Nordyne M4RC Upflow, M4RL Downflow, M4RC, M4RL, M4RC054D-24B Installation Instructions Manual

...
GAS FURNACES
Installation Instructions
Single Stage Condensing Gas Furnaces
92.1% AFUE
M4RC Upfl ow Furnace
WARNING:
PROPOSITION 65 WARNING: This product contains chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product. Safety should always be the deciding factor when installing this product and using common sense plays an important role as well. Pay attention to all safety warnings and any other special notes highlighted in the manual. Improper installation of the furnace or failure to follow safety warnings could result in serious injury, death, or property damage.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/ service personnel for this type of equipment. Please read all instructions carefully before starting the installation. Return these instructions to the customer’s package for future
reference
.
M4RL Downfl ow Furnace
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could result in serious injury or property damage.
• Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
• Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbors phone. Follow the gas suppliers instructions.
• If you cannot reach your gas supplier, call
the fi re department.
DO NOT DESTROY.
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
TABLE OF CONTENTS
SAFETY INFORMATION .............................................3
REQUIREMENTS AND CODES ..................................4
GENERAL INSTRUCTIONS ........................................5
Manufacturer Warranty ............................................5
Combustion Air Quality ............................................5
Installation in a Garage ............................................ 5
Heating Load ...........................................................6
Clearances to Combustible Materials ......................6
COMBUSTION AIR REQUIREMENTS ........................6
General Information ................................................. 6
Installation in Confi ned Spaces ............................... 7
Air From Inside .................................................... 7
Outdoor Air from a Crawl Space or
Vented Attic .........................................................7
Outdoor Air Using Vertical Ducts ........................ 7
Outdoor Air Using Horizontal Ducts .................... 7
Air Directly Through an Exterior Wall .................8
Alternate Method of Providing air from
Outside ............................................................... 8
Installation in Unconfi ned Spaces ........................... 8
VENTING REQUIREMENTS ......................................10
Vent Pipe Length and Diameter ............................. 10
Vent Pipe Material ................................................. 11
Vent Pipe Installation ............................................. 11
Outdoor Terminations - Horizontal Venting ............ 11
Outdoor Terminations - Vertical Venting ................. 12
Vent Freezing Protection ....................................... 12
Condensate Disposal ............................................ 13
Concentric Vent Termination .................................. 13
Existing Installations .............................................. 13
CIRCULATING AIR REQUIREMENTS ...................... 14
Plenums and Air Ducts .......................................... 14
Return Air Connections .........................................14
Supply Air Connections ......................................... 15
Acoustical Treatments............................................ 15
FURNACE INSTALLATION ....................................... 15
General Requirements .......................................... 15
Requirements and Codes .....................................15
Upfl ow Furnace Installation .................................. 16
Downfl ow Furnace Installation .............................. 16
Alternate Attachment Method ........................... 18
Bottom Panel Removal .......................................... 19
Alternate Bottom Panel Removal ...................... 19
Pressure Switch Relocation .................................. 19
Inducer Assembly Rotation ...................................20
2
Direct Vent (2 - Pipe) Applications ......................... 20
Vent and Inducer Assembly Options ..................... 20
Accessories ..........................................................21
Finish Flange ....................................................21
Rubber Grommets ............................................21
Inline Drain Assembly .......................................21
PVC TEE, Reducer, and Hose Barbs ...............21
Condensate Drain Lines ...................................22
Filter Retainer Brackets ....................................22
Ventilaire™ Bracket...........................................22
Vent Couplings ..................................................23
Upfl ow Furnaces ...........................................23
Downfl ow Furnaces .......................................23
Alternate Vent Pipe Installation .............................23
GAS SUPPLY AND PIPING .......................................24
Leak Check ..........................................................24
High-Altitude Application .......................................24
Conversion to LP/Propane ....................................25
ELECTRICAL WIRING ...............................................29
Low Voltage Wiring ................................................29
Line Voltage Wiring................................................29
Grounding .............................................................29
Twinning ................................................................30
START-UP & ADJUSTMENTS ...................................31
Pre-Start Checklist ................................................31
Start-Up Procedures .............................................31
Verifying and Adjusting Input Rate ........................31
Verifying and Adjusting Temperature Rise ............31
Verifying Burner Operation ....................................31
Verifying Operation of the supply Air
Limit Switch ...........................................................32
OPERATING SEQUENCE .........................................32
Heating Cycle ........................................................32
Cooling Cycle ........................................................32
Fan Mode ..............................................................32
MAINTENANCE .........................................................32
Air Filters ...............................................................33
Blower Compartment ............................................33
Cleaning of Burners ..............................................33
Heat Exchanger and Burner Maintenance ............33
Lubrication ............................................................33
Vent System ..........................................................33
DESCRIPTION OF COMPONENTS ..........................34
TROUBLESHOOTING ...............................................34
FRENCH TRANSLATIONS ........................................35
FIGURES AND TABLES ............................................37
Figure 40 - Furnace Dimensions .......................37
Table 8 - Blower Performance Chart
Electrical Information ..............................................39
Figure 41 - Wiring Diagram ................................39
Gas Information ......................................................40
Table 9 ­Table 10 ­Table 11 - High Altitude Deration Chart for
Table 12 - Natural Table 13 - High Altitude Deration Chart for
Table 14 - High Altitude Deration Chart for
Venting Information .................................................43
Table 15 -
Figure 42 - Horizontal and Vertical Venting ........44
Figure 43 - Upfl ow Options .................................45
Figure 44 - Downfl ow Options ............................46
Location of Furnace Components ..........................47
Figure 45 - Upfl ow/Horizontal Gas Furnace
Components.....................................47
Figure 46 -
Components ....................................47
INSTALLATION/PERFORMANCE CHECKLIST ........48
Gas Flow Rates ...................................40
Gas Pipe Capacities ..........................40
Propane Gas .....................................41
Gas Heating Values ..............41
Nat. Gas - High Heating Values .........42
Nat. Gas - Low Heating Values ..........42
Vent Termination Clearances .............43
Downfl ow Gas Furnace
..................38
SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING:
The safety information listed below must be followed during the installation, service, and operation of this furnace. Failure to follow safety recommendations could result in possible damage to the equipment, serious per
injury or death
• Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
• Install this furnace in accordance to the minimum clearances to combustible materials listed in Table 1 (page 9).
