NAPCO GEM-P801 Installation Manual

®
GEM-P801
Control Panel/Communicator
Installation Instructions
WI1089 09/01© NAPCO 2000
WI1089 GEM-P801 Installation Instructions
Table of Contents
General Information .......................................... 2
GEM-P801 Features ......................................... 2
Specifications.................................................... 3
UL Compatible Smoke Detectors...................... 4
Listings and Approvals...................................... 4
Ordering Information ......................................... 4
Optional Accessories ........................................ 4
Programming the Panel .................................... 5
Installation......................................................... 6
Wiring................................................................ 6
Keypad Operation ............................................. 7
Panel Operation ................................................ 8
Bypassing ........................................................ 9
User Program Mode.......................................... 10
GEM-P801 Commands ..................................... 10
Dealer Commands ........................................... 11
Wireless Operation (Signal Strength) ............. 11
Zone Features................................................... 12
System Times ................................................... 13
System Features............................................... 14
Telephone Number 1 Programming.................. 16
Backup Telephone Programming ..................... 17
Pager Programming.......................................... 17
Telephone Number 3 Programming.................. 18
Report Codes.................................................... 19
Enhanced Communicator Features .................. 19
Wireless ............................................................ 19
Downloading ..................................................... 21
Dealer Programming......................................... 22
System Troubles ............................................... 23
Troubleshooting ................................................ 25
GEM-P801 Wiring Diagram .............................. 27
Limited Warranty............................................... 28
General Information
The GEM-P801 is wireless ready. When used with a GEM-RECV-XP8 receiver, the control panel can support up to 8 wireless zones, 4 wireless smoke detectors and 4 Keyfobs.
The GEM-RP8 keypad provides complete control of the GEM-P801 control panel. Information on system status, bypassed zones, system troubles etc. can be viewed at the keypad.
The control panel can be easily and quickly programmed from the keypad. The panel can also be locally or remotely downloaded using PCD-Windows Version 4.1 software and a PCI2000/3000 interface or PCL2000B local Download cable. See Downloading Section (pg. 5) for more information.
NAPCO Security Systems, Inc.
333 Bayview Avenue  Amityville, New York 11701
For Sales and Repairs, call Toll Free: (800) 645-9445
For Technical Assistance, Contact the NAPCO Toll Free Helpline
(800) 645-9440
GEM-P801 Features
Control Panel
8 Zones (6 Hardwired/Wireless + 2 wireless)
2-wire Fire Zone
3 Keypad Panics
Wireless Ready
Bell Supervision
Line Cut Detection
Answering Machine Override (Second Call)
50 Event Log
Communicator
2 Telephone Numbers
Backup Reporting
Pager Format
Point ID Format
Individually Report 8 Users
Opening after Alarm Report (Cancel Code)
Conditional Closing Report
2
Specifications
Current & Voltage Ratings
Alarm Output --------------------------------- Burg: 12 VDC, 2A (max.)
Fire: 12 VDC, 65 mA
Output Current Limiting -------------------- Burg/Fire: 2.25 A
AUX Power: 750 mA
Residential Burglary (4 Hour Standby) Combined Standby Current: -------------- 500 mA Bell Output: ----------------------------------- 2 A (Using Rechargeable 12 VDC 4 AH BATTERY, minimal requirement)
Residential Fire (4 Hour Standby) Combined Standby Current: -------------- 500 mA Bell Output: ----------------------------------- 65 mA (Using Rechargeable 12 VDC 4 AH BATTERY, minimal requirement)
Residential Fire (24 Hour Standby) Combined Standby Current: -------------- 120 mA Bell Output: ----------------------------------- 95 mA (Using Rechargeable 12 VDC 7 AH BATTERY, minimal requirement)
Transformer and Battery
Required Transformer: -------------------- NAPCO TRF12 OR BASLER 16.5 VAC 20VA
Required Battery: --------------------------- 12V 4 AH or 7 AH Rechargeable Change Battery every 5 years or as required
Maximum Charging Current: ------------- 165 mA
Maximum Input Current: ------------------- 2.58 A
Loop Characteristics
Loop Voltage: -------------------------------- 5 Volts
Loop Current :-------------------------------- 1.1mA
Loop Resistance:---------------------------- 300Ω per zone (max.)
