Downfl ow, Direct Vent (Sealed Combustion)
Forced Air Gas & Oil Furnaces
Series M1B, M1M & M5S
For installation in:
• Manufactured Homes
• Recreational Vehicles, Park Models,
& Manufactured Buildings
• Modular Homes / Buildings
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly
could result in serious injury or property
damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or the
gas supplier.
• Do not store or use gasoline or other
fl ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call
the fi re department.
AVERTISSEMENT
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de
sécurité pourrait entraîner des blessures
graves, la mort ou des dommages matériels.
• L’installation et l’entretien doivent être
effectués par un installateur qualifi é, un
organisme de service ou le fournisseur de
gazstaller, service agency or the gas supplier.
• Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables
dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique;
n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de
gaz en employant le téléphone d’un voisin.
Respecter à la lettre les instructions du
fournisseur de gaz.
• Si personne ne répond, appeler le service des
incendies.
DO NOT DESTROY THIS MANUAL. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Page 2
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .......................3
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.
WARNING:
Do not use this appliance if any part has been
submerged under water. Immediately call a
qualifi ed service technician to inspect the
appliance and to replace any part of the control
system and any gas control that has been
submerged underwater.
WARNING:
The safety information listed below must be
followed during the installation, service, and
operation of this furnace. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious personal
injury or death.
WARNING:
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death.
Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance. Storage of or use of gasoline
or other fl ammable vapors or liquids in the
vicinity of this or any appliance can result in
serious injury or death.
AVERTISSEMENT:
RISQUE D’INCENDIE ET D’EXPLOSION
Risque de blessures graves ou de mort.
Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables
dans le voisinage de cet appareil, ni de tout
autre appareil. Le fait d’entreposer ou d’utiliser
de l’essence ou d’autres liquides ou vapeurs
infl ammables à proximité de cet appareil ou de
tout autre appareil peut causer des blessures
graves ou la mort.
REQUIREMENTS & CODES
• This furnace must be installed in accordance with
these instructions, all applicable local building codes
and the current revision of the National Fuel Gas Code
(NFPA54/ANSI Z223.1) or the Natural Gas and Propane
Installation Code, CAN/CGA B149.1.
• CE générateur d’air chaud doit être installé conformément aux instructions du fabricant et aux codes locaux.
En l’absence de code local, respecter la norme ANSI
Z223.,1, institulé National Fuel Gas Code ou les codes
d’installation CAN/GCA-B149.
• Use only with type of gas approved for this furnace.
Refer to the furnace rating plate.
• Install this furnace in accordance to the minimum
clearances to combustible materials listed in Table 1
(page 6).
• Provide adequate combustion and ventilation air to the
furnace space as specifi ed on page 23. Do not block
or obstruct air openings on the furnace, air openings
to the area where the furnace is installed, or the space
around the furnace.
• Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system, as
specifi ed on pages 11 - 14.
• Never test for gas leaks with an open fl ame. Use a
commercially available soap solution to check all
connections (page 17).
• This furnace is designed to operate with a maximum
external pressure rise of 0.5 inches of water column.
Consult Table 12 (page 31) and the rating plate for the
proper circulating air fl ow and temperature rise.
NOTE: It is important that the duct system be designed
to handle the desired fl ow rate and external pressure
rise. An improperly designed duct system can result in
nuisance shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace
to areas outside the space containing the furnace, the
return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space
containing the furnace. See pages 8 - 10.
• This furnace may not be used for temporary heating of
buildings or structures under construction.
• The Commonwealth of Massachusetts requires
compliance with regulation 248 CMR 4.00 and 5.00 for
installation of through – the – wall vented gas appliances
as follows:
3
Page 4
1. For direct-vent appliances, mechanical-vent heating
appliances or domestic hot water equipment, where
the bottom of the vent terminal and the air intake is
installed below four feet above grade the following
requirements must be satisfi ed:
a.) A carbon monoxide (CO) detector and alarm
shall be placed on each fl oor level where there are
bedrooms. The detector shall comply with NFPA 720
(2005 Edition) and be mounted in the living area
outside the bedroom(s).
b.) A (CO) detector shall be located in the room that
houses the appliance or equipment and shall:
• Be powered by the same electrical circuit as the
appliance or equipment. Only one service switch
shall power the appliance and the (CO) detector;
• Have battery back-up power;
• Meet ANSI/UL 2034 Standards and comply with
NFPA 720 (2005 Edition); and Approved and listed
by a Nationally Recognized Testing Laboratory as
recognized under 527 CMR.
c.) A Product-approved vent terminal must be used,
and if applicable, a product-approved air intake must
be used. Installation shall be in strict compliance
with the manufacturer’s instructions. A copy of the
installation instructions shall remain with the appliance
or equipment at the completion of the installation.
d.) A metal or plastic identifi cation plate shall be
mounted at the exterior of the building, 4 feet directly
above the location of vent terminal. The plate shall
be of suffi cient size, easily read from a distance of
eight feet away, and read “Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical vent heating
appliances or domestic hot water equipment where
the bottom of the vent terminal and the air intake is
installed above four feet above grade the following
requirements must be satisfi ed:
a.) A (CO) detector and alarm shall be placed on each
fl oor level where there are bedrooms. The detector
shall comply with NFPA 720 (2005 Edition) and be
mounted in the living area outside the bedroom(s).
b.) The (CO) detector shall:
• Be located in the room that houses the appliance
or equipment;
• Be hard-wired, battery powered or both.
• Shall comply with NFPA 720 (2005 Edition).
c.) A product-approved vent terminal must be used,
and if applicable, a product-approved air intake must
be used. Installation shall be in strict compliance
with the manufacturer’s instructions. A copy of the
installation instructions shall remain with the appliance
or equipment at the completion of the installation.
Additional information listed below is for reference purposes only and
does not necessarily have jurisdiction over local or state codes. Always
consult with local authorities before installing any gas appliance.
Combustion & Ventilation Air
• US: National Fuel Gas Code (NFGC), Air for Combustion and
Ventilation
• CANADA: Natural Gas and Propane Installation Codes
(NSCNGPIC), Venting Systems and Air Supply for Appliances
Duct Systems
• US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors
National Association (SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE)
Fundamentals Handbook
Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
Gas Piping & Gas Pipe Pressure Testing
• US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
• US: Current edition of the NFGC and the NFPA 90B. For copies,
contact the National Fire Protection Association Inc., Batterymarch
Park, Quincy, MA 02269; or American Gas Association, 400 N.
Capitol, N.W., Washington DC 20001 or www.NFPA.org
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA
International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario,
M9W 1R3 Canada
Safety
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the Installation
Standards, Warm Air Heating and Air Conditioning Systems ANSI/
NFPA 90B.
• Federal Manufactured Home Constructions & Safety Standard
(H.U.D. Title 24, Part 3280.707[a][2])
• The Standard for Manufactured Home Installations (Manufactured
Home Sites, Communities, and Set-Ups) ANSI A225.1 and/or CAN/
CSA-2240 MH Series).
• American National Standard (ANSI-119.2/NFPA-501C) for all
recreational vehicle installations.
• CANADA: CAN/CGA-B149.1 and .2–M00 National Standard of
Canada. (NSCNGPIC)
4
Page 5
GENERAL INFORMATION
CAUTION:
• Do Not alter or modify this furnace or any of
its components.
• Never attempt to repair damaged or inoperable
components. This may cause unsafe operation,
explosion, fi re and/or asphyxiation.
• If furnace malfunctions or does not operate
properly, contact a qualifi ed service agency or
gas utility for assistance.
Manufacturer Warranty - Owner’s
Responsibilities
A warranty certifi cate with full details is included with these
instructions. Carefully review these responsibilities with
your manufactured housing dealer, service company or
gas supplier. It is the sole responsibility of the homeowner
to make certain the gas furnace has been correctly set
up and converted to the proper fuel (L.P. gas or Natural
gas) and adjusted to operate properly. All gas furnaces are
manufactured for Natural gas and must be fi eld converted
when using L.P. gas.
NORDYNE will not be responsible for any costs found
necessary to correct problems due to improper setup,
improper installation, furnace adjustments, improper
operating procedure on the part of the user, etc. Some
specifi c examples of service calls which cannot be included
in warranty payments are:
• Converting the furnace to use another type of gas.
• Repairing duct work in the home found to be faulty.
• Correcting wiring problems in the electrical circuit
supplying the furnace.
• Resetting circuit breakers, blown fuses or other switches.
• Correcting problems due to improper gas supply
pressure to the furnace.
• Providing instructional training on how to light and
operate the furnace.
• Furnace problems caused by installation of an air
conditioner, heat pump or other air comfort devices.
• Adding a Roof Jack extension because of unusual wind
and/or snow conditions.
• Revising installation of the furnace fl ue assembly (Roof
Jack).
• Adjusting or calibrating of thermostat.
• Any construction debris which falls into fl ue system.
Minimum Clearances
This heating appliance must be installed with clearances
not less than the minimums listed in Table 1. This furnace
must be installed with ample clearance for easy access to
the air fi lter, blower assembly, burner assembly, controls,
and vent connections. See Figures 1 - 3 (page 6).
• The dimensions of the room or alcove must be able to
accommodate the overall size of the furnace and the
installation clearances listed in Table 1 and in Figure 4
(page 6).
• Alcove installations: minimum 18” clearance at front
of furnace shall be provided for future servicing. A
removable access panel should be installed between
top of the furnace door frame and the ceiling.
• Closet installations must use a louvered door having
a minimum free area of 235 in2 when located 6” from
furnace or 390 in2 for 5 ton ready M1/M5 furnaces. For
special clearance between 1” - 6”, requirements are a
louvered door with a minimum of 250 in2 free area, with
the openings in the closet door in line with the louvered
openings in the furnace door. A fully louvered closet
door may be used. See Circulating Air Requirements
(page 7).
• The furnace must be kept free and clear of insulating
material. Examine the furnace area when the furnace is
installed or when insulation is added. Insulating material
may be combustible.
Applications
M1 Series gas and M5 Series oil furnaces are listed direct
vent (sealed combustion), downfl ow heating appliances
for manufactured (mobile) homes, recreational vehicles,
and for use in residential/modular/commercial construction.
The furnace must be located so that venting can be
properly achieved.
Air conditioning may be added to structures with M1/M5
series furnaces using air conditioning or conventional
units. This Installation Instruction manual includes
special requirements for incorporation of air conditioning
equipment to the M1/M5 series of furnaces. See Table
12 (page 31).
Multi-speed blower assemblies shown in Table 2 (page 6),
have been certifi ed for fi eld installation in M1/M5 Series
furnaces.
Unit Location
• The furnace shall be appropriately located to the supply
and return air distribution system (page 7). Sides and
back of the furnace may be enclosed by wall framing.
See Minimum Clearances and Figures 1- 3 (page 6).
• The fur nace installation is only intended for free air return
through the furnace door louvers. DO NOT connect a
ducted return air system directly to the furnace. Improper
installation may create a hazard and damage equipment,
as well as void all warranties.
• Furnace may be installed on combustible fl ooring when
using NORDYNE Duct Connectors. See pages 8 - 10.
• When installed in a residential garage, the furnace must
be positioned so the burners and the source of the
ignition are located no less than 18 inches above the
fl oor and protected from physical damage by vehicles.