• Provide adequate combustion and ventilation air to the furnace space as specifi ed on pages 6 - 9.
• Provide adequate clearances around the vent air intake terminal as specifi ed in Figures 6 - 9 (pages 12 - 13).
• Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specifi ed on Pages 10 - 13.
• Never test for gas leaks with an open fl ame. Use a commercially available soap solution to check all connections (page 24).
• This furnace is designed to operate with a maximum external pressure rise of 0.5 inches of water column. Consult Table 8 (page 38), and the rating plate for the proper circulating air fl ow and temperature rise.
NOTE: It is important that the duct system be designed
to handle the desired fl ow rate and external pressure rise. An improperly designed duct system can result in nuisance shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See page 14.
• This furnace may not be used for temporary heating of buildings or structures under construction.
.
sonal
3
REQUIREMENTS and CODES
This furnace must be installed in accordance with these instructions, all applicable local building codes and the current revision of the National Fuel Gas Code (NFPA54/ANSI Z223.1) or the Natural Gas and Propane Installation Code, CAN/CGA B149.1.
CE générateur d'air chaud doit être installé conformément aux instructions du fabricant et aux codes locaux. En l'absence de code local, respecter la norme ANSI Z223.,1, institulé National Fuel Gas Code ou les codes d'installation CAN/GCA-B149.
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 4.00 and 5.00 for installation of through – the – wall vented gas appliances as follows:
1. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfi ed:
a.) A carbon monoxide (CO) detector and alarm shall be
placed on each fl oor level where there are bedrooms. The detector shall comply with NFPA 720 (2005 Edition) and be mounted in the living area outside the bedroom(s).
b.) A (CO) detector shall be located in the room that
houses the appliance or equipment and shall:
• Be powered by the same electrical circuit as the appliance or equipment. Only one service switch shall power the appliance and the (CO) detector;
• Have battery back-up power;
Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and Approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR.
c.) A Product-approved vent terminal must be used,
and if applicable, a product-approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
d.) A metal or plastic identifi cation plate shall be mounted
at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of suffi cient size, easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment where the bottom of the vent terminal and the air intake is installed above four feet above grade the following requirements must be satisfi ed:
a.) A (CO) detector and alarm shall be placed on
each fl oor level where there are bedrooms. The detector shall comply with NFPA 720 (2005 Edition) and be mounted in the living area outside the bedroom(s).
b.) The (CO) detector shall:
Be located in the room that houses the appliance or equipment;
• Be hard-wired or battery powered or both.
• Shall comply with NFPA 720 (2005 Edition).
c.) A product-approved vent terminal must be used,
and if applicable, a product-approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
Additional information listed below is for reference purposes only and does not necessarily have jurisdiction over local or state codes. Always consult with local authorities before installing any gas appliance.
Combustion and Ventilation Air
• US: National Fuel Gas Code (NFGC), Air for Combustion and Ventilation
• CANADA: Natural Gas and Propane Installation Codes (NSCNGPIC), Venting Systems and Air Supply for Appliances
Duct Systems
• US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) Fundamentals Handbook
Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
Gas Piping and Gas Pipe Pressure Testing
• US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
• US: Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or American Gas Association, 400 N. Capitol, N.W., Washington DC 20001 or www.NFPA.org
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada
4
Safety
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B.
• Federal Manufactured Home Constructions & Safety Standard (H.U.D. Title 24, Part 3280.707[a][2])
• The Standard for Manufactured Home Installations (Manufactured Home Sites, Communities, and Set-Ups) ANSI A225.1 and/or CAN/CSA-2240 MH Series).
• Amer ican National Standard (ANSI-119.2/NFPA-501C) for all recreational vehicle installations.
• CANADA: CAN/CGA-B149.1 and .2–M00 National Standard of Canada. (NSCNGPIC)
GENERAL INSTRUCTIONS
Manufacturer Warranty, Owner’s Responsibilities
It is the sole responsibility of the homeowner to make certain the gas furnace has been correctly installed in the home, converted to the proper fuel (LP gas or Natural gas), and adjusted for proper operation.
A warranty certifi cate with full details is included with this furnace. However, NORDYNE will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, furnace adjustments, improper operating procedure on the part of the user, etc.
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a corrosive atmosphere.
To maximize heat exchanger life, the combustion air must be free of chemicals that can form corrosive acidic compounds in the combustion gases. The recommended source of combustion air is to use outdoor air. However, the use of indoor air in most applications is acceptable except as listed:
• If the furnace is a single pipe installation and installed in a confi ned space, it is required that the necessary combustion air come from the outdoors by way of attic, crawl space, air duct, or direct opening. See pages 6 - 9 for combustion air requirements.
• Installations in these locations may require outdoor air for combustion, due to chemical exposures:
Commercial buildings Buildings with indoor pools Furnaces installed in laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas
Some specifi c examples of service calls which cannot be included in warranty payments are:
• Converting the furnace to use another type of gas.