Device Specifications
Max # keypads: ------------------------------ 4, GEM-RP8 current = 65 mA
Max # of receivers: -------------------------- 2, GEM-RECV-XP8
current = 65 mA each
Max # of compatible 2-wire smoke detectors : ------------------ 10
Max Keypad wire length : ---------------- 1000’ total wire length
Miscellaneous
Housing Dimensions : -------------------- 11" x 121/8" x 3"
(28 x 30.8 x 7.6) HxWxD
Shipping Weight: --------------------------- GEM-P801 5.5 lbs.
Operating Temperature: ------------------- 0-49ºC (32-120°F)
3
WI1089 GEM-P801 Installation Instructions
UL Compatible Smoke Detectors
GEM-P801 Compatible Smoke Detectors
Mfg 4-Wire
Smoke Detector
Sentrol
System Sensor
NAPCO
449AT 449C 449CRT 449CST 449CSRT 449CSRH
1112 2112
FW-4 FW-2
449CSST 449CLT 449CSLT 449CTE 741U 742U
2112T 2112TSRB
(Approved by UL)
2-Wire
Smoke Detector
712U 722U 732U 711U 721U
2100 2100T
721UT 731U
1100
Smoke Detector
Base
701U 702U 702RE 702RU
Listings and Approvals
UL HOUSEHOLD FIRE AND BURGLARY WARNING SYSTEM CONTROL UNIT STANDARDS # 1023, 985
California State Fire Marshal (CSFM) - Control Unit (Household) # 7187-0992:126
VERIFIED TO COMPLY WITH F.C.C. PART 15 AS CLASS B : DIGITAL DEVICE
European E.M.C. Regulations CE Certification
HARMONIZED STANDARDS: EN50081-1 and EN50082-1 EC DIRECTIVES: 89/336/EEC, Electromagnetic Compatibility Directive
Ordering Information
GEM-P801
GEM-RP8 OI219 WI1090
8 zone Control Panel with 2-wire Fire (6 Hardwire/Wireless+2 wireless) Keypad Operating Instructions GEM-P800 Series Programming Instructions GEM-P801
Optional Accessories
GEM-RECV-XP8: *Wireless Receiver
GEM-TRANS2 Window/Door Transmitter
GEM-KEYF: Keyfob Transmitter
GEM-WP: Wireless Waterproof Panic Button
GEM-SMK: Wireless Smoke Detector
GEM-HEAT:
GEM-PIR: Wireless PIR
GEM-PIRPET: Wireless Pet-Immune PIR
GEM-DT: Wireless Dual-Technology Sensor
GEM-GB:
RB1000 Single Form C Relay Board
Veriphone: Audio Verification Module
PCD-Windows: Downloading Software for IBM Compatible PC
PCI2000/3000: Downloading Interface for IBM Compatible PC
PCL2000B: Local Download cable
*Supports up to 8 zones, 4 Key Fobs, 4 Smoke Detectors
Note: Wireless and Access Features have not been evaluated by UL
Wireless 135°F / Rate of Rise Heat Detector
Wireless Glass-Break Detector
Must be PCD-Windows Version 4.1
(includes PCL2000B Local Download cable)
4
Programming the Panel
Refer to GEM-P801 Programming Instructions (WI1090)
Defaulting the Panel
1. Remove power from the panel.
2. Remove all wiring from terminal 19 (PGM) and terminal 3.
3. Connect terminal 19 (PGM) to terminal 3.
4. Apply power to the GEM-P801 control panel.
5. After a few seconds the ARMED, READY and
SYSTEM TROUBLE LEDs will flash.
H
6. The keypad will beep 3 times indicating the panel default values have been loaded.
7. Remove wiring between terminal 19 (PGM) and terminal 3.
8. Re-install original wiring for terminal 19 (PGM) and terminal 3.
N
:
OTE
Any programming in Dealer Options 1 [96] and Dealer Options 2 [97] will not be defaulted. If Dealer Code Lockout has been programmed the panel will not default
the Dealer Code.
