NEC Express5800-320Ma Installation Guide

Express5800/320Ma:
System Installation Guide
NEC Solutions (America), Inc. NR575-01
Notice
The information contained in this document is subject to change without notice.
UNLESS EXPRESSLY SET FORTH IN A WRITTEN AGREEMENT SIGNED BY AN AUTHORIZED REPRESENTATIVE OF NEC, NEC MAKES NO WARRANTY OR REPRESENTATION OF ANY KIND WITH RESPECT TO THE INFORMATION CONTAINED HEREIN, INCLUDING WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PURPOSE. NEC assumes no responsibility or obligation of any kind for any errors contained herein or in connection with the furnishing, performance, or use of this document.
Software described in NEC (a) is the property of NEC and/or its licensees, (b) is furnished only under license, and (c) may be copied or used only as expressly permitted under the terms of the license.
NEC documentation describes all supported features of the user interfaces and the application programming interfaces (API) developed by NEC and/or its licensees. Any undocumented features of these interfaces are intended solely for use by NEC personnel and are subject to change without warning.
This document is protected by copyright. All rights are reserved. No part of this document may be copied, reproduced, or translated, either mechanically or electronically, without the prior written consent of NEC Solutions (America), Inc.
Portions of this document are copyrights of Stratus Technologies and are reprinted here, under permission from Stratus
Technologies Bermuda, Ltd.
The NEC Solutions (America), Inc. logo, Express5800/320Ma, and the Express5800/320Ma logo, are trademarks of NEC Solutions (America), Inc. ActiveService Network is a trademark of Stratus Technologies Bermuda, Ltd. All other trademarks and trade names are the property of their respective owners.
Manual Name: Express5800/320Ma: System Installation Guide
Part Number: NR575-01 Express5800/320Ma Software Release Number: 4.1.0 Publication Date: January 2006
© 2006 NEC Solutions (America), Inc. All rights reserved.

Contents

Preface vii
1. Unpacking Your System 1-1
Checking the System Components 1-1 Inspecting the System 1-4 Verifying the System Serial Number 1-5 Safety Notices 1-5 Safety Considerations 1-6 Next Steps 1-6
2. Installing a Rack-Mountable System 2-1 Managing Cables 2-1 Installing a Rack-Mounted System 2-2
Numbering the Vertical Rails 2-2 Attaching Mounting Brackets to the Cabinet Vertical Rails 2-5 Installing the Shelf Unit 2-7
Installing the System Components 2-11
3. Installing a Pedestal System 3-1
4. Setting Up Your System 4-1
Ports on the System 4-1 Connecting a Monitor, Mouse, and Keyboard 4-3 Connecting the System to Ethernet Networks 4-4 Connecting the Modem 4-5 Connecting an External USB Floppy Disk Drive 4-6 Connecting the System to Electrical Power 4-6
System Power Overview 4-6 Connecting the System Directly to AC Power (Mains) 4-7 Connecting the System to a UPS 4-10
Contents iii
Contents
Connecting the Systems to Power Through PDUs 4-13
5. Installing PDUs 5-1 PDU Components 5-1 Installing a PDU in a Cabinet 5-2 Connecting PDUs to AC Power 5-3 Removing a PDU from a Cabinet 5-5
6. Installing Express5800/320Ma System Software 6-1 Overview of the IPL and Post-IPL Procedures 6-2 IPL Considerations 6-2 Mini-Setup Worksheet 6-3 Performing the IPL Procedure 6-5
Preparing for the IPL Procedure 6-6 Performing the IPL Procedure 6-6
The Post-IPL Procedure 6-9
Responding to Mini-Setup Prompts 6-9 Completing the Post-IPL Procedure 6-10
Appendix A. Ordering CRUs A-1
System CRUs A-2 Network Adapters A-3 Host Bus Adapters A-3 Peripheral Components A-3 KVM Switch and Cables A-3 System Power Cords A-4 PDU and PDU Power Cables A-4
Index Index-1
iv Express5800/320Ma: System Installation Guide

Figures

Figure 1-1. Rack-Mounted System Components 1-3 Figure 1-2. Pedestal System Components 1-4 Figure 2-1. EIA Square-Hole Pattern on the Vertical Rail 2-3 Figure 2-2. Numbering the Middle Hole of 4U 2-4 Figure 2-3. Screw Locations on the Rear Vertical Rails 2-5 Figure 2-4. Attaching the Mounting Brackets 2-6 Figure 2-5. Cage Nut Locations on Front Vertical Rails 2-7 Figure 2-6. Mounting the Shelf Unit on the Mounting Brackets 2-8 Figure 2-7. Securing the Shelf Unit to the Front Rails 2-9 Figure 2-8. Securing the Shelf Unit to the Mounting Brackets 2-10 Figure 2-9. Installing the Backplane Assembly on a Rack-Mounted
System 2-11
Figure 2-10. Installing the Modem Assembly on a Rack-Mounted
System 2-12 Figure 2-11. Installing the CPU-I/O Enclosures into a Cabinet 2-13 Figure 2-12. System in a Cabinet 2-14 Figure 3-1. Installing the Modem Assembly on a Pedestal System 3-2 Figure 3-2. Installing the CPU-I/O Enclosures into a Pedestal Case 3-3 Figure 3-3. CPU-I/O Enclosures Fully Inserted in a Pedestal Case 3-4 Figure 4-1. Ports on a Pedestal System 4-2 Figure 4-2. Ports on a Rack-Mountable System 4-3 Figure 4-3. Connecting a Rack-Mounted System Directly to AC Power 4-8 Figure 4-4. Connecting a Pedestal System Directly to AC Power 4-9 Figure 4-5. Connecting a Rack-Mounted System to a UPS 4-11 Figure 4-6. Connecting a Pedestal System to a UPS 4-12 Figure 4-7. Connecting the Systems to PDUs 4-14 Figure 5-1. PDU Components 5-2 Figure 5-2. Cage Nut Locations: PDU 5-3 Figure 5-3. Connecting a PDU to a UPS 5-4
Figures v

Tables

Table 6-1. Mini-Setup Worksheet 6-3 Table A-1. System CRUs A-2 Table A-2. Network Adapters and PCI Adapter Cables A-3 Table A-3. Host Bus Adapter Cables A-3 Table A-4. Peripheral Components A-3 Table A-5. KVM Switch CRUs A-3 Table A-6. System Power Cords A-4 Table A-7. Power Cords from a System to a UPS A-4 Table A-8. PDU and PDU Power Cords A-5 Table A-9. Storage Enclosure, Monitor, and Tape Drive Power Cords A-5
vi Express5800/320Ma: System Installation Guide
Purpose of This Manual
The Express5800/320Ma: System Installation Guide describes how to install and set up your system and power distribution units (PDUs). It also describes how to install Express5800/320Ma software and lists the part numbers of customer-replaceable units (CRUs), which are components that you can easily replace.
Audience
This manual is intended for system administrators who are responsible for installing Express5800/320Ma systems and optional components.
Notation Conventions
This document uses the notation conventions described in this section.
Warnings, Cautions, and Notes
Warnings, cautions, and notes provide special information and have the following meanings:

Preface

WARNING
!
A warning indicates a situation where failure to take or avoid a specified action could cause bodily harm or loss of life.
CAUTION
!
A caution indicates a situation where failure to take or avoid a specified action could damage a hardware device, program, system, or data.
NOTE
A note provides important information about the operation of an ftServer system.
Preface vii
Preface
Typographical Conventions
The following typographical conventions are used in Express5800/320Ma documents:
The bold font emphasizes words in text or indicates text that you type, the name of
a screen object, or the name of a programming element. For example:
Before handling or replacing a PCI adapter, make sure that you are properly grounded by using a grounded wrist strap.
In the System Properties dialog box, click the Hardware tab.
Call the RegisterDeviceNotification function.
The italic font introduces new terms and indicates programming and command-line
arguments that the user defines. For example:
Many hardware components are customer-replaceable units (CRUs), which can be replaced on-site by system administrators with minimal training or tools.
copy filename1 filename2
Pass a pointer for the NotificationFilter parameter
The monospace font indicates message text. For example:
The operation completed successfully.
Getting Help
If you have a technical question about Express5800/320Ma hardware or software, try these online resources first:
Online support from NEC Technical Support. You can find the latest technical
information about an Express5800/320Ma through online product support at the
NEC Technical Support Web site:
http://support.necsam.com/servers/
Online product support for Microsoft
support is the computer manufacturer who provided your software, or an authorized Microsoft Support Provider. You can also find the latest technical information about Microsoft Windows product support at the Microsoft Help and Support Web site:
http://support.microsoft.com/
If you are unable to resolve your questions with the help available at these online sites, and the Express5800/320Ma system is covered by a service agreement, please contact NEC Technical Support (866-269-1239).
viii Express5800/320Ma: System Installation Guide
®
products. Your primary source for
®
and other Microsoft products through online
Notices
Preface
All regulatory notices are provided in the site planning guide for your system.
Although this guide documents modem functionality, modems are not available for
all systems. Ask your sales representative about modem availability.
ActiveService Network (ASN) is not currently available, but may be ordered in the
future.
Preface ix
Preface
x Express5800/320Ma: System Installation Guide
Chapter 1
When you receive your system, unpack it as described in the Readme First booklet that accompanies the system.
After you unpack the system, do the following:
Make sure you have the components you require and have ordered.
Inspect the system to make sure nothing was damaged during shipment.
Verify that the system serial number on the system label and on the packing list
match.
Make sure you understand safety considerations.