5
Page 6
6" (152 mm)
Top Clearance
0" Side
Clearance
to Furnace
Cabinet
Figure 1. Alcove Installation
Removable access
panel should be
installed above
furnace door frame
to access roof jack
18"
(457 mm)
Nearest
Wall or
Partition
ALL MODELSCLOSETALCOVE
Front6”18”
Back0”0”
Sides0”0”
Roof Jack0”0”
To p6 ”6 ”
Top and Sides of Duct0”0”
Bottom of Duct
B Cabinet0”0”
A Cabinet (w/ coil box)0”0”
A Cabinet (w/o coil box)1/4”1/4”
Table 1. Minimum Clearances
6" (152 mm)
Top Clearance
0" Side
Clearance
to Furnace
Cabinet
6" (152 mm)
Top Clearance
0" Side
Clearance
to Furnace
Cabinet
Provide min. 235
sq. in. (1516 cm )
open free area in
front or side wall
6"
(152 mm)
CLOSET DOOR
Figure 2. Closet Installation
Provide min. 250
sq. in. (1613 cm )
open free area in
front or side wall
1"
(25 mm)
2
or
In closet
door
located
at top,
center
or bottom
2
or
in closet
door
a fully
louvered
door may
be used
“A”- 56"
“A” Model
w/o Coil
Cabinet
“B”- 76"
“B” Model
w/Coil
Cabinet
23 3/4"
19 3/4"
Figure 4. Overall Dimensions
Part
No.
90377310 x 81/42, 2½ & 3
90341311 x 81/22, 2½, 3 & 4
90389011 x 83/42, 2½, 3, 4 & 5
Blower / Motor Assembly
Blower WheelMotor (Hp)
A/C Capacity
(Tons)
Table 2. Blower Assemblies
CLOSET DOOR
Figure 3. Special 1” Clearance
6
Page 7
CIRCULATING AIR REQUIREMENTS
A Single trunk duct
B
Dual trunk duct
w/crossover connector
C
Transition duct
w/branches
WARNING:
Do not allow combustion products to enter the
circulating air supply. Failure to prevent the
circulation of combustion products into the
living space can create potentially hazardous
conditions including carbon monoxide poison-
ing that could result in personal injury or death.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in confi ned spaces, all return
ductwork must be adequately sealed. The joint
between the furnace and the return air plenum
must be air tight.
The surface that the furnace is mounted on must
provide sound physical support of the furnace
with no gaps, cracks or sagging between the
furnace and the fl oor or platform.
Return air and circulating air ductwork must
not be connected to any other heat producing
device such as a fi replace insert, stove, etc. This
may result in fi re, explosion, carbon monoxide
poisoning, personal injury, or property damage.
Return Air Connections
U.S.A. home manufacturers shall comply with all of the
following conditions to have acceptable return air systems
for closet installed forced air heating appliances:
• The return air opening into the closet shall not be less
than specifi ed in the appliance’s listing.
• The cross-sectional area of the return duct system
leading into the closet, when located in the fl oor or
ceiling shall not be less than 235 in2 (or 390 in2 for 5
ton ready M1/M5 Furnaces).
• Noncombustible pans having 1” upturned fl anges are
located beneath openings in a fl oor duct system.
• Wiring materials located in the return duct system shall
conform to Articles 300-22 of the National Electrical
Code (ANSI C1/NFPA-70).
• Gas piping is not run in or through the return duct system.
CAUTION:
HAZARD OF ASPHYXIATION: Negative pressure
inside the closet, with closet door closed and
the furnace blower operating on high speed,
shall be no more negative than minus 0.05 inch
water column.
• Test the negative pressure in the closet with the aircirculating fan operating at high speed and the closet
closed. The negative pressure is to be no more negative
than minus 0.05 inch water column.
• Air conditioning systems may require more duct register
and open louver area to obtain necessary airfl ow. Use
NORDYNE’s certiduct program to determine proper
duct sizes for air conditioning.
Supply Air Connections
For proper air distribution, the supply duct system must be
designed so that the static pressure measured external
to the furnace does not exceed the listed static pressure
rating shown on the furnace rating plate.
Location, size, and number of registers should be selected
on the basis of best air distribution and fl oor plan of the
home. The supply air must be delivered to the heated
space by duct(s) secured to the furnace casing,
running full size and without interruption. Three typical
distribution systems are shown in Figure 5
HAZARD OF ASPHYXIATION: Do not cover or
restrict return air opening.
• Means shall be provided that prevent inadvertent closure
of fl at objects placed over the return air opening located
in the fl oor of the closet (versus the vertical front or side
wall).
• The total free area of openings in the fl oor or ceiling
registers serving the return air duct system must be at
least 235 in2. At least one register should be located
where it is not likely to be covered by carpeting, boxes
and other objects.
• Materials located in the return duct system must have a
fl ame spread classifi cation of 200 or less. This includes
a closet door if the furnace is in a closet.
CAUTION:
Figure 5. Typical Supply Duct System
7
Page 8
FURNACE INSTALLATION
NOTE: These Installation procedures are suggested for
typical furnace installations. Since each installation is
different, the sequence of instructions may differ from
the actual installation. Only qualifi ed HVAC technicians
should install this furnace.
The installer must be familiar with and comply with all
codes and regulations applicable to the installation of
these heating appliances and related equipment. In
the absence of local codes, the installation must be in
accordance with the current provisions of one or more of
the following standards.
• Federal Manufactured Home Constructions & Safety
Standard (H.U.D. Title 24, Part 3280.707[a][2])
• American National Standard (ANSI-119.2/NFPA-501C)
for all recreational vehicle installations.
• American National Standard (ANSI-Z223.1/NFPA-54)
and/or CAN/CSA B149 for all gas-fi red furnace models.
• American National Standard (ANSI-Z95.1/NFPA-31)
and/or CSA B139 for all oil-fi red furnace models.
• American National Standard (ANSI-C1/NFPA-70) and/or
CSA 22.1 Canadian Electric Code Part 1 for all electrical
fi eld wiring.
• Units have been researched under standards UL 307A
& B, UL727-1999, ANSI Z21.47b/CSA 2.3b-2008, and
CSA B140.10.
General Information
• The furnace must be leveled at installation and attached
to a properly installed duct system. Do not use the back of the furnace for return air. See page 7 for circulating
requirements.
• The furnace must be installed so that all electrical
components are protected from water.
• The dimensions of the room or alcove must be able to
accommodate the overall size of the furnace and the
installation clearances listed in Table 1 and Figure 3
(page 6)
• The furnace must be installed upstream from a
refrigeration system.
• The M1 Series gas and M5 Series oil furnace is
certifi ed for use on wood fl ooring or supports, but must
be installed on top of a duct connector. This factory
supplied accessory must be installed in the fl oor cavity
and attached to the supply air duct before the furnace
is installed.
Locating & Cutting Duct Openings
Floor cut-outs and fuel line holes must be carefully located
to avoid misalignment of the furnace, and vent piping. To
locate standard ducts see Figure 6 (page 9). For round
ducts, see Figure 7.
1. Measure 10” from the rear wall or alcove and mark the
centerline of the cut-out on the fl oor.
2. Using the centerline as a starting point, draw the rest
of the duct cut-out to the dimensions shown in Figures
6 or 7.
3. Cut out the fl oor opening 1/16” larger than the actual
cutout drawn. This will allow some clearance when
installing the duct connector.
4. Measure from the top of the fl oor down to the top of
the supply air duct to obtain the depth of the fl oor
cavity. NOTE: The depth of the fl oor cavity shown as
“X” in Figure 9 (page 9) will determine the correct duct
connector.
5. Determine which duct connector to use from Table 3
(page 9).
6. Measure and drill gas hole and cut out for cooling coil
(if applicable). See Figures 6 or 7.
Standard Duct Connector Installation
The standard duct connector is designed for use on ducts
12” in width. However ducts narrower than 12” may not
allow suffi cient clearances for this type of installation. For
an alternate installation method, see page 9.
1. Center the duct connector in the fl oor opening with
bottom tabs resting on top of the supply air duct.
2. Mark the cut-out area on the supply air duct by tracing
around the connector tabs (Figure 8, page 9) of the
duct connector.
3. Remove the duct connector and cut out the marked
area of the supply air duct 1/4” larger the actual cutout
drawn.
4. Install the duct connector back in the fl oor opening with
the bottom tabs extending into the supply air duct.
5. Install the mounting plate (Figure 8) under the back
side of the duct connector. Align the screw holes in
both components.
6. Secure the duct connector and the mounting plate to
the wood fl oor with appropriate size screws.
7. Bend the connector tabs on the bottom of the duct
connector upwards and as tight as possible against
the supply air duct.
8. Bend both tabs up 90° on the mounting plate. See
Figure 10 (page 10)
9. Seal all connections with industrial grade sealing tape
or liquid sealant.
NOTE: Requirements for sealing ductwork vary
from region to region. Consult with local codes for
requirements specifi c to your area.
8
Page 9
20"
14 1/2"
C
L
REAR WALL OF CLOSET OR ALCOVE
2 3/4"
2 1/4"
10"
FLOOR CUT-OUT
24"
21 3/4"
23 1/4"
C
L
1 3/4"
3/4"
FOR STANDARD
DUCT CONNECTORS
14 1/2"
FURNACE OUTLINE
C
C
L
L
CUT-OUT FOR
OPTIONAL
COOLING COIL
ALT FUEL-LINE
ENTRY 1 1/4" Dia.
1 7/8"
2 7/8"
1 3/4"
C
L
FURNACE
OUTER
DOOR
C
L
FUEL
LINE
3/4"
Figure 6. Cut-Out Dimensions for
Standard Duct Connectors
20"
C
L
10"
REAR WALL OF CLOSET OR ALCOVE
“X”
FLOOR OPENING
SUPPLY AIR DUCT
FLOOR
CAVITY
Figure 9. Floor Cavity
C
L
2"
If Floor Cavity
“X” is:
Standard DuctRound Duct
7/8” / (22)901987A904008
2” / (51)901988A904009
4-1/4” / (108)901989A904010
6-1/4” / (159)901990A904011
8-1/4” / (210)901991A904012
10-1/4” / (260)901992A904013
12-1/4” / (311)901993A904014
NOTE: Dimensions shown as Inches / (Millimeter)
Duct Connector
Type & Part Number
Table 3. Duct Connector Sizes
FLOOR
CUT-OUT FOR
24"
C
L
23 1/4"
21 3/4"
1 3/4"
3/4"
1 7/8"
ROUND DUCT
(14 1/4” DIAMETER)
FURNACE OUTLINE
CUT-OUT FOR
C
C
L
L
COOLING COIL
ENTRY 1 1/4" Dia.
2 7/8"
OPTIONAL
ALT FUEL-LINE
C
L
C
L
FURNACE
OUTER
DOOR
Figure 7. Cut-Out Dimensions for
Round Duct Connectors
Hole for
Gas Line
Duct
Connector
Wood Floor
Connector
Tabs
Supply
Air Duct
Mounting Plate
10"
1 3/4"
3/4"
FUEL
LINE
Bend tabs
C
L
2"
up 90°
Alternate Attachment Method
The standard duct connector is designed for use on ducts
12” in width. However if there is insuffi cient clearance to
bend the duct connector tabs, this alternate attachment
method may be used.
1. Score and cut the top of the supply air duct as indicated
in Option 1 or Option 2 (Figure 11, page 10). With Option
1 choice, cut out the metal from the shaded area.
2. Fold the two fl aps (Options 1 or 2) up to form the opening
for the duct connector.
3. Install the duct connector with the bottom tabs extending
into the supply air duct.
4. Bend the tabs on the bottom of the duct connector
upwards and as tight as possible against the supply
air duct (Figure 12, page 10).
5. Form the fl aps (Options 1 or 2) up against the duct
connector as tight as possible.
6. Secure the duct connector fl aps to the supply air duct
with staples (3 minimum) or if a 2x block/joist is not
provided, use sheet metal screws (2 minimum).
NOTE: The duct connector tabs may be attached to
the air duct with sheet metal screws or other suitable
fasteners as long as the duct connector and the air duct
are securely attached.
7. Seal all connections with industrial grade sealing tape
or liquid sealant.
Figure 8. Standard Duct Connector Installed
NOTE: Requirements for sealing ductwork vary
from region to region. Consult with local codes for
requirements specifi c to your area.
