THIS MANUAL INCLUDES FEATURES WHICH ARE ONLY AVAILABLE IN CONTROL PANEL
FIRMWARE VERSION 10.0 OR LATER.
CHANGES FROM PREVIOUS EDITION
The following changes have been made to this manual (WI994C) since the previous edition (WI994B).
Page 2, "Important Notice", deleted NOTE which begins, "Typically, most versions of the GEM-P816 control panel can be upgraded…" and
•
ends, "...affixed to the GEM-P816 circuit board."
Page 6 contained a note with an asterisk, " *Not Evaluated by UL", referencing the Residential Burglary and Commercial Burglary specifica-
•
tions. This note was changed to "Commercial Burglary Specifications have not been Evaluated by UL".
Page 7, the M278 Line-Reversal Module and the Veri-Phone Two-Way Module accessories now reference an asterisk (*) in that they have not
•
yet been evaluated by UL.
•
Page 7, references to UL609, UL1610, and UL365 listings were removed. (the GEM-P816/1632 panels have not yet been evaluated to these
standards). However, the listing of the Security Industry Association (SIA) False Alarm Reduction Standard CP-01 was added.
Page 8 specified that the system be serviced once every three years; this time period specification was changed to "annually".
•
•
All systems on Page 11 in WI808E have not been evaluated by UL and therefore were removed.
Page 13 in the Siren/Bell Power section, the following statement was added: "In NFPA Household Fire Installations, only a single siren or bell
•
can be used on this bell circuit."
•
Page 33 listed the "Easy Exit Always Enabled in Interior Mode" definition. This definition was changed as follows: The entry name was
changed to "Easy Exit"; the statement "Not Evaluated by UL" was added; the sentence, "Disable D or U buttons to initiate Silent (Easy) Exit."
was added.
The glossary definition on Page 34, "Exit Urgency Annunciation" was modified as follows: The following sentence was removed, "When armed
•
Stay, Silent Exit is evoked and time is doubled (120 seconds by default)".
•
The glossary definition on Page 37, "No EOL Resistor" now includes the following notation: "Note: Do not program for UL installations".
The glossary definition listed on Page 37, "Panic Zone…" was changed as follows: The entry name is now listed as "Panics"; the following sen-
•
tence was added: "Tamper must be enabled on the keypad".
•
The glossary definition on pages 39-40, "Swinger Shutdown" was modified.
See the chart on Page 52, The entry for "Cross Zoning", the following sentence was added: "The Cross Zone set time = one (1) minute".
•
All references to "Auto Reset after Alarm Time-Out" changed to "Auto Reset after Burglary Output Timeout".
•
•
All references to 0720-Bit 6--"Enable PGM2 Chirp on Keyfob Arming" name changed to "Chirp Output on Keyfob Arm/Disarm".
All references to 0722-Bit 0--"Automatic Interior Bypass" name changed to "Automatic Interior Bypass/Easy Exit".
•
All references to 0721-Bit 7--"Enable Bell Output on Keyfob Arming" name changed to "Select Alarm Output for Keyfob Chirp".
•
IMPORTANT NOTICE
GEM-P816 panel version 10 requires the use of the following version keypads:
!
•GEM-RP1CAe2 Version 8, GEM-K1CA Version 8
GEM-RP2ASe2, Version 6, GEM-K2AS, Version 6
•
Upon entering program mode, the keypad display will flash the control panel firmware version, followed by the keypad firmware
version:
GEM-RP1CAe2: [1008], GEM-RP2ASe2: [1006], GEM-RP3DGTL: [1002]
GEM-K1CA: [1008], GEM-K2AS: [1006], GEM-K3DGTL: [1002]
Refer to accompanying GEM-P816 Programming Instructions (WI995 and WI1182) for programming information.
•GEM-RP3DGTL, Version 2, GEM-K3DGTL, Version 2
NAPCO Security Systems, Inc.
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, call toll free: (800) 645-9445
For direct line to Technical Service, call toll free: (800) 645-9440
Napco's Gemini GEM-P816 is a state-of-the-art microcomputer-based burglary and residential fire alarm control panel of
modular design. Integrally an 8-zone panel, it will support up to 16 zones with the use of optional zone expansion
modules, wireless receiver modules and/or GEM-RP1CAe2/GEM-K1CA Keypads. Each panel includes an integral digital
communicator.