Checking the System Components

Refer to the packing list on the box and make sure you have all the ordered components:
Accessories box, containing one or more of the following:
– One gray and one black power cable for connecting the system to power
distribution units (PDUs)

Unpacking Your System

1-
– CD-ROMs and a printed copy of this guide.
Keyboard and mouse
Installed Virtual Technician Module (VTM), if ordered
Unpacking Your System 1-1
Checking the System Components
The following, if ordered:
–– Monitor unit
– External USB floppy disk drive
– PDUs for rack-mounted systems
– Keyboard, video, and mouse (KVM) switch
For a rack-mounted system, the components shown in Figure 1-1 and, for a
pedestal system, the components shown in Figure 1-2.
NOTE
If you received the system already mounted in a cabinet, the components shown in Figure 1-1 have been assembled in the cabinet, with the exception of the power cords.
1-2 Express5800/320Ma: System Installation Guide
Figure 1-1. Rack-Mounted System Components
Checking the System Components
3
4
5
2
6
7
1
9
10
asys012
1 Shelf unit (1)
2 Rear mounting brackets (2), with one guide screw in each bracket
3 Power cords
4 10-32 cage nuts (8)
5 10-32 x 5/8 in. pan-head crest-cup Phillips-head screws (4)
6 10-32 x 1/2 in. pan-head crest-cup Phillips-head screws (8). Two screws are
installed, one in each rear mounting bracket.
7 10-32 x 1/2 in. counter-sunk screws with lock washers (4)
8 Backplane assembly (1)
9CPU-I⁄ O enclosures (2)
10 Front bezel (1)
8
Unpacking Your System 1-3

Inspecting the System

Figure 1-2. Pedestal System Components
2
1
3
4
asys013
1 Pedestal case
2 Power cords
3CPU-I⁄ O enclosures (2)
4Front bezel (1)
Inspecting the System
Inspect all equipment for damage. Verify that the equipment has no dents, scratches, or scrapes. If you notice damage, contact NEC Technical Support.
1-4 Express5800/320Ma: System Installation Guide

Verifying the System Serial Number

Ensure that the serial numbers on the system and on the packing list match.
1. Find the label that contains the serial number and site ID affixed to the bottom rear of the shelf unit.
2. Compare the serial number on the label with the serial number on the packing list.
If the serial numbers do not match, contact NEC Technical Support before installing the system.

Safety Notices

WARNING
!
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS PROVIDED WITH THE BATTERY.
WARNING
!
If you receive locking power cords with your system, do not substitute other power cords. Use of the locking power cords ensures proper grounding of the system.
Verifying the System Serial Number
WARNING
!
The system uses two power cords to provide redundant sources of power. To fully remove power from a system, disconnect both power cords. To reduce the risk that electrical shock could injure a person or damage the system, exercise caution when working in the unit even when only one power cord is connected.
WARNING
!
To prevent a cabinet from tipping over and injuring a person or damaging the system, start installing systems from the bottom of the cabinet upward.
Unpacking Your System 1-5

Safety Considerations

WARNING
!
If you replace the modem cable supplied by NEC Solutions (America), Inc., use a cable with a gauge of at least 26 AWG to prevent fire.
Safety Considerations
Before installing the system, take the following important precautions:
Observe all applicable industry safety standards. See the “Safety Notices” on
page 1-5.
Provide the necessary space and light to safely perform the installation.
Do not wear conducting objects, such as rings, bracelets, and keys.

Next Steps

Go to Chapter 2, “Installing a Rack-Mountable System” to install a rack-mountable system in your own cabinet.
Go to Chapter 3, “Installing a Pedestal System” to install a pedestal system,
Go to Chapter 4, “Setting Up Your System” to set up a system that is already mounted in a cabinet.
1-6 Express5800/320Ma: System Installation Guide
Chapter 2

Installing a Rack-Mountable System

Before you install the system, make sure that the site has been prepared as described in the Express5800/320Ma: Site Planning Guide.
To install your rack-mountable system, see:
Figure 1-2, which identifies the components of a rack-mountable system
“Safety Notices” on page 1-5 and “Safety Considerations” on page 1-6
“Managing Cables” on page 2-1
“Installing a Rack-Mounted System” on page 2-2
“Installing the System Components” on page 2-11
Tools required:
A #2 Phillips-head screwdriver
A flat-head screwdriver or a cage-nut insertion and extraction tool
2-

Managing Cables

When routing cables within the cabinet, keep all power cords separate from peripheral and communication cables as much as possible. For example, route all power cords on one side of the cabinet and all peripheral and communications cables on the other side of the cabinet, using the cable management rings on your cabinet to constrain the cords and cables.
Installing a Rack-Mountable System 2-1

Installing a Rack-Mounted System

Installing a Rack-Mounted System
Before installing the system, ensure that:
Your cabinet (if you are installing the system in your own cabinet) meets the
requirements described in the Express5800/320Ma: Site Planning Guide.
The site has been prepared as described in the Express5800/320Ma: Site
Planning Guide.
If you are using power distribution units (PDUs), install them in your cabinet as described in Chapter 5, “Installing PDUs” before you install the system.
A rack-mounted system consists of the components shown in Figure 1-2.
To install a rack-mounted system, see the following sections:
“Numbering the Vertical Rails” on page 2-2
“Attaching Mounting Brackets to the Cabinet Vertical Rails” on page 2-5
“Installing the Shelf Unit” on page 2-7

Numbering the Vertical Rails

Each system requires 4U, equal to 12 holes, of vertical space.
NOTE
The cabinet rails and the system are measured in EIA rack units (U). One U equals 1.75 in. (4.45 cm).
Every three square holes on the EIA square-hole pattern on the vertical rail equals one U. The square holes on EIA rails are located in a repeating pattern of 1/2 in. (1.27 cm), 5/8 in. (1.59 cm), 5/8 in. (1.59 cm), as shown in
Figure 2-1.
The middle hole of each U has equal spacing between it and the holes adjacent to it. In some cabinets, numbers on the vertical rails identify the middle hole of each U.
2-2 Express5800/320Ma: System Installation Guide
Figure 2-1. EIA Square-Hole Pattern on the Vertical Rail
1U
Installing a Rack-Mounted System
1U
5/8 in. (1.59 cm)
5/8 in. (1.59 cm)
1/2 in. (1.27 cm)
If your rack is not already numbered, use a marker or pencil to number the middle hole of at least the following:
The 4U in which to install each system
The 1U in which to install a keyboard, video, and mouse (KVM) switch, if ordered
The following instructions direct you to start numbering the middle hole of the third U in the cabinet, which is the eighth hole, to leave room at the bottom of the cabinet for the PDUs.
To number the vertical rails in a cabinet
1. On each of the front rails, number the middle hole of the 4U where you will install the system. In Figure 2-2, the middle hole of the third, fourth, fifth, and sixth Us are numbered.
Installing a Rack-Mountable System 2-3
Installing a Rack-Mounted System
Figure 2-2. Numbering the Middle Hole of 4U
6
5
4
3
2. If you are installing additional systems in the same cabinet, continue numbering the middle hole of another 4U for each system.
3. Repeat the preceding steps at the rear vertical rails.
To ensure that the components will be level when you install them, mark the same holes on the rear rails that you marked on the front vertical rails.
2-4 Express5800/320Ma: System Installation Guide
Installing a Rack-Mounted System

Attaching Mounting Brackets to the Cabinet Vertical Rails

Two mounting brackets, one on each rear vertical rail, support the shelf unit.
To attach the mounting brackets
1. On the rear vertical rails, use a pen to mark the holes indicated by dots in
Figure 2-3.
Figure 2-3. Screw Locations on the Rear Vertical Rails
6
5
4
3
2. Position a mounting bracket inside a rear vertical rail, lining up the holes in the mounting bracket with the two holes you marked on the rear vertical rail. See
Figure 2-4.
3. Insert and tighten two 10-32 x 5/8-in. pan-head crest-cup screws (item 1 in
Figure 2-4) through the marked holes in the rear vertical rails and into the holes in
the mounting bracket.
4. Repeat steps 2 and 3 for the second mounting bracket.
Installing a Rack-Mountable System 2-5
Installing a Rack-Mounted System
Figure 2-4. Attaching the Mounting Brackets
3
2
1
asys014
1 10-32 x 5/8-in. pan-head crest-cup screw
2 Right guide screw, 10-32 x 1/2-in. pan-head crest-cup
3 Left guide screw, 10-32 x 1/2-in. pan-head crest-cup
5. Measure the distance between the front and rear vertical rails in the cabinet.
NOTE
Left and right in the following instructions are as seen from the rear of the cabinet.
If the rail depth is less than 27 in. (68.58 cm), move the guide screw (item 2 in
Figure 2-4) in the right mounting bracket one hole closer to the rear of the
cabinet.
If the rail depth is greater than 27 in. (68.58 cm), move the guide screw (item 3)
in the left mounting bracket one hole closer to the front of the cabinet.
2-6 Express5800/320Ma: System Installation Guide