Keypad Programming
Refer to WI1090 for information on keypad programming.
Downloading
The GEM-P801 panel can be download/uploaded with PCD-Windows Version 4.1 software using the Ring Method, Answering Machine Override (Second Call) or
A6
downloading. The panel can also be automatically downloaded/uploaded using the
method of
PCPreset utilty. For Site Initiated Downloaded, see Auto Download ID Number [93].
Local Downloading
Wire as shown in Figure 1. Use the power up or
A6
The power up method is recommended if the panel is attempting to report.
FIGURE
method of establishing a connection.
TELCO
JACK
16 17 18 19 20
GND
+PWR
RED
BLACK
RED
*
*
GREEN
Insulate if not used
*
PCL2000B
MODEM
L
OCAL DOWNLOAD
1
Remote Downloading
Wire as shown in Figure 2. The panel can be remotely download/uploaded using any one of the following methods:
A6
1. The
2. Call-in method
3. Answering Machine Override (Second
method
Call)
4. Site-Initiated (PCPreset &
A6
5. Automatic Downloading (Using PCPreset)
TELCO JACK
RJ31X
GEM-P801 Panel at the site
TELCO
PCI2000
J1
TO COMPUTER
J2
TO EXTERNAL
MODEM
J3
LOCAL
TO
J4
TELCO
J5 LINE OUT TO
MODEM
FIGURE
EMOTE DOWNLOAD
R
2
)
5
WI1089 GEM-P801 Installation Instructions
Installation
Mounting the Panel
Mount the Panel close to an unswitched AC source, a cold-water pipe ground, and a telephone line connection.
Mounting the Keypad
A keypad should be located near an exit/entry door. To remove the keypad from the backplate, insert a small screwdriver into the slots at the bottom of the keypad. Pull up on the screwdriver to pop off the cover.
Up to 4 keypads can be connected on individual wire runs with #22 AWG wire with a maximum total cable length of 1000 feet. Each keypad draws approximately 65 mA.
Keypad Wire Color Control Panel Terminal
RED 12 (+PWR)
BLACK 13 (GND)
GREEN 14 (GREEN)
TABLE
Typical Fire Installation
(Where permitted by local codes) Install smoke detectors outside each sleeping area and on each floor, including the basement. Install the living room and basement smoke detectors near the stairway of the next upper level. For increased protection, additional detectors should be installed in areas other than
K
EYPAD WIRING
1
those required, such as the dining room, bedrooms and utility room. Heat detectors, rather than smoke detectors, are recommended in kitchens, attics, and garages due to conditions that may result in false alarms and improper operation.
Refer to NFPA Standard 74 (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269) for additional information, including proper mounting methods.
FIGURE
Typical Fire Installation
3
Wiring
Grounding the Panel
Connect the control-panel EARTH GROUND screw through a No. 16 AWG or larger wire to a metal cold-water pipe. Do plastic pipe or AC ground connections. Use at least #16 AWG wire. Connect a wire with a ground lug crimped or soldered onto one end and connect it to the EARTH GROUND screw in the cabinet.
AC Power and Battery Wiring
Complete all wiring before connecting the battery or AC Power. Do switched outlet.
not plug the transformer into a
Telephone Wiring
Wire as shown in the wiring diagram in the back of this manual.
WARNING
The FCC restricts the use of this equipment on certain telephone lines. Read the FCC statement on the back of this manual to ensure compliance.
not use a gas pipe,
6
Burglary Zone Wiring
The GEM-P801 provides 6 true hard-wired, End­Of-Line Resistor terminated burglary zones. Wire zones as shown in the wiring diagram (pg. 27). All resistors must be installed, even if the zone is not used. If required, the feature No End Of Line Resistor may be programmed, in which case a direct short across the zone will cause the zone to set up. (NOTE: Not for UL applications) Program the zone as a No EOL Resistor Zone [06].
If necessary, use the voltage chart below to verify proper voltages. These values represent the DC voltage of the zone while in the indicated state with reference to the the zone’s respective ground terminal.
