The iQ Drive heat pump operates as part of a larger intercommunicating system which provides temperature, air fl ow, and
humidity control for a residence or other similarly sized building. This system includes this outdoor unit, the dedicated iQ
controller (thermostat), and an iQ system-compatible indoor unit, typically an air handler with electric strip heat or a gas
furnace. The system will function only if these components are matched and intended f or use within this system. A complete
list of compatible equipment by model and serial number is available in NORDYNE document 709031, iQ Field Wiring
Installation Instruction. Accessory equipment which may be used with this system includes humidifi ers, electric or electronic
air cleaners, and U/V (ultraviolet) sterilizing lamps.
Refer to the System Operation section below for a complete description of how to use the various features of the system.
In addition to providing the means for operation, the controller also serves as the means for initial system confi guration and
setup, and it provides a considerable amount of information for troubleshooting the system and diagnosing problems.
OTHER REFERENCE DOCUMENTS
• Installation instruction documents for indoor equipment (furnace or air handler, optional humidifi er, etc.)
• iQ Field Wiring Installation Instruction, document 709031, provided in the iQ thermostat/controller kit
• iQ Thermostat/Controller User’s Manual, document 709063, provided in the iQ thermostat/controller kit
• local wiring and building codes
• Nordyne Application Guideline for Refrigerant Lines Over 75 Feet document 044B-0600
Electrical Power Wiring ....................................................................................................................................3
Control Circuit Wiring .......................................................................................................................................4
iQ Zone Control Wiring ....................................................................................................................................4
REFRIGERANT LINE CONNECTIONS ...............................................................................................................4
Line Design and Routing ..................................................................................................................................4
System Evacuation ..........................................................................................................................................5
Alternate Procedure for Charging a Heat Pump in Cooling Mode ...................................................................6
Alternate Procedure for Charging a Heat Pump in Heating Mode ...................................................................6
SYSTEM SETUP USING THE IQ CONTROLLER ...............................................................................................6
General ............................................................................................................................................................6
The Main Screen ..............................................................................................................................................6
System Confi guration ..................................................................................................................................7
Dealer Information .......................................................................................................................................8
Heat Off Delay .............................................................................................................................................9
Service T ests ...............................................................................................................................................9
SERVICE INFORMATION Screens ................................................................................................................... 10
Other Confi guration Entries ........................................................................................................................... 11
Auto Changeover Time .............................................................................................................................. 12
Date and Time ........................................................................................................................................... 12
Program Schedule vs. Nonprogrammable .................................................................................................12
Zone Control ..............................................................................................................................................13
System Operation: Quick Start.......................................................................................................................14
System Startup, Checkout, & Troubleshooting ............................................................................................... 15
SYSTEM DIAGNOSIS & TROUBLESHOOTING ...............................................................................................16
Outdoor Unit Inverter .....................................................................................................................................16
Outdoor Unit Interface Board (right side small circuit board) ......................................................................... 16
Outdoor Unit EXV Board (left side small circuit board) .................................................................................. 17
Indoor Unit Interface Board (in G6 iQ furnace kit or air handler) ...................................................................17
Indoor Unit EXV Board ...................................................................................................................................17
Indoor Unit Constant CFM Motor Control Board ............................................................................................ 17
Indoor Unit One or Two-Stage G7 Furnace Board .........................................................................................
17
Indoor Unit iQ Modulating Gas Furnace Board .............................................................................................. 17
Airzone Control Board ....................................................................................................................................17
iQ Zone System Confi guration .......................................................................................................................18
Common Troubleshooting Issues ...................................................................................................................18
Before proceeding with installation of iQ heat pump equipment,
consult with the distributor and homeowner to confi rm that the
equipment listed on the order is what was ordered, and that
it matches labeling on the equipment packaging.
Next determine (including consultation with the homeowner) the
intended/preferred location for placement of the compressor/
outdoor coil unit. Unit envelope dimensions are shown in
Figure 1.
This heat pump is designed for outdoor installation only.
Unit placement must take into consideration the following
clearances: (a) A minimum of 18 inches must be provided
between each of the four sides and any solid barrier or wall
which might block free inlet air fl ow into the coil. A minimum
clearance of 36 inches is required between multiple units.
(b) The corner of the unit covered by the control access
cover must be clear enough to allow comfortable access by
a serviceperson. (c) The top of the unit must be open and
unobstructed to prevent recirculation of outdoor f an discharge
air, particularly for air conditioning usage. A minimum distance
of 4 feet ov erhead clearance is recommended. Do not locate
the unit in a pit with high walls on all sides.
• Refrigerant lines should NOT be buried. (in concrete or
otherwise)
• Refer to Nordyne Application Guideline for Refrigerant Lines
Over 75 Feet document 044B-0600, for piping details
Once the above inf ormation has been confi rmed and potential
questions regarding location, refrigerant line routing, and
wire routing have been resolv ed, proceed with unpacking the
equipment. It is strongly recommended that inspection of the
hardware be performed prior to bringing it to the installation
site. Inspect for cosmetic as well as functional damage (such
as obvious holes or gaps in tubes and joints, cut or pinched
wires or wire insulation).
V erify that the iQ Drive
®
heat pump unit package includes the
following:
• Coil/compressor/control unit.
• Packet containing installation instructions and one fi lter-drier.
NOTE: The thermostat/controller which is required for
system operation is part of a separately purchased kit.
ELECTRICAL CONNECTIONS
Locate the unit away from o verhangs which would allow water
runoff or ice to fall directly onto the heat pump. Avoid placing
the unit near sidewalks or walkways to avoid possible icing
from defrost cycles. In low temperature climates, place the
unit where it is not directly in prevailing winds. Avoid placing
the heat pump near sleeping quarters or windows. As the unit
goes through defrost cycles, a change in sound will occur.
Slab Mounting
The preferred unit mounting is on an outdoor slab (concrete
or plastic), on the ground, in an area with good drainage
unlikely to be affected b y heavy runoff, ground settling, or deep
snowdrift accumulation. The support slab should be level. If
the area is subject to heavy snowfall or drift accumulation, the
use of a snow stand is recommended as well. Make sure that
the drain holes in the bottom of the unit are not obstructed.
Roof Mounting
The method used for roof mounting should be designed so
as not to overload roof structures nor transmit noise to the
interior of the structure. Refrigerant and electrical lines should
be routed through suitably waterproofed openings to prev ent
leaking into the structure. Make sure that the roof structure
can adequately support the weight of the equipment. Consult
local building codes for rooftop installations.
After a location has tentatively been selected, trace routing
of new (or pre-existing) refrigerant lines (two), and po wer and
control wiring. See further discussion below.
• Maximum recommended length for refrigerant lines: 100 ft.
• Maximum elevation diff erence, compressor base to indoor
coil base (compressor higher): 50 feet NOTE: An oil trap
is required for elevations exceeding 50 feet.
• Maximum elevation diff erence, compressor base to indoor
coil base (compressor lower): 50 feet NOTE: An oil trap is
required for elevations exceeding 50 feet.
W ARNING:
ELECTRIC SHOCK HAZARD
Disconnect all electrical power at main circuit bo x
before wiring electrical power to the outdoor unit.
Failure to follow these instructions may result in
electric shock or death.
Electrical Power Wiring
Electrical power wiring shall comply with the current
provisions of the National Electrical Code (ANSI/NFP A 70) as
supplemented by applicable local building codes . The installer
should become familiar with the wiring diagram before making
electrical connections to the outdoor unit. An equipment
wiring diagram is included in this instruction and inside the
unit control panel cover . Refer to the unit rating label located
on the exterior of the control box cover for operating voltage,
minimum circuit ampacity , and maximum fuse size. See Table
I for wire sizing.
Wire Sized based on N.E.C. for 60°C type copper conductors
up to 50 51 - 100 101 - 150 151 - 200
Table 1. Copper Wire Ampacity Tables
Supply Wire Length - Ft
3
Page 4
• A properly siz ed branch circuit and disconnect switch must
be installed where it is easily accessible and within line of
sight of the outdoor unit.
• Remove the control panel cover . Route the power and ground
wires (3 wires, including earth ground) from the disconnect
box to the unit. Use of outdoor shielded conduit (metal
lined Sealtite
®
) is required. The electrical conduit opening
is located on the lower left corner of the control box.
• Connect the power wires to L1 and L2 box lugs of the
contactor, and the ground wire to the grounding lug to the
left of the contactor. See Figures 2 and 3. Only copper wires
should be used.
• Replace the control panel cover before applying power.
Control Circuit Wiring
The heat pump is designed to operate with a 24 VAC Class
II control circuit. Control circuit wiring must comply with the
latest version of the National Electrical Code (ANSI/NFPA
70) as supplemented by local building codes.
In general, 24 VAC control power and communication bus
wiring must be run to interconnect the thermostat/controller,
the indoor unit, and the outdoor unit. The “hub” of this network
and source of the 24 VAC is located within the indoor unit (air
handler or furnace). Refer to iQ Drive System Field Wiring
Instructions, NORDYNE document 709031 shipped with the
controller, for connection of control wires to the indoor unit
and for description of other indoor fi eld wiring, including to
the controller.
Five (5) wires must be run between the indoor unit and the
outdoor unit (2 for 24 VAC pow er and 3 f or communications).
Use one shielded cable (3 or more conductors) for
communications only, and a separate cable or pair of wires
for control power . Refer to wiring diagram Figure 4 and Table
II.
1. Pass the 5 control wires into the hole in the lower right side
of the control panel of the outdoor unit, into the separate
low voltage wiring compartment. See Figures 5 and 6.
2. Locate the 5 corresponding factory-wired leads with
stripped ends. Assure that each of these 5 wires (on the
factory wiring side of the wire connections) loops around
and through the “donut” (toroidal choke). Refer to Figure
7 which shows one wire making a single loop.
3. Connect each of the 5 fi eld-run wires to its factory-wired
counterpar t using a wire nut, as indicated in Figures 4, 5
and 6.
4. Replace the control panel cover before applying power.
IMPORTANT
It is critical that the wires meant to connect to 24
vac control power (RED & GRA Y) are not mistakenly
connected to the communication bus wires (YEL,
WHT , GRN). 24 volts applied to the communication
bus will damage the equipment.
