start-up profile fails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Cannot access BCM450 through Element Manager . . . . . . . . . . . . . . . . . . . . . . . . . . 71
BCM450 shuts down unexpectedly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Chapter 7
Downloading Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Downloading software from the BCM450 webpage . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Downloading software from the Nortel web site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Chapter 8
Troubleshooting Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Service Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Status and Metrics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
NN40160-700NN40160-700
Contents 7
Utilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Command Line Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Accessing the CLI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Using the Configuration CLI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Using the Maintenance CLI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Chapter 9
Understanding system messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Alarms, logs, and traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Reporting for dropped calls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Chapter 10
Useful Troubleshooting Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Partner Bulletins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Knowledge and Solution Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Using the Knowledge and Solution Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Chapter 11
Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Backup, restore, and reset operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
How do I back up the database? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
How do I restore the BCM450 from a previous backup? . . . . . . . . . . . . . . . . . . . 88
How do I complete a Warm Reset or Cold Reset? Is it safe and will I lose customer data? 88
Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
How do I recover a lost password for the BCM450? . . . . . . . . . . . . . . . . . . . . . . . 89
Fault management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
How do I view Alarms? Can I acknowledge and clear them? . . . . . . . . . . . . . . . . 90
System and status information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
How do I capture the logs from the BCM450? . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
How do I capture the current BCM450 configuration? . . . . . . . . . . . . . . . . . . . . . 93
How do I find the BCM450 system health? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
How do I show specific process states? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
How do I verify current software revision? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
How do find the BCM450 System ID and Serial Number? . . . . . . . . . . . . . . . . . . 95
Connectivity problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
What is an Ethernet loop, and how do I avoid creating one? . . . . . . . . . . . . . . . . 96
IP addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Can I modify the IP address of the OAM port? . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
What are the default IP addresses of the BCM450 ports? . . . . . . . . . . . . . . . . . . 96
BCM450 Troubleshooting Guide
8 Contents
Chapter 12
Contacting Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Gathering critical information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Getting Help from the Nortel Web site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Getting help over the phone from a Nortel Solutions Center . . . . . . . . . . . . . . . . . . . 100
Getting help from a specialist by using an Express Routing Code . . . . . . . . . . . . . . 101
Getting help through a Nortel distributor or reseller . . . . . . . . . . . . . . . . . . . . . . . . . . 101
NN40160-700NN40160-700
Chapter 1

Introduction

The Nortel Business Communications Manager 450 (BCM450) provides private network and telephony management capability to small and medium-sized businesses. The BCM450 system integrates voice and data capabilities, and IP Telephony gateway functions into a single telephony system. It also enables you to create and provide telephony applications for use in a business environment.

Purpose

This guide provides procedural information to help you troubleshoot and isolate problems in your BCM450 network.

Audience

9
The BCM450 Troubleshooting Guide is for use by network administrators responsible for maintaining BCM networks that include BCM450 devices. This guide is also useful for network operations center (NOC) personnel supporting a BCM450 managed services solution. To use this guide, you must:
be an authorized BCM450 administrator within your organization
know basic Nortel BCM450 terminology
be knowledgeable about telephony and IP networking technology

Organization

This guide is organized for easy access to information that explains the troubleshooting procedures associated with using the BCM450 system. This guide contains information on the following topics:
Initial Troubleshooting on page 15
Hardware Troubleshooting on page 19
Software Troubleshooting on page 37
Advanced Troubleshooting on page 51
Recovery trees on page 69
Downloading Software on page 75
Troubleshooting Tools on page 79
Understanding system messages on page 83
Useful Troubleshooting Links on page 85
Frequently Asked Questions on page 87
BCM450 Troubleshooting Guide
10 Chapter 1 Introduction
Contacting Technical Support on page 99

Acronyms

The following is a list of acronyms used in this guide.
Table 1 List of acronyms
Acronym Description
AIS Alarm Indication Signal BCM Business Communications Manager BFT Base Function Tray BRI Basic Rate Interface CbC Call by Call CDR Call Detail Recording CF A Carrier Failure Alarms CIF Chassis Interface Card CLID Calling Line Identification CPE Customer Premises Equipment CSU Channel Service Unit DHCP Dynamic Host Configuration Protocol DN Directory Number DNS Domain Name Server DNIS Dialed Number Idenification Service DTM Digital Trunk Module ES Errored Seconds HTTP Hypertext Transfer Protocol IP Internet Protocol ISDN Integrated Switched Digital Network LAN Local Area Network MBM Media Bay Module MIB Management Information Base MGS Media Gateway Server MOS Mean Opinion Score MPS Media Path Server NAT Network Address Translation NCM Network Configuration Manager NOC Network Operations Center NTP Network Time Protocol
NN40160-700NN40160-700
Table 1 List of acronyms
Acronym Description
OOF Out of Frame PPP Point-to-Point Protocol PRI Primary Rate Interface PBX Private Branch Exchange PSTN Public Switched Telephone Network PVQM Proactive Voice Quality Monitoring QoS Quality of Service RAI Remote Alarm Indication RTP Real-time Transport Protocol SFTP Secure File Transfer Protocol SNMP Simple Network Management Protocol SSH Secure Shell SSL Secure Socket Layer UAS Unavailable Seconds UPS Uninterrr uptable Power Supply USB Universal Serial Bus VoIP V o i c e over Internet Protocol VLAN Virtual Local Area Network WAN Wide Area Network
Chapter 1 Introduction 11
BCM450 Troubleshooting Guide
12 Chapter 1 Introduction
!

Symbols and conventions used in this guide

These symbols are used to highlight critical information for the BCM450 system:
Caution: Alerts you to conditions where you can damage the equipment.
Danger: Alerts you to conditions where you can get an electrical shock.
Warning: Alerts you to conditions where you can cause the system to fail or work
improperly.
Note: A Note alerts you to important information.
Tip: Alerts you to additional information that can help you perform a task.
Security note: Indicates a point of system security where a default should be changed,
or where the administrator needs to make a decision about the level of security required for the system.
Warning: Alerts you to ground yourself with an antistatic grounding strap before performing the maintenance procedure.
Warning: Alerts you to remove the BCM450 main unit and expansion unit power cords from the ac outlet before performing any maintenance procedure.
NN40160-700NN40160-700

Related publications

Related publications are listed below. To locate specific information, you can refer to the
Master Index of BCM450 Library (NN40020-100).
BCM450 Administration and Security Guide (NN40160-601) BCM450 Installation Guide—System (NN40160-301) BCM450 Maintenance Guide (NN40160-503) Keycode Installation Guide (NN40010-301) BCM450 Configuration Guide—Devices (NN40160-500) BCM450 Configuration Guide—System (NN40160-501) BCM450 Telset Administration Guide (NN40020-604) CallPilot Telephone Administration Guide (NN40090-500) CallPilot Contact Center Telephone Administration Guide (NN40040-600) Reporting for Contact Center Troubleshooting
Chapter 1 Introduction 13
BCM450 Troubleshooting Guide
14 Chapter 1 Introduction
NN40160-700NN40160-700
Chapter 2

Initial Troubleshooting

You can better troubleshoot the problems on your network and reduce their impact by preparing for such events in advance. To do this, you must know the following:
that your system is properly installed and routinely maintained
the configuration of your network
the normal behavior of your network

Navigation

Proper installation and routine maintenance on page 15
Network configuration on page 15
Normal behavior on your network on page 16
15

Proper installation and routine maintenance

See the BCM450 Installation Guide—System (NN40160-301) for detailed installation information. This document also outlines the routine tasks required for operating the BCM450.

Network configuration

To keep track of your network’s configuration, gather the information described in the following sections. This information, when kept up-to-date, is extremely helpful when you experience network or device problems.
Site network map on page 15
Logical connections on page 16
Device configuration information on page 16
Other important data about your network on page 16

Site network map

A site network map identifies where each device is physically located on your site, which helps locate the users and applications that are affected by a problem. You can use the site network map to systematically search each part of your network for problems.
BCM450 Troubleshooting Guide
16 Chapter 2 Initial Troubleshooting

Logical connections

You must know how your devices are connected logically as well as physically. For example, while virtual LANs (VLANs) are not supported on the BCM450 system, VLANs may exist between IP sets connected to the BCM450.

Device configuration information

You should maintain online and paper copies of your device configuration information. Ensure that all online data is stored with your site’s regular data backup. If your site does not have a backup system, copy the information onto a backup disk (such as a CD or zip disk) and store the backup disk at an offsite location.

Other important data about your network

For a complete picture of your network, have the following information available:
All passwords—Store passwords in a safe place. It is a good practice to keep records of your
previous passwords in case you must restore a device to a previous software version and need
to use the old password that was valid for that version.
Device inventory—It is a good practice to maintain a device inventory, which list all devices
and relevant information for your network. The inventory allows you to easily see the device
type, IP address, ports, MAC addresses, and attached devices.
MAC address-to-port number list—If your hubs or switches are not managed, you must
keep a list of the MAC addresses that correlate to the ports on your hubs and switches.
Change control—Maintain a change control system for all critical systems. Permanently store
change control records.
Contact details—It is a good practice to store the details of all support contracts, support
numbers, engineer details, and telephone and fax numbers. Having this information available
when troubleshooting can save a lot to time.

Normal behavior on your network

When you are familiar with the performance of your network when it is fully operational, you can be more effective at troubleshooting problems that arise. To understand the normal behavior of your network, monitor your network over a long period of time. During this time you can see a pattern in the traffic flow, such as which devices are typically accessed or when peak usage times occur.
To identify problems, you can use a baseline analysis, which is an important indicator of overall network health. A baseline serves as a useful reference of network traffic during normal operation, which you can then compare to captured network traffic while you troubleshoot network problems. A baseline analysis speeds the process of isolating network problems. By running tests on a healthy network, you compile normal data for your network. This normal data can then be
NN40160-700NN40160-700
Chapter 2 Initial Troubleshooting 17
used to compare against the results that you get when your network is experiencing trouble. For example, ping each node to discover how long it typically takes to receive a response from devices on your network. Capture and save each device’s response time and when yo u are troubleshooting you can use these baseline response times to help you troubleshoot.
BCM450 Troubleshooting Guide
18 Chapter 2 Initial Troubleshooting
NN40160-700NN40160-700
Chapter 3

Hardware Troubleshooting

Use the tasks in this chapter to troubleshoot problems related to the BCM450 hardware components.

