Nordyne JT5BD, JT5BD-018K, JT5BD-024KA, JT5BD-030KA, JT5BD-036K Installation Manual

...
Page 1
JT5BD Series
USER’S MANUAL / INSTALLATION INSTRUCTIONS
SPLIT SYSTEM HEAT PUMP - R-22
13 SEER
Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate the problem, call your servicing contractor.
The Installation Instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
Page 2
USER INFORMATION
Important Safety Information ....................................3
About the Heat Pump .................................................3
Operating Instructions ...............................................3
Cooling Operation .....................................................3
Heating Operation .....................................................3
Emergency Heat........................................................3
Defrost Operation ......................................................3
Operating the Heat Pump for Automatic
Cooling & Heating .....................................................4
Operating the Indoor Blower Continuously ................4
Turning the Heat Pump Off ........................................4
Heat Pump Maintenance ............................................4
Regular Cleaning.......................................................4
Troubleshooting ..........................................................4
INSTALLER INFORMATION
Important Safety Information ....................................5
Heat Pump Installation ...............................................6
General Information ...................................................6
Before You Install this Unit .........................................6
Locating the Heat Pump ............................................6
Packaging Removal ...................................................6
Ground Level .............................................................6
Connecting Refrigerant Tubing between the
Indoor & Outdoor Unit ...............................................7
Electrical Wiring ..........................................................7
Pre - Electrical Checklist ...........................................7
Line Voltage ...............................................................7
Grounding..................................................................8
Thermostat Connections ...........................................8
Startup & Adjustments ..............................................9
Pre - Start Checklist ..................................................9
Start-up Procedures ..................................................9
Air Circulation - Indoor Blower ...............................9
System Cooling ......................................................9
System Heating ......................................................9
Refrigerant Charging ..................................................9
Charging R-22 Units in AC Mode with
Outdoor Temperatures Above 55° F ........................10
Heat Pump Maintenance ..........................................10
Replacement Parts ...................................................10
WARRANTY INFORMATION
A warranty certifi cate with full details is included with the Heat Pump. Carefully review these responsibilities with your dealer or service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc. Some specifi c examples of service calls which are not included in the limited warranty are:
• Correcting wiring problems in the electrical circuit supplying the Heat Pump.
• Resetting circuit breakers or other switches.
• Adjusting or calibrating of thermostat.
Figures & Tables .......................................................11
Figure 5. Unit Dimensions ...................................11
Refrigerant Charging Charts ...................................11
Figure 6. JT5BD-018K (1.5 Ton Units) ................11
Figure 7. JT5BD-024KA (2 Ton Units) .................12
Figure 8. JT5BD-030KA (2.5 Ton Units) ..............12
Figure 9. JT5BD-036K (3 Ton Units) ...................13
Figure 10. JT5BD-042K (3.5 Ton Units) ..............13
Figure 11. JT5BD-048K (4 Ton Units) .................14
Figure 12. JT5BD-060K (5 Ton Units) .................14
Refrigerant Charging Tables - Cooling Mode ..........15
Table 4. JT5BD-018K (1.5 Ton Units) ..................15
Table 5. JT5BD-024KA (2 Ton Units) ...................15
Table 6. JT5BD-030KA (2.5 Ton Units) ................16
Table 7. JT5BD-036K (3 Ton Units) .....................16
Table 8. JT5BD-042K (3.5 Ton Units) ..................17
Table 9. JT5BD-048K (4 Ton Units) .....................17
Table 10. JT5BD-060K (5 Ton Units) ...................18
Refrigerant Charging Tables - Heating Mode ..........19
Table 11. JT5BD-018K (1.5 Ton Units) ................19
Table 12. JT5BD-024KA (2 Ton Units) .................19
Table 13. JT5BD-030KA (2.5 Ton Units) ..............20
Table 14. JT5BD-036K (3 Ton Units) ...................20
Table 15. JT5BD-042K (3.5 Ton Units) ................21
Table 16. JT5BD-048K (4 Ton Units) ...................21
Table 17. JT5BD-060K (5 Ton Units) ...................22
Electrical Information ...............................................23
Figure 12. JT5BD Wiring Diagram .......................23
Table 18. Electrical Specs & Physical Data ..........24
2
Page 3
USER INFORMATION
IMPORTANT SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
ABOUT THE HEAT PUMP
Your heat pump is a unique, all weather comfort-control appliance that will heat and cool your home year round and provide energy saving comfort. It’s an unknown fact that heat is always in the air, even when the outside temperature is below freezing. The heat pump uses this basic law of physics to provide energy saving heat during the winter months. For example, If the outdoor temperature is 47° F (8° C), your heat pump can deliver approximately
3.5 units of heat energy per each unit of electrical energy used, as compared to a maximum of only 1 unit of heat energy produced with conventional heating systems.
In colder temperatures, the heat pump performs like an air conditioner run in reverse. Available heat energy outside the home is absorbed by the refrigerant and exhausted inside the home. This effi cient process means you only pay for “moving” the heat from the outdoors to the indoor area. You do not pay to generate the heat, as is the case with more traditional furnace designs.
During summer, the heat pump reverses the fl ow of the heat-absorbing refrigerant to become an energy-effi cient, central air conditioner. Excess heat energy inside the home is absorbed by the refrigerant and exhausted outside the home.
