NEC EcoPowerGateway N8142-36F User Manual

Page 1
NEC Express5800/100 Series
N8142-36F
EcoPowerGateway
User's Guide
1st Edition
7-2010
ONL-520_005_02-COMMON-100-00-1007
Page 2
PROPRIETARY NOTICE AND LIABILITY DISCLAIMER
The NEC product(s) discussed in this document are warranted in accordance with the terms of the Warranty Statement accompanying each product. However, actual performance of each such product is dependent upon factors such as system configuration, customer data, and operator control. Since implementation by customers of each product may vary, the suitability of specific product configurations and applications must be determined by the customer and is not warranted by NEC.
To allow for design and specification improvements, the information in this document is subject to change at any time, without notice. Reproduction of this document or portions thereof without prior written approval of NEC is prohibited.
First Printing, July 2010
Copyright 2010
NEC Corporation
7-1 Shiba 5-Chome, Minato-Ku
Tokyo 108-8001, Japan
All Rights Reserved
Printed in Japan
Page 3
Keep this User's Guide at hand for quick reference at anytime necessary.

SAFETY INDICATIONS

Follow the instructions in this User's Guide for your safety to use the EcoPowerGateway.
The EcoPowerGateway contains components with possible danger, hazards that may cause by ignoring warnings, and preventive actions against such hazards.
The EcoPowerGateway components with possible danger are indicated with a warning label placed on or around them as well as described in this User's Guide.
In the User's Guide or warning labels, "WARNING" or "CAUTION" is used to indicate a degree of danger. These terms are defined as follows:
WARNING
CAUTION
Precautions and notices against hazards are presented with one of the following three symbols. The individual symbols are defined as follows:
This symbol indicates the presence of a hazard if the instruction is ignored. An image in the symbol illustrates the hazard type. (Attention)
This symbol indicates prohibited actions. An image in the symbol illustrates a particular prohibited action. (Prohibited Action)
This symbol indicates mandatory actions. An image in the symbol illustrates a mandatory action to avoid a particular hazard. (Mandatory Action)
(Example)
Symbol to draw attention
Indicates the presence of a hazard that may result in death or serious personal injury if the instruction is ignored.
Indicates the presence of a hazard that may cause minor personal injury, including burns, or property damage if the instruction is ignored.
Description of a danger Term indicating a degree of danger
CAUTION
Plug in to a proper power source of the specified voltage. Use a proper wall outlet. Use of an improper power source may cause a fire or a power leak.
Page 4
Page 5

Symbols Used in This User's Guide and Warning Labels

Attentions
Indicates that improper use may cause an electric shock.
Indicates that improper use may cause fumes or fire.
Indicates that improper use may cause fingers to be caught.
Indicates that improper use may cause personal injury.
Indicates that improper use may cause explosion.
Indicates that improper use may cause personal injury.
Indicates a general notice or warning that cannot be specifically identified.
Prohibited Actions
Do not disassemble, repair, or modify the EcoPowerGateway. Otherwise, an electric shock or fire may be caused.
Do not use the EcoPowerGateway in the place where water or liquid may pour. Otherwise, an electric shock or fire may be caused.
Do not place the EcoPowerGateway near the fire. Otherwise, a fire may be caused.
Do not touch the EcoPowerGateway with wet hand. Otherwise, an electric shock may be caused.
Do not touch the component specified by this symbol. Otherwise, an electric shock or burn may be caused.
Indicates a general prohibited action that cannot be specifically identified.
Mandatory Action
Unplug the power cord of the EcoPowerGateway. Otherwise, an electric shock or fire may be caused.
Be sure to provide earthing. Otherwise, an electric shock or fire may be caused.
Indicates a mandatory action that cannot be specifically identified. Make sure to follow the instruction.
Page 6
Page 7
NOTE: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
CE Statement
Warning : This is a Class A product. In domestic environment this product may cause radio interference in which case the user may be required to take adequate measures (EN55022).
Page 8
Page 9
Trademarks
NEC ESMPRO, NEC EXPRESSBUILDER, and EXPRESSSCOPE are registered trademarks of NEC Corporation.
Notes:
(1) No part of this manual may be reproduced in any form without the prior written permission of
NEC Corporation.
(2) The contents of this User's Guide may be revised without prior notice.
(3) The contents of this User's Guide shall not be copied or altered without the prior written
permission of NEC Corporation.
(4) All efforts have been made to ensure the accuracy of all information in this User's Guide. If
you notice any part unclear, incorrect, or omitted in this User's Guide, contact the service representative where you purchased this product.
(5) NEC assumes no liability arising from the use of this product, nor any liability for incidental or
consequential damages arising from the use of this User's Guide regardless of Item (4).
Page 10
(This page is intentionally left blank.)
Page 11

PREFACE

Thank you very much for purchasing our N8142-36F EcoPowerGateway.
The N8142-36F EcoPowerGateway can supply DC power of up to 1700 watts with 4 ports. Consolidating power supplies to servers in rack realizes the system configuration of higher density. In addition, optional power units can be additionally installed to meet with your power requirements (up to four power units including standard power units).
Read this User's Guide thoroughly to fully understand handling of the EcoPowerGateway and appreciate its functions to the maximum extent.
i
Page 12
ii

ABOUT THIS USER'S GUIDE

This User's Guide is a guide for proper setup and use of the EcoPowerGateway.
This User's Guide also covers useful procedures for dealing with difficulties and problems that may arise during setup or operation of the EcoPowerGateway.
Keep this manual for future use.
The following describes how to proceed with this User's Guide.
How to Use This User's Guide
To aid you in finding information quickly, this User's Guide contains the following information:
Chapter 1 Notes on Using Your EcoPowerGateway
includes information that needs attention to use the EcoPowerGateway. Make sure to read this chapter before setting up and using the EcoPowerGateway. It also includes requirements and advisory information for transfer and disposal of the EcoPowerGateway.
Chapter 2 General Description
includes information necessary to use the EcoPowerGateway, such as names and functions of its components.
Chapter 3 Setting Up Your EcoPowerGateway
tells you how to setup your EcoPowerGateway, make cable connections, and power on your system.
Chapter 4 Configuring Your EcoPowerGateway
tells you how to configure the system and provides instructions for running the BIOS Setup Utility.
Chapter 5 Maintenance
provides you with all the information necessary to maintain successful operation of the EcoPowerGateway.
Chapter 6 Troubleshooting
contains helpful information for solving problems that might occur with your system.
Chapter 7 Installing Options
provides you installation procedure for optional devices.
Appendix A Specification
provides specifications for your EcoPowerGateway.
Page 13
Text Conventions
The following conventions are used throughout this User's Guide. For safety symbols, see "SAFETY INDICATIONS" provided earlier.
iii
IMPORTANT:
NOTE:
Items that are mandatory or require attention when using the EcoPowerGateway
Helpful and convenient piece of information

IN THE PACKAGE

The carton contains various accessories, as well as the EcoPowerGateway itself. See the packing list to make sure that you have everything and that individual components are not damaged. If you find any component missing or damaged, contact your service representative.
Store the provided accessories in a designated place for your convenience. You will need
them to install an optional device or troubleshoot the EcoPowerGateway, as well as to set it up.
Page 14
iv

CONTENTS

Preface ..............................................................................................................................................i
About This User's Guide..................................................................................................................ii
In the Package................................................................................................................................ iii
Chapter 1 Notes on Using Your EcoPowerGateway................................................... 1-1
Warning Labels ............................................................................................................................ 1-2
Safety Notes................................................................................................................................. 1-3
General .................................................................................................................................... 1-4
Power Supply and Power Cord Use......................................................................................... 1-8
Rack........................................................................................................................................1-11
Installation, Relocation, and Storage..................................................................................... 1-14
During Operation................................................................................................................... 1-16
For Proper Operation ................................................................................................................. 1-17
Transfer to Third Party............................................................................................................... 1-19
Disposal and Consumables ........................................................................................................1-19
Regarding the Transportation of this System............................................................................. 1-19
User Support .............................................................................................................................. 1-20
Chapter 2 General Description ..................................................................................... 2-1
Names and Features of Components............................................................................................ 2-2
Front View ............................................................................................................................... 2-2
Rear View ................................................................................................................................ 2-4
Lamp Indications..................................................................................................................... 2-7
Using Your EcoPowerGateway...................................................................................................2-11
Power-on of EcoPowerGateway.............................................................................................2-11
DC Output ON/OFF .............................................................................................................. 2-12
Starting Maintenance Mode................................................................................................... 2-15
Power-off of EcoPowerGateway........................................................................................... 2-17
Device Identification ............................................................................................................. 2-17
Chapter 3 Setting Up Your EcoPowerGateway ........................................................... 3-1
Installation ............................................................................................................................... 3-1
Making Connections...............................................................................................................3-11
Chapter 4 Configuring Your EcoPowerGateway......................................................... 4-1
System BIOS ~ SETUP ~ ............................................................................................................ 4-1
Starting SETUP Utility ............................................................................................................ 4-2
Description on On-Screen Items and Key Usage .................................................................... 4-3
Configuration Examples..........................................................................................................4-4
Menu and Parameter Descriptions........................................................................................... 4-7
Page 15
Chapter 5 Maintenance.................................................................................................. 5-1
Making Backup Copies ................................................................................................................5-1
Maintenance Tools........................................................................................................................5-2
Function of Maintenance Tools ................................................................................................5-2
Cleaning........................................................................................................................................5-4
Cleaning the EcoPowerGateway..............................................................................................5-4
Relocating/Storing The EcoPowerGateway..................................................................................5-5
Chapter 6 Troubleshooting ........................................................................................... 6-1
System Viewers ............................................................................................................................6-2
STATUS Lamp..............................................................................................................................6-3
Error Messages .............................................................................................................................6-4
POST Error Messages ..............................................................................................................6-4
Error Messages on Virtual LCD...............................................................................................6-8
Solving Problems........................................................................................................................6-17
EcoPowerGateway .................................................................................................................6-17
Collecting Fault Information ......................................................................................................6-18
Maintenance Tools......................................................................................................................6-18
v
Chapter 7 Installing Options......................................................................................... 7-1
Safety Notes..................................................................................................................................7-2
Anti-static Measures .....................................................................................................................7-3
Preparation for Installation/Removal............................................................................................7-4
Confirmation after Installation/Removal......................................................................................7-5
Installation/Removal Procedure....................................................................................................7-6
N8181-76F Power Unit ............................................................................................................7-6
Replacing a Failing Power Unit ...............................................................................................7-9
Appendix A Specifications............................................................................................A-1
Page 16
vi
(This page is intentionally left blank.)
Page 17
Chapter 1

Notes on Using Your EcoPowerGateway

This chapter includes information necessary for proper and safe operation of the EcoPowerGateway.
Page 18
1-2 Notes on Using Your EcoPowerGateway