Installing the Shelf Unit

WARNING
!
To avoid personal injury or damage to the shelf unit, two persons are required to insert the shelf unit into the cabinet and onto the mounting brackets.
1. At the front of the cabinet, insert four cage nuts into each vertical rail, in the locations shown in Figure 2-5.
Figure 2-5. Cage Nut Locations on Front Vertical Rails
Installing a Rack-Mounted System
6
5
4
3
2
1
ca
ge n
cage
c
age
ca
g
e n
u
t
nut
n
ut
ut
To insert cage nuts, refer to Figure 2-5 and perform the following steps:
a. Position the cage nut so that the flanges are on the top and bottom. b. Insert the cage nut so that the top flange overlaps the vertical rail. c. Use a cage-nut insertion tool or your fingers to pull the rest of the cage nut
through so that the bottom flange overlaps the vertical rail.
Installing a Rack-Mountable System 2-7
Installing a Rack-Mounted System
2. With two people, one positioned at the front of the cabinet and one positioned at the rear of the cabinet, insert the shelf unit into the cabinet and onto the mounting brackets.
a. At the front of the cabinet, slide the shelf unit into the cabinet. b. At the rear of the cabinet, flex the right mounting bracket towards the side of
the cabinet and guide the shelf unit so that the guide slot at the top right of the shelf unit (item 1 in Figure 2-6) aligns with the guide screw (item 2) on your right.
c. At the rear of the cabinet, flex the left mounting bracket towards the side of the
cabinet and guide the shelf unit so that the guide slot at the top left of the shelf unit (item 1) aligns with the guide screw (item 2) on your left.
Figure 2-6. Mounting the Shelf Unit on the Mounting Brackets
1
2
1
2
2
Rear
1
Front
1 Guide slots
2 Guide screws
2-8 Express5800/320Ma: System Installation Guide
asys018
Installing a Rack-Mounted System
3. At the front of the cabinet, slide the shelf unit all the way in.
4. In the locations shown in Figure 2-7, secure the shelf unit to the vertical rails by inserting and tightening two 10-32 x 1/2-in. counter-sunk screws and lock washers into each mounting flange on the shelf unit and into the cage nuts behind them.
Figure 2-7. Securing the Shelf Unit to the Front Rails
2
1
asys019
1 10-32 x 1/2-in. counter-sunk screws with lock washers
2 Mounting flange
Installing a Rack-Mountable System 2-9
Installing a Rack-Mounted System
5. Secure each side of the shelf unit to a rear mounting bracket with four 10-32 x 1/2-in. screws on each side, including the guide screws, as shown in
Figure 2-8.
Tighten all eight screws.
Figure 2-8. Securing the Shelf Unit to the Mounting Brackets
1
2
asys020
1 Mounting bracket
2 10-32 x 1/2 in. pan-head crest-cup screws with washers
2-10 Express5800/320Ma: System Installation Guide

Installing the System Components

1. Install the backplane assembly.
a. At the rear of the system, install the backplane assembly (item 2 in Figure 2-9),
inserting the thumbscrews (item 1) into the screw holes as shown in
Figure 2-9.
b. Slide the backplane assembly slightly to the right and secure it in place by
tightening the thumbscrews.
Figure 2-9. Installing the Backplane Assembly on a Rack-Mounted System
Installing the System Components
1
2
1
asys022c
1Thumbscrews
2 Backplane assembly
Installing a Rack-Mountable System 2-11
Installing the System Components
2. If ordered, install the modem assembly.
CAUTION
!
Make sure that the system is powered off. You can install the modem if the system is turned off and no power cords are connected to the system. If you must install the modem assembly while the system is in operation, see the Express5800/320Ma: Operation and Maintenance Guide.
a. At the rear of the system, remove the metal plate from the backplane. b. Insert the modem assembly into its slot on the backplane, as shown in
Figure 2-10.
c. Secure the modem assembly in place by tightening the thumbscrews.
Figure 2-10. Installing the Modem Assembly on a Rack-Mounted System
1
2
1
asys054a
1 Thumbscrews
2 Modem assembly
2-12 Express5800/320Ma: System Installation Guide
Installing the System Components
3. Install the CPU- I ⁄ O enclosures.
a. Place each CPU- I O enclosure on a flat surface and turn the two
thumbscrews (item 1 in Figure 2-11) counterclockwise to loosen them and pull the two ejector levers down (item 2).
b. Slide each CPU- I O enclosure into a shelf and, with the ejector levers in the
open position, slide the CPU-I O enclosure all the way into its opening.
WARNING
!
Lifting an enclosure requires two people.
Figure 2-11. Installing the CPU-I/O Enclosures into a Cabinet
1
1
2
2
1 Thumbscrew
2 Ejector lever
Installing a Rack-Mountable System 2-13
asys021a
Installing the System Components
c. Push the ejector levers up into the closed position and tighten the thumbscrews
so that the system is installed in the rack as shown in Figure 2-12.
Figure 2-12. System in a Cabinet
4. Attach the bezel.
a. Standing in front of the system, position the bezel so that the LED light
extensions that are inside the bezel are on the left.
b. Press the bezel towards the mounting rails until the bezel snaps into place.
asys024a
2-14 Express5800/320Ma: System Installation Guide
Chapter 3

Installing a Pedestal System

Before you install the system, make sure that the site has been prepared as described in the Express5800/320Ma: Site Planning Guide
To install your pedestal system, see Figure 1-2, which identifies the components of a pedestal system, “Safety Notices” on page 1-5, and “Safety Considerations” on
page 1-6.
Tools required: None
To install the system in a pedestal case
1. Install the modem assembly.
CAUTION
!
Make sure that the modem is powered off. You can install the modem assembly if the system is turned off and no power cords are connected to the system. If you must install the modem assembly while the system is in operation, see the Express5800/320Ma: Operation and Maintenance Guide.
3-
a. At the rear of the system, remove the metal plate from the backplane. b. Insert the modem assembly into its slot on the backplane, as shown in
Figure 3-1.
c. Secure the modem assembly in place by tightening the thumbscrew.
Installing a Pedestal System 3-1
Installing a Pedestal System
Figure 3-1. Installing the Modem Assembly on a Pedestal System
asys056
2. Install the CPU- I ⁄ Oenclosures.
a. Place each CPU- I O enclosure on a flat surface and turn the two
thumbscrews (item 1 in Figure 3-2) counterclockwise to loosen them. Pull the two ejector levers down (item 2).
WARNING
!
Lifting the enclosure requires two people.
b. Slide each CPU- I O enclosure into a shelf and, with the ejector levers in the
open position, slide the CPU-I O enclosure all the way into its opening.
3-2 Express5800/320Ma: System Installation Guide
Installing a Pedestal System
Figure 3-2. Installing the CPU-I/O Enclosures into a Pedestal Case
A
1
1
2
2
asys021a
1 Thumbscrew
2 Ejector lever
Installing a Pedestal System 3-3
Installing a Pedestal System
c. Push the ejector levers into the closed position and tighten the thumbscrews
so that the system is installed in the case as shown in Figure 3-3.
Figure 3-3. CPU-I/O Enclosures Fully Inserted in a Pedestal Case
asys26
3. Attach the bezel.
a. Standing in front of the system, position the bezel so that the LED light
extensions that are inside the bezel are on the bottom.
b. Press the bezel towards the mounting rails until the bezel snaps into place.
3-4 Express5800/320Ma: System Installation Guide
Chapter 4
To set up your system, see:
“Ports on the System” on page 4-1
“Connecting a Monitor, Mouse, and Keyboard” on page 4-3
“Connecting the System to Ethernet Networks” on page 4-4
“Connecting the Modem” on page 4-5
“Connecting an External USB Floppy Disk Drive” on page 4-6
“Connecting the System to Electrical Power” on page 4-6

Ports on the System

The ports are located at the rear of the system, as shown in Figures 4-1and 4-2. Refer to these illustrations as you connect cables and power cords to the system.
Your system may contain PCI adapters that require cables. Your system contains a half-height PCI adapter slot in each CPU-I O enclosure. In addition, the system may contain two full-height PCI adapter slots (expansion slots).

Setting Up Your System

4-
Figure 4-1 shows the rear of a pedestal system that contains PCI adapters in the
half-height PCI adapter slots.
Figure 4-2 shows a rack-mounted system that contains PCI adapters in the standard
half-height slots and in each expansion PCI adapter slot.
When you receive your system from the manufacturer, PCI adapters that were ordered at the same time the system was ordered are installed. If you need to install PCI adapters in the system, see the Express5800/320Ma: PCI Adapter Guide and the Express5800/320Ma: Operation and Maintenance Guide.
Setting Up Your System 4-1
Ports on the System
Figure 4-1. Ports on a Pedestal System
1
2
3
4
5
6
7
asys007
1 Ports on PCI adapters in slot 1
2 System 10/100/1000-Mbps Ethernet ports (4)
3 USB ports (3)
4 VGA (monitor) port
5 Serial (COM) ports (2)
6 Power receptacles (2)
7 VTM 10/100-Mbps Ethernet ports (2)
4-2 Express5800/320Ma: System Installation Guide
Figure 4-2. Ports on a Rack-Mountable System

Connecting a Monitor, Mouse, and Keyboard

2
1
1 Ports on PCI adapters in PCI expansion slot 3
2 Ports on PCI adapters in PCI expansion slot 2
3 Ports on PCI adapters in PCI slot 1
4 System 10/100/1000-Mbps Ethernet ports (4)
5 USB ports (3)
6 VGA (monitor) port
7 Serial (COM) ports (2)
8 Power receptacles (2)
9 VTM 10/100-Mbps Ethernet ports (2)
10 RJ-11 port on modem
3
54
67
9
8
asys011
Connecting a Monitor, Mouse, and Keyboard
To connect a generic monitor and the V115 mouse and keyboard to the system, see
“Connecting a Generic Monitor” on page 4-3.

