Please read this information thoroughly and become familiar with the capabilities and
use of your appliance before attempting to operate or maintain this unit. Keep this
literature where you have easy access to it in the future. If a problem occurs, check the
instructions and follow recommendations given. If these suggestions don’t eliminate
the problem, call your servicing contractor.
The Installation Instructions are primarily intended to assist qualifi ed individuals
experienced in the proper installation of this appliance. Some local codes require licensed
installation/service personnel for this type of equipment. Please read all instructions
carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
Page 2
USER INFORMATION
Important Safety Information ....................................3
Outdoor Temperatures Above 55° F .......................9
WARRANTY INFORMATION
A warranty certifi cate with full details is included with the
air conditioner. Carefully review these responsibilities with
your dealer or service company. The manufacturer will not
be responsible for any costs found necessary to correct
problems due to improper setup, improper installation,
adjustments, improper operating procedure on the part
of the user, etc. Some specifi c examples of service calls
which are not included in the limited warranty are:
• Correcting wiring problems in the electrical circuit
supplying the air conditioner.
Air Conditioner Maintenance .....................................9
Replacement Parts .....................................................9
2
Page 3
USER INFORMATION
IMPORTANT SAFETY INFORMATION
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.
OPERATING INSTRUCTIONS
NOTE: Thermostat styles vary. Some models may not
include the AUTO mode and others will have the AUTO
in place of the HEAT and COOL. Others may include all
three. Please refer to the thermostat manufacturer’s User
manual for detailed programming instructions.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO
and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired
temperature level. The outdoor fan, compressor, and
blower motor will all cycle on and off to maintain the
indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the
system mode is reset, the fan and compressor in the
outdoor unit may not start immediately. A protective
timer circuit holds the compressor and the outdoor fan
off for approximately 5 minutes following a previous
operation or the interruption of the main electrical
power (if applicable).
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO
and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired
temperature level. The optional heating equipment
(furnace or electric heat) will cycle on & off to maintain
the indoor temperature at the desired temperature
level.
Operating the AC for Automatic Cooling & Heating
1. Set the thermostat system mode to AUTO and the
thermostat fan mode to AUTO. See Figure 1.
2. Set the thermostat temperature selector to the desired
temperature level. The thermostat will maintain the
desired temperature level by switching between either
the outdoor cooling unit or the indoor heating unit
(furnace or electric heat) automatically.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to
circulate the indoor air to equalize a temperature unbalance
due to a sun load, cooking, or fi replace operation.Set the
thermostat fan mode to ON (Figure 1). The indoor blower
starts immediately, and will run continually until the fan
mode is reset to AUTO.
The continuous indoor blower operation can be obtained
with the thermostat system mode set in any position,
including OFF.
Turning the Air Conditioner OFF
Change the thermostat’s system mode to OFF and the fan
mode to AUTO (See Figure 1). NOTE: The system will not
operate, regardless of the temperature selector setting.
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
AIR CONDITIONER MAINTENANCE
Proper maintenance is most important to achieve the best
performance from the appliance and should be performed
frequently at the beginning of each air conditioning season.
WARNING:
Your air conditioner contains liquid and gaseous
refrigerant under pressure. Installation and
servicing should only be attempted by qualifi ed,
trained personnel thoroughly familiar with the
equipment and safe responsible refrigerant
handling procedures. Failure to comply with
this warning could result in equipment damage,
personal injury, or death.
• Keep the outdoor unit clean. Hose off periodically and
keep unit fi ns clear of leaves and grass clippings.
• Keep the outdoor unit clear of obstructions.
DO NOT obstruct airfl ow with tall plants or shrubs.
DO NOT store gasoline or other fl ammable materials
on or near the outdoor unit.
• Never operate the appliance without a fi lter installed in
the return air duct. Inspect fi lters frequently and replace
when necessary with fi lter of same dimensional size.
TROUBLESHOOTING
• Check the thermostat setting. Make sure the system
mode and temperature settings are correct.
• Check the electrical panel for tripped circuit breakers.
• Check the fi lters for dust accumulation.
• Check the outdoor unit and make sure it is clean and
not covered with grass or leaves.
3
Page 4
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially hazardous
situation that if not avoided, could result in personal injury
or death. CAUTION indicates a potentially hazardous
situation that if not avoided, may result in minor or moderate
injury or property damage.