WARNING LABELS

The warning label is attached to components with possible danger or their vicinity in your EcoPowerGateway to inform the user that a hazardous situation may arise when operating the EcoPowerGateway. (Do not intentionally remove or damage any of the labels.)
If you find any labels totally/partially removed or illegible due to damage, contact your service representative.
See "Safety Notes" for meaning of the symbols that appear on the warning label.
This label is also on the bottom.
Page 19
Notes on Using Your EcoPowerGateway 1-3

SAFETY NOTES

This section provides notes on using the EcoPowerGateway safely. Read this section carefully to ensure proper and safe use of the EcoPowerGateway. For symbols, see "SAFETY INDICATIONS" provided earlier.
The EcoPowerGateway contains power supply units. Pay attention to electric hazard. In addition, pay attention to personal injury when installing/removing the EcoPowerGateway in/from the rack assembly.
Page 20
1-4 Notes on Using Your EcoPowerGateway

General

WARNING
Do not use the EcoPowerGateway for services where critical high availability may directly affect human lives.
The EcoPowerGateway is not intended to be used with or control facilities or devices concerning human lives, including medical devices, nuclear facilities and devices, aeronautics and space devices, transportation facilities and devices; and facilities and devices requiring high reliability. NEC assumes no liability for any accident resulting in personal injury, death, or property damage if the EcoPowerGateway has been used in the above conditions.
Do not disassemble, repair, or alter the EcoPowerGateway.
Never attempt to disassemble, repair, or alter the EcoPowerGateway on any occasion other than described in this User's Guide. Failure to follow this instruction may cause an electric shock or fire as well as malfunctions of the EcoPowerGateway.
Do not use the EcoPowerGateway if any smoke, odor, or noise is present.
If smoke, odor, or noise is present, immediately turn off the system and disconnect the power plug from the outlet, then contact your service representative. Using the EcoPowerGateway in such conditions may cause a fire.
Keep needles or metal objects away from the EcoPowerGateway.
Do not insert needles or metal objects into ventilation holes. Doing so may cause an electric shock.
Do not use the equipment in the place where corrosive gases exist.
Make sure not to locate or use the EcoPowerGateway in the place where corrosive gases (sulfur dioxide, hydrogen sulfide, nitrogen dioxide, chlorine, ammonia, ozone, etc) exist. Also, do not set it in the environment where the air (or dust) includes components accelerating corrosion (ex. sulfur, sodium chloride) or conductive metals. There is a risk of a fire due to corrosion and shorts of an internal printed board.
Page 21
Notes on Using Your EcoPowerGateway 1-5
Page 22
1-6 Notes on Using Your EcoPowerGateway
CAUTION
Keep water or foreign matter away from the EcoPowerGateway.
Do not let any form of liquid (water etc.) or foreign matter (e.g., pins or paper clips) enter the EcoPowerGateway. Failure to follow this warning may cause an electric shock, a fire, or a failure of the EcoPowerGateway. When such things accidentally enter the EcoPowerGateway, immediately turn off the power and disconnect the power plug from the outlet. Do not disassemble the EcoPowerGateway. Contact your service representative.
Make sure to complete device installation.
Always connect the interface cable and power cable firmly. An incompletely installed device may cause a contact failure, resulting in smoking or fire.
Do not use any unauthorized interface cable.
Use only interface cables provided by NEC and locate a proper device and connector before connecting a cable. Using an unauthorized cable or connecting a cable to an improper destination may cause a short circuit, resulting in a fire. Also, observe the following notes on using and connecting an interface cable.
Do not use any damaged cable connector.Do not step on the cable.Do not place any object on the cable.Do not use the equipment with loose cable connections.Do not use any damaged cable.
Avoid installation in extreme temperature conditions.
Power unit installed in EcoPowerGateway may get very hot. Leave them until fully cool down before installing/removing the power unit. The air exhausted from the fan also gets very hot. Do not let your hands or face close to the exhaust hole.
Avoid contact with the equipment during thunderstorms.
Disconnect the power plug from the outlet when a thunderstorm is approaching. If it starts thundering before you disconnect the power plug, do not touch any part of the equipment including the cables. Failure to follow this warning may cause a fire or an electric shock.
Keep animals away from the equipment.
Pet's discharges or fur may enter the equipment and cause a fire or electric shock.
Page 23
Notes on Using Your EcoPowerGateway 1-7
Page 24
1-8 Notes on Using Your EcoPowerGateway

Power Supply and Power Cord Use

WARNING
Do not hold the power plug with a wet hand.
Do not disconnect/connect the plug while your hands are wet. Failure to follow this warning may cause an electric shock.
Do not connect the ground wire to a gas pipe.
Never connect the ground wire to a gas pipe. Failure to follow this warning may cause a gas explosion.
Page 25
Notes on Using Your EcoPowerGateway 1-9
CAUTION
Plug in to a proper power source.
Use a proper wall outlet of the specified voltage equipped with the ground line. Use of an improper power source may cause a fire or a power leak. Do not install the EcoPowerGateway where you need an extension cord. Use of a cord that does not meet the power specifications of the EcoPowerGateway may heat up the cord and cause a fire. The power consumption per one power unit is described in the label sticked on the power unit. Use the power cord appropriate to the power unit.
Do not connect the power cord to an outlet that has an illegal number of connections.
The electric current exceeding the rated flow overheats the outlet, which may cause a fire.
Insert the power plug into the outlet as far as it goes.
Heat generation resulting from a halfway inserted power plug (imperfect contact) may cause a fire. Heat will also be generated if condensation is formed on dusty blades of the halfway inserted plug, increasing the possibility of fire.
Use the authorized power cord only.
Use only the power cord that comes with your EcoPowerGateway. Use of an unauthorized power cord may cause a fire when the electric current exceeds the rated flow. Also, observe the following to prevent an electric shock or fire caused by a damaged cord.
Do not stretch the cord harness.Do not pinch the power cord.Do not bend the power cord.Keep chemicals away from the
power cord.
Do not twist the power cord.Do not place any object on the
power cord.
Do not bundle power cords.
Do not use the attached power cord for any other devices or usage.
The power cord that comes with your EcoPowerGateway is designed aiming to connect with this EcoPowerGateway and to use with the EcoPowerGateway, and its safety has been tested. Do not use the attached power cord for any other purpose. Doing so may cause a fire or an electric shock.
Do not alter, modify, or repair the
power cord.
Do not secure the power cord with
staples or equivalents.
Do not use any damaged power
cord. (Replace a damaged power cord with a new one of the same specifications. Ask your service representative for replacement.)
Page 26
1-10 Notes on Using Your EcoPowerGateway
Page 27

Rack

Notes on Using Your EcoPowerGateway 1-11
WARNING
Do not use the EcoPowerGateway in any unapproved place.
Install the EcoPowerGateway on a standard EIA 19-inch rack assembly. Do not install the rack containing the EcoPowerGateway in a place inappropriate to the rack installation environment. Failure to follow these instructions may cause some bad influences to be imposed on the EcoPowerGateway and other devices installed on the rack and also a fire or personal injury due to falling of the rack may occur. For the detailed explanation on the place where the rack should be installed and the earthquake-resistant construction for the rack, refer to the manual attached to the rack or contact you service representative.
Always install the EcoPowerGateway on a rack conforming to the relevant standard.
Install the EcoPowerGateway on a rack conforming to the EIA standard. Do not use the EcoPowerGateway with installed on any other rack than standard EIA rack or without the installation on a proper rack. Failure to follow these instructions may cause the EcoPowerGateway to operate incorrectly and/or personal injury or damages of surrounding devices to occur. Contact your service representative for the racks available for the EcoPowerGateway.
Page 28
1-12 Notes on Using Your EcoPowerGateway
CAUTION
Do not provide the wiring to exceed the rating of the power supply.
To prevent burns, fires, and device damages, the power supplied to the power supply in the rack shall not exceed the rating load of the power branch circuit. Contact your electric constructor or the local power company for the requirements on the wiring and installation of electric facilities.
Do not carry or install the rack only by a single person.
At least two persons are required to carry or install the rack. Failure to follow this instruction may cause the rack to fall to result in personal injury and/or breakage of surrounding devices. In particular, a high rack (such as 44U rack) is unstable if it is not fixed by stabilizers. At least two persons must always carry or install the rack while they support it.
Do not install the rack and devices so that the load may be concentrated on a specific point.
Install stabilizers on the rack so that the total load of the rack and devices mounted on the rack is not concentrated on a singe point, or join more than one rack with each other to distribute the load. Failure to follow this instruction may cause the rack to fall to result in personal injury.
Do not install components on the rack only by a single person.
At least two persons are required to install components including the doors and rails for the rack. Failure to follow this instruction may cause some components to fall to be broken and/or to result in personal injury.
Insert hinges completely.
When installing the rack door, make sure that hinge pins at top and bottom of the door are completely inserted into the rack. Failure to follow this instruction may cause the door to fall to be broken and/or to result in personal injury.
Do not pull out a device from the rack if the rack is unstable.
Always pull out a device from the rack in the state that the rack is made stable (by the installation of stabilizers or earthquake-resistant construction).
Do not leave more than one device being pulled out from the rack.
Pulling out more than one device from the rack may cause the rack to be fallen. Only pull out a single device from the rack at a time.
Page 29
Notes on Using Your EcoPowerGateway 1-13
Page 30
1-14 Notes on Using Your EcoPowerGateway

Installation, Relocation, and Storage

WARNING
Do not install the EcoPowerGateway in any place other than specified.
Do not install the EcoPowerGateway in the following places or any place other than specified in this User's Guide. Failure to follow this instruction may cause a fire.
a dusty placea humid place such as near a boilera place exposed to direct sunlightan unstable place
Do not use the EcoPowerGateway with leaving cover and power unit being removed.
Do not use the EcoPowerGateway with the cover and power unit being removed. Failure to follow this instruction may reduce the cooling effect in the EcoPowerGateway to result in some malfunction and/or dusts to enter the EcoPowerGateway to result in a fire or electric shock.
Do not pinch your finger with rails or other components.
Note sufficiently that your fingers may not be caught between a rail and another mechanical part or cut by a rail at installation or removal of the EcoPowerGateway from the rack.
Pay attention not to drop the EcoPowerGateway.
Firmly hold the bottom of the EcoPowerGateway when installing/removing it in the rack. The rack mount bracket has no stopper or lock mechanism to prevent the EcoPowerGateway from falling down. Failure to follow this instruction may cause personal injury.
Page 31
Notes on Using Your EcoPowerGateway 1-15
CAUTION
Do not leave the EcoPowerGateway being pulled out from the rack.
Working with the EcoPowerGateway being pulled out from the rack may cause personal injury if the EcoPowerGateway drops.
Page 32
1-16 Notes on Using Your EcoPowerGateway