Connecting a Generic Monitor

1. Connect the USB cable from the mouse to the USB port located at the back of the keyboard.
NOTE
Remove the green USB-to-PS2 converter on the USB cable from the mouse supplied by NEC Solutions (America), Inc.
Setting Up Your System 4-3

Connecting the System to Ethernet Networks

2. Connect the USB cable from the keyboard to one of the system’s USB ports. The system’s USB ports are interchangeable. Item 3 in Figure 4-1 and item 5 in
Figure 4-2 shows the USB ports on the system.
3. Connect the 15 pin D-sub connector on the VGA cable from the monitor to the system’s VGA port. Item 4 in Figure 4-1 and item 6 in Figure 4-2 shows the VGA ports on the system.
4. Connect the VGA cable to the monitor.
Connecting the System to Ethernet Networks
1. Connect the ports for the embedded Ethernet controllers to the network. Provide an unshielded twisted pair (UTP) cable with RJ-45 connectors for each of the four system Ethernet ports you plan to use. Connect one end of each cable to a network port on the system and the other end to an Ethernet wall jack or switch. Item 3 in
Figure 4-1 and item 5 in Figure 4-2 shows the USB ports on the systems.
2. Connect the VTMs, if present, to a maintenance or other network. You need two UTP cables with RJ-45 connectors. Connect one end of each cable to a VTM network port. Attach the other end of each cable to an Ethernet wall jack or a switch. Item 8 in Figure 4-1 and item 9 in Figure 4-2 shows the VTM ports on the system.
4-4 Express5800/320Ma: System Installation Guide

Connecting the Modem

3. If the system contains Ethernet adapters in PCI slots, connect them to a network.
For ports on copper gigabit Ethernet adapters, use UTP cables with RJ-45
connectors.
For ports on fiber gigabit Ethernet adapters, use multimode 62.5- or 50-micron,
DUAL fiber cable with LC-type connectors to the PCI adapter, and connectors on the other end that are compatible with the network switch.
NOTES
1. If you are installing the adapters, install them in pairs, one in the same slot in each CPU- I ⁄ O enclosure.
2. Add cables in pairs, a cable connected to the same port in the same slot in each CPU- I O enclosure. If you are using a single pair of ports, attach cables to the top port(s) of each card and attach both cables to the same network.
3. The top connector of a port on a U574 Dual-Port Fiber Gigabit Ethernet Adapter is the transmit port.
For example, in Figure 4-2, U575 Dual-Port Copper Gigabit Ethernet Adapters are shown in slots 2 and 3 in both CPU-I ⁄ O enclosures.
See the Express5800/320Ma: PCI Adapter Guide for further information.
After you connect the cables and when the system is running, use PROSet to configure Ethernet ports into teams. For more information about teaming Ethernet ports, see the Express5800/320Ma: PCI Adapter Guide.
Connecting the Modem
1. Connect the modem cable to the RJ-11 line jack on the modem, item 6 in
Figure 4-1 and item 10 in Figure 4-2.
2. If necessary, attach a Telco adapter to the modem cable.
3. Connect the modem cable to a telephone jack.
Setting Up Your System 4-5

Connecting an External USB Floppy Disk Drive

Connecting an External USB Floppy Disk Drive
Use the USB extension cable to connect an optional USB floppy disk drive to a USB port on the system as follows:
1. Connect the USB extension cable to the cable on the floppy disk drive.
2. Connect the USB extension cable to one of the system USB ports. Item 3 in
Figure 4-1 and item 5 in Figure 4-2 show the USB ports on the system.
NOTES
1. Software generally assigns the letter A to the optional floppy disk drive when it is first connected to a USB port. If you subsequently connect the drive to a different USB port or if the system fails over, software may assign the letter B to the disk drive.
2. Do not connect the floppy disk drive to the USB hub on the keyboard. The keyboard does not supply the power required by the floppy disk drive.

Connecting the System to Electrical Power

This section describes how to connect both the rack-mounted and pedestal systems to electrical power.
“System Power Overview” on page 4-6
“Connecting the System Directly to AC Power (Mains)” on page 4-7
“Connecting the System to a UPS” on page 4-10
“Connecting the Systems to Power Through PDUs” on page 4-13

System Power Overview

Your system requires at least two separate and independent AC power outlets, an A-side power source and a B-side power source. Either source must be capable of continuing to provide power if power to the other source is lost.
The A-side power source provides power to the top CPU0I/O enclosure and a keyboard-video-mouse (KVM) switch. If you use a UPS, the UPS is the A-side power source.
The B-side power source provides power to the bottom CPU- I ⁄ Oenclosure.
A pair of PDUs supplies power to multiple systems and components in a cabinet. The top PDU in the cabinet provides A-side power. The bottom PDU in the cabinet provides
4-6 Express5800/320Ma: System Installation Guide
Connecting the System to Electrical Power
B-side power. See Chapter 5, “Installing PDUs” for more information about installing PDUs and using them with your system.
WARNING
!
Use only the power cords or cables you receive from NEC Solutions (America), Inc.
DO NOT MODIFY THE POWER CORDS OR CABLES you receive with your system.
Failure to comply with this warning will void agency certification.
Failure to comply with this warning can cause a fire hazard.
When routing cables within a cabinet, keep power cords separate from peripheral and communications cables as much as possible. For example, route all power cords on one side of the cabinet and all peripheral and communications cables on the other side of the cabinet, using the cable management rings on your cabinet to constrain the cords and cables.
To configure the system to communicate with a UPS in the case of a power outage, see the Express5800/320Ma: Software Installation and Configuration Guide.

Connecting the System Directly to AC Power (Mains)

1. Locate two black power cords and two labels, A and B.
2. Attach an A label to one power cord. Connect the power cord according to the system you have:
Rack-mounted system: Connect the female end to the receptacle on the top
CPU- I O enclosure. Connect the other end to a power source.
Pedestal system: Connect the female end to the receptacle on the right
CPU- I O enclosure. Connect the other end to a power source.
CAUTION
!
Make sure the power interlock mechanism is unlocked when you insert the power cord. On rack-mounted systems, the unlocked position is vertical and on pedestal systems the unlocked position is horizontal. In Figure 4-1 and in Figure 4-2, the interlock mechanism, located beneath the power connector, is shown in the unlocked
Setting Up Your System 4-7
Connecting the System to Electrical Power
position. In Figure 4-3 and in Figure 4-4, the interlock mechanism is shown in the locked position.
3. Attach a B label to the second power cord. Connect the power cord according to the system you have:
Rack-mounted system: Connect the female end to the receptacle on the
bottom CPU- I ⁄ O enclosure. Connect the other end to a second, separate, power source.
Pedestal system: Connect the female end to the receptacle on the left
CPU- I O enclosure. Connect the other end to a second, separate, power source.
4. From the front of the system, make sure that the CPU- IO enclosures are fully inserted in the shelf unit by tightening, if necessary, the thumbscrews. Then, at the rear of the system, turn the power interlock mechanisms into the locked position.
Figure 4-3 shows where the two power cords (not color coded) connect to a
rack-mounted system.
Figure 4-3. Connecting a Rack-Mounted System Directly to AC Power
2
1
3
1 B-side power cord
2 A-side power cord
3 AC power outlets
4 AC power (mains) distribution circuit breakers (maximum of 20A)
4
4
3
asys001
Figure 4-4 shows where the two black power cords connect to a pedestal system.
4-8 Express5800/320Ma: System Installation Guide
Connecting the System to Electrical Power
Figure 4-4. Connecting a Pedestal System Directly to AC Power
4
3
4
3
1
2
1 A-side power cord
2 B-side power cord
3 AC power outlets
4 AC power (mains) distribution circuit breakers (maximum of 20A)
asys002
Setting Up Your System 4-9
Connecting the System to Electrical Power

Connecting the System to a UPS

1. Locate two black power cords and two labels, A and B.
2. Attach an A label to one power cord. Connect the power cord according to the system you have:
Rack-mounted system: Connect one end of the cable to the receptacle on the
top CPU- I O enclosure. Connect the other, country-specific, end to the UPS.
Pedestal system: Connect end of the cable to the receptacle on the right
CPU- I O enclosure. Connect the other, country-specific, end to the UPS.
CAUTION
!
Make sure the power interlock mechanism is unlocked when you insert the power cord. On rack-mounted systems, the unlocked position is vertical and on pedestal systems the unlocked position is horizontal. In Figure 4-1 and in Figure 4-2, the interlock mechanism, located beneath the power connector, is shown in the unlocked position. In Figure 4-3 and in Figure 4-4, the interlock mechanism is shown in the locked position.
3. Attach a B label to the second power cord. Connect the power cord according to the system you have:
Rack-mounted system: Connect one end of the cable to the receptacle on the
top CPU- I ⁄ O enclosure. Connect the other end to a second, separate, power source.
Pedestal system: Connect end of the cable to the receptacle on the left
CPU- I O enclosure. Connect the other end to a second, separate, power source.
4. From the front of the system, make sure that the CPU- IO enclosures are fully inserted in the shelf unit by tightening, if necessary, the thumbscrews. Then, at the rear of the system, turn the power interlock mechanisms into the locked position.
To configure the system to communicate with a UPS in the case of a power outage, see the Express5800/320Ma: Software Installation and Configuration Guide.
4-10 Express5800/320Ma: System Installation Guide
Connecting the System to Electrical Power
Figure 4-5 shows how the rack-mounted system connects to power through a UPS.
Figure 4-5. Connecting a Rack-Mounted System to a UPS
1 B-side power cord
2 A-side power cord
3UPS
4 UPS power cord
5 AC power outlets
6 AC power (mains) distribution circuit breakers
(maximum of 20A)
6
5
6
5
1
4
2
3
asys004
Figure 4-6 shows how the pedestal system connects to power through a UPS.
Setting Up Your System 4-11
Connecting the System to Electrical Power
Figure 4-6. Connecting a Pedestal System to a UPS
6
5
6
1
5
4
2
3
1 B-side power cord
2 A-side power cord
3UPS
4 UPS power cord
5 AC power source
6 AC power (mains) distribution circuit breakers
(maximum of 20A)
asys005
4-12 Express5800/320Ma: System Installation Guide
Connecting the System to Electrical Power