WARNING:
Shut off all electrical power to the unit before
performing any maintenance or service on the
system. Failure to comply may result in personal
injury or death.
WARNING:
Unless noted otherwise in these instructions,
only factory authorized parts or accessory
kits may be used with this product. Improper
installation, service, adjustment, or maintenance
may cause explosion, fi re, electrical shock or
other hazardous conditions which may result in
personal injury or property damage
WARNING:
JS5BD Split System Air conditioners leave
the factory with a nitrogen holding charge.
Follow all charging instructions for maximum
unit performance and effi ciency. Some local
codes require licensed installation/service
personnel to service this type of equipment.
Refrigerant charging must be done by qualifi ed
personnel familiar with safe and environmentally
responsible refrigerant handling procedures.
Under no circumstances should the owner
attempt to install and/or service this equipment.
Failure to comply with this warning could result
in property damage, personal injury, or death.
CAUTION:
This unit uses refrigerant R-22. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant will damage the unit.
WARNING:
The information listed below must be followed
during the installation, service, and operation
of this unit. Unqualifi ed individuals should
not attempt to interpret these instructions or
install this equipment. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious per
injury or death
• The installer must comply with all local codes and
regulations which govern the installation of this type
of equipment. Local codes and regulations take
precedence over any recommendations contained in
these instructions. Consult local building codes and
the National Electrical Code (ANSI CI) for special
installation requirements.
• All electrical wiring must be completed in accordance
with local, state and national codes and regulations
and with the National Electric Code (ANSI/NFPA 70)
or in Canada the Canadian Electric Code Part 1 CSA
C.22.1.
• This equipment contains liquid and gaseous refrigerant
under high pressure. DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK TESTING.
Installation or servicing should only be performed by
qualifi ed trained personnel thoroughly familiar with this
type equipment.
• Fully annealed, refrigerant grade copper tubing should
be used when installing the system. Refrigerant suction
line tubing should be fully insulated.
• Installation of equipment may require brazing
operations. Installer must comply with safety codes
and wear appropriate safety equipment (safety glasses,
work gloves, fi re extinguisher, etc.) when performing
brazing operations.
• Follow all precautions in the literature, on tags, and
on labels provided with the equipment. Read and
thoroughly understand the instructions provided with
the equipment prior to performing the installation and
operational checkout of the equipment.
.
sonal
4
Page 5
AIR CONDITIONER INSTALLATION
General Information
The JS5BD series air conditioner is designed only for
outdoor rooftop or ground level installations. This unit has
been tested for capacity and effi ciency in accordance with
A.H.R.I. Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and
create unsafe hazards.
To achieve optimum performance and minimize equipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain
mechanical skills and tools.
Before You Install this Unit
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to
the indoor unit's installation instructions for installation
details.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage
prior to installing the equipment at the job site. Verify
coil fi ns are straight. If necessary, comb fi ns to remove
fl attened or bent fi ns. Claims for damage (apparent or
concealed) should be fi led immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read
all instructions before installing the unit.
Locating the Air Conditioner
• Survey the job site to determine the best location for
mounting the outdoor unit. See Figure 5 (page 12) for
unit dimensions.
• Overhead obstructions, poorly ventilated areas, and
areas subject to accumulation of debris should be
avoided.
• Suffi cient clearance for unobstructed airfl ow through the
outdoor coil must be maintained in order to achieve rated
performance. See Figure 2 for minimum clearances to
obstructions.
• Consideration should be given to availability of electric
power, service access, noise, and shade.
Packaging Removal
NOTE: To prevent damage to the tubing connections,
carefully remove the carton and user’s manual from the
equipment. Discard the shipping carton.
Ground Level
Ground level installations must be located according to
local building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown
in Figure 2.
• A suitable mounting pad (Figure 3) must be provided
and separate from the building foundation. The pad
must be level and strong enough to support the weight
of the unit. The slab height must be a minimum of 2”
(5 cm) above grade and with adequate drainage.
DO NOT
18"
18"
18"
OBSTRUCT
TOP OF UNIT
Figure 2. Clearance Requirements
2”
Figure 3. Ground Level Installation
18"
5
Page 6
Connecting Refrigerant Tubing Between the Indoor
& Outdoor Unit
CAUTION:
This system uses R-22 refrigerant with POE
oil. When servicing, cover or seal openings to
minimize the exposure of the refrigerant system
to air to prevent accumulation of moisture and
other contaminants.