Navigation

Troubleshooting the BCM450 hardware on page 19
Power on self test on page 27
Testing basic hardware functionality on page 28
Monitoring the boot process on page 34

Troubleshooting the BCM450 hardware

19
Complete the following tasks, in the order shown below, to troubleshoot some of the common problems that you may encounter with the BCM450 hardware:
Check the power source on page 19
Check LED indicators on page 19
Check the wiring connections on page 24
Verify the keycodes on page 24
Restart or shut down the system on page 25

Check the power source

Begin troubleshooting the hardware by checking the power source:
check the connection between the power supply and the main unit
check the connection from the power supply to the electrical outlet

Check LED indicators

After checking the power source, check the LED indicators. This section describes the operation of the BCM450 system LEDs:
System status LEDs on page 20
LAN port LEDs on page 21
Media bay module LEDs (expansion units only) on page 21
DTM LEDs on page 22
BRIM LEDs on page 24
BCM450 Troubleshooting Guide
20 Chapter 3 Hardware Troubleshooting
System status LEDs
The chassis of the BCM450 contains two LEDs: a Status LED and a Power LED. The Power LED is located at the bottom left of the chassis; the Status LED is immediately above it. The table
System status LEDs states and descriptions on page 20 describes the meaning of the system status
LEDs in the following situations:
start-up sequence: LED indicators during the normal start-up process
safe-mode start-up sequence: LED indicators during a safe-mode start-up
shutdown sequence: LED indictors during a shutdown or failure
start-up profile sequence: LED indicators during an initial installation or staging
Table 1 System status LEDs states and descriptions
Power
Start-up sequence
Solid yellow Solid yellow Power applied to the system. Solid yellow Off Powe r on self test (POST); 9 seconds. Solid yellow Solid yellow System initialization; 14 seconds. Solid green Solid yellow Kernel initialization; 8 seconds. Solid green Flashing green Services initialization; 1 minute. Solid green Solid green System running; normal operation. Solid green Solid red Services initialization failure
Safe mode start-up sequence
Solid red Solid green System running with manufacturing settings enabled Solid red Solid red System running in software reset mode Sold red Flashing yellow System running in configuration reset mode
Shutdown sequence or failure
Solid green Flashing yellow Shutdown in progress Off Solid yellow Shutdown completed Solid red Flashing yellow Overheating detected; thermal shutdown completed Solid red Solid red Power spike or rail pow er fluctuation detected Flashing red Solid red Rail power fluctuation; power monitor shutdown completed Solid yellow Solid red Power spike shutdo wn completed Off Off No power; system is shut down
Start-up profile sequence
Flashing yellow Flashing yellow Start-up profile executing Flashing green Flashing green Start-up profile completed (USB device can be removed) Solid green Solid green Start-up profile successfully applied Solid green Solid red Start-up profile failure
Status
Description
NN40160-700NN40160-700
Chapter 3 Hardware Troubleshooting 21
LAN port
LAN port LEDs
LAN port
LAN port LEDs
Each LAN port on the main unit and expansion unit has two LEDs. These LEDs indicate the status of the connection for that LAN port. The figure LAN port LED locations on page 21 shows the location of these LEDs on the main unit.
Figure 1 LAN port LED locations
The table LAN port and expansion port LED indicators on page 21 describes the possible LED states for the LAN ports LEDs.
Table 2 LAN port and expansion port LED indicators
LED Status Description
Yellow (left LED)
Green (right LED)
Both LEDs Off No connection. Any LED Flashing The LAN port is sending or receiving network data. The frequency of the flashes
On
On
The LAN port is operating at 10 Mb/s.
The LAN port is operating at 100 Mb/s.
increases with increased traffic.
Media bay module LEDs (expansion units only)
The two media bay module (MBM) LEDs on an expansion unit show the power and status of the MBM. The figure MBM LEDs on page 22 shows the location of the LEDs on an MBM. The power and status LEDs are in the same location on all MBMs.
(Power) and (Status)
BCM450 Troubleshooting Guide
22 Chapter 3 Hardware Troubleshooting
Power Status
Figure 2 MBM LEDs
The table MBM LED descriptions on page 22 describes the possible MBM LED states.
Table 3 MBM LED descriptions
Power Status Description
Off Off The MBM has no power, or a failure occurred on the MBM power converter. On Off BCM450 to expansion unit failure or system initialization. On Blinking Hardware is working, but an operational problem exists such as:
no link to the main unit is detected
frame alignment is lost on messages from the main unit
bandwidth not allocated
MBM is in maintenance state
MBM is in download state (GASM, GATM4/GATM8)
Blinking Blinking The MBM has power, but a hardware problem exists such as:
partial failure of power con verter
thermal overload
fan failure
On On The MBM is ready to operate.
DTM LEDs
The DTM has additional LEDs that are not on most other MBMs. The figure DTM LEDs on page 23 shows the location of the DTM LEDs.
NN40160-700NN40160-700
Chapter 3 Hardware Troubleshooting 23
Power LED Status LED In service LED Loopback test LED Receive LEDs Transmit LEDs
Figure 3 DTM LEDs
The table DTM LED functions on page 23 describes the functions of the DTM LEDs.
Table 4 DTM LED functions
LED Status Descriptions
Power See “Media bay module LEDs (expansion units only)” for details. Status See “Media bay module LEDs (expansion units only)” for details. In service Flashing The T1, ETSI, or PRI trunks are out of service because a loopback test is
running or the DTM is initializing. Loopback test On A continuity loopback test is running. Receive alarm On A problem with the received digital transmission. This half-duplex link does
not work. Receive error On A small error as a result of degraded digital transmission. Possible causes are
an ohmic connection, water ingress, or too long a loop. Transmit alarm On The DTM cannot transmit. The DTM sends an alarm indication signal (AIS) to
Transmit error On The DTM is sending a remote alarm indication (RAI) carrier failure alarm
All LEDS Flashing The DTM is initializing.
the terminating switch. This half-duplex link does not work.
(CFA) to the terminating switch. If the transmit alarm is not on, this error
indicates a far-end or cable problem.
BCM450 Troubleshooting Guide
24 Chapter 3 Hardware Troubleshooting
Power LED Status LED
BRIM LEDs
The BRIM has one additional LED beside each RJ-48C jack. These LEDs are on when the ISDN line is active. The figure BRIM LEDs on page 24 shows the location of the LEDs on a BRIM.
Figure 4 BRIM LEDs
For more information on the power and status LED functions, see Media bay module LEDs
(expansion units only) on page 21.

Check the wiring connections

After you check the power source and the LEDs, begin to check the wiring. Check the connections between the following components:
the expansion unit and the main unit
the main unit and to the MBMs—make sure that the cables are properly seated and are connected to the correct ports
the power supply and the AC power outlet
if you are using a UPS, check the connection from:
— the USB port on the BCM450 to the USB port on the UPC — the UPS and the electrical outlet — the connection from the power supply to both the UPS and the BCM450 main unit
the lines and extensions connected through the RJ-21 telephony connector
the auxiliary equipment—connections at the auxiliary terminal block, or at the patch panel

Verify the keycodes

If a specific feature is not functioning, verify that the feature is included in your installed keycodes. This section provides procedure for verifying the installed keycodes using either Element Manager or Telset. For more detailed information about retrieving and entering the keycode for your system, see the Keycode Installation Guide (NN40010-301).
To verify the keycodes using Element Manager
1 In the Task Navigation Panel, select the Configuration tab.
NN40160-700NN40160-700
Chapter 3 Hardware Troubleshooting 25
2 Select the System folder and click the Keycodes task.
The Keycodes panel displays and the installed features appear in the Keycodes list.
3 To enter a new keycode, click Load File. 4 Browse to where you saved the keycode file you downloaded from KRS. 5 Click Open.
The file uploads and the feature appears in the Keycodes list.
To verify the keycodes using Telset
1 Select Feature 9*8 from a two-line display telephone. 2 Enter the following user ID and password:
User ID: SETNNA Password: CONFIG
The numerical values of the user ID and password are 738662 and 266344, respectively.
3 Press NEXT to scroll through the menu and select Feature Codes. 4 Press OK.
The system ID (SID) displays.
5 Press NEXT. 6 Enter your sequence ID. 7 Press NEXT to scroll through the list and perform one or both of the following tasks:
a To activate features, select Feature List.
Press SHOW to view the available features.
Use the soft keys to activate features for your system. b To enter a new keycode, select Entitlement Code.
Press SHOW to view the current keycode.
Use the soft keys to modify the keycode for your system.

Restart or shut down the system

You can use the Reset utility in Element Manager to:
reboot the BCM450 system
perform a warm reset of telephony services
perform a cold reset of telephony services
shut down the system
Use this procedure to restart the system.
BCM450 Troubleshooting Guide
26 Chapter 3 Hardware Troubleshooting
To restart the system
Use this procedure to restart the system from the Element Manager.
1 Select Administration > Utilities > Reset. 2 Click the appropriate reset button.
Table 5 lists the Reset functions.
Table 5 Reset functions
Function Description Impact
Reboot BCM450 System Restarts the operating system of the
BCM450 system
Warm Reset Telephony Services
Cold Reset Telephony Services
Shutdown BCM System Shuts down the BCM450. Stops all services running on the
Restarts telephony services running on the BCM450 system
Resets telephony programming of the BCM450 system to the factory defaults for that software level
Temporarily stops all services on the system. Restarts all services.
This operation does not affect configuration parameters or programming.
Restarts all telephony services, including LAN CTE, Voicemail, and IP telephony.
This operation does not affect configuration parameters or programming.
Affects all telephony services, including LAN CTE, Voicemail, and IP telephony.
Telepho ny services restart with all telephony programming at default values for the specified region, template, and start DN, for the current software release level.
A cold reset erases voice message mailboxes and messages if the DN length is not set to system defaults. For information about setting the DN length, refer to the BCM450 Device Configuration Guide.
system.
NN40160-700NN40160-700
Chapter 3 Hardware Troubleshooting 27
To restart the system from the BCM450 hardware, use the reset button as described in Hardware
reset functions on page 27.
Table 6 Hardware reset functions
Function Description Impact
Press the Reset button on the BCM450 system
Press and hold the Reset button on the BCM450 system for 5 seconds
Shuts down and reboots the BCM450 system
Immediately shuts down the BCM450 system
Stops all services and restarts the system.
This operation does not affect configuration parameters or programming.
Immediately stops and restarts the operating system. This operation does not affect configuration parameters or programming, but can result in data loss. Use only if the BCM450 system is non-responsive.
Note: When you restart the BCM450 system using the Reset button, the system will wait for 10 seconds for a user to log into the Maintenance CLI. If a user does not log in during that time period, the BCM450 will reboot to the Main OS.

Power on self test

The power on self test (POST) feature tests basic hardware functionality when the BCM450 system powers up, and stores the results in a log file. You can view the log file for hardware failures.
Viewing the POST log file
1 Use Element Manager to transfer the log files to your PC. Refer to the “BCM450 Log
management” chapter in the BCM450 Administration and Security Guide (NN40160-601) for information about how to transfer log files.
2 View the bootloader.log file. 3 Check the log file for errors. Figure 5 on page 28 shows a bootloader. l og file with no errors;
Figure 6 on page 28 shows a file with errors.
BCM450 Troubleshooting Guide
28 Chapter 3 Hardware Troubleshooting
Figure 5 Example: Bootloader.log file with no errors
Figure 6 Example: Boot file with errors

