Nordyne JT5BD, JT5BD-018K, JT5BD-024KA, JT5BD-030KA, JT5BD-036K Installation Manual

...
JT5BD Series
USER’S MANUAL / INSTALLATION INSTRUCTIONS
SPLIT SYSTEM HEAT PUMP - R-22
13 SEER
Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate the problem, call your servicing contractor.
The Installation Instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
USER INFORMATION
Important Safety Information ....................................3
About the Heat Pump .................................................3
Operating Instructions ...............................................3
Cooling Operation .....................................................3
Heating Operation .....................................................3
Emergency Heat........................................................3
Defrost Operation ......................................................3
Operating the Heat Pump for Automatic
Cooling & Heating .....................................................4
Operating the Indoor Blower Continuously ................4
Turning the Heat Pump Off ........................................4
Heat Pump Maintenance ............................................4
Regular Cleaning.......................................................4
Troubleshooting ..........................................................4
INSTALLER INFORMATION
Important Safety Information ....................................5
Heat Pump Installation ...............................................6
General Information ...................................................6
Before You Install this Unit .........................................6
Locating the Heat Pump ............................................6
Packaging Removal ...................................................6
Ground Level .............................................................6
Connecting Refrigerant Tubing between the
Indoor & Outdoor Unit ...............................................7
Electrical Wiring ..........................................................7
Pre - Electrical Checklist ...........................................7
Line Voltage ...............................................................7
Grounding..................................................................8
Thermostat Connections ...........................................8
Startup & Adjustments ..............................................9
Pre - Start Checklist ..................................................9
Start-up Procedures ..................................................9
Air Circulation - Indoor Blower ...............................9
System Cooling ......................................................9
System Heating ......................................................9
Refrigerant Charging ..................................................9
Charging R-22 Units in AC Mode with
Outdoor Temperatures Above 55° F ........................10
Heat Pump Maintenance ..........................................10
Replacement Parts ...................................................10
WARRANTY INFORMATION
A warranty certifi cate with full details is included with the Heat Pump. Carefully review these responsibilities with your dealer or service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc. Some specifi c examples of service calls which are not included in the limited warranty are:
• Correcting wiring problems in the electrical circuit supplying the Heat Pump.
• Resetting circuit breakers or other switches.
• Adjusting or calibrating of thermostat.
Figures & Tables .......................................................11
Figure 5. Unit Dimensions ...................................11
Refrigerant Charging Charts ...................................11
Figure 6. JT5BD-018K (1.5 Ton Units) ................11
Figure 7. JT5BD-024KA (2 Ton Units) .................12
Figure 8. JT5BD-030KA (2.5 Ton Units) ..............12
Figure 9. JT5BD-036K (3 Ton Units) ...................13
Figure 10. JT5BD-042K (3.5 Ton Units) ..............13
Figure 11. JT5BD-048K (4 Ton Units) .................14
Figure 12. JT5BD-060K (5 Ton Units) .................14
Refrigerant Charging Tables - Cooling Mode ..........15
Table 4. JT5BD-018K (1.5 Ton Units) ..................15
Table 5. JT5BD-024KA (2 Ton Units) ...................15
Table 6. JT5BD-030KA (2.5 Ton Units) ................16
Table 7. JT5BD-036K (3 Ton Units) .....................16
Table 8. JT5BD-042K (3.5 Ton Units) ..................17
Table 9. JT5BD-048K (4 Ton Units) .....................17
Table 10. JT5BD-060K (5 Ton Units) ...................18
Refrigerant Charging Tables - Heating Mode ..........19
Table 11. JT5BD-018K (1.5 Ton Units) ................19
Table 12. JT5BD-024KA (2 Ton Units) .................19
Table 13. JT5BD-030KA (2.5 Ton Units) ..............20
Table 14. JT5BD-036K (3 Ton Units) ...................20
Table 15. JT5BD-042K (3.5 Ton Units) ................21
Table 16. JT5BD-048K (4 Ton Units) ...................21
Table 17. JT5BD-060K (5 Ton Units) ...................22
Electrical Information ...............................................23
Figure 12. JT5BD Wiring Diagram .......................23
Table 18. Electrical Specs & Physical Data ..........24
2
USER INFORMATION
IMPORTANT SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
ABOUT THE HEAT PUMP
Your heat pump is a unique, all weather comfort-control appliance that will heat and cool your home year round and provide energy saving comfort. It’s an unknown fact that heat is always in the air, even when the outside temperature is below freezing. The heat pump uses this basic law of physics to provide energy saving heat during the winter months. For example, If the outdoor temperature is 47° F (8° C), your heat pump can deliver approximately
3.5 units of heat energy per each unit of electrical energy used, as compared to a maximum of only 1 unit of heat energy produced with conventional heating systems.
In colder temperatures, the heat pump performs like an air conditioner run in reverse. Available heat energy outside the home is absorbed by the refrigerant and exhausted inside the home. This effi cient process means you only pay for “moving” the heat from the outdoors to the indoor area. You do not pay to generate the heat, as is the case with more traditional furnace designs.