OPERATING INSTRUCTIONS
Please refer to the thermostat manufacturer’s User manual for detailed programming instructions.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately 5 minutes following a previous operation or the interruption of the main electrical power.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately 5 minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat
Some thermostats may include a system mode called EM HT or AUX HT, etc. This is a back-up heating mode that should only be used if a problem is suspected. With the mode set to EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
Defrost Operation
During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will defrost itself. This unit monitors ambient and coil temperatures to regulate the defrost function accordingly.
3
Page 4
USER INFORMATION
At the beginning of the defrost cycle, both the outdoor condenser fan and compressor will turn off. After approximately 30 seconds, the compressor will turn on and begin to heat the outdoor coil causing the ice and snow to melt.
NOTE: While the ice and snow is melting, some steam may rise from the outdoor unit as the warm coil causes the melting frost to evaporate. When defrost is completed, the outdoor fan motor will start, and the compressor will turn off again. In approximately 30 seconds the compressor will start up again and continue normal operation.
Operating the Heat Pump for Automatic Cooling and Heating
1. Set the thermostat system switch to AUTO and the thermostat fan switch to AUTO. See Figure 1.
NOTE: Thermostat styles vary. Some models will not include the AUTO mode and others will have the AUTO in place of the HEAT and COOL. Others may include all three. Refer to the instructions supplied with your thermostat for specifi c instructions.
2. Set the thermostat temperature to the desired temperature level. The outdoor unit and the indoor blower will then cycle on and off in either the heating or cooling mode of operation as required to automatically maintain the indoor temperature within the desired limits.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
Set the thermostat fan mode to ON (Figure 1). The indoor blower starts immediately, and will run continually until the fan mode is reset to AUTO.
The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, including OFF.
HEAT PUMP MAINTENANCE
CAUTION:
Shut off all electrical power to the unit before performing any maintenance. Failure to comply may result in personal injury or death.
Proper maintenance is most important to achieve the best performance from the appliance and should be performed by a qualifi ed service technician at least once a year. Read the maintenance items below and follow the instructions for years of safe, trouble free operation.
Regular Cleaning
WARNING:
Do not place combustible material on or against the unit cabinet. Do not place combustible materials, including gasoline and any other fl ammable vapors and liquids, in the vicinity of the unit.
• Clean or replace the indoor air fi lter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air fi lter.
• Remove any leaves and grass clippings from around the coil of the outdoor unit, being careful not to damage the aluminum fi ns.
• Check and remove any obstructions, such as twigs, sticks, etc.
TROUBLESHOOTING
If the unit fails to operate, check the following:
• The thermostat is properly set. See Cooling Operation for air conditioning or Heating Operation for furnace.
• The unit disconnect fuses are in good condition and the electrical power to the unit is turned on.
Turning the Heat Pump Off
Change the thermostat’s system mode to OFF and the fan mode to AUTO. See Figure 1. NOTE: The system will not operate, regardless of the temperature selector setting.
4
Page 5
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
WARNING:
Unless noted otherwise in these instructions, only factory authorized parts or accessory kits may be used with this product. Improper installation, service, adjustment, or maintenance may cause explosion, fi re, electrical shock or other hazardous conditions which may result in personal injury or property damage
WARNING:
JT5BD Split System Heat Pumps leave the factory with a nitrogen holding charge. Follow all charg­ing instructions for maximum unit performance and effi ciency. Some local codes require licensed installation/service personnel to service this type of equipment. Refrigerant charging must be done by qualifi ed personnel familiar with safe and en­vironmentally responsible refrigerant handling procedures. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
CAUTION:
This unit uses refrigerant R-22. DO NOT use any other refrigerant in this unit. Use of another refrigerant will damage the unit.
WARNING:
The information listed below must be followed during the installation, service, and operation of this unit. Unqualifi ed individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious per
injury or death
• The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
• All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
• This equipment contains liquid and gaseous refrigerant under high pressure. DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment.
• Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
• Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fi re extinguisher, etc.) when performing brazing operations.
• This unit is designed for outdoor installations only and should be located as descibed on page 6.
• Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
.
sonal
5
Page 6
HEAT PUMP INSTALLATION
General Information
The JT5BD series Heat Pump is designed only for outdoor rooftop or ground level installations. This unit has been tested for capacity and effi ciency in accordance with A.H.R.I. Standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.
Before You Install this Unit
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired and provided with circuit protection in accordance with local building codes. If there is any question concerning the power supply, contact the local power company.
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to the indoor unit's installation instructions for installation details.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Verify coil fi ns are straight. If necessary, comb fi ns to remove fl attened or bent fi ns. Claims for damage (apparent or concealed) should be fi led immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read all instructions before installing the unit.
Locating the Heat Pump
• Survey the job site to determine the best location for mounting the outdoor unit. See Figure 5 (page 11) for unit dimensions.
• Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided.
• Suffi cient clearance for unobstructed airfl ow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 2 for minimum clearances to obstructions.
• Consideration should be given to availability of electric power, service access, noise, and shade.
Packaging Removal NOTE: To prevent damage to the tubing connections,
carefully remove the carton and user’s manual from the equipment. Discard the shipping carton.
Ground Level
Ground level installations must be located according to local building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown in Figure 2.