Connecting the Systems to Power Through PDUs

1. Locate one black and one gray power cable (jumper).
2. Connect oneend of each gray cable to the receptacle on the top CPU- I O enclosure. Connect the other end of each gray cable to the top PDU.
CAUTION
!
Make sure the power interlock mechanism is unlocked when you insert the power cord. On rack-mounted systems, the unlocked position is vertical and on pedestal systems the unlocked position is horizontal. In Figure 4-1 and in Figure 4-2, the interlock mechanism, located beneath the power connector, is shown in the unlocked position. In Figure 4-3 and in Figure 4-4, the interlock mechanism is shown in the locked position.
3. Connect the end of each black cable to the receptacle on the left CPU- I O enclosure. Connect the other end of each black cable to the bottom PDU.
4. From the front of the system, make sure that the CPU- IO enclosures are fully inserted in the shelf unit by tightening, if necessary, the thumbscrews. Then, at the rear of the system, turn the power interlock mechanisms into the locked position.
See Chapter 5, “Installing PDUs” for more information about the PDUs.
Setting Up Your System 4-13
Connecting the System to Electrical Power
Figure 4-7 shows the color-coded power cables connected to the systems and PDUs.
Figure 4-7. Connecting the Systems to PDUs
3
3
1
2
4
9 9
8 8
7
4
5
6
5
asys003
1 A-side PDU
2 B-side PDU
3 B-side system power cables (black)
4 A-side system power cables (gray)
5 PDU power cords
6UPS
7 UPS power cord
8 AC power outlets
9 AC power (mains) distribution circuit
breaker (maximum of 20A)
See Chapter 6, “Installing Express5800/320Ma System Software” before you turn on the system.
4-14 Express5800/320Ma: System Installation Guide
Chapter 5
To install PDUs, see:
“PDU Components” on page 5-1
“Installing a PDU in a Cabinet” on page 5-2
“Connecting PDUs to AC Power” on page 5-3
“Removing a PDU from a Cabinet” on page 5-5
Tool required: #2 Phillips-head screwdriver.

PDU Components

The power distribution units (PDU) should be ordered in pairs. When each PDU is shipped, mounting brackets are attached to the PUU to form one unit.
Verify that you have the components shown in Figure 5-1, and inspect them to ensure that they are not damaged. If you notice damage, contact NEC Technical Support.

Installing PDUs

5-
Installing PDUs 5-1

Installing a PDU in a Cabinet

Figure 5-1. PDU Components
6
5
1
4
1 PDU
2 Mounting brackets
3 Power cables (one black and one gray) which accompany the system
4Power cord
5 10-32 cage nuts (4)
6 10-32 pan-head screws with captive external tooth washers (4)
Installing a PDU in a Cabinet
You can install one or two pairs of PDUs in a cabinet, for a total of four PDUs. Install the first pair of PDUs in the bottom two contiguous one-U locations of the cabinet, and the second pair in two convenient, contiguous one-U locations in the middle of the cabinet.
For each pair of PDUs, the PDU in the top U provides A-side power. That is, the PDU in the top location powers one CPU-I O enclosure, and is the only source of power to KVM switches. The PDU in the bottom location provides B-side power. That is, the PDU in the bottom U provides power to the other CPU-I O enclosure and to the other side of an external storage enclosure.
2
3
ssys110
Removable fasteners attach two reversible mounting brackets to the body of the PDU. Eight mounting holes on the PDU let you adjust the bracket.
5-2 Express5800/320Ma: System Installation Guide

Connecting PDUs to AC Power

To install a PDU
1. For each PDU, insert four cage nuts in the rear vertical cabinet rails. Insert two cage nuts in each rear rail, in the top and bottom holes of U positions 1 and 2. The locations in which to install the cage nuts for two PDUs are indicated in Figure 5-2. For detailed information about installing cage nuts, see “Installing the Shelf Unit”
on page 2-7.
Figure 5-2. Cage Nut Locations: PDU
cage nut
2
ca
g
e
1
ca
ca
n
u
t
g
e
n
u
t
g
e
n
u
t
2. Hold the PDU at the back of the cabinet, so that the power outlets and controls face you, and the blank side of the PDU faces the inside of the cabinet.
3. Align the screw holes on the mounting brackets with the top and bottom holes of the U with cage nuts, as follows:
a. Align the first PDU with the U numbered 1 (the bottom U). b. Align the second PDU with the U numbered 2 (the second U from the bottom).
4. Attach the PDU with four 10-32 screws with one hand while supporting the PDU with the other.
5. Tighten the screws.
Connecting PDUs to AC Power
At the back of the cabinet, attach a connector end of the country-specific external power cable to the single PDU inlet connector on the right. Connect the country-specific connector end to a power source.
CAUTION
!
Connect each PDU to a separate power source.
To connect the PDU to the system, see “Connecting the Systems to Power Through
PDUs” on page 4-13.
Installing PDUs 5-3
Connecting PDUs to AC Power
Figure 5-3 shows how to connect PDUs to power sources when one source is a UPS.
Figure 5-3. Connecting a PDU to a UPS
3
1
2
4
1 A-side PDU
2 B-side PDU
3 Power cord for top PDU
4 Power cord for bottom PDU
5UPS
6 UPS power cord
7 AC power sources
8 AC power (mains) distribution circuit breakers
(maximum of 20A)
8
7
8
7
5
6
s4u092b
5-4 Express5800/320Ma: System Installation Guide

Removing a PDU from a Cabinet

CAUTION
!
If you are removing both PDUs that provide power to the same components, turn off the system components.
1. Remove the system from service. Use one of the following procedures:
Click Start and select Shut Down.
Press the power button once, if you have enabled Allow system to be
shutdown without having to logon enabled. See the Express5800/320Ma: System Administrator’s Guide.
2. Remove the power cables from the PDU.
3. Remove the four screws with one hand while supporting the PDU with the other hand.
4. Slide the PDU out of the cabinet and place the PDU in a safe place.
Removing a PDU from a Cabinet
Installing PDUs 5-5
Removing a PDU from a Cabinet
5-6 Express5800/320Ma: System Installation Guide
Chapter 6
Installing Express5800/320Ma
System Software
If the operating system has been installed by the manufacturer, a Microsoft Certificate of Authenticity is placed on the system equipment label at the rear of the system. In this case, supply the information in Ta b l e 6 - 1 and perform only the procedure described in
“The Post-IPL Procedure” on page 6-9.
If the operating system has not been installed by the manufacturer, review the information in “Overview of the IPL and Post-IPL Procedures” on page 6-2 and “IPL
Considerations” on page 6-2, supply the information in Ta b le 6- 1 , and perform the
procedure described in “Performing the IPL Procedure” on page 6-6, followed by the post-IPL procedure.
NOTES
1. The IPL procedure allows you to perform a single IPL and then duplicate the system disk for bulk deployment. If you are using a duplicate system disk, perform only the post-IPL procedure described in
“The Post-IPL Procedure” on page 6-9.
6-
2. Software installation services are available. Contact NEC Technical Support for details.

Installing Express5800/320Ma System Software 6-1

Overview of the IPL and Post-IPL Procedures

Overview of the IPL and Post-IPL Procedures
The IPL procedure installs the following:
Microsoft Windows Server 2003
On Express5800/320Ma systems, Windows Server 2003 Enterprise Edition and Service Pack 1 is installed and supported.
Express5800/320Ma, including ftServer drivers, ftServer Manager, and
Express5800/320Ma Software Availability Manager (SAM)
Java™ Runtime Environment (JRE) for using the Virtual Technician Module (VTM)
console
Operating system files that are customized for the systems
System documentation

IPL Considerations

Neither the IPL procedure nor the post-IPL procedure mirrors the system disk. To
achieve fault tolerance, mirror it after the installation. See the Express5800/320Ma: Software Installation and Configuration Guide for instructions.
Do not attempt to use your Windows Server CD alone to install or reinstall Windows
Server. Instead, use the NEC ExpressBuilder CD (1 of 2) to perform the IPL procedure. The NEC ExpressBuilder CD (1 of 2) contains customized drivers that are necessary to run an Express5800/320Ma system properly.
The Post Installation Check, which runs after the IPL, automatically creates a file
named Versiondate.plt (date represents the file creation time and date) that contains information about the files that were installed. NEC Technical Support can use this file to analyze installation problems. This information file is created in the following folder:
%ProgramFiles%\Stratus\CustomerService\VersionReports
The Post Installation Check tool, which also runs after the IPL, creates a file named
Postcheck_yyyy_mm_dd_hh_mm.txt in the %ProgramFiles%\Stratus\Customerservice\Installcheck folder on the system drive. In the file name, yyyy_mm_dd_hh_mm indicates the year, month, date, hour, and minute when the file was created.
6-2 Express5800/320Ma: System Installation Guide
The Post Installation Check tool verifies that:
– Express5800/320Ma applications are properly installed.
– Correct versions of drivers are properly installed.
– The correct, compiled Managed Object Format (MOF) files are present.
– Express5800/320Ma services are installed and started, except for services
that run only at system startup.
– Third-party applications are properly installed.
– Microsoft hotfixes are installed.
The IPL procedure takes approximately two and one-half hours to complete.