The control panel features programmable area partitioning. That is, the system may be divided into up to two discrete
multiple-zone areas, each allowing access by only those users programmed for their respective area.
Opening Suppression and Closing Suppression, available through Napco Quickloader software, suppress reporting
within programmed “windows”. Conversely, Exception Reporting can transmit a “fail to close” if the panel is not armed
within programmed intervals and, similarly, a “fail to open” if the panel is not disarmed within programmed intervals.
Furthermore, the panel can be programmed to automatically arm either area at any time. A log containing up to 400
events (accessible through Quickloader
clock. A detailed event history may be displayed at the computer, using Napco’s PCD Windows Quickloader Software.
Keypads feature a liquid-crystal display for messages. In normal use, the LCD shows zone identification and status
messages. Conventional LEDs and a sounder are also provided for annunciation.
Data may be quickly and easily downloaded to the control panel using a PC-compatible computer with Napco's PCDWindows Quickloader software and PCI2000 computer interface. Or, the panel may be programmed using the keypad in
its secondary mode of operation. In the keypad programming modes (there are two: Dealer and User), the LCD shows
memory address, data values, programming prompts, and the alphanumeric characters required for entering up to 16
user codes and custom zone descriptions.
TM
software) monitors control-panel activity referenced to a precision real-time
NOTE:
Underwriters Laboratories, Inc.
Failure to install and program as described in this manual for UL-listed systems voids the listing mark of
FEATURES
Control Panel Features
Features
Eight end-of-line-resistor burglary zones programmable for Area, Exit/Entry Delay, Interior (Stay) Bypass, Exit/
!
Entry Follower, Day Zone, Chime, Fire options, Swinger Shutdown, Zone Anding and a variety of other features.
Supports up to 16 zones with optional zone-expansion modules, wireless receiver modules and 4-zone keypads.
!
!Supports up to 16 individually coded users.
Supports three outputs (Bell, PGM1 and PGM2).
!
Supports three keypad panics: Fire, Police & Auxiliary
!
!Supports two independent area partitions.
Supports up to seven separate access stations (keypads) by up to 16 users.
!
English-language prompts & system status messages.
!
!User-customized zone descriptions, re-programmable as required.
Supports 2-wire and 4-wire smoke detectors.
!
Reports alarms, restores and troubles by zone.
!
!400 Event Log.
Two programmable entry delay times.
!
One Interior Zone Group
!
!Dynamic battery test interrupts charging and places battery under load every four hours.
Chime by zone; programmable duration.
!
Quickloader programmable.
!
!2 PGM outputs.
Supports Gemini Wireless Devices
!
X
GEM-P816 Installation Instructions
L
NAPCO Security Systems
WI994C 3/04
Communicator Features
Compatible with all major receiver formats, including 4/2, SIA and Point ID (except Radionics Modem II).
16 User Codes with Opening/Closing -Reporting by user.
!
AC Failure Reporting with programmable report delay.
!
Supervised telephone line with a fixed 60 second delay.
!
Pager Capability.
!
Keypad Features.
!
English-language LCD display; LED and sounder annunciators.
!
Supports up to seven 4-wire keypads.
!
Provisions for fire, police and auxiliary panic alarms.
!
Integral 4-zone EZM included in each keypad (GEM-RP1CAe2/GEM-K1CA only).
!
Fault-Find diagnostics simplify troubleshooting.
!
SIA CP-01 Features.
See page 51-52 for complete information regarding the Factory Program complies with the Security Industry Asso-
!
ciation False Alarm Reduction Control Panel-01 Standard (SIA FAR CP-01).
Page 5
!
IMPORTANT NOTE
This manual supports the keypad programming of the GEM-P1632 control panel with the NAPCO "classic" GEMRP1CAe2, GEM-RP2ASe2, and GEM-RP3DGTL keypads as well as the GEM-K1CA, GEM-K2AS, and GEM-K3DGTL
"K Series" keypads. The new "K Series" models offer the new STAY and AWAY buttons with simplified functionality,
along with the new MENU and ENTER buttons.