After outdoor and indoor unit placement has been
determined, route refrigerant tubing between the
equipment in accordance with sound installation practices.
• When connecting refrigerant linesets together, it is
recommended that dry nitrogen be fl owing through
the joints during brazing to prevent internal oxidation
and scaling.
• Refrigerant tubing should be routed in a manner that
minimizes the length of tubing and the number of bends
in the tubing. If precise forming of refrigerant lines is
required, a copper tubing bender is recommended.
Avoid sharp bends and contact of the refrigerant lines
with metal surfaces.
• Refrigerant tubing should be supported in a manner
that the tubing will not vibrate or abrade during system
operation.
• Tubing should be kept clean of foreign debris during
installation.
• Every effort should be made by the installer to ensure
that the fi eld installed refrigerant containing components
of the system have been installed in accordance with
these instructions and sound installation practices to
insure reliable system operation and longevity.
• The maximum recommended interconnecting
refrigerant line lengths is 75 ft. and the vertical elevation
difference between the indoor and outdoor sections
should not exceed 20 ft.
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
Supply Circuit
Ampacity
• Installing a fi lter dryer is optional. However it is good
practice to install a fi lter dryer when replacing the
evaporator and/or condensor of a system. The fi lter
dryer must be installed in strict accordance with the
manufacturer’s installation instructions.
• Optional equipment such as liquid line solenoid
valves, low ambient, etc., should be installed in
strict accordance with the manufacturer’s installation
instructions.
ELECTRICAL WIRING
WARNING:
To avoid risk of electrical shock, personal injury,
or death, disconnect all electrical power to the unit
before performing any maintenance or service.
The unit may have more than one electrical
supply.
Label all wires prior to disconnection when
servicing the unit. Wiring errors can cause
improper and dangerous operation.
• All electrical connections must be in compliance with
all applicable local codes and ordinances, and with
the current revision of the National Electric Code
(ANSI/NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist
Verify that the voltage, frequency, and phase of the
supply source match the specifi cations on the unit
rating plate. See Table 4 (page 12).
Verify that the service provided by the utility is suffi cient
to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper voltage wiring.
Verify factory wiring is in accordance with the unit
wiring diagram (Figure 4, page 10). Inspect for loose
connections.
Line Voltage
• A wiring diagram is located on the inside cover of the
electrical box of the outdoor unit. The installer should
become familiar with the wiring diagram before making
any electrical connections to the outdoor unit.
• An electrical disconnect must be located within sight of and readily accessible to the unit. This
switch shall be capable of electrically de-energizing
the outdoor unit.
• Line voltage to the unit should be supplied from a
dedicated branch circuit containing the correct fuse
or circuit breaker for the unit. Incoming fi eld wiring
and minimum size of electrical conductors and circuit
protection must be in compliance with information listed
on the outdoor unit data label. Any other wiring methods
must be acceptable to authority having jurisdiction.
6
Page 7
• The outdoor unit requires both power and control circuit
electrical connections. Refer to the wiring diagram /
schematic for identifi cation and location of outdoor
unit fi eld wiring interfaces (Figure 4, page 10). Make all
electrical connections in accordance with all applicable
codes and ordinances.
• Overcurrent protection must be provided at the branch
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes.
See the unit rating plate for minimum circuit ampacity
and maximum overcurrent protection limits.
• Provide power supply for the unit in accordance with the
unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the terminals on the contactor
inside the control compartment.
• Use only copper wire for the line voltage power supply
to this unit as listed in Table 1. Use proper code agency
listed conduit and a conduit connector for connecting
the supply wires to the unit. Use of rain tight conduit
is recommended.
• 208/230 Volt units are shipped from the factory wired
for 230 volt operation. For 208V operation, remove the
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
• Optional equipment requiring connection to the power
or control circuits must be wired in strict accordance
of the NEC (ANSI/NFPA 70), applicable local codes,
and the instructions provided with the equipment.
Grounding
• The thermostat should be mounted about 5 feet
above the fl oor on an inside wall. DO NOT install the
thermostat on an outside wall or any other location
where its operation may be adversely affected by radiant
heat from fi replaces, sunlight, or lighting fi xtures, and
convective heat from warm air registers or electrical
appliances. Refer to the thermostat manufacturer’s
instruction sheet for detailed mounting and installation
information.