During Operation

CAUTION
Do not pull out or remove the EcoPowerGateway from the rack unnecessarily.
Do not pull out or remove the EcoPowerGateway from the rack unnecessarily. Pulling out or removing the EcoPowerGateway from the rack may cause not only the EcoPowerGateway to operate incorrectly but also the EcoPowerGateway to fall on people to make them injured.
Do not place any object on top of the EcoPowerGateway.
The EcoPowerGateway may fall and cause property damage to the surroundings.
Page 33
Notes on Using Your EcoPowerGateway 1-17

FOR PROPER OPERATION

Observe the following notes for successful operation of the EcoPowerGateway. Use of the EcoPowerGateway ignoring the notes will cause malfunctions or failures of the EcoPowerGateway.
EcoPowerGateway
Mount the EcoPowerGateway on a rack which can accept the EcoPowerGateway.
The socket-outlet shall be installed near the EcoPowerGateway and shall be easily
accessible.
Clear the dust adhering to the external surfaces of the EcoPowerGateway and the
ventilation hole of the power unit periodically. (See Chapter 5 for details.) Regular cleaning proactively prevents various failures of the unit.
Always use the power cable dedicated to EcoPowerGateway to connect with the target
device.
Before connecting/disconnecting the cable to/from the peripherals, be sure to turn off the
POWER switch of the EcoPowerGateway.
Before turning off the power of EcoPowerGateway, make sure that all the devices
connected with the EcoPowerGateway are powered off.
After turning off the EcoPowerGateway and Maintenance card, wait for at least 30
seconds before turning on.
When you connect the target device with the EcoPowerGateway, wait for 30 seconds or
longer before turning on the DC output switch.
After disconnecting the power cable from the connector, wait for at least 30 seconds
before connecting it again.
Before relocating the EcoPowerGateway, turn off the power, and disconnect the power
cable from the connector.
Check and adjust the system clock before the operation if any of the following conditions
is applicable.
– After carriage of the EcoPowerGateway
– After storage of the EcoPowerGateway
– After the device is entered into the pause state under the environmental condition
enduring device operation (temperature: 10 to 40°C, humidity: 20 to 80%)
Check the system clock at the rough rate of once per month.
When the system clock is installed in a system requiring high time precision, it is recommended to use a time server (NTP server).
If the system clock is remarkably delayed or advanced as the passage of time in spite of adjustment, contact your service representative to ask maintenance.
Page 34
1-18 Notes on Using Your EcoPowerGateway
Store the EcoPowerGateway under the storage condition (temperature: –10 to 55°C,
humidity: 20 to 80%, without condensation) to allow internal devices and the Maintenance card to operate correctly in the next operation.
The EcoPowerGateway contains precision component that is easily affected by drastic
temperature change. If the EcoPowerGateway is used after storage or relocation, make sure that the EcoPowerGateway is fully adapted to the operating environment.
The Maintenance Card can be powered on by pressing the Maintenance switch or using
the remote power-on feature from the management PC. In either case, you must wait for at least 30 seconds after the power is supplied to the Maintenance Card (after the AC POWER lamp on power unit is lit green). If power-on operation is performed within 30 seconds, you may fail to power on the Maintenance Card. In such a case, make sure that the power is supplied to the Maintenance Card, wait for at least 30 seconds, then press the Maintenance switch to turn on the power.
Do not perform any of the following operation during POST (including similar operations
from external applications).
– Press the POWER switch or the Maintenance switch of the EcoPowerGateway.
– Remove the power unit from the EcoPowerGateway.
– Disconnect the power cords from the power unit of the EcoPowerGateway.
Additional Power Unit and Other Electronic Components
Make sure to use optional devices supported by the EcoPowerGateway. Some non-
supported devices may be physically installed/connected but cause failures of the EcoPowerGateway as well as malfunctions of the EcoPowerGateway.
It is recommended to use options provided by NEC. Some devices of other vendors are
designed to be available for the EcoPowerGateway. If such an option causes the EcoPowerGateway to be defected or damaged, you will be charged for the repair even in the warranty period.
Turn Off the Cellular Phone or Pager
Turn off the cellular phone or pager. Radio interference may cause malfunctions of the
EcoPowerGateway.
Page 35
Notes on Using Your EcoPowerGateway 1-19

TRANSFER TO THIRD PARTY

The following must be observed when you transfer (or sell) the EcoPowerGateway to a third party:
EcoPowerGateway
Make sure to provide this manual along with the EcoPowerGateway to a third party.

DISPOSAL AND CONSUMABLES

Dispose of the EcoPowerGateway, DVD-ROM, optional power supply unit, and battery
according to all national laws and regulations. Also dispose of the power cord provided with the EcoPowerGateway to avoid diversion to some other devices.
WARNING
Ask your service representative for dispose of the battery mounted on the maintenance card.
IMPORTANT: It is the user's responsibility to completely erase or
modify all the data stored in storage device (e.g., a hard disk drive, backup data cartridge, and rewritable media such as CD-R/CD-RW) so that the data cannot be restored.
The EcoPowerGateway contains some components that are only good for a limited period
of time and require replacement. For stable operation of the EcoPowerGateway, NEC recommends you replace these components on a regular basis. Consult with your service representative for replacement or the product lives.

REGARDING THE TRANSPORTATION OF THIS SYSTEM

This system and/or associated options and accessories may be using lithium metal batteries or lithium ion batteries.
There may be restrictions regarding the air or sea transportation of such lithium batteries.
Please contact your service representative prior to transporting this system and/or its options.
Page 36
1-20 Notes on Using Your EcoPowerGateway

USER SUPPORT

Before asking for repair, do the following when the EcoPowerGateway appears to fail:
1. Check if the power cable and the cable to be connected with other devices are properly
connected.
2. See Chapter 6 to find if your problem fits the description. If it does, take the
recommended measure for it.
3. Refer to "Troubleshooting" described in the EcoPowerGateway User's Guide or Modular
Server User's Guide to find if your problem fits the description. If it does, take the recommended measure for it.
If the EcoPowerGateway still appears to fail after you have taken the above actions, consult with your service representative immediately. Take notes on lamp indications of the EcoPowerGateway and alarm indications on the display unit before consultation, which may provide a significant help to your service representative.
Page 37
Notes on Using Your EcoPowerGateway 1-21
Advice for Health
The longer you keep using the computer equipment, the more you become tired, which may cause disorders of your body. When you use a computer, observe the following to keep yourself from getting tired:
Good Working Posture
You have good posture if the following are satisfied when you use a computer:
You sit on a chair with your back straight.
Your hands are parallel with the floor when you put them on the
keyboard.
You look at the screen slightly lower than your eye height.
You have "good working posture" as described in the above when no part of your body is under excess strain, in other words when your muscles are most relaxed.
You have "bad posture" when you sit with your back hunched up or you operate a display unit with your face close to the screen. Bad working posture may cause eye strain or poor eyesight.
Adjustment of Display Unit Angles
Most display units are designed for adjustment of the horizontal and vertical angles. This adjustment is important to prevent the screen from reflecting bright lights and to make the display contents easy to see. You will not be able to keep "good working posture" and you will feel more tired than you should if you operate a display unit without adjusting horizontal and vertical angles.
Adjustment of Screen Brightness and Contrast
The display unit has brightness and contrast adjustment functions. The most suitable brightness and contrast depend on the individual and the working environment (well-lighted room or insufficient light). Adjust brightness and contrast so that the screen will be easy to see. An extremely bright or dark screen will give a bad effect to your eyes.
Adjustment of Keyboard Angle
The keyboard provided with the EcoPowerGateway is designed for adjustment of an angle. Adjust the keyboard angle at which the keyboard is easy to operate. The adjustment assists in reducing strain on your shoulders, arms, and fingers.
Cleaning of Equipment
Clean equipment regularly. It is difficult to see the display contents on a dusty screen. Keeping equipment clean is also important for your sight.
Fatigue and Rest
If you feel tired, you should stop working and do light exercises.
Page 38
1-22 Notes on Using Your EcoPowerGateway
(This page is intentionally left blank.)
Page 39
Chapter 2

General Description

This chapter provides information that you should be familiar with before using the EcoPowerGateway. It includes names and features of the components and features of the EcoPowerGateway.
Page 40
2-2 General Description

NAMES AND FEATURES OF COMPONENTS

This section describes the names and features of the components in the device.

Front View

12 3 5 7
89 10
64
11
N code
Product
name
F
1 POWER lamp (green)
Lights green when power is turned on.
2 POWER switch
Press this switch to power on or off the EcoPowerGateway.
3 UID (Unit ID) lamp (blue)
This lamp lights when the UID switch is pressed. When the EcoPowerGateway receives a software command, this lamp blinks. (The same lamp is located on the rear side. They work together.)
Serial No.
Barcode
Page 41
General Description 2-3
4 UID (Unit ID) switch
Press this switch to turn on or off the UID (Unit ID) lamp. (The same lamp is located on the rear side. You can use either one.)
5 STATUS lamp (green/amber)
This lamp indicates the current status of EcoPowerGateway. See "Lamp Indications" for details.
6 Maintenance switch
Press this switch to power on or off the maintenance card installed in the EcoPowerGateway. Pressing this switch for 4 seconds or longer forcedly power off the maintenance card.
7 Maintenance lamp (green)
Lights green when the maintenance card is powered on.
8 Serial port connector
Used to connect with the device having the serial interface. Not used in usual operation.
9 USB connector
Used to connect with the device having the USB interface. Not used in usual operation.
10 Display connector
Used to connect with the display unit.
11 Sliding tag (front)
A label indicating the model name and the serial number is attached on this tag.
Page 42
2-4 General Description

Rear View

1-4 1-3 1-2 1-1
9
2-4 2-3 2-2 2-1
3-4 3-3 3-2
4-4 4-3 4-2 4-1
1 Slot for power supply unit
Install the power supply unit that supplies DC power to the Module Enclosure. The last digit indicates installation order. Slots 1 and 2 contain factory-installed power units. Slots 3 and 4 are equipped with blank covers. Install the separately priced N8181-76F power units into these slots to make the maximum configuration with four power supply units.
2 DC output lamp
Lights green when DC output is turned on. Goes off when DC output is turned off. The last digit indicates the corresponding DC output port.
3-1
85
7
6
3 DC output switch
Press this switch to turn on or off the DC output. The last digit indicates the corresponding DC output port.
4 DC output port
Supplies DC power to the target device. Connect the dedicated cable to this port. The last digit indicates the port number.
5 Management port
Connector that accepts 100BASE-TX/10BASE-T interface.
Page 43
General Description 2-5
6 UID (Unit ID) lamp (blue)
This lamp lights when the UID switch is pressed. When the EcoPowerGateway receives a software command, this lamp blinks. (The same lamp is located on the front side. They work together.)
7 UID (Unit ID) switch
Press this switch to turn on or off the UID (Unit ID) lamp. (The same lamp is located on the front side. You can use either one.)
8 Sliding tag (rear)
A label indicating the rating of DC output port and precautions is attached on this tag.
9 AC inlet
Connect the power cord to this socket.
Page 44
2-6 General Description
Number of Required Power Units
The number of power units to be installed depends on the total power consumption for the devices connected to each DC output port. See the table below.
IMPORTANT:
Install the power units of same model. If the power units of different
model are installed, the system will fail to operate correctly.
Install the sufficient number of power units according to the table
shown below. Insufficient power supply may cause stoppage of the EcoPowerGateway and other devices connected with the EcoPowerGateway.
Use the dedicated DC cable K410-213 for connection with DC
output port. Before connection, make sure that the DC output switch is turned off.
When DC output switch is turned on, the electric power of high
current flows. Never touch the K410-213 DC cable while the power is being supplied.
The DC output port of EcoPowerGateway does not support the hot-
swap mode. Be sure to turn off the relevant DC output switch before disconnecting the DC output port.
Total power consumption
630 W or less 2 (factory-installed) 1140 W or less 3 1700 W or less 4
Number of required power units (N+1 redundant power supply)
Page 45
General Description 2-7