9
Page 10
DUCT CONNECTOR
MTG. PLATE TABS
SLIDE FURNACE
ALL THE WAY BACK
ONTO MTG. PLATE
SUPPLY AIR DUCT
Knockout Over Holes
SECURE FURNACE
WITH 2 FASTENERS AT FRONT
CORNER HOLES
BEND TABS TIGHTLY
AGAINST SUPPLY AIR DUCT
Figure 10. Duct Connector Tabs
OPTION 1OPTION 2
Remove
this
Cut Here
Cut Here
Cut Here
Fold Flap Here
Cut Here
Remove
this
Flap
Flap
Cut Here
Cut Here
Supply
Air Duct
Fold Flap Here
Fold Flap Here
Cut Here
Cut Here
Cut Here
SUPPLY
AIR DUCT
Fold Flap Here
Round Duct Connector Installation
1. Apply a bead of caulking, mastic, or other approved
sealant around bottom side of connector.
2. Install and center the duct connector in the fl oor opening.
3. Install the mounting plate under the back side of the
duct connector. See Figure 13. NOTE: Align the screw
holes in both components.
4. Secure the duct connector and the mounting plate to
the wood fl oor with appropriate size screws.
5. Connect the round supply duct to the underside of the
duct connector and secure them with fi eld supplied
sheet metal screws.
6. Seal all connections with industrial grade sealing tape
or liquid sealant.
NOTE: Requirements for sealing ductwork vary
from region to region. Consult with local codes for
requirements specifi c to your area.
Installing the Furnace
Sides and back of the furnace may be enclosed by wall
framing such as in a closet or alcove. The dimensions of the
room or alcove must be able to accommodate the overall
size of the furnace and the installation clearances outlined
on page 5 and Figures 1 - 4 (page 6). The furnace shall
be appropriately connected to the supply and return air
distribution system as shown in Figures 14 & 15 (page 11).
Figure 11. Narrow Air Duct Openings
Duct connector tabs
Narrow
Duct
Duct
Flap
Sheet metal
screws
Staples or sheet metal screws
Duct
Connector
Narrow
Duct
Figure 12. Narrow Ducts
SCREWS
DUCT
CONNECTOR
14” SUPPLY CONNECTION
Figure 13. Round Duct Connector Installed
Narrow
Duct
MOUNTING
PLATE
FUEL LINE
HOLES
1. Remove furnace outer door(s) and bottom fuel line
knockout.
2. Place furnace onto duct connector and center with fl oor
opening.
3. Slide onto mounting plate. (Bottom rear slots on furnace
should engage with mounting plate tabs.)
4. Secure front with one (1) fastener at each corner
(Figures 14 or 15).
NOTE: Additional fasteners may be used at rear, sides
or through door frame, as desired, to secure furnace to
closet or alcove framing.
Figure 14. “A” & “B” Cabinet Furnaces
10
Page 11
SLIDE FURNACE
BACK AGAINST
MTG. PLATE
MTG. PLATE TABS
SECURE FURNACE
WITH 2 FASTENERS
AT FRONT CORNER HOLES
FUEL LINE HOLES
SUPPLY
AIR DUCT
Figure 15. “A” Cabinet Furnace on Coil Cabinet
ROOF JACK INSTALLATION
Required ceiling and roof cut-out openings must be
carefully located to avoid misalignment of the furnace
and Roof Jack. NOTE: Install only Roof Jack Assemblies
listed in Table 4 on this heating appliance.
Roof Jack Selection
1. Determine depth of ceiling cavity from center of roof
opening to center of ceiling opening (Dimension [A] in
Figure 16).
2. Determine ceiling height and subtract height of furnace
(Dimension [B] in Figure 16).
3. Add dimensions [A] + [B] (and [X] from Table 5 & Figure
16, page 12 if slant deck fl ashing is used). The total
length of [A] + [B] + [X] must be within the minimum
and maximum range of the Roof Jack listed in Table 4.
ROOF JACK
SLANT DECK
PITCHED
ROOF
CEILING
CAVITY
CEILING
“A”
“B”
Furnace
FLASHING
"X" (SEE TABLE 5)
Roof
Opening
Flue Pipe
Combustion Air Pipe
56" or 76"
Figure 16. Ceiling Cavity Depth
MODEL NUMBER
(F,S)AW(T)1523-(0,2,4)(A,S)15” - 23”
(F,S)AW(T)2135-(0,2,4)(A,S)21” - 35”
(F,S)AW(T)2747-(0,2,4)(A,S)27” - 47”
(F,S)AW(T)3563-(0,2,4)(A,S)35” - 63”
(F,S)AW(T)5195-(0,2,4)(A,S)51” - 95”
SSAW
F = FLAT FLASHING
S = SLANT FLASHING
AW= ALL WEATHER
TYPE:
BLANK = NON-TRANSIT
T= TRANSIT MODE
APPROX. LENGTH
BELOW FLASHING
47 - 2
T
27
MIN. ADJ.
LENGTH
MAX. ADJ.
LENGTH
FLUE STEEL TYPE
A= ALUMINIZED
S=STAINLESS
FLASHING
PITCH/12" RISE
0=FLAT
2=2.5/12
4=4/12
Application Notes
• FAW, FAWT, SAW and SAWT Series Roof Jacks with a
5” diameter inner vent pipe may be used with all models
of M1 Series gas and M5 Series oil furnaces.
F = Flat Flashing: fl exes from 0/12 to 1/12 roof slope.
See Figure 17 (page 12).
S = Slant Flashing: 2.5/12 Slope fl exes from 1/12 to
4/12 roof slope, 4/12 fl exes from 3/12 to 5/12.
See Figure 18.
• Stainless steel roof jacks are available.
• M1/M5 furnaces may be used with roof jacks as tall as
170” (except M1M 056 & M1B 066 models, which are
limited to 120”). An internal roof jack extension (p/n
901935 - 10”, p/n 903107 - 18”) can be used to increase
roof jack height. All connections inside the home must
be made below the ceiling.
• This furnace must never be connected to a chimney
fl ue servicing a fi replace or other appliance designed
to burn solid fuel.
NOTE: If the roof jack crown is covered or blocked
with snow, the furnace will not operate properly. If the
home is located in regions where snow accumulation
exceeds 7” (HUD snowload zones) use an external roof
jack extension (p/n 901937). Extensions are optional
accessories and may be purchased through your
NORDYNE distributor.
See Table 5
Table 4. Roof Jack Assemblies
Figure 17. Example of Flat Jack with Flashing
11
Page 12
Figure 18. Example of 2½ / 12 Slant Jack
CEILING
CUT-OUT FOR
FLUE AND
ROOF JACK
C
L
C
L
24"
20"
13 1/2"
REAR WALL OF CLOSET OR ALCOVE
10"
FURNACE
OUTER
DOOR
FURNACE OUTLINE
with Flashing
ROOF JACK
SERIES
“F Series
“S” Series
(2.5 / 12 Pitch only)
Optional deck fl ashings for fl at and 2.5/12 pitch roof jacks.
4/12 pitch roof jacks not applicable.
Table 5. Slant Deck Flashings
Locating & Cutting Roof/Ceiling Openings
Do not allow debris to fall into the furnace.
This could cause unsafe operation and void
the furnace warranty. Use the top cap that
comes with the furnace packaging (or alternate
protector) to prevent debris from falling into the
furnace before the fi nal roof jack connection
is made
NOTE: Refer to the installation instructions provided
with optional air conditioning packages when installing
furnaces with optional cooling coil cabinet or with optional
C* series indoor coils.
1. Locate center of Roof Jack opening, measure 13 1/2”
2. Cut ceiling and roof holes:
from the rear wall of closet or alcove along the center
line of furnace and fl oor opening. See Figure 19.
• Ceiling = 8 3/4” (222 mm) diameter
• Roof = 9 3/8” (238 mm) diameter
IF ROOF
PITCH IS:
2” in 12”903893 (2.5/12)2-1/8”
2-1/2” in 12”903893 (2.5/12)2-1/2”
3” in 12”903894 (3/12)2-7/8”
3-1/2” in 12”903894 (3/12)3-1/4”
4” in 12”903895 (4/12)3-5/8”
4-1/2” in 12”903895 (2.5/12)2-1/8”
5” in 12”903895 (2.5/12)2-1/2”
5-1/2” in 12”903894 (3/12)2-7/8”
6” in 12”903894 (3/12)3-1/4”
6-1/2” in 12”903895 (4/12)3-5/8”
SLANT DECK
FLASHING
NUMBER
FACTOR
IMPORTANT:
“X”
IS:
Figure 19. Cut-Out Dimensions for
Flue & Roof Jack
Installing The Roof Jack
1. Apply caulking compound on underside of roof fl ashing
to form a continuous strip at least 3/8” wide around the
underside of the perimeter of the fl ashing. See Figures
20 or 21 (page13).
2. Connect Roof Jack Assembly to the furnace. Insert
telescoping Roof Jack Assembly through the opening
cut on the roof.
3. Connect fl ue pipe to fl ue collar of furnace. See Figure
22 (page 13).
4. Connect combustion air pipe to furnace collar with
sheet metal screw (See Figure 22).
NOTES:
• It is recommended that the connection of the combustion
air pipe to the furnace be made before the fl ashing is
secured to the roof to maintain alignment of roof jack
and furnace connections.
• For replacement furnaces, be sure the inner fl ue pipe
connects over the furnace vent collar. DO NOT use a
smaller diameter inner fl ue pipe which could slide
inside the furnace vent collar and restrict the fl ow
of furnace fl ue products.
5. Attach Roof Flashing. If necessary, shift roof fl ashing
slightly in the roof opening so that assembly is in
alignment with furnace.
NOTE: If fl ashing is mounted on 12 degree angle, it
may be necessary to adjust the angle to match the roof
pitch; (1/12 - 4/12 maximum).
6. Press down fi rmly on roof fl ashing (over caulking) to
make the seal with roof water tight.
7. Secure fl ashing with appropriate fasteners.
added protection against leaks, coat the fl ashing plate
and fasteners with approved roofi ng compound.
NOTE: For
12
Page 13
Secure roof jack with
SCREWS
COMPLETED
ASSEMBLY
TO FURNACE
UPPER ROOF
JACK (CROWN)
INNER FLUE
PIPE
FLUE ASSEMBLY
OUTER PIPE
FLASHING
WEATHER CAP
appropriate fasteners
after connecting to
furnace
Caulk under roof
flashing to prevent
water leakage
Optional 2-piece ceiling
ring #902521
Secure lower roof
jack section with
no. 10 S.M. screws
Caulk under roof
ashing to prevent
water leakage
Figure 20. Flat Roof
Upper Roof Jack Section
Ceiling
Figure 21. Pitched Roof
Ceiling
Optional Slant
Deck Flashing
Secure ashing
with appropriate
fasteners
Roof
Figure 23. Roof Jack Crown
Installation of Transit-Mode Venting System
(Manufactured Home Factory)
1. Furnace must be installed in accordance to furnace
installation manual.
2. Select appropriate Roof Jack from Table 4 (page 11).
3. Roof Jack (less upper Roof Jack crown), with weather
cap to be installed as described under Install Roof Jack.
NOTE: Upper Roof Jack crown to be stored in a
prominent location inside manufactured home until
on-site installation.
4. The four warning tags supplied must be installed as
follows:
• To weather cap
• To fuel line connection point (Gas) or furnace burner
(Oil)
• To furnace fl ame observation door (Gas or Oil)
• To furnace wall thermostat
5. Transit-mode weather cap to be removed and upper
Roof Jack crown installed (See Figure 23). Do Not
Discard screws.
6. Place upper Roof Jack (crown) on the fl ue pipe assembly.
Figure 22. Combustion Air Pipe Connection
NOTE: Make sure inside fl ue pipe attaches over inner
fl ue pipe and outer Roof Jack pipe fi ts over outer pipe.
7. Secure in place using three (3), #10, 1/2” sheet metal
screws removed in step 5. Do not use the same holes
which secured the rain cap in place.
8. Remove and discard venting system warning tags.
WARNING:
Failure to properly secure the fl ue pipe to
the furnace may result in fi re, explosion or
asphyxiation when operating the furnace.