Communication Wiring
Indoor
Interface
Board
Terminal
DX+YELYEL
DX-WHTWHT
GNDGRNGRN
R (screw)
C (screw)
Indoor
Interface
Board plug
wire color
Control Power Wiring
[no factory
wire]
[no factory
wire]
Outdoor unit
wire color
Outdoor Interface
Board Terminal
(RHS circuit
board)
3 pin 3 wire white
connector plug at
RHS circuit board
terminal
“INDOOR”
RED“R” terminal screw
GRY
(contactor coil,
RHS)
Table 2. Control Wiring to Outdoor iQ Heat Pump Unit
iQ Zone Control Wiring
For iQ Zone systems, fi eld wiring is required to connect the
Airzone control board to the iQ communication bus and to
provide a ground connection for the separate zoning control
and communication network. Refer to the iQ Field Wiring
Instruction document provided in the iQ controller kit for more
details. A 3-wire cable must be run from a splice point in the
iQ communication bus to the one 3-pin connector on the
Airzone control board.
Recheck Wiring
Check that wire routing is correct and connections are secure
for all power and control wiring.
REFRIGERANT LINE CONNECTIONS
Line Design and Routing
Refrigerant lines must be connected by a licensed EPA
certifi ed technician following sound established installation
practice. Once the heat pump location has been determined
and the unit set in place the refrigerant lines should be routed
and connected.
• Refrigerant lines should f ollow a direct path from the indoor
coil to the outdoor unit avoiding sharp bends. When lines
pass through walls, make sure to properly seal and support
them so that vibration is not transmitted to the structure.
• Refrigerant tubing should be supported in a manner which
assures that the tubing will not vibrate or wear as a result
of contact with sharp materials or edges during system
operation.
• Lines must be clean refrigeration-grade copper.
• A void removing caps and plugs from the heat pump or lines
until they are ready to be connected.
• Insulate the vapor line with refrigerant line insulation ¼” wall
thickness or greater.
Proper system performance and oil management depend on
properly selecting the liquid and vapor line sizes. Refer to T able
III for the proper size of fi eld supplied lines. The maximum
allowable refrigerant line length is 100 ft.
4
Page 5
Liquid
Line
up to 100
ft.
3/8 in.
(10 mm)
3/8 in.
(10 mm)
3/8 in.
(10 mm)
Line Set
Length
-024K Units
-036K Units
-048K Units
Vapor Line
up to 24 ft. 25 to 39 ft. 40 to 75 ft.
3/4 in.
(19 mm)
7/8 in.
(22 mm)
7/8 in.
(22 mm)
3/4 in.
(19 mm)
7/8 in.
(22 mm)
1 1/8 in.
(29 mm)
7/8 in.
(22 mm)
1 1/8 in.
(29 mm)
1 1/8 in.
(29 mm)
75 to 100
ft.
1 1/8 in.
(29 mm)
1 1/8 in.
(29 mm)
1 1/8 in.
(29 mm)
Table 3. Permissible Refrigerant Line Sizes
The maximum vertical elevation between the heat pump and
indoor coil is 50 ft. Systems that require more elevation will
need to have an oil trap installed in the vapor line. Refer to
Nordyne Application Guideline for Refrigerant Lines Over 75
Feet (document 044B-0600) for piping details.
A fi lter drier is supplied with the heat pump. It is required and
recommended that it be installed near the indoor coil.
It is recommended to replace existing refrigerant lines that
were previously used f or an R-22 system. If the lines are not
replaced, they must be properly fl ushed by a licensed EPA
certifi ed technician in accordance with the manufacturer’s
instructions and established procedures.
valves and stop the vacuum pump to look for a rapid loss
of vacuum. Loss of vacuum indicates that there is a leak
in the system. Repeat the leak test if required.
3. Evacuate the system to at least 500 microns to remove
non-condensables and water vapor. Close the manifold
valves and remove the vacuum pump.
4. Connect the refrigerant tank to the center manifold port of
the gauge set. Pressurize the system enough to break the
vacuum.
5. Open both service valves by tur ning the valve stems ¼
turn counterclockwise. The stem will be in line with the
tubes. Replace the stem caps and tighten. Proceed with
Refrigerant Charging section.
W ARNING:
The heat pump system contains liquid and
gaseous refrigerant under pressure. Adjustment
of refrigerant charge should only be done by a
qualifi ed, EPA certifi ed technician thoroughly
familiar with this type of equipment. Under no
circumstances should the homeowner attempt to
install and/or service this equipment. Failure to
comply with this warning could result in equipment
damage, personal injury, or death.
Brazing
Use the appropriate safety equipment while brazing. Items
such as gloves, safety glasses, proper ventilation, and a fi re
extinguisher should be used.
1. Route the refrigerant lines from the indoor coil to the service
valves on the heat pump. Avoid sharp radius bends and
turns.
2. Make sure that the vapor line is properly insulated for the
entire length of the run for maximum system effi ciency.
Improper insulation may also create condensation and result
in water damage to the equipment and building structure.
3. Remove the valv e cores from the heat pump service v alves.
Wrap the valves completely with wet rags to protect them
from overheating during the brazing operation.
4. Connect both the vapor and liquid lines. Tubes should be
round, de-burred and free of debris. Use a phosphorous
and copper or silver brazing alloy f or the joints. Do not use
soft solder with a low melting point.
5. Connect the indoor lines according to the indoor unit
instructions. The indoor coil will require the same alloys
and wet rags to protect the sensors from excessive heat
on the refrigerant lines.
6. Allow the service valves to cool and replace the valve cores .
7. Leak test the connections using low pressure dry nitrogen.
System Evacuation
1. Connect the refr igerant gauge manifold to both the vapor
and liquid service valves. See Figure 8. Connect the center
port to the vacuum pump.
2. Open both manifold valves and start the vacuum pump.
After a short time, it is recommended to close the manifold
Refrigerant Charging
NOTE: The unit must be charged at a fi xed speed setting.
or this purpose the thermostat/controller needs to be wired
and powered prior to charging. Using the thermostat, go
to CHARGE MODE under SERVICE TESTS from the
INSTALLER SETTINGS menu, described later in this
document. Select CHARGE MODE to add or verify system
charge. In the CHARGE MODE screen, HEATING or
COOLING mode may be selected, depending upon which
mode of operation is more appropriate or convenient at the
time of charging.
NOTES:
• The heat pump is factory charged for fi eld installed lines 15
ft. in length with the matching indoor equipment. Adjustments
to the refrigerant charge will be required for other length
and tube sizes. For lines longer than 15 ft with a 3/8” OD
liquid line, add 0.52 oz. per ft.
• Small variations in the temperatures and pressures are
normal due to differences in the installation.
• Large variations in the temperatures and pressures
could indicate incorrect charge or another problem with a
component in the system.
The preferred method of charging is by weighing in the
additional refrigerant required. If a charging scale is not
available, the next preferred charging method would be to
use the sub-cooling method in cooling mode.
5
Page 6
MODEL:
Factory Charge
(for 15 ft. line set)
Additional Charge
for 50 ft. line set
Additional Charge
for 100 ft. line set
2 TON
(-024K)
10.0 lbs
(160 oz)
+ 1.1 lbs
(18 oz)
+ 2.8 lbs
(44 oz)
3 TON
(-036K)
10.5 lbs
(168 oz)
+ 1.1 lbs
(18 oz)
+ 2.8 lbs
(44 oz)
4 TON
(-048K)
11.8 lbs
(188 oz)
+ 1.1 lbs
(18 oz)
+ 2.8 lbs
(44 oz)
Table 4. Refrigerant Charge Quantities
Alternate Procedure for Charging Heat Pump in
Cooling Mode (with outdoor temperatures above
60 °F) Based on Subcooling:
While charging based on weight is preferred, this method is
acceptable. Use this method when the outdoor temperature
is 60°F or higher to verify the correct charge in cooling mode.
The indoor temperature should be between 70°F and 80°F.
1. Connect the gauge manifold to the liquid and vapor service
valves (Figure 8).
2. Start the system in CHARGE MODE, COOLING. Allow
the system to run 15 minutes to stabilize.
3. Record the liquid refrigerant pressure in psig at the service
valve.
4. Record the liquid refrigerant temperature in °F at the service
valve.
5. Using the temperature value recorded, determine the
corresponding liquid refrigerant pressure from the upper
curve (for cooling) in the charging chart (Figure 9).
6. If the pressure measured in step 3 is less than the required
liquid refrigerant pressure determined in step 5, then
refrigerant needs to be added.
7. If the pressure measured in step 3 is greater than the
required liquid refrigerant pressure determined in step 5,
then the system is over-charged.
8. Add or remove charge from the system depending on the
measurements recorded. Allo w the system to stabilize f or
15 minutes before taking the next readings.
2. Start the system in CHARGE MODE, HEA TING. Allow the
system to run 15 minutes to stabilize.
3. Record the liquid refrigerant pressure in psig at the service
valve.
4. Record the liquid refrigerant temperature in °F at the service
valve.
5. Using the temperature value recorded, determine the
corresponding liquid refrigerant pressure from the lower
curve (for heating) in the charging chart (Figure 9).
6. If the pressure measured in step 3 is less than the required
liquid refrigerant pressure determined in step 5, then
refrigerant needs to be added.
7. If the pressure measured in step 3 is greater than the
required liquid refrigerant pressure determined in step 5,
then the system is over-charged.
8. Add or remove charge from the system depending on the
measurements recorded. Allo w the system to stabilize f or
15 minutes before taking the next readings.
SYSTEM SETUP USING THE IQ CONTROLLER
IMPORTANT:
It essential that the wires meant to provide 24 v olts
to the outdoor unit are not mistakenly connected to
the communication terminals. Chec k again before
you apply power!
General
Pow er up the entire system with the iQ controller (thermostat)
installed in its base. The controller will be of use to the installer
for the following general purposes:
• Confi guring the system using INSTALLER SETTINGS
screens (required)
• Running system service tests (recommended)
• Using service information screens to examine and diagnose
system operation (very helpful, if needed)
• Setting options and features which are not typically used
or understood by the homeowner (recommended)
• Setting options and features with the homeowner’ s oversight
in an effort to train him/her (suggested)
Alternate Procedure for Charging Heat Pump in
Heating Mode (with outdoor temperatures below
60 °F) Based on Subcooling:
Use this method when the outdoor temperature is 60°F or
lower to estimate the correct charge in heating mode. The
indoor temperature should be between 65° F and 75° F.