Lamp Indications

This section explains the indication and meanings of the lamps on the EcoPowerGateway.
Lamps on Front Side
STATUS
POWER
lamp
UID (Unit ID)
lamp
lamp
Maintenance
lamp
POWER Lamp ( )
The POWER lamp goes on green while the EcoPowerGateway is powered on. It goes off when the EcoPowerGateway is powered off.
UID (Unit ID) Lamp
The UID lamp goes on when either of the UID (Unit ID) switches on the front and rear sides of the EcoPowerGateway is pressed. It goes off when the UID switch is pressed again. The UID lamp allows you to identify the device you are working on among the several devices in the rack.
The UID lamp goes on when the UID switch is pressed, and it blinks when the command is received from the management software such as NEC ESMPRO Manager.
Page 46
2-8 General Description
STATUS Lamp ( )
The STATUS lamp goes on green while the EcoPowerGateway works normally. If the STATUS lamp blinks amber, it indicates that the EcoPowerGateway is in abnormal state. You can view the detailed error information on virtual LCD while the STATUS lamp is blinking amber. You can access the virtual LCD through the Web browser of NEC EXPRESSSCOPE Engine 2 (BMC) or NEC ESMPRO Manager. See Chapter 6 for indications on virtual LCD, their meanings, and actions to be taken.
Contact your service representative when an error occurs on your EcoPowerGateway.
Indication of STATUS lamp
On Green
Off The EcoPowerGateway is off-
Blinking Amber Refer to "When STATUS lamp is blinking in amber" in Chapter 6
Stay lit Amber Refer to "When STATUS lamp is lighting in amber" in Chapter 6
Color Meaning Action to take
The EcoPowerGateway works normally.
powered.
for details of indication on virtual LCD.
for details of indication on virtual LCD.
Power on the EcoPowerGateway.
Maintenance Lamp
The Maintenance lamp goes on while the maintenance card installed in the EcoPowerGateway is powered on. It goes off when the maintenance card is off-powered.
Page 47
Lamps on Rear Side
General Description 2-9
AC POWER lamp
UID (Unit ID) lamp
DC output lamp 4 DC output lamp 2
DC output lamp 3
DC output lamp 1
100/10 lamp
LINK/ACT lamp
AC POWER Lamp
The AC POWER lamp is located on the power unit at the rear side of the EcoPowerGateway.
The lamp starts blinking in green when the power cord is connected to the AC inlet and the power is supplied to the power unit.
The lamp stays lit green when the power of the EcoPowerGateway is turned on (the DC power is supplied to the main unit).
If the AC POWER lamp is not lit even when the EcoPowerGateway is turned on, or lit or blinking in amber (*1), the power unit may be faulty.
*1 If the several power units are installed in the EcoPowerGateway and some of them are accepting
AC power through the connected power cord, the AC POWER lamp on the power unit to which no power cord is connected blinks amber. The AC POWER lamp on such a power unit starts blinking green when the power cord is connected. If the AC POWER lamp still blinks in amber, check if AC power is properly supplied to that power unit. If the power is normally supplied, the power unit may be faulty.
DC Output Lamp 1 to 4
DC output lamp goes on green while the DC power is output from the DC output port. It goes off when DC output is turned off. The lamp blinks when the POWER switch is turned off (the EcoPowerGateway is off-powered) and the DC output switch is turned on.
Page 48
2-10 General Description
UID (Unit ID) Lamp
The UID lamp goes on when either of the UID (Unit ID) switches on the front and rear sides of the EcoPowerGateway is pressed. It goes off when the UID switch is pressed again. The UID lamp allows you to identify the device you are working on among the several devices in the rack.
The UID lamp goes on when the UID switch is pressed, and it blinks when the command is received from the management software such as NEC ESMPRO Manager.
LINK/ACT Lamp ( )
The LINK/ACT lamp indicates the status of the management LAN port of the EcoPowerGateway (LINK). While the connection between the EcoPowerGateway and management PC is correct, the lamp is on. The lamp blinks while the management LAN port is transmitting/receiving data (ACT).
If the lamp does not go on when the LINK state is placed, check if the network cable is in normal state and if it is connected correctly. If the lamp does not go on yet when the network cable is normal, the network (LAN) controller may be faulty. In this case, contact your service representative.
100/10 Lamp
The management LAN port supports 100BASE-TX (100Mbps) and 10BASE-T (10Mbps) network interface.
The 1000/100/10 lamp indicates whether the management LAN port is operated through the 100BASE-TX or 10BASE-T network interface.
If the lamp is lit green, the management LAN port is operated through 100BASE-TX. If the lamp is off, the management LAN port is operated through 10BASE-T.
Page 49
General Description 2-11

USING YOUR EcoPowerGateway

This section describes the basic operation of the EcoPowerGateway.

Power-on of EcoPowerGateway

Press the POWER switch on the front side of the EcoPowerGateway and make sure that the POWER lamp goes on green.
POWER switch POWER lamp
IMPORTANT:
The power of the EcoPowerGateway must be turned on after 30
seconds or longer has passed from the previous power-off. If power-on operation is performed within 30 seconds, you may fail to power on the EcoPowerGateway. In such a case, make sure that the power is supplied to the EcoPowerGateway, then press the POWER switch again to turn on the power.
Before the management PC can remotely control the
EcoPowerGateway through the management port, the power of the EcoPowerGateway must be turned on.
Page 50
2-12 General Description

DC Output ON/OFF

Take the following procedure to output 12VDC power to the server unit or Module Enclosure containing the modular servers, connected with the EcoPowerGateway.
1. Prepare the separately priced K410-213 DC cable.
IMPORTANT: Do not use any other cable than K410-213(xx).
xx denotes the cable length and branched or not. Contact your service representative for the cable appropriate to your requirement.
2. Make sure that the DC output port you are going to connect is turned off (DC output lamp
is unlit).
Make sure that the DC output lamp is off.
If the DC output lamp is on, press this switch to turn it off.
Port you are going to connect the DC cable
IMPORTANT:
Do not hot-swap the DC cable.
Do not turn on the DC output port to which the DC cable is not
connected.
Do not turn on the DC output port before the other end of DC cable
is not connected to any port.
Page 51
General Description 2-13
3. Connect the EcoPowerGateway with the server unit or Module Enclosure.
The cable connectors have locking mechanism. Make sure that the cable connector is surely locked.
Module enclosure EcoPowerGateway
K410-213 DC cable
Insert the connector to the end until it clicks. To disconnect the connector, push both sides of the connector with your fingers to unlock the connector, as shown in the figure.
IMPORTANT: Incomplete locking of DC cable connector may cause power leakage, electric shock due to the spark, hardware failure as well as malfunction of the EcoPowerGateway.
4. Push the DC output switch to the end.
Make sure that the DC output lamp goes on green.
DC output switch
The DC output switch is a latch-type pushbutton switch and equipped on every four output ports. DC output ON: Concave DC output OFF: Convex
Rear of the EcoPowerGateway
DC output lamp
DC power output ON: Lit green DC power output OFF: Unlit
Page 52
2-14 General Description
IMPORTANT: Never attempt to connect/disconnect the DC cable while the DC power is being output. The DC cable and output port connectors on Module Enclosure and EcoPowerGateway do not support hot-swap mode.
5. To turn off the DC power output, shutdown all the server units connected with the
EcoPowerGateway and blade servers in enclosure, then press the DC output switch.
After that, make sure that the DC output lamp is unlit.
To remove the DC cable, perform reverse order of installation procedure.
NOTE: Refer to the User's Guide of the server unit or enclosure unit
for how to power off the server unit or enclosure unit.
Page 53
General Description 2-15

Starting Maintenance Mode

The maintenance card installed in the EcoPowerGateway monitors the system status (e.g., thermal sensor and load to power units).
Start the maintenance mode only when you need to update the firmware of maintenance card, change configuration information of the server, or provide settings for the management LAN. To start the maintenance mode, press the Maintenance switch on the front side.
In usual operation, the maintenance mode should be turned off.
Maintenance switch
Maintenance
lamp
Device with serial
interface
USB device
Keyboard
1. Connect peripheral devices to the relevant connectors on the front side.
Connect a display unit to the monitor connector if you want to view the maintenance mode screen on display unit. Connect a console to the serial port if you want to view the maintenance mode screen on serial console.
If you use the display unit to view the screen, you need to connect the keyboard to the USB connector.
Display
unit
Page 54
2-16 General Description
2. Press the Maintenance switch on the front side to start the maintenance mode.
The maintenance mode should be turned off in usual operation.
To prevent an incorrect operation, use the thin rod such as a pin to press the switch.
Maintenance switch Press this switch using a pin or the like.
Maintenance lamp When pressed the Maintenance switch, make sure that this lamp goes on green.
3. The initial diagnosis menu of maintenance card is displayed on the screen.
Perform the necessary operation according to BIOS SETUP menu or firmware update procedure. See Chapter 4 for details.
Page 55
General Description 2-17

Power-off of EcoPowerGateway

Take the following steps to power off the EcoPowerGateway.
1. Shutdown all of the server units connected or modular servers in Module Enclosure.
2. Press every DC output switch to turn off the DC output. (Make sure that all of the DC
output lamps are unlit.)
3. Remove all the DC cables from the EcoPowerGateway.
4. Press the POWER switch on front side to turn the power off. (Make sure that the POWER
lamp is unlit.)
5. Remove all the power cords from the power supply units on the rear side.
IMPORTANT: Be sure to turn off the DC output switch before
disconnecting the power cable.