• A suitable mounting pad (Figure 3) must be provided and separate from the building foundation. The pad must be level and strong enough to support the weight of the unit. The slab height must be a minimum of 2” (5 cm) above grade and with adequate drainage.
DO NOT
18"
18"
18"
OBSTRUCT
TOP OF UNIT
Figure 2. Clearance Requirements
6
2”
Figure 3. Ground Level Installation
18"
Page 7
Connecting Refrigerant Tubing Between the Indoor & Outdoor Unit
CAUTION:
This system uses R-22 refrigerant with POE oil. When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.
After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices.
• To maintain the unit's warranty, it is required that a fi lter drier be installed when the system is open to the atmosphere. This includes, but is not limited to, replacing the evaporator and/or condenser of a system. The fi lter drier must be installed in strict accordance with the manufacturer’s installation instructions.
• Optional equipment such as liquid line solenoid valves, low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.
ELECTRICAL WIRING
• When connecting refrigerant linesets together, it is recommended that dry nitrogen be fl owing through the joints during brazing to prevent internal oxidation and scaling.
• Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.
• Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.
• Tubing should be kept clean of foreign debris during installation.
• Every effort should be made by the installer to ensure that the fi eld installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.
• The maximum recommended interconnecting refrigerant line lengths is 75 ft. and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 ft.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire Length-Feet
200 150 100 50
6 8 10 14 15 46812 20 46810 25 44610 30 3468 35 3468 40 2346 45 2346 50 2346 55 1234 60
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
Supply Circuit
Ampacity
WARNING:
To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.
Label all wires prior to disconnection when servicing the unit. Wiring errors can cause improper and dangerous operation.
• All electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
Verify that the voltage, frequency, and phase of the
supply source match the specifi cations on the unit rating plate. See Table 18 (page 24).
Verify that the service provided by the utility is suffi cient
to handle the additional load imposed by this equipment. Refer to the unit wiring label for proper voltage wiring.
Verify factory wiring is in accordance with the unit
wiring diagram or Figure 13 (page 23). Inspect for loose connections.
Line Voltage
• A wiring diagram is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit.
An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.
• Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming fi eld wiring and minimum size of electrical conductors and circuit
7
Page 8
Thermostat
GRW2CEOY
NOTE: Jumper between W2 and E is required when no OD T-Stat is used.
For 2-Stage Heater Kits
Green
Red
Brown
Orange
Black
G
R
W
W
2
C
Air Handler Heat Pump OD
Section
Typical Heat Pump with Standard Air Handler
Thermostat
GRW2CEOY
Red
G
R
W
C
C
Green
White
Black
C
W
O Y
OY
E
R
2
protection must be in compliance with information listed on the outdoor unit data label. Any other wiring methods must be acceptable to authority having jurisdiction.
• The outdoor unit requires both power and control circuit electrical connections. Refer to the wiring diagram / schematic for identifi cation and location of outdoor unit fi eld wiring interfaces Figure 13 (page 23). Make all electrical connections in accordance with all applicable
R
W
2
codes and ordinances.
• Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits.
• Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the terminals on the contactor inside the control compartment.
• Use only copper wire for the line voltage power supply to this unit as listed in Table 1. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
• 208/230 Volt units are shipped from the factory wired for 230 volt operation. For 208V operation, remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V.
• Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not use gas piping as an electrical ground
!
Air Handler Heat Pump OD
Typical Heat Pump with
Outdoor Thermostat and Air Handler
Figure 4. Typical Thermostat Connections
8
Section
This unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical Code. Use the grounding lug provided in the control box for grounding the unit.
Thermostat Connections
• Thermostat connections should be made in accordance with the instructions supplied with the thermostat and the indoor equipment.
• The outdoor unit is designed to operate from a 24 VAC Class II control circuit. The control circuit wiring must comply with the current provisions of the NEC (ANSI/ NFPA 70) and with applicable local codes having jurisdiction.
• The low voltage wires must be properly connected to the units low voltage terminal block (Figure 4).
Page 9
Recommended wire gauge and wire lengths for typical thermostat connections are listed in Table 2.
• The thermostat should be mounted about 5 feet above the fl oor on an inside wall. DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fi replaces, sunlight, or lighting fi xtures, and convective heat from warm air registers or electrical appliances. Refer to the thermostat manufacturer’s instruction sheet for detailed mounting and installation information.
Recommended T-Stat Wire
Thermostat
Wire Gauge
24 55 25
22 90 45
20 140 70
18 225 110
Table 2. Thermostat Wire Gauge
Unit to T-Stat (Length in FT)
2-Wire
(Heating)
5-Wire
(Heating/Cooling)
START UP & ADJUSTMENTS
Pre-Start Check List
Verify the indoor unit is level and allows proper
condensate drainage.
Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/ control panels are in place.
Verify air fi lters are cleaned and properly installed. Verify duct work is sealed to prevent air leakage. Verify line voltage power leads are securely connected
and the unit is properly grounded.
Verify low voltage wires are securely connected to the
correct leads on the low voltage terminal strip.
Verify power supply branch circuit overcurrent protection
is sized properly.
Verify the thermostat is wired correctly.
Start-Up Procedures
The thermostat's function mode should be set to OFF and the fan mode should be set to AUTO. Close all electrical disconnects to energize the system.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan
mode to ON.