While the instructions in this manual are depicted using the GEM-K1CA and GEM-K2AS keypads, the manual applies to
both the "classic" and the "K Series" keypads.
Program Mode is the same for both keypads--only the button names have changed, as follows:
• The
• The
•
•
A
D
The
"NEXT/YES button" are used in this manual.
The
"PRIOR/NO button" are used in this manual.
button and the
button and the U button operate identically (in Program Mode) for both keypads.
button and the button operate identically (in Program Mode) for both keypads. The words
button and the button operate identically (in Program Mode) for both keypads. The words
R
button operate identically (in Program Mode) for both keypads.
Features
L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
!
Page 6
WI994C 3/04
SPECIFICATIONS
GEM-P816
O
perating Temperature: 0-49°C (32-120°F)
Input Power: 16.5-18.0 VAC via CLASS 2 Plug-In 20VA, 40VA or 50VA Transformer
Loop Voltage: 10-13Vdc
Loop Current: 3mA without Zone Doubling, 2.4mA with Zone Doubling using a 2.2K Ohm end-of-line resistor (Model EOL2.2K); 5mA
for 2-wire smoke-detector zones; 1.4 mA using a 3.9K Ohm resistor (Model EOL 3.9K) with Zone Doubling
Loop Resistance: 300 Ohm max.; 50 Ohm for 2-wire smoke-detector zones
Alarm Voltage Output: 1
Programmable Negative Outputs: 2
Auxiliary Power Output: 11.7-12.5 VDC
Remote Power Output: 12 VDC regulated (for keypads)
Combined Standby Current(Remote Power + Aux. Power + Fire Power): See following charts.
Specifications
16.5VAC
TRANSFORMER
40VA/50VA 7 AH 650 mA 2.0 A 4 Hours
20VA * 7 AH 500 mA 2.0 A 4 Hours
20VA * 7 AH 500 mA 2.0 A 6 Hours
16.5VAC
TRANSFORMER
40VA/50VA 7 AH 120 mA
40VA/50VA * Two 7 AH 360 mA
20VA * 7 AH 120 mA
20VA * Two 7 AH 360 mA
(1)
NOTE:
Alarm current can be increased by reducing standby current by the same amount.
RESIDENTIAL BURGLARY & COMMERCIAL BURGLARY*
BATTERY
(12 VDC)
BATTERY
(12 VDC)
STANDBY
CURRENT
RESIDENTIAL FIRE
STANDBY
CURRENT
ALARM
CURRENT
ALARM
CURRENT
(1)
520 mA
(1)
280 mA
(1)
360 mA
(1)
120 mA
* Commercial Burglary specifications not evaluated by U.L.
STANDBY
TIME
STANDBY
TIME
24 Hours
24 Hours
24 Hours
24 Hours
RESIDENTIAL FIRE PROGRAMMING OPTION: Refer to GEM-P816 Programming Instructions (WI995 and WI 1182)
for programming information. This option changes the operation of the power supply in alarm conditions to optimize
performance. In installations that do not monitor fire conditions (Residential and Commercial Burglary) U. L. allows the
battery to be depleted in alarm conditions when AC is present. To prevent the regulator and rectifier from exceeding
75% of their rated temperature the regulator drops to 10V causing the battery to support the entire alarm current. In
installations that do monitor fire conditions (Residential Fire) U.L. does not allow the battery to be depleted in alarm
conditions when AC is present. Therefore when this bit is set the regulator is not dropped to 10V during alarm
conditions. When this bit is set the current specifications for Residential Fire should not be exceeded. If the
specifications are exceeded when a 40VA or 50VA transformer is used the regulator may exceed 75% of its rated
temperature up to 85% of its rated temperature at which point the regulator will protect itself by current limiting. This
would cause the battery to deplete, but no damage would occur to the panel. If a 20VA transformer is used and the
Residential Fire current specifications are exceeded then the Transformer VA rating may be exceeded thereby
damaging the transformer.