Testing basic hardware functionality

This section describes how to test the components of the BCM450 system, and how to troubleshoot them if they fail the test.
Use the following procedures to help isolate and identify problems with your BCM450 hardware:
To test the main unit on page 29
To troubleshoot the main unit on page 29
To test the expansion unit on page 29
To troubleshoot the expansion unit on page 30
Testing an MBM on page 30
Troubleshooting the FEM on page 31
To determine why the AT A 2 does not function on page 31
To determine why there is no dial tone at the ATA2 on page 32
To check the ATA2 wiring on page 32
Reset to factory settings on page 32
To perform a Level 1 reset (configuration reset) on page 34
NN40160-700NN40160-700
Chapter 3 Hardware Troubleshooting 29
To test the main unit
If you have the digital station feature included in your installed keycode, use the following test to ensure the main unit is operating properly:
1 Go to an extension that is connected to the RJ-21 telephony connector on the main unit. 2 Check for a dial tone. 3 Use this extension to make a call to another extension on the system. 4 If this system has an expansion unit with a media bay module (MBM) that supports
extensions, repeat steps 3 and 4 for an extension connected to the expansion unit.
5 Go to an extension that has access to one of the lines on the main unit. 6 Select the line or line pool to which the line belongs. 7 Check for a dial tone. 8 Make a call using the line or line pool. 9 If this system has an expansion unit with an MBM that supports lines, repeat steps 6 to 8 with
an extension that can access one of the lines connected to the expansion unit.
To troubleshoot the main unit
If a test fails, use the following procedure:
1 Verify that any nonfunctional feature is included in your installed keycode. 2 Check the wiring to the main unit and to the MBMs. Make sure that the cables are properly
seated and are connected to the correct ports.
3 Reboot the BCM450 system. 4 Check LEDs. 5 Use Element Manager or the Telset Administration feature to check the programming for the
lines or extensions that failed the call test.
6 If the programming is incorrect, use the Backup and Restore Utility to load a recent backup of
system programming. If a recent backup is not available, correct the programming using Element Manager or the Telephone Administration feature.
To test the expansion unit
Use the following test to ensure the expansion unit is operating properly:
1 Make sure that the BCM450 system is fully booted. 2 Check the power and status LEDs on the MBM that is inserted in the expansion unit. Both
LEDs must be solid green. If either LED is not solid green, a problem exists with the MBM or the expansion unit.
3 If the expansion unit has an MBM that supports extensions, go to an extension that is
connected to the MBM.
BCM450 Troubleshooting Guide
30 Chapter 3 Hardware Troubleshooting
4 Check for a dial tone. 5 Use this extension to make a call to another extension on the system. 6 If the expansion unit has an MBM that supports lines, go to an extension that has access to one
of the lines on the MBM.
7 Select the line or line pool to which the line belongs. 8 Check for a dial tone. 9 Make a call using the line or line pool.
To troubleshoot the expansion unit
1 Check that the correct feature for the expansion unit is included in your installed keycode. 2 Check that the expansion port is connected to the proper connector. 3 Check the wiring to the MBM. Make sure that the cables are properly seated and are connected
to the correct ports with proper LED indications.
4 Check that the switches on the MBM are all set to on.
If the MBM is a GASM or GATM, all the switches on the right are not on. To check the MBM switches, you must remove the MBM from the expansion unit.
5 Perform a firmware download to ensure that the correct version is loaded on the ASM/GASM
or GATM unit.
6 Use Element Manager or Telset Admin to check the programming for the lines or extensions
connected to the MBM.
7 Reboot the system to ensure that the BCM450 main unit functions correctly. 8 If the programming is incorrect, use the Backup and Restore Utility to load a recent backup of
system programming. If a recent backup is not available, correct the programming using Element Manager or the Telephone Administration feature.
Testing an MBM
Use the following procedure to test an MBM installed in the main unit or expansion cabinet.
If you are ex periencing an issue with an FEM, ensure all DIP switches ar e set to the On position.
Procedure steps
Step Action
1 Check the Power and Status LEDs on the MBM. Both LEDs must be solid
green. If either LED is not solid green, a problem exists with the MBM.
NN40160-700NN40160-700
2 Go to an extension on the MBM if it is a station MBM.
OR
Chapter 3 Hardware Troubleshooting 31
Go to an extension that has access to one of the lines on the MBM if it is a trunk MBM. Select the line or line pool to which the line belongs.
3 Check for a dial tone. 4 Use this extension to make a call to another extension on the system if it is a
station MBM.
OR
Make a call using the line or line pool if it is a trunk MBM.
5 Use this extension to make a call to an external telephone number if you are
testing a station MBM.
--End--
Determining why an MBM does not appear in Element Manager
Use the following procedure if an installed MBM does not appear in Element Manager.
Procedure steps
Step Action
1 Check that the correct feature is inclueded in your installed keycode. 2 Check that both the Power and Status LEDs on the MBM are solid gr een. 3 If the Power LED is off, and the MBM is installed in the expansion cabinet,
check that the po wer sup ply cab le is p roperly seated in the e xpa nsion cabinet and the power supply is connected to a working power outlet.
4 Ensure that the MBM is properly seated in the MBM bay. 5 If the Status LED is not solid gree n, and the MBM is inst alled in the e xp ansion
cabinet, check that the Expansion cable is properly seated in the Expansion port on the expansion cabinet and on the main unit.
6 Ensure that the MBM is enabled using either Element Manager or Telset
Administration. If the MBM is enabled, disable and re-enable it.
7 Ensure that all DIP switches are set correctly.
--End--
Troubleshooting the FEM
Use the following procedure to troubleshoot an installed fibre expansion module (FEM).
1 Ensure that all six connector LEDs are lit. 2 If all six LEDs are not lit, ensure that all six DIP switches are set to the On (up) position.
--End--
To determine why the ATA 2 does not function
1 Check for a dial tone using an analog device. 2 Check that AC power is connected to the ATA 2 unit.
BCM450 Troubleshooting Guide
32 Chapter 3 Hardware Troubleshooting
3 Check that the correct feature for digital sets is included in your installed keycode. 4 Verify that the ATA2 is connected to a digital station port. 5 Allow sufficient startup time (30–60 sec). 6 Plug an analog device into the phone port of the ATA2 and check for a dial-tone. 7 In Element Manager, verify that the ATA 2 is correctly configured:
a Select Configuration > Telephony > Sets > All DNs. b Select the appropriate DN from the list and click the ATA settings tab.
The options for the Device Type are Modem or Telephone.
To determine why there is no dial tone at the ATA2
1 If you hear no dial tone, replace a single-line telephone for the data communication device. 2 If you hear no dial tone at the ATA2 unit:
a Disconnect the line side of the ATA2. Connect a digital telephone to the ATA2 port. b Check that the connection from the ATA2 to the BCM450 hardware works correctly.
To check the ATA2 wiring
1 Use an analog phone to test the ATA2. 2 Check the following connections:
a ATA 2 to the terminal
The resistance must be 200 ohms or less for data applications and 1300 ohms or less for voice applications.
b BCM450 hardware to the ATA2
The wiring must be equivalent to 800 m of 0.5 mm wire (2600 ft. of 24-AWG) or less. Do not use bridge taps and loading coils between the BCM450 hardware an d ATA2.

Reset to factory settings

This section describes how to reset the BCM450 system to the factory settings or a stable working condition using the reset switch (see the figure Reset switch location on page 33). When the BCM450 is in this condition, you can make further modifications.
NN40160-700NN40160-700
Chapter 3 Hardware Troubleshooting 33
Reset button
Figure 7 Reset switch location
Some possible situations in which you use the reset feature are:
If the BCM450 system is configured incorrectly to an extent that it is no longer functional. The customer must use a level 1 reset to return to the default system programming and restore a previous configuration or reconfigure the system.
If distributors want to reuse BCM450 systems, they must first erase all customer-specific data using a level 1 or level 2 reset.
Reset levels
Reset to factory settings is a stand-alone feature that has the following levels of reset:
Level 1 reset erases all customer-specific data and restores the default configuration for all components. This reset leaves the software componen ts untouched. That is, the system has th e latest release and patch level of the softwa re installed. Only the system and user configuration data is erased and replaced with default values.
Level 2 reset erases all customer and system configuration data and all software releases and patches. This reset re-installs the original factory configuration settings.
Warning: If you perform a Level 2 reset to solve an undetermined problem and still have access to Element Manager, you must retrieve all the log files for technical support before performing the Level 2 reset. A Level 2 reset erases all log files from the system.
BCM450 Troubleshooting Guide
34 Chapter 3 Hardware Troubleshooting
Activate the reset feature
You activate the reset feature through the Maintenance CLI or the Configuration CLI. When you initiate a reset from the CLI menu, no further action is needed to complete the reset. You can monitor the progress of the reset by observing the LED states, or through the serial connection.It is important that you wait for the system to complete the reset before taking any further action; do not interrupt the reset process.
Warning: Before performing a Level 1 or Level 2 reset, review all the effects of the levels of reset. See Reset levels on page 33.
To perform a Level 1 reset (configuration reset)
1 Access the CLI. For information about how to access the CLI, refer to Command Line
Interface on page 80.
2 From the Configuration CLI, select option 4—Configuration Reset. If you are using the
Maintenance CLI ,select option 5—Configuration Reset.
3 The LEDs will progress through the start-up and shut down sequence. This process may take
more than 2 minutes.
4 A Staus LED that is flashing yellow, and a Power LED that is solid red, indicates that a
configuration reset is in progress. This process may take more than 2 minutes.
5 The system reboots to the Main OS. This process may take more than 2 minutes.
To perform a Level 2 reset (software reset)
1 Access the CLI. For information about how to access the CLI, refer to Command Line
Interface on page 80.
2 From the Configuration CLI, select option 5—Software Reset. If you are using the
Maintenance CLI ,select option 6—Software Reset.
3 The LEDs will progress through the start-up and shut down sequence. This process may take
more than 2 minutes.
4 A Staus LED that is flashing yellow, and a Power LED that is solid red, indicates that a
software reset is in progress. This process may take more than 5 minutes.
5 The system reboots to the Main OS. This process may take more than 2 minutes.

Monitoring the boot process

1 Connect a serial cable with a 9-pin female connector from the serial port on a PC to the serial
port on the BCM450.
2 Ensure that you use the following settings:
bits per second: 115200
NN40160-700NN40160-700
Chapter 3 Hardware Troubleshooting 35
data bits: 8
•parity: N
stop bits: 1
no flow control
3 Use a terminal emulation program, such as Hyperterminal or Nortel CLI Manager, to establish
a connection to the BCM450.
4 Reboot the system and observe the boot pro cess. Figure 8 shows an example of a boot process
when there is failed or missing memory; Figure 9 shows an example of a boot process when there is a failed or missing hard drive.
5 If the system starts normally, the CLI login prompt displays when the boot cycle is complete.
BCM450 Troubleshooting Guide
36 Chapter 3 Hardware Troubleshooting
Figure 8 Boot process with failed or missing memory
Figure 9 Boot process with failed or missing hard drive
NN40160-700NN40160-700
Chapter 4

Software Troubleshooting

Use the information in this chapter to troubleshoot problems related to the BCM450 software components.

Navigation

Complete the following tasks, in the order shown below, to troubleshoot some of the common problems that you may encounter with the BCM450 software:
Verify the software version on page 37
Verify the keycodes on page 37
Check the programming of lines and phones on page 37
Restoring system data on page 46
Verify the software inventory on page 48
37

Verify the software version

In the Element Manager, select Help > About. A panel displays and provides information about the Element Manager, such as the Release level.

Verify the keycodes

If a specific feature is not functioning, verify that the feature is included in your installed keycodes. For information about how to verify the installed keycodes, see Verify the keycod es on page 24.

Check the programming of lines and phones

You can use the Element Manager to view the programming of lines and phones. When you view the lines, the information on the panels may vary, depending on the type of line.
The Element Manager displays line information in two sections:
The main section, Trunk/Line data, is located at the top of the screen and provides a table of lines and the current or default settings.
The bottom section contains three tabs. The cont ents of the tabs may vary, depending on the line selected in the top table.
—The Properties tabbed panel provides the settings for individual line characteristics. —The Preferences tab shows information that may vary from trunk to trunk
BCM450 Troubleshooting Guide
38 Chapter 4 Software Troubleshooting
—The Restrictions tabbed panel allows you to define which restrictions will be active for
individual lines. Note that lines that are assigned to the same line pool will automatically assign the same restrictions.
—The Assigned DNs tabbed panel provides a quick way to assign lines to telephones. You
must use the DN records panels to assign line pools to telephones.