Device Identification

To identify the device to be maintained among more than one device, UID (Unit ID) lamp is used.
The UID switches and UID lamps are located both on front and rear of the EcoPowerGateway.
The UID lamp allows you to identify the device subject to maintenance among more than one device installed in the Module Enclosure.
The UID lamp on modular server can also be made blinking blue by proper software commands from the management PC on the network. In addition, pressing the UID switch on the EcoPowerGateway brings the UID lamp to light.
Page 56
2-18 General Description
(This page is intentionally left blank.)
Page 57
Chapter 3

Setting Up Your EcoPowerGateway

This chapter describes installation and connection of the EcoPowerGateway.

Installation

To use the EcoPowerGateway, install it on a rack assembly conforming to EIA standard.
Installing Rack
Refer to the manual attached to the rack or contact your service representative for the installation of the EcoPowerGateway on the rack.
WARNING
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may result in death or serious personal injury. See pages 1-4 to 1-16 for details.
Do not use the EcoPowerGateway in any unapproved place.
Do not connect the ground line to a gas pipe.
CAUTION
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may cause a fire, personal injury, or property damage. See pages 1-4 to 1-16 for details.
Do not install the rack where the load may be concentrated on a specific
point.
Do not install any component on the rack only by a single person.
Insert the hinge pins completely.
Do not pull out a device from the rack if the rack is unstable.
Do not leave more than one device being pulled out from the rack.
Do not provide the wiring exceeding the rating power.
Do not use the rack in a place where corrosive gases exist.
Page 58
3-2 Setting Up Your EcoPowerGateway
IMPORTANT: Rack Mount Instructions
Elevated Operating Ambient - If installed in a closed or multi-unit
rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer.
Reduced Air Flow - Installation of the equipment in a rack should
be such that the amount of air flow required for safe operation of the equipment is not compromised.
Mechanical Loading - Mounting of the equipment in the rack should
be such that a hazardous condition is not achieved due to uneven mechanical loading.
Circuit Overloading - Consideration should be given to the
connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.
Reliable Earthing - Reliable earthing of rack-mounted equipment
should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips).
Page 59
Setting Up Your EcoPowerGateway 3-3
Do not install the rack in the places listed below. Installing the rack or mounting the EcoPowerGateway on the rack in such a place may cause some malfunction to occur.
Narrow space from which devices cannot be pulled out from the rack completely
Place that cannot bear the total weights of the rack and devices mounted on the rack
Place where stabilizers cannot be installed or where the rack can be installed only after the
practice of proper earthquake-resistant construction
Place of uneven or slanting floor
Place of drastic temperature change (near a heater, air conditioner, or refrigerator)
Place where intense vibration may be generated
Place where corrosive gases (sulfur dioxide, hydrogen sulfide, nitrogen dioxide, chlorine,
ammonia, ozone, etc) exist. Place where the air (or dust) includes components accelerating corrosion (ex. sulfur, sodium chloride) or conductive metals.
Place where chemicals may be accidentally sprayed over
Place where a carpet not subject to anti-static process is laid.
Place where some objects may be fallen on the rack
Place near a device generating intense magnetic field (such as a TV, radio,
broadcast/communication antenna, power transmission wire, and electromagnetic crane) is placed (If unavoidable, contact your service representative to request proper shield construction.)
Place where the power cord of the EcoPowerGateway must be connected to an AC outlet
that shares the outlet of another device with large power consumption.
Place near equipment that generates power noise (e.g., contact spark at power-on/power-
off of commercial power supply through a relay). If you must install the EcoPowerGateway close to such equipment, request your service representative for separate power cabling or noise filter installation.
IMPORTANT: Increase in temperature within rack and air flow
If two or more devices are installed on the rack or the ventilation within the rack is not enough, the temperature in the rack may be raised by the heat generated from the devices to be higher than the operation temperature of the EcoPowerGateway (10 to 40°C).
It causes the EcoPowerGateway to operate improperly. Review the air flow within the rack or in the room and take sufficient measures so that the temperature within the rack does not exceed the warranted temperature range during the system operation.
The EcoPowerGateway takes in the air from the front and exhausts it to the rear.
Page 60
3-4 Setting Up Your EcoPowerGateway
Installing/Removing the EcoPowerGateway in/from Rack
This subsection provides the instructions for installing the EcoPowerGateway into a rack cabinet. (This subsection also describes the removal procedures.)
If you are going to use the non-NEC rack, make sure that the rack is compliant to EIA standard and it can accept the EcoPowerGateway. Contact your service representative for applicable rack.
WARNING
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may result in death or serious personal injury. See pages 1-4 to 1-16 for details.
Do not use any rack which does not conform to the relevant standard.
Always use the EcoPowerGateway in the specified place.
CAUTION
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may cause a fire, personal injury, or property damage. See pages 1-4 to 1-16 for details.
Do not carry the EcoPowerGateway with the power units being installed.
Do not install the EcoPowerGateway in any other place than specified.
Do not install the EcoPowerGateway on the rack leaving the cover
removed.
Do not pinch your finger with mechanical components.
Page 61
Setting Up Your EcoPowerGateway 3-5
Checking Components
Refer to the Packing List to make sure that all the components have contained in carton box.
Installation
This EcoPowerGateway can be installed in either the NEC rack or a third vendor's rack. If you are going to use the non-NEC rack, make sure that the rack is compliant to EIA standard and it can accept the EcoPowerGateway. Contact your service representative for applicable rack.
Take the following steps to install the EcoPowerGateway in the rack.
Preparation for installation
The slide rail assembly contains inner rails (to be attached to the EcoPowerGateway) and outer rails (to be attached to the rack). First, remove the outer rails before installation.
IMPORTANT: The two sliding rails are provided with the EcoPowerGateway. Assort the inner and outer rails exactly same as they were at the shipment.
One outer rail for left side
One outer rail for right side
Page 62
3-6 Setting Up Your EcoPowerGateway
Installing the outer rail
Insert the square projection of the outer rail into the angle hole on the 19-inch rack until it is locked with clicking sound.
The figure below shows the right side (front) of the rack. Install the rail assemblies to the right side (rear), and left side (front and rear) of the rack in the same procedure.
Make sure that the rail assembly is installed at the same level as the other slide rail assembly already installed.
NOTES:
There may be some backlashes in the front and rear, however, it is
not a deficiency.
Make sure that the rail assembly is surely locked to the rack.
Page 63
Setting Up Your EcoPowerGateway 3-7
Installing the EcoPowerGateway
CAUTION
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may cause a fire, personal injury, or property damage. See pages 1-4 to 1-16 for details.
Do not pinch your finger with mechanical components.
1. Pull out the sliding rails (bearing portion) of the right and left outer rails.
Outer rail
Sliding rail
2. Securely hold the EcoPowerGateway and install it in the rack.
Firmly insert the inner rails at the sides of the EcoPowerGateway into the left and right outer rails, and then slowly push the EcoPowerGateway into the rack.
When the EcoPowerGateway is completely pushed into the rack, the EcoPowerGateway is locked.
Outer rails
Inner rail at EcoPowerGateway side
Page 64
3-8 Setting Up Your EcoPowerGateway
IMPORTANT:
Be very careful not to get your finger caught in the rails.
Insert both sides of inner rails straight into the rack.
Hold the handles on both sides of the EcoPowerGateway, and install
the EcoPowerGateway carefully while making sure the installation position.
NOTE: At the first installation, you may feel strong friction in pushing
because the mechanical components cannot be completely engaged with each other. Push the EcoPowerGateway intensely.
3. Make sure that the sliding rails move smoothly by pulling the EcoPowerGateway out of
the rack and pushing it in several times.
NOTE: To install the EcoPowerGateway in the location adjacent to the
other device, pay attention to interference. If the installing EcoPowerGateway disturbs the other devices already been installed, adjust the position, and install the outer rail again.
Page 65
Setting Up Your EcoPowerGateway 3-9
Removing the EcoPowerGateway
Remove the EcoPowerGateway from the rack in the following procedure.
CAUTION
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may cause a fire, personal injury, or property damage. See pages 1-4 to 1-16 for details.
Do not pinch your finger with mechanical components.
Do not pull out a device from the rack if the rack is unstable.
Do not leave more than one device being pulled out from the rack.
Do not pull out the EcoPowerGateway from the rack while it is operating.
Pay attention not to drop the EcoPowerGateway.
1. Make sure that the EcoPowerGateway is off-powered, and disconnect the power cables
and all the interface cables from the EcoPowerGateway.
NOTE: Make sure that the Power lamp at the front side is unlit.
2. While pushing the left and the right unlock buttons on the front of the EcoPowerGateway,
pull out the EcoPowerGateway from the rack slowly and carefully.
Push this button to unlock the EcoPowerGateway.
Page 66
3-10 Setting Up Your EcoPowerGateway
NOTE: Push the two unlock buttons on left and right side of the
EcoPowerGateway at the same time.
Left side Right side
3. Firmly hold the EcoPowerGateway, and take it out from the rack.
IMPORTANT:
Pull out the EcoPowerGateway slowly holding the bottom of the
EcoPowerGateway.
Be very careful not to get your finger caught in the rails.
4. To remove the outer rail from the rack, pull the rail toward the direction shown by the
arrow while pushing the lever.
Lever
Page 67
Setting Up Your EcoPowerGateway 3-11

Making Connections

Connect the power supply unit, DC cable, and LAN cable to the EcoPowerGateway.
Two slots for installing additional power unit are located on the rear side of the EcoPowerGateway.
At the rear side, connector for outputting 12 VDC power from the EcoPowerGateway, and LAN ports for communicating with management PC are located.
The figure on the next page illustrates available power supply units in the standard configuration and locations of the connectors for the cables.
IMPORTANT: Consult with your service representative if you want to connect the EcoPowerGateway to server switch unit and configure it.
WARNING
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may result in death or serious personal injury. See pages 1-4 to 1-16 for details.
Do not hold the power plug with a wet hand.
Do not connect the ground wire to a gas pipe.
CAUTION
Observe the following instructions to use the EcoPowerGateway safely. Failure to follow these instructions may cause a fire, personal injury, or property damage. See pages 1-4 to 1-16 for details.
Do not plug the power cord in to an improper power source.
Do not connect the power cord to an outlet that has an illegal number of
connections.
Insert the power plug into the outlet as far as it goes.
Use the authorized power cord only.
Do not connect any interface cable with the power cord of the
EcoPowerGateway plugged to a power source.
Do not use any unauthorized interface cable.
Page 68
3-12 Setting Up Your EcoPowerGateway
Front Side
The port on the front side is for maintenance or management port. The peripherals shown in the figure are connected when Maintenance switch is turned on.
Serial interface
device
Display unit
USB device
(e.g., keyboard)
Page 69
Rear Side
N8181-76F Additional
power units
(separately-priced)
Setting Up Your EcoPowerGateway 3-13
Finally connect the provided power cords to the receptacle.
Connect the server unit or Module Enclosure that has the same interface with the dedicated DC cable (K410-213).
*1) Two USB ports are supported. Use the USB hub as needed. The USB hub should have the self-power
specification if it is used.
*2) Only one separately-priced N8160-64 or N8160-85 external DVD-ROM drive can be connected to the USB
port.
Network system on LAN (connected via a multi-port repeater) (for management)
IMPORTANT: To connect a peripheral or interface cable provided by a vendor other than NEC (or third party) to the EcoPowerGateway, make sure that the device is available for the EcoPowerGateway. Some third party devices are not available for the EcoPowerGateway.
Page 70
3-14 Setting Up Your EcoPowerGateway
Route the cables (LAN cable and power cable) so that they do not block the ventilation hole of cooling fan.
IMPORTANT:
The cooling fans are located in the power unit. If the rear side of the
power unit is blocked, the cooling effect of the maintenance card or the electric component becomes insufficient. It may cause malfunction of the EcoPowerGateway.
Form the cables in such a way that they will not come into contact
with the door or the guide rails on the sides of the rack.
Page 71
Chapter 4

Configuring Your EcoPowerGateway

This chapter describes Basic Input Output System (BIOS) configuration.
When you install the EcoPowerGateway for the first time or configure the management LAN, thoroughly read this chapter for better understanding and correct setups.