13
Page 14
On-Off
Switch
Blower
Plug
Powe r
Entry
On-Auto Switch
(Heating Models Only)
Thermostat Wires
Furnace
Control Box
To combustion
Blower or Flame
Roll-out Switch
To Gas Valve
or Burner
WARNING:
To avoid electric shock, personal injury, or death,
turn off the electric power at the disconnect
or the main service panel before making any
electrical connections.
• Electrical connections must be in compliance with all
applicable local codes with the current revision of the
National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Figure 24. Control Panel (All Models)
ELECTRICAL INFORMATION
WARNING:
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical power
to furnace.
• When servicing controls, label all wires prior to
disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.”
AVERTISSEMENT:
RISQUE DE CHOC ÉLECTRIQUE,
D’INCENDIE OU D’EXPLOSION
Le non-respect des avertissements de sécurité
pourrait entraîner un fonctionnement dangereux
de l’appareil, des blessures graves, la mort ou
des dommages matériels.
Un entretein incorrect pourrait entraîner un
fonctionnement dangereux de l’appareil, des
blessures graves, la mort ou des dommages
matériels
• Couper toute alimentation électrique au générateur d’air chaud avant de prodéder aux travaux
d’entretein.
• Au moment de l’entretien des commandes,
étiquetez tous les fi ls avant de les débrancher.
S’assurer de les raccorder correctement.
• S’assurer que l’appareil fonctionne adéquatement
aprés l’entretien.
Line Voltage Wiring
It is recommended that 115VAC line voltage be supplied
to the furnace from a dedicated branch circuit containing
the correct fuse or circuit breaker for the furnace.
IMPORTANT NOTE: An electrical disconnect must be
installed readily accessible from and located within
sight of the furnace. Refer to the wiring diagram inside
the control box cover or Figures 38 & 39 (pages 33
& 34) for the wiring of your particular unit. Any other
wiring methods must be acceptable to authority
having jurisdiction.
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
IMPORTANT NOTE: Proper line voltage polarity must
be maintained in order for the control system to
operate correctly. Verify the incoming neutral line is
connected to the white wire and the incoming “hot”
line is connected to the black wire. The furnace will not
operate unless the polarity and ground are properly
connected as shown in Figure 25.
Route all electrical wiring to the left side of the furnace
(See Figure 24). For installation of “A” Cabinet furnaces,
allow suffi cient slack in the wiring if an optional cooling coil
cabinet is added at a later time. Use of copper conductors
is recommended.
Connecting Power Supply Wires
1. Remove the furnace control panel cover.
2. Route wires (115 VAC) through the strain relief on the
left side of the furnace control box (Figure 24).
3. Connect the hot wire to the black pigtail lead, and
the neutral wire to the white pigtail lead. Secure all
connections with suitable wire nuts.
4. Connect the ground wire to the grounding screw.
5. Reinstall the control panel cover and secure with the
original mounting screws.
14
Page 15
Low Voltage Wiring
The thermostat must be installed according to the
instructions supplied by the thermostat manufacturer.
Low voltage connections (24 VAC) from the thermostat
are wired to the terminal strip on the integrated control
in the furnace.
NOTE: The thermostat must not be installed on an
outside wall or any other location where its operation may
be adversely affected by radiant heat from fi replaces,
sunlight, or lighting fi xtures, and convective heat from
warm air registers or electrical appliances. The nominal
anticipator setting is 0.4. (Refer to the thermostat literature
for additional information.)
Five-conductor thermostat wire is recommended for 24
volt low-voltage circuit (2-wire is required for furnace only;
5-wire for heating and optional cooling systems). Refer to
Table 6 for thermostat wire information.
Connecting Thermostat Wires
1. Insert 24 volt wires through the plastic grommet just
above the control panel.
2. Connect the thermostat wires to the fur nace low voltage
pigtails (see Figure 25).
3. Connect low-voltage circuit to the wall thermostat.
4. A hole may be made in the furnace cabinet to ease
thermostat wiring. Make sure that the wiring is protected
from the sharp edge of the added hole.
Verifying Anticipator Setting
After the furnace is installed, check the thermostat
anticipator against the nominal setting of 0.4.
1. Connect the milliamp meter in series with one of the
gas valve’s low voltage terminals.
2. Energize the gas valve.
3. Read the value of the milliamps.
4. Adjust the heat anticipator of the thermostat to the
value on the milliamp meter. If the heat anticipator is
set too high, the furnace may delay turning on. If set too
low, the furnace may cycle frequently and not provide
comfort to the homeowner.
Grounding
WARNING:
To minimize personal injury, the furnace cabinet
must have an uninterrupted or unbroken
electrical ground. The controls used in this
furnace require an earth ground to operate
properly. Acceptable methods include electrical
wire or conduit approved for ground service.
Do not use gas piping as an electrical ground!
Thermostat
Rc
H
R
W
G
Y
Figure 25. Thermostat Wiring For
Thermostat
Wire Gauge
245525
229045
2014070
18225110
Red
White
Green
Yellow
A/C Ready Models
Recommended T’STAT Wire
Length (Unit to T’STAT)
2-Wire
(Heating)
M1/M5 A/C
Ready Furnace
Red
White
Green
Grey
5-Wire
(Heating/Cooling)
Table 6. Thermostat Wire Gauge
15
Page 16
FUEL SUPPLY & PIPING
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could
result in serious injury or property damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or the
gas supplier.
• Do not store or use gasoline or other
fl ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call
the fi re department.
AVERTISSEMENT:
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de
sécurité pourrait entraîner des blessures
graves, la mort ou des dommages matériels.
• L’installation et l’entretien doivent être
effectués par un installateur qualifi é, un
organisme de service ou le fournisseur de
gazstaller, service agency or the gas supplier.
• Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables
dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique;
n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de
gaz en employant le téléphone d’un voisin.
Respecter à la lettre les instructions du
fournisseur de gaz.
• Si personne ne répond, appeler le service
des incendies.
WARNING:
All piping must conform with local building
codes, or in the absence of local codes, with
the most recent edition of the National Fuel Gas
Code ANSI Z223.1 or (CAN/CGA B149.1 or .2).
Failure to follow all safety warnings could result
in serious injury, death or property damage.
This furnace may be installed with left, right, or bottom gas
entry. When connecting the gas supply, provide clearance
between the gas supply line and the entry hole in the
furnace casing to avoid unwanted noise and/or damage
to the furnace. Typical gas service hookup for this furnace
is shown in Figure 26 (page 17). Table 14 (page 37) lists
gas fl ow capacities for standard pipe sizes as a function of
length in typical applications based on nominal pressure
drop in the line.
IMPORTANT NOTES:
• Some local regulations require the installation of a
manual main shut-off valve and ground joint union
external to the furnace (Figure 27, page 18). The shutoff valve should be readily accessible for service
and/or emergency use. Consult the local utility or
gas supplier for additional requirements regarding
placement of the manual main gas shut-off.
• Gas piping must never run in or through air ducts,
chimneys, gas vents, or elevator shafts.
• Compounds used on threaded joints of gas piping
must be resistant to the actions of -liquefi ed
petroleum gases.
• The main gas valve and main power disconnect to
the furnace must be properly labeled by the installer
in case emergency shutdown is required.
• Flexible gas connectors are not recommended for
this furnace but may be used if allowed by local
jurisdiction. Only new fl exible connectors may be
used. DO NOT reuse old fl exible gas connectors.
• A drip leg is recommended for a vertical run to the
unit.
• All piping shall be black iron pipe, or equivalently
sized steel tubing. Internally tinned copper tubing
may be used for gas supply systems.
• Fuel line installations other than typical installations
shown in Figures 26 (page 17) & 27 (page 18) must
comply with the fuel piping provisions stated in
the Federal Manufactured Home Standard (H.U.D.
TITLE 24, PART 280) and the National Fuel Gas Code
(ANSI-Z223.1/NFPA-54).
• Shut-off valve must be designed and listed for use
with liquid petroleum (L.P. gas).
• A 1/8” NPT plugged tappings for test gauge
connection are present on the gas valve. See Figure
28 for locations
16
Page 17
NOTE: Optional fuel inlet lines are available for all gas
furnace models to permit the addition of a 1/2” F.P.T.
shut-off valve above the fl oor.
The gas supply to your home will either be Natural Gas or
L.P. (bottle gas). Your furnace is factory equipped to operate
on Natural Gas. If your gas supply is L.P. (bottle gas), you
must contact a qualifi ed serviceman or gas supplier to
convert the furnace. Instructions for gas conversion are
listed on page 19. Factory installed orifi ce sizes are listed
in Table 10 (page 30).
For natural gas operation, the furnace is designed for 7”
W.C. inlet pressure. Pressure is reduced to 3 1/2” W.C.
by the pressure regulator in the gas valve. The maximum
inlet pressure for the valve is 7” W.C and the minimum
inlet pressure is 4.5” W.C.
For L.P. gas, pressure to the gas valve must be more than
11” W.C. but not more than 13” W.C. Pressure is reduced
to 10” W.C. by the pressure regulator in the gas valve.
Leak Check
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Never test for gas leaks with an open fl ame. Use
a commercially available soap solution made
specifi cally for the detection of leaks to check
all connections. A fi re or explosion may result
causing property damage, personal injury or
loss of life.
AVERTISSEMENT:
RISQUE D’INDENDIE OU D’EXPLOSION
Le non-respect des avertissements de sécurité
pourrait d’entraîner des blessures graves, la mort
ou des dommages matériels.
Ne jamais utiliser une fl amme nue por vérifi er la
présence des fuites de gaz. Pour la vérifi cation de
tous les joints, utiliser plutôt une solution savonneuse commerciale fabriquée spécifi quement pur
la détection des fuites de gaz. Un incendie ou une
explosion peut entraîner des dommages matériels,
des blessures ou la mort.
On-Off-Fan
Switch
Control
Panel
To Gas
Supply
Floor
Floor Cavity
Figure 26. Typical Gas Piping
Alt. Fuel
Line Entry
After the gas piping to the furnace is complete, all
connections must be tested for gas leaks. This includes
pipe connections at the main gas valve, emergency shutoff
valve and fl exible gas connectors (if applicable). The soap
and water solution can be applied on each joint or union
using a small paintbrush. If any bubbling is observed,
the connection is not sealed adequately and must be
retightened. Repeat the tightening and soap check process
until bubbling ceases.
IMPORTANT NOTE: When pressure testing gas supply
lines at pressures greater than 1/2 psig (14 inch W.C.),
the gas supply piping system must be disconnected
from the furnace to prevent damage to the gas control
valve. If the test pressure is less than or equal to 1/2
psig (14 inch W.C.), close the manual shut-off valve.
Oil Tank & Piping Installation
The following procedures are recommended as good
practice. However, requirements of local codes and
ordinances, H.U.D. Manufactured Home and Safety
Standards or National Fire Protection Association must
be satisfi ed, where they apply, for an approved installation.
• Use a tank capacity suitable for the application with a
weatherproof, capped fi ll opening and a shielded vent
to let in air as fuel is used.
17
Page 18
Vent with cap
t
Gauge
End of Oil Supply Line
3" to 5" Above Bottom Drain
3/8" Oil Supply Line
Guide
Pipe
NOTE: Additional venting may be
required if tank is filled rapidly.
Cordset
Pressure Adjustment
Becket
INLET
USE ONLY WITH
VALVE ON DELAY
A2EA-6520
4 GPH 100-150 PSI 3450 RPM
NO. 2 & LIGHTER FUEL
3 GPH 150-200 PSI 3450 RPM
NO. 2 FUEL
INLET
BY-PASS
Made by Suntec
Exclusively for Beckett
If fuel pump fails to lift oil, check for air
leaks and tighten all fuel fittings. Reprime fuel pump by injecting fuel oil into
optional (top) return port. Replace return
port plug and repeat priming procedure.
Inlet Port
1/4 NPTF
Bleed & Gauge Port
Return Port - Install 1/6” Bypass Pipe
Plug for 2-pipe System Only.