• Repairing duct work in the home found to be faulty.
• Correcting wiring problems in the electrical circuit supplying the furnace.
• Resetting circuit breakers, blown fuses or other switches.
• Correcting problems due to improper gas supply pressure to the furnace.
• Providing instructional training on how to light and operate the furnace.
• Correcting any problems caused by installation of an air conditioner, heat pump or other air comfort devices.
• Revising installation of the furnace fl ue assembly.
• Adjusting or calibrating of thermostat.
• Removing any construction debris which has fallen into fl ue system.
Carefully review these responsibilities with your manufactured housing dealer, service company, or gas supplier, so that there will be no misunderstanding at a later time.
• Exposure to the following substances in the combustion
air supply may require outdoor air for combustion:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon Tetrachloride Halogen type refrigerants Cleaning solvents (perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric Acid Cements and glues Antistatic fabric softeners Masonry acid washing materials
Installation in a Garage
WARNING:
Do not place combustible material on or against the furnace cabinet or within 6 inches of the vent pipe. Do not place combustible materials, including gasoline or any other fl ammable vapors and liquids, in the vicinity of the furnace.
5
This Gas-fi red furnace may be installed in a residential garage with the provision that the burners and igniter are located no less than 18 inches (457mm) above the fl oor. The furnace must be located or protected to prevent physical damage by vehicles.
Heating Load
This furnace should be sized to provide the design heating load requirement. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air Conditioning Engineers; or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace and/or vent to fail prematurely. In addition, the ductwork
should be appropriately sized to the capacity of the furnace to ensure its proper airfl ow rating. For installations above 2,000 ft., the furnace should have a sea level input rating large enough that it will meet the heating load after deration for altitude.
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada by CSA International for the minimum clearances to combustible material listed in Table 1 (page 9). To obtain model number and specifi c clearance information, refer to the furnace rating plate, located inside of the furnace cabinet.
Access for positioning and servicing the unit must be considered when locating unit. The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements.
Allow 30 inches minimum clearance from the front of the unit for servicing and positioning. However, 36 inches is strongly recommended.
COMBUSTION AIR REQUIREMENTS
General Information
Provisions must be made during the installation of this furnace that provide an adequate supply of air for combustion. NORDYNE condensing furnaces must be installed with outdoor combustion air piped directly to the furnace.
WARNING:
Furnace installation using methods other than those described in the following sections must comply with the National Fuel Gas Code (NFGC) and all applicable local codes.
• Requirements in Canada (B149.1) are structured differently. Consult with B149.1 and local code offi cials for Canadian installations.
• The M4 series gas furnace has been certifi ed for use in manufactured homes in the United States to the UL 307B standard and to ANSI Z21.47 CAN/CGA-2.3 in Canada and the United States. These furnaces may be installed in:
Manufactured Homes Recreational Vehicles, Park Models Manufactured Buildings Modular Homes / Buildings
• The M4 furnace is listed as a Direct Vent (2-pipe) forced air furnace (type FSP) for use with both natural and propane (LP) gases. NOTE: Direct vent appliances draw combustion air from the outdoors and vent combustion products back outside, isolating the entire system from the indoor space. It is important to make sure that the whole system is sealed and clearances to combustibles are maintained regardless of the installation being in a confi ned or unconfi ned space.
• The combustion air from the outside needs to be clear of chemicals that can cause corrosion. The inlet pipe should not be placed near corrosive chemicals such as those listed on page 5. severe corrosion in the furnace combustion system.
• Air openings on top of the furnace and in closet doors or walls must never be restricted. If the furnace is operated without adequate combustion air, the fl ame roll-out switch will open and turn off the gas supply to the burners. This safety device is a manually
reset switch. DO NOT install jumper wires across these switches to defeat their function or reset a switch without identifying and correcting the fault condition. If a switch must be replaced, use only the
correct sized part specifi ed in the Replacement Parts List provided online.
These chemicals can cause
CAUTION:
Exhaust fans, clothes dryers, fi replaces and other appliances that force air from the house to the outdoors can create a negative pressure inside the house, resulting in improper furnace operation or unsafe conditions such as fl ame roll out. It is imperative that suffi cient air exchange with the outdoors is provided to prevent depressurization. Additional information about how to test for negative pressure problems can be found in the NFGC.
• Instructions for determining the adequacy of an installation can be found in the current revision of the NFGC (ANSI Z223.1 / NFPA54). Consult local codes for special requirements. These requirements are for US installations as found in the NFGC.
6
Installation in Confi ned Spaces
A confi ned space is an area with volume less than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing combustion air from that space.
Furnace closets, small equipment rooms and garages are confi ned spaces. Furnaces installed in a confi ned space which supply heated air to areas outside the space must draw return air from outside the space and must have the return air ducts tightly sealed to the furnace.
The required sizing of these openings is determined by whether inside or outside air is used to support combustion, the method by which the air is brought to the space, and by the total input rate of all appliances in the space. In all cases, the minimum dimension of any combustion air opening is 3 inches.
Furnace
Alternate
Air Inlet
Vent or
Chimney
Ventilation Louvers (each end of attic)
Water Heater
Inlet Air
---------
---------
NOTE: Air openings shall
each have a free area of not less than one square inch per 4,000 Btuh of the total input rating of all equipment in the enclosure.
---------
Outlet Air
---------
Air From Inside If combustion air is taken from the heated space, the two openings must each have a free area of at least one square inch per 1,000 Btuh of total input of all appliances in the confi ned space, but not less than 100 square inches of free area. See Example and Figure 1.