EZM Module:
GEM-EZM816: Input, 50mA
Keypad Current:
GEM-RP1CAe2: 100mA; 35mA if back lighting is disabled (cut W1, W2 & W3)
PGM Output: 5mA, 12V Special Application
Maximum Number of Keypads: 7
Maximum Wiring Length for each run (#22AWG): 1000' divided by total number of keypads and EZMs on run
Keypad Dimensions: 4” x 5” x 1” (HWD); 11.1cm x 14.9cm x 2.7cm (HWD)
X
GEM-P816 Installation Instructions
L
NAPCO Security Systems
WI994C 3/04
ORDERING INFORMATION
System Components
GEM-P816: Residential UL-Listed Burg and Fire Control
Panel.
GEM-RP1CAe2: 32-Character LCD Burg & Fire Keypad
with 4 EOL Zones.
GEM-RP2ASe2: LCD Burg & Fire Keypad with remote
panic.
GEM-RP3DGTL: Burg & Fire Keypad.
GEM-RP4RFC: Digital Icon Burg & Fire Keypad with In-
tegral RF Receiver.
GEM-RP4C:
GEM-K1CA: 32-Character LCD Burg & Fire Keypad with
4 EOL Zones.
GEM-K2AS:
GEM-K3DGTL: Burg & Fire Keypad.
GEM-K4RF: Digital Icon Burg & Fire Keypad with Inte-
gral RF Receiver.
GEM-K4:
Optional Accessories and Peripherals
GEM-EZM8: 8 Zone Expansion Zone Module
GEM-EZM816:
GEM-EVA 1: Electronic Voice Annunciator
GEM-RECV8: Wireless Receiver, 8 Zones
GEM-RECV16:
GEM-RECV96:
GEM-TRANS2: Window/Door Transmitter, 2-Point
GEM-RTRANS: Recessed Window/Door Transmitter
GEM-KEYF:
GEM-SMK: Wireless Smoke Detector
GEM-PIRPET: Wireless Pet Immune Transmitter *
GEM-PIR: Wireless PIR
GEM-DT:
GEM-GB: Wireless Glass-Break Detector *
GEM-X10KIT: X-10 Interface *
GEM-OUT8: 8 output active low output module
M278:
PS3002: Power-Supply Module, 13.2Vdc, 1.9A *
EOL2.2K: End-of-Line Resistor Assy., 2.2k Ohm, for Fire
Circuit
FT2200:
RB1000: Relay Board, single output *
RBATH1: Dual Battery Harness
RPB-3: Universal Keypad Mounting Box
TRF11:
TRF14: Transformer, 16.5Vac/50VA, Class 2
WL1: Wire Assembly with Lug Connector, 20”
Digital Icon Burg & Fire Keypad.
LCD Burg & Fire Keypad with remote panic.
Digital Icon Burg & Fire Keypad.
4-16 Zone Expansion Zone Module
Wireless Receiver, 16 Zones
Wireless Receiver, 96 Zones
Key Fob Transmitter
Wireless Dual-Technology Sensor
Line-Reversal Module*
End-of-Line Relay/Resistor Supervisory Module
Transformer, 16.5Vac/40VA, Class 2
Page 7
VERI-PHONE:
PCD3000: Downloading Software (for DOS) for IBM PC-
Compatible*
PCD-Windows: Downloading Software (for Windows) for
IBM PC-Compatible*
PCI2000/3000: Software with Interface for IBM PC-
Compatible Computer *
PCI-MINI: Notebook Computer Interface *
W834-1:
OI193: User Guide, GEM-RP1CAe2
OI192: User Guide, GEM-RP2ASe2
OI249:
OI278: User Guide, GEM-RP4C & RP4RFC
WI1212: Installation Manual, GEM-RP4C
WI1128: Installation Manual, GEM-RP4RFC
OI279:
OI280: User Guide, GEM-K2AS
OI281: User Guide, GEM-K3DGTL
OI283:
WI1178:
WI1179: Installation Manual, GEM-K4RF
WI995: GEM-P816 Programming Instructions (using
WI1182: GEM-P816 Programming Instructions (using
WI994:
WIZARD IIe: Telephone Interface Module *
* Not investigated by UL.
User Guide, GEM-RP3DGTL
User Guide, GEM-K1CA
User Guide, GEM-K4 & K4RF
GEM-RP1CAe2 / GEM-K1CA keypads).
GEM-RP2ASe2 / GEM-K2AS or GEM-RP3DGTL /
GEM-K3DGTL keypads).