(Use 5/32” Allen Wrench)
2" Duplex
Bushing
2" Fill
Drain
Top of Tank
Shut-off
Valve
Optional
Fuel
Filter
8 ft.
Alternate
Fuel Line
Entry
Furnace
Control
Panel
Oil
Bypass Solenoid Valve
Nozzle Port
3/16 Flare Fitting
Flue Gas
Sampling
Hole
On-Off-Fan
Switch
Oil-Gun
Burner
Floor
Floor Cavity
Inlet Port
1/4 NPTF
Figure 27. Typical Oil Piping for Above Ground (Single-Line) Supply
Screw
• The inside of the tank must be clean before fi lling. All
water, rust, sediment, and debris must be fl ushed out.
• A fuel or tank gauge (Figure 27) is recommended for
easy checking of the fuel level. Check the gauge reading
with a dipstick.
• Locate the storage tank conveniently near the home.
If the fuel tank is installed above ground, the tank may
rest 3 to 4 inches off the ground. Fuel tanks may also
be buried if properly coated to resist corrosion. The
vertical dimension from the bottom of the fuel tank to
the fuel pump must not exceed 10 feet.
• Keep the tank fi lled, especially in the summer to reduce
the accumulation of condensation.
One-Line System
The One-Line System is highly recommended where
vertical lift, from bottom of tank to pump, is less than 8
feet (Figure 27). A single line hookup has the advantage
of lower cost and quieter operation.
Two-Line System
If a Two-Line system is used or if oil is taken from the
bottom of the tank, a fi lter is recommended. A Two-Line
system should only be used if vertical lift exceeds 8 feet.
1. Install the oil feed line as outlined in steps 1 - 6 below.
2. Install the oil pump bypass plug in the bottom return
port.
3. Route the return line up through the furnace base to
the return port of the pump. Route the other end of the
line to the tank, using 3/8” O.D. copper tubing or 1/4”
pipe with the ends capped.
4. Insert the return line through the second opening in the
duplex bushing. If the bottom of the tank is lower than
the pump intake, the tube should be inserted three or
four inches from the tank bottom. If the bottom of the
tank is higher than the pump intake, the return line
should extend not more than 8” inside the tank.
Fuel line Hook-Up
1. Use a 3/8” O.D. copper tubing for the fuel line.
NOTE: Cap the end with tape to keep out dirt while the
line is being routed.
2. Install duplex bushing for two 3/8” lines in the top fi tting
of the tank. See Figure 27.
3. Inser t one end of the tubing through the duplex bushing
until it is three to fi ve inches from the bottom drain.
Tighten the bushing.
4. Route the line where it will not incur any damage. Make
bends gradual and avoid kinks which might restrict oil
fl o w .
5. Open the furnace door and connect the oil line to the
intake port on the pump. Tighten other port plugs on
the pump. NOTE: Verify the oil line is airtight! Air leaks
can cause the pump to lose prime and will create other
problems such as nozzle failure, odors, rumbling noise,
and false safety shutdown.
6. Insert the short length of the copper tube level with the
bottom of the duplex bushing. Form the tube into an
inverted “U” to serve as a vent.
Fuel Line Bleeding
To eliminate problems caused by air in the oil line, all
connections in the oil supply line and all plugs, nuts,
and fi ttings on the pump must be airtight. NOTE: This
includes the nut that covers the pressure adjustment. It
is important that the hook-up be done carefully and with
a good fl aring tool.
Prepare the burner for priming by attaching a clear plastic
hose over the bleed port fi tting and fully opening the pump
bleed port. Use a suitable container to collect purged oil.
To ensure continuous operation, use a wire to jump
terminals T-T (or F-F) on the primary control while burner
is running.
18
Page 19
Priming furnaces equipped with Honeywell
R7184 primary control:
1. While the ignition is on, press for 1/2 second (or less),
and release the reset button. The lockout time will be
extended to 4 minutes.
2. If prime is not established within the 4 minutes, the
control will lock out. Press the reset button to reset the
control.
3. Repeat steps 1 & 2 (if needed) until the oil pump is
fully primed.
Priming furnaces equipped with Beckett 7505
primary control:
1. After the burner starts, press and hold the reset button
until the yellow LED turns on (15 seconds). This indicates
that the button has been held long enough.
2. Release the reset button. The yellow LED will turn off
and the burner will start up again.
3. At burner star t up, click the reset button while the igniter
is still on. This transitions the control to a dedicated pump
prime mode, during which the motor, igniter and valve
are powered for 4 minutes. The yellow LED will be on.
NOTE: If prime is not established during the four minute
pump prime mode, repeat step 3 until the oil pump is
fully primed.
4. When oil fl ow is clear and free of air bubbles, close
air-bleed valve and tighten. NOTE: Air bleed out time
will varies depending on length of oil line, number of
bends, etc.
Fuel Oil Type
WARNING:
Do not use gasoline, crankcase oil, or any oil
containing gasline. Failure to keep supply of oil
clean by various procedures described above
may cause failure of certain components such
as the fuel pump gears, check valve, shaft seal, or
burner nozzle which may result in a burner fi re.
Do not use fuel oil heavier than Grade No. 2. In areas
where the oil supply is subject to low temperatures, Grade
No. 1 may be used.
Conversion to Propane (LP) Gas
can be converted for use with LP gas. Use the following
procedure for gas conversion of the burner.
Atmospheric & Direct Ignition Furnaces
1. Follow the instructions “How to Shut Off Gas” (page
22).
2. Disconnect the gas pipe union and the electrical wires
connected to the gas valve.
3. Remove the gas valve assembly:
a. Remove screw(s) from gas valve bracket. Gas valve
and spud may be removed. Orifi ce is located at the
end of the spud (M1M Models)
b. Remove three (3) bolts from U-shaped manifold plate
and orifi ce assembly (M1B Models).
5. Replace the main or ifi ce with the L.P. gas orifi ce supplied
in the envelope located by the gas valve. Verify the
orifi ce size matches the nameplate or Table 10 (page
31).
6. For Honeywell gas valves with the regulator converter:
a. Unscrew the pressure regulator cap and check for
the letters NAT or LP. See Figure 28, page 20.
b. Invert the cap and tighten until snug.
7. For Robertshaw gas valves with the regulator converter:
a. Remove the black cover and unscrew the converter
located on top of the gas valve. See Figure 29.
b. Invert the converter. For LP, the red ring will be located
at the bottom and the LP stamping on the converter
will appear right side up.
c. Screw converter back into the regulator, hand tight
plus 1/8 turn. Replace the black cover on the converter
top to protect the threads.
8. Reassemble the burner assembly into the furnace.
9. Reconnect the gas piping and electrical wires to the
gas valve.
10. Open the manual shut-off valve and follow the Lighting
and Operating instructions on page 22.
High Altitude Conversion
High altitude conversion with this furnace depends on
the installation altitude and the heating value of the gas.
The installation of this furnace at altitudes above 2,000
feet must meet the requirements of the National Fuel Gas
Code or local jurisdiction. In Canada, the requirements for
high altitude are different and governed by CGA B149.1.
Please consult your local code authority.
CAUTION:
Furnace conversion must be performed by a
qualifi ed technician. Improper conversion can
cause unsafe operation, explosion, fi re and/or
asphyxiation.
This gas fi red heating appliance was shipped from the
factory for use with natural gas. However, the appliance
WARNING:
The reduction of input rating necessary for high
altitude installation may only be accomplished
with factory supplied orifi ces. Do not attempt to
drill out orifi ces in the fi eld. Improperly drilled
orifi ces may cause fi re, explosion, carbon
monoxide poisoning, personal injury or death.
19
Page 20
REGULATOR
INLET PRESSURE
TAP (1/8 NPT)
LP Gas
Configuration
Black Cover
Natural Gas
Configuration
OR
PRESSURE
CAP
T
N
A
A
N
T
T
N
A
A
N
T
P
L
L
OTHER SIDE
P
M11678
OF CAP
OUTLET PRESSURE
Figure 28. Honeywell Gas Valve
Red
TAP (1/8 NPT)
This furnace is shipped from the factory with orifi ces and
gas regulator settings for natural gas operation at sea
level altitudes. At 2000 feet, the NFGC requires that this
appliance be derated 4% for each 1000 feet of altitude. For
example, the input needs to be reduced 8% at 2,000 feet,
12% at 3,000 feet and etc. This deration is in reference
to the input rate and gas heating value at sea level. See
Table 11 (page 31).
Flue Gas Sampling
It may be necessary to take fl ue gas sampling from oil
and gas furnaces (M5S and M1B Series Models) in order
to check the performance after furnace installation. A
fl ue gas sample may be taken from the heat exchanger,
which is located behind the hole of the top-front of blower
compartment.
1. Turn off all electric power to the appliance.
2. Remove the black plastic cap located above the blower.
Do not discard cap.
3. Drill a hole through the top of the blower compartment.
NOTE: Hole diameter should be same size as sampling
tube.
4. Insert sampling tube through the drilled hole and into
the heat exchanger.
5. After a complete check and adjustment of furnace
performance, seal the drilled hole with a screw larger
than the hole. NOTE: Seal the screw threads with silicon
sealant - rated at least 500° F.
6. Plug the outside hole with the plastic cap removed in
step 3.
Figure 29. Robertshaw Gas Valve
20
Page 21
STARTUP & ADJUSTMENTS
PLEASE READ ALL SAFETY INFORMATION BEFORE LIGHTING THE FURNACE
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could
result in serious injury or property damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or the
gas supplier.
• Do not store or use gasoline or other
fl ammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call
the fi re department.
WARNING:
Before placing the furnace in service, it must
be checked to ensure it is equipped for the
type of gas being used. The burner fl ame must
be observed and adjusted if necessary. Failure
to observe this caution may result in unsafe
operation, explosion and/or fi re, or asphyxiation.
See the Gas Supply and Combustion Air
sections.
• The fi rst lighting of the furnace after any home setup
must be performed by a qualifi ed service technician.
• BEFORE LIGHTING: Smell all around the furnace for
gas and next to the fl oor. Some gas is heavier than air
and may settle on the fl oor.
• Use only your hand to push in the gas control lever. Never
use tools. If the lever will not push in by hand, don’t try
to repair it. Force or attempted repair may result in a
fi re or explosion. Call a qualifi ed service technician.
• Do not use this furnace if any part has been under
water. Immediately call a service technician to inspect
the furnace and to replace any part of the gas valve or
control system which has been under water.
AVERTISSEMENT:
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de
sécurité pourrait entraîner des blessures
graves, la mort ou des dommages matériels.
• L’installation et l’entretien doivent être
effectués par un installateur qualifi é, un
organisme de service ou le fournisseur de
gazstaller, service agency or the gas supplier.
• Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables
dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique;
n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de
gaz en employant le téléphone d’un voisin.
Respecter à la lettre les instructions du
fournisseur de gaz.
• Si personne ne répond, appeler le service
des incendies.
WARNING:
Close the hinged fi re door. If door is left open
or spring is broken it may allow products of
combustion into the living space by the furnace
blower, resulting in possible asphyxiation.
WARNING:
Should overheating occur, or the gas supply
fails to shut off, shut off the manual gas valve
to the furnace before shutting off the electrical
supply.
AVERTISSEMENT:
En case de température excessive, ou sail est
impossible de cooper l’alimentation en gaz,
fermer le robinet manuel d’alimentation en
gaz du générateur d’sir chaud avant de cooper
l’alimentation électrique.
21
Page 22
Operating Instructions for Direct Ignition
GAS CONTROL KNOB
Furnaces (M1M Models)
Direct ignition furnaces do not have a pilot. Ignition is
accomplished by a silicon carbide hot surface ignitor. A
control module takes care of all timing functions. After
lighting, the control module uses the ignitor as a fl ame
sensor, shutting off gas should the fl ame go out. There
are no external relays or timing devices. Do not try to
light this furnace by hand. The control module is not
fi eld serviceable.
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance.