During summer, the heat pump reverses the fl ow of the heat-absorbing refrigerant to become an energy-effi cient, central air conditioner. Excess heat energy inside the home is absorbed by the refrigerant and exhausted outside the home.
OPERATING INSTRUCTIONS
Please refer to the thermostat manufacturer’s User manual for detailed programming instructions.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately 5 minutes following a previous operation or the interruption of the main electrical power.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately 5 minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat
Some thermostats may include a system mode called EM HT or AUX HT, etc. This is a back-up heating mode that should only be used if a problem is suspected. With the mode set to EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
Defrost Operation
During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will defrost itself. This unit monitors ambient and coil temperatures to regulate the defrost function accordingly.
3
USER INFORMATION
At the beginning of the defrost cycle, both the outdoor condenser fan and compressor will turn off. After approximately 30 seconds, the compressor will turn on and begin to heat the outdoor coil causing the ice and snow to melt.
NOTE: While the ice and snow is melting, some steam may rise from the outdoor unit as the warm coil causes the melting frost to evaporate. When defrost is completed, the outdoor fan motor will start, and the compressor will turn off again. In approximately 30 seconds the compressor will start up again and continue normal operation.
Operating the Heat Pump for Automatic Cooling and Heating
1. Set the thermostat system switch to AUTO and the thermostat fan switch to AUTO. See Figure 1.
NOTE: Thermostat styles vary. Some models will not include the AUTO mode and others will have the AUTO in place of the HEAT and COOL. Others may include all three. Refer to the instructions supplied with your thermostat for specifi c instructions.
2. Set the thermostat temperature to the desired temperature level. The outdoor unit and the indoor blower will then cycle on and off in either the heating or cooling mode of operation as required to automatically maintain the indoor temperature within the desired limits.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
Set the thermostat fan mode to ON (Figure 1). The indoor blower starts immediately, and will run continually until the fan mode is reset to AUTO.
The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, including OFF.
HEAT PUMP MAINTENANCE
CAUTION:
Shut off all electrical power to the unit before performing any maintenance. Failure to comply may result in personal injury or death.
Proper maintenance is most important to achieve the best performance from the appliance and should be performed by a qualifi ed service technician at least once a year. Read the maintenance items below and follow the instructions for years of safe, trouble free operation.
Regular Cleaning
WARNING:
Do not place combustible material on or against the unit cabinet. Do not place combustible materials, including gasoline and any other fl ammable vapors and liquids, in the vicinity of the unit.
• Clean or replace the indoor air fi lter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air fi lter.
• Remove any leaves and grass clippings from around the coil of the outdoor unit, being careful not to damage the aluminum fi ns.
• Check and remove any obstructions, such as twigs, sticks, etc.
TROUBLESHOOTING
If the unit fails to operate, check the following:
• The thermostat is properly set. See Cooling Operation for air conditioning or Heating Operation for furnace.
• The unit disconnect fuses are in good condition and the electrical power to the unit is turned on.
Turning the Heat Pump Off
Change the thermostat’s system mode to OFF and the fan mode to AUTO. See Figure 1. NOTE: The system will not operate, regardless of the temperature selector setting.
4
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
WARNING:
Unless noted otherwise in these instructions, only factory authorized parts or accessory kits may be used with this product. Improper installation, service, adjustment, or maintenance may cause explosion, fi re, electrical shock or other hazardous conditions which may result in personal injury or property damage
WARNING:
JT5BD Split System Heat Pumps leave the factory with a nitrogen holding charge. Follow all charg­ing instructions for maximum unit performance and effi ciency. Some local codes require licensed installation/service personnel to service this type of equipment. Refrigerant charging must be done by qualifi ed personnel familiar with safe and en­vironmentally responsible refrigerant handling procedures. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury, or death.
CAUTION:
This unit uses refrigerant R-22. DO NOT use any other refrigerant in this unit. Use of another refrigerant will damage the unit.
WARNING:
The information listed below must be followed during the installation, service, and operation of this unit. Unqualifi ed individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious per
injury or death
• The installer must comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
• All electrical wiring must be completed in accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C.22.1.
• This equipment contains liquid and gaseous refrigerant under high pressure. DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment.
• Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
• Installation of equipment may require brazing operations. Installer must comply with safety codes and wear appropriate safety equipment (safety glasses, work gloves, fi re extinguisher, etc.) when performing brazing operations.
• This unit is designed for outdoor installations only and should be located as descibed on page 6.
• Follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
.
sonal
5
HEAT PUMP INSTALLATION
General Information
The JT5BD series Heat Pump is designed only for outdoor rooftop or ground level installations. This unit has been tested for capacity and effi ciency in accordance with A.H.R.I. Standards and will provide many years of safe and dependable comfort, providing it is properly installed and maintained. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.
Before You Install this Unit
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired and provided with circuit protection in accordance with local building codes. If there is any question concerning the power supply, contact the local power company.
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to the indoor unit's installation instructions for installation details.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Verify coil fi ns are straight. If necessary, comb fi ns to remove fl attened or bent fi ns. Claims for damage (apparent or concealed) should be fi led immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read all instructions before installing the unit.