Example:
If the combined input rate of all appliances is less than or equal to 100,000 Btuh, each opening must have a free area of at least 100 square inches. If the combined input rate of all appliances is 120,000 Btuh, each opening must have a free area of at least 120 square inches.
Vent or
Chimney
NOTES: Each opening must be at least 100 sq. in. or 1 sq. in. per 1,000 Btuh of total input rating, whichever is greater.
Openings must start at no more than 12 inches from the top and bottom of the enclosure.
Total Input Rating
(Btuh)
40,000 100 sq. In 12 inches 60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches 100,000 100 sq. In 12 inches 120,000 120 sq. In 13 inches 140,000 140 sq. In 14 inches 160,000 160 sq. In 15 inches
Water Heater
Minimum Free Area
(Each Opening)
12” Max.
Furnace
See
Notes
See
Notes
12” Max.
Round Duct
Diameter
Figure 1. Combustion Air Drawn from Inside
Outdoor Air from a Crawl Space or Vented Attic When the openings can freely exchange air with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btuh of total appliance input. The openings shall exchange directly, or by ducts, with the outdoor spaces (crawl or attic) that freely exchange with the outdoors. See Figure 2.
Ventilation Louvers For Unheated Crawl Space
Figure 2. Combustion Air Drawn from a Crawl
Space or Vented Attic
Outdoor Air Using Vertical Ducts If combustion air is taken from outdoors through vertical ducts, the openings and ducts must have a minimum free area of one square inch per 4,000 Btuh of total appliance input. Attics or crawl spaces must connect freely with the outdoors if they are the source of air for combustion and ventilation. See Figure 3.
Ventilation Louvers at each end of attic
Vent or
Chimney
Total Input Rating
(Btuh)
40,000 10 sq. In 4 inches 60,000 15 sq. In 5 inches
80,000 20 sq. In 5 inches 100,000 25 sq. In 6 inches 120,000 30 sq. In 6 inches 140,000 35 sq. In 7 inches 160,000 40 sq. In 8 inches
Attic
Insulation
Water Heater
Furnace
Minimum Free Area
(Each Opening)
Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Ducts must extend above attic insulation.
Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
12" Max
Round Duct
Diameter
Figure 3. Combustion Air Drawn from Outside
Through Vertical Ducts
Outdoor Air Using Horizontal Ducts If combustion air is taken from outdoors through horizontal ducts, the openings and ducts must have a minimum free area of one square inch per 2,000 Btuh of total appliance input. Ducts must have cross - sectional area at least as large as the free area of their respective openings to the furnace space. See Figure 4 (page 8).
7
Vent or
Chimney
Water Heater
Air Duct
Furnace
Air Ducts must be at least 1 sq. in. per 2,000 Btuh of total input rating.
Air Duct
Total Input Rating
(Btuh)
40,000 20 sq. In 5 inches 60,000 30 sq. In 6 inches
80,000 40 sq. In 7 inches 100,000 50 sq. In 8 inches 120,000 60 sq. In 9 inches 140,000 70 sq. In 10 inches 160,000 80 sq. In 10 inches
Minimum Free Area
(Each Opening)
Round Duct
Diameter
Alternate Method of Providing Air from Outside: If acceptable under local Codes, it is permitted to provide outside air using one opening (See NFGC).
Generally, confi ned spaces must have two openings in the space for combustion air. One opening must be within 12 inches of the ceiling, and the other must be within 12 inches of the fl oor. However, an alternative method recently adopted by the NFGC uses one opening within 12 inches of the top of the space. This method may be used if it is acceptable to the local codes.
The following conditions must be met:
1. The opening must start within 12” of the top of the
structure and connect with the out of doors through vertical or horizontal ducts or be ducted to a crawl or attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1 sq.
in. per 3,000 Btu per hour of the total input rating of all equipment located in the enclosure.
Figure 4. Combustion Air Drawn from Outside
Through Horizontal Ducts
Air Directly Through An Exterior Wall If combustion air is provided directly through an exterior wall, the two openings must each have free area of at least one square inch per 4,000 Btuh of total appliance input. See Figure 5.
Vent or
Chimney
-
-
-
-
-
See
-
-
-
-
See
Note
-
-
-
-
-
-
-
-
-
12"
Max
Water Heater
Minimum Free Area
(Each Opening)
Note
12" Max.
Total Input Rating
(Btuh)
40,000 10 sq. In 4 inches 60,000 15 sq. In 5 inches
80,000 20 sq. In 5 inches 100,000 25 sq. In 6 inches 120,000 30 sq. In 6 inches 140,000 35 sq. In 7 inches 160,000 40 sq. In 8 inches
NOTE: Each opening to outside must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Furnace
Round Duct
Diameter
3. The free area must not be less than the sum of all the areas of the vent connectors in the enclosure.
Installation in Unconfi ned Spaces
An unconfi ned space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will not require outside air for combustion. However, in homes built for energy effi ciency (low air change rates), it may be necessary to provide outside air to ensure adequate combustion and venting, even though the furnace is located in an unconfi ned space. See example.
Example:
A space with a water heater rated at 45,000 Btuh input and a furnace rated at 75,000 Btuh requires a volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to be considered unconfi ned. If the space has an 8 foot ceiling, the fl oor area of the space must be 750 square feet (6,000 / 8 = 750).