2. Verify the blower runs continuously. Check the air delivery
at the supply registers and adjust register openings for balanced air distribution. If insuffi cient air is detected, examine ductwork for leaks or obstructions.
3. Set the thermostat fan mode to AUTO and verify the
blower stops running.
System Cooling
1. Set the thermostat’s system mode to COOL and the fan mode to AUTO. Gradually lower the thermostat temperature setpoint below room temperature and verify the outdoor unit and indoor blower energize.
2. Verify blower wheel is spinning in direction indicated by arrow. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes and then set the temperature selector above room temperature. Verify the fan and compressor cycle off with the thermostat. NOTE: The blower should also stop unless fan mode is set to the ON position.
System Heating (optional)
1. Set the thermostat's system mode to HEAT and the temperature mode above room temperature.
2. Verify the optional heating equipment (furnace or electric heat) and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
Refrigerant Charging
WARNING:
JT5BD Split System Heat Pumps leave the factory with a nitrogen holding charge. DO NOT operate any unit while it contains a Nitrogen holding charge. Doing so may damage the units compressor. Follow these charging instructions for maximum unit performance and effi ciency. Some local codes require licensed installation/ service personnel to service this type of equipment. Refrigerant charging must be done by qualifi ed personnel familiar with safe and environmentally responsible refrigerant handling procedures. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
To properly charge these units:
1. Read all Installation Instructions fi rst.
2. Complete any brazing operations. (e.g. Split system line-sets)
3. Leak check and evacuate the whole system using proper methods.
4. Purge the nitrogen holding charge.
5. Evacuate the unit to 350-500 microns.
9
Page 10
6. Allow the unit to remain under vacuum for at least 30 min.
7. Weigh-In the proper amount of new (or reclaimed) R-22 refrigerant. Refer to Table 3 or the units rating label to determine the correct amount of charge.
• Refrigerant charging charts are applicable only to
matched assemblies of NORDYNE equipment and listed airfl ows for the indoor coil. Refer to Figures 6 ­12 (pages 11 - 14) and Tables 4 - 10 (pages 15 - 18) for correct system charging.
• JT5BD outdoor units with indoor coils not listed are
not recommended. Deviations from rated airfl ows or non-listed combinations may require modifi cation to the expansion device and refrigerant charging procedures for proper and effi cient system operation.
• The refrigerant charge can be checked and adjusted
through the service ports provided external to the outdoor unit. Use only gage line sets which have a “Schrader” depression device present to actuate the valve.
Charging an R-22 system in AC mode at outdoor tem­peratures above 55° F for optimized sub-cooling of 10° F - 12° F.
1. With the system operating at steady-state, measure the liquid refrigerant pressure (in psig) at the outdoor unit service valve.
2. Measure the liquid refrigerant temperature (in Fahrenheit) at the service valve.
3. Deter mine the required liquid refrigerant pressure. Refer to Tables 11 - 17 (pages 19 - 22) for correct system charging.
• If the pressure measured in Step 1 is greater than the required liquid refrigerant pressure determined in Step 3, then there is too much charge in the system. Remove refrigerant and repeat Steps 1 through 3 until the system is correctly charged.
• If the pressure measured in Step 1 is less than the required liquid refrigerant pressure determined in Step 3, there is too little charge in the system. Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged.
Restrictor Bore Size
Model
Number
JT5BD-
(inches)
Indoor Outdoor
System Charge R2 (oz.)
018K 0.053 0.041 93 024KA 0.061 0.047 96 030KA 0.069 0.049 144
036K 0.078 0.057 155
042K 0.083 0.059 248
048K 0.090 0.065 248
060K 0.101 0.071 268
HEAT PUMP MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.
Proper maintenance is important to achieve optimum performance from the Heat Pump. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools. If you do not possess these skills, contact your dealer for maintenance. Consult your local dealer about the availability of maintenance contracts. Routine maintenance should include the following:
• Inspect and clean or replace air fi lters at the beginning of each heating and cooling season, or more frequently if required.
• Inspect the condensate drain and outdoor coil at the beginning of each cooling season. Remove any debris. Clean the outdoor coil and louvers as necessary using a mild detergent and water. Rinse thoroughly with water.
• Inspect the electrical connections for tightness at the beginning of each heating and cooling season. Service as necessary.
CAUTION:
The unit should never be operated without a fi lter in the return air system. Replace disposable fi lters with the same type and size.
• Do not attempt to add additional oil to motors unequipped with oil tubes. The compressor is hermetically sealed at the factory and does not require lubrication.
REPLACEMENT PARTS
Replacement parts are available through all Nordyne Please have the complete model and serial number of the unit when ordering replacement parts.
ELECTRICAL:
Capacitors Temperature Limit Switches
Compressors Thermostats
Contactors Time Delay Relays
Pressure Switches Transformers
Relays
MOTORS:
Blower Motor Fan Motor
COMPONENTS:
Blower Assembly Fan Grille
Cabinet Panels Filter/Driers
Expansion Valves
distributors.
Table 3.