Locating the Heat Pump
• Survey the job site to determine the best location for mounting the outdoor unit. See Figure 5 (page 11) for unit dimensions.
• Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided.
• Suffi cient clearance for unobstructed airfl ow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 2 for minimum clearances to obstructions.
• Consideration should be given to availability of electric power, service access, noise, and shade.
Packaging Removal NOTE: To prevent damage to the tubing connections,
carefully remove the carton and user’s manual from the equipment. Discard the shipping carton.
Ground Level
Ground level installations must be located according to local building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown in Figure 2.
• A suitable mounting pad (Figure 3) must be provided and separate from the building foundation. The pad must be level and strong enough to support the weight of the unit. The slab height must be a minimum of 2” (5 cm) above grade and with adequate drainage.
DO NOT
18"
18"
18"
OBSTRUCT
TOP OF UNIT
Figure 2. Clearance Requirements
6
2”
Figure 3. Ground Level Installation
18"
Connecting Refrigerant Tubing Between the Indoor & Outdoor Unit
CAUTION:
This system uses R-22 refrigerant with POE oil. When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.
After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices.
• To maintain the unit's warranty, it is required that a fi lter drier be installed when the system is open to the atmosphere. This includes, but is not limited to, replacing the evaporator and/or condenser of a system. The fi lter drier must be installed in strict accordance with the manufacturer’s installation instructions.
• Optional equipment such as liquid line solenoid valves, low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.
ELECTRICAL WIRING
• When connecting refrigerant linesets together, it is recommended that dry nitrogen be fl owing through the joints during brazing to prevent internal oxidation and scaling.
• Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.
• Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.
• Tubing should be kept clean of foreign debris during installation.
• Every effort should be made by the installer to ensure that the fi eld installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.
• The maximum recommended interconnecting refrigerant line lengths is 75 ft. and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 ft.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire Length-Feet
200 150 100 50
6 8 10 14 15 46812 20 46810 25 44610 30 3468 35 3468 40 2346 45 2346 50 2346 55 1234 60
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
Supply Circuit
Ampacity
WARNING:
To avoid risk of electrical shock, personal injury, or death, disconnect all electrical power to the unit before performing any maintenance or service. The unit may have more than one electrical supply.
Label all wires prior to disconnection when servicing the unit. Wiring errors can cause improper and dangerous operation.
• All electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
Verify that the voltage, frequency, and phase of the
supply source match the specifi cations on the unit rating plate. See Table 18 (page 24).
Verify that the service provided by the utility is suffi cient
to handle the additional load imposed by this equipment. Refer to the unit wiring label for proper voltage wiring.
Verify factory wiring is in accordance with the unit
wiring diagram or Figure 13 (page 23). Inspect for loose connections.
Line Voltage
• A wiring diagram is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram before making any electrical connections to the outdoor unit.
An electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.
• Line voltage to the unit should be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit. Incoming fi eld wiring and minimum size of electrical conductors and circuit
7
Thermostat
GRW2CEOY
NOTE: Jumper between W2 and E is required when no OD T-Stat is used.
For 2-Stage Heater Kits
Green
Red
Brown
Orange
Black
G
R
W
W
2
C
Air Handler Heat Pump OD
Section
Typical Heat Pump with Standard Air Handler
Thermostat
GRW2CEOY
Red
G
R
W
C
C
Green
White
Black
C
W
O Y
OY
E
R
2
protection must be in compliance with information listed on the outdoor unit data label. Any other wiring methods must be acceptable to authority having jurisdiction.
• The outdoor unit requires both power and control circuit electrical connections. Refer to the wiring diagram / schematic for identifi cation and location of outdoor unit fi eld wiring interfaces Figure 13 (page 23). Make all electrical connections in accordance with all applicable
R
W
2
codes and ordinances.
• Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes. See the unit rating plate for minimum circuit ampacity and maximum overcurrent protection limits.
• Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate. Connect the line-voltage leads to the terminals on the contactor inside the control compartment.
• Use only copper wire for the line voltage power supply to this unit as listed in Table 1. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
• 208/230 Volt units are shipped from the factory wired for 230 volt operation. For 208V operation, remove the lead from the transformer terminal marked 240V and connect it to the terminal marked 208V.
• Optional equipment requiring connection to the power or control circuits must be wired in strict accordance of the NEC (ANSI/NFPA 70), applicable local codes, and the instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not use gas piping as an electrical ground
!
Air Handler Heat Pump OD
Typical Heat Pump with
Outdoor Thermostat and Air Handler
Figure 4. Typical Thermostat Connections
8
Section
This unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical Code. Use the grounding lug provided in the control box for grounding the unit.
Thermostat Connections
• Thermostat connections should be made in accordance with the instructions supplied with the thermostat and the indoor equipment.
• The outdoor unit is designed to operate from a 24 VAC Class II control circuit. The control circuit wiring must comply with the current provisions of the NEC (ANSI/ NFPA 70) and with applicable local codes having jurisdiction.
• The low voltage wires must be properly connected to the units low voltage terminal block (Figure 4).
Loading...
+ 16 hidden pages