Figure 5. Combustion Air Drawn from Outside
Through an Exterior Wall
8
INSTALLATION CLEARANCES to COMBUSTIBLE MATERIALS
For UPFLOW, HORIZONTAL & DOWNFLOW FURNACES
Left Side ...................................0 Inches Vent ............................................. 1 Inch Top ...........................................1 Inches
Right Side ................................0 Inches Back .........................................0 Inches Front.......................................4 Inches
UPFLOW APPLICATION
TOP
DOWNFLOW APPLICATION
TOP
LEFT SIDE
BOTTOM
Allow 30 in. minimum clearance for servicing. Recommended clearance is 36 in.
NOTE: The furnace is listed for installation on combustible or non-combustible fl ooring. However, wood is the only combustible fl ooring allowed for installation.
Table 1. Minimum Clearances to Combustible Materials
RIGHT SIDE
WARNING:
LEFT SIDE
BOTTOM
RIGHT SIDE
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being
placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed with each individual appliance connected to the venting system being placed in operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223. 1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage,
corrosion and other defi ciencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fi replace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the fl ame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers and any other gas-fi red burning appliance to their previous conditions of use.
9
VENTING REQUIREMENTS
WARNING:
This furnace must not be vented with other appliances, even if that appliance is of the condensing type. Common venting can result in severe corrosion of other appliances or their venting and can allow combustion gases to escape through such appliances or vents. Do not vent the furnace to a fi replace chimney or building chase.
Upon completion of the furnace installation, carefully inspect the entire fl ue system both inside and outside the furnace to assure it is properly sealed. Leaks in the fl ue system can result in serious personal injury or death due to exposure of fl ue products, including carbon monoxide.
• This furnace must be vented in compliance with the current revision of the National Fuel Gas Code (ANSI-Z223.1/NFPA54) and the instructions provided below. Consult local codes for special
requirements.
• In Canada, venting shall conform to the requirements of the current (CAN/CGA B149.1 or .2) installation codes.
Consult local codes for special requirements.
This furnace is classifi ed as a “Category IV” appliance, which requires special venting materials and installation procedures. This type of appliance operates with positive vent pressure and therefore requires the furnace to be vented to the outdoors and thoroughly sealed. They also produce liquid condensate, which is slightly acidic and
can cause severe corrosion of ordinary venting materials. Furnace operation can be adversely affected by restrictive vent and combustion air piping.
Vent Pipe Length and Diameter
In order for the furnace to operate properly, the combustion air and vent piping must not be excessively restrictive.
• The venting system should be designed to have the minimum number of elbows or turns.
• All horizontal runs must slope upwards from the furnace at 1/4 inch minimum per running foot of vent.
• Transition to the fi nal vent diameter should be done as close to the furnace outlet as practical.
• Always use the same size or a larger pipe for combustion air that is used for the exhaust vent.
Table 2 specifi es the maximum allowable pipe length for vent and combustion air for a furnace of known input rate, when installed with piping of selected diameter and number of elbows. To use the table, the furnace input rate, the centerline length and the number of elbows on each pipe must be known.
When estimating the length of vent runs, consideration must be made to the effect of elbows and other fi ttings. This is conveniently handled using the idea of “equivalent length”. This means the fi ttings are assigned a linear length that accounts for the pressure drop they will cause. For example: a 2” diameter, long radius elbow is worth the equivalent of 2.5 feet of linear run. A 90 degree tee is worth 7 ft.
The equivalent lengths of tees and various elbows are listed in Table 2. Measure the linear length of your vent run and then add in the equivalent length of each fi tting. The total length, including the equivalent fi tting lengths, must be less than the maximum length in the table.
Furnace
(BTU)
54,000 Upfl ow 90 90
72,000 Upfl ow 90 90
90,000
108,000 Upfl ow 90 90
1. The length of 2” pipe needed between the inducer and the exit hole (top of cabinet) is 8 3/4” for upfl ow models and 16” for downfl ow models.
2. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3 inch long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 8ft for each 3” tee.
3. Two 45 degree elbows are equivalent to one 90 degree elbow.
4. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.
10
FURNACE
INSTALLATION
Upfl ow 90 90
Downfl ow 90 90
SINGLE PIPE LENGTH (FT.)
with 1 long radius elbow
(See Notes)
OUTLET
3” Diameter
NOTES:
Table 2. Vent Pipe Lengths
DUAL VENT PIPE LENGTH (FT.)
with 1 long radius elbow on each pipe (See
Notes)
INLET/OUTLET
3” Diameter
Condensing furnace combustion products have very little buoyancy, so Table 2 is to be used without consideration of any vertical rise in the piping.
Vent Pipe Material
Vent and combustion air pipe and fi ttings must be one of the following materials in the list and must conform to the indicated ANSI/ASTM standards. Cement must conform to ASTM Standard D2564 for PVC and Standard D2235 for ABS. PVC Primer must meet standard ASTM F656. When joining PVC piping to ABS, use PVC solvent cement. (See procedure specifi ed in ASTM Standard D3138).
Material ...............................................Standard
Schedule 40PVC ....................................D1785
PVC-DWV ...............................................D2665
SDR-21 & SDR-26 ..................................D2241
ABS-DWV ...............................................D2661
Schedule 40 ABS ....................................F628
Foam/Cellular Core PVC ........................F891
In Canada, all plastic vent pipes and fi ttings including any cement, cleaners, or primers must be certifi ed as a system to ULC S636. However, this requirement does not apply to the fi nish fl anges or piping internal to the furnace.
Vent Pipe Installation
CAUTION:
Combustion air must not be drawn from a corrosive atmosphere.
This furnace has been certifi ed for installation with zero clearance between vent piping and combustible surfaces. However, it is good practice to allow space for convenience in installation and service.