3. Remove the furnace door and turn off the gas valve:
• Honeywell: push in and turn the gas control knob
clockwise to OFF (Figure 30)
• Robertshaw: push the gas control lever to the OFF
position (Figure 31). Do not force!
4. Wait ten (10) minutes to clear out any gas. If you smell
gas, STOP! and follow the Safety Information on page
19. If you do not smell gas, proceed to next step 5.
5. Set the thermostat MODE the ON position.
6. Turn the gas valve ON:
• Honeywell: push in and turn gas control knob counterclockwise to ON (Figure 30).
• Robertshaw: push the gas control lever to the ON position
(Figure 31). Do not force!
7. Replace the furnace door.
8. Turn on all electric power to the appliance.
9. Change the thermostat mode to HEAT and the
temperature selector to a desired temperature level.
The igniter should light in approximately 75 seconds.
If the appliance will not operate, see “How To Shut Off
Gas - Direct Ignition” and call your service technician
or gas supplier.
NOTE: In the event of any fl ashback or explosion,
immediately shut off the furnace and call your service
technician.
How to Shut Off Gas - Direct Ignition
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance before
servicing unit.
3. Set the furnace On-Off Switch to OFF.
• Honeywell (Figure 30): Turn gas control knob clockwise
to OFF, Robertshaw (Figure 31): Push the gas control
lever to OFF.
• For oil, shut off all valves.
4. Replace the furnace door.
Operating Instructions for Oil Gun
Furnaces (M5S Models)
If your furnace model number begins with M5S*, the
furnace is equipped with an ignition device which
automatically lights the burner.Do not try to light this
furnace manually.
1. Open all valves in the oil line.
2. Verify the fi re door is closed.
3. Set the furnace On-Off switch to ON.
4. Set the thermostat to the desired setting.
NOTE: M5 oil gun furnaces may be converted to gas gun
in the fi eld by using the proper conversion kit listed in the
Replacement Parts List.
Operating Instructions for Gas Gun
Furnaces (M1B Models)
If your furnace model number begins with M1B, the furnace
does not have a pilot. Ignition is accomplished by a silicon
carbide hot surface ignitor. A control module takes care
of all lighting and timing functions. There are no external
relays or timing devices.Do not try to light this furnace
by hand. The control module is not fi eld serviceable.
1. Before operation, smell for gas all around the furnace,
especially near the fl oor because some gases are
heavier than air and will settle on the fl oor. If you detect
gas, STOP and follow all the safety instructions.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Turn off the gas valve:
• Honeywell: push in the gas control knob and turn
clockwise to OFF (Figure 30).
• Robertshaw: push the gas control lever to OFF (Figure
31).The lever cannot be placed in the off position unless
it is pushed in slightly. DO NOT FORCE!
Figure 30. Direct Ignition Gas Valve - Honeywell
22
Gas Control Lever
Figure 31. Direct Ignition Gas Valve - Robertshaw
Page 23
5. Wait ten minutes to clear out any gas. If you smell gas,
STOP! and follow the safety information. If gas is not
detected, proceed to the next step.
6. Set the furnace On-Off switch to the ON position.
• Honeywell: turn knob on gas control counter clockwise
to ON.
• Robertshaw: push the gas control lever to ON.
7. Turn electric power to the appliance ON.
8. Set the thermostat to HEAT and/or the desired
temperature setting. The furnace should light in
approximately 45 seconds. If the appliance will not
operate, follow the instructions “How to Shut Off Gas Direct Ignition Furnace” (page 22) and call your service
technician or gas supplier.
In the event of any fl ashback or explosion, immediately
shut off the furnace and call your service technician.
How to Shut Off Gas - Oil & Gas Gun
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance at the breaker
or fuse box.
3. Set the thermostat MODE switch to OFF.
4. Turn the gas valve OFF:
• Honeywell: push in and turn the gas control knob
clockwise to the OFF position (Figure 30).
• Robertshaw: push the gas control lever to the OFF
position (Figure 31).
5. Replace the furnace door.
NOTE: M1B gas gun furnaces may be converted to oil
gun in the fi eld by using the proper conversion kit listed
in the Replacement Parts List available online.
Verifying & Adjusting Temperature Rise
Confi rm the temperature rise through the furnace is
within the limits specifi ed on the furnace rating plate. Any
temperature rise outside the specifi ed limits could result
in premature failure of the heat exchanger.
1. Place thermometers in the return and supply air
stream as close to the furnace as possible. To avoid
false readings, the thermometer on the supply air side
must be shielded from direct radiation from the heat
exchanger.
2. Adjust all registers and duct dampers to the desired
position and run the furnace for 10 to 15 minutes in
high fi re before taking any temperature readings. The
temperature rise is the difference between the supply
and return air temperatures.
For typical duct systems, the temperature rise will fall
within the limits specifi ed on the rating plate with the
blower speed at the factory recommended setting. If
the measured temperature rise is outside the specifi ed
limits, it may be necessary to change the speed of the
blower. NOTE: Lowering the blower speed increases the
temperature rise and a higher blower speed will decrease
the temperature rise.
The furnace is equipped with a multi-speed motor. Refer
to the furnace wiring diagram (Figures 38 & 39, pages
33 & 34) for blower speed selection.
Burner Adjustments
Burner settings are made at the factory. However, these
settings may change during shipping, handling, and
installation. The following items should be checked and
readjusted if necessary.
Gas Pressure
The gas pressure can be checked with a manometer at
the pressure tap (Figure 28, page 20) located on the top
of the gas valve. The gas valve pressure regulator can
be adjusted by removing the regulator selector stack and
turning the slotted insert located directly under the selector
stack. The regulator selector stack must be secured in
place before each pressure reading is taken. Natural
gas manifold pressure should be 3.5” W.C. and L.P. gas
manifold pressure should be 10” W.C. Replace the gas
pressure tap plug on the gas valve.
Combustion Air
CAUTION:
• Combustion air adjustment must be made only
by a qualifi ed technician. Improper air adjustment may cause unsafe operation, explosion
and/or fi re asphyxiation.
• If the input to the furnace is too great because
of excessive gas pressure, wrong size nozzle or
orifi ce, high altitude, etc., the burner fl ame will
be sooty and can produce carbon monoxide,
which could result in unsafe operation,
explosion and/or fi re or asphyxiation.
In order for the fl ame to burn effi ciently, it must receive
adequate combustion air. The amount of combustion air
required varies according to altitude, actual B.T.U. content
of the fuel, gas pressure, conversion to another gas and
other factors. The burner fl ame should be observed and
any necessary adjustments made before the furnace is
placed into service. See Table 7 for Factory Air settings.
ModelNat. GasLP GasOil
66,0003.53.53.5
86,0005.365
Table 7. Factory Combustion Air Settings
23
Page 24
Gas Gun (M1B Models)
Combustion air box adjustment is made to the main burner
by loosening the two lock nuts on the plastic air shutter,
located on the left side of the burner blower housing. Air
shutter adjustment line is located on the same side of
the blower housing. Turn the plastic shutter to a smaller
number (counter clockwise) for less air to a larger number
(clockwise) for more air. Gently tighten the lock nuts after
completing the adjustment. For best results, use instrument
to measure between 8 - 9% CO
, after the combustion air
2
has been adjusted. NOTE: Do not over-tighten the lock
nuts. This may damage the plastic air shutter.
Oil Gun Only (M5S Models)
It is recommended that the CO2 and Smoke levels be
measured for maximum performance. CO2 readings should
be 10 - 11% for 66,000 BTUH furnaces and 12 - 13% for
86,000 BTUH furnaces. The Smoke should be N0. 0 on
the Bacharach Scale, and 0 to 0.02 negative draft over fi re.
Electrode Setting (Oil Gun Only)
Poor ignition of the oil spray may result if the electrodes
are not adjusted as shown in Figure 32. Do not permit
any electrodes to be grounded to any surface.
Switching Ignition Control between
Interrupted and Intermittent Duty (Oil Gun
Only)
Honeywell and Beckett oil primar y controls can be switched
between interrupted and intermittent ignition control. To
switch from interrupted duty (Factory set) to intermittent
duty, remove the blue wire from the quick-connect terminal.
Attach the burner motor and igniter wire to the burner
motor (orange) control terminal by splicing or adding tab
adapters. Seal and isolate any bare wires.
5/32” GAP
5/16” ABOVE CL
0-1/16”
1 1/8”
ELECTRODE
NOZZLE
OPERATING SEQUENCE
Direct Ignition Furnaces (M1M Models)
1. On a call for heat, the thermostat contacts close,
supplying 24 VAC between terminals C and W of the
control module.
2. When the inducer starts, the air pressure switch closes
at -0.20 W.C. differential pressure and energizes the
gas valve.
3. After a 45 second purge, the ignitor is energized for a 30
second warm-up period. After warm up, the gas valve
opens. NOTE: The time for ignition is approximately 6
seconds, after which the gas valve either remains open
if fl ame is sensed, or closes if fl ame is not sensed.
5. If fl ame is not sensed, the sequence repeats four more
times before a lockout occurs. To reset, wait 30 seconds
and then interrupt the 24 VAC power by turning the room
thermostat below room temperature, then returning it
to the original set point.
6. If fl ame does not establish on the 5th attempt (initial
fi re + 4 re-tries), the control de-energizes the gas valve,
the red LED fl ashes 4 times, and the furnace locks out
heat operation for 1 hour. See Table 9 (page 28).
7. If a fl ame is present, the control energizes the main
blower on heat speed 30 seconds after the gas valve
opens.
8. When call for heat is satisfi ed the thermostat contacts
open, the gas valve shuts off gas fl ow and the
combustion blower remains on for a 30 second postpurge period.
9. The main blower is de-energized after a 120 second
blower off delay.
Oil Gun Furnaces (M5S Models)
With Honeywell R7184 / Beckett 7505 Control
1. When a call for heat is initiated, there is a 2 to 6 second
delay while the control performs a safe start check.
2. The ignition and motor are turned on and a fl ame
should establish within a 15-second lockout time.
NOTE: Burner will prepurge for 15 seconds if equipped
with Honeywell R7184B or Beckett 7505B Control.
3. If fl ame is not sensed within the 15-second lockout
time, the control shuts down on safety lockout and must
be manually reset by pushing the reset button on the
control. If control locks over three times in a row, the
control enters restricted lockout. To reset Honeywell
R7184: Hold down the reset button for 45 seconds until
the LED fl ashes once. Beckett 7505: Hold down reset
button for 15 seconds until the red LED turns off and
the yellow LED turns on.
24
WARNING:
If furnace still doesn’t light, turn the furnace off
as described above and call your technician. In
the event of fl ashback or explosion, immediately
shut off furnace and call your service technician.
Figure 32. Oil Gun electrode Position
Page 25
4. After fl ame is established, the ignition remains on for
10 seconds to ensure fl ame stability. It then turns off.
5. The circulating air blower will energize after the
temperature fan switch closes.
6. The furnace runs until the call for heat is satisfi ed.
7. The circulating air blower will de-energize when the
temperature fan switch opens.
Gas Gun Furnaces (M1B Models)
1. On a call for heat, the furnace control begins an ignition
sequence which lasts approximately 45 seconds.
2. After this sequence, the control module tests to see if
fl ame is sensed. If it has, the furnace continues to heat
until the thermostat is satisfi ed.
3. If the burner has not lit, the ignition sequence is repeated
a maximum of two more times. If fl ame is not sensed
after three attempts, the control enters Lockout and
no further attempts to light the burner will occur. If
Lockout occurs, contact a qualifi ed service technician
for assistance.
4. When call for heat is satisfi ed, the thermostat contacts
open and the gas valve shuts off gas fl ow.
WARNING:
Should overheating occur, or the gas supply
fails to shut off, shut off the manual gas valve
to the furnace before shutting off the electrical
supply.
AVERTISSEMENT:
En case de température excessive, ou sail est
impossible de cooper l’alimentation en gaz,
fermer le robinet manuel d’alimentation en
gaz du générateur d’sir chaud avant de cooper
l’alimentation électrique.