The preferred method of charging is by weighing in the
additional refrigerant required. If a charging scale is not
available , the correct charge can be estimated by this method.
Refrigerant can be stored in the receiver and accumulators
and result in an over-charged system. If it is necessary to
use this method, follow up service should be scheduled when
the temperature is above 60°F, and then charge should be
verifi ed in cooling mode.
1. Connect the gauge manifold to the liquid service valve and
suction service por t located at the left side of the access
panel above the liquid service valve. See Figure 8.
6
The following descriptions of the controller apply specifi cally
to software Version 5.0. A summary of the controller menu
structure is provided in Figures 10 & 11. NOTE: This guideline
is not intended to be a comprehensive substitute for proper
iQ Drive system training (required).
Screen Navigation
Moving between option categories on menu screens or
moving between possible values for any one option is done
using the and keys. The line or value with a dark
background behind the characters is considered “selected”.
In order to change a selected option in most screens, or to
save a changed v alue , use the
key. Use the key to back
up into the previous screen in the menu/screen structure.
The Main Screen
The Main Screen is the normal display viewed on the
controller. It prominently shows room temperature and
Page 7
operating mode (e.g., COOL or HEAT) in large numerals and
letters. Across the bottom line of the display are fi ve words
or abbreviations (normally RH TEMP MODE FAN MENU)
which represent selectable entry points into the menus. The
user can always return to the main screen from any other
screen by repeatedly pressing the
3/13/09
OUTDOOR
70
key.
12:18 PM
FAN AUTO
NOTE: It is important that any settings or service tests which
are appropriate be made at the time of system installation.
System Confi guration
Any time “CONFIGURATION NEEDED” appears at the top of
the Main Screen, the user must proceed through the SYSTEM
CONFIGURATION screens, even if no changes to values or
options are necessary. This will occur when installing a new
thermostat or moving a thermostat to a different type of iQ
system. The outdoor unit should be powered up when
confi rming or entering system confi guration.
76°
HUMIDITY
36
TEMP
MODERH
HEAT
HEAT 62
COOL 85
MENU
FAN
For iQ Zone systems with zone control enabled, the Main
Screen will appear slightly different, as shown below . The local
temperature reading is absent, and ZONE CNTL appears
under the operating mode.
1/19/09
OUTDOOR
46
10:00 AM
FAN AUTO
COOL
HUMIDITY
36
RHTEMP
ZONE CNTL
MODEMENU
FAN
With the fi rst line SYSTEM CONFIGURATION selected,
press the
key to proceed through the system confi guration
screens. The next screen, titled SYSTEM CONFIGURATION,
provides a read-only summary of the confi guration (as
detected, and otherwise showing either defaults or pre viously
confi gured information).
SYSTEM CONFIGURATION
OUTDOOR SYSTEM
2 TON
HEAT PUMP - IQ
WITH
1 STG GAS FURNACE
BLOWER TYPE B
COMMUNICATION
INDOOR UNIT - OK
OUTDOOR UNIT - OK
The words under OUTDOOR SYSTEM and WITH describe
the system components as automatically detected by the
controller. Both entries under COMMUNICATION should
show “OK”. If “CHECK” appears , it is an indication that either
communication wiring is incomplete or incorrect, or the
outdoor unit is not powered up. Proceed through subsequent
screens by using either the
or key (indicated by “NEXT”).
Installer Settings
Using procedures explained in iQ Drive training, go to the
INSTALLER SETTINGS menu screen.
INSTALLER SETTINGS
SYSTEM CONFIGURATION
ACCESSORIES
DEALER INFORMATION
SERVICE TESTS
RESTORE DEFAULTS
DEFROST CONFIG
HEAT OFF DELAY
ALTITUDE ADJUST
IQ DRIVE REV 5.0
Other than in the splash screen displayed when power is
fi rst applied to the controller, this is the only screen which
displays the controller software version number.
The following table indicates the information that may be
or needs to be manually confi gured or confi rmed by the
installer. (Information not listed is automatically determined.)
If necessary, check the ratings of the indoor unit before
proceeding.
Indoor Unit
Electric Heat
G6 gas furnace
G7 single stage gas
furnace
G7 two stage gas
furnace
Modulating MQ gas
furnace
Items Requiring Manual Confi guration
Heat type, number of stages, staging
differentials, kW
Heat type, number of stages, 1
differential, furnace input rate, furnace rise. If
2-stage: 2nd stage differential
st
stage start differential, furnace rise
1
st
stage start differential, 2nd stage differential,
1
furnace rise
Furnace rise
(or Confi rmation)
st
stage start
Table 5. System Confi guration Entry Summary
7
Page 8
For MQ modulating iQ gas furnaces only, an additional
screen titled “OUTDOOR SYSTEM” will appear after the
SYSTEM CONFIGURATION summary screen. “HEAT
PUMP-IQ” should appear on the second line; no other option
may be selected in this screen. Press the
OUTDOOR SYSTEM
HEAT PUMP - IQ
CAPACITY (TONS)
-
STAGES
-
2ND STG DIFFERENTIAL
-
AIR FLOW, CFM PER TON
-
key to proceed.
Proceed through the subsequent confi guration screens
either accepting or changing entries, until the INSTALLER
SETTINGS menu is displayed again. This is an indication
that confi guration has been completed.
Accessories
Use the or keys to select ACCESSORIES. Press the
key to enter the accessories submenus and screens. This
set of screens allows the installer to trigger alerts (reminders)
when periodic maintenance is recommended for any of the
following accessories:
• Air fi lter
• Humidifi er
• U/V lamp
• Air cleaner
Dealer Information
Use the or keys to select DEALER INFORMA TION. Press
the key to enter the dealer information summary screen,
and submenus and screens. This set of screens allows the
installer to enter text information which will be display ed on a
SERVICE NEEDED displa y screen if a persistent fault occurs.
The following items may be entered:
• Brand name (Maytag, Frigidaire, NuTone, Broan, Tappan,
Westinghouse, or custom)
• Model Number
• Contractor Name
• Contractor Phone Number
DEALER INFORMATION
BRAND NAME
MAYTAG
MODEL NUMBER
FT4BI - 048K
CONTRACTOR NAME
JOE’S HVAC
CONTRACTOR PHONE
911 - 393 - 7777
The entered dealer information summary screen accessible
here will be available for future reference by a serviceperson
(under INSTALLER SETTINGS > DEALER INFORMATION).
Entry of this information is optional.
Defrost Confi guration
Use the or keys to select DEFROST CONFIG. Press the
key to enter the screen which allows changes to:
If desired, set the maintenance alert timing for any of these
based on either hours of operation or calendar time. When
triggered by the passing of the selected time or operating
hours, the maintenance reminder message string will be
displayed on the top of the Main Screen. In addition, at the
base of the Main Screen “CANCEL ALERT” will appear. When
this is selected and the
key is pressed, the maintenance
reminder message will be removed.
ACCESSORIES
AIR FILTER
HUMIDIFIER
UV LAMP
AIR CLEANER
Making changes or entries under ACCESSORIES is optional.
• DEFROST TERMINATION TEMPERATURE. This is the
outdoor coil temperature value which, when reached during
the defrost sequence, will signal the end of the defrost phase
during which the system heats up the outdoor coil to melt
accumulated frost. (Default value is 75°F.)
• COIL DEFROST DELTA T. During heat pump heating
operation a defrost sequence will be triggered when
the outdoor coil temperature falls this amount below the
temperature it would operate at with a clear , unfrosted coil.
(Default value is 6°F.)
DEFROST CONFIG
DEFR TERMINATION TEMP
75 DEG F
COIL DEFROST DELTA T
6 DEG F
8
Page 9
Under normal circumstances it is not necessary or advisable
to change these from their default values.
Heat Off Delay
If the system includes a G6 gas furnace, you may use the
or
keys to select HEAT OFF DELAY. Press the key to
enter the screen which allows changes to the length of time
that the blower (indoor fan) will remain on after the fur nace
fl ame is extinguished. Under normal circumstances it is not
necessary or advisable to change this from its default value
of 120 seconds.
Altitude Adjust
If the system includes an iQ modulating gas furnace, you
may use the or keys to select ALTITUDE ADJUST.
Press the key to enter the screen which allows changes to
the installation altitude (feet above sea level). This entry is
advisable for the modulating gas furnace. Refer also to the
furnace Installation Instructions.
Service T ests
You may use the or keys to select SERVICE TESTS.
Press the key to enter the screen which allows access to
a list of service tests. These tests provide an easy way for
the service person to operate the system in various modes
for operational confi rmation and diagnostic troubleshooting
during installation startup. The following fi ve options are
available in the submenu.
SERVICE TESTS
CHARGE MODE
FURNACE TESTS
AIR COND RUN TESTS
HEAT PUMP RUN TESTS
DISCRETE OUTPUTS
CHARGE MODE – Runs the system at the proper speed for
checking and adjusting refrigerant charge. Select the mode as
HEATING or COOLING, then change RUN from OFF to ON.
The screen backlight will blink red. The user may navigate
to other screens (e.g., SERVICE INFORMATION) during the
process until ON in the CHARGE MODE screen is changed
back to OFF and saved. The red b linking backlight serves as
a reminder that the unit is operating in an abnormal (service)
mode. Select OFF (from the list that includes ON and OFF)
and SAVE (
) when fi nished.
FURNACE TESTS – Runs the system at the selected fi re
level to allow confi rmation of proper operation. The screen
backlight will blink red. A short list of instructions (reminders)
is provided. Select STAR T to run a single stage furnace . Select
LO FIRE or HI FIRE to run a two stage furnace. The user may
navigate to other screens (e.g., SERVICE INFORMATION)
during the process. The red blinking backlight serves as a
reminder that the unit is operating in an abnormal (service)
mode. Select DONE (from the list that includes LO FIRE, HI
FIRE, ST ART , STOP) and SA VE (
) when the test is complete,
before leaving the screen for the last time.
AIR COND RUN TESTS and HEAT PUMP RUN TESTS – In
these screens the unit can be made to run at a fi xed speed
regardless of room temperature. RUN can be changed
between OFF, MAX (speed), INTERMED(iate speed), and
MIN (speed). MAX speed is the same as that used in charge
mode. The screen backlight will blink red when anything but
OFF is selected and saved. The user may navigate to other
screens (e.g., SERVICE INFORMATION) during the process
until RUN in this screen is changed back to OFF and saved.