GEM-P816 Installation Instructions
Two-Way Voice/Listen-In Module*
Keypad Cable, plug-in (20”)
Installation Manual, GEM-K4
!
UL Listings
Household Burglar Alarm System Units: UL1023
Household Fire Warning System Units: UL985
Security Industry Association (SIA) False Alarm Reduc-
tion Standard CP-01
** Pending
Ordering Information
L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
!
Page 8
WI994C 3/04
Smoke Detectors, 4-Wire:
1. ESL 445AT, 445C, 445CT, 445CR, 445CRT
2. Hochiki America SLG-12 with YBC-RL4-RA Base
3. System Sensor 2312/24T; 1412; 1412TH; 2412TH
Subtract total smoke-detector alarm current from available standby current.
Note: Any normally-open devices that do not require power from the control panel, such as pull stations and thermostats
may be used if acceptable to the Authority having Jurisdiction.
UL Compatible Smoke Detectors (Providing UL Recognition or Listing)
Manufacturer 4-Wire
Smoke Detector
Napco FW-4 FW-2
Sentrol
System
Sensor
449AT
449C
449CRT
449CST
449CSRT
449CSRH
449CSST
1112
2112
449CLT
449CSLT
449CTE
741U
742U
2112T
2112TSRB
712U
722U
732U
711U
721U
721UT
2100
2100T
2-Wire
Smoke Detector *
731U
1100
Smoke Detector
Base
701U
702U
702RE
702RU
Note: * Voltage Rating: 8.5-13.3 VDC, Maximum Number of Detectors: 10
SUMMARY OF UL REQUIREMENTS
Residential
Recognized Limited-Energy Cable for initiating, indicating and supplementary circuits.
!
Initiating loops supervised if longer than 3 feet
!
FT2200 End-of-Line Relay for Fire (if using 4-wire smoke detectors)
!
Minimum alarm timeout of 5 minutes
!
Maximum exit time: 60 seconds
!
Maximum entry time: 45 seconds
!
!Do not program “Swinger Shutdown”, “Force Arming”, “Selective Bypass” or “50 ms Loop Response”
Summary of UL Requirements
!“Abort Delay” may not exceed 45 seconds
!Program “Disable Callback Download”
!Automatic dialer may not dial a police station number that has not been dedicated for such service
System must be tested at least weekly under AC/battery and Battery-Only conditions
!
Replace the rechargeable battery at least every 5 years
!
If the battery is heavily discharged, replace it or have it tested by a qualified technician
!
For silent panic, connect only to UL-listed holdup devices
!
All zones must be programmed for “Priority”
!
Do not program any zones for “Keyswitch Arming”
!
System must be serviced at least once every year
!
Residential Fire and Combination Residential Fire & Burglary must program “Residential Fire”
!
Keypad Expansion (EZM) Zones are not to be used as fire zones
!
Keypad Auxiliary is not to be selected
!
!The GEM-K Series Keypads must have the indicators printed on the face label (Fire, Police and Auxiliary) covered
by a supplied label if not in use.
X
GEM-P816 Installation Instructions
L
NAPCO Security Systems
WI994C 3/04
Page 9
!
INSTALLATION
CAUTION: This equipment generates and uses radio-frequency energy. If not installed using conventional installation
practices for RF devices, it may cause interference to radio and television reception. It has been tested and found to
comply with the limits for a Class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which are
designed to provide reasonable protection against such interference. However, there is no guarantee that interference
will not occur in a particular installation. If it has been found to cause interference to radio or television reception, which
can be determined by removing and reapplying AC and battery power to the equipment, the installer should try to
correct the interference by one or more of the following measures: reorient the receiving antenna; connect the power
transformer to a different outlet so that the control panel and receiver are on different branch circuits; relocate the
control panel with respect to the receiver.
MOUNTING
Control Panel
Choose a mounting location accessible to (a) a continuously-powered AC source, (b) system ground, a steel or copper
ground rod, ideally no further away than 10 feet, and (c) telephone lines (keep telephone wiring away from keypad
wires). Remove appropriate knockouts for cables. Place the control panel at a convenient viewing height and mark the
mounting holes. Attach the enclosure using screws suitable for the mounting surface.