Positive Temperature Coeffi cient Resistor (PTCR)
(Select models only)
The PTCR is factory installed and located on the control
panel of the outdoor unit.This soft start device is for use
with reciprocating compressors. If a hard start kit is needed
on this unit, the soft start (PTCR) must be removed fi rst.
Recommended T-Stat Wire
Thermostat
Wire Gauge
Unit to T-Stat (Length in FT)
2-Wire
(Heating)
5-Wire
(Heating/Cooling)
245525
229045
2014070
18225110
Table 2. Thermostat Wire Gauge
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the control box for grounding the unit.
Thermostat Connections
• Ther mostat connections should be made in accordance
with the instructions supplied with the thermostat and
the indoor equipment.
• The outdoor unit is designed to operate from a 24 VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having
jurisdiction.
• The low voltage wires must be properly connected to
the units low voltage terminal block. Recommended
wire gauge and wire lengths for typical thermostat
connections are listed in Table 2.
!
JS5BD-24K
Volts-Cycles-Phase208/230-60-1
Electrical
Data
Component
Data
Refrigerant Suction Line:
Length/O.D.
Liquid Line: All Lengths - 3/8”O.D.
R-22 Refrigerant Charge (in Ounces):
(Outdoor unit, Indoor Unit - 15’ Line Set)
Approximate Weight (lbs.)
Table 3. Electrical Specifi cations & Physical Data
Total Amps11.5
Delay Fuse Max.20
Min. Circuit Ampacity14.1
Area8.3
Coil
Fan Motor
Fan Blade
Compressor
Data
Rows-FPI1-22
Tube Dia.MC
TypePSC
Amps0.7
Watts-HP0.1
Dia.18”
# Blades3
SCFM2800
RLA10.8
LRA40.3
15 - 24 ft.3/4”
25 - 39 ft.3/4”
40 - 75 ft.3/4”
53
Net113
Ship118
7
Page 8
START UP & ADJUSTMENTS
Pre-Start Check List
Verify the indoor unit is level and allows proper
condensate drainage.
Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/
control panels are in place.
Verify air fi lters are cleaned and properly installed.
Verify duct work is sealed to prevent air leakage.
Verify line voltage power leads are securely connected
and the unit is properly grounded.
Verify low voltage wires are securely connected to the
correct leads on the low voltage terminal strip.
Verify power supply branch circuit overcurrent protection
is sized properly.
Verify the thermostat is wired correctly.
Start-Up Procedures
The thermostat's function mode should be set to OFF and
the fan mode should be set to AUTO. Close all electrical
disconnects to energize the system.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan
mode to ON.
2. Verify the blower runs continuously. Check the air
delivery at the supply registers and adjust register
openings for balanced air distribution. If insuffi cient
air is detected, examine ductwork for leaks or
obstructions.
3. Set the thermostat fan mode to AUTO and verify the
blower stops running.
System Cooling
1. Set the thermostat’s system mode to COOL and the
fan mode to AUTO. Gradually lower the thermostat
temperature setpoint below room temperature and
verify the outdoor unit and indoor blower energize.
2. Verify blower wheel is spinning in direction indicated
by arrow. Feel the air being circulated by the indoor
blower and verify that it is cooler than ambient
temperature. Listen for any unusual noises. If unusual
sounds occur, determine the source of the noise and
correct as necessary.
3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes
and then set the temperature selector above room
temperature. Verify the fan and compressor cycle off
with the thermostat. NOTE: The blower should also
stop unless fan mode is set to the ON position.
System Heating (optional)
1. Set the thermostat's system mode to HEAT and the
temperature mode above room temperature.
2. Verify the optional heating equipment (furnace or
electric heat) and indoor blower energize. Feel the air
being circulated by the indoor blower and verify that
it is warmer than ambient temperature. Listen for any
unusual noises. If unusual sounds occur, determine
the source of the noise and correct as necessary.
Refrigerant Charging
WARNING:
JS5BD Split System Air Conditioners leave the
factory with a nitrogen holding charge.
operate any unit while it contains a Nitrogen
holding charge. Doing so may damage the
units compressor. Follow these charging
instructions for maximum unit performance and
effi ciency. Some local codes require licensed
installation/service personnel to service this
type of equipment. Refrigerant charging must be
done by qualifi ed personnel familiar with safe and
environmentally responsible refrigerant handling
procedures. Under no circumstances should
the owner attempt to install and/or service this
equipment. Failure to comply with this warning
could result in property damage, personal injury,
or death.