The red blinking backlight serves as a reminder that the unit
is operating in an abnormal (service) mode. This screen is
primarily intended for test agency usage. Heat pump run
tests apply only to heat pump units. Select OFF and SAVE
(
) when fi nished.
NOTE: While running the system from Service Tests is
convenient for some startup operations, much of the nor mal
fault handling and diagnostic message functionality is disabled.
Within each test screen there may be more than one entry which
can be changed. Select the desired entry to be modifi ed using
the
and keys. The line or v alue with a dark background
behind the characters is considered “selected”. Press the
key to allow changing the selected item (its dark backg round
will then blink). Set the desired value for the item using the
and keys, then press the key to save it.
The following is a brief description of the SERVICE TEST
categories. NOTE: With iQ Zone systems there may be a delay
before the test begins, as all zone dampers open.
For iQ heat pumps the capability to force a defrost is a vailable.
As indicated on the HEAT PUMP RUN TESTS screen, this
feature may only be used when MAX speed has been selected.
To perform a sample defrost while a MAX speed heating run
test is running, press the
key to select DEFROST NO W, then
press the ( ) key to begin the defrost. The defrost sequence
will proceed, including use of auxiliary heat while heating the
coil and the 8 minute post-defrost coil temperature calibration.
Only use this feature if the outdoor conditions are typical
heating conditions. Do not force a defrost before the system
has operated in heating for several minutes fi rst.
DISCRETE OUTPUTS – When the unit is off, this screen
allows the user to operate certain relay-driven outputs in the
system for diagnostic purposes: humidifi er (on the indoor
interface board or blower control board), reversing valve (on
the outdoor interface board), indoor coil EXV (on the indoor
interface board or blow er control board), outdoor coil EXV (on
the outdoor interface board), and crankcase heater (on the
outdoor interface board). More than one of these can be set
to ON at the same time. Lea ving the DISCRETE OUTPUTS
screen will shut all of the listed outputs off.
9
Page 10
SERVICE INFORMATION SCREENS
T ypically, when any of these service tests is being perf ormed,
the serviceperson should check operation visually , with special
instrumentation (if available), and vie w operational data on the
SERVICE INFORMATION screens. Refer to iQ Driv e training
information for how to view these screens.
SERVICE INFORMATION
FAULT STATUS
COMPRESSOR STATUS
OUTDOOR FAN STATUS
INDOOR FAN STATUS
FURNACE STATUS
TEMPERATURE STATUS
CLEAR FAULT HISTORY
CALIBRATION DATA
COMMUNICATION DATA
DEFROST STATUS
ZONING DATA
CAPACITY CONTROL
SELECT OPTION
PREVIOUS
Most of the items on the SERVICE INFORMATION menu are
self-explanatory by title. Some k ey f eatures are the f ollowing
(by item name):
FAULT STATUS – The top entry is ACTIVE FAULT. This
should show NO FAULT unless the last fault detected has
not cleared after its 5 minute lockout period, or the fault
condition still exists. The remainder of the screen shows a
history of previous faults or conditions detected, with military
time and date stamps for each. (Ha ving the correct time and
date confi gured is important in making this list useful.) Use
the
key to view the remainder of the last (most recent) 10
faults logged. Generally , fault logging is not functional during
Service T ests.
FAULT STATUS
ACTIVE FAULT
LOW PRESSURE SWITCH
FAULT HISTORY
1
LOW PRESSURE SWITCH
FLT 23:59 11/14/09
2
OD UNIT COMM FLT
#20 23:59 10/31/09
3
NO FAULT
OUTDOOR F AN ST ATUS – Any FAN ERR OR CODE number
(normally 0) will be logged in the FAULT STATUS screen in
more easily understood wording.
INDOOR FAN STATUS – The contents of this screen varies
depending on which type of blower motor is in the equipment
and whether or not iQ Zone is in use. Much of the information
is not useful to the installer.
TEMPERA TURE ST A TUS – This screen lists all temperatures
measured by the iQ system. TEMP AT TSTAT is the local
temperature used for control (when zoning is not enabled),
and it displays one decimal place without showing the decimal
point (e.g., 704 = 70.4°). In iQ Zone systems, a supply duct
temperature sensor is required, and its reading is displayed
here.
CLEAR F A UL T HIST OR Y – It is recommended that any faults
that appeared during and as a consequence of installation be
cleared out before leaving.
CALIBRA TION DA T A – A Panasonic blower can be recalibrated
any time from this screen by pressing the
key. This ma y be
done if a signifi cant change has been made to blower discharge
ducting or damper usage. This screen is not normally useful to
an installer. Data is not displayed for type “B” blower motors.
COMMUNICA TION DA T A – This important screen indicates the
status of communication with all elements on the iQ bus. All
should show OK. If not, investigate and resolve communication
wiring issues. In iQ Zone systems only, the entry ZONE BOARD
will be displayed, representing the main Airzone control board.
COMMUNICATION DATA
BLOWER
OUTDOOR
ID INTERFACE BD
OD INTERFACE BD
OK
BAD
OK
BAD
COMPRESSOR STATUS – This screen should confi rm the
confi gured size as MODEL NUMBER (20 = 2 tons, 30 = 3
tons, etc.) With correct confi guration only 20, 30, or 40 should
appear here. LOW PRESSURE SW shows the state of the
low pressure switch. Any COMPR ERROR CODE number
(normally 0) will be logged in the FAULT STATUS screen in
more easily understood wording. The displayed information
is read from the outdoor unit.
10
Page 11
DEFROST STATUS – This screen confi rms that a heat pump
is in defrost and provides detailed information helpful to
understand (a) the status of an in-progress defrost cycle and
(b) conditions which may trigger the next defrost cycle. It also
indicates the state of the reversing valve (ON for cooling or
during defrost heating). (Refer to training.)
DEFROST STATUS
DEFROST ON
DEFR STG
TARGET STEP
TIMERS:
COMP 210
OUTDOOR TEMP
OD COIL TEMP
ID COIL TEMP
CLEAR COIL DT
DEFROST COIL T
RV ON
7
9
DEFR 210
33
72
66
3
24
F
F
F
F
F
CAPACITY CONTROL
HEAT PUMP HEATING
ROOM TEMP
SP 700
USED DEMAND
STEP
COMP RPM
OD FAN RPM
ID FAN RPM
OVERRIDE ACTIVE?
MODSP
704 F
698 F
-6F
ACT
TARG
8
2636
2640
1042 1050
91090 0
NO
8
Other Confi guration Entries
The following settings in the controller fall into the following
categories:
ZONING DATA – This screen and its sub-screen ZONE
MODULE STATUS (accessible by pressing the key when
in the ZONING DATA screen) provide impor tant information
to help confi rm proper installation and setup of an iQ Zone
system. Among other things , the ZONING DA T A screen shows
the numbers of the zones which are active (open and in use)
and the weighting assigned to each zone.
Press the
key to view ZONE MODULE ST A TUS. During zone
system setup this screen will indicate which zone modules are
detected in the zone system communication network, which
zone each module is associated with, and any damper motor
issues. After installation of an iQ Zone system, this screen is
essential to confi rm that all module assignments have been
made and detected correctly.
ZONING DATA
ZONES ACTIVE
AZF
HEAT DEMAND
COOL DEMAND
MODE
ZONE FLAGS
ZONE WEIGHTS
ZONE 1 40
ZONE 2 25
ZONE 3 15
ZONE 4 10
OUTPUT
PREVIOUS
00100001
12345678
65
-90
400
COOL
10000001
ZONE 5 10
ZONE 6 0
ZONE 7 0
ZONE 8 0
NF
DETAILS
CAPACITY CONTROL – This screen contains information
primarily relating to the status of the outdoor iQ unit. Target
and actual speeds are shown for the compressor , outdoor fan,
and indoor blower. The line above “ROOM TEMP” displays
helpful system status messages, including whether or not the
system is dehumidifying during cooling.
• options and features which are not typically used or
understood by the homeowner, and should be examined
and considered for adjustment if desired by the installer,
including:
- minimum heat pump operating temperature
- autochangeover time
• settings which are recommended to be done by the installer,
including:
- setting date and time
• options and features which are recommended to be set with
the homeowner’s oversight, including
- selection of programmable schedule versus nonprogrammable
- usage of dehumidifi cation (enabled by default)
- humidity settings
- usage of Smart Recovery (disabled by default)
• further features which the installer may demonstrate to
the homeowner, including
- schedule, including setback temperature settings
- usage of holds
- fan options
- temperature units (°F or °C)
- USA clock or military time (12 or 24 hour)
• settings and features which are unique to the iQ Zone system
(if installed) which should be explained to the homeowner,
including
- how to disable or re-enable zone control
- ventilation (fan) options
- settings typically made at the iQ controller which do not
apply with an iQ Zone system (with zone control enabled)
- settings associated with an iQ Zone system (with
zone control enabled) which are entered at local zone
thermostats, not from the iQ controller
The above settings are described below:
Minimum Heat Pump Operating Temperature
This is the outdoor temperature (measured beneath the outdoor
unit control panel) below which, when heating is called for , the
heat pump will not operate and backup heat means (electric
heat or gas furnace) will take over. The ideal temperature
setting is the “balance point” below which it would be more
11
Page 12
economical to run the backup heat rather than the heat pump.
The default and minimum value f or this parameter is 12°F . Once
the outdoor temperature rises above this setpoint, the heat
pump will be permitted to operate again after the demand has
been satisfi ed and backup heat has shut off. (Determination
of the balance point is not simple and depends on a variety of
local factors, including the price of electricity and gas at any
particular time.)
1. From the Main Screen, press the
To modify the value, perform the following:
or key to select
MENU at the bottom of the screen, then press the key
to see the Main Menu.
2. Use the or key to select SETTINGS, then press the
key to enter the Settings menu.
3. Use the
or key to select OPTIONS, then press the
key to enter the Options screen.
PROGRAM SCHED USAGE
DEHUMIDIFICATION
AUTO CHANGEOVER TIME
SMART RECOVERY
HEAT PUMP USAGE LIMIT
OPTIONS
4 SCHED EVENTS/DAY
ON
60
OFF
NOT BELOW
MINUTES
14F
4. Use the or key to select the value under HEAT PUMP
USAGE LIMIT, then press the key to allow changing the
setting.
5. Use the or key to change the value (2°F increments),
then press the
key to save the setting.