Grounding
Connect the control-panel grounding screw to a long steel or copper ground rod driven deeply into the earth. Do not use
a gas pipe, plastic pipe or ac ground connections. Use at least 16-gauge wire. Make the run as short and direct as
possible, without any sharp bends in the wire.
Keypad
A keypad should be located near each exit/entry door. The keypad features a handy pull-up reference label. Before
mounting the keypad onto the wall, push the Sliding Label Plate (with label and felt backing affixed and handle facing
forward) down the guides at the rear of the keypad until it snaps into place. Once installed, the Sliding Label Plate
cannot be removed without first removing the keypad from the wall. Note: (1) The keypad fire and panic keys should not
be considered a substitute for a listed manual initiating device, such as a pull box. (2) Each GEM-RP1CAe2 includes
provisions for four additional zones. See ADDING EXPANSION ZONES.
If installing onto a double-gang box, insert mounting screws through the two vertical elongated holes on the left side of
the case and into the box. If the box is visible when viewed from the front, adjust the keypad vertically and tighten the
screws. Then, using hardware suitable for the mounting surface, add one or two screws at the right side of the keypad
case directly into the wall to ensure a secure installation. Note: Do not overtighten the screws! Uneven walls may cause
the keypad case to distort.
Mounting
L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
Page 10
!
WI994C 3/04
Wiring
Wire keypad(s), zones, expansion zone modules and output devices as shown on the Wiring Diagram. Note that the
Wiring Diagram contains important information not available elsewhere in this manual.
CAUTION: Do not run telephone wiring near speaker wires; do not run keypad wiring with loop wiring.
Wireless Systems
With the addition of at least one GEM-RECV series receiver, the GEM-P816 will support up to 32 wireless transmitters.
The panel can accommodate one or two receivers within the premises, responding to the one with the stronger
transmitter signal. If any transmitters are selected for the default program, a GEM-RECV receiver will automatically be
programmed.
The keypad can display the status of any transmitter, indicating the condition of the zone (normal or open) and
transmitter troubles (low battery, tamper or supervisory failure), and signal strength of the last transmission. A receiver
failure will be indicated by “E06-NN” (“no response”, with NN representing the receiver number).
TYPICAL RESIDENTIAL FIRE INSTALLATION (Where permitted by local codes)
At least one smoke detector should be installed directly outside each sleeping area. If there is more than one floor,
additional smoke detectors should be installed on each level, including the basement. The living-area and basement
smoke detectors should be installed near the stairway of the next upper level.
For increased protection, additional detectors should be installed
Wiring
with common-area protection of the control-panel room. This system meets UL requirements for a partitioned installation.
in areas other than those required, such as the dining room,
bedrooms, utility room, furnace room, and hallways. Heat
detectors, rather than smoke detectors, are recommended in
kitchens, attics, and garages due to conditions that may result in
false alarms and improper operation. Large areas and areas with
partitions, ceiling beams, doorways, and open joists will require
additional detectors.
Refer to NFPA Standard No. 74 (National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269) for additional
information, including proper mounting of detectors.
TYPICAL PARTITIONED INSTALLATION
!
Described and illustrated here are an example of a partitioned system
Both areas must be owned and managed by the same person(s).
!
!
Both areas must be part of one building at one street address.
!
X
GEM-P816 Installation Instructions
The control panel and all wiring protecting each partitioned area must be
confined to the respective area and may not impinge upon the other area. This
requires that the control panel room have redundant protection; that is (a) multiple
sets of door contacts, each wired to a separate zone and (b) one of those zones
programmed for each area. In order to gain access to this protected area without
causing an alarm, both partitions must be disarmed. In lieu of redundant
protection, 24-Hour Zones may be used. Any zone protecting the control panel
and transformer may not be programmed for bypass.
!
The sounding device must be placed such that the bell test can be heard by all
partitions. Note: NFPA 74 (Household Fire Warning Equipment) requires that a
fire alarm audible device be installed indoors.
The User Program Code is not to be given to anyone except the authority
responsible for all partitions.
L
NAPCO Security Systems
WI994C 3/04
THIS PAGE INTENTIONALLY LEFT BLANK
Page 11
!
L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
Page 12
!
TESTING THE SYSTEM
After installation is completed, test the system as follows.