• The quality of outdoor air must also be considered. Be sure that the combustion air intake is not located near a source of solvent fumes or other chemicals which can cause corrosion of the furnace combustion system. See list of substances on page 5.
• Route piping as direct as possible between the furnace and the outdoors. Longer vent runs require larger diameters. Vent piping must be sloped upwards 1/4” per foot in the direction from the furnace to the terminal. This is to ensure that any condensate fl ows back to the condensate disposal system.
• The combustion air intake and the vent exhaust must be located in the same atmospheric pressure zone. This means both pipes must exit the building through the same portion of exterior wall or roof as shown in Figures 6 - 9 (page 12 - 13) and Figure 41 (page 44).
• Piping must be mechanically supported so that its weight does not bear on the furnace. Supports must be at intervals no greater than 5 ft. Supports may be at shorter intervals if necessary to ensure that there are no sagging sections that can trap condensate.
Outdoor Terminations - Horizontal Venting
Vent and combustion air intake terminations shall be installed as depicted in Figures 6 - 7 (page 12) and in accordance with these instructions:
• Vent termination clearances must be consistent with the NFGC, ANSI 2223.1/NFPA 54 and/or the CSA B149.1, Natural Gas and Propane Installation Code.
• All minimum clearances must be maintained to protect building materials from degradation by fl ue gases as shown in Figure 7.
• Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes. The minimum distance from any door, open window, or air gravity inlet is 1ft. below, 1ft. horizontally, or 1ft. above. In Canada, CSA B149.1 takes precedence over these instructions. Table 15 (page 43) lists the necessary distances from the vent termination to windows and building air intakes.
• The vent termination shall be located at least 4 ft. horizontally from any electric meter, gas meter, regulator and any relief equipment. These distances apply ONLY to U.S. installations. In Canada, the Canadian Fuel Gas Code takes precedence over these instructions.
• Do not install the vent terminal such that exhaust is directed into window wells, stairwells, under decks or into alcoves or similar recessed areas, and do not terminate above any public walkways.
• If venting horizontally, a side wall vent kit is available according to the pipe diameter size of the installation. For 2 inch pipe use side wall vent kit #904617, and for 3 inch pipe use kit #904349. Please follow the
instructions provided with the kit.
• When the vent pipe must exit an exterior wall close to the grade or expected snow level where it is not possible to obtain clearances shown in Figure 6, a riser may be provided as shown in Figure 8 (page 12). Insulation is required to prevent freezing of this section of pipe. For vent freezing protection, see page 13.
WARNING:
The combustion air vent and exhaust vent must be confi gured as shown in Figure 9. Improper vent terminations can cause the recirculation of fl ue gases which may result in furnace vibration. In severe cases, the furnace will cycle, due to the intermittent contact between the fl ame and the fl ame sensor. If you notice these oscillations occurring, check the vent confi guration to make sure the exhaust vent does not have a 90 degree termination.
11
l
Mounting Kit
Faceplate Secured
to Wall with Screws
Typical Both Pipes
Combustion
Air Inlet
Exhaust Vent Left Side Option
Exhaust
Inlet
12" Min. to Maximum
Expected Snow Level
Typical Both Pipes
90°
Elbow
Figure 6. Exhaust and Combustion Air
Pipe Clearances
9 in.
Note 3
4 ft.
4ft.
Notes 2 & 5
Notes
2 & 3
NOTES:
1. All dimensions shown are minimum requirements.
2. Exterior vent terminations must be located at least 12” above the maximum expected snow level.
3. Mechanical draft vent terminal
4. Direct vent terminal - more than 50,000 Btuh.
5. Direct vent terminal - less than 50,000 Btuh.
12 in.
12 in.
Notes 2 & 4
Less
than
8" min. 36" max.
Both Sides
Exhaust Vent
Right Side Option
10 ft.
Note 3
3 ft.
Forced Air Inlet
• For optimal performance, vent the furnace through a wall
that experiences the least exposure to winter winds.
• Termination kits consist of two face plates and an
insulating gasket to seal the exterior surface.
• The hole in the wall must be sized closely to the
diameter of the pipe.
• The pipe that penetrates the wall should be long
enough that it can be held in place by standard close fi tting couplings.
• Face plates are secured to both sides of the wall by
the couplings, and the gasket is retained against the wall by the exterior face plate.
• Face plates must be fastened to the wall. Exterior face
plates must be fl ashed to prevent water infi ltration.
If termination kits are not used, these requirements must be followed:
• The hole size cut through the exterior wall is smaller
than the outside diameter of the couplings.
• The vent pipe extends through the wall approximately
1" and the gap between the wall and pipe is sealed.
• Couplings are applied to the vent pipe on the interior
and exterior sides of the wall. NOTE: This insures the pipe can not be pushed or pulled through the wall.
• The combustion air inlet pipe must have a 90 degree
termination elbow, and pointed downwards as shown in Figure 6 & Figure 9 (page 13).
Outdoor Terminations - Vertical Venting
Termination spacing requirements from the roof and from each other are shown in Figure 9.
• The roof penetration must be properly fl ashed and
waterproofed with a plumbing roof boot or equivalent fl ashing.
• The combustion air intake must be provided with an
elbow opening downward.
Vent and combustion air piping may be installed in an existing chimney which is not in use provided that:
Figure 7. Vent Locations
Vent Configuration to Provide 12" Minimum height above Snow Level.
Outside Wall
Figure 8. Alternate Horizontal Vent Installation
12
12" Min.
19" Max.
Support
1/2" Armaflex Insulation or Equivalent (if required)
12" Above Maximum Expected Snow Leve
• Both the exhaust vent and air intake run the length of
the chimney.