SYSTEM BIOS ~ SETUP ~

The SETUP utility is provided to make basic configuration for the maintenance card of EcoPowerGateway. This utility is pre-installed in the flash memory on the maintenance card of EcoPowerGateway and ready to run.
The Maintenance card is configured with the correct parameters using the SETUP utility and shipped in the best conditions. Thus, you do not need to use the SETUP utility in most cases. However, you might wish to use the SETUP utility in the cases described below.
IMPORTANT:
The SETUP utility is intended for system administrator use only.
The SETUP utility allows you to set a password. The Maintenance
card is provided with two levels of password: Supervisor and User. With the Supervisor password, you can view and change all system parameters of the SETUP utility. With the User password, system parameters available for viewing and changing are limited.
The Maintenance card contains the latest version of the SETUP
utility. Dialog boxes appear on your SETUP utility, thus, may differ from descriptions in this manual. If you find anything unclear, see the online help or ask your service representative.
Page 72
4-2 Configuring Your EcoPowerGateway

Starting SETUP Utility

Powering on the Maintenance card starts POST (Power On Self-Test) and displays its check results. If the NEC logo is displayed, press Esc.
After a while, the following message appears at bottom left on the screen. The message depends on the status of your Maintenance card.
Pattern 1:
Press <F2> to enter SETUP
Pattern 2:
Press <F2> to enter SETUP or <F12> to Network
Pattern 3:
Press <F1> to resume, <F2> to enter Setup, <F12> to Network
Press F2 to start the SETUP utility and display its Main menu.
If you have previously set a password with the SETUP utility, the password entry screen appears. Enter the password.
Enter password [ ]
Password entry is accepted up to three times. If you fail to enter the correct password for three consecutive times, the Maintenance card halts. (You can no longer proceed.) Power off the Maintenance card.
NOTE: The Maintenance card is provided with two levels of
password: Supervisor and User. With the Supervisor password, you can view and change all system parameters. With the User password, system parameters available for viewing and changing are limited.
Page 73
Configuring Your EcoPowerGateway 4-3

Description on On-Screen Items and Key Usage

Use the following keyboard keys to work with the SETUP utility. (Key functions are also listed at the bottom of the screen.)
Indicates the current menu.
Indicates there are submenus.
Online help window
Setup item
menu
Explanation of key functions
Cursor (↑, ):
Selects an item on the screen. The highlighted item is currently
Parameter (high-lights upon selection) menu
selected.
Cursor (←, →): – and +:
Selects the Main, Advanced, Security, Server, Boot, or Exit menu. Changes the value (parameter) of the selected item. When a
submenu option (an option preceded by "
³") is selected, these
keys are disabled.
Enter Press Enter to select (determine) parameters. Esc
Displays the previous screen.
F1: Press F1 when you need help on SETUP operations. The help
screen for SETUP operations appears. Press Esc to return to the previous screen.
F9: Sets the parameter of the currently displayed item back to the
default (may differ from the factory set parameter).
F10:
Saves the parameter value and exit SETUP utility.
Page 74
4-4 Configuring Your EcoPowerGateway

Configuration Examples

The following describes examples of configuration required to use software-link features or for system operations.
Time and Date Settings
Select [Main] - [System Time].
Select [Main] - [System Date].
Set the current date and time before starting the system.
Boot
To change the boot order of devices connected to the EcoPowerGateway
Select [Boot] and specify the boot order.
To display POST check results
Select [Advanced] - [Boot-time Diagnostic Screen] - [Enabled].
You can also press Esc while the NEC log is on the screen to display POST check results.
To use the remote wakeup feature of Maintenance Card
Via Modem:
Select [Advanced] – [Advanced Chipset Control] – [Wake on Ring] – [Enabled]
Via RTC alarm:
Select [Advanced] – [Advanced Chipset Control] – [Wake on RTC Alarm] – [Enabled]
To control from the HW console
Select [Server] - [Console Redirection] and set each item.
Page 75
Memory
To check the installed memory (DIMM) status
Select [Advanced] - [Memory Configuration] - [DIMM# Status] and check the status indications.
To clear the memory (DIMM) error information
Select [Advanced] - [Memory Configuration] - [Memory Retest] - [Yes] and reboot the system.
Processor
To check the installed processor status
Select [Main] - [Processor Settings] and check the status indications.
Keyboard
To set Numlock
Select [Advanced] - [Numlock] – [On]/[Off].
Configuring Your EcoPowerGateway 4-5
Security
To set passwords on the BIOS
Select [Security] - [Set Supervisor Password] and enter a password.
Set Supervisor password first, then set User password.
To enable/disable the Maintenance switch
To disable
Select [Security] - [Power Switch Inhibit] - [Enabled].
To enable
Select [Security] - [Power Switch Inhibit] - [Disabled].
To set this item, the Supervisor and User passwords must have been set.
IMPORTANT: Even if [Power Switch Inhibit] is set to [Enabled], the
forced shutdown is still available.
Page 76
4-6 Configuring Your EcoPowerGateway
External Devices
To set up external devices
Select [Advanced] - [Peripheral Configuration] and set up each device.
Internal Devices
To clear the hardware configuration data (after installing/removing internal devices)
Select [Advanced] - [Reset Configuration Data] - [Yes] and reboot the system.
Saving the Configuration Data
To save the BIOS configuration data
Select [Exit] - [Exit Saving Changes] or [Save Changes].
To discard changes to the BIOS configuration data
Select [Exit] - [Exit Discarding Changes] or [Discard Changes].
To resume the default BIOS configuration data (may differ from factory-set value)
Select [Exit] - [Load Setup Defaults].
To save the current settings as user-defined configuration
Select [Exit] – [Save Custom Defaults].
To load the user-defined configuration data
Select [Exit] – [Load Custom Defaults].
Page 77
Configuring Your EcoPowerGateway 4-7