10
13 SEER Split System Heat Pump Orifi ce
Page 11
FIGURES & TABLES
DO NOT OBSTRUCT TOP OF UNIT
Allow adequate clearance for airflow
D
W
H
Model Number JT5BD- Height -H- Width -W- Depth -D-
018K 27" 30 3/4" 30 3/4"
024KA 27" 30 3/4" 30 3/4"
030KA 39" 30 3/4" 30 3/4"
036K 43" 30 3/4" 30 3/4"
042K 39" 30 3/4" 30 3/4"
048K 43" 30 3/4" 30 3/4"
060K 43" 30 3/4" 30 3/4"
Figure 5. Unit Dimensions
REFFRIGERANT CHARGING CHARTS
JT5BD-018K Charging Chart
375
350
Remove refrigerant when above curve
325
300
275
250
225
200
Liquid Pressure (psig)
175
Add refrigerant when below curve
150
125
75 80 85 90 95 100 105 110 115 120 125 130
Liquid Temperature (F)
Figure 6. Charging Chart for 1.5 Ton Units
11
Page 12
JT5BD-024KA Charging Chart
350
325
Remove refrigerant when above curve
300
275
250
225
Liquid Pressure (psig)
200
Add refrigerant when below curve
175
150
75 80 85 90 95 100 105 110 115 120 125 130
Liquid Temperature (F)
Liquid Pressure (psig)
350
325
300
275
250
225
200
175
Figure 7. Charging Chart for 2 Ton Units
JT5BD-030KA Charging Chart
Remove refrigerant when above curve
Add refrigerant when below curve
150
75 80 85 90 95 100 105 110 115 120 125 130
12
Liquid Temperature (F)
Figure 8. Charging Chart for 2.5 Ton Units
Page 13
JT5BD-036K Charging Chart
350
325
Remove refrigerant when above curve
300
275
250
225
200
Liquid Pressure (psig)
175
150
75 80 85 90 95 100 105 110 115 120 125 130 135
Liquid Temperature (F)
Add refrigerant when below curve
Figure 9. Charging Chart for 3 Ton Units
JT5BD-042K Charging Chart
350
325
Remove refrigerant when above curve
300
275
250
225
200
Liquid Pressure (psig)
Add refrigerant when below curve
175
150
75 80 85 90 95 100 105 110 115 120 125 130 135
Figure 10. Charging Chart for 3.5 Ton Units
Liquid Temperature (F)
13
Page 14
JT5BD-048K Charging Chart
350
325
Remove refrigerant when above curve
300
275
250
225
200
Liquid Pressure (psig)
Add refrigerant when below curve
175
150
75 80 85 90 95 100 105 110 115 120 125 130 135
Liquid Temperature (F)
Liquid Temperature (psig)
350
330
310
290
270
250
230
210
190
170
Figure 11. Charging Chart for 4 Ton Units
JT5BD-060K Charging Chart
Remove refrigerant when above curve
Add refrigerant when below curve
150
75 80 85 90 95 100 105 110 115 120 125 130 135
14
Liquid Temperature (F)
Figure 12. Charging Chart for 5 Ton Units
Page 15
REFRIGERANT CHARGING TABLES - COOLING MODE
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode at ambient above 70°F.
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
73 140 135
75 143 140 155 137
77 145 146 157 143 170 140
79 147 150 160 148 172 145 185 142
81 151 153 162 152 175 150 187 147 200 144
83 166 155 177 154 189 151 202 149 215 147
85 181 157 192 155 204 153 217 151 230 149
87 196 159 207 157 219 155 232 153 244 151
89 199 163 211 161 222 159 234 157 246 154
91 214 165 226 163 237 161 248 158
93 229 167 241 165 252 163
95 244 169 256 167
97 259 172
99
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 4. Charging Table for JT5BD-018K Series (1.5 Ton Units)
Liq.
Press.
Dis.
Temp.
Suct.
Press.
71 149 137
73 151 143 164 141
75 154 148 166 146 176 145
77 156 153 169 151 181 150 194 149
79 160 155 171 156 184 155 196 153 209 152
81 175 159 186 159 198 158 211 157 224 156
83 190 162 202 162 213 161 226 160 239 160
85 205 166 217 165 228 164 241 164 254 163
87 208 169 220 169 232 168 243 168 256 167
89 224 173 235 173 247 172 258 171
91 239 177 250 176 262 175
93 254 180 265 180
95 269 184
97
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 5. Charging Table for JT5BD-024KA Series (2 Ton Units)
Liq.
Press.
OUTDOOR TEMPERATURE (° F)
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
15
Page 16
REFRIGERANT CHARGING TABLES - COOLING MODE
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode at ambient above 70°F.
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
70 143 136
72 145 141 158 139
74 147 147 160 144 173 142
76 150 152 162 149 175 147 188 145
78 153 155 165 154 177 152 190 149 202 147
80 168 157 180 156 192 154 204 152 217 150
82 183 159 195 158 207 156 219 154 232 152
84 198 161 210 160 221 158 234 156 247 154
86 202 165 213 164 225 162 236 160 249 158
88 217 168 228 166 240 164 251 162
90 232 170 243 169 255 167
92 247 173 258 171
94 261 176
96
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 6. Charging Table for JT5BD-030KA Series (2.5 Ton Units)
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
71 148 144
73 150 149 164 147
75 152 155 166 152 179 149
77 155 158 168 157 181 154 195 152
79 159 161 171 161 183 159 197 156 210 154
81 174 164 187 163 199 161 212 158 226 156
83 190 166 202 165 214 163 228 161 241 159
85 206 168 218 167 230 165 243 163 257 161
87 209 172 221 171 233 169 245 167 259 165
89 225 174 237 173 249 171 261 169
91 240 177 252 175 264 173
93 256 180 268 178
95 271 182
97
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Table 7. Charging Table for JT5BD-036K Series (3 Ton Units)
Dis.