Check line programming

Use the following procedure to check line programming in your BCM450 system.
To check line programming
1 In the Task Navigation Panel, select the Configuration tab. 2 Select Te lephony > Lines. 3 Verify that the programming for all lines is correct; see Trunk/Line data on page 38 for an
explanation of the fields on the panel.
4 Select a line, and then select a tab:
a Select the Properties tab and verify that the settings are correct; see Properties on
page 40 for an explanation of the fields on the tab.
b Select the Preferences tab and verify that the settings are correct; see Preferences on
page 42 for an explanation of the fields on the tab.
c Select the Restrictions tab and verify that the settings are correct; see Restrictions on
page 45 for an explanation of the fields on the tab.
d Select the Assigned DNs tab and verify that the settings are correct; see Assigned
DNs on page 46 for an explanation of the fields on the tab.
5 Repeat step 4 for the remaining lines. 6 Correct any programming problems, or restore the system data; see “Restoring system data”
on page 46 for more information.

Trunk/Line data

The top-level Table View panel shows line records for all lines active on the system, and the common assigned parameters.
Table 7 on page 38 describes the fields found on the Trunk/Line Data main panel.
Table 7 Trunk/Line Data main panel (Sheet 1 of 3)
Attribute Value Description
Line This list contains all the
possible line numbers for the system, including target lines.
NN40160-700NN40160-700
Configure only those lines that are active on th e system. (Click the Active check box and ensure that the Inactive check box is empty).
Table 7 Trunk/Line Data main panel (Sheet 2 of 3)
Attribute Value Description
Chapter 4 Software Troublesho oting 39
Trunk Type PSTN-based lines, VoIP,
Target
Name <maximum of seven
alphanumeric characters>
Control Set DN <control telephone DN>
Default: 221 (default Start DN)
Tips: External lines and telephones must be programmed to use one of the Scheduled Services: Ringing, Restriction, and Routing Services. For maximum flexibility, Nortel recommends that you create two different control telephones, one for the lines and one for the telephones. You can turn on a service manually or automatically for all e xternal lines from an a ssigned control telephone. However, you cannot combine schedules . A service can only be active as normal service or one of the six schedules at any one time. Several schedules can be active at one time, but they must use different services.
Line Type Public
Private to: <telephone DN> Pool A to O, BlocA to BlocF
There are three main categories of lines: PSTN-based lines: (analog, T1, PRI, BRI) Voice over IP (VoIP) trunks, which connect t hrough the LAN
or WAN. Target lines, which are internal channels that provide direct
dial capability. Identify the line in a way that is meaningful to your system,
such as by the type of line and line pool or the DN it is attached to in the case of target lines.
Enter a telephone DN for a telephone that you want to use to turn service off or on for other telephones using this line.
The control telephone must have the line assig ned, or must be assigned to the line pool the line is in.
Define how the line is used in relation to other lines in the system.
Public line: can be accessed by more than one telephone.
Private line: can be assigned only to one telephone and the prime telephone for that line. Enter the internal number of the telephone.
Pool A - O (analog and T1 lines) BlocA to BlocF (PRI and VoIP lines): assigns the line to one of the line pools. If a line is assigned to a line pool, but is not assigned to any telephone, that line is available only for outgoing calls. Bloc line pools must be used in conjunction with routes and destination codes. Target lines cannot be put into line pools.
Prime set DN: <telephone DN>
None
Assign a telephone to provide backup answering for calls on the line. For an Auto Answer line, calls are redirected if the received number is invalid or the target line is busy, and if the If busy parameter is set To prime.
Each line can be assigned only one prime telephone.
BCM450 Troubleshooting Guide
40 Chapter 4 Software Troubleshooting
Table 7 Trunk/Line Data main panel (Sheet 3 of 3)
Attribute Value Description
Pub. Received #
(Target lines only)
Priv. Received #
(Target lines only)
Distinct ring None
<digits associated with a specific target line>
<digits associated with a specific target line>
Pattern 2 Pattern 3 Pattern 4
Specify the digits the system will use to identify a call from the public network to this target line.
A received number cannot be the same as, or be the start digits, of a line pool access code, a destination code, the DISA DN or the Auto DN.
If you are configuring auto-answer BRI trunks to map to target lines, the received number should be the same as the Network DN supplied by your service provider. The call will be directed to the prime telephone for the incoming line if the Network DN is not used.
Specify the digits the system will use to identify a call from the private network to this target line.
A received number cannot be the same as, or be the start digits, of a line pool access code, a destination code, the DISA DN or the Auto DN.
If you are configuring auto-answer BRI trunks to map to target lines, the received number should be the same as the Network DN supplied by your service provider. The call will be directed to the prime telephone for the incoming line if the Network DN is not used.
Choose the distinctive ring pattern that you want to assign to the line. This allows you to provide selective service to calls with differing answer priorities.
When more than one line with the di stinct ring set tings ring s at a telephone, the line with the highest priority rings first.
Pattern 4 has the highest ring priority
Pattern 3 has second highest ring priority
Pattern 2 has third highest ring priority
None ha s the lowest ring priority.
By default, all telephones and lines are set to None.

Properties

The Properties tab shows basic line properties. Not all fields apply to all types of lines. The Properties tab is shown in Figure 10 on page 41.
NN40160-700NN40160-700
Chapter 4 Software Troublesho oting 41
Figure 10 Properties details panel
Table 8 on page 41 defines the fields on this panel and indicates the lines.
Table 8 Properties line settings (Sheet 1 of 2)
Attribute Value Description Legend: Loop = analog/digital loop; GS = ground start; DID = DID; E&M = E&M; BRI = BRI; DPNSS
= DPNSS; VoIP = VoIP; TL = Target. Note: PRI fields are all included under the main table.
Trunk mode
Loop
Unspr Supervised *Earth calling *Loop guarded *Loop unguarded **ROE, ROI
l mode Loop GS DID E&M
Dia
Pulse Tone
Loss package
Impedance (Ohms)
Loop (analog only)
Short CO Medium CO Long CO Short PBX Long PBX
Loop (analog only)
600 ohm-900 ohm The GATM can be set to a specific impedance level.
Define whether disconnect supervision, also r eferred to as lo op supervision, releases an external line when an open switch interval (OSI) is detected during a call on that line. You m ust set this to Supervised if a loop trunk has its Answer mode set to Auto or if you enable Answer with DISA. Disconnect supervision is also required to conference two external callers. The line must be equipped with disconnect supervision from th e central office for the Supervised option to work.
* These listing only appear for UK analog lines. ** These appear only for Australia.
Specify whether the system uses dual tone multifrequency (DTMF) or pulse signaling on the trunk.
Tone does not appear if Signaling is set to Immediate (T1 DID &T1 E&M trunk types only).
Select the appropriate loss/gain and impedance settings for each line.
BCM450 Troubleshooting Guide
42 Chapter 4 Software Troubleshooting
Table 8 Properties line settings (Sheet 2 of 2)
Attribute Value Description Legend: Loop = analog/digital loop; GS = ground start; DID = DID; E&M = E&M; BRI = BRI; DPNSS
= DPNSS; VoIP = VoIP; TL = Target. Note: PRI fields are all included under the main table.
Signaling
WinkStart Immediate DelayDial
Link at CO
Line Tuning Digit drop-down menu Select the line tuning digit to use. When a trunk is connected,
Loop (analog only)
<check box> Some exchanges respond to a Link signal, also called hook
DID E&M
Select the signal type for the line. The immediate setting does not appear for T1 E&M or T1 DID trunks connected to a DTM if the Dial mode is set to tone.
Make sure that this matches the signal type programmed f or the trunk at the other switch.
flash (FEATURE 71), by providing an alternative line for making outgoing calls.
Enabling Link at CO causes the system to apply t he restrict ions on outgoing calls to the digits dialed after the Link signal. As well, the call on the alternative line is subject to all restrictions.
Disabling Link at CO prevents a Link signal from resetting the BCM450 restrictions in cases where the host exchange does not provide an alternative line.
the BCM450 starts a call and sends this digit to the CO to turn off the dial tone signal, and then tests the line to optimize the trunk levels. The default digit is 1. You may need to change the default digit if your CO uses the digit 1 to route the call to a special service or to a second dial tone or busy/re-order tone. Select the digit that will result in silence on the trunk.

Preferences

The Preferences tab shows information that may vary from trunk to trunk. Most of this information needs to coordinate with the line service provider equipment.
The Preferences tab is shown in Figure 11.
Figure 11 Preferences details panel
NN40160-700NN40160-700
Chapter 4 Software Troublesho oting 43
Table 9 defines the fields on this panel and indicates the lines.
Table 9 Prefer ences details fields for lines (Sheet 1 of 3)
Attribute Value Description Legend: Loop = analog/digital loop; GS = ground start; DID = DID; E&M = E&M; BRI = BRI; DPNSS
= DPNSS; VoIP = VoIP; TL = Target and DASS2. Note: PRI fields are all included under the main panel.
Auto privacy
Full autohold
Aux. ringer
Loop GS DID E&M BRI VoIP
<check box> Define whether one BCM450 user can select a line in use at
another telephone to join an existing call.
Loop BRI DPNSS VoIP
<check box> Enables or disables Full autohold.
When enabled, if a caller selects an idle line but does not dial any digits, that line is automatically placed on hold if you then select another line.
Full autohold is always in place for T1 E&M trunks because it has no meaning for incoming-only T1 DID trunks.
The default setting should be changed only if Full autohold is required for a specific application.
Loop GS DID E&M BRI DPNSS VoIP TL
<check box> Turn the auxiliary ringer on or off for all telephones using this
line. When programmed on a line, the auxiliary ringer will ring every
time a call is received.
ANI Number
DNIS Number
Distinct Rings in use
Note: When programmed only on a telephone, no ring occurs for a transferred call. An auxiliary ringer can also be programmed in Services to ring for a line placed into
a scheduled Ringing service.
DID E&M
<check box> Define whether the telephone number of the caller will be
shown for this line. For T1 E&M and T1 DID trunks connected to a DTM, this setting
only appears if Signaling is set to WinkStart. The central office must deliver ANI/DNIS in DTMF mode. No
additional equipment is required.
E&M
<check box> Defines whether the digits dialed by an external caller on this
line will be shown.For T1 E&M trunks connected to a DTM, this setting only appears if Signaling is set to WinkStart and Answer mode is set to Manual.
<read-only> Indicates if a special ring has been assigned. See Distinct Ring
on the main table.
BCM450 Troubleshooting Guide
44 Chapter 4 Software Troubleshooting
Table 9 Prefer ences details fields for lines (Sheet 2 of 3)
Attribute Value Description Legend: Loop = analog/digital loop; GS = ground start; DID = DID; E&M = E&M; BRI = BRI; DPNSS
= DPNSS; VoIP = VoIP; TL = Target and DASS2. Note: PRI fields are all included under the main panel.
Answer mode
Answer with DISA
If busy
Loop GS E&M BRI DPNSS
Manual Auto
Note: You require Disconnect supervision on the line if loop start trunks a re to operate in auto-answer mode.
Loop GS E&M BRI
<check box> Define whether the system prompts a caller for a six-digit class
To Prime Busy Tone
Define whether a trunk is manual or automatic answer. Auto answer mode allows the trunk to be a shared resource by
the system telephones. This shared resource is created through routing to target lines or using DISA.
For auto answer trunks being used to allow remote call-in from system users, the trunk can be configured to answer with a straight dial tone, if DISA has not been enabled. It can also be configured to answer with a stuttered dial tone if DISA is enabled and the caller is expected to enter a CoS password. The CoS password defines which system features the caller is permitted to access.
Manual answer trunks are assigned to one or more teleph ones. The assigned telephones exclusively own the line.
of service (CoS) password. start, T1 E&M lines that have auto-answer mode, and analog trunks. Set this option to No for T1 E&M lines on a private network that have auto-answer mode.
Define whether a caller receives a busy tone or the call forwards to the prime telephone when the target line is busy. Busy tone only works for PRI trunks.
This setting appears for T1 loop
TL
Voice Message Center
Redirect to
NN40160-700NN40160-700
Tips: The duration of an open switch interval (OSI) before BCM450 disconnects a call is programmed by the Disconnect timer setting.
Loop GS DID E&M BRI DPNSS VoIP TL
Center 1 ­Center 5
Loop GS DID E&M TL
<dial string> Enter a dial string (including destination code) to redirect the
If this line connects t o a remote voice mail, either through the private network or at the Central Office, indicate which Center number has been configured with the contact number.The system calls that number to check voice mail messages when a message indicator is presented to a telephone.
line to an external telephone, such as a call attendant on another system.
If you want to stop redirection, you need t o delete t he dial strin g and allow the record to update.
Warning: If the dialstring is set up, the line will immediately be redirected out of the system not ringing any telephone.
Chapter 4 Software Troublesho oting 45
Table 9 Prefer ences details fields for lines (Sheet 3 of 3)
Attribute Value Description Legend: Loop = analog/digital loop; GS = ground start; DID = DID; E&M = E&M; BRI = BRI; DPNSS
= DPNSS; VoIP = VoIP; TL = Target and DASS2. Note: PRI fields are all included under the main panel.
Warning: Enable modules
If you disabled any trunk media bay modules prior to performing programming, enable them now to ensure your system will function properly.