Mini-Setup Worksheet

Before you start the IPL or Mini-Setup procedure, record site-specific information on the worksheet shown in Tab le 6- 1 , which lists the information requested by the IPL and Mini-Setup prompts.
For more information about the settings listed in Ta b le 6 -1 , see the Windows documentation.
Mini-Setup Worksheet
Table 6-1. Mini-Setup Worksheet
Setting Description Entry
Regional settings
User name and organization
Installing Express5800/320Ma System Software 6-3
The first Customize button changes general settings (such as location or language); the appearance of dates, time, numbers, and currency; and the input locale (the keyboard’s input language).
The second Customize button changes only the input locale.
A user name is the name of the person who is performing the installation.
An organization (an optional field) is the organization to which a copy of Windows is licensed.
N/A
User name:
Organization:
Mini-Setup Worksheet
Table 6-1. Mini-Setup Worksheet (Continued)
Setting Description Entry
Microsoft product key
Licensing mode
System name and administrator password
If Windows Server 2003 was installed by the manufacturer, you do not need a product key.
The product key is located on the Windows Server 2003 CD case or on the cover of Windows Server 2003 documentation.
Windows Server 2003 supports two licensing modes: per seat and per server.
If you choose Per server, each concurrent connection to the server requires a separate Client Access License. If you select this mode, you can change the mode to the Per Device or Per User mode later.
If you choose Per Device or Per User, each computer that accesses the server requires a separate Client Access License. If you select this mode, you cannot change the mode to the per-server mode later.
A system name is a unique computer name that differs from other computer, workgroup, or domain names on your network. Mini-Setup suggests a system name, but you can change the name. Ask your network administrator for name recommendations.
Product key:
Check one:
Per server: ________ (Default value)
Per Device or Per User ____
System name:
An administrator password is the password for the Administrator account that Windows automatically creates during installation. It is the logon password for the user whose logon name is Administrator. Record this password.
Date and time settings
6-4 Express5800/320Ma: System Installation Guide
Use this dialog box to set the date, time, and time zone.
Administrator password:
N/A
Table 6-1. Mini-Setup Worksheet (Continued)
Setting Description Entry

Performing the IPL Procedure

Networking settings
Workgroup or computer domain
If you have a simple peer-to-peer network, you may want to click Typical settings.
To configure advanced network options or add more services during Mini-Setup, click Custom settings. If you click Custom settings, another dialog box prompts you for more information.
Note: To join a domain, first set your networking settings appropriately. Ask your network administrator for the correct networking settings.
You must join either a workgroup or a domain.
A workgroup is one or more computers with the same workgroup name. To join a workgroup, provide a new workgroup name, or use the workgroup name that Windows suggests during Mini-Setup.
A domain is a group of computers that are part of a network, are managed by a domain controller, and share a common directory database. Joining a domain requires a computer account in the domain you want to join. To join a domain during Mini-Setup, provide the name of an existing domain, your user name, and your password.
Check one:
Typical settings: ________
Custom settings: ________
Workgroup or domain:
Performing the IPL Procedure
The IPL procedure takes approximately two and one-half (2.5) hours. System configuration procedures take additional time. See the Express5800/320Ma: Software Installation and Configuration Guide for information about these configuration procedures.

Checklist: The IPL Procedure

Prepare for the IPL procedure as described in “Preparing for the IPL Procedure” on
page 6-6.
Perform the IPL procedure as described in “Performing the IPL Procedure” on
page 6-6.
Installing Express5800/320Ma System Software 6-5

Performing the IPL Procedure

Preparing for the IPL Procedure

1. Make sure you have the following media:
NEC ExpressBuilder CD (1 of 2)
NEC ExpressBuilder CD (2 of 2)
One of the following:
– For an Express5800/320Ma system, Microsoft Windows Server 2003,
Enterprise Edition CD with Service Pack 1
NOTE
If you are supplying your own Windows Server 2003 CD, make sure it contains only one operating system. If the CD contains more than one operating system, the IPL procedure does not execute correctly.
2. Connect a monitor and keyboard to the system, either directly or through a keyboard, video, mouse switch.
3. Make sure that the hard disk on which you want to install Express5800/320Ma is inserted in one of the following locations:
– In a rack-mountable system, in the bottom-most slot in the top enclosure
– In a pedestal system, in the right-most slot in the enclosure on the left
4. Unlatch all other disks. After the IPL, you insert and mirror the disks.
Performing the IPL Procedure
1. If the system is powered on, remove power before starting the IPL. To remove power from the system, shut down Windows.
2. If any storage enclosures are connected to the system, disconnect them.
3. Turn on power to the system.
a. Verify that the system power cords are plugged into live AC power outlets.
If the system is connected to power distribution units (PDUs), make sure that
the PDUs are plugged into live AC power outlets and are turned on. b. Turn on power to the monitor. c. Turn on system power: Press the power button on the enclosure whose power
button LED is green-lit.
4. Insert the NEC ExpressBuilder CD (1 of 2) in the CD-ROM drive of the enclosure whose power button LED is green-lit.
6-6 Express5800/320Ma: System Installation Guide
Performing the IPL Procedure
5. Disable boot monitoring and, optionally, Option ROM for PCI slots.
a. When the system is booting and the progress bar has started to fill, press F2
to enter the BIOS Setup program. An Entering Setup message appears,
but several minutes may elapse before the BIOS Setup program runs. b. Use the RIGHT ARROW key to select the Advanced tab. c. To disable boot monitoring, use the DOWN ARROW key to select Monitoring
Configuration. Press ENTER. Use the DOWN ARROW key to select OS
Boot Monitoring. Use the PLUS SIGN (+) key to change the value to
Disabled. Press ESC.
d. If the system contains any PCI adapters that contain option ROMs, the system
boots faster if you disable Option ROM for the PCI slots that contain the
adapters. To disable Option ROM, select Monitoring Configuration on the
Advanced tab. Select each slot that contains an adapter and use the PLUS
SIGN (+) key to change the values to Disabled. e. Press F10. In the Setup Confirmation dialog box, select Yes and press
ENTER to save the new settings and exit from the BIOS Setup program.
The system reboots after you exit from the BIOS Setup program.
NOTE
Disabling boot monitoring prevents several unnecessary restarts of the system during the IPL process.
6. Make sure theNEC ExpressBuilder CD (1 of 2) is inserted in the CD-ROM drive whose power button LED is green-lit.
7. During the next few minutes, the following normally appear:
A message: Initial Program Load
A Windows XP splash screen
A black screen, then a blue screen, with no text
A Fault Tolerant Server splash screen
8. In the Start Express5800 series system software IPL dialog box, accept the default setting, Run the Initial Program Load for Express5800/320Ma software Release 4.1.x.x, and click Next.
NOTES
1. The dialog box advises you to disable boot monitoring. If you already disabled boot monitoring as described in step 5, you do not need to do so again.
2. The Open a session in the Windows Preinstallation Environment option opens a WinPE command shell.
Installing Express5800/320Ma System Software 6-7
Performing the IPL Procedure
3. Do not use a customized CD except with the supervision of the NEC Technical Support.
9. Follow the prompts to specify the size of the partition that you want the IPL to create.
Specify a value within the range of the minimum and maximum allowed partition sizes for your disk, as shown in the dialog box.
NOTE
If you plan to use a disk-management tool to configure the system disk as a dynamic disk, ensure that the partition size that you create now is the size that you want. To extend the partition size after the disk becomes dynamic, you may need to purchase and use a third-party tool.
10. Follow the prompts to complete the preinstallation steps of the IPL.
11. If Windows Setup displays the message The Setup script file does not contain a valid Product ID, click OK. Then, in the Your Product Key dialog box, enter the product key you specified in Ta bl e 6 - 1 and click Next.
12. In the Preinstallation Completed dialog box, click Restart.
NOTE
If the system is left unattended for an extended period of time after this point, an Unlock Computer dialog box may prompt you to log in. You do not need to provide a password to log in and continue the installation process.
13. For the next few minutes, Windows Setup copies files and starts installation of Windows updates (hotfixes), restarting the computer at several points.
14. When the Windows Server Post-Setup Security Updates dialog box appears, configure the system to download, but not automatically install, hotfixes. Use the following guidelines to install the hotfixes:
You can install Microsoft hotfixes that are released in a Security Bulletin as a
group of security-related hotfixes.
Obtain validation from NEC Solutions (America), Inc. before you install other
types of hotfixes, such as Microsoft patches that fix a particular problem.
See the Express5800/320Ma ActiveService Network Configuration Guide for more information about installing hotfixes.
15. Follow the instructions in the Windows Setup Completed dialog box.
6-8 Express5800/320Ma: System Installation Guide
16. A few minutes may pass before the system restarts and the post-IPL procedure starts.

The Post-IPL Procedure

Perform the post-IPL procedure if Windows and Express5800/320Ma were preinstalled on your system, or if you have just performed the IPL procedure.