Temp.
16
Page 17
REFRIGERANT CHARGING TABLES - COOLING MODE
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode at ambient above 70°F.
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
71 144 150
73 146 155 159 152
75 148 161 161 157 175 153
77 152 163 164 162 177 158 191 154
79 155 165 167 164 179 163 193 159 206 156
81 171 167 183 166 195 164 208 160 222 157
83 186 169 198 167 210 165 224 162 237 159
85 202 171 214 169 226 166 239 163 253 160
87 205 174 217 172 229 170 241 167 255 164
89 221 176 233 174 245 171 257 168
91 236 178 248 175 260 172
93 252 180 264 177
95 267 181
97
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 8. Charging Table for JT5BD-042K Series (3.5 Ton Units)
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
69 132 130
71 134 136 149 135
73 136 141 151 140 166 140
75 137 149 153 145 168 145 183 145
77 140 152 154 152 170 150 185 149 200 149
79 158 155 172 155 188 154 203 153 218 153
81 176 158 190 158 205 158 220 157 235 157
83 193 162 207 162 222 162 237 161 252 161
85 197 166 211 166 225 166 239 165 254 165
87 214 170 229 170 243 170 256 169
89 232 174 246 174 260 174
91 250 178 264 178
93 267 183
95
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Table 9. Charging Table for JT5BD-048K Series (4 Ton Units)
Dis.
Temp.
17
Page 18
REFRIGERANT CHARGING TABLES - COOLING MODE
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
3. In Cooling Mode suction pressure will be lower than design value if indoor air fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
4. In Heating Mode, charge should be weighed in. It is strongly recommended to verify charge in Cooling Mode at ambient above 70°F.
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
66 143 146
68 145 152 159 149
70 147 157 161 154 175 152
72 148 164 163 159 178 157 192 155
74 152 167 165 165 180 162 194 159 208 157
76 169 168 182 167 196 164 210 161 224 159
78 185 170 198 168 212 166 226 164 240 161
80 202 172 215 170 228 168 242 165 256 163
82 205 175 218 174 232 172 244 169 258 167
84 222 178 235 176 248 174 260 171
86 238 180 252 178 265 176
88 255 182 268 180
90 271 185
92
70 75 80 85 90 95 100 105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 10. Charging Table for JT5BD-060K Series (5 Ton Units)
18
Page 19
Disch.
Temp.
Disch.
Temp.
(° F)
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
235 182
72
215 163
63
195 143
53
249 170
74
229 154
65
209 138
55
(° F)
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
214 183
68
198 168
58
183 152
48
228 171
70
212 159
60
197 146
50
REFRIGERANT CHARGING TABLES - HEATING MODE
Rated design values. Suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures vary.
Shaded boxes indicate fl ooded conditions.
Liquid
Press.
Suc.
Press.
OUTDOOR TEMPERATURE
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
0 102030405060
Liquid
Press.
180 130
43
162 123
34
144 116
25
125 109
187 126
45
171 119
36
155 112
27
139 105
Table 11. Charging Table for JT5BD-018K Series Heat Pump (1.5 Ton Units)
Liquid
Press.
Suc.
Press.
OUTDOOR TEMPERATURE
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
0 102030405060
Liquid
Press.
173 138
39
160 127
31
147 115
23
134 103
180 134
41
169 123
33
Table 12. Charging Table for JT5BD-024KA Series Heat Pump (2 Ton Units)
159 111
25
148 99
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than charted values indicate an undercharged system.
Suc.
Press
13 111 113 23 132 120 32 152 127 41 173 134 51 181 149 61 201 172 70 221 195
14 118 111 24 138 118 33 157 125 42 176 132 52 188 146 62 208 167 71 228 188
15
16 132 107 26 149 114 35 167 121 44 184 128 54 202 140 64 222 158 73 242 176
17
18 146 103 28 161 110 37 176 117 46 191 124 56 216 135 66 236 149 75 256 164
19 153 101 29 167 108 38 181 115 47 195 122 57 223 132 67 243 145 76 263 158
Suc.
Press
12 120 107 21 135 119 29 150 131 37 165 142 46 169 158 56 184 177 66 200 196
13 127 105 22 141 117 30 155 129 38 169 140 47 176 155 57 191 172 67 207 189
14
15 141 101 24 153 113 32 165 125 40 176 136 49 190 149 59 205 163 69 221 177
16
17 155 97 26 165 109 34 174 121 42 184 132 51 204 144 61 219 154 71 235 165
18 162 95 27 171 107 35 179 119 43 187 130 52 211 141 62 226 150 72 242 159
19
Page 20
Disch.
Temp.
Disch.
Temp.
(° F)
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
244 183
67
225 165
58
205 147
50
258 171
69
239 157
60
219 142
52
(° F)
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
232 187
70
215 166
61
197 145
51
246 174
72
229 157
63
211 139
53
REFRIGERANT CHARGING TABLES - HEATING MODE
Rated design values. Suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures vary.
Shaded boxes indicate fl ooded conditions.
Liquid
Press.
Suc.
Press.