Restrictions

Assigning Line restrictions and Remote Access Package restrictions are part of the configuration for controlling calls out of the system (line restrictions) and into the system from a private network node or from a remote user calling in over the PSTN lines (Remote Access Packages).
The Restrictions tab shows the restrictions for a line.
Table 10 describes the fields on this panel.
Table 10 Restrictions
Attribute Values Description
Use remote package <remote package #> If the line is being used to receive external calls or calls
from other nodes on the private network, ensure that you indicate a remote package that provides on ly the availability that you want external callers to have. This attribute is typically used for tandeming calls.
Schedule Default: Normal, Night, Evening, Lunch, Sched 4, Sched 5, Sched 6 Line Restrictions -
Use Filter
Remote Restrictions
- Use Filter
<00-99> Enter the restriction filter number that applies to each
schedule. (controls outgoing calls)
<00-99> Enter the restriction filter that applies to each schedule.
This setting provides call controls for incoming calls over a private network or from remote user dialing in over PSTN)
BCM450 Troubleshooting Guide
46 Chapter 4 Software Troubleshooting

Assigned DNs

The Assigned DNs tabbed panel displays the DN properties for lines that are assigned to telephones.
This information can also be configured on the DN record. Any information added, deleted or modified in this table reflects in the DN record.
Note: Lines that do not allow single-line assignment, such as PRI lines and VoIP lines, will not display this tabbed panel.

Restoring system data

If the programming of lines and extensions is incorrect, you can restore from an archive file, or you can restore the system to factory defaults. This section provides the procedures to follow to restore system data from an archive file, and to restore factory defaults. For information about the effects of performing a restore operation, or about optional components, see the BCM450 Administration and Security Guide (NN40160-601)
Restoring data from an archive
Caution: A backup operation can interrupt services running on the BCM450. A
warning displays whenever the backup will cause a service interruption. If you want to perform a backup that does not affect the system, you can exclude services that would be affected. Alternatively, you can include these services and perform a backup at a time when the system is typically not in use.
To restore data from an archive
1 In the task panel, click the Administration tab. 2 Open the Backup and Restore folder, and then click Restore.
The Restore panel opens. The Restore From selection field has BCM as a default value.
3 In the Restore From selection field, select the location of the archive file to restore:
BCM
My Computer
Network folder
•FTP server
•SFTP server
USB storage device
•Factory Default
4 Click the Restore button.
The Select Components to Restore window opens.
NN40160-700NN40160-700
Chapter 4 Software Troublesho oting 47
5 Select the optional components that you want to include from the backup file. 6 Click the OK button.
A warning window opens and displays informatio n about components that will be affected by the restore operation. Read the warning carefully before proceeding.
7 Click the Yes button to proceed.
A progress window opens. When the operation is complete, the Restore Complete window opens.
8 Click the OK button.
Restoring the factory configuration
Caution: A restore operation is a service-affecting operation. A nu mber of
services running on the BCM450 system will be stopped and then restarted using the restored configuration or application data. A reboot is required if you choose Keycodes as a restore option. It will take several minutes before Voicemail is working again.
To restore the factory configuration
Your BCM450 is delivered with a backup file that was created at the factory. This file can be a helpful starting point if you decide to completely re-configure your BCM450 and would like to erase the settings programmed on your device. Although you can select individual components to restore, Nortel recommends that you restore all components when using this option.
1 In the task panel, click the Administration tab. 2 Open the Backup and Restore folder, and then click Restore.
The Restore panel opens.
3 In the Restore From selection field, select Factory Default.
A warning dialog box displays.
4 Click the Restore button.
The Select Components to Restore panel opens.
5 Select the optional components that you want to include from the backup archive. 6 Click the OK button.
A warning window opens and displays informatio n about components that will be affected by the restore operation. Read the warning carefully before proceeding.
7 Click the Yes button to proceed.
A progress window opens. When the operation is complete, the Restore Complete window opens.
8 Click the OK button.
BCM450 Troubleshooting Guide
48 Chapter 4 Software Troubleshooting

Verify the software inventory

This section provides information about how to verify the level of software components and obtain updates to your software inventory. For information about applying software updates, please refer to the BCM450 Administration and Security Guide (NN40160-601).

Viewing the inventory of BCM450 software

BCM450 software is organized into software components that you can individually update as required. The version of each software component is tracked so that you can determine the exact software release level of a BCM450 to the component level.
You can view the complete inventory of software installed on the BCM450. The Software Inventory table displays all the software components installed on the system, the functional group and the software version of each component.
Table 11 lists the information displayed in the Software Component Version Information table.
Table 11 Information displayed in the Software Component Version Information table
Column Description
Component The name of the software component installed on the BCM450. For
example, backup-recovery.
Group The functional group to which the software component belongs. For
Version The version of the software component.
example, Operating System.
You can change the order of the information displayed in the table by clicking a column heading and dragging it to a new place in the table. You can also sort the information in a column by descending or ascending order, by clicking the column heading.
To view the BCM450 software inventory
1 In the task panel, click the Administration tab. 2 Open the Software Management folder, and then click the Software Inventory task.
The Software Inventory panel opens.
3 View the details in the Software Component Version Information table.

Obtaining software updates

Before you can apply a software update to your BCM450, you must obtain the software update and unzip the file. Authorized Nortel partners can download BCM450 software updates from the Nortel Technical Support web page.
NN40160-700NN40160-700
Chapter 4 Software Troublesho oting 49
To obtain updates from the Nortel Technical Support Web page
1 In your web browser, enter www.nortel.com/cs and then click the Go button.
The Nortel Technical Support Web page opens.
2 Download the required updates. 3 Create a directory for each update and unzip the downloaded file into a directory.
BCM450 Troubleshooting Guide
50 Chapter 4 Software Troubleshooting
NN40160-700NN40160-700
Chapter 5

Advanced Troubleshooting

This chapter contains examples of advanced troubleshooting procedures. You must be a system administrator to perform these procedures.

Navigation

Example 1: Cannot dial out from an analog trunk on page 51
Example 2: Cannot dial out from a SIP or H323 VoIP trunk on page 53
Example 3: IP set is not registering with the BCM450 on page 58
Example 4: Cannot install keycode or invalid keycode application on page 60
Example 5: Cannot dial out from digital trunk on page 61
Example 6: MeetMe Conferencing commands do not work, or conferencing is busy on page 66
Example 7: Unable to apply a software update from a USB storage device on page 67
Example 8: Element Manager incorrectly shows expansion cabinet as empty on page 68
51

Example 1: Cannot dial out from an analog trunk

When you cannot dial out from an analog trunk, you may experience the following problems in your network:
you are unable to reach a destination number when you dial it
there is no dial tone
instead of a dial tone, you hear a re-order or fast-busy tone
you hear a “wrong number” message from the central office.
Use the following procedure when you cannot dial out from an analog trunk.
Troubleshooting example 1
1 Check that the LED indicators on the BCM450 Chassis and the MBM are solid green. 2 Using an analog test set, verify that a dial tone is present at the MBM termination point. 3 From the Element Manager, select Configuration > System > Keycodes to view the list of
installed features.
4 Verify that the appropriate keycode is active. For analog trunk modules, the keycode is Exp
Port.
5 Select Configuration > Resources > Telephony Resources and select the appropriate trunk.
Verify that the trunk is active.
BCM450 Troubleshooting Guide
52 Chapter 5 Advanced Troubleshooting
6 Select Configuration > Telephony > Lines > Active Physical Lines. Select the appropriate
line and verify that it is provisioned correctly. The Line Type should be Pool A, the Trunk Mode should be Supervised, and the Dial Mode should be Tone.
7 Select Configuration > Telephony > Sets > Active Sets. Select the appropriate set and verify
that it is provisioned correctly . On the Line Assignment tab, verify that the A ppearance Type is one of the following: appear only, appear and ring, or ring only.
8 Select Administration > Utilities > BCM Monitor and click the Launch BCM Monitor
button.
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 53
9 Select the BCM Info tab and verify the status of the line.

Example 2: Cannot dial out from a SIP or H323 VoIP trunk

When you cannot dial out from a SIP or H323 VoIP trunk, you may experience the following problems in your network:
you are unable to reach a destination number when you dial it
there is no route to the destination
Use the following procedure when you cannot dial out from a SIP or H323 trunk.
Troubleshooting example 2
1 Check that the LED indicators on the BCM Chassis are solid green. 2 From the Element Manager, select Configuration > System > Keycodes to view the list of
installed features.
BCM450 Troubleshooting Guide
54 Chapter 5 Advanced Troubleshooting
3 Verify that the appropriate keycode is active. For H323 trunks, the keycode is VoIP GW
Trunk, and for SIP trunks, the keycode is SIP GW Trunk.
4 Select Configuration > Telephony > Lines > Active VoIP Lines. Select the appropriate line
and verify that the Control Set and Prime Set are provisioned correctly.
5 Select Configuration > Resources > Telephony Resources and select the appropriate trunk.
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 55
6 Click the Add button to open the Add Remote Gateway dialog box. Verify that the remote
gateway is configured correctly.
7 Select Configuration > Telephony > Dialing Plan > Routing and select the Routes tab.
Verify that the route is configured correctly.
8 Select Configuration > Telephony > Dialing Plan > Routing and select the Destination
Codes tab. Verify that the destination code is configured correctly.
BCM450 Troubleshooting Guide
56 Chapter 5 Advanced Troubleshooting
Note: Ensure that the Absorbed Length is configured to the expected dialing plan.
9 Select Configuration > Telephony > Sets > Active Sets and select the Line Access tab.
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 57
10 Highlight the appropriate set and select the Line P ool Access tab . Verify that the set has access
to VoIP trunks
11 Select Configuration > Telephony > Dialing Plan > Private Network and ensure that the
Private Network Type is set to CDP or UDP.
BCM450 Troubleshooting Guide
58 Chapter 5 Advanced Troubleshooting
Note: In this example, the dialing plan is configured for a CDP Network with the recommen ded minimum
4 digit Private DN length