FURNACE CONTROLS & FUNCTIONS
Furnace On / Off Switch
This switch turns electrical power to the furnace on and off.
The switch must be set in the ON position for the furnace
to operate. If blower operation is not desired, the furnace
On-Off switch may be set in the OFF position to cut the
electrical power to the furnace. See Figure 33.
Gas Valve
The gas valves for the gas furnaces are a 100% shut-off
type and will fail safe, if for some reason the gas is turned
off. The valve is a “slow-open” for M1M and M1B models
which means it opens to a low-fi re position, and after a
few seconds, “steps-open” to high-fi re.
Oil Burner Primary Control
The primary control for oil gun furnaces starts the burner,
monitors a safe operating cycle, and shuts the burner
off at the end of a heating cycle. The control uses a light
sensing transducer to determine if fuel ignition has been
successfully attained. If ignition is not attained by the end
of the safety ignition timing period, the control shuts the
burner off and enters “lock-out.” See Figure 33.
Summer Cooling - (B, C, & D Series)
Your furnace is A/C ready, equipped with A/C relay and
transformer. The unit is equipped to use a 4-wire thermostat.
When using a 5-wire thermostat, RC and RH should be
jumped (see instructions included with thermostat).
Upper
Limit
Switch
Furnace
On-Off
Switch
Oil
Pump
Lower
Limit
Switch
Fan
Control
Oil
Burner
Control
Limit Control
This furnace is protected by two high temperature safety
limit switches. The auxiliary (upper) limit switch and the
high temperature (lower) limit switch are automatic reset
types. If either limit trips, the burner will shut off. If either
limit switch trips off again soon after resetting, set the
furnace furnace On-Off switch to the OFF position and
call your authorized serviceman. See Figure 33.
Figure 33. Furnace Controls - Oil Furnace
25
Page 26
TROUBLESHOOTING
Direct Ignition Furnaces (M1M Models) &
Gas Gun Furnaces (M1B Models)
High Gas Bills
a. Verify the proper orifi ce is being used.
b. Check the return air system. Is it clear and free of
blockage?
c. Check the furnace fi lter. Is it clean or need replacing?
d. Verify the home is insulated, windows and doors fi t
tightly, and there are no leaks in the heating duct system.
e. Check the room thermostat. Is the setting higher than
necessary? Low humidity requires higher temperatures
for the same level of comfort. Check for proper humidity
level in the home.
Burner Motor won’t Run - T-stat Calls for Heat
1. Check the electrical supply to the furnace.
2. Verify the furnace furnace On-Off switch is in the ON
position.
3. Defective thermostat circuit - white and red thermostat
low voltage leads (M1/M5M, M1/M5B models). If the
burner motor or combustion fan runs, check:
• Thermostat connections
• Thermostat
4. No voltage to control module - determine if 24 volts (or
120 volts) is available to the control module. If voltage
is not available check for:
• Blown fuse, defective transformer, circuit breaker,
no electrical supply.
• Limit switch open.
• Loose connections.
Combustion Blower Runs - No Flame
1. Defective centrifugal switch (M1B Model).
• Check the operation of centrifugal switch by removing
end bell of the burner motor.
3. Burner in purge mode - allow 75 seconds for fl ame
establishing period.
4. Check for proper electrical connections at purge timer,
control box, or gas valve.
5. Check for gas supply - gas line valve on, control lever
on.
120 VAC Is Available At AMP Plug Ignitor Does Not Heat Up
1. Disconnect power to the furnace.
2. Disconnect AMP plug to the ignitor, and check ignitor
resistance with an ohm meter. Set on RX1 scale.
• Normal reading should be 40 - 75 ohms.
• If above or below this rating at room temperature
change ignitor.
3. Check for continuity from ignitor receptacle to burner.
Control Module is Powered - Ignitor won’t Heat
Up
1. Disconnect ignitor leads at AMP receptacle and check
for 120 volts at the plug during ignition sequence.
2. Replace ignition control if 120 volts is not available at
AMP plug during ignition sequence.
Main Flame Ignites - Burner Locks Out
• Ignition control is not properly grounded.
• Defective ignition control.
• Improper polarity of 120 volt power supply.
• Ignitor has hairline crack.
• Improper gas pressure or burner air adjustment is not
allowing fl ame to contact ignitor tip for fl ame rectifi cation.
• Misaligned ignitor does not allow fl ame to contact ignitor
tip for fl ame rectifi cation.
Burner Short Cycling - Thermostat Calls
for Heat, Limit Switches Closed
• Check for polarity.
• Check ground.
• Check fl ue.
• Check combustion air.
• Check gas pressure.
• Check orifi ce.
• Check the position of ignitor, a normal reading should
be 40-75 ohms.
24 Volts Supplied To Gas Valve During Ignition
- No Main Gas Flow
• Gas valve may be defective. Replace if necessary.
• Gas piping may be plugged. Check for adequate gas
supply to gas valve at union.
Burner Operates - Insuffi cient Heat
• Check thermostat for proper setting and location.
Thermostat should not be located where it will be affected
by another heat source.
• Check for clean fi lter and proper air fl ow.
• Check burner for proper gas fi ring rate.
• Be sure unit is not undersized for its thermal load.
• Check thermostat anticipator. The nominal setting is
0.4.
Burner Flame Without Motor Running
• Gas valve stuck open, check gas valve for proper
operation (replace if necessary) and inspect heat
exchanger.
• Check for 115 volts to the combustion blower motor;
replace if necessary.
• If no power to combustion blower then check wiring and
control module; replace if necessary.
Circulation Air Blower Will Not Operate
Even Though The Burner Does Operate
• Check thermostat G connection.
• Check wiring to motor.
• Check for a defective motor.
26
Page 27
Oil Gun - Honeywell R7184 or Beckett 7505
Controls Only - M5S Series.
Burner does not start with a call for heat
• Check the electrical supply to furnace.
• Verify the furnace door switch is in the ON position.
• Check for line voltage (115 VAC) at the oil primary
control.
• Check indicator LED with burner off, no call for heat (no
fl ame). See Table 9 (page 28).
- If green LED indicator is on, the cad cell is seeing
stray light or the cad cell of controller is defective.
- If green LED indicator is off, go immediately to step
5.
- If LED indicator is fl ashing (red or green on Beckett
7505 control), refer to the next step 1 below - Reset
primary control.
• Jumper T to T terminals on primary control.
- If burner starts, check thermostat or limit wiring
connections.
- If burner does not start, turn off power. Check all
wiring connections.
- If burner does not start, replace primary control.
Burner starts & then locks out on safety
with Honeywell R7184 LED indicator fl ashing
½ second on, ½ second off. For Beckett 7505
control, the red LED will fl ash
1. Reset primary control: To reset the control from (soft)
lockout, the button needs only to be pressed and
released. If the R7184 control is in restricted mode,
press and hold the button for 45 seconds - until the
LED fl ashes once. If the 7505 control is in restricted
mode, press and hold the button in for 15 seconds until
the red turns off and the yellow LED turns on.
7. If the burner stays running, the system is operational.
8. If the (LED indicator for R7184 control; green LED for
7505 control) is off, check the cad cell assembly after
disconnecting the line voltage.
Burner will not start and the LED indicator
is fl ashing at 2 seconds on, 2 seconds off
for R7184 (or green LED is fl ashing for 7505)
• Hold the reset button down for 1 - 2 seconds. If LED
indicator continues to fl ash, wait for 60 - 70 seconds. If
it still continues to fl ash, replace the primary control.
• Honeywell R7184 control: To check cad cell resistance,
press and release the button during the run mode, with
the igniter off. The LED will fl ash to indicate the cad cell
resistance. For proper burner operation, it is important
that the cad cell resistance is under 1600 Ohms. For
cad cell resistance, see Table 8.
• Beckett 7505 control: To check cad cell resistance,
unplug the cad cell leads (yellow wires) from the control.
Measure the resistance with a meter in the conventional
way (when a fl ame is present). For proper burner
operation, it is important that the cad cell resistance is
under 1,600 Ohms.
LED Flashes (Ohms)Cad Cell Resistance
10-400
2400-800
3800-1600
4>1600
Table 8. Cad Cell Resistance when
sensing fl ame
NOTE: Restricted Lockout: If the control locks out three
times in a row without a complete heat cycle between
attempts, the lockout becomes a restricted (hard) lockout.
2. If the LED indicator stops fl ashing and the ignition
remains off, the primary control could be defective. If
line voltage is present at the igniter terminals, and there
is no ignition, the igniter is likely defective and needs
to be replaced.
3. If the stops fl ashing, burner turns on, but the control
locks out again, check the cad cell. If the cad cell is
operational, replace the primary control.
4. If the LED continues to fl ash at the interval listed
above, verify that the control is not in restricted mode.
If in restricted mode, reset it. If not in restricted mode,
replace the control.
5. If the (LED indicator for R7184 control; green LED for
7505 control) stays off while the fl ame is on, check the
cad cell sighting for view of the fl ame.
6. If the burner locks out, check the cad cell resistance
(See Table 8).
27
Page 28
CONTROL MODULE STATUS INDICATORS - M1M SERIES
Red LED IndicatorStatus
Steady ONControl OK
Steady OFFNo power
Rapid fl ashFalse fl ame or internal control fault
One fl ashLimit switch is open
Two fl ashesPressure switch is open
Three fl ashesPressure switch is stuck closed
Four fl ashesLockout due to failed ignition
Five fl ashes
Flame Status - A Yellow LED labeled “Flame” is provided to indicate
fl ame status. When fl ame is sensed, the fl ame LED is lit. If fl ame sense
is weak, yellow LED will fl ash.
CONTROL MODULE STATUS INDICATOR - M1B
Red LED IndicatorStatus
One fl ash
Two fl ashes
Three fl ashes
Four fl ashes
L1 neutral reversed or L1 voltage not
present on L1
The control is in lock-out because the inducer
centrifugal switch is or was stuck closed.
The control is in lockout because the signal
was not received by the control that the
inducer centrifugal switch had closed within
the time.
The control is in lockout because a failed
ignition attempt, a gas valve error, or a false
fl ame sensed during the warm up period. If
false fl ame has been sensed, the control
will return to normal operation, and repeat
ignition sequence when the false fl ame is
not present.
The control is in lockout due to a failure
within the control board
OPTIONAL ACCESSORIES
Necessary when the Furnace is Used with Some
Central Air Conditioners
If an air conditioner is installed that does not use the furnace
blower for air distribution and operates independently of
the furnace, the thermostat system must have an interlock
to prevent the furnace and air conditioner from operating
at the same time. This interlock system usually contains
either a “Heat-Cool” switch which must be turned to one
of the positions to activate heat or cool operation, or a
positive “OFF” switch on the cooling thermostat.
The furnace must also be equipped with an automatic
damper to prevent cold air from being discharged up
around the heat exchanger (NORDYNE p/n 901996 for
furnaces without coil cavity, or p/n 901083 with coil cavity).
See Figure 34 or 35. Cold air may cause condensation
inside the heat exchanger which can rust and lead to
early failure.
Control Module Status Indicator -
M5S Series Honeywell R7184 Control
Green LED
Indicator
On
OffCad cell is not sensing fl ame
Flashing - 1/2 sec.
on, 1/2 sec. off
Flashing - 2 sec. on,
2 sec. off
LED Indicator
Color
Red
Green
Yellow
Cad cell is sensing fl ame
(could be fl ame or stray light)
Lockout / Restricted Lockout
Recycle
Beckett 7505 Control
On ContinuouslyFlashing
Restricted (hard)
lockout
Cad cell is sensing
fl ame - (could be
fl ame or stray light)
Pump prime mode
or reset button
currently held for
15+ sec.
Status
Soft lockout
Recycle
N/A
Table 9. Control Module Status Indicators
Figure 34. Coil Cavity Damper
Figure 35. Damper without Coil Cavity
28
Page 29
Optional Add-On Air Conditioning
Check for
Ice Here
Whether split system or single package, an energysaving NORDYNE Air Conditioner is available that has
been designed specifi cally for manufactured housing
applications and can best handle your home comfort
needs. Ask your dealer or contractor about NORDYNE
add-on central air conditioning systems.