OUTDOOR TEMPERATURE
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
0 102030405060
Liquid
Press.
189 134
41
169 125
32
149 115
24
129 106
196 130
43
179 121
34
161 111
26
143 102
Table 13. Charging Table for JT5BD-030KA Series Heat Pump (2.5 Ton Units)
Liquid
Press.
Suc.
Press.
OUTDOOR TEMPERATURE
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
0 102030405060
Liquid
Press.
183 132
42
166 126
33
148 121
24
130 116
191 128
44
175 122
35
Table 14. Charging Table for JT5BD-036K Series Heat Pump (3 Ton Units)
160 117
26
144 112
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than charted values indicate an undercharged system.
20
Suc.
Press
13 115 110 22 137 119 30 159 129 39 181 138 48 191 153 56 211 174 65 230 196
14 122 108 23 143 117 31 164 127 40 185 136 49 198 150 57 218 170 66 237 190
15
16 136 104 25 155 113 33 174 123 42 192 132 51 212 145 59 232 161 68 251 177
17
18 150 100 27 167 109 35 183 119 44 200 128 53 226 139 61 246 152 70 265 165
19 157 98 28 173 107 36 188 117 45 203 126 54 233 136 62 253 148 71 272 159
Suc.
Press
13 116 120 22 136 125 31 156 130 40 176 136 49 183 151 59 201 175 68 218 199
14 123 118 23 142 123 32 161 128 41 180 134 50 190 148 60 208 170 69 225 193
15
16 137 114 25 154 119 34 171 124 43 187 130 52 204 142 62 222 161 71 239 181
17
18 151 110 27 166 115 36 180 120 45 194 126 54 218 136 64 236 152 73 253 168
19 158 108 28 172 113 37 185 118 46 198 124 55 225 134 65 243 148 74 260 162
Page 21
(° F)
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
253 175
74
220 159
60
187 143
46
267 162
76
234 150
62
201 137
48
(° F)
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
227 193
68
208 169
59
189 144
49
241 180
70
222 160
61
203 139
51
REFRIGERANT CHARGING TABLES - HEATING MODE
OUTDOOR TEMPERATURE
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
169 132
37
161 126
33
152 120
29
177 128
39
170 122
35
163 116
31
Table 15. Charging Table for JT5BD-042K Series Heat Pump (3.5 Ton Units)
OUTDOOR TEMPERATURE
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
175 129
40
160 123
32
144 117
23
183 125
42
169 119
34
Table 16. Charging Table for JT5BD-048K Series Heat Pump (4 Ton Units)
156 113
25
0 102030405060
Rated design values. Suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures vary.
Shaded boxes indicate fl ooded conditions.
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than charted values indicate an undercharged system.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
23 129 118 27 140 124 31 151 130 35 162 136 44 173 149 58 206 168 72 239 187
136 116 28 146 122 32 156 128 36 166 134 45 180 146 59 213 163 73 246 18125143 114
24
26 150 112 30 158 118 34 165 124 38 173 130 47 194 140 61 227 154 75 260 168
157 110
27
28 164 108 32 169 114 36 175 120 40 180 126 49 208 134 63 241 145 77 274 156
29 171 106 33 175 112 37 180 118 41 184 124 50 215 132 64 248 141 78 281 150
Temp.
Disch.
0 102030405060
Liquid
Press.
Suc.
Press
13 114 115 21 132 121 30 150 127 38 168 133 47 175 150 57 194 178 66 213 205
14 121 113 22 138 119 31 155 125 39 172 131 48 182 147 58 201 173 67 220 199
128 111
15
16 135 109 24 150 115 33 165 121 41 179 127 50 196 142 60 215 164 69 234 187
142 107
17
18 149 105 26 162 111 35 174 117 43 186 123 52 210 136 62 229 155 71 248 174
19 156 103 27 168 109 36 179 115 44 190 121 53 217 133 63 236 151 72 255 168
21
Page 22
(° F)
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
276 200
67
250 180
57
223 160
47
290 187
69
264 171
59
237 155
49
REFRIGERANT CHARGING TABLES - HEATING MODE
OUTDOOR TEMPERATURE
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
Temp.
Disch.
Liquid
Press.
Suc.
Press.
202 149
38
177 145
30
153 141
22
209 145
40
187 141
32
Table 17. Charging Table for JT5BD-060K Series Heat Pump (5 Ton Units)
165 137
24
0 102030405060
Rated design values. Suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures vary.
Shaded boxes indicate fl ooded conditions.
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than charted values indicate an undercharged system.
22
Temp.
Disch.
Liquid
Press.
Suc.
Press
12 114 141 20 141 145 28 168 149 36 195 153 45 209 166 55 236 189 65 262 212
13 121 139 21 147 143 29 173 147 37 198 151 46 216 163 56 243 184 66 269 206
128 137
14
15 135 135 23 159 139 31 182 143 39 206 147 48 230 158 58 257 175 68 283 193
142 133
16
17 149 131 25 171 135 33 192 139 41 213 143 50 244 152 60 271 166 70 297 181
18 156 129 26 176 133 34 196 137 42 217 141 51 251 149 61 278 162 71 304 175
Page 23
Single Phase
LPS
DEFROST CONTROL BOARD
(IF EQUIPPED)
ELECTRICAL INFORMATION
BLACK
BLACK
Y
C
O
O
T1
T2
W2
BLACK
R
DFT
ODT (IF
EQUIPPED)
DF1 DF2
E
RED
BLACK
CCH
BLUE
BLACK
(IF EQUIPPED)
(IF
LLS
EQUIPPED)
04/08
7108050
CC
L2L1
T1 T2
SINGLE PHASE
BLACK
CONTACTOR
YELLOW
LUG
GROUNDING
¢710805ª¤
FIELD SUPPLY
VALVE
SELENOID
REVERSING
Red
2
1
Yellow
5
Start
Relay
to “H” on capacitor
Black
to T2 on
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de
150 volt a la terre.