Checklist: Performing the Post-IPL Procedure

If you have not already done so, complete the Mini-Setup Worksheet. See
“Mini-Setup Worksheet” on page 6-3.
Respond to Mini-Setup prompts. See “Responding to Mini-Setup Prompts” on
page 6-9.
Complete the post-IPL procedure. See “Completing the Post-IPL Procedure” on
page 6-10.
NOTE
Before proceeding, check for the latest information about your system and Express5800/320Ma in the Release Notes: Express5800/320Ma on the NEC ExpressBuilder CD (2 of 2) shipped with your system.
The Post-IPL Procedure

Responding to Mini-Setup Prompts

1. If you have just performed the IPL procedure, go to step 2. Otherwise:
a. Insert the disk that contains the boot partition in the following location:
– In a rack-mountable system, in the bottom-most slot in the top enclosure
– In a pedestal system, in the enclosure on the left, in its right-most slot
b. Turn on the system, if you have not already done so. See “Performing the IPL
Procedure” on page 6-6.
2. If the Welcome to the Windows Setup Wizard starts, respond to the Mini-Setup prompts. If prompted by Mini-Setup, enter the license key again. (You are not prompted for the license key if Windows was installed by the manufacturer.) Use the information you provided in Ta bl e 6 - 1 to respond to these prompts.
When Mini-Setup is finished, the system reboots.
NOTE
If your system contains VTMs, the mouse and keyboard may appear unresponsive at some point after the system
Installing Express5800/320Ma System Software 6-9
The Post-IPL Procedure
has restarted. This is normal behavior while the virtual mouse and keyboard are found by the operating system as new hardware. Responsiveness returns after a short period of time.

Completing the Post-IPL Procedure

1. When the Welcome to Windows dialog box appears, press CTRL+ALT+DELETE.
2. Log on by using the Administrator account and password you entered during Mini-Setup and click OK.
3. Two separate end-user licensing agreements (EULAs) appear:
a. Select the appropriate language for the Express5800/320Ma EULA. If you
display the EULA, review it, and then click Close. Click I accept the terms of the license agreement if you agree to the terms, and then click Continue.
b. Select whether you want to display the Microsoft Quick-Fix Engineering EULA
Addendum. If you display the EULA, review it, and then click Close. Click I accept the terms of the license agreement if you agree to the terms, and then click Continue.
4. The installation programs for third-party software run. Be sure to install the following software, as NEC Solutions (America), Inc. does not support systems that lack this software.
When the Java Runtime Environment Wizard starts, follow the prompts to
install JRE, accept the license agreement and the default settings in the remaining dialog boxes. (The JRE Setup dialog box may become partially obscured by the progress bars. Click the dialog box to bring it forward.)
CAUTION
!
If the Setup Complete dialog box for any third-party software appears, click No, I will restart my computer later, and then click Finish. If you restart the system now, the installation does not complete properly.
5. When Setup displays the IPL Completed dialog box, click Restart.
6. Restore the default BIOS settings to enable boot monitoring and, optionally, to enable Option ROM on the PCI slots. While the system is booting, press F2 to enter the BIOS Setup program. In the BIOS Setup program, press F9 to restore the default settings, then press F10 to exit from the BIOS Setup program. You must enable boot monitoring to maintain fault tolerance.
6-10 Express5800/320Ma: System Installation Guide
The Post-IPL Procedure
CAUTION
!
If you do not enable boot monitoring after you perform the IPL, fault-tolerance of the system is compromised.
7. Express5800/320MaAfter the system has restarted, log on again. The Post Installation Check window appears for several minutes.
8. The Post Installation Check Tool dialog box appears and automatically runs. This tool verifies that the upgrade was successful and that the system is restored to full operation. Click Exit to dismiss the Post Installation Check Tool dialog box. See
“IPL Considerations” on page 6-2 for a description of the file created by the Post
Installation Check tool.
9. The message box 'Has the NEC ExpressCluster Web service been set up?' may appear during the NEC ExpressCluster SRE installation, but will automatically disappear after 5 seconds. DO NOT take action to this prompt, or the system may appear to hang.
10. If you are attaching any EMC
a. Download and install the latest QLogic
®
storage systems to the system, do the following:
®
Fibre Channel drivers for
Windows 2003.
– See the Express5800/320Ma: PCI Adapter Guide for information about the
U525 or U526 PCI adapters that provide connectivity to EMC CLARiiON and Symmetrix
®
storage systems, and instructions for downloading,
extracting, and installing the driver.
–See Attaching an EMC CLARiiON AX100 Storage System to an
Express5800/320Ma System for information about the U531 Optical Fibre Channel PCI Adapter that provides connectivity to AX100 storage systems, and instructions for downloading, extracting, and installing the driver.
b. Install the EMC PowerPath
®
software. See the PowerPath documentation from
EMC.
c. Connect the system to the storage enclosure. If the storage enclosure is part
of a storage area network (SAN), add the system to the SAN.
11. Configure your system. In particular, do the following:
Installing Express5800/320Ma System Software 6-11
®
The Post-IPL Procedure
Mirror the disks.
If your system contains VTMs, make sure the VTMs contain the most
up-to-date firmware.
Use PROSet to configure Ethernet ports into teams.
For more information about configuring your system, see the Software Installation and Configuration Guide.
Express5800/320Ma:
6-12 Express5800/320Ma: System Installation Guide
Appendix A

Ordering CRUs

To find the part number for a customer-replaceable unit (CRU), see the following:
“System CRUs” on page A-2
“Network Adapters” on page A-3
“Host Bus Adapters” on page A-3
“Peripheral Components” on page A-3
“KVM Switch and Cables” on page A-3
“System Power Cords” on page A-4
“PDU and PDU Power Cables” on page A-4
CAUTION
!
Do not attempt to remove or replace hardware components that are not listed in the CRU tables. Instead, contact the NEC Technical Support to determine the best course of action.
A-
Ordering CRUs A-1

System CRUs

System CRUs
Ta bl e A - 1 lists the part numbers of customer replaceable units (CRUs) for your system.
Table A-1. System CRUs
Description Part Number
CPU- I O enclosure
1GB DDR2-400 DIMM M231
2GB DDR2-400 DIMM M232
Processor kit: Intel
Processor kit: Intel Xeon 3.6 GHz AK-000541
SATA backplane assembly AA-E93400
System backplane assembly AA-E91100
IDE backplane assembly AA-E93500
Fan assembly (CPU or PSU) AS-000394
Virtual Technician Module (VTM) AA-U46300
®
Xeon® 3.2 GHz AK-000527
AA-G90730
SATA disk drive, 160GB, 7200 RPM D642
SATA disk drive, 73GB, 10000 RPM D643
SATA disk drive, 400 GB, 7200 RPM D644
SATA disk drive, 160 GB, 7200 RPM D645
Disk slot filler panel AS-000390
Cabinet ground cable AW-002000
CD-ROM drive AK553
DVD-RW drive AK554
† Specify memory and processor configuration when requesting a replacement CPU- I O enclosure. Processors and DIMMs are not CRUs. Their part numbers are supplied solely for use in configuring a replacement enclosure.
A-2 Express5800/320Ma: System Installation Guide

Network Adapters

Ta bl e A - 2 lists the part numbers of the network adapters—network interface cards or
NICs—for your system.
Table A-2. Network Adapters and PCI Adapter Cables
Description Part Number
U575 Dual-Port Copper Gigabit Ethernet Adapter U575

Host Bus Adapters

Ta bl e A - 3 lists the part numbers of host bus adapters (HBAs) for your system.
Table A-3. Host Bus Adapter Cables
Description Part Number
U525 Optical Fibre Channel PCI Adapter AA-U52500
U526 Optical Fibre Channel PCI Adapter AA-U52600
Network Adapters

Peripheral Components

Ta bl e A - 4 lists the part numbers of peripheral components that NEC Solutions
(America), Inc. supplies for your system. For monitor power cords, see Ta bl e A - 9.
Table A-4. Peripheral Components
Description Part Number
USB floppy disk drive, external AA-000400
Keyboard AA-V11520
Mouse AA-V11610

KVM Switch and Cables

Ta bl e A - 5 lists the part numbers of the KVM switch and its cables.
Table A-5. KVM Switch CRUs
Description Part Number
Four VGA and USB cables B40500-10
Ordering CRUs A-3

System Power Cords

Table A-5. KVM Switch CRUs
Description Part Number
One VGA and USB extension cable, 6 ft (1.82m) B40501-06
System Power Cords
Ta bl e A - 6 lists the part numbers of the power cords that NEC Solutions (America), Inc.
supplies to connect your system directly to AC power. Ta bl e A - 7 lists the part numbers of the power cables that connect the system to an uninterruptible power supply (UPS).
Table A-6. System Power Cords
Power Cord Part Number
North America (Chicago), NEMA 5-15, 15A, 100-127 VAC, 50-60 Hz, 7 ft
North America domestic, NEMA 5-15, 15A, 100-127 VAC, 50-60 Hz, 15 ft
North America and Japan, locking power cord, NEMA L6-20, 20A, 200-240 VAC, 50 Hz, 4.5m
International, locking power cord, IEC-309, 16A, 200-240 VAC, 50 Hz, 4.5m
Table A-7. Power Cords from a System to a UPS
Power Cord Part Number
North America and Japan, NEMA 5-15 to IEC-C13, 120 VAC, 15 ft (4.5m)
North America and Japan, locking power cord, NEMA L6-20 to IEC-C13, 200-240 VAC, 50 Hz, 15 ft (4.5m)
International, IEC-320 C14 to IEC-320 C13, 250 VAC 3.5m B50301-35M