• The top of the chimney is sealed and weatherproofed.
• The termination clearances shown in Figure 9 are
maintained.
• No other gas fi red or fuel-burning equipment is vented
through the chimney.
Vent Freezing Protection
• When the vent pipe is exposed to temperatures below
freezing (i.e., when it passes through unheated spaces, chimneys, etc.) the pipe must be insulated with 1/2 inch thick sponge rubber insulation, Armafl ex-type insulation or equivalent. Insulating pipe is important to avoid condensate icing.
• Table 3 (page 13) lists the maximum length of fl ue pipe
that can travel through an unconditioned space or an exterior space. The total vent length must not exceed
the lengths noted in Table 2 (page 10). For Canadian installations please refer to the Canadian Installation Code (CAN/CGA-B149.1 or 2) and/or local codes.
• For extremely cold climates or conditions of short furnace cycles (i.e. set back thermostat conditions), the last 18 inches of vent pipe can be reduced from 3” to 2-1/2”, 3” to 2” or 2” to 1-1/1” if the total vent length is at least 15 feet in length and the vent is sized in accordance with Table 2. The length of the 2 inch pipe must not be longer than 18 inches. Smaller vent pipes are less susceptible to freezing, but must not be excessively restrictive.
• To prevent debris or creatures from entering the combustion system, a protective screen may be installed over the combustion air intake opening. The screens hole size must be large enough to prevent air restriction
90° Elbow
12” Above Maximum
Expected Snow Level
(Typ. Both pipes)
Exhaust Vent
Combustion Air
8" Min.
36" Max.
Plumbing Vent
Roof Boot
(Typ. Both Pipes)
Figure 9. Vertical Vent Termination
Maximum Flue Pipe Length
Winter Design
Temperature
20 45 70
02070
-20 10 60
* = Insulation thickness greater than 3/8 inch, based on an R value of 3.5 (ft x F x hr) / (BTU x in.)
Without Insulation
in Unconditioned and
Exterior Spaces
With Insulation
(feet)
(feet)*
After the condensate lines are J-trapped, they may be combined together when routed to the drain. Avoid areas where condensate drainage may cause problems by dropping onto planters, patios, etc.
NOTE: Industry research studies indicate that when condensate is routed to an active drain, household detergents, etc., buffer its acidity. If the drain is not actively used or if codes require, obtain a neutralizer kit (usually contains limestone). Proper drains and connections to the condensate tubing are required as NORDYNE cannot be held responsible for water leakage which occurs due to loose hose connections or improperly sealed drain line pipes.
Concentric Vent Termination
A concentric vent termination is approved for use with these furnaces. Please follow the installation instructions provided with the kit for proper installation.
Existing Installations
When an existing furnace is removed from a vent system serving other appliances, the existing vent system may not be sized properly to vent the remaining appliances (Example: water heater). An improperly sized venting system can result in the formation of condensate, leakage, or spillage. The existing vent system should be checked to make sure it is in compliance with NFGC, ANSI Z223.1, or CAN/CGA B149 and must be brought into compliance before installing the furnace.
NOTE: If replacing an existing furnace, it is possible you will encounter an existing plastic venting system that is subject to a Consumer Product Safety Commission recall. The pipes involved in the recall are High Temperature Plastic Vent (HTPV). If your venting system contains these pipes DO NOT reuse this venting system! This recall does not apply to other plastic vent pipes, such as white PVC or CPVC. Check for details on the CPSC website or call their toll-free number (800) 758-3688.
Table 3. Vent Protection
Condensate Disposal
The method for disposing of condensate varies according to local codes. Consult your local code or authority having jurisdiction. Neutralizer kit P/N 902377 is available for use with this furnace. Please follow the instructions
provided with the kit.
This furnace has multiple options for positioning the vent pipe as described in the Vent and Inducer Assembly Options section (page 20). Each of the condensate drain lines must be J-trapped using fi eld supplied parts.
13
CIRCULATING AIR REQUIREMENTS
WARNING:
Do not allow combustion products to enter the circulating air supply. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.
All return ductwork must be secured to the furnace with sheet metal screws. For installations in confi ned spaces, all return ductwork must be adequately sealed. When return air is provided through the bottom of the furnace, the joint between the furnace and the return air plenum must be air tight.
The surface that the furnace is mounted on must provide sound physical support of the furnace with no gaps, cracks or sagging between the furnace and the fl oor or platform.
Return air and circulating air ductwork must not be connected to any other heat producing device such as a fi replace insert, stove, etc. This may result in fi re, explosion, carbon monoxide poisoning, personal injury, or property damage.
Plenums and Air Ducts
• Plenums and air ducts must be installed in accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems (NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning Systems (NFPA No. 90B).
• Table 8 (page 38) contains the maximum airfl ow and temperature rise data for each furnace input rate. NOTE: If the maximum airfl ow is 1,600 CFM or more, it is recommended that two openings be used for return air on upfl ow furnaces. Downfl ow furnaces can only use one return opening.
• It is recommended that the outlet duct contain a removable access panel. The opening should be accessible when the furnace is installed in service and shall be of a size that smoke or refelcted light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The cover for the opening shall be attached in such a manner as to prevent leaks.
• If outside air is used as return air to the furnace for ventilation or to improve indoor air quality, the system must be designed so that the return air is not less than 60° F (15° C) during operation. If a combination of indoor and outdoor air is used, the ducts and damper system must be designed so that the return air supply
14
to the furnace is equal to the return air supply under normal, indoor return air applications.
• When a cooling system is installed which uses the furnace blower to provide airfl ow over the indoor coil, the coil must be installed downstream (on the outlet side) of the furnace or in parallel with the furnace.