To properly charge these units:
1. Read all Installation Instructions fi rst.
2. Complete any brazing operations. (e.g. Split system
line-sets)
3. Leak check and evacuate the whole system using
proper methods.
4. Purge the nitrogen holding charge.
5. Evacuate the unit to 350-500 microns.
6. Allow the unit to remain under vacuum for at least 30
min.
7. Weigh-In the proper amount of new (or reclaimed)
R-22 refrigerant. Refer to the units rating label or see
Table 4 to determine the correct amount of charge.
• Refrigerant charging charts are applicable only to
matched assemblies of NORDYNE equipment and
listed airfl ows for the indoor coil. Refer to Figures 5 11 or Tables 5-11 (pages 10 - 16) for correct system
charging.
• JS5BD outdoor units with indoor coils not listed are
not recommended. Deviations from rated airfl ows or
non-listed combinations may require modifi cation to the
Model
Number
1.5 ton0.05378
2.0 ton (-KB)0.06053
2.5 ton (-KB)0.06556
3.0 ton (-KB)0.07568
3.5 ton0.078122
4.0 ton0.089126
5.0 ton0.099160
Table 4. Refrigerant Metering Device
for 13 SEER Split System Air Conditioner
Restrictor Bore
Size (inches)
DO NOT
System charge
R-22 (oz.)
8
Page 9
expansion device and refrigerant charging procedures
D
W
H
DO NOT OBSTRUCT TOP OF UNIT
Allow adequate clearance for airflow
for proper and effi cient system operation.
• The refrigerant charge can be checked and adjusted
through the service ports provided external to the
outdoor unit. Use only gage line sets which have a
“Schrader” depression device present to actuate the
valve.
Charging an R-22 system in AC mode at outdoor temperatures above 55° F for optimized sub-cooling of 10°
F - 12° F.
1. With the system operating at steady-state, measure
the liquid refrigerant pressure (in psig) at the outdoor
unit service valve.
2. Measure the liquid refrigerant temperature (in
Fahrenheit) at the service valve.
3. Determine the required liquid refrigerant pressure
from Table 4.
• If the pressure measured in Step 1 is greater than
the required liquid refrigerant pressure determined in
Step 3, then there is too much charge in the system.
Remove refrigerant and repeat Steps 1 through 3
until the system is correctly charged.
• If the pressure measured in Step 1 is less than the
required liquid refrigerant pressure determined in
Step 3, there is too little charge in the system. Add
refrigerant and repeat Steps 1 through 3 until the
system is correctly charged.
CAUTION:
The unit should never be operated without a
fi lter in the return air system. Replace disposable
fi lters with the same type and size.
• Do not attempt to add additional oil to motors
unequipped with oil tubes. The compressor is
hermetically sealed at the factory and does not require
lubrication.
REPLACEMENT PARTS
Replacement parts are available through all Nordyne
Please have the complete model and serial number of the unit
when ordering replacement parts.
ELECTRICAL:
CapacitorsTemperature Limit Switches
CompressorsThermostats
ContactorsTime Delay Relays
Pressure SwitchesTransformers
Relays
MOTORS:
Blower MotorFan Motor
COMPONENTS:
Blower AssemblyFan Grille
Cabinet PanelsFilter/Driers
Expansion Valves
distributors.
AIR CONDITIONER MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or
death, disconnect all electrical power to the unit
before performing any maintenance or service.
The unit may have more than one electrical
supply.
Proper maintenance is important to achieve optimum
performance from the air conditioner. The ability to properly
perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these
skills, contact your dealer for maintenance. Consult your
local dealer about the availability of maintenance contracts.
Routine maintenance should include the following:
• Inspect and clean or replace air fi lters at the beginning
of each heating and cooling season, or more frequently
if required.
• Inspect the condensate drain and outdoor coil at the
beginning of each cooling season. Remove any debris.
Clean the outdoor coil and louvers as necessary using
a mild detergent and water. Rinse thoroughly with water.
• Inspect the electrical connections for tightness at the
beginning of each heating and cooling season. Service
as necessary.