6. Press the key multiple times to return to the Main Screen.
Auto Changeover Time
This adjustment enables AUTO mode, which allows the system
to automatically switch between heating and cooling without
having to touch the controller. Autochangeov er time is the delay
(minimum time) between the end of cooling operation and
the beginning of heating operation (or the reverse). DISABLE
removes A UTO as an available mode . Otherwise, the time may
be selected from 15 to 120 minutes (default 60 minutes).To
modify the value, perform the following:
1. From the Main Screen, press the
MENU at the bottom of the screen, then press the key
to see the Main Menu.
2. Use the or key to select SETTINGS, then press the
key to enter the Settings menu.
3. Use the or key to select OPTIONS, then press the
key to enter the Options screen.
4. Use the or key to select the value under AUTO
CHANGEOVER TIME, then press the key to allow
changing the setting.
5. Use the
or key to change the value , then press the
key to save the setting.
6. Press the
key multiple times to return to the Main Screen.
or key to select
Date and Time
Setting date and time early in the installation process not only
saves the homeowner from having to do it, but provides an
accurate time and date stamp for any faults logged (during
installation checkout, for example) in FAULT HISTORY. By
default, the clock is in 12 hour format. This ma y be changed
on the OPTIONS menu screen (see either of the above two
items). Da ylight Saving Time is automatically taken into account
but may be disabled from the SET DATE AND TIME menu
screen.
To set date and time, perform the following:
1. From the Main Screen, press the or key to select
MENU at the bottom of the screen, then press the key
to see the Main Menu.
2. SET DATE AND TIME will be selected. Press the
key
two times.
3. Enter the year, month, day (date), hour, and minute on
consecutive screens. Use the
or key to change any
value, and press the key to advance to the next. After
setting the minutes value, press the key to save the
complete setting.
4. Press the key multiple times to return to the Main Screen.
Program Schedule versus Nonprogrammable.
While using “setback” program schedules are advisable to
take advantage of potential economic and energy savings,
some homeowners still prefer to perf orm setpoint adjustment
by exclusiv ely using the
and keys. The f ollowing setting
provides the nonprogrammable option or the option f or different
numbers of events per da y (2 or 4) on the prog ram schedule.
To set the program schedule option, perform the following:
1. From the Main Screen, press the
or key to select
MENU at the bottom of the screen, then press the key
to see the Main Menu.
2. Use the
or key to select SETTINGS, then press the
key to enter the Settings menu.
3. Use the or key to select OPTIONS, then press the
key to enter the Options screen.
4. The value under PROGRAM SCHED USAGE will be
selected. Press the
key to allow changing the setting.
5. Use the or key to change the value between “NON
PROGRAMMABLE”, “4 SCHED EVENTS/D AY”, “2 SCHED
EVENTS/DA Y”, and “2 EVENTS/D BUSINESS”. Then press
the
key to save the setting. (The difference between “2
EVENTS/D BUSINESS” and “2 SCHED EVENTS/DAY”
is only the name given to the time blocks within a daily
schedule.)
6. Press the
key multiple times to return to the Main Screen.
Dehumidifi cation
When dehumidifi cation is enabled (as it is by default),
the system will (depending upon the conditions) suspend
responding to room temperature and lower blower speed to
enhance removal of moisture from the air circulating through
the indoor coil. When operating in this manner, the unit will
run cycles of 10 minutes dehumidifying, 5 minutes normal
cooling (adjusting capacity). See also setting the humidity
setpoints in (6) below . To change the dehumidifi cation option,
perform the following:
12
Page 13
1. From the Main Screen, press the or key to select
MENU at the bottom of the screen, then press the key
to see the Main Menu.
2. Use the or key to select SETTINGS, then press the
key to enter the Settings menu.
3. Use the
or key to select OPTIONS, then press the
key to enter the Options screen.
4. Use the or key to select the value under
DEHUMIDIFICATION, then press the key to allow
changing the setting.
5. Use the
(the default) and “OFF”, then press the
or key to change the value between “ON”
key to save the
setting.
6. Press the key multiple times to return to the Main Screen.
Humidity Settings
Separate setpoints for humidifi cation and dehumidifi cation are
available in units of percent RH (relativ e humidity). The humidify
setpoint only is relevant if optional humidifi er equipment has
been installed and connected to the system (the 24 vac
“H” output – See the Field Wiring Installation Instr uctions).
The installer should clarify for the homeowner that priority
is given to cooling over dehumidifying, so the ability of the
system to satisfy the RH setpoint(s) depends on a variety of
conditions. For example if the cooling load causes the unit
to run at an intermediate speed or higher, the effectiveness
of dehumidifi cation is increased.
Humidifi cation can operate when the system is heating
or the fan is set to Manual (ON) with the compressor off.
Dehumidifi cation can operate only when the system is
cooling mode, the dehumidifi cation option is enabled, and
room temperature is close to the setpoint.
To set the humidity
setpoint(s), perform the following:
1. F rom the Main Screen, press the
or key to select RH
at the bottom of the screen, then press the key to see
the Humidity screen. The current setpoints are displayed.
2. As indicated at the bottom of the screen, press the key
to enter the Humidity Settings screen.
HUMIDITY SETTINGS
HUMIDIFY
45%
DEHUMIDIFY
50%
HUMIDIFY and DEHUMIDIFY are different, and changing
one may push the other so that a minimum of 5% is
maintained between the settings. The humidify setpoint
can be set in the range 30 to 45% in increments of 5%. The
dehumidify setpoint can be set in the range 35 to 70% in
increments of 5%. Press the
key to save any changes
5. Press the key multiple times to return to the Main Screen.
Smart Recovery
When Smart Recovery is enabled, the system will start
changing the cooling or heating setpoint in advance of a
schedule change so that the room temperature is at or near
the setpoint of the subsequent schedule time block when that
time block begins. It only applies if the subsequent cooling
setpoint is lower or heating setpoint in higher. Also, if PROGRAM
SCHED USAGE is set to NON PROGRAMMABLE, this option
does not apply . T o change the smart recovery option, perform
the following:
1. From the Main Screen, press the
or key to select
MENU at the bottom of the screen, then press the key
to see the Main Menu.
2. Use the
or key to select SETTINGS, then press the
key to enter the Settings menu.
3. Use the or key to select OPTIONS, then press the
key to enter the Options screen.
4. Use the
or key to select the value under SMART
RECOVERY, then press the key to allow changing the
setting.
5. Use the or key to change the value between “OFF”
(the default) and “ON”, then press the
key to save the
setting.
6. Press the key multiple times to return to the Main Screen.
Zone Control
The installer should provide to the homeowner(s) a document
or diagram which lists or shows (a) the rooms assigned to
each zone number , (b) the weighting assigned to each z one,
(c) the zone module number associated with each supply vent.
Current date and time must be set in the iQ thermostat/controller
since they will be transmitted to, and continually updated in
the local zone thermostats. The Security Lockout feature will
not prevent changing settings in local z one thermostats in an
iQ Zone system.
Temperature units (Fahrenheit or Celsius) can be changed
as follows: Locate the set of eight microswitches on the iQ
Zone main circuit board. Disconnect control power from the
circuit board. Set micros witch #6 up (on) f or °F, down (off) for
°C. Reconnect control power.
It is recommended for the installer to instruct the homeowner(s)
on the following:
3. Use the or key to select the RH setting to change,
then press the
key to allow changes.
4. Use the or key to change the RH setting then press
the key to save the setting. The confi gurable ranges f or
For zoning operation, Operating Mode (COOL, HEAT,
AUTO, E-HEAT, or OFF) must be selected from the iQ Drive
thermostat/controller as with non-zoning systems. Ho w e v er,
the temperature setpoints that will be used are entered and
stored at the local zone thermostats. With iQ Zone systems,
13
Page 14
all settings made in the iQ thermostat/controller dealing
with temperature setpoint (temporary hold, vacation hold,
permanent hold, time schedule, smart recovery) do not apply
unless zone control is disabled. Similar f eatures are provided
and controlled at each zone independently, from the local
zone thermostats. For example, Manual Setpoint Control
replaces T emporary Hold, Automatic Setpoint Control replaces
time schedules, and Sleep Mode replaces Smart Recovery.
See the iQ Zone System Zone Thermostat User’ s Manual f or
information on these alternative features. With the iQ Zone
system a single setpoint is used for both heating and cooling,
as opposed to the standard non-zoning system, which uses
a different setpoint for each.
Zone Control is enabled by def ault if the system is equipped
with and wired for iQ Zone (the normal operating situation).
However, zone control operation can be disabled by choice,
or it may be automatically disabled if there is a problem
detected with it.
T o manually disable zone control when zoning
is already enabled:
ZONE CONTROL
ZONE CONTROL
ENABLE
MODIFY
PREVIOUS
SAVE
1. From the Main Screen select MENU using the
or button.
2. Press the
button.
3. Select SETTINGS using the or button.
4. Press the button.
5. Select ZONE CONTROL using the or button.
6. Press the button.
7. Press the
or button to change ENABLE to DISABLE.
8. Press the button to save the setting.
T o restore zone control (when the zoning system components
are functioning properly), follow the above sequence, but in
step 7 change DISABLE to ENABLE.
iQ Zone offers two types of ventilation that can be turned on
when the cooling or heating systems are not running:
• To deliver air to some but not all zones when not heating
or cooling, use the zone ventilation f eature that is set up at
the individual zone thermostats. See the iQ Zone System
Zone Thermostat User’s Manual for information on how to
set up zone-by-zone v entilation. From the F AN MENU, enter
the VENTILATION SPEED screen in the iQ thermostat/
controller to select or modify the relative speed to be used
when this type of ventilation is operating.
• To use the fan to deliver air to all zones when not heating
or cooling, set the Fan Mode to ON. The Intermittent Fan
feature described earlier will also operate, serving all zones.
Refer to the iQ Drive User’s Manual for other details relating
to zone control operation.
System Operation: Quick Start
The following is a summary of the sequence for typical operation
of the system.
1. Set the date and time (if not already set).
2. Check the program schedule for desired “setback”, and
modify if desired.
3. From the main screen, check/set the Fan operating mode:
• AUTO oper ates the fan (indoor b lower) when the unit is
cooling or heating. This is the “normal” setting.
• ON operates the fan at the selected speed at all times.
The selected speed may change when the compressor ,
electric heat, or furnace is operating.