• If a cooling system is installed in parallel with the furnace, a damper must be installed to prevent chilled air from entering the furnace and condensing on the heat exchanger. If a manually operated damper is installed, it must be designed so that the furnace will not operate when the damper is in the cooling position or when in heating position, the cooling system is inoperable.
• It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant. Requirements for sealing ductwork vary from region to region. Consult with local codes for requirements specifi c to your area.
Return Air Connections
In applications where the supply ducts carry heated air to areas outside the space where the furnace is installed, the return air must be delivered to the furnace by duct(s) secured to the furnace casing, running full size and without interruption.
• Upfl ow furnaces draw the return air from the base of the furnace. A stand or return air duct must be supplied to the furnace to provide the required return air.
• Downfl ow models draw the return air from the top of the furnace. The minimum required clearance to the top of the furnace is detailed on the furnace rating plate. Additional clearance may be required depending upon fi lter accessibility.
For each U.S.A. application, the home manufacturer shall comply with all of the following conditions to have acceptable return air systems for closet installed forced air heating appliances:
• Regardless of the location, the return air opening into the closet shall not be less than specifi ed in the appliance’s listing.
• Means shall be provided to prevent inadvertent closure by a fl at object placed over the return air opening when it is located in the fl oor of the closet (versus the vertical front or side wall).
• The cross-sectional area of the return duct system leading into the closet shall not be less than 390 square inches.
• The total free area of openings in the fl oor or ceiling registers serving the return air duct system must be at least 352 sq. in. At least one register should be located where it is not likely to be covered by carpeting, boxes and other objects.
• Materials located in the return duct system must have a fl ame spread classifi cation of 200 or less. This includes a closet door if the furnace is in a closet.
• Noncombustible pans having 1" upturned fl anges are
A Single trunk duct
B
Dual trunk duct w/crossover connector
C
Transition duct w/branches
located beneath openings in a fl oor duct system.
• Wiring materials located in the return duct system shall conform to Articles 300-22 of the National Electrical Code (ANSI C1/NFPA-70).
• Gas piping is not run in or through the return duct system.
• Test the negative pressure in the closet with the air­circulating fan operating at high speed and the closet closed. The negative pressure is to be no more negative than minus 0.05 inch water column.
• Air conditioning systems may require more duct, register and open louver area to obtain necessary airfl ow. Use NORDYNE’s certiduct program to determine proper duct size for A/C.
• For floor return systems, the manufactured home manufacturer shall affi x a prominent marking on or near the appliance where it can be easily read when the closet door is open. The marking shall read:
CAUTION:
HAZARD OF ASPHYXIATION: Do not cover or restrict return air opening.
Supply Air Connections
For proper air distribution, the supply duct system must be designed so that the static pressure measured external to the furnace does not exceed the listed static pressure rating shown on the furnace rating plate. The supply
air must be delivered to the heated space by duct(s) secured to the furnace casing, running full size and without interruption.
Three typical distribution systems are shown in Figure 10. The location, size, and number of registers should be selected on the basis of best air distribution and fl oor plan of the home.
noise eminating from the furnace. These treatments can produce a quieter installation, particularly in the heated space. However, they can increase the pressure drop in the duct system. Care must be taken to maintain the proper maximum pressure rise across the furnace, temperature rise and fl ow rate. This may mean increasing the duct size and/or reducing the blower speed. These treatments must be constructed and installed in accordance with NFPA and SMACNA construction standards. Consult with local codes for special requirements. For best sound performance, install all the needed gaskets and grommets around penetrations into the furnace, such as for electrical wiring.
FURNACE INSTALLATION
*RC series gas furnaces are shipped ready for installation in the upfl ow position with upfl ow return air. *RL series gas furnaces may only be used for downfl ow operation. See Table 1 (page 9) for the required clearances needed to move the furnace to its installation point (hallways, doorways, stairs, etc).
General Requirements
• The furnace must be leveled at installation and attached
to a properly installed duct system. Do not use the back of the furnace for return air. See page 14 for circulating requirements.
• The furnace must be installed so that all electrical components are protected from water.
• The dimensions of the room or alcove must be able to accommodate the overall size of the furnace and the installation clearances listed in Table 1.
• The furnace must be installed upstream from a refrigeration system.
• The plenum attached to the A/C coil box and ductwork within 3 ft. of the furnace must be installed so that surfaces are at least 1/4” from combustible construction.
• The cabinet plug must always be used to close the hole in the side of the furnace when rotating the inducer.
• Upfl ow and downfl ow models must be installed with the Nordyne A/C coil box which are listed according to the cabinet size of the furnace: “B” cabinet - 920169, “C” cabinet - 920171, and “D” cabinet - 920172.
Figure 10. Typical Supply Duct System
Acoustical Treatments
Damping ducts, fl exible vibration isolators, or pleated media-style fi lters on the return air inlet of the furnace may be used to reduce the transmission of equipment
Requirements and Codes
The installer must be familiar with and comply with all local codes and regulations applicable to the installation of heating appliances and related equipment. In the absence of local codes, the installation must conform with these instructions and the current provisions of one or more of the following standards:
• Federal Manufactured Home Constructions & Safety Standard (H.U.D. Title 24, Part 3280.707[a][2])
• The Standard for Manufactured Home Installations (Manufactured Home Sites, Communities, and Set­Ups) ANSI A225.1 and/or CAN/CSA-2240 MH Series).
• American National Standard (ANSI-119.2/NFPA-501C) for all recreational vehicle installations.
15
Loading...
+ 33 hidden pages