Single package unit includes cooling coils, compressor,
and vertical discharge fan. This type of unit connects with
the existing home air duct system (an optional close-off
damper is required with the furnace).
Split system unit with vertical discharge for quiet operation
connects with NORDYNE cooling coil furnace (optional
coil cavity required with “A” model furnaces).
MAINTENANCE
Homeowner Information
• On some closet installations, the return air opening
to the furnace may be on the fl oor, in the door, in the
side wall of the closet, or any combination of these. The
upper grille on the front of the furnace admits return air
to the blower. Return air must be provided back to the
circulating blower in order to provide air distribution.
See Figure 36.
• Filters - At least twice each season (more often in dusty
areas) remove and clean the air fi lters with a vacuum
or with warm water and soap. Reinstall when dry. Also
clean dust and lint around furnace and in the furnace
vestibule.
• During extremely cold weather, ice may form on the
furnace roof jack (Figure 37). Small amounts of ice
forming on the roof jack will present no problems to
proper furnace operation. Excessive ice formation
could restrict the combustion air supply to the burner,
causing ineffi cient burner operation. If excessive ice
has formed on the air inlet or exhaust portions of the
roof jack, it must be carefully removed.
WARNING:
Use of furnace or air conditioning components
that are not included in the certifi cation of
this appliance may create a hazard, invalidate
the certifi cation, and in many states, make
installations illegal. Listed NORDYNE air
conditioning components are specifi ed on the
furnace label.
Additional Oil Furnace Maintenance
In addition to the preceding, the following should be
performed by a qualifi ed service contractor at least once
each season for oil-fi red furnaces:
• Replace the oil nozzle with the type nozzle specifi ed
for your furnace.
• Clean, adjust and replace if necessary the spark
electrodes.
• Reset the nozzle/drawer assembly to factory
specifi cations.
• Clean the inside of the furnace heat exchanger and
replace the combustion liner if necessary.
• Clean or replace the oil fi lter element at the oil tank.
• Adjust the burner for top effi ciency and check to make
sure all fi ttings are leak-tight.
Installer Information
All furnaces need periodic service at the beginning of each
heating season. Call your qualifi ed service contractor for
these items:
• Remove the air circulator and clean all dust and lint
from the unit with a stiff bristle brush.
• Inspect the combustion chamber blower compartment,
fl ue collar and Roof Jack.
• Check the gas valve (if applicable) and fuel line
connections for leaks.
• Make any adjustments necessary for good operation.
NOTES: For Canadian high altitude (2,000 - 4,500’), reduce gas manifold pressure to 3.0” W.C. for natural gas and 9” W.C. for LP gas.
(Includes 4% Input Reduction for Each 1,000 Feet). These specs do not apply to oil furnace installations. Reference Sources: ANSI Z233.1 &
NFPA 54, National Fuel Gas Code.
Table 11. Equivalent Orifi ce Sizes for High Altitude Installations
M1/M5*B Models & for use with Blower Kit No. 903773 1/4 Hp 3 Speed
Furance Input
086, 090HLMH
066, 070, 077MLMH
56LLMH
Heating Speed
Setting
2 Ton2-1/2 Ton3 Ton
Cooling Speed/ Evap Coil
M1/M5*C Models & for use with Blower Kit No. 903413 1/2 Hp 4 Speed
Furance Input
077, 086, 090MLLMLMHH
056, 066, 070LLMLMHH
Heating
Speed
Setting
2 Ton2-1/2 Ton & 3 Ton3-1/2 Ton4 Ton
Cooling Speed/ Evap Coil
M1/M5*D Models & for use with Blower Kit No. 903890 3/4 Hp 4 Speed
Furance Input
077, 086, 090MLLMLMHH
056, 066, 070LLMLMHH
Heating
Speed
Setting
2 Ton2-1/2 Ton & 3 Ton3-1/2 Ton & 4 Ton5 Ton
Cooling Speed/ Evap Coil
Table 12. A/C Blower Speed Selection Chart
31
Page 32
GAS INFORMATION
TIME FOR
ONE REVOLUTION
(SECONDS)
103601,8003,600
123001,5003,000
142571,2862,571
162251,1252,250
182001,0002,000
201809001,800
221648181,636
241507501,500
261386921,385
281296431,286
301206001,200
321135631,125
341065291,059
361005001,000
3895474947
4090450900
4286429857
4482409818
4678391783
4875375750
5072360720
5269346692
5467333667
5664321643
5862310621
6060300600
6258290581
6456281563
GAS FLOW RATES
CUBIC FEET PER
REVOLUTION OF GAS METER
15 10
GAS FLOW RATES
TIME FOR
ONE REVOLUTION
(SECONDS)
6655273545
6853265529
7051257514
7250250500
7449243486
7647237474
7846231462
8045225450
8244220439
8443214429
8642209419
8841205409
9040200400
9239196391
9438191383
9638188375
9837184367
10036180360
10235176353
10435173346
10634170340
10833167333
11033164327
11232161321
11432158316
11631155310
11831153305
12030150300
CUBIC FEET PER
REVOLUTION OF GAS METER
15 10
32
Table 13. Gas Flow Rates (Cubic Feet per Hour)
GAS PIPE CAPACITIES
Nominal Pipe
Diameter (IN.)
1/213090756555504540
3/42801901501301151059590
1520350285245215195180170
1 1/41,050730590500440400370350
1 1/21,6001,100890760670610
1020304050607080
Cubic Feet Per Hour Required =
Length of Pipe Run (Feet)
Input To Furnace (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
NOTE: The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas fl ow required by
the furnace. To determine the cubic feet per hour of gas fl ow required by the furnace, divide the input rate of the furnace by
the heating value (from gas supplier) of the gas.
Table 14. Capacity of Black Iron Gas Pipe (cu. ft. per hour)
for Natural Gas w/ Specifi c Gravity = 0.60
Page 33
SUPPLIED
BY INSTALLER
ELECTRICAL INFORMATION
Control
Board "H"
BlackBlu eOrange
Wire #2Wire # 3 Wir e #4
MOTOR
4 SPEED
BLOWER
MOTOR
3 SPEED
BLOWER
654321
WHITE
ORANGE (MED. LO)
BLUE (MED. HI)
BLACK (HIGH)
RED (LO)
654321
WHITE
RED (LO)
BLUE (MED. HI)
BLACK (HIGH)
Blowe r Wire Conne ctions
Wire #1
Furnace
TieTieTi e
Red
Model
M1MA 056/
TieControlTieControl
M1MB
Wrapped Board "C" Wrapped Board "H"
056
Wrapped Wrapped Wrapped
070/077/090
AUX. LIMIT
HI-LIMIT
WHITE
GREEN
RED
GRAY
BLUE
BLUE
BLUE
Gas Direct Ignition Furnace,
Heating & A/C Ready, M1M All Models.
C
R
G
W
654321
SPEED
MOTOR
SINGLE
BLOWER
GREEN
BLACK
See Table
See Table
See Table
CONNECTOR
HOUSING CAP
TIE
WIRE
COMBUSTION FAN
BLACK
BLACK
TRANS-
FORMER
GROUND
24V
COM
TieTieControl Control
M1MB
21
Wrapped Wrapped Board "H" Board "C"
070/077
CR
24 V
SCREW
C W G R
123
456
789
115 V
L1N
CONTROL
TieControlTieTie
Wrapped Board "H" Wrapped Wrapped
90
M1MB
BLACK
LIGHTS
BLACK
ORANGE
See Table
RM
1
2
3
ControlTieTieControl
M1M(C,D)
PRESSURE
SWITCH
ORANGE
C
H
L1
F
X
NEU
4
5
6
Board "H" Wrapped Wrapped Board "C"
056/070
RED
WHITE
WHITE
BLACK
WHITE
TieTieTi eCon trol
Blower Wire Table
Wrapped Wrapped Wrapped Board "H"
077/090
M1M(C,D)
CONTROL LIGHT STATUS
FURNACE ELECTRICAL BOX
Jumper must be removed if
BLACK
BLACK
710152C 8/10
(Replaces 710152B)
langiS emalF kaeWgniknilBrewop oNFFO ydaetS
langiS emalF dooGNO ydaetSKO lortnoCNO ydaetS
WOLLEYDER
Rapid Flash False flame or internal control faultSteady OFFNo Flame Signal
1 FlashLimit switch is open
2 FlashesPressure switch is open with inducer on
3 FlashesPressure switch is closed with inducer off
4 FlashesLockout due to failed ignition
5 Flashes115 vac & neutral reversed or no ground
converting to a multispeed blower.
Jumper is required for M1MA
models and M1MB 090
A/C & Heating Speeds: Refer to
Table 12, A/C Blower Selection
in the manual
GAS VALVE
ON/OFF
SWITCH
coding. (See furnace data label for electrical
information.)
appliance) must be replaced, use 105˚C Thermoplastic
NOTES
WIRING DIAGRAM
1. Incoming power must be polarized. Observe color
type wire or its equivalent.
2. If any of the original wires (as supplied with the
BLACK
YELLOW
YELLOW
L1
GROUND SCREW
NEUTRAL
Figure 38. Gas Direct Ignition Furnace, Heating & A/C Ready - All M1M Models
5. If any of the original wire supplied with the appliance is replaced,
use
6. Use copper conductors only.
7. Flash Codes: Refer to Table 9, Control Module Status Indicators.
4 SPEED
3 SPEED
RGW
MOTOR
BLOWER
MOTOR
BLOWER
BLUE
C
6
WHITE
5
ORANGE (MED LO)
4
BLUE (MED. HI)
3
BLACK (HIGH)
2
1
RED (LO)
6
WHITE
543
RED (LO)
BLUE (MEDHI)
21
BLACK (HI)
SWITCH
ON/OFF
ERI
W
E
IT
WHITE
RED
BLUE
BLUE
WHITE
GREEN
RED
GRAY
CONNECTOR
HOUSING CAP
GREEN
ORANGE
BLACK
BLACK
A/C
BLOWER
RELAY
3
1
5
6
4
2
(SEE NOTE 3)
RED
FAN
SWITCH
HI-LIMIT
3A FUSE
GRAY
BLACK
RED
GRAY
C
GREEN
24 V
115 V
R
L1 N
TRANSFORMER
BLACK
BY INSTALLER
SUPPLIED
WHITE
RED
GRAY
BLACK
ORANGE
BLACK
WHITE
WHITE
ELECTRICAL BOX
FURNACE
SCREW
GROUND
BUSHING
CRW
TO BURNER CONTROL
RECEPTACLE
LEGEND:
34
WIRING DIAGRAM
NOTES:
1. Incoming power must be polarized. Observe color coding.
(See furnace data label for electrical information.)
2. If any of the original wires (as supplied with the appliance) must
be replaced, use 105˚C Thermoplastic type wire or its equivalent.
3. On models M1(B,S)A and M1/M5(B,S)086 jumper wire is installed.
M1B & M5S Furnace Series
On all other models, cooling speed is connected to black wire.
L1
NEUTRAL
Figure 39. Gas and Oil Furnaces, A/C Ready - M1B & M5S (066, 086) Models
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
Page 35
35
Page 36
INSTALLATION / PERFORMANCE CHECK LIST
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer.
This includes being able to install the product according to strict
safety guidelines and instructing the customer on how to operate
and maintain the equipment for the life of the product. Safety should
always be the deciding factor when installing this product and using
common sense plays an important role as well. Pay attention to
all safety warnings and any other special notes highlighted in the
manual. Improper installation of the furnace or failure to follow safety
warnings could result in serious injury, death, or property damage.
These instructions are primarily intended to assist qualifi ed individuals
experienced in the proper installation of this appliance. Some local
codes require licensed installation/service personnel for this type of
equipment. Please read all instructions carefully before starting the
installation. Return these instructions to the customer’s package for
future reference.