Example 3: IP set is not registering with the BCM450

When an IP set cannot register with the BCM450, you may notice the following problem in your network:
the IP set is not registered and repeatedly tries to connect to the BCM450
If an IP phone is not registering with the BCM450, there are three possible causes:
there are not enough licenses for the number of IP phones connected to the system
the number of IP sets connected exceeds the maximum; the maximum is 300
the phone is not correctly configured
Verify that the number of phones does not exceed the number of licenses. If there are too many phones for the number of licenses, disconnect any unneccesary phones, or increase the number of licenses.
If the number of IP sets connected to the BCM450 exceeds the maximum number of 300, it is possible that after a system reboot, not all of the 300 supported sets will be able to register. To resolve this problem, refer to the procedure Troubleshooting example 3a on page 59.
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 59
If the number of phones connected does not exceed the number of licenses, and does not exceed the maxium number of IP sets supported, use the procedure Trou bleshooting example 3b on page 59 to verify the configuration of the IP phone.
Troubleshooting example 3a
1 Select Configuration > Telephony Resources deregister the offline sets.
OR
2 To connect more than 300 IP sets, configure unused Application DNs for these sets by
selecting Configuration > Telephony Resources > Application Sets.
3 Decrease the Application DNs and increase the IPSet DN count.
Troubleshooting example 3b
1 Select Configuration > Resources > Telephony Resources and select the appropriate IP set
from the list.
2 On the IP Terminal Global Settings tab, ensure that the Enable Registration checkbox is
selected.
3 Verify that the Global password on the BCM450 is the same password that you are using the
register the IP set (the default passw ord is 22 64). If this field is left blank, no password prompt occurs during phone registration.
BCM450 Troubleshooting Guide
60 Chapter 5 Advanced Troubleshooting
4 Verify S1/S2 IP address & Port settings on phone (Port 7000 for BCM)

Example 4: Cannot install keycode or invalid keycode application

When you cannot install a keycode, or have an invalid keycode application, you will see the following message: “Error Happened. Error detail; Invalid Keycode File.”
Use the following procedure when you cannot install a keycode, or when a keycode application is invalid. For further information about keycodes, see the Keycode Installation Guide (NN40010-301).
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 61
Troubleshooting example 4
1 Verify that the keycode is generated against the right system ID in the Keycode Retrieval
System (KRS). Access the KRS using one of the following methods:
a Connect to http://www.nortel.com/support/tools/krs/ b In Element Manager, select Configuration > System > Keycodes and click the
Connect to Nortel Keycode Retrieval System button.
2 In the Element Manager, select Help > About. Verify that the installed version is the latest
version of the software.

Example 5: Cannot dial out from digital trunk

When you cannot dial out from a digital trunk, you may experience the following problems in your network:
you are unable to reach a destination number when you dial it
there is no route to the destination
Use the following procedure when you cannot dial out from a digital trunk.
BCM450 Troubleshooting Guide
62 Chapter 5 Advanced Troubleshooting
Troubleshooting example 5
1 Check that the LED indicators on the BCM Chassis are solid green. 2 Verify the physical connection from the carrier demarcation; ensure that the cable is securely
connected.
3 Verify the physical connection from the carrier demarcation to the BCM450 equipment;
ensure that the cable is securely connected.
4 If you are using SL-1 or ETSI QSIG, verify that the MCDN keycode is active. From the
Element Manager, select Configuration > System > Keycodes to view the list of installed features.
5 Verify that the digital trunk parameters are configured according to the parameters specified by
your carrier or central office.
6 Select Configuration > Resour ces > Telephony Resources and click the Trunk P ort Details
tab. Verify that the trunk port details and state are correctly provisioned.
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 63
7 Select the Provision Lines tab and verify that the lines are correctly provisioned.
8 Select Configuration > Telephony > Dialing Plan > Routing and select the Routes tab.
Verify that the route is configured correctly
9 Select Configuration > Telephony > Dialing Plan > Routing and select the Destination
Codes tab. Verify that the destination code is configured correctly.
BCM450 Troubleshooting Guide
64 Chapter 5 Advanced Troubleshooting
Note: Ensure that the Absorbed Length is configured to the expected dialing plan.
10 Select Administration > Telephony Metrics > Trunk Module Metrics and select the DTM
module. Verify that the State of the DTM module is Enabled.
11 Select the CSU Alarm History tab and check the alarm status of the module.
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 65
12 Select Administration > Telephony Metrics > CBC Limit Metrics and verify calls were not
denied due to exceeding CBC limits.
13 Select Administration > Utilities > BCM Monitor and click the Launch BCM Monitor
button.
BCM450 Troubleshooting Guide
66 Chapter 5 Advanced Troubleshooting
14 Select the Line Monitor tab and verify the status of the line; select the UIP tab and verify the
call set up.

Example 6: MeetMe Conferencing commands do not work, or conferencing is busy

Use the following procedure to troubleshoot problems with MeetMe Conferencing.
NN40160-700NN40160-700
Chapter 5 Advanced Troubleshooting 67
Troubleshooting example 6
1 Select Configuration > Resources > Application Resources and select the VoiceMail + CC
application.
2 Increase the maximum number of application resources (voice ports) for Voice Mail + CC.

Example 7: Unable to apply a software update from a USB storage device

Use the following procedure when a software update from a USB storage device fails. When the update fails, the BCM450 generates alarm 1003.
Troubleshooting example 7
1 Verify that only one USB storage device is attached to the BCM450 in the bottom USB port. 2 If a second USB storage device is attached, remove it. 3 Verify that there is only one partition on the USB storage device, and that the software update
is on the first partition. The BCM450 will recognize only the first partition.
BCM450 Troubleshooting Guide
68 Chapter 5 Advanced Troubleshooting

Example 8: Element Manager incorrectly shows expansion cabinet as empty

Use the following procedure when a module is installed in the expansion cabinet, but the Element Manager shows the expansion cabinet as empty, and the MBM is not active.
1 Select Configuration > Resources > Telephony Resources. 2 Double-click the Module Type field for the expansion cabinet. 3 Select the module from the list. 4 Configure the module and select Enable.
NN40160-700NN40160-700
Chapter 6

Recovery trees

The chapter provides recovery trees for common troubleshooting scenarios.

Navigation

System is not processing calls on page 69
Start-up profile fails on page 70
Cannot access BCM450 through Element Manager on page 71
BCM450 shuts down unexpectedly on page 73

System is not processing calls

Use the following flowchart when the BCM450 is not processing calls.
69
BCM450 Troubleshooting Guide
70 Chapter 6 Recovery tree s
Figure 12 System is not processing calls

Start-up profile fails

Use the following flowchart when the start-up profile of the BCM450 fails.
NN40160-700NN40160-700
Figure 13 Start-up profile fails
Chapter 6 Recovery trees 71

Cannot access BCM450 through Element Manager

Use the following flowchart when you cannot access the BCM450 through Element Manager.
BCM450 Troubleshooting Guide
72 Chapter 6 Recovery tree s
Figure 14 Cannot access BCM450 through Element Manager
NN40160-700NN40160-700

BCM450 shuts down unexpectedly

Use the following flowchart when the BCM450 shuts down unexpectedly.
Figure 15 Unexpected shutdown
Chapter 6 Recovery trees 73
BCM450 Troubleshooting Guide
74 Chapter 6 Recovery tree s
NN40160-700NN40160-700
Chapter 7

Downloading Software

Use the information in this chapter to download BCM450 software.

Navigation

Downloading software from the BCM450 webpage on page 75
Downloading software from the Nortel web site on page 77

Downloading software from the BCM450 webpage

The BCM450 web page facilitates the download of applications, documentation, and other information necessary for running the BCM450 and its services. You connect to the BCM450 web page by typing the IP address of your BCM450 device into your browser. A valid user name and password are required in order to access the web page .
75
The BCM450 web page contains the following links:
Quick Link - Provides links to frequently used applications, including Mailbox Manager,
Activity Reporter Basic, and CallPilot Manager.
User Applications - Applications listed in Ta ble 12 that are available to the end users of
the BCM450.
Business Applications - Applications listed in Table 12 that are available to business users
of the BCM450.
Administrator Applications - Applications listed in T able 12 that are available to BCM450
administrators.
Documentation - Documentation for the BCM450 end users to explain the end-user
applications and BCM450-specific tasks.
Table 12 Applications available on BCM450 web page
Application User Administrator User Applications
Mailbox Manager Y Y Desktop Assistant Pro Y Y CallPilot Unified Messaging Y Y Personal Call Manager Y Y LAN CTE Client Y Y IP Software Phone 2050* Y Y Mobile Voice Client 2050 Y Y
BCM450 Troubleshooting Guide
76 Chapter 7 Downloading Software
Table 12 Applications available on BCM450 web page (Continued)
Application User Administrator Business Applications
Reporter Applications
Activity Reporter Basic N Y Activity Reporter N Y
Contact Center Applications
Reporting for Contact Center N Y Contact Center Reporting
Server Multimedia Contact Center N Y IP View Softboard N Y
Administrator Applications
Administrator Management Tools
CallPilot Manager N Y Business Element Manager N Y Desktop Assistant Pro AE N Y NCM for BCM N Y* BCM Monitor N Y CDR Clients N Y BCM
MIBs N Y
RADIUS Dictionary SSH Client (PuTTY) N Y BCM Logs N Y
Digital Mobility Tools
Digital Mobility Controller N Y Digital Mobility Service Tool N Y
Templates
Startup Profile Template N Y Factory Default Programming
Record
NY
NY
To download software from the BCM450 webpage
1 Connect to the BCM450 web page:
— If the BCM450 is installed on the network use a browser and type in the BCM450 IP
— If the BCM450 is installed but not yet configured, connect directly to the BCM450
NN40160-700NN40160-700
address as the URL in the following format: http://xxx.xxx.xxx.xxx
through the OAM port and, using a browser, type the following:
Chapter 7 Downloading Software 77
http://10.10.11.1/
2 Enter the user name and password to be authenticated on the BCM450 web page. 3 Select the link for the type of application that you want to download. 4 Select the link for the specific application or tool that you want to download and select the
download link.

Downloading software from the Nortel web site

To download software from the Nortel Web site, see the following web site: http://www.nortel.com/downloadingcontent
BCM450 Troubleshooting Guide
78 Chapter 7 Downloading Software
NN40160-700NN40160-700
Chapter 8

Troubleshooting Tools

The BCM450 system provides several tools that you can use to diagnose problems.

Navigation

Service Management on page 79
Status and Metrics on page 79
Utilities on page 80
Command Line Interface on page 80

Service Management

You can use the Element Manager to view a list of the services that are running on your BCM450 system.
79
For information about service management on the BCM450, see “Using the BCM450 Service Managment System” in the BCM450 Administration and Security Guide (NN40160-601).

Status and Metrics

You can use the Element Manager to view detailed information about the performance of the BCM450 and about the performance of system resources.
You monitor system status using the following tools:
QoS Monitor—QoS Monitor monitors the quality of service (QoS) of IP trunk services.
UPS Status—The Uninterruptible Power Supply (UPS) feature provides monitoring of the power source and the battery backup.
NTP Metrics—The Network Time Protocol (NTP Metrics) feature provides an overview of the integrity of the NTP time source
For information about monitoring the system status, see the chapter “Using BCM450 System Metrics” in the BCM450 Administration and Security Guide (NN40160-601).
You can monitor system performance using the following tools:
Activity Reporter Basic—Generate reports about call activity and voice mail receive statistics.
Trunk Module Metrics— View the status of digital trunk modules as well as identify any device or lines connected to the system.
CbC Limit Metrics—Use the CbC Limit metrics panel to monitor denied call activity for each service on each line pool.
BCM450 Troubleshooting Guide
80 Chapter 8 Troubleshooting Tools
Hunt Group Metrics—Access the Hunt Group metrics to evaluate total call processing by hunt group member.
PSTN Fallback Metrics—View how many fallback attempts and fallback failures occur within a specific period using the PSTN Fallback Metrics panel.
Proactive Voice Quality Management—Proactive Voice Quality Management (PVQM) metrics allow you to monitor the quality of VoIP calls. You can also use the PVQM metrics to diagnose infrastructure problems in your network.
For information about monitoring system performance, see the chapter “Monitoring BCM450 Telephony Metrics” in the BCM450 Administration and Security Guide (NN40160-601):

Utilities

BCM450 provides the following utilities:
BCM Monitor—BCM Monitor is a stand-alone diagnostic application that the system administrator can use to view real-time system and IP telephony information about BCM450 systems.
Ping—Ping (Packet InterNet Groper) is a utility that you can use to verify that a route exists between the BCM450 and another device.
Route trace—You ca n use Trace Route to measure round-trip times to all hops along a route. This helps you to identify bottlenecks in the network.
Ethernet activity—The Ethernet Activity panel is a utility that you can use to view ethernet activity in the BCM450 system.
For information about utilities, see the “BCM450 Utilities” chapter in the BCM450 Administration and Security Guide (NN40160-601).