PDU and PDU Power Cables

Ta bl e A - 8 lists the part numbers of the PDU, the power cords that connect the PDU to
external power and that connect the PDU to a UPS, and the power cables that connect the system and storage enclosures to a PDU.
B50101-07
B50104-15
B50161-45M
B50153-45M
B50104-15
B50161-45M
A-4 Express5800/320Ma: System Installation Guide
PDU and PDU Power Cables
Table A-8. PDU and PDU Power Cords
Description Part Number
PDU AA-P41104
PDU power cords to external power
NEMA L6-20, 20A, 250 VAC, 50-60 Hz, 15 ft (4.5m) B50155-45M
NEMA L6-30, (Receptacle must be fused at no more than 20A), 30A, 250 VAC, 50-60 Hz, 15 ft (4.5m)
IEC-309, 20A, 250 VAC, 50-60 Hz, 15 ft (4.5m) B50154-45M
PDU power cords to a UPS
North America and Japan, NEMA L6-20 to IEC-320 C19, 208V, 15 ft (4.5m)
International, IEC-320 C14 to IEC-320 C19, 230V 3.5m B38003
PDU power cables (jumper cables from PDU to system)
Gray, IEC-320 C13 to IEC-320 C14, 10A, 250V, 2.0m B50502-02M
Black, IEC-320 C13 to IEC-320 C14, 10A, 250V, 2.0m B50503-02M
B50156-45M
B50155-45M
Ordering CRUs A-5
PDU and PDU Power Cables
A-6 Express5800/320Ma: System Installation Guide

Index-Index

A
accessories box, contents, 1-1 adapters. See PCI adapters Administrator account password
setting in Mini-Setup program, 6-4
A-side power source, 4-6
B
backplane assembly
IDE
ordering, A-2
SATA
ordering, A-2
system
installing, 2-11 ordering, A-2
bezel
pedestal system
illustrated, 1-4 installing, 3-4
rack-mount system
illustrated, 1-3 installing, 2-14
BIOS
changing settings, 6-7
boot monitoring
disabling, 6-7 enabling, 6-7
B-side power source, 4-6
C
cabinets
numbering rail units (U), 2-2
cables
Ethernet network, 4-5 from system to UPS, ordering, A-4 managing, 2-1, 4-7 power (PDU), ordering, A-4 routing, 2-1, 4-7
USB, ordering, A-3, A-4
cage nuts
front rail locations, 2-7
illustrated, 1-3, 1-4 CD-ROM drive, ordering, A-2 checklists
IPL procedure, 6-5
post-IPL procedure, 6-9 COM ports
illustrated, 4-2, 4-3 CPU fan assembly
ordering, A-2 CPU-I/O enclosures
installing, 2-13, 3-2
ordering, A-2
D
damage, inspecting for, 1-4 date and time settings of Mini-Setup
program, 6-4
disk drives
external floppy, 4-6
ordering, A-3 location during IPL, 6-6 SATA
ordering, A-2 states during IPL, 6-6
disk partitions
during IPL, 6-8
disk slot filler panel, ordering, A-2 disk space requirements
during IPL, 6-6
documentation, system, 6-2, 6-11 drive letter, floppy disk drive, 4-6 DVD-R/W drive
ordering, A-2
E
EMC PowerPath installation, 6-11
Index-1
Index
enclosures
installing, 2-13, 3-2 ordering, A-2
Ethernet networks
connecting to PCI adapters, 4-5 connecting to ports, 4-4 connecting to VTM, 4-4
Ethernet ports
system
illustrated, 4-2, 4-3
VTM
illustrated, 4-2 Express5800/320Ma EULA, 6-10 Express5800/320Ma Series System Software
IPL procedure, 6-5 post-IPL procedure, 6-9
extension cables
USB, ordering, A-4 VGA, ordering, A-4
external floppy disk drive
connecting, 4-6 drive letter, 4-6 ordering, A-3
F
floppy disk drive
connecting, 4-6 drive letter, 4-6
ordering, A-3 front vertical rails, cage nut locations, 2-7 ftServer Management Console. See ftSMC ftServer Management Tools. See ftSMC ftSMC, 6-2
shortcut, 6-11
G
ground cables, ordering, A-2
H
Help and Manuals shortcut, 6-11
I
IDE backplane assembly
ordering, A-2 Initial Program Load (IPL) procedure
CDs required, 6-6
checklist, 6-5 disk states during, 6-6 media required, 6-6 Open a session in the Windows
Preinstallation Environment
option, 6-7 post-IPL procedure, 6-9 preparing for, 6-5 Start Express5800/320Ma System
Software IPL dialog box, 6-7 system disk location, 6-6 time to complete, 6-5
inspecting the system, 1-4 installation
Express5800/320Ma system software, 6-1
installation information file, 6-2 installing
Java 2 Runtime Environment, 6-10
J
Java 2 Runtime Environment. See JRE JRE, 6-10
K
keyboards
connecting to system, 4-3 ordering, A-3 USB hub restrictions, 4-6
L
licensing mode settings of Mini-Setup
program, 6-4
M
Microsoft EULA, 6-10 Mini-Setup program, 6-9 modem assembly
connecting cable, 4-5 installing, 2-12, 3-1
monitor
connecting
table top, 4-3
mounting brackets
PDUs, 5-2 system, 2-5
mouse
Index-2 Express5800/320Ma: System Installation Guide
Index
connecting to keyboard, 4-3 ordering, A-3
N
NEC ExpressBuilder CD (2 of 2), 6-6 networking settings of Mini-Setup program, 6-5
P
password, Administrator account, 6-4 PCI adapters
connecting, 4-5 Ethernet networks, 4-5 installed, 4-1 ordering, A-3 slots, 4-1 See also specific adapter part numbers
PDUs
components, 5-1
cables, 5-2 illustrated, 5-2
mounting brackets, 5-2 connecting to power sources, 5-3 connecting to system, 4-13, 4-14 installing, 5-2, 5-3 maximum number in a cabinet, 5-2 ordering, A-4 power cords, 5-2 removing from cabinet, 5-5
ports, 4-1
Ethernet
system, 4-2, 4-3
VTM, 4-2, 4-3 pedestal system, illustrated, 4-2 rack-mountable system, illustrated, 4-3 RJ11, 4-3 serial (COM), 4-2, 4-3 USB, 4-2 VGA, 4-2
Post Installation Check Tool, 6-11 Post Installation Check tool, 6-2, 6-11 Postcheck_yyyy_mm_dd_hh_mm.txt file, 6-2 post-IPL procedure
checklist, 6-9 completing, 6-10
power (AC)
sources, 4-6
power cables
ordering, A-4
power cords
color coded, 4-13
illustrated, 4-14 illustrated, 1-3 monitor, ordering, A-5 PDU, 5-2
connecting to AC, 5-3
connecting with a UPS, illustrated, 5-4 safety precautions, 4-7 system
connecting, 4-7
connecting, illustrated, 4-8
ordering, A-5 tape drive, ordering, A-5 to UPS, A-4
power distribution unit (PDU). See PDUs power receptacles
illustrated, 4-2, 4-3
power, AC
connecting to pedestal system, 4-9 connecting with PDUs, 4-13, 5-3 connecting with UPS, 4-10
powering up
server systems, 6-6
PowerPath installation, 6-11 product key, Windows
setting of Mini-Setup program, 6-4
Q
QLogic Fibre Channel drivers
installing for U525 and U526 Optical Fibre
Channel PCI Adapters, 6-11
R
rack, 2-2
system requirements, 2-2
rail unit (U)
defined, 2-2 illustrated, 2-3
rails, numbering, 2-3 rear vertical rails, screw locations, 2-5 regional settings of Mini-Setup program, 6-3 reinstalling Windows Server 2003, 6-2 removing power, 1-5 RJ-11 port
illustrated, 4-3
Index-3
Index
S
safety
installation, 1-6 notices, 1-5
SATA backplane assembly
ordering, A-2
SATA disk drive
ordering, A-2
screw locations
front rails, 2-7 rear rails, 2-5
serial (COM) ports
illustrated, 4-2, 4-3 serial numbers, system, 1-5 system documentation, 6-2 systems
accessories, listed, 1-1
components
illustrated, 1-3, 1-4
listed, 1-1 power, removing from service, 5-5 setting up, 4-3
systems, installing, 2-2
attaching mounting brackets, 2-5 connecting to Ethernet networks, 4-4 inspecting for damage, 1-4 reporting damage, 1-4 tools, 2-1, 3-1
T
third-party software during a System Software
installation, 6-10
tools, required for installing, 2-1, 3-1
floppy disk drive, connecting, 4-6 hubs, use restrictions, 4-6 ports
illustrated, 4-2, 4-3
user name setting of Mini-Setup program, 6-3
V
Versiondate.plt file, 6-2 VGA cables
extension cable, ordering, A-4 ordering, A-3
VGA port
illustrated, 4-2, 4-3 Virtual Technician Module. See VTM VTM
Ethernet ports
illustrated, 4-2, 4-3
ordering, A-2
W
Welcome to the Windows Setup Wizard, 6-9 Welcome to Windows Logon dialog box, 6-10 Windows Server 2003
CD, 6-6
reinstalling, 6-2 Windows Setup dialog box, 6-8 workgroup or computer domain settings of
Mini-Setup program, 6-5
U
U (rack unit)
defined, 2-2 illustrated, 2-3 numbering, 2-3 requirements, 2-3
U525 adapter
ordering, A-3
U575 adapter
ordering, A-3 UPS, connecting, 4-10 USB
cables, ordering, A-3, A-4
Index-4 Express5800/320Ma: System Installation Guide
Loading...