Menu and Parameter Descriptions

The SETUP utility has the following six major menus:
Main
Advanced
Security
Server
Boot
Exit
To set minute functions, select a submenu from the above menus. The following describes available functions and parameters, as well as the factory-set, for each menu.
Page 78
4-8 Configuring Your EcoPowerGateway
Main
Option Parameter Description Your Setting
System Time HH:MM:SS Set the time. System Date MM/DD/YYYY Set the date. Hard Disk Pre-
Delay
SATA Port 0 Information
Processor Settings N/A Language
Disabled 3 seconds [6 seconds] 9 seconds 12 seconds 15 seconds 21 seconds 30 seconds
[English] Français Deutsch Español Italiano
When accessing the SATA hard disk drive for the first time during POST, the system waits for the specified time until the hard disk drive becomes ready.
Shows the information on the device connected to each channel, on the submenu. The settings of some items may be changed. However, leave the items as factory-set.
Select which language BIOS SETUP displays.
[ ]: Factory-set
IMPORTANT: Check and adjust the system clock before the
operation if any of the following conditions is applicable.
After carriage of deviceAfter storage of deviceAfter the device is entered into the pause state under the
environmental condition enduring device operation (temperature:
10°C - 40°C, humidity: 20% - 80%) Check the system clock at the rough rate of once per month. When the system clock is installed in a system requiring high time precision, it is
recommended to use a time server (NTP server).
If the system clock is remarkably delayed or advanced as the passage of time in spite of adjustment, contact your service representative for maintenance.
Page 79
Configuring Your EcoPowerGateway 4-9
Processor Settings
Option Parameter Description Your Setting
Processor Speed Setting
Processor CPUID
Processor L2 Cache
Hyper­Threading Technology
Execute Disable Bit
Intel SpeedStep(R) Technology
C1 Enhanced Mode
Indicates the clock speed of the processor.
Indicates the ID of processor. (View only)
Indicates the L2 cache of processor. (View
only) Disabled [Enabled]
Disabled [Enabled]
Disabled [Enabled]
Disabled [Enabled]
With this feature, a single physical processor
can work as two logical processors. This
menu appears only when the processor
supports this feature.
Specify whether HW DEP feature on OS is
enabled or disabled.
This menu appears only when the processor
supports this feature.
Specify whether Enhanced Intel
SpeedStep(R) Technology feature is enabled
or disabled.
If the CPU does not support this feature, this
item is not visible.
Specify whether the Enhanced Halt State
(C1E) feature of Intel processor is enabled or
disabled.
This menu appears only when the processor
supports this feature.
[ ]: Factory-set
Page 80
4-10 Configuring Your EcoPowerGateway
Advanced
Option Parameter Description Your Setting
Memory Configuration
PCI Configuration
Peripheral Configuration
Advanced Chipset Screen
Boot-time Diagnostic Screen
Reset Configuration Data
NumLock On
N/A
N/A
N/A
N/A
[Disabled] Enabled
[No] Yes
[Off]
Specify whether the self-diagnosis (POST) running screen is displayed or not on booting.
If this item is set to "Disabled", the NEC logo appears during POST. (Pressing Esc in the status causes the screen display to be switched to the POST running screen.
If [Enabled] is specified for [Server] - [Console Redirection] - [BIOS Redirection Port], the POST running screen is automatically displayed.
Select "Yes" to clear the system configuration data (system information stored by POST). The parameter is changed to "No" after the system is booted.
Specify whether the Numlock feature is enabled or disabled on booting.
[ ]: Factory-set
Page 81
Configuring Your EcoPowerGateway 4-11
Memory Configuration
Option Parameter Description Your Setting
Installed memory Available under 4GB DIMM1 Status
DIMM2 Status
Memory Retest
Extended RAM Step
Indicates the capacity of mounted memory.
(View only)
Indicates the capacity of memory available in
the area smaller than 4GB. (View only)
Normal Error
Normal [Not installed] Error
[No] Yes
1MB 1KB [Every Location] Disabled
Indicates the current memory status.
"Normal" indicates the normal status, and
"Error" indicates the memory error. (View
only).
Indicates the current memory status.
"Normal" indicates the normal status, "Error"
indicates the memory error, and "Not
installed" indicates no DIMM is installed.
(View only).
Set to "Yes" to clear the error information on
the memory, and perform retest. The
parameter is changed to "No" after the
system is booted.
1MB: The memory test is performed in the
unit of 1MB.
1KB: The memory test is performed in the
unit of 1KB.
Every-location: Every memory device is
tested.
Disabled: Only memory initialization is
performed.
[ ]: Factory-set
Page 82
4-12 Configuring Your EcoPowerGateway
PCI Configuration
Option Parameter Description Your Setting
Onboard NIC N/A
[ ]: Factory-set
Onboard NIC
IMPORTANT: Always use the "Onboard NIC" submenu with the
factory-set value.
Option Parameter Description Your Setting
LAN Controller 1 [Disabled]
Enabled
LAN#1 Option ROM Scan Disabled
[Enabled]
PXE/iSCSI Select [PXE]
iSCSI
LAN Controller 2 [Disabled]
Enabled
LAN#2 Option ROM Scan Disabled
[Enabled]
PXE/iSCSI Select [PXE]
iSCSI
Specify whether the LAN controller 1 is
enabled or disabled.
Specify whether the extraction of BIOS
of LAN controller 1 is enabled or
disabled.
Specify the ROM to be extracted for
LAN controller 1.
Specify whether the LAN controller 2 is
enabled or disabled.
Specify whether the extraction of BIOS
of LAN controller 2 is enabled or
disabled.
Specify the ROM to be extracted for
LAN controller 2.
[ ]: Factory-set
Page 83
Configuring Your EcoPowerGateway 4-13
Peripheral Configuration
IMPORTANT: Make sure to avoid any conflict in the interrupt
requests or the base I/O addresses. If an assigned value is already used by another resource, it appears in yellow. Any yellow value must be re­assigned.
Option Parameter Description Your Setting
Serial Port Disabled
[Enabled]
Base I/O Address [3F8h]
2F8h 3E8h 2E8h
Interrupt IRQ 3
[IRQ 4]
USB 2.0 Controller Disabled
[Enabled]
Serial ATA Disabled
[Enabled]
SATA AHCI [Disabled]
Enabled
Specify whether serial port is enabled or disabled.
Specify the base I/O address for serial port.
Specify the interrupt request (IRQ) for serial port.
Specify whether the USB 2.0 controller is enabled or disabled.
Specify whether the onboard SATA controller is enabled or disabled. Do not change this item to "Disabled" in normal operation.
The AHCI (Advanced Host Controller Interface) is always disabled on this system. This option is view only. This menu appears only when [Serial ATA] is enabled.
[ ]: Factory-set
Page 84
4-14 Configuring Your EcoPowerGateway
Advanced Chipset Control
Option Parameter Description Your Setting
Multimedia Timer [Enabled]
Disabled
Wake On LAN/PME
Wake On Ring Enabled
Wake On RTC Alarm
Enabled [Disabled]
[Disabled]
Enabled [Disabled]
Specify whether the timer supporting a
multimedia is enabled or disabled.
Specify whether the remote power-on
feature through the device connected
to the standard network card is
enabled or disabled. To use Wake On
LAN feature, set the link speed and
duplex to [Auto].
Specify whether the remote power-on
feature through a serial port (modem)
is enabled or disabled.
Specify whether the remote power-on
feature by using RTC (Real Time
Clock) alarm is enabled or disabled.
[ ]: Factory-set
NOTE: The EcoPowerGateway does not support the Wake On LAN
feature.
Page 85
Configuring Your EcoPowerGateway 4-15
Security
Select "Set Supervisor Password" or "Set User Password" and press Enter to display the pop-up screen. Note that User password setup is not available before Supervisor password setup.
Set a password on the pop-up screen. Enter a password of up to eight alphanumeric characters and symbols from the keyboard.
IMPORTANT:
User password setup is not available before Supervisor password
setup.
If you have forgotten your password, ask your service
representative.
Option Parameter Description Your Setting
User Password Is [Clear]
Set
Supervisor Password Is
Set User Password
Set Supervisor Password
Password on boot [Disabled]
Fixed disk boot sector
Power Switch Inhibit
[Clear] Set Up to eight alphanumerics
Up to eight alphanumerics
Enabled
[Normal] Write Protect
[Disabled] Enabled
Indicates the user password setting status (view only).
Indicates the supervisor password setting status (view only).
Press Enter to display the user
*1
password entry screen. With a user password, accessible SETUP menus are restricted. This option is available only when you log into the SETUP utility with the password "Supervisor". Press Enter to display the supervisor
*1
password entry screen. With the supervisor password, all SETUP menus are available for access. This option is available only when you log into the SETUP utility with the password "Supervisor". Specify whether to request a user password entry at boot-up. User password must be set beforehand. If the supervisor password is set and this option is disabled, BIOS determines that a user is booting. Specify whether to permit writing into boot sector of the SATA hard disk drive or not. Specify whether the Maintenance switch is enabled or disabled. If Enabled, the Maintenance switch cannot be used to power off the maintenance card. (The forced shutdown, by pressing the POWER switch for 4 seconds or longer, is available.)
Page 86
4-16 Configuring Your EcoPowerGateway
Option Parameter Description Your Setting
Disable USB Ports [Disabled]
Front Internal Front Internal
*1 One of the following messages appears when you press Enter.
Specify whether the USB port is
enabled or disabled.
[ ]: Factory-set
In case of no password setting
Set Supervisor Password
Enter New Password [ ] Confirm New Password [ ]
If the input of "Enter New Password" is different from the input of "Confirm New Password", the following message is displayed.
Setup Warning
Passwords do not match
Re-enter password
[Continue]
If the input of "Current Password" failed three times, the following message is displayed.
System Disabled
In case of any password stored
Set Supervisor Password
Enter Current Password [ ] Enter New Password [ ] Confirm New Password [ ]
If the input of "Current Password" is different from the stored password, the following message is displayed.
Set Supervisor Password
Setup Warning
Invalid Password
[Continue]
If the Password setting succeeded, the following message is displayed.
Setup Notice
Changes have been saved
[Continue]
Page 87
Configuring Your EcoPowerGateway 4-17
Server
The items which can be set on the Server menu and their functions are described below.
For setting of [System Management], [Console Redirection], [BMC LAN Configuration], and [Event Log Configuration], first select the item and press Enter to display the submenu.
Option Parameter Description Your Setting
System Management
Console Redirection
BMC LAN Configuration
BMC Configuration
Event Log Configuration Assert NMI on PERR
Assert NMI on SERR
FRB-2 Policy
Boot Monitoring [Disabled]
Boot Monitoring Policy
N/A
N/A
N/A
N/A
N/A
Disabled [Enabled]
Disabled [Enabled]
Disable FRB2 Timer [Retry 3 Times] Always Reset
5 minutes 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes 35 minutes 40 minutes 45 minutes 50 minutes 55 minutes 60 minutes [Retry 3 Times] Always Reset
When enabled, PCI bus parity error (PERR) can be detected and notified as NMI at occurrence of an error.
When enabled, PCI bus system error (SERR) can be detected and notified as NMI at occurrence of an error.
Set the policy to be applied to FRB level 2 timer at occurrence of an error..
Specify whether the boot monitoring feature is enabled or disabled and the timer value on booting. Set this item to "Disabled" because the EcoPowerGateway does not support the NEC ESMPRO Agent.
This item indicates the processing at the occurrence of timeout during boot monitoring. Retry 3 times: The system is reset after the
occurrence of timeout and OS boot is retried up to three times.
Always Reset: The system is reset after the
occurrence of timeout and OS boot is retried repeatedly.
Page 88
4-18 Configuring Your EcoPowerGateway
Option Parameter Description Your Setting
Thermal Sensor Disabled
[Enabled]
BMC IRQ Disabled
[IRQ 11]
Post Error Pause Disabled
[Enabled]
AC-LINK Stay Off
[Last State] Power On
Power ON Delay Time (Sec)
Platform Event Filtering
[20] - 255 Specify the power-on delay time between 20
Disabled [Enabled]
Specify whether the temperature sensor monitoring feature is enabled or disabled. If a thermal error is detected with this item being set to "Enabled", the system stops at the end of POST.
Specify whether to assign IRQ for BMC (Baseboard Management Controller).
Specify whether POST is aborted once at the end of POST if an error occurs during the execution of POST. Specify the AC-LINK feature. Shows the system status when the AC power is supplied again to the EcoPowerGateway. See the table below.
and 255 seconds. This option is available only when "Power On" or "Last State" is specified for AC LINK. Specify whether the Platform Event Filtering feature of the Baseboard Management Controller (BMC) is enabled or disabled.
[ ]: Factory-set
The table below shows the operation when the DC power to the EcoPowerGateway is turned off once and then on again, depending on the setting of "AC-LINK". When the DC power to the EcoPowerGateway is turned on, the standby power is supplied to the Maintenance Card.