• PROGRAMMED FAN operates the fan in A UTO or ON
as specifi ed in the program schedule.
4. From the main screen, check/set the Mode:
• COOL runs the heat pump as an air conditioner using
the cooling setpoint. (With iQ Zone, zone control enabled,
there is a single setpoint for both heating and cooling.)
• HEA T attempts to run the heat pump to provide heat using
the heating setpoint. If (a) the outdoor temperature is
below the Heat Pump Usage Limit, or (b) the heat pump
cannot satisfy the load, or (c) the heat pump is disabled
due to a fault, auxiliary (backup) heat will operate. If
backup heat is electric strip heat, it may operate along
with and supplementing the heat pump. If backup heat
is a gas furnace, the furnace and heat pump will not
operate at the same time (except during defrost). (With
iQ Zone, zone control enabled, there is a single setpoint
for both heating and cooling.)
If the outdoor coil temperature is below 35°F, demand
defrost is enabled. Under these conditions, a fi rst time
defrost will occur after approximately one half hour of
compressor operation. Subsequent defrost cycles ma y
be triggered by a drop in outdoor coil temperature or by
a maximum time between defrosts of 6 hours. Refer to
training material for details.
• E HEAT will run the auxiliary heat (electric strip heat or
gas furnace) using the heating setpoint and disable the
heat pump.
• OFF terminates any of the above.
NOTE: Equipment may not shut off immediately after
switching to OFF due to various system limitations.
Once put into the OFF mode, wait until the furnace or
compressor has shut off before selecting another mode.
14
Page 15
5. For systems without iQ Zone, adjust the operating setpoint
if desired using a temporary hold (pressing the or key
when the Main Screen is displayed). With iQ Zone, zone
control enabled, adjust the operating setpoint for each z one
individually by touching the
System Zone Thermostat User’s Manual for details.)
or icon. (Ref er to iQ Zone
System Startup Checkout & Troubleshooting
The following is a summary of the sequence for typical fi rst
operation to check out the system. Reference is made to
INSTALLER SETTINGS and SERVICE INFORMATION
described above.
1. Install system hardware as described in the individual
component installation instructions.
2. Install power and control wiring to all system components,
including the controller, in accordance with the iQ Field
Wiring Installation Instructions.
3. Perf orm pre-charge evacuation of fi eld-installed refrigerant
lines as described in preceding sections.
4. For iQ Zone systems, fi rst apply 12 volt dc power to the
zone control board with the provided AC/DC converter. Apply
electrical power to the system (including the heat pump).
The controller screen display backlight should come on,
and the “iQ” splash screen should appear. If it does not,
trace the 24 vac control power to the “R” terminal on the
thermostat. CONFIGURATION NEEDED should appear
on the top line of the Main Screen (unless the thermostat
had been previously used on a similar iQ system).
5. Proceed with System Confi guration from the INSTALLER
SETTINGS menu (described above). On the SYSTEM
CONFIGURA TION screen v erify that the using size (2 ton,
3 ton, or 4 ton) is correct as indicated. If the wrong value
is shown, the inverter may require re-initialization. Contact
the service representative of the distributor in this case.
On the same screen, the entries under COMMUNICA TION
should be followed by “OK”. If “CHECK” appears for a
communication item, go to the COMMUNICA TION ST A TUS
screen (in the SERVICE INFORMATION menu, described
above), and view which elements are not comm unicating.
T race and check the three communication wires throughout
the system. If isolating a comm unication problem proves to
be diffi cult, it may be useful to disconnect all communication
wires except those which link the thermostat and the noncommunicating element.
6. If COMMUNICA TION ST ATUS was not checked during the
previous step, check it at this time. All listed items should
show a status of “OK”. If any show “BAD”, determine the
source of the problem as indicated in the previous step,
and resolve.
7. For iQ Zone systems only, the main screen should appear
with no temperature reading, and “ZONE CTRL” should
appear below “OFF”. If this is not the case, go to the ZONE
CONTROL screen from the SETTINGS menu, and change
the zone control option to ENABLE. If ZONE CONTROL
does not show up on that menu, the iQ controller has nev er
communicated with the zone control board, and power and
communication wiring to the zone control board need to be
checked. If the main screen reverts to back to the zoningdisabled screen (showing room temperature), power and
communication wiring to the zone control board need to
be checked.
8. Set date and time as described above. This will provide a
“time stamp” for any fault which may arise during system
checkout.
9. If the installation includes a new gas furnace, check out
its operation fi rst. This may be best accomplished from
FURNACE TESTS under SERVICE TESTS from the
INSTALLER SETTINGS menu (see above). Follow steps
instructions provided in the furnace’s installation instructions.
Be sure to verify blower operation during the test.
10. If the outdoor temperature is abo ve 60°F (14°C), test the
refrigerant system running in cooling mode fi rst. If the
outdoor temperature is between 12° and 60°F (-11 and
14°C), test the refrigerant system running in heating mode
fi rst. This may best be accomplished from CHARGE MODE
under SERVICE TESTS from the INST ALLER SETTINGS
menu. Follow the refrigerant charge adjustment procedure
explained above. Note that if a fault is determined in the
outdoor equipment, the backup heating means (electric
strip heat or gas furnace) will start instead.
11. When charge adjustment is completed (if required), run
the heat pump in both cooling and heating modes. This
may also be done using SER VICE TESTS although some
diagnostic messages are disabled in that method.
12. Check the FAULT STATUS screen (described above)
for any faults logged during the startup process. Any
message listed as “ACTIVE FAULT” refers to a condition
which either still exists or occurred within the preceding 5
minutes. Every fault or notifi cation should appear in the
FAULT HISTORY log which star ts on the same screen.
The last 10 faults to have occurred are retained in this
list. Each new item pushes other logged faults down in
the list. The second line associated with each of the 10
entries includes the time and date of detection. While
the wording of fault messages is intended to provide a
reasonable indication as to the responsible condition, the
information conveyed by the abbreviated wording is limited.
Consequently the installer should refer to training literature
for further information in understanding fault messages.
13. If needed, make use of inf ormation provided below under
Troubleshooting: What to Expect with Normal Operation.
14. Independently confi rm operation of any accessories
installed with the heat pump system following instructions
provided with that equipment.
15. Complete the remainder of confi guration settings and
entries as specifi ed above under Installer Settings and
Other Confi guration Entries.
16. For iQ Zone systems, confi rm the zone system setup by
checking information on the ZONING DATA and ZONE
MODULE ST A TUS screens, accessed from the SER VICE
INFORMATION menu. (See SYSTEM DIAGNOSIS AND
TROUBLESHOOTING below.).
15
Page 16
SYSTEM DIAGNOSIS & TROUBLESHOOTING
The following is a summary of normal and abnormal operation
for typical startup to check out the system. Reference is made
to INSTALLER SETTINGS and SERVICE INFORMATION
screens described above. Refer to tr aining literature for more
details.
Diagnostic information for the heat pump can be obtained
from all of the following sources:
• Controller displays. Refer to training materials for
interpretation of fault messages which appear on the Main,
Fault Status, and Service Needed screens.
• Refrigerant system pressure and temperature measurements
(using standard fi eld service instrumentation)
• LED indicator lights on each of the system’s circuit boards
(see below).
Controller
Normal - As soon as 24 vac power is applied, the blue backlight
of the controller should light up. The “iQ” splash screen will
display the software version. If the System Confi guration
procedure has not been performed yet for this system-controller
combination, “CONFIGURATION NEEDED” will be displayed
across the top (alternating with other information).
If the system has a T ype “P” blo wer motor (shown on SYSTEM
CONFIGURA TION and INDOOR FAN ST A TUS screens), used
in air handlers or G6 gas furnaces, the blower will self-calibrate
for 60 seconds as soon as System Confi guration is completed.
All communications links in COMMUNICATION DATA
should show “OK”. All information displayed in the System
Confi guration screen should be accurate.
Abnormal – If the display is not lit, check that 24 vac is being
provided between the “R” and “C” terminals in the thermostat’s
back connection plate. If not, trace the connection of all
controller wires back to the indoor unit (furnace or air handler).
Check that connections are in accordance with fi eld wiring
diagrams and instructions.
If a SERVICE NEEDED screen with a red backlight is displayed,
a fault has been detected. A brief description of the fault
is displayed on the screen. Access to the FAULT STATUS
screen is permitted.
If communication with the outdoor unit is OK but the unit
size (in tons) shown on the System Confi guration screen in
wrong, contact the service representative of the equipment
distributor. The inverter may not have undergone its initialization
procedure, performed at the factory.
Outdoor Unit Inverter
W ARNING
ELECTRIC SHOCK HAZARD!
Disconnect power before servicing the
outdoor unit. Failure to follow these
instructions may result in electric shock or
death. Trouble-shooting the outdoor unit
may require that power be restored with
the control panel cover removed. Become
familiar with the control panel and hazardous
voltage areas before proceeding.
Time is required for inver ter voltage to bleed
down after removal of line po wer . Wait at least
60 seconds after removing line volta ge before
touching any inverter parts or wiring.
Normal – Examine the following with the control panel cover
off. Note the two smaller circuit boards mounted on a metal
“bridge” over the in verter. The red LED behind the upper right
side of the bridge should be lit and on steady when power is
applied to the inverter. Refer to Figures 3 and 12.
Abnormal –The red LED behind the upper right side of the
bridge is not lit. In this case, power is not being provided to
the inverter. Check that line voltage is being applied to the
bottom of the contactor. If so, check that 24 vac is being
provided across the contactor coil. If not, check the control
power wiring (RED and GRY wires) for 24 vac. Check that
the high pressure switch is closed. A fault indicating OD
UNIT COMM FAULT or OD UNIT LOST POWER would also
result from no line voltage applied.
The red LED behind the upper right side of the bridge is lit
but blinking. This indicates that the inver ter is powered up
and that it detects a fault condition. If the controller does not
display a fault message, put the unit into HEAT or COOL
mode, and a message will be displayed. NOTE: When
line power is removed, the red LED will blink for about 1
minute before going out. Check that the 3- and 4-position
communication plugs are connected to the terminals marked
“INVERTER” and “INDOOR” on the right side of the outdoor
interface board.