Command Line Interface

You can use the Command Line Interface (CLI) to configure basic settings, as well as shut down, reboot, or reset the BCM450 system. Two CLI modes are available: Maintenance CLI, and Configuration CLI.
This section contains information about the following topics:
Accessing the CLI on page 80
Using the Configuration CLI on page 81
Using the Maintenance CLI on page 82

Accessing the CLI

There are two methods of accessing the CLI:
through a serial connection
through the OAM port
NN40160-700NN40160-700
Chapter 8 Troubleshooting Tools 81
For either method, your user account must be assigned the System-CLI privilege before you can access the CLI.
Accessing the CLI through a serial connection
Caution: The CLI is intended for use by experienced technicians, or as directed
by Nortel Technical Support. Improper use of the CLI may result in data loss.
1 Connect a serial cable with a 9-pin female connector from the serial port on a PC to the serial
port on the BCM450.
2 Ensure that you use the following settings:
bits per second: 115200
data bits: 8
•parity: N
stop bits: 1
no flow control
3 Use a terminal emulation program, such as Hyperterminal or Nortel CLI Manager, to establish
a connection to the BCM450.
4 Log into the BCM450 by entering your username and password. Your user account must be
assigned the System-CLI privilege in order to access the CLI.
Accessing the CLI through the OAM port
Caution: The CLI is intended for use by experienced technicians, or as directed
by Nortel Technical Support. Improper use of the CLI may result in data loss.
1 Connect an Ethernet cable from the Ethernet port on a PC to the OAM Ethernet port on the
BCM450.
2 Set the IP address of the PC to 10.10.11.2. 3 Use putty to establish an SSH connection to the default IP address of the OAM port:
10.10.11.1.
4 Log into the BCM450 by entering your username and password. Your user account must be
assigned the System-CLI privilege in order to access the CLI.

Using the Configuration CLI

The Configuration CLI dislays when the system is in Main OS mode. The options available on the Configuration CLI are:
0—Exit. The system exits the CLI to the login prompt.
1—Reboot. The system reboots to the Main OS.
BCM450 Troubleshooting Guide
82 Chapter 8 Troubleshooting Tools
2—Shutdown. The system shuts down. You need physical access to the BCM450 hardware to restart the system.
3—Safe OS. The system reboots to the Safe OS and waits 1 minute for you to login. When you login within 1 minute, the Maintenance CLI displays. If you do not login within 1 minute, the system changes to the Main OS. For more information about the Safe OS, see Using the
Maintenance CLI on page 82.
4—Configuration Reset. A Level 1 reset occurs. The system resets all configuration data to the factory defaults.
5—Software Reset. A Level 2 reset occurs. The system resets all configuration data and software to the factory defaults.
6—IP Configuration. You can configure the following basic IP settings:
0—Return to Previous Menu. The system returns to the main menu.
1—Hostname. Provision the hostname of the system.
2—IP Address. Provision the IP address of the system.
3—Subnet Mask. Provision the subnet mask for the IP address.
4—Default Gateway. Provision the default gateway for the system.
5—DHCP Client Mode. Enable or disable the DHCP client.
6—Commit Changes. Save changes to the IP settings.
7—Reload Settings. Reload the existing IP settings.

Using the Maintenance CLI

The Maintenance CLI displays when the system is in Safe OS mode. The Safe OS is a diagnostic mode that you can use if the Main OS is experiencing problems. No applications or telephony services are running when the BCM450 is in Safe OS mode. The options available on the Maintenance CLI are:
0—Exit. The system exits to the Safe OS login prompt.
1—Reboot into Main OS. The system reboots to the Main OS.
2—Shutdown. The system shuts down. You need physical access to the BCM450 hardware to restart the system.
3—Reboot into Safe OS. The system reboots to the Safe OS and waits 1 minute for you to login. If you do not login within 1 minute, the system changes to the Main OS.
4—Transition to Main OS. The system changes from the Safe OS to the Main OS without restarting.
5—Configuration Reset. A Level 1 reset occurs. The system resets all configuration data to the factory defaults.
6—Software Reset. A Level 2 reset occurs. The system resets all configuration data and software to the factory defaults.
NN40160-700NN40160-700
Chapter 9

Understanding system messages

The BCM450 system generates alarms, logs, traps, and other system messages that you can use to troubleshoot problems.

Alarms, logs, and traps

For information about system messages, see the following chapters in the BCM450 Fault and Performance Management Guide (NN40160-701):
“Using the BCM450 Fault Management System,” which describes fault management tools such as alarms, logs, and SNMP traps
“List of Alarms,” which provides alarm messages, problem descriptions, and possible solutions
83

Reporting for dropped calls

You can specify the level of system reporting that you require for released ISDN or VoIP calls. You can choose to have no text, a simple explanation, or a detailed explanation in the dropped call notification.
Use this procedure to set the level of reporting for dropped calls.
To set Release Reasons
To set Release reasons, follow these steps:
1 Click Administration > Utilities > Diagnostic settings. 2 Click the Telephony tab.
The Release Reasons panel appears.
3 From the Release Reason drop-down menu, select the level of reporting that you require.
Table 13 lists the possible values for Release reasons.
Table 13 Release reasons
Attributes Values Description
None Default Value No text will accompany a dropped call notification. Simple Cause Code:
Off On
Off: no text is provided On: the code only is provided Note: if you select Simple text, you must turn off the Cause code. This is for
diagnostic purposes only.
BCM450 Troubleshooting Guide
84 Chapter 9 Understanding system messages
Table 13 Release reasons
Attributes Values Description
Detailed No setting A detailed explanation of the Cause code is provided. Cause
Code
check box This check box appears when you select Simple in the Release Reason
Text drop-down menu. When you select the check box, only the cause code accompanies a dropped call notification.
NN40160-700NN40160-700
Chapter 10

Useful Troubleshooting Links

Use the information in this chapter to find additional reference information when you are troubleshooting a problem with the BCM450 system. As part of your initial troubleshooting, Nortel recommends that you check these resources for information about known issues and for solutions related to the problem you are experiencing.

Navigation

Partner Bulletins on page 85
Knowledge and Solution Engine on page 85

Partner Bulletins

85
To locate Partner Bulletins, visit the Nortel Partner Information Center: http://www.nortel.com/pic

Knowledge and Solution Engine

The Knowledge and Solution Engine allows you to search an entire database of Nortel technical documents, troubleshooting solutions, software, and technical bulletins.
The document types available from the Knowledge and Solution Engine include the following:
Bulletins: Includes a listing of technical bulletins.
Documentation: Includes all technical documentation written for Nortel
products (such as installation guides, administration guides, release
•notes).
Service Requests: Includes technical support cases created within the past year. The availability of service requests is based on your customer entitlement.
Software: Includes software patches and software releases.
Solutions: Includes troubleshooting solutions written by the Nortel Technical Support team.
When searching through the Knowledge and Solution Engine, enter a natural language qu ery (that is, a query in the form of a statement or a question).

Using the Knowledge and Solution Engine

Use the following procedure to access the Knowledge and Solution Engine.
BCM450 Troubleshooting Guide
86 Chapter 10 Useful Troub leshooting Links
To use the Knowledge and Solution Engine
1 Go to the Nortel Web site: www.nortel.com 2 Log in using user name and password. 3 Select SUPPORT & TRAINING. 4 Select ONLINE SELF-SERVICE, and then select Knowledge Base.
The Online Self-Service page appears and shows the Knowledge and Solution Engine. For information on performing your search, click the Search Tips link.
To view an interactive tutorial for the Knowledge and Solution Engine, go to the Help &
Contact section, click the Help Using This Site link and then scroll to find the Knowledge Base tutorial.
5 Enter your problem statement or question in the text box. Ensure that you leave spaces
between the words in the statement or question.
6 From the ALL TYPES drop-down list, select the document type you would like to search
against. The default is ALL TYPES, which searches on all available documents (bulletins, documentation, services requests, software, and solutions).
7 Click > (the arrow adjacent to the text box) or press Enter to start your search. The page
reloads and provides the option to narrow your search by product family.
NN40160-700NN40160-700
Chapter 11

Frequently Asked Questions

The chapter provides answers to frequently asked questions.

Navigation

Backup, restore, and reset operations on page 87
Password protection on page 89
Fault management on page 90
System and status information on page 91
Connectivity problems on page 95
IP addresses on page 96
87

Backup, restore, and reset operations

This section contains answers to the following questions:
How do I back up the database? on page 87
How do I restore the BCM450 from a previous backup? on page 88
How do I complete a Warm Reset or Cold Reset? Is it safe and will I lose customer data? on page 88

How do I back up the database?

Use the following procedure to back up the BCM450 database.
To perform a backup
1 In the task panel, click the Administration tab. 2 Open the Backup and Restore folder, and then click Backup.
The Backup panel opens and displays the Immediate Backup tab. In the Backup To selection field, choose a destination for the backup archive.
3 Click the Backup button.
The Backup window opens.
4 In the Optional Components table, select or clear the check box for each component to
include or exclude these components from the backup operation.
5 Click the OK button.
A warning window opens. Read the warning carefully before proceeding.
BCM450 Troubleshooting Guide
88 Chapter 11 Frequently Asked Questions
6 Click the Yes button to proceed.
A progress window opens. When the backup is complete, the Backup Complete message appears.
7 Click the OK button.

How do I restore the BCM450 from a previous backup?

Use the following procedure to restore the BCM450 database.
To restore data from the BCM450
1 In the task panel, click the Administration tab. 2 Open the Backup and Restore folder, and then click Restore.
The Restore panel opens. In the Restore From field, select the locati on of the b ackup ar chive to use.
3 Click the Restore button.
The Select Components to Restore window opens.
4 Select the optional components that you want to include from the backup file. 5 Click the OK button.
A warning window opens and displays informatio n about components that will be affected by the restore operation. Read the warning carefully before proceeding.
6 Click the Yes button to proceed.
A progress window opens. When the operation is complete, the Restore Complete window opens.
7 Click the OK button.

How do I complete a Warm Reset or Cold Reset? Is it safe and will I lose customer data?

You can use the Reset utility in Element Manager to:
reboot the BCM450 system
perform a warm reset of telephony services
perform a cold reset of telephony services
shut down the system
For a description of the impact on the system of each of these resets, see Reset functions on page
26.
Use this procedure to perform a warm or cold reset.
NN40160-700NN40160-700
Completing a warm or cold reset
1 Select Administration > Utilities > Reset, and click one of the following buttons:
a Reboot BCM450 System will restart the operatingsystem of the BCM450 b Warm Reset Telephony Services will restart telephony services. Customer data will
be retained.
c Cold Reset Telephony Services will reset telephony programming to factory defaults.
Customer data will be lost.
d Shutdown System will stop all services and shut down the system. Restarting the
system requires physical access to the BCM450.