!
1. Call the central station to inform them of the test.
!
2. Initiate an alarm, preferably on a zone that activates a steady siren, and verify proper signalling.
!
3. Call the central station to confirm their receipt of a good transmission.
Be sure to test all enabled keypad panics.
Note:
Signal Strength Testing/Wireless Systems
To test the operation of wireless transmitters, proceed as follows.
!
1. Enter the Fault-Find Mode. (See Dealer Mode on page 46. Panel must be disarmed).
!
2. Fault a point of the transmitter to be tested by opening the loop. If the signal strength of the transmitter is 3 or
greater, the keypad will beep, as follows:
!
3. Restore the wireless point (close the loop).
!
The transmitter signal strength will be displayed on a scale of 3-10 with 3 considered marginal and 10
considered excellent. Note that if the signal strength is less than 3, the keypad will not beep and the strength
will be displayed. Except in the Fault-Find Mode, signal strengths less than 3 will be entered into the system
log. Upon zone restore, the keypad will beep once.
Signal Power Beeps
0-2 0
3 1
4-5 2
6-7 3
8-10 4
WI994C 3/04
Testing the System
X
GEM-P816 Installation Instructions
L
NAPCO Security Systems
WI994C 3/04
WIRING CONNECTIONS
BATTERY
7
TRANSFORMER
Connect a 16.5 VAC Transformer to Terminals 1 and 2, using a wire of #18 AWG. or
larger at a distance of 15 ft. or less from the control panel.
switched outlet.
Page 13
The RED (+) and BLACK (-) flying leads must be connected to
a 12VDC 4-7 AH Rechargeable Battery, to serve as backup
power in the event of AC Power Failure. NOTE: To calculate
the available standby time refer to the Standby-Battery
Calculation Worksheet at the back of this manual.
Connect the auxiliary devices (motion detectors, glass breaks, etc.) to Terminals 5 and 6.
Auxiliary Power provides 11.7-12.5 VDC nominal output which is used for powering auxiliary
devices. NOTE: To calculate the available standby time refer to the Standby-Battery
Calculation Worksheet at the back of this manual.
PGM OUTPUTS (PGM1 & PGM2)
Connect the alarm sounding devices (self-contained sirens,
speakers or a mechanical bell) to Terminals 3 and 4. Any selfcontained siren requiring a 12 VDC input can be connected.
When connecting a mechanical bell, it must be supervised
using a 2.2k Ohm resistor. To connect 8 Ohm Speakers use a
Siren Driver with the proper polarity observed. NOTE: Refer to
the GEM-P816 Wiring Diagram for alarm current specification.
Note: In NFPA Household Fire Installations. only a single siren
or bell can be used on this bell circuit.
PGM1 and PGM2 are negative switched
programmable outputs that can be activated
depending on the programming options selected
(see GEM-P816 Programming Instructions).
Connect the device controlled by the
programmable output between terminal 5 (+) and
the PGM output (-), either terminal 7 or 8. As an
example, the connection to the RB1000 Relay
Module is shown.
L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
Page 14
!
REMOTE BUS
REMOTE BUS
ADDITIONAL
EZMs
Example:
(GEM-RP1CAe2)
2 LINE KEYPAD
STATUS
ARMED
NOTE: Refer to the EZM Installation Instructions for
4. WIRELESS RECEIVERS: GEM-RECV8, GEM-RECV16, GEM-RECV96
(32 zones maximum)
5. RELAY MODULE: RM3008 (8 relays maximum)
6. VOICE INTERFACE: GEM-EVA 1
7. TELEPHONE INTERFACE: WIZARD IIe
AVAILABLE DEVICES
GEM-X10 (8 devices maximum)
GEM-EZM8, GEM-EZM816 (32 zones
WI994C 3/04
Connect the available devices as shown above to the remote bus terminals (9, 10, 11 & 12). Observe the correct color
wire connections. When connecting the keypads, first configure them accordingly (refer to the Keypad Configuration
Mode at the back of this manual). Keypads should be located near every exit/entry door. Up to seven keypads may be
connected if the longest cable run from the panel, to the farthest keypad (daisy chained or home-run) is less than 1000
feet. The maximum distance for seven keypads is 300 feet using 22 AWG. wire.