Outdoor Unit Interface Board (right side small
circuit board)
Normal – Refer to Figure 13. The red LED at the upper left
of this board should do a “heartbeat” blink, consisting of a
double-blink followed by a pause, repeated. Note 4 other
LEDS towards the lower edge of the board. When the
compressor is off, the 3rd LED from the right should be
on (crankcase heater). When the compressor is running
in heating, the 2nd LED from the right should be on (EXV
enabled to open). When the unit is heating and in a defrost
cycle, the 1st and 4th LEDs from the right should be on.
16
Page 17
When the compressor is running in cooling, the right-most
LED should be on (reversing valve is energized).
wired to “R” and “C” on the EXV board. These should not be
cross-wired.
Abnormal – If no LEDs are lit on the board, 24 vac control
power is not being provided across the “R” and “C” terminals.
Check for this voltage between the left-most two screw
terminals (labeled R and C).
Outdoor Unit EXV Board (left side small circuit
board)
Normal – Refer to Figure 14. The green LED at the upper left
of this board should be steadily on, except that a blink at a
regular rate can be expected during cooling operation.
Abnormal – If the green LED is not lit, the EXV board is not
getting 24 vac power from the interf ace board next to it. Chec k
for 24 vac between R and C on the interf ace board, and check
that the tabs marked “R” and “C” on the interface board are
wired to “R” and “C” on the EXV board (red and gray wires,
respectively). These should not be cross-wired.
If the green LED is blinking at a regular rate during heat
pump heating, it indicates that one of the two EXV sensors
is reading out of range. Refer to training literature for sensor
interpretation and troubleshooting.
If the green LED is blinking at a non-uniform rate (heartbeat), it
indicates that the board has been placed in the Manual Mode.
Hold down the small black b utton on the board f or more than
3 seconds to return it to automatic control mode.
Indoor Unit Interface Board
(in G6 iQ furnace kit or air handler)
Normal – The red LED at the upper left of this board should
do a “heartbeat” blink, consisting of a double-blink followed
by a pause, repeated. Note 4 other LEDS towards the lower
edge of the board. When the equipment is off, none of the
LEDs should be on. If the furnace or electric strip heat is
on, 3rd LED or 3rd and 4th LEDs from the right should be
on (fi rst and second stage auxiliary heat). When the unit is
cooling the right-most LED should be on (EXV enabled to
open). If humidifi cation is called for, the 2nd LED from the
right should be on.
Abnormal – If no LEDs are lit on the board, 24 vac control
power is not being provided across the “R” and “C” terminals.
Check for this voltage between the left-most two screw
terminals (labeled R and C).
If the green LED is blinking at a regular rate during cooling,
it indicates that one of the two EXV sensors is reading out
of range. Refer to training literature for sensor interpretation
and troubleshooting.
If the green LED is blinking at a non-uniform rate (heartbeat), it
indicates that the board has been placed in the Manual Mode.
Hold down the small black b utton on the board f or more than
3 seconds to return it to automatic control mode.
Indoor Unit Constant CFM Motor Control Board
Normal – The red LED near the top of the board should be
on steadily. The green LED near the top of the board should
have a “heartbeat” blink, consisting of a double-b link follow ed
by a pause, repeated. Of the four LEDs towards the left side
of the board, the lowest one marked “H” should be on when
humidifi cation is called for.
Abnormal – If the green LED near the top of the board is not
lit, the board is not connected to the communication network
properly . If the red LED near the top of the board is not lit, the
board is not getting 24 vac control power from the furnace board.
Indoor Unit One- or Two-Stage G7 Furnace Board
Normal – The red and green LEDs should be on steadily.
When the furnace is on and a fl ame is detected, the amber
LED should be on.
Abnormal – The LEDs will provide a diagnostic code through
their blink pattern. Refer to furnace Installation Instr uctions
for detailed troubleshooting.
Indoor Unit iQ Modulating Gas Furnace Board
Normal – The red LED should be on steadily. The g reen LED
near the top of the board should have a “hear tbeat” blink,
consisting of a double-blink followed by a pause, repeated.
When the furnace is on and a fl ame is detected, the amber
LED should be on.
Abnormal – The LEDs will provide a diagnostic code through
their blink pattern. Ref er to furnace Installation Instructions f or
detailed troubleshooting. If the green LED alone is not lit, the
board is not connected to the communication network properly .
Airzone Control Board
Indoor Unit EXV Board
Normal – The green LED at the upper left of this board
should be steadily on, except that a blink at a regular rate
can be expected during heat pump heating operation.
Abnormal – If the green LED is not lit, the EXV board is not
getting 24 vac power from the interface board. Check for
24 vac between R and C on the interface board, and check
that the tabs marked “R” and “C” on the interface board are
Normal – One red power LED should be on steady near
where the dc power plugs into the board (upper left corner).
Red and green LEDs at the lower right side of the board (just
below the DIP switch block) fl ash quickly and continuously
(indicating zone network activity). A second set of red and
green LEDs (about 1” to the left of the other green and red
LED pair) also fl ash, with the red LED fl ashing every 3 to 5
seconds, indicating iQ bus communication. See Figure 15.
17
Page 18
Abnormal – If the red LED near the dc power plug is not on,
then the AC/DC power supply is not connected or not working.
If the red LED 1 ½” from the lower right edge does not fl ash,
the module is not communicating properly on the iQ bus.
iQ Zone System Confi guration
Normal – Check the ZONING DA T A screen from the SER VICE
INFORMATION menu (shown on page 11). In the lower
portion of the screen the zone weights shown should match
the intended values, and they should add up to 100(%).
ZONE MODULE STATUS
MOD
1Z10
2Z20
3Z3X
4Z40
5Z50
6Z
7Z
8Z
9Z10
10Z12
PREVIOUS
Press the key to view the ZONE MODULE ST ATUS screen
(shown here). Every module installed in the system should show
up on this list with the proper zone identifi cation number after
the “Z”, follo wed by a “0”. For example , “23Z40” is module 23
in zone 4. The “0” indicates normal functioning. Zone numbers
should only appear with module numbers that were intended to
be assigned. F or master zone modules 1-8, the zone n umber
must match the module number.
Abnormal – If any zone weight shown in the ZONING DATA
screen is incorrect, or if the total for the eight zones is not
100(%), make the appropriate corrections from the zone
thermostat for the zone(s) which require(s) correction.
• For normal operation without changing modes of operation,
the compressor will not restart until 5 minutes (the minimum
off time) have expired since it shut off last.
• A minimum demand of 0.5°F is required before the heat
pump (heating or cooling) will start up.
• The system will wait 5 minutes following detection of a fault
condition before attempting a restart.
Compressor Does Not Shut Off Immediately
• For normal operation without changing modes of operation,
the compressor will not shut off until 5 minutes (the minimum
run time) have expired since it started last.
The Outdoor Fan Does Not Shut Off When the
Compressor Does
• For normal operation the outdoor fan is designed to run for
30 seconds after the compressor shuts off.
In Cooling, the Blower Slows Down and the Unit
Is Not Responding to Room Temperature
• Slowing of blower speed and suspension of normal capacity
control will occur when the unit goes into Dehumidifi cation.
If conditions for dehumidifi cation persist, the unit will run
cycles of 10 minutes in dehumidifi cation, 5 minutes in normal
cooling (responding to room temperature).
In Heating, the Unit Appears to be Cooling
• During heat pump heating when the outdoor temperature
is in the mid-30’s (°F) or lower, the unit will periodically
go into a Demand Defrost operation. After power to the
controller is turned on, the fi rst defrost may occur as soon
as 34 minutes after startup. Subsequently, defrost will be
determined by outdoor coil temperature or by the maximum
time between defrosts of 6 hours (if the coil temperature is
low enough).
If an installed zone module does not show up in the ZONE
MODULE STATUS screen with an assigned zone number,
such as with module 25 in the fi gure, check the wiring to that
zone module. If the zone number is wrong or if the wrong
module number shows up as used, the module needs to be
reconfi gured. If the last character after the zone number is
not “0”, look for the following problems:
• “1” may indicate a disconnected damper motor connector.
• “2” may indicate a damper that is jammed due to b lockage
from a foreign object or damage or dirt on the internal
transmission.
• “3” may indicate that a zone thermostat is not connected
properly to its associated master zone module (1-8).
• “X” may indicate that a module is assigned but not
communicating.
18
In Heat Pump Heating, the Furnace Runs At the
Same Time
• The indoor (backup) heating system will operate during
defrost cycles. (See above item.)
In Heating, the Furnace or Electric Heat Runs
Instead of the Heat Pump
• The indoor backup heat equipment will run instead of the
heat pump if (a) the outdoor air temperature is below the
Minimum Heat Pump Usage Limit, (b) the heat pump is in
a fault condition, or (c) the heat pump is not able to satisfy
the demand (after a time delay).
The System Is In AUTO Mode, but It Won’t Switch
Quickly From Heating to Cooling (or the Reverse)
• There is a confi gurable delay (Auto Changeover Time)
between operating in heating and restarting in cooling (or
the reverse) when in AUTO mode. The default delay for
this changeover is 60 minutes.
Page 19
Although There Is a Large Demand At Startup,
the Compressor Only Runs at Medium Speed
• Regardless of demand the system will always start and run
at an intermediate speed for one minute. Subsequently the
speed may increase signifi cantly.
Humidifi cation or Dehumidifi cation Setpoints Are
Not Being Satisfi ed
• The fi rst priority of the system is to achieve the temperature
setpoint(s). While under most circumstances it will also
satisfy humidity setpoints, its ability to accomplish this is
signifi cantly affected by a variety of installation-based factors
and circumstances.
In an iQ Zone System, the system does not
respond promptly to changes in setpoint or mode
• With zoning systems additional delays may be noticed.
Most commonly this is due to no new changes processed
until zone dampers have completed any prior operation.
For example , an extra minute dela y is deliberately included
when one or more zones are closed.
MAINTENANCE
IMPORTANT:
Be certain the electrical power to the outdoor unit
and the furnace or air handler is disconnected before
doing the following recommended maintenance.
• Inspect the indoor air fi lter monthly. Clean or replace it at
the start of each heating and cooling season or when an
accumulation of dust or dirt is visible. If the indoor coil needs
to be cleaned, contact a qualifi ed service technician.
• Inspect the condensate disposal line from the indoor coil at
the beginning of the cooling season to make sure it is not
obstructed.
• Remove any leaves, grass clippings, and debris from the
outdoor unit coil, being careful not to damage the aluminum
fi ns. Dirt may be cleared from the coil by using a water hose
directed through the discharge fan grille toward the outside
of the unit.