System status before DC power off of EcoPowerGateway
Operating Off On On Aborting (power of the Maintenance Card being off also) Off Off On Forced shutdown Off Off On
* Press the Maintenance switch continuously at least four seconds. This forcibly turns off the
power.
Setting of AC-LINK Stay Off Last State Power On
Page 89
Configuring Your EcoPowerGateway 4-19
System Management
Option Parameter Description Your Setting
BIOS Revision Indicates the version of BIOS. (View only) Board Part Number
Board Serial Number
System Part Number
System Serial Number
Chassis Part Number
Chassis Serial Number
Onboard LAN1 MAC Address
Onboard LAN2 MAC Address
Management LAN MAC Address
BMC Device ID
BMC Device Revision Indicates the firmware revision of BMC.
BMC Firmware Revision
SDR Revision Indicates the revision of SDR (Sensor
PIA Revision Indicates the revision of PIA (Platform
Indicates the MAC address for LAN port
Indicates the firmware revision of BMC.
Indicates the part number of the mother board. (View only)
Indicates the serial number of the mother board. (View only)
Indicates the part number of the system. (View only)
Indicates the Indicates the serial number of the system. (View only)
Indicates the part number of the chassis. (View only)
Indicates the serial number of the chassis. (View only)
Indicates the MAC address for LAN port
1. With this system, Onboard LAN1 MAC Address 1 is not displayed.
2. With this system, Onboard LAN1 MAC Address 2 is not displayed.
Indicates the MAC address for management LAN port. (View only)
Indicates the device ID of BMC (Baseboard Management Controller.) (View only)
(View only)
(View only)
Data Record). (View only)
Information Area). (View only)
[ ]: Factory-set
Page 90
4-20 Configuring Your EcoPowerGateway
Console Redirection
Option Parameter Description Your Setting
BIOS Redirection Port
Baud Rate 9600
Flow Control None
Terminal Type PC ANSI
Continue Redirection after POST
Remote Console Reset
Disabled [Enabled]
[19.2K]
38.4K
57.6K
115.2K
XON/XOFF [CTS/RTS] CTS/RTS+CD
[VT100+] VT-UTF8 Disabled [Enabled]
[Disabled] Enabled
Specify the serial port to which a
hardware console is connected.
Specify the baud rate for the interface
with hardware consoles.
Specify the flow control method.
Specify the type of remote console.
Specify whether the console
redirection feature is continuously
executed after POST or not.
Specify whether to enable or disable
resetting by Escape command (Esc R)
sent from the remote console.
[ ]: Factory-set
Page 91
Configuring Your EcoPowerGateway 4-21
BMC Configuration
Option Parameter Description Your Setting
Alert Test N/A Common N/A LAN1
Configuration Clear BMC
Configuration
Reset BMC [Enter]
* If you press Enter on [Clear BMC Configuration], the following message appears.
N/A
[Enter]
*1
Press Enter and select "Yes" to reset the BMC, and then initialize the BMC configuration.
*2
Press Enter and select "Yes" to reset the BMC, and then reset the system.
Clear BMC Configuration
Are you sure to clear the BMC Configuration?
If you select "Yes", it may take about 30 seconds
to reset BMC setting. Please wait for a while.
[ ]: Factory-set
[Yes] No
* If you press Enter on [Reset BMC], the following message appears.
Reset BMC
If you select "Yes", it may take about 30 seconds
Are you sure to reset the BMC?
to reset BMC. Please wait for a while.
[Yes] No
IMPORTANT: Notes on performing Clear BMC Configuration
Executing "Load Setup Defaults" in BIOS SETUP utility does not
restore the default value for settings related to management LAN of BMC. To restore the default value, you need to execute Clear BMC Configuration.
It takes about several tens seconds until initialization completes
after execution of Clear BMC Configuration.
Page 92
4-22 Configuring Your EcoPowerGateway
Alert Test
Option Parameter Description Your Setting
Primary [Enter] (*1)
Alert Status OK
NG
Secondary [Enter] (*1)
Alert Status OK
NG
Tertiary [Enter] (*1)
Alert Status OK
NG
* If you press Enter on the menu, the following message appears.
Press Enter and select "Yes" to send
test alert to the primary destination.
Indicates the alert sending status
(view only).
Press Enter and select "Yes" to send
test alert to the secondary destination.
Indicates the alert sending status
(view only).
Press Enter and select "Yes" to send
test alert to the tertiary destination.
Indicates the alert sending status
(view only).
[ ]: Factory-set
Alert Test
If you select "Yes", it may take a few minutes
Are you sure to test alert?
to test alert. Please wait for a while.
[Yes] No
IMPORTANT: To perform alert test, select [BMC Configuration] submenu and change parameters for [Common] and [BMC LAN1 Configuration] appropriately. Then, select [Exit] - [Save Changes] or [Exit Saving Changes] to reflect the setting to BMC.
Page 93
Configuring Your EcoPowerGateway 4-23
Common
Option Parameter Description Your Setting
Comment 1 [ ] Enter the comment. Comment 2 [ ] Enter the comment. Computer Name [ ] Specify the name of server to be
managed by NEC ESMPRO Manager. Each server name must be unique.
Authentication Key [ ] Specify the authentication key for
connection between NEC ESMPRO Manager and BMC. The authentication key is required when using the management LAN. The authentication key you have set in BMC is not displayed at the next boot of SETUP BIOS. Be sure to remember the key.
Community Name [public ] Specify the community name for
SNMP trap sent from BMC. *1
Alert Disabled
[Enabled]
Alert Process [All]
One
Alert Acknowledge [Disabled]
Enabled
Alert Level: *2 [Level0]
Level1 Level2 Level3 Level4 Level5 Level6
Remote Control (LAN1) Disabled
[Enabled]
Redirection (LAN) Disabled
[Enabled]
Specify whether the alert is sent or not. If Enabled, the alert is sent to the destination where alert is enabled, according to the setting for protocol and alert level. If Disabled, alert is not sent to any destination. Select "All" or "One". All: An alert is sent to every media where the alert is enabled. One: An alert is sent to a single media. If the alert is sent successfully, the alert is not sent to the remaining destination having the lower priority. Enables or disables acknowledgement of alert. If Enabled, the response from the destination is acknowledged. Specify the severity level of the event to send an alert. This setting remain unchanged even if [Clear BMC Configuration] is executed (the initial value is not restored.)
Enables or disables remote management via LAN1. If Disabled, NEC ESMPRO Manager cannot connect with the EcoPowerGateway via LAN1. An alert from the managed server is not sent via LAN1. Enables or disables remote console feature via LAN. If Disabled, remote console feature via LAN cannot be used.
[ ]: Factory-set
Page 94
4-24 Configuring Your EcoPowerGateway
*1 When changing community name, configure the destination PC so that it can accept the
community name.
*2 The alert level is as shown below.
Alert level Severity of event
1 Unrecoverable 2 Unrecoverable, Error 3 Unrecoverable, Error, Warning 4 Unrecoverable, Error, Warning, Recovered 5 Unrecoverable, Error, Warning, Recovered, Information 6 Unrecoverable, Error, Warning, Recovered, Information, Monitor
Page 95
Configuring Your EcoPowerGateway 4-25
BMC LAN1 Configuration submenu
Option Parameter Description Your Setting
LAN Connection Type
IP Address [192.168.001.001]
Subnet Mask [255.255.255.000]
Default Gateway
DHCP [Disabled]
Web Interface HTTP [Disabled]
HTTP Port Number
HTTPS [Disabled]
HTTPS Port Number
Command Line Interface Telnet [Disabled]
Telnet Port Number
SSH [Disabled]
SSH Port Number
Alert Interface Alert (Primary) [Disabled]
Alert IP (Primary)
Alert (Secondary)
Alert IP (Secondary)
[Auto Negotiation] 100Mbps Full Duplex 100Mbps Half Duplex 10Mbps Full Duplex 10Mbps Half Duplex
[000.000.000.000]
Enabled
Enabled [80] Specify the TCP port number which
Enabled [443] Specify the TCP port number which
Enabled
[23]
Enabled
[22] Specify the TCP port number to be
Enabled [000.000.000.000] Specify an IP address of the primary
[Disabled] Enabled [000.000.000.000] Specify an IP address of the
Specify the connection type for management LAN port.
Specify an IP address for management LAN. Specify a subnet mask for management LAN. Specify a default gateway for management LAN.
Set to [Enabled] to obtain an IP address from DHCP automatically. If you intend to specify an IP address manually, set to [Disabled].
Set to [Enabled] to use HTTP communication for Web interface.
the management LAN uses for HTTP communication.
Set to [Enabled] to use HTTPS communication for Web interface.
the management LAN uses for HTTPS communication.
Set to [Enabled] to use Telnet communication as a command line interface.
Specify the TCP port number to be used for Telnet communication.
Set to [Enabled] to use SSH communication as a command line interface.
used for SSH communication.
Enables or disables an alert to be sent to the primary destination.
destination of the managed server. Use the IP address of NEC ESMPRO
Manager server for the primary destination.
Enables or disables an alert to be sent to the secondary destination.
secondary destination.
Page 96
4-26 Configuring Your EcoPowerGateway
Option Parameter Description Your Setting
Alert (Tertiary) [Disabled]
Enabled
Alert IP (Tertiary)
Alert Retry Count
Alert Timeout [3] - 30
[000.000.000.000]
[0] - 7
Enables or disables an alert to be sent
to the tertiary destination.
Specify an IP address of the tertiary
destination.
Specify the number of retries to send
an alert.
Specify the timeout value (in seconds)
until the alert is sent.
[ ]: Factory-set
Page 97
Configuring Your EcoPowerGateway 4-27
Event Log Configuration
Option Parameter Description Your Setting
System Event Logs
Auto Clear Event Logs
Clear All Event Logs
* If you press Enter on [Clear All Event Logs], the following message appears.
N/A
Disabled [Enabled]
[Enter] *
Are you sure to clear the System Event Log?
If set to "Enabled", logs are automatically cleared when the error log area is fulfilled.
Press Enter to clear the system event log.
Clear System Event Log
[Yes] No
[ ]: Factory-set
System Event Log
Use , , +, –, Home, or End to view the newer or older system event logs recorded.
Page 98
4-28 Configuring Your EcoPowerGateway
Boot
If you move the cursor to the position of "Boot", the Boot menu appears, which is used to set the boot priority.
1. When BIOS detects a bootable device, it displays the information on the device in the
relevant indication.
To boot the system from a desired device, the device must be registered as a boot device. (Up to eight boot devices can be registered.)
2. Pressing X after selecting a device allows the selected device to be registered as a boot
device or deleted from the registration.
With eight boot devices being registered, any other device cannot be registered as a boot device even if you press X. To register a device as a boot device newly, first delete the registration of a device registered as a boot device but not booted any more.
3. You can change the boot priority (first to eighth) of each device by using , , + and/or –.
To change the priority of a device, move the cursor to the device by using the or ↓, and press + or –.
Page 99
Configuring Your EcoPowerGateway 4-29
Exit
The options on the menu are described below.
Exit Saving Changes
Select this item to exit from SETUP after saving the newly selected information in CMOS (non­volatile memory). The selection of "Exit Saving Changes" causes the confirmation screen to appear.
If you select "Yes", SETUP is terminated with the newly selected information saved in CMOS (non­volatile memory). Then the SETUP automatically reboots the system.
Exit Discarding Changes
Select this item to exit from SETUP without saving the newly selected information in CMOS (non­volatile memory).
Selecting "No" on the confirmation screen [Save before exiting?] allows SETUP to be terminated without storage of the modified information. If you select "Yes", SETUP is terminated with the modified information saved in CMOS. Then the SETUP automatically reboots the system.
Load Setup Defaults
Select this item to return all the values of SETUP to the default values. Selecting "Load Setup Defaults" causes the confirmation screen to appear.
Select "Yes" to return the values to the default values. Select "No" to return to the Exit menu screen.
Save Custom Defaults
Selecting the Save Custom Defaults menu and pressing Enter saves the current SETUP parameters as the user-defined SETUP defaults. When saved, [Load Custom Defaults] menu is displayed.
Load Custom Defaults
Select this item and press Enter to load the stored custom default values. This menu does not appear when no custom default values are stored.
Discard Changes
Select this item to return the values modified to the previous values before saving the values to CMOS. Selecting "Discard Changes" causes the confirmation screen to appear.
Select "Yes" to discard the newly selected information and return to the previous values.
Page 100
4-30 Configuring Your EcoPowerGateway
Save Changes
Select this item to save the newly selected information to CMOS (non-volatile memory) without the termination of SETUP. Selecting "Save Changes" causes the confirmation screen to appear.
Select "Yes" to save the newly selected information to CMOS (non-volatile memory)
Loading...