NOTE:
When running keypad wire,
avoid wiring parallel to other types of wiring.
EARTH GROUND
Connect the control panel EARTH GROUND screw to a metal cold-water
Wiring Connections: Remote Bus & Earth Ground
pipe using at least a #16 AWG. wire. Do not use a gas pipe, plastic pipe or
AC ground connections. Also, connect the circuit board to the metal
enclosure. Connect a wire with a ground lug crimped or soldered onto one
end of the EARTH GROUND screw to the cabinet.
NOTE:
Grounding
connections should avoid bends in the grounding wire whenever possible.
NOTE: Do not use a gas pipe, plastic
X
GEM-P816 Installation Instructions
L
NAPCO Security Systems
WI994C 3/04
BASIC ZONE CONFIGURATION
Page 15
!
(-)
The basic zone configuration for the GEM-P816 is 8 zones. Connect as shown above to terminals 13-24. Normally
Closed (N.C.) devices may be wired in series or Normally Open (N.O.) devices may be wired in parallel. Use the 2.2K
Ohm end-of-line (E.O.L.) resistor in each zone, if selected in programming (refer to the GEM-P816 Programming
Instructions). Zones 1-8 can be selected for a “Fast Loop Response (50 ms)” or a “Normal Loop Response (750 ms)”.
Other zone options include Zone Type (Entry/Exit, Interior, 24 Hour Protection, Trouble and Fire), Instant, Chime, Area
Selection and PGM Output selection. Additional expansion zone modules or wireless sensor transmitters/receivers can
be used to obtain zones numbered 9 through 16.
Wiring Connections: Basic Zone Configuration & EZ Zone Doubling Configuration
L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
Page 16
!
4-WIRE SMOKE DETECTORS
WI994C 3/04
4-WIRE SMOKE DETECTOR WIRING
The GEM-P816 can use conventional 12 VDC 4-wire smoke detectors. To use
them, select fire zone programming option and do not select 2-wire smoke detector
programming option for the desired fire zone (refer to the GEM-P816 Programming
Instructions). Set JP3 to the position as shown, if zones 7 or 8 are to be used.
Four wire smoke detectors may be connected to any programmed fire zone (1-8) as
shown, within the panel. If external EZMs are used for zones 9-16, then 4-wire
smoke detectors may be connected to any programmed fire zones (9-16).
Power must be obtained from terminal 25 and 6. If Fire Alarm Verification is desired
to reset the smoke detectors, select this option for the desired fire zone.
The GEM-P816 can use conventional 12 VDC 4-wire
smoke detectors. To use them, select fire zone
programming option and do not select 2-wire smoke
detector programming option for the desired fire zone
(refer to the GEM-P816 Programming Instructions).
Set JP3 to the position as shown, if zones 7 or 8 are to
be used.
2-WIRE SMOKE DETECTORS
2-WIRE SMOKE
DETECTOR WIRING
Two-wire smoke detectors can only be connected to zones 7 and 8. To use them,
select fire zone programming option and select 2-wire smoke detector
programming option for the desired fire zone 7 or 8 (refer to the GEM-P816
Programming Instructions) and set JP3 to the “2-WF” position as shown. Connect
the 2-wire smoke detectors as shown.
If Fire Alarm Verification is desired to reset the smoke detectors, select this option
for the desired fire zone (zone 7 or 8).
Connect the Model 368 Cord as follows: 26 (RED = Telco Ring), 27 (GREEN = Telco Tip), 28 (GRAY = Home Ring) and
29 (BROWN = Home Tip). Insert the modular plug into an approved USOCRJ31X jack (or a CA31A jack for Canadian
installations). The Telco Line is used by the control panel to dial the central station and for downloading. This line should
not be connected to party lines or coin operated telephones. If connected to a line with call waiting, then call waiting
interrupt numbers must be programmed into the CS Telephone Numbers (refer to the GEM-P816 Programming
Instructions).
When communicating to central station and during downloading, the control panel seizes the telephone lines from the
house phones, rendering them inoperative during communication. Upon completion of central station communication,
the telephone line is restored to the house phones.
L
NAPCO Security Systems
X
GEM-P816 Installation Instructions
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.