• Have a yearly inspection by a qualifi ed service technician
to ensure that the system is performing at its optimal level.
FIGURES & DIAGRAMS
EXTERIOR WALL
18"
18"
CONTROL
PANEL
18"
18"
Figure 2. Power Wiring ConnectionsFigure 1. Unit Envelope Dimensions
19
Page 20
}
}
}
Inverter
(black plastic case)
Outdoor
EXV Board
Contactor
}
Outdoor
Interface Board
Low V oltage
Control Wiring
Compartment
Figure 3. iQ Drive Heat Pump Control Panel
20
Page 21
iQ DRIVE - HEAT PUMP (OUTDOOR SECTION)
C
COMPR
OD COIL TEMP
SENSOR
(FOR DEFROST)
PRESSURE
TRANSDUCER
EXV
S
R
SUCTION LINE
THERMISTOR
RED
YELLOW
BLACK
6-WIRE
HARNESS
2X
OD FAN
MOTOR
RED
BLACK
YELLOW
V
W
U
TA5
TA4
TA6
EXV BOARD
P3
P2
PANASONIC
INVERTER
R
C
Y
YELLOW
1 2 3 4 5 6 7
COIL T
C
GRAY
RED
CN3
P3
P4
IFB2
R
R
P2
C
CCH
LPS HARNESS
6 5 4 3 2 1
CN6
G-+
G-+
G-+R
O
Y
CN7
CN8
YEL
WH
GN
GN
WH
YL
4-PIN
3 WIRE
4 3 2 1
2 1
CN11
+ - G
LOW PRESSURE
SWITCH
COMPR
DISCHG
TEMP
SENSOR
3-WIRE
HARNESS
OUTDOOR
AMBIENT
TEMP
SENSOR
RED
REACTOR
T2
T1
CONTACTOR
L1
L2
LINE VOLTAGE (208/230)
TA8
TA7
HIGH PRESS.
SWITCH
GRAY
BLACK
GRAY
RED
GRAY
B
CCH RELAY
C
NO
A
LEGEND:
FIELD WIRING
LOW VOLT A GE
HIGH VOLT AGE
WHITE
CRANKCASE
HEATER
TA1
REVERSING VALVE COIL
TA2
TA3
BLACK
GREEN
30A
YELLOW
30A
BLACK
YELLOW
1X
FIELD WIRING TO
INDOOR SECTION
Figure 4. iQ Heat Pump Wiring Diagram
21
Page 22
Figure 5. Low Voltage Compartment Control Wiring Connections
DX-
DX+
GND
Figure 6. iQ Heat Pump Control Wiring Outdoor Destinations
22
CR
GRY
RED
GRN
WHT
YEL
Page 23
SINGLE LOOP SHOWN
Figure 7. Wire Looping Through a Toroidial Choke
Liquid Line
Service Valve
Figure 8. Service Ports and Valves (Below Control Panel)
Suction
Service Port
Vapor Line
Service Valve
23
Page 24
175
225
275
325
375
425
475
525
60708090100110120130
Liquid Pressure (psig)
Liquid Temperatur e (°F)
Cooling Mode
(Outdoor Temperature above 60 °F)
Remove Refrigerant if above the curve
240
260
280
300
320
340
360
380
7580859095100105110115
Liquid Pressure (psig)
Heating Mode
(Outdoor Temperature below 60 °F)
3 Ton
2 Ton
4 Ton
Add Refrigerant if below the curve
Remove Refrigerant if above the curve
3 Ton
2 Ton
4 Ton
Add Refrigerant if below the curve
24
Figure 9. Charging Charts for iQ Heat Pump
Page 25
ZONE MODULE STATUS
ENABLE / DISABLE
ZONE CONTROL
Main Screen
SETTINGS
INSTALLER
NAFEDOMTEMPMENURH
MAIN MENU
SET TIME AND DATE
HOLD
PROGRAM
FAN MENU
VENTILATION SPEED
AUTOONPROGRAMMED FAN
OPERATING MODE
MENU
OFF
AUTO
COOL
FAN
HEAT
MODE
SETTINGS
E HEAT
SECURITY LOCKOUT
SERVICE INFORMATION
FAULT STATUS
COMPRESSOR STATUS
OUTDOOR FAN STATUS
INDOOR FAN STATUS
FURNACE STATUS
SECURITY LOCKOUT
TEMP ADJUST ONLY
TOTAL KEYPAD LOCKOUT
SETTINGS MENU
SCREEN SETTINGS
OPTIONS
OFFSETS
INTERMITTENT FAN
ZONE CONTROL
MODE MENU
OFF
AUTO
COOL
HEAT
E HEAT
FAN MENU
VENTILATION SPEED
AUTOONPROGRAMMED FAN
TEMPERATURE STATUS
CLEAR FAULT HISTORY
CALIBRATION DATA
COMMUNICATION DATA
ZONING DATA
CAPACITY CONTROL
DEFROST STATUS
ENTER PIN NUMBER
FAULT STATUS
COMPRESSOR STATUS
OUTDOOR FAN STATUS
INDOOR FAN STATUS
FURNACE STATUS
CALIBRATION DATA
CLEAR FAULT HISTORY
TEMPERATURE STATUS
MONDAY
SCHEDULE BLOCK 1
SCHEDULE BLOCK 2
SCHEDULE BLOCK 3
SCHEDULE BLOCK 4
TIME HEAT COOL FAN
ZONING DATA
DEFROST STATUS
CAPACITY CONTROL
COMMUNICATION DATA
(TYPICAL FOR EACH DAY OR GROUP OF DAYS LISTED)
INTERMITTENT FAN
FAN ON TIME
FAN OFF TIME
OFFSETS
INDOOR TEMPERATURE
REMOTE INDOOR TEMP
RELATIVE HUMIDITY
HEAT ANTICIPATOR
OPTIONS
PROGRAM SCHED USAGE
DEHUMIDIFICATION
AUTO CHANGEOVER TIME
SMART RECOVERY
HEAT PUMP USAGE LIMIT
BACKUP HEAT RESPONSE
SCREEN SETTINGS
FAHRENHEIT OR CELSIUS
12 OR 24 HOUR CLOCK
CONTRAST
INTERMITTENT FAN
BACKLIGHT ON TIME
HOLD THIS
TEMPERATURE
HUMIDITY
HUMIDITY SETTINGS
HUMIDIFY
DEHUMIDIFY
COPY
[list of days]
EVERY DAY
PROGRAM MENU
HOLD MENU
VACATION
PERMANENT
SET DATE AND TIME
SET DATE AND TIME
AUTO DAYLIGHT SAVING
WEEKDAYS
WEEKENDS
AUTO DAYLIGHT SAVING
ON
SET YEAR
SET DATE AND TIME
OFF
PERMANENT HOLD
HOLD TEMPERATURE
VACATION HOLD
HOLD TEMPERATURE
SET DAY
SET MONTH
COPY FROM
VACATION HOLD
HOLD UNTIL DATE
SET HOUR
COPY TO
VACATION HOLD
HOLD UNTIL TIME
SET MINUTE
(Confirmation)
COPY PROGRAM
Figure 10. Controller Menu Structure: Main Screen
NOTE: Bold Font Indicates Menu or Screen Title Name
25
Page 26
ALTITUDE ADJUST
SET ALTITUDE
SETTINGS
INSTALLER
HEAT OFF DELAY
DEFROST CONFIG
RESTORE
DEFAULTS
SET HEAT OFF DELAY
DEFROST CONFIG
DEFR TERMINATION TEMP
COIL DEFROST DELTA T
RESTORE
DEFAULTS
SERVICE TESTS
CHARGE MODE
FURNACE TESTS
AIR COND RUN TESTS
DEALER INFORMATION
BRAND NAME
MODEL NUMBER
CONTRACTOR NAME
CHARGE MODE
HEAT PUMP RUN TESTS
DISCRETE OUTPUTS
CONTRACTOR PHONE
SELECT BRAND NAME
FURNACE TESTS
AIR COND RUN TESTS
MODEL NUMBER
CONTRACTOR NAME
CHANGE
AIR FILTER
HEAT PUMP RUN TESTS
CONTRACTOR PHONE
CHANGE
HUMIDIFIER
DISCRETE OUTPUTS
CHANGE
UV LAMP
CHANGE
AIR CLEANER
SERVICE AIR CLEANER
CUMULATIVE RUN TIME
CALENDAR TIME
SET CALENDAR TIME
SET CUMULATIVE RUN TIME
(TYPICAL FOR ALL 4 ACCESSORIES)
SERVICE TESTSDEALER
INFORMATION
ACCESSORIES
SYSTEM
CONFIGURATION
ACCESSORIES
AIR FILTER
HUMIDIFIER
UV LAMP
AIR CLEANER
OUTDOOR SYSTEM
HEAT PUMP-IQ
G7 FURNACE SYSTEMS
PANASONIC
BLOWER SYSTEMS
TWO STAGE
START DIFFERENTIAL
STAGE 1
STAGE 2
SINGLE STAGE
START DIFFERENTIAL
STAGE 1
SELECT GAS OR ELECTRIC HEAT
SELECT ONE OR TWO STAGES
GAS FURNACE
INPUT RATE
IQ MODULATING
GAS FURNACE
RISE
RISE
TWO STAGE
START DIFFERENTIAL
STAGE 1
STAGE 2
SINGLE STAGE
START DIFFERENTIAL
STAGE 1
GAS FURNACE
INPUT RATE
RISE
KW
ELECTRIC HEAT
Figure 11. Controller Menu Structure: Installer Settings
26
Page 27
Inverter LED
(to the left of blue
DIP switch block)
Figure 12. Inverter LED Location
(Behind Interface Board, to the left of
blue DIP switch block)
Communication
LED
DEF CCH YRV
Figure 13. Interface Board LED Locations
Power
LED
Figure 14. EXV Board Green LED Location
27
Page 28
Power
Plug
Red Power
LED
iQ Bus
Connection
Figure 15. iQ Control Board LED locations
INSTALLER: PLEASE LEAVE THESE
INSTRUCTIONS WITH THE OWNER.
iQ Comm
LED’s
Zone Network
LED’s
Specifi cations & illustrations subject to change without notice or incurring obligations.
O’ Fallon, MO | Printed in U.S.A. (09/10)
¢708921(¤
708921D (Replaces 708921C)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.