OPTIONAL HARD START KIT
contactor
L2
T2
Contacts
Compressor
C
R
BLACK
Start
RED
Capacitor
DEFROST
THERMOSTAT
Yellow
to T1 on contactor
Compressor
S
S
YELLOW
C
PTCR
PTCR
YELLOW
YELLOW
BLACK
(If equipped)
DF1
DF2
Outdoor
Fan Motor
DFT
R
DFT
F
C
H
RED
YELLOW
T3
S
T1
R
C
COMPRESSOR
T2
BLUE
S
ORANGE
OUTDOOR FAN MOTOR
C
Legend
Factory Wiring:
Field Wiring
Low Voltage
High Voltage
R
CC - Contactor Coil
CCH - Crankcase Heater (If Equipped)
DFT - Defrost Thermostat
LLS - Liquid Line Solenoid (If Equipped)
RVS - Reversing Valve Solenoid
ODT - Outdoor Thermostat (If Equipped)
LPS - Low Pressure Switch (If Equipped)
2
Logic
Control
3
1
1
4
R
W2
O
Y
C
Defrost Control Board
T2
T1
RVS
CC
LLS (IF
EQUIPPED)
Closing during defrost. Rating: 1 Amp. Max.
Opens during defrost. Rating: 2 HP at 230 Vac Max.
2
1
Defrost Board Operation:
Closed when "Y" is on. Open when "Y" is off.
Provides "off" delay time of 5 min. when "Y" opens.
With DFT closed and "Y" closed, compressor run time is accumulated.
Opening of DFT during defrost or interval period resets the interval to 0.
3
4
WIRING DIAGRAM
Split System Heat Pump (Outdoor Section)
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 C.
5. For ampacities and overcurrent protection, see unit rating plate.
L1
6. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler
instructions for control circuit and optional relay/transformer kits.
7. DO NOT install a Hard Start Kit on a model with a PTCR installed.
CCH
H
F
C
Dual Capacitor
PTCR (If equipped)
T1
Figure 13. JT5BD Wiring Diagram
ODT
(IF EQUIPPED)
LPS
(IF EQUIPPED)
E
R
W2
O
Vol ta g e
Y
C
Low
Terminals
PTCR - Positive Temperature
Coefficient Resistor
23
Page 24
Model Number JT5BD- 018K 024KA 030KA 036K 042K 048K 060K
Volts-Cycles-Phase (1) 208/230-60-1
Electrical Data
Component Data
Refrigerant suction line: Length/O. Liquid Line: All Lengths - 3/8” O.D.
Total Amps 9.9 11.8 14.6 15.7 17.5 19.7 26.4
Delay Fuse Max. (2) 20 25 30 30 35 40 50
Min. Circuit Ampacity 12.1 14.5 18.0 19.4 21.6 24.3 32.6
Coil
Fan Motor
Fan Blade
Compressor Data
Area 15.17 15.17 22.88 25.42 22.88 25.42 25.42
Rows-FPI 1 - 18 1 - 18 1 - 20 1 - 20 2 - 16 2 - 16 2 - 16
Tube Dia 3/8” O.D.
Type PSC
Amps 0.91 0.91 1.00 1.00 1.00 1.4 1.4
HP 1/8 1/8 1/4 1/4 1/4 1/4 1/4
Dia-#
Blades
SCFM 2370 2370 3000 3000 3000 4000 4000
RLA 8.3 10.8 13.4 15.3 19.2 19.8 25.3
LRA 40.3 56 68 87 112 105 146
0-24 ft. 3/4” 3/4” 3/4” 3/4” 7/8” 7/8” 7/8”
25-39 ft. 3/4” 3/4” 3/4” 7/8” (3) 7/8” 7/8” 1-1/8” (4)
40-75 ft. 3/4” 3/4” 7/8” (3) 7/8” (3) 7/8” 1-1/8” (4) 1-1/8” (4)
24” - 3
R-22 Refrigerant charge (in ounces):
(Outdoor unit, Indoor Unit 15’ Line Set)
Approximate Weight (lbs.)
(1) Operating Voltage Range: 198v min. - 253v max. (2) HACR type circuit breakers may be used. (3) Requires 7/8" to 3/4" reducer from line to unit. (4) Requires 1 1/8" to 7/8" reducer from line to unit.
Net 166 171 190 204 252 276 285
Ship 175 180 200 215 265 290 300
Table 18. Electrical Specifi cations & Physical Data
93 96 144 155 248 248 268
Specifi cations & illustrations subject to change without notice or incurring obligations. O’ Fallon, MO | Printed in U.S.A. (09/10)
¢709242¤
7092420 (Replaces 708452D)
Loading...