Zone Normal (EOL across zone) 2.5 V
Zone shorted 0 V
Zone Open 5 V
TABLE
OLTAGE AT TERMINALS
V
3
3&5, 6&8, 9&11
Fire Zone Wiring
Wire the Fire Zone as shown in the Wiring Diagram in the back of this manual. An EOL resistor must
be installed, even if the Fire Zone
is not used.
Fire Zone Normal 13.0V
Fire Trouble 13.8V
Fire 0.0 V
TABLE
OLTAGE AT FIRE ZONE
V
4
(Terminals 12&13)
PGM Wiring
The PGM (Terminal 19) is a switched negative output that is activated through programming option(s) that have been selected in programming blocks [08], [23] - [25], [26-2]. Connect the device controlled by the PGM between +PWR and the PGM terminal. (maximum load of 50 mA).
Keypad Operation
Keypad zone LEDs indicate zone status. ARMED, STATUS and
provide system status. The keypad sounder provides feedback beeps for correct and incorrect entries.
H
SYSTEM LEDs
Keypad Sounder
QUICK BEEPS
3
Panel Armed (System ON) Chime ON Fault Find Mode ON Keypad Sounder ON Zone Bypassed
6
QUICK BEEPS
Panel Disarmed (System OFF) Chime OFF Fault Find Mode OFF Keypad Sounder OFF Zone Un-Bypassed
SECOND - STEADY TONE
1
Incorrect Code Entered Invalid key entry
LONG BEEPS (PRIORITY CONDITION
4
1. Entering an Arm Code with a faulted zone (Not an Auto-Bypass Reentry Zone).
2. Entering an Arm Code when the Bell or PGM is ON (Bell and PGM will turn OFF).
3. Arming with the Fire LED ON - reset required. Press the
C
)
key.
7
WI1089 GEM-P801 Installation Instructions
Keypad LEDs
ARMED LED DEFINITION
Armed ON Instant Mode Rapid Flash Zone in Alarm Flashing
STATUS LED DEFINITION
Ready to be Armed ON Zone faulted OFF
H
TROUBLE LED DEFINITION
AC Failure Flashing System Trouble(s) ON
I
FIRE LED DEFINITION
Fire Alarm Flashing Fire Memory/*Fire Trbl ON *See Note 1
AC LED DEFINITION
AC Present ON AC Failure OFF
ZONE LED DEFINITION
Faulted Zone ON Bypassed Zone Slow Flash Zone in Alarm Flashing
N
:
OTE
* If Fire Trouble on Fire LED [96-4] has been enabled, a steady Fire LED will indicate Fire Trouble.
Panel Operation
Arming (System ON)
Before arming the system close all protected zones (unless programmed as Auto-Bypass Reentry Zones). Enter a 4-digit Arm/Disarm code, followed by the
provide a feedback beep for each key pressed. If a valid Arm/Disarm code is entered, the keypad will beep 3 times. If an incorrect Arm/ Disarm code is entered, the keypad will sound a 1-second tone indicating an incorrect entry.
Arming without Entry Delay (Instant Mode)
Enter the The ARMED LED will flash rapidly to indicate
the panel is in Instant Mode. If an Exit/Entry Zone is tripped while the panel is in Instant Mode the panel will go into alarm immediately.
key to eliminate the entry delay.
F
Arming/Disarming with a Keyfob
The system can be armed by pressing the key, and disarmed by pressing the the Keyfob. Zones programmed as Exit/Entry
Follower Zones can be bypassed when the or
N keys on the Keyfob have been
programmed for Interior [81-84]. Zones programmed as Home/Away with Delay Zones can be armed regardless of the state of the Exit/Entry Zones when the
the Keyfob have been programmed for Full Set [81-84]. To arm the system with all zones
key, the keypad will
D
L
key on
or
N
keys on
M
K
M
protected press the
or
M
N key for 1.5s to fully set the system
key. Press and hold the
K
(The LED on the Keyfob indicate the Keyfob has transmitted the signal). Program Keyfob/ Keyswitch Chirp [23-4] for an audible indication of system arming and disarming.
Arming/Disarming with a Keyswitch
The system can be armed/disarmed by using a momentary Keyswitch wired to
Zone 6
. Program
Keyfob/Keyswitch Chirp [23-4] for an audible
indication of system arming and disarming. To convert keyswitch operation from Normally Closed style to Normally Open, program [27-1] Keyswitch Polarity.