Password protection

This section answers the following frequently asked question:
How do I recover a lost password for the BCM450? on page 89
Chapter 11 Frequently Asked Questions 89

How do I recover a lost password for the BCM450?

There is a Nortel support default user which cannot be deleted or modified. This account is set up to allow Nortel troubleshooting technicians to access areas of the system that are not available to other users. You can change the default challenge key, but be sure to retain a record of the change so that Nortel support technicians can access your system.
Recovering a lost password
1 Select Configuration > Administrator Access > Security Policies, and select the Entry
Policy tab.
2 With the Challenge Key available, contact Nortel Technical Support and request help to
recover the lost password.
BCM450 Troubleshooting Guide
90 Chapter 11 Frequently Asked Questions

Fault management

This section answers the following frequently asked question:
How do I view Alarms? Can I acknowledge and clear them? on page 90

How do I view Alarms? Can I acknowledge and clear them?

When you view an alarm on the alarms panel, you can change the order of the columns in the table and you can sort alarms. For example, you may want to sort alarms by Component ID and Alarm ID.
Use the following procedures to view alarms and to acknowledge alarms.
To view an alarm
1 Click the Administration tab. 2 Open the General folder, and then click the Alarms task.
The Alarms page opens.
3 In the Alarms Panel table, select an alarm.
The Alarm Details panel displays below the Alarms table.
NN40160-700NN40160-700
4 To change the order of columns in the Alarm table, select a column and drag it left or right to
the desired location, and release it.
5 To view a column by ascending or descending order, click the column heading.
To acknowledge an alarm
1 Click the Administration tab. 2 Open the General folder, and then click the Alarms task.
The Alarms panel opens.
3 In the Alarms table, select the alarm you want to acknowledge.
The Alarm Details panel is displayed below the Alarms table.
4 On the Alarms Details panel, click the Acknowledge Alarm button.
A check box appears in the Alarm ACKed column in the Alarms table for this alarm.
Acknowledging the alarm does not clear the alarm; it indicates only that the alarm has been noted.

System and status information

Chapter 11 Frequently Asked Questions 91
This section answers to the following frequently asked questions:
How do I capture the logs from the BCM450? on page 91
How do I capture the current BCM450 configuration? on page 93
How do I find the BCM450 system health? on page 94
How do I show specific process states? on page 94
How do I verify current software revision? on page 94
How do find the BCM450 System ID and Serial Number? on page 95

How do I capture the logs from the BCM450?

You can capture or transfer logs from the BCM450 using Element Manager, or from the BCM450 Web page.
When you use the BCM450 Web page to transfer log files, you cannot choose the log file categories that you will transfer; all the log files in all the categories will be transferred.
Use the following procedures to transfer log files.
Using the Element Manager to transfer log files
1 Click the Administration tab, and then open the Logs folder. 2 Click the Log Management task.
The Log Management panel opens.
3 Click the Immediate Log Transfer tab. 4 In the Transfer To selection field, select a storage location.
BCM450 Troubleshooting Guide
92 Chapter 11 Frequently Asked Questions
5 Click the Transfer button.
The Transfer To window opens.
6 Select the log file categories that you want to include in the log file transfer. All the log files
associated with the selected categories will be transferred.
7 Click the OK button.
A transfer window opens and displays applicable warnings.
8 Click the Yes button to initiate the transfer.
A Save dialog box displays.
9 Specify a filename and location for the log file and click Save.
The Progress Update window opens. When the log files are transferred, the Transfer Complete window opens.
10 Click the OK button.
The log archive is saved in the location you specified.
Using the BCM450 Web Page to transfer log files
1 In your web browser, type the IP address of the BCM450 and click the Go button.
The login screen opens.
2 Log in to the BCM450 using the same username and password that you use to log into a
BCM450 using the Element Manager. The BCM450 Web page opens.
3 Click the Administrators Applications link. 4 Click BCM Logs. 5 Click the Retrieve Log Files link.
The Retrieve Log Files panel appears.
6 Click one of the three options for file transfer: Transfer to My Computer, Store on USB
Memory, or Send to.
7 If you select the Send to radio button, select a destination from the drop-down list, otherwise,
go to the next step.
8 Click Submit. The web page shows the status as Working; when complete, it shows Success. 9 Click the Click Here to Download Logs link.
The File Download screen opens.
10 Click the Save button.
The Save As screen opens.
11 Specify the location where you want to save the log file transfer, and enter a name for the file
in the File Name field.
12 Click the Save button.
The file is saved.
NN40160-700NN40160-700
Chapter 11 Frequently Asked Questions 93

How do I capture the current BCM450 configuration?

You can create a programming file that contains the current settings of all or part of your Element Manager data. These files can be saved in either HTML or Excel spreadsheet format. You can access the programming record in the same way you access any other HTML file or by using Excel, version 2002 or later, for the spreadsheet format.
A programming record that contains the factory default settings is available in Excel format from the BCM web page.
Note: It may take several hours to save programming records, depending on the size of the system. Nortel recommends that you saving programming records during periods of low system use.
Use the following procedure to capture the current programming record.
Capturing the current configuration
1 Select the item on the task navigation panel for which you want to sav e the data into an HTML
report or Excel workbook. An item can be a task item, task bullet, or a folder.
2 Click on Session > device IP address > Save Programming Record > Save Selected Data.
A warning dialog box appears; review the warning and click Yes. A Save dialog box then displays.
Figure 16 Save dialog box
3 In the Save: field choose the path where you want the file stored. 4 In the Files of type: field, choose the format in which you want to save the data (HTML or
Microsoft Excel spreadsheet).
5 Enter a File name. Nortel recommends that you make the current date and system name part of
the file name.
BCM450 Troubleshooting Guide
94 Chapter 11 Frequently Asked Questions
6 Click on Save.
Note: The Save All Data selection can take up to 45 minutes to complete. Your
computer must stay connected to the element during this time, as the Save All Data function is actively writing into the file specified until the function is
complete.

How do I find the BCM450 system health?

You can use the BCM Monitor to view information about system health. The Usage Indicators tab on the BCM Monitor displays real time information about the BCM450
system, including:
BCM450 system data, including CPU and memory use
resources used on the Media Card, including signaling channels, media channels, voice bus channels, and DSP resources
active telephony devices, such as IP trunks, IP sets. voice ports, and media gateways
The information is displayed as an absolute figure and as a percentage of the resource used. Use this procedure to access system health information.
Viewing the system health
1 Select Administration > Utilities > BCM Monitor and click the Launch BCM Monitor
button.
1 Select the Usage Indicators tab.

How do I show specific process states?

Use the following procedure to view specific process states.
Viewing specific process states
1 Select Administration > General > Service Manager.
The Service Manager page opens. Services are displayed in the Services table.

How do I verify current software revision?

Use the following procedure to view the current software revision.
NN40160-700NN40160-700
Chapter 11 Frequently Asked Questions 95
Verify the current software revision
1 Select Configuration > Sytem > Identification.

How do find the BCM450 System ID and Serial Number?

Use the following procedure to view the system ID and serial number.
Viewing the system ID and serial number
1 Select Administration > General > Hardware Inventory. 2 Select the BCM450 System tab.

Connectivity problems

This section answers the following question:
What is an Ethernet loop, and how do I avoid creating one? on page 96
BCM450 Troubleshooting Guide
96 Chapter 11 Frequently Asked Questions
BCM450
Hub / Hub /
Ethernet Loop
BCM450
Hub / Hub /
No Ethernet Loop

What is an Ethernet loop, and how do I avoid creating one?

The BCM450 does not support the Bridging Protocol Data Unit (BPDU), and therefore, you must be careful not to create Ethernet lops in the network while connected ot these two ports.
Figure 17 shows and Ethernet loop and how to avoid it.
Figure 17 Ethernet loops

IP addresses

This section answers the following questions:
Can I modify the IP address of the OAM port? on page 96
What are the default IP addresses of the BCM450 ports? on page 96

Can I modify the IP address of the OAM port?

You cannot change the IP address of the OAM port. You can use Element Manager to view the OAM port parameters.

What are the default IP addresses of the BCM450 ports?

NN40160-700NN40160-700
The default addresses of the OAM LAN port are:
IP address: 10.10.11.1
Subnet mask: 255.255.255.0
The default addresses of the customer LAN port are:
IP address: 192.168.2.2
Subnet mask: 255.255.254.0
Chapter 11 Frequently Asked Questions 97
BCM450 Troubleshooting Guide
98 Chapter 11 Frequently Asked Questions
NN40160-700NN40160-700
Chapter 12

Contacting Technical Support

If you have been unable to resolve an issue using the information and steps provided in this guide, use the information in this chapter to contact Nortel Technical Support. This chapter identifies all of the critical information that you must gather before contacting Nortel Technical Support.

Navigation

Gathering critical information on page 99
Getting Help from the Nortel Web site on page 100
Getting help over the phone from a Nortel Solutions Center on page 100
Getting help from a specialist by using an Express Routing Code on page 101
Getting help through a Nortel distributor or reseller on page 101
99

Gathering critical information

Before contacting Nortel Technical Support, you must gather information that can help the technical support personnel when troubleshooting. This section identifies all the critical information that should be gathered before contacting Nortel Technical Support.
You must attempt to resolve your problem using this troubleshooting guide. Contacting Nortel is a final step taken only when you have been unable to resolve the issue using the information and steps provided in this troubleshooting guide. Gather the following information before contacting Nortel Tech Support. Collecting this information helps Nortel analyze and address the reported issue.
Problem scenario:
— Detailed description of the problem — Expected Response (how you would expect the system to perform) — Actual Response (A detailed account of how the system actually performs) — Date and time when the problem started — Frequency of the problem — Is this a new installation? — Can you restore normal operation?
History:
— Have you recently changed or upgraded your system, your network, or a custom
application? For example, has any configuration or code been changed?
— What events can be identified prior to the fault: e.g. upgrade, new LAN, increased traffic,
new hardware?
— When were these changes made? Provide the date and time.
BCM450 Troubleshooting Guide
100 Chapter 12 Contacting Technical Support
— Who made these changes? Were the changes made by a partner or customer? Provide the
names of the individuals who made the changes.
Actions taken:
— Have you checked that the product’s software or firmware is a Current or Sustained
Release?
— Have you checked whether patches or maintenance releases are available that address this
issue?
— You hav e checked the solutions database for possible solutions (found on http://
www.nortel.com/cs)?
— Detailed description of your investigation to date, previous actions taken and outcomes.
Also provide Nortel Technical Support with the following information:
Provide a full list of patches that you have applied to your system
Have any additional information available , such network diagrams, diagnostic/error logs, and configuration files
Is remote access to the system available?

Getting Help from the Nortel Web site

The best way to get technical support for Nortel products is from the Nortel Technical Support Web site:
http://www.nortel.com/support This site provides quick access to software, documentation, bulletins, and tools to address issues
with Nortel products. More specifically, the site enables you to:
download software, documentation, and product bulletins
search the Technical Support Web site and the Nortel Knowledge Base for answers to technical issues
sign up for automatic notification of new software and documentation for Nortel equipment
open and manage technical support cases

Getting help over the phone from a Nortel Solutions Center

If you do not find the information you require on the Nortel Technical Support Web site, and have a Nortel support contract, you can also get help over the phone from a Nortel Solutions Center.
In North America, call 1-800-4NORTEL (1-800-466-7835). Outside North America, go to the following Web site to obtain the phone number for your region: www.nortel.com/callus
NN40160-700NN40160-700
Loading...