Model Number
JS5BD-
Height
-H-
Width
-W-
02423"22 3/4"22 3/4"
Figure 4. Unit Dimensions
Depth
-D-
9
Page 10
FIGURES & TABLES
REFRIGERANT CHARGING TABLES
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
74156119
76159124173126
78161130175131190133
80161139177136192138206139
82165142178143194142208144223145
84182146195148211148225150239151
86199151213153227154241156256157
88216157230158243160258161272163
90220160233162247164260165274166
92237166250168264169276170
94254172267174281175
96271178284180
98288184
100
707580859095100105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 5. Charging Table for JS5BD-018 Series (1.5 Ton Units)
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
71149103
73152109167115
75154114170120185126
77154124172125187131203137
79157126172132190135205141221147
81176135191141207146223151239157
83194145209150225156241162257167
85213154228160243166259171274177
87216158231164246170261175276181
89235168250174265180278185
91253178268184283190
93272188287194
95290199
97
707580859095100105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 6. Charging Table for JS5BD-024KB Series (2 Ton Units with Microchannel Coil)
10
Page 11
REFRIGERANT CHARGING TABLES
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
6813994
70142100158108
72144105160113176120
74142118162118178125194133
76145121161127180130196137212144
78165130180137198142214149230156
80184140199147216153232160248167
82203151218158234164250171266178
84206154222161237168252175268182
86225165241173256180270186
88244177260184275191
90263188279196
92282200
94
707580859095100105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 7. Charging Table for JS5BD-030KB Series (2.5 Ton Units with Microchannel Coil)
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
6914799
71150105167113
73152110169118186126
75150124171123188131205139
77153126170133190136207144224151
79174136190143209148226156243163
81194146210153228160245168262175
83214157230164247172264179281186
85217161234168251176266183283190
87237172254180271187285194
89257184274192291199
91277196294204
93297208
95
707580859095100105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 8. Charging Table for JS5BD-036KB Series (3 Ton Units with Microchannel Coil)
11
Page 12
REFRIGERANT CHARGING TABLES
Shaded boxes indicate fl ooded conditions.
Rated design values. The suction pressure will vary from design value if indoor air fl ow, entering dry bulb,
or entering wet bulb temperatures are lower than design.
1. All pressures are listed in psig and all temperatures in ° F
2. Discharge temperatures greater than charted values indicate an undercharged system.
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
73174138
75176143186142
77178149188147198146
79181153190152200151210150
81185156193156202156212155222154
83197159205160214159224158234158
85209163217163226163236162246162
87221167229167238166248166258165
89224170233171242170250170260169
91236174245174254174262173
93248178257178266177
95260182269182
97272186
99
707580859095100105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Table 9. Charging Table for JS5BD-042 Series (3.5 Ton Units)
OUTDOOR TEMPERATURE (° F)
Suct.
Press.
72150125
74153130167131
76155135169136184138
78155144171141186143200144
80159147172148188148202149217151
82176151190153204154219155233157
84193156207158221159235161249162
86210162224164237165251166266168
88213165227167241169253170268172
90230171244173257175270176
92247177261179274181
94264183278185
96281190
98
707580859095100105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Table 10. Charging Table for JS5BD-048 Series (4 Ton Units)
Dis.
Temp.
12
Page 13
OUTDOOR TEMPERATURE (° F)
Add refrigerant when below curve
JS5BD-018 SERIES CHARGING CHART
Remove refrigerant when above curve
Suct.
Press.
68149141
70151146166146
72154151168151183151
74154160171156185156200156
76158163172163187161202160217160
78175166189166204165219165234165
80193169207170221169236169251169
82210173224173238173253173267173
84213177227177241177255177269177
86231181245181259181271180
88248185262186276185
90265190279190
92283194
94
707580859095100105
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Dis.
Temp.
Liq.
Press.
Table 11. Charging Table for JS5BD-060 Series (5 Ton Units)
Dis.
Temp.
TXV COOLING CHARGING CHARTS
400
380
360
340
320
300
280
260
240
220
Liquid Pressure (psig)
200
180
160
140
7580859095100105110115120125130135
Liquid Temperature (F)
Figure 5. Charging Chart for 1.5 Ton Units
13
Page 14
400
Add refrigerant when below curve
JS5BD-024KB SERIES CHARGING CHART
Remove refrigerant when above curve
Add refrigerant when below curve
JS5BD-030KB SERIES CHARGING CHART
Remove refrigerant when above curve
380
360
340
320
300
280
260
240
220
Liquid Pressure (psig)
200
180
160
140
7580859095100105110115120125130135
Liquid Temperature (F)
Figure 6. Charging Chart for 2 Ton Units (with Microchannel Coil)
400
380
360
340
320
300
280
260
240
220
Liquid Pressure (psig)
200
180
160
140
7580859095100105110115120125130135
Liquid Temperature (F)
Figure 7. Charging Chart for 2.5 Ton Units (with Microchannel Coil)
14
Page 15
400
Add refrigerant when below curve
JS5BD-036KB SERIES CHARGING CHART
Remove refrigerant when above curve
Add refrigerant when below curve
JS5BD-042 SERIES CHARGING CHART
Remove refrigerant when above curve
380
360
340
320
300
280
260
240
220
Liquid Pressure (psig)
200
180
160
140
7580859095100105110115120125130135
Liquid Temperature (F)
Figure 8. Charging Chart for 3 Ton Units (with Microchannel Coil)
400
380
360
340
320
300
280
260
240
220
Liquid Pressure (psig)
200
180
160
140
7580859095100105110115120125130135
Liquid Temperature (F)
Figure 9. Charging Chart for 3.5 Ton Units
15
Page 16
400
Add refrigerant when below curve
JS5BD-048 SERIES CHARGING CHART
Remove refrigerant when above curve
Add refrigerant when below curve
JS5BD-060 SERIES CHARGING CHART
Remove refrigerant when above curve
380
360
340
320
300
280
260
240
220
Liquid Pressure (psig)
200
180
160
140
7580859095100105110115120125130135
Liquid Temperature (F)
Figure 10. Charging Chart for 4 Ton Units
400
380
360
340
320
300
280
260
240
220
Liquid Pressure (psig)
200
180
160
140
7580859095100105110115120125130135
Liquid Temperature (F)
Figure 11. Charging Chart for 5 Ton Units
16
Page 17
WIRING DIAGRAM
Split System Air Conditioner (Outdoor Section)
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 deg C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40ca/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
7. Anti-Short Cycle Timer (ASCT) may or may not be installed in the unit. If desired,
ASCT is factory installed on select models only or may be field installed as shown using
manufacturer’s approved kit. If not present, connect Yellow and Black wires per Note 6.
8. DO NOT use a Hard Start Kit on a model with a PTCR installed.
208/230V
L1
CCH
(OPTIONAL)
T1
PTCR (If equipped)
H
C
F
24 VOLT FIELD
CONNECTIONS
CC - Contactor Coil
CCH - Crankcase Heater
HPS - High Pressure Switch
COMPRESSOR
R
C
S
COMPRESSOR
S
C
R
ASCT
(SEE NOTE 7)
CC
ASCT
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
CONTACTS
OUTDOOR FAN
MOTOR
L2
T2
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs
en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
BLUE
ORANGE
RED OR
ASCT
YELLOW
(SEE
NOTE 7)
T2
T1
T3
YELLOW
SEE NOTE 6
BLACK
BLACK
CRANKCASE
HEATER
(OPTIONAL)
¢710570|¤
R
S
OUTDOOR
FAN MOTOR
F
C
H
RED OR
RED BLACK
CONTACTOR
RED OR
RED BLACK
C
Single Phase
Optional Hard Start Kit
to “H” on capacitor
to T2 on
contactor
BLACK
C
DUAL
CAPACITOR
YELLOW
R
S
L1 L2
(Replaces 710570A)
PTCR
(if equip)
YELLOW
T2
T1
L1
L2
GND
710570B
BLACK
START
RELAY
PTCR
GROUNDING
0109
3
YELLOW
START
CAPAC
YELLOW
to “C” on
capacitor
YELLOW
YELLOW
OR
YELLOW
BLACK
BLACK OR
BLK WHT
SCREW
RED
2
1
Figure 12. JS5BD Wiring Diagram
17
Page 18
18
Page 19
19
Page 20
¢709234&¤
Specifi cations & illustrations subject to change without notice or incurring obligations.
O’ Fallon, MO | Printed in U.S.A. (08/10)
7092340 (Replaces 7088500)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.