N
:
OTE
Faulted Keyswitch or silent 24 hour zone normally do not display at the keypad. If a silent 24 hour zone or Keyswitch is faulted at the time of arming the faulted zone will display only while the priority sound is ON.
Arming Instant with a Keyfob
The panel can be ARMED INSTANT when the [A1] or [A2] keys on the Keyfob have been programmed for Instant [81-84]. To arm the system with Instant protection press the [ON] key, then press and hold the [A1] or [A2] key for
1.5s to arm the panel with INSTANT protection.
Disarming (System OFF)
After entering the premises through an Exit/Entry Zone, the keypad will sound the Entry Delay Tone. Enter a valid Arm/Disarm code, then press
J
. If a valid Arm/Disarm code is entered, the
8
keypad will beep 6 times, indicating the panel has been disarmed. The red Armed LED will go out. If an incorrect Arm/Disarm Code is entered, the keypad will sound a 1-second tone, indicating incorrect entry. Press the
the code.
Disarming after an Alarm
The armed LED and the zone(s) that caused the alarm will be be flashing. Disarm the panel. The system is currently not detecting zone faults or displaying system trouble. The zone(s) that caused the alarm will continue to flash. The STATUS and
indicating:
The system is displaying
Press the
H
SYSTEM TRBL LEDs are out
key to clear Alarm Memory.
C
key and re-enter
C
(Alarm Memory)
Alarm Memory
.
Bypassing
Automatic Bypassing
Note: Automatic Bypassing has not been evaluated by UL
Home/Away with Delay Zones
This zone type has the following operation depending on whether an Exit/Entry Zone has been violated during the Exit Delay time.
Home
Exit/Entry Zone
Zones selected as Home/Away with Delay Zones will be bypassed automatically.
Away with Delay
E xit/Entry Zone is violated
is not
violated
Zones selected as Home/Away with Delay Zones will have a fixed 20-second entry delay when violated before an Exit/Entry Zone.
Full Setting the System with Automatic Bypassing - Home/Away with Delay Zones
From the Keypad
Press
BC
Home/Away with Delay Zones that have been automatically bypassed. Three minutes are allowed to walk through Exit/ Entry and Exit/Entry Follower Zones.
to return protection to
Using A Keyfob (GEM-KF)
All zones in the system can be armed regardless of the state of the Exit/Entry Zone when arming with a Keyfob and using an AUX key programmed as Press [ON] and press and hold the [A1] or [A2] keys for 1.5s when leaving the premises. All zones, including Home/Away Zones are armed.
Full Set
Bypassing a zone
Press the B key, then the zone number to be bypassed. While the panel is DISARMED,
the bypassed zone LED will flash slowly; indicating the zone has been bypassed. While the panel is ARMED, the bypassed zones will only be displayed if the Display Bypassed [21-3] option has been selected.
Unbypassing a zone (Disarmed only)
Press the B key then the number of the zone to be unbypassed.
Group Bypass
Press the E key to Bypass all Exit/Entry Follower Zones [02] or Home/Away Zones
[01] (only if the system is programmed exclusively for
zones).
Home/Away with Delay
Using A Keyfob (GEM-KF)
Hold the [A1] or [A2] key on the Keyfob to Bypass all Exit/Entry Follower Zones [02] or Home/Away Zones [01] (only if the system is programmed exclusively for Home/Away with Delay zones).
User Program Mode
To prevent the loss of the User 1 Code, the panel default program includes User 1 Code Lockout
.
[96-2].
To change the User 1 Code from its default value of
, program the 4-digit User 1 Code through
1234
Dealer Programming [95]. User 1 Arm/Disarm code is also used to program User Codes 2 - 8. By default, the User 1 code cannot be re­programmed by the user.
If it is necessary to change the User 1 code, it can be changed through downloading or Dealer keypad programming. From Dealer Program Mode, change the User 1 Code Lockout ([96-2] LED=OFF) to disabled.
Entering User Program Mode
9
Loading...
